20R0003 Atch 17 WAFB IFS Appendix.pdf

PDF 6 MB Posted

Attached to
Whiteman AFB Multiple Award Task Order Contract (MATOC) - FA462520R0003 Federal contract opportunity
Solicitation number
FA462520R0003
Issued by
Department of the Air Force Global Strike Command

About this file

This document outlines a federal contract opportunity for construction services on Whiteman Air Force Base. The North American Industry Classification System code for this acquisition is 236220 for commercial and institutional building construction. Work consists of providing labor, materials, equipment and other resources to execute multiple construction projects on the base involving design, repair, renovation, alteration or new construction of real property. This will be a multiple award task order contract with a target of three small business awardees competing for firm fixed price task orders. The base contract period is five years with two optional two-year extensions for a total of nine years. The estimated contract value is between $100-$250 million.

View the file

Other files for this federal contract opportunity

Other files attached to Whiteman AFB Multiple Award Task Order Contract (MATOC) - FA462520R0003, newest first.
File Type Posted
Solicitation Amendment FA462520R00030012 SF 30.pdf PDF
20R0003 Atch 19 ISV Attendees.pdf PDF
20R0003 Atch L-4 Construction Cost Breakdown - Amended.xls XLS spreadsheet
20R0003 Atch 20 Q and A 200622.pdf PDF
Solicitation Amendment FA462520R00030011 SF 30.pdf PDF
20R0003 Atch 18 Q and A 200609.pdf PDF
Solicitation Amendment FA462520R00030010 SF 30.pdf PDF
20R0003 Atch 1 SOW 20May20.docx.pdf PDF
Solicitation Amendment FA462520R00030009 SF 30.pdf PDF
20R0003 Atch 15 Q and A 200520.pdf PDF
Attachment 13 509 MDG Public Health Travel Risk Assessment Form.pdf PDF
Attachment 14 509 SF Fast Pass Request.pdf PDF
Solicitation Amendment FA462520R00030008 SF 30.pdf PDF
20R0003 Atch 12 Q and A 200512.pdf PDF
20R0003 Atch 1 SOW 11May20.pdf PDF
Solicitation Amendment FA462520R00030007 SF 30.pdf PDF
Solicitation Amendment FA462520R00030006 SF 30.pdf PDF
Q and A 200507 Atch 1 - Bldg 3008 AHU Schedule.PNG PNG image
Q and A 200507 Atch 2 - Restroom Floor.jpeg JPEG file
20R0003 Atch L-3 Consent Letter.pdf PDF
20R0003 Atch L-2 Transmittal Letter.pdf PDF
20R0003 Atch L-1 Past Performance Questionaire.pdf PDF
20R0003 Atch 10 Q and A 200507.pdf PDF
Q and A 200507 Atch 3 - Storage Room Floor.jpeg JPEG file
20R0003 Atch 8 Q and A 200506.pdf PDF
20R0003 Atch L-4 Construction Cost Breakdown.xls XLS spreadsheet
Solicitation Amendment FA462520R00030005 SF 30.pdf PDF
Solicitation Amendment FA462520R00030004 SF 30.pdf PDF
20R0003 Atch 8 Q and A 200430.pdf PDF
20R0003 Atch 5 Q and A 200420 REVISED.pdf PDF
20R0003 Atch L-4 Construction Cost Breakdown.xls XLS spreadsheet
Solicitation Amendment FA462520R00030003 SF 30.pdf PDF
Solicitation Amendment FA462520R00030002 SF 30.pdf PDF
20R0003 Q and A 200420.pdf PDF
Solicitation Amendment FA462520R00030001 SF 30.pdf PDF
20R0003 Atch 2 Rep Project SOO 02Jan20.pdf PDF
20R0003 Atch 1 SOW 02April20.pdf PDF
20R0003 Atch L-2 Transmittal Letter.pdf PDF
20R0003 Atch L-1 Past Performance Questionaire.pdf PDF
20R0003 Atch L-3 Consent Letter.pdf PDF
20R0003 Atch 3 Whiteman AFB Climatology Data.pdf PDF
Solicitation - FA462520R0003.pdf PDF
20R0003 Atch L-4 Construction Cost Breakdown.xls XLS spreadsheet
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

Whiteman Air Force Base

Software Standards Document

Last Update: September 27th, 2019

Metasys Standards for Whiteman AFB, MO

TABLE OF CONTENTS

Table of Contents

Revision History

Notes

Network Address Scheme

Site and ADX Server

Engine Name

Field Bus Name

Controller Name

Object Naming

Alarm Management:

