3_Bldg 631 Utility Site Plan (Revised 19Dec24).pdf
PDF 1 MB Posted
- Attached to
- DSN/CSN Demo Dorm 631 Federal contract opportunity
- Solicitation number
- FA4626-25-R-0001
About this file
This is a site utility plan drawing for Building 631 demolition at Malmstrom Air Force Base in Great Falls, Montana, under contract NZAS 23-0030. The drawing details the utility disconnection and removal requirements for the demolition project.
The plan specifies key tasks including: terminating natural gas service and removing above-ground gas equipment; removing and capping water service lines while repurposing some for new irrigation; removing sanitary sewer services; pulling and storing fiber cable; demolishing HTHW lines to the valve station; coordinating with the 341 CES Electrical Shop for transformer removal; removing storm sewer laterals; removing the chiller and utility trench; and removing headbolt heaters while protecting certain infrastructure like light posts and a transformer. General notes require contractor notification of utility companies, obtaining work clearance permits, asbestos testing prior to demolition, and installation of a new irrigation system with backflow preventer and relocated control panel for the newly seeded area after demolition.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G
G
G
G
G
G
G
G
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
WV
N/A Contract No.:
NZAS 23-0030
Project No.:Designed by:
Drawn by:
Checked by:
N/A Drawing No.:
APR 2024
Date:
1" = 20' Scale:
Sheet No.
Sheet: 1
D. PACE
D. PACE
341ST MISSLE WING
341ST CIVIL ENGINEERING SQUADRON
ENGINEERING TECHNICAL SUPPORT (CEN)
AIR FORCE GLOBAL STRIKE COMMAND
MALMSTROM AIR FORCE BASE
GREAT FALLS, MONTANA
SITE PLAN
BLDG 631 DEMO
M. AMMONS
Sheet Id.
C-100
DNAMMOCEKIRTS
AIRFORCE GLOBAL
G
WI
N
ELI
1 s t M I S S
LEGEND
WATER_S_LINE
WATER_M_LINE
WATER_CONTROL_VALVE
WALLS
STORMWATER_LINES
STORMWATER_INLET
SIDEWALKS
SEWER_S_LINE
SEWER_MANHOLE
SEWER_M_LINE
PAVEMENTS
PAVEMENT_SLAB
HTHW_SUPPLY
HTHW
GAS_S_LINE
GAS_M_LINE
GAS_CONTROL_VALVE
FIRE_HYDRANT
FENCE_LINE
EXTR_LIGHTS
ELECTRICAL_TRANSFORMER
ELECTRICAL_S_UG
ELECTRICAL_S_OVERHEAD
ELECTRICAL_P_UG
ELECTRICAL_P_OVERHEAD
CURB_GUTTER
COMM_UTIL
BLDGS
WV
G
Feet 0 40 80
ADDENDUM #1
NOT FOR CONSTRUCTION
KEY NOTES
1. TERMINATE EXISTING NATURAL GAS SERVICE AS SHOWN ON THE ATTACHED PLAN. REMOVE AND DISPOSE ALL
ABOVE-GROUND GAS EQUIPMENT SUCH AS METERS, REGULATORS AND VALVES. CUT AND CAP 3 FEET FROM
THE MAIN AND INSTALL ISOLATION VALVE. REMOVE PIV FOR FIRE SERVICE LINE.
2. REMOVE PIPING BACK TO MAIN, REMOVE “TEE” AND INSTALL SLEEVE TO RE-CONNECT MAIN. CUT WATER
SERVICE LINES FROM BUILDING AND USE TO PROVIDE NEW IRRIGATION FOR FINISHED SITE.
3. REMOVE EXISTING SANITARY SEWER SERVICE TO BUILDING. CUT AND GROUT THE EXISTING SANITARY SEWER
SERVICES AT LIMITS OF CONSTRUCTION.
4. CONTRACTOR WILL PULL FIBER CABLE OFF SITE AND PLACE IN HAND HOLD FOR FUTURE USE. REMOVE ALL
COMM EQUIPMENT LEFT IN THE BUILDING.
5. DEMO AND REMOVE HTHW LINE FROM BUILDING TO VALVE STATION NEXT TO GODDARD. PROTECT HTHW
ENCLOSURES ALONG GODDARD.
6. COORDINATE WITH ELECTRIC SHOP PRIOR TO WORKING ON ELECTRIC LINES FOR BLDG 631. 341 CES
ELECTRICAL SHOP WILL DISCONNECT ELBOWS FROM JUNCTION CAN. CONTRACTOR WILL REMOVE
TRANSFORMER AND PULL OUT CABLES. DELIVER TRANSFORMER TO 341 CES ELECTRIC SHOP STORAGE YARD.
7. CUT, CAP AND REMOVE ANY STORM SEWER LATERALS FROM DOWNSPOUTS TO THE MAIN. PROTECT STORM
SEWER MAIN LINES.
8. REMOVE CHILLER AND SUPPLY/RETURN LINES AND CONCRETE UTILITY TRENCH. DEMO CMU WALLS AND
CONCRETE PAD.
9. PROTECT TRANSFORMER, DO NOT REMOVE.
10. REMOVE ALL HEADBOLT HEATERS, CIRCUITS AND PEDESTALS. REPAIR ASPHALT AND SIDEWALKS.
GENERAL NOTES
a. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER AND WATER SHOP IN THE EVENT
OF A WATER LINE BREAK OR EMERGENCY.
b. CONTRACTOR SHALL NOTIFY ALL UTILITY COMPANIES, OBTAIN BASE CIVIL ENGINEERING WORK CLEARANCE
REQUEST (AF FORM 103) FOR EXCAVATION AND DETERMINE THE EXACT LOCATION OF ALL UNDERGROUND
UTILITIES BEFORE COMMENCING WORK.
c. PERFORM ASBESTOS TESTING PRIOR TO DEMOLITION.
d. PROTECT ALL LIGHT POSTS AROUND PERIMETER OF BUILDING.
e. CAPTURE EXISTING WATER SUPPLY LINE FOR BUILDING AND USE FOR NEW IRRIGATION SUPPLY. ABANDON
EXISTING IRRIGATION SYSTEM AND INSTALL NEW IRRIGATION SYSTEM TO COVER NEWLY SEEDED AREA.
INSTALL NEW BACKFLOW PREVENTOR WITH CAGE FOR IRRIGATION SYSTEM. RELOCATE CONTROL PANEL FROM MECH ROOM AND MOUNT ON PEDESTAL NEAR 75 KVA TRANSFORMER AT THE NE SIDE OF THE SITE.
PROVIDE POWER FROM TRANSFORMER TO CONTROLLER THROUGH NEW DISCONNECT.
f. TERMINATE CONCRETE TUNNEL WITHIN FOOTPRINT OF BUILDING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text