Trending

Totalization

Scheduling and Calendars

Optimum Start Stop

Programming

User Views

Tailored Summaries

Graphics

Object Lists

Heavy Equipment Delay

Passwords

Other Topics

Customer Sign Off

Appendix A – Graphics Standard Examples

Appendix B -- Object Naming List/Examples

Appendix C – WAFB Mo Metasys Alarm Priority Standard

REVISION HISTORY

Date By Revisions

1/17/17 Dylan Wilson JCFS Site Supervisor

Network Address Scheme, Site and ADX Server Name,Building Names (Removed), Engine Names, Field Bus Names & Field Controller Names

2/9/17 Dylan Wilson JCFS Site Supervisor

Alarm Management

4/09/19 Thomas Wilkes JCFS Project Manager

Appendix A – Graphics Standard Examples Appendix B – Object Naming List Appendix C – WAFB Mo Metasys Alarm Priority Standard

9/27/19 Thomas Wilkes JCFS Project Manager

Appendix D – HVAC BAS Control Drawing Standards Content Examples

NOTES

NETWORK ADDRESS SCHEME

• The following IP Address scheme will be used

Starting Address

Ending Address Use Comments

137.1.248.21 ADX25L-001 (Server)

137.1.248.21 ADS Repository

10.40.X.XX Network Supervisory Devices for

CEVLAN

SITE AND ADX SERVER NAMES

• Metasys hierarchy o Name – max 400 characters (practical limit 32 chars), o Description – max 40 characters o Look towards the future and think about growth and what the structure should look.

o Stay consistent with all projects large or small, base all jobs as if they are large and structure your object naming appropriately.

o The naming chosen below will affect the Fully Qualified Reference for all objects.

Keep the names concise but meaningful and use the descriptions for more details.

• Archive Name “WAFB1” o The archive name contains a numeric character to permit backup copies and to provide flexability to create future sites.

• Site Name “WhitemanAFB” Site Description “Whiteman Air Force Base” o Should be between 8 and 15 characters

• ADX name “ADX25L-001” ADX Description “ADX server 25 Licence”

Site Name

Site Director Name

Engine Name

Field Bus Name

Controller Name

ENGINE NAMES

• Engine name = Building Number

• Number incrementally for additional NAE’s per building.

• Description to include Building number and location

Bldg. NAE NAE Name

NAE Description Location

1 1 1-1 Example: Bldg.1 NAE-1 S. Mech. Rm.

1 2 1-2 Example: Bldg.1 NAE-2 2nd Flr. Electrical Rm.

1 3 1-3

FIELD BUS NAMES

• N2-x for N2 Trunk

• FC-x for MS/TP Field Bus

• Description includes NAE name

“N2-1” “xxx N2 Trunk 1”

“FC-1” “xxx MSTP Field Bus 1”

“FC-2” “xxx MSTP Field Bus 2”

NAE Trunk Name Trunk Description FC-1 MSTP Trunk 1 FC-2 MSTP Trunk 2

N2-1 N2 Trunk 1 N2-2 N2 Trunk 2

LON-1 LON Trunk 1

BAC-IP1 BacNet IP Trunk 1

N1 Migration 1 N1 Migration

VND Integration

VND Integration

Wireless

Supervisor 1 Wireless Supervisor

XL5K Integration

XL5K Integration

FIELD CONTROLLER NAMES

• Controller Name = System Type-Short Name

• Description = Building Name or Number, System Name and Number

• Software file name for controller application matches controller name

• Subdirectory structure on ADX for files matches structure of All Items Tree

Controller Name

Trunk Description

AHU-## Bldg.#### Air Handler ## Controller RTU-## Bldg.#### Rooftop Unit ## Controller HP-## Bldg.#### Heat Pump ## Controller

MAU-## Bldg.#### Make Up Air Unit ## Controller HVU-## Bldg.#### Heating & Ventilation Unit ## Controller FCU-## Bldg.#### Fan Coil Unit ## Controller FUR-## Bldg.#### Furnace Packaged Unit ## Controller EF-SYS# Bldg.#### Exhaust Fan System ## Controller UH-SYS# Bldg.#### Unit Heater System ## Controller

VAV##-## Bldg.#### Ducted System ## Variable Air Volume Box ## Room ##

CHWS# Bldg.#### Chilled Water System # Controller HWS# Bldg.#### Hot Water System # Controller AC-## Bldg.#### Air Conditioner ## Controller FT-## Bldg.#### Fin Tube ## Controller UH-## Bldg.#### Unit Heater ## Controller EF-## Bldg.#### Exhaust Fan #### Controller

MECH-RM# Bldg.#### Mechanical Room # Controller ELECT-RM# Bldg.#### Electrical Room # Controller

DTWS-# Bldg.#### Duel Temperature Water System Controller FPTB##-## Bldg.#### Ducted System ## Fan Powered Terminal Box ## Room ##

CAV##-## Bldg.#### Ducted System ## Constant Air Volume Box ## Room ##

METER Bldg.#### Metering Controller

OBJECT NAMES

• When mapping objects from controllers, the intent is to map only what is needed to operate the mechanical system and what is needed for primary troubleshooting. All additional objects in the controller can be accessed through the Engineering View of the Field Bus (MSTP).

• General rule of thumb is to follow these standards:

• 15 objects max per Terminal Equipment (VAV, Heat Pump, Fan Coil)

• 30 objects max per AHU

• 50 objects max per complex system

• Object Name will be generated by default naming conventions within controller type software.

• 3rd party devices that are applied to the Metasys system will be integrated as is through the discovery tool. Should the integrated templates not be available through the discovery tool or not discover with specified description the points will be named from the 3rd party Bacnet mapping templates associated with company standardization forms.

• Object Names – all field points to be based on standard CCT naming convention and descriptions

• All object names need to maintain consistency relative to similar objects types e.g. PRE-FILT vs P-FLT vs PREFILTER = PREFILTER-S

• All NAE object (AV, BV, LCT, Interlock, MCO, etc) names will Object Name and description conventions with consistency.

e.g. Metering LCT naming for electrical in building XX will match building X

• Descriptions will identify system association. Zones temperature description shall reference location.

• Object Names will not be modified from the Item Reference Name used during database generation.

• Any changes should be done by deleting the object and reading it with the correct name.

ALARM MANAGEMENT:

• Input/Output mismatch Alarm extensions will reside on Input Point.

• All equipment that is utilized as failure backup or maintenance backup equipment will generate an alarm in Metasys with the reference delay timing per sequence of operations.

All other Input/Output mismatch alarm type will be set for 180 seconds.

• Analog alarms High and Low Alarm thresh holds will follow sequence of operations.

• Generate alarm extensions for the following points.

Alarm Type Examples

Command/Status Mismatch Fan Command/Fan Status, Pump Command/Pump Status, Unit Heater Command/Unit Heater Status

Control Process Variables Zone Temperature, Hot Water Supply Temperature

Device Alarms Low Temperature Alarm, Duct Air High Pressure Alarm

Software Reset Points Low Temperature Alarm Status Reset, Isolation Valve Alarm Reset

• Alarm Message Text will be added for all critical alarms to identify system and location of object. Refer to appendix C WAFB Mo Metasys Alarm Priority Standard for additional.

• Naming Convention will use standards as described previously and Alarm Message Text to provide identification of equipment location for Alarms. The “Building Name.System Name.Object Name” convention is required to avoid the issue shown by the yellow arrow.

“Bldg. 4055 AHU-1 Low Temperature Alarm”

“Bldg. 4055 HX-1 Hot Water Supply High Alarm”

• The graphic reference needs to be filled in so that an easy link to the graphic can be used when an alarm occurs.

• This will also help in usability of the Event Viewer

Priority Settings:

• Life Safety Objects will be set to a Priority 14.

• High Priority Objects will be set to a Priority 50.

• Medium Priority Objects will be set to a Priority 60.

• Low Priority Objects will be set to a Priority 70.

Alarm pop up will be setup for Priority 14 and Priority 50 only. Offline Supervisory Controllers do not need to generate a pop up.

• Auto Shutdown objects need to be created for all systems where false alarms are not desired.

Startup Delay = 15 minutes for AHU Startup Delay = 30 minutes for CHW and HW systems

TRENDING

• All Critical Systems - 10 min sample time, ADX repository = Enabled, Trend Buffer = 144

• All Mechanical Systems - 10 min sample time, ADX repository = Enabled, Trend Buffer =

144. Includes all primary temperatures, pressures, flows, set points, valves and fan outputs

• All Zone Temperatures and Set Points - 30 min sample time, ADX repository = Disabled, Trend Buffer = 144

• Trending will be setup based on COV or Interval, whichever will minimize the data collected.

If COV is used, the COV increment for the object needs to be set to a value that will not generate an excessive number of samples.

• Trend Studies will be generated for all critical systems as defined by WAFB HVAC personnel.

TOTALIZATION

• Run time Totalization will be setup on all fans and pumps with no periods defined (manual reset of value will be needed)

• Analog (consumption) Totalization will be setup for all meters that monitor consumption

• Event Totalization will be setup for large primary equipment (e.g. Chillers)

SCHEDULING AND CALENDARS

• Schedules and Calendars will setup during database generation per WAFB HVAC personnel and /or project manager guidance. Schedules are based on facility requirments.

• Only those schedules needed during commissioning will be setup by Johnson Controls.

OPTIMUM START STOP

• Optimum Start Stop will not be setup during database generation and will be setup by WAFB HVAC personnel after training is completed.

• Only those Optimum Start Stop objects needed during commissioning will be setup by Johnson Controls.

PROGRAMMING

• All programming and related objects to be kept in NAE folders below the Programming Folder based on Building + System Name

• Programming using Feature objects (Interlock, Global Data, Multiple Command, Signal

Select, Solar Clock, etc.) shall be maximized when possible in lieu of LCT programming.

USER VIEWS

• User Views will be created based on review with Customer

• In the absence of customer input, User Views will be created based on Building + Systems

• User Views will be created for each piece of terminal equipment and Tailored Summaries will be created.

• Any special User Views that need to be created must be identified in advance of database generation.

TAILORED SUMMARIES

Tailored Summaries will be created for all repetitive terminal control systems (Fan Coils, Heat Pumps, AC Units, etc.) in addition to individual User Views for each piece of equipment

• The following Tailored Summaries will be created

• Engines, Field Controllers, Field Bus

• VAV boxes, Fan Coils, AHUs,?

• The following System Definition objects will be installed on the Metasys server (found on Branch Purchase Package DVD).

GRAPHICS

The following graphics will be created

• One per major mechanical system (each AHU, HW, CHW, ??)

• Floor plans with interactive status colors will be generated for each build. The customer will be able to navigate to the equipment that serves the space by clicking on the floor plan area served.

• Any additional graphics will be defined in advance of database generation

• The Graphics Plus environment will be used for creating all project graphics

• The base graphics template will be defined before any graphics are created

• Graphics to be created will be reviewed after partial (25%) completion for customer approval and sign off

• The following default color scheme will be used for object values shown on the graphics

• The following template will be used for all graphics (Refer to Appendix A)

• The time and date will be added to each graphic header as shown at the locations in the table. The binding is against the ADX object with a "Local Date" and "Local Time" attributes

Canvas Size Date Location (x,y) Time Location (x,y)

800 x 1200 765, 15 765, 28

950 x 1550 1200, 21 1200, 34

800 x 1100 755,15 755, 28

• The following navigation scheme will be used for the graphics. The final navigation scheme needs to be defined more fully with WAFB HVAC personnel before any graphics are built.

Campus Dashboard

Building Dashboard with Links to

Key Central Plant Graphics

Stacked Floor Plan Thermo-graphics

Single Thermo-graphic Floorplan with Room Control

Module

Tailored Summary of Zone Controllers and Key Data for Central Systems

Zone Mechanical System Graphics (e.g. VAV Boxes, Fan Coils)

Central System Mechanical Graphics (e.g. AHUs serving

VAV Boxes)

OBJECT LISTS

• Object Lists will not be setup during database generation and will be setup by WAFB HVAC personnel after training is completed.

• Only those Object Lists needed during commissioning will be setup by Johnson Controls.

HEAVY EQUIPMENT DELAYS

• Each NAE has 5 internal Heavy Equipment Delay controllers and provides startup delays for large electrical loads within the NAE

• BO and MSO objects may be configured to use one of the five HED objects the configuration on the delay (Heavy Equip Delay) is the number of seconds added to the HED counter after this object starts. This delays the start of the next object in the HED list.

• Use one HED Controller and define a 30 second delay for all large motors without VFDs per

NAE

PASSWORDS

• Category and Object relationships must be established before database is created o All NxE, Field Buses and Field Controllers will use category = “System” o All other objects will use category as determined by customer o If no input from customer is received, all point objects will use the “HVAC” category

• Categories are used to separate users and objects and alarms received

• Custom categories can be used to create unique object grouping and reporting requirements

• Set passwords to required User Views to separate access to objects by Role or Location

• Define Roles as needed for various user type access and authority requirements

OTHER TOPICS

CUSTOMER SIGN OFF

At the completion of each project a Performance Verifiation Test (PVT) will be conducted by but not limited to WAFB HVAC personnel, COE representive, contractor representive (JCFS). Upon completion of the PVT a report will be submitted for record. The following signature blocks are provided for reference as a minimum requirement and may be modified as the project requires.

<Customer Name>

<Customer Title>

<Customer Company>

<Your Name>

<Your Title>

Johnson Controls Federal Systems

APPENDIX A

GRAPHIC STANDARD EXAMPLES

FLOOR PLAN & DASHBOARD

APPENDIX A 05/09/2019

NETWORK RISER

AIR SIDE SYSTEMS

WATER SIDE SYSTEMS

UNITARY SYSTEMS

Item No. Application Name Derived Name Description 1 2 Pipe Bypass Loop HCBYPVLV-% Htg.Clg Bypass Loop Valve Eff Cmd 2 2 Pipe Bypass Loop HCBYPVLV-O Htg.Clg Bypass Valve Output 3 2 Pipe Circulation Pump 1 HCP1-C Heating/Cooling Pump 1 Command 4 2 Pipe Circulation Pump 2 HCP2-C Heating/Cooling Pump 2 Command 5 2 Pipe Damper HCFBD-% Heating/Cooling Face & Bypass Eff Cmd 6 2 Pipe Damper HCFBD-POS Heating/Cooling Face & Bypass Position 7 2 Pipe Damper HCFBD-S Heating/Cooling Face & Bypass Status 8 2 Pipe Damper CL HCFBD-CL Htg/Clg Face & Bypass Closed Status 9 2 Pipe Damper OP HCFBD-OP Htg/Clg Face & Bypass Open Status

10 2 Pipe Loop DP HCLOOP-DP Heating Cooling Loop Diff Pressure 11 2 Pipe Pump 1 Lockout HCP1-LO Heating/Cooling Pump 1 Lockout Status 12 2 Pipe Pump 1 Status HCP1-S Heating/Cooling Pump 1 Status 13 2 Pipe Pump 2 Lockout HCP2-LO Heating/Cooling Pump 2 Lockout Status 14 2 Pipe Pump 2 Status HCP2-S Heating/Cooling Pump 2 Status 15 2 Pipe Valve HC-% Heating/Cooling Effective Command 16 2 Pipe Valve HC-EC Heating/Cooling Effective Command 17 2 Pipe Valve HCV-POS Heating/Cooling Valve Position 18 2 Pipe Valve HCV-S Heating/Cooling Valve Status 19 2 Pipe Valve CL HCV-CL Heating/Cooling Valve Closed Status 20 2 Pipe Valve OP HCV-OP Heating/Cooling Valve Open Status 21 24 VAC Supply 24VAC-VOLTS 24 VAC Supply Voltage 22 APS or Humidistat APSORHUM-S APS or Humidistat Status 23 Blr1 BLR1-% Boiler 1 Effective Command 24 Blr1 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 25 Blr1 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 26 Blr1 LO BLR1-LO Boiler 1 Lockout Switch 27 Blr1 OL BLR1-OL Boiler 1 Overload 28 Blr2 BLR2-% Boiler 2 Effective Command 29 Blr2 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 30 Blr2 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 31 Blr2 LO BLR2-LO Boiler 2 Lockout Switch 32 Blr2 OL BLR2-OL Boiler 2 Overload 33 Blr3 BLR3-% Boiler 3 Effective Command 34 Blr3 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 35 Blr3 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 36 Blr3 LO BLR3-LO Boiler 3 Lockout Switch 37 Blr3 OL BLR3-OL Boiler 3 Overload 38 Blr4 BLR4-% Boiler 4 Effective Command 39 Blr4 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 40 Blr4 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 41 Blr4 LO BLR4-LO Boiler 4 Lockout Switch 42 Blr4 OL BLR4-OL Boiler 4 Overload 43 Blr5 BLR5-% Boiler 5 Effective Command 44 Blr5 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 45 Blr5 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 46 Blr5 LO BLR5-LO Boiler 5 Lockout Switch 47 Blr5 OL BLR5-OL Boiler 5 Overload 48 Blr6 BLR6-% Boiler 6 Effective Command 49 Blr6 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 50 Blr6 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 51 Blr6 LO BLR6-LO Boiler 6 Lockout Switch 52 Blr6 OL BLR6-OL Boiler 6 Overload 53 Blr7 BLR7-% Boiler 7 Effective Command 54 Blr7 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 55 Blr7 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 56 Blr7 LO BLR7-LO Boiler 7 Lockout Switch 57 Blr7 OL BLR7-OL Boiler 7 Overload 58 Blr8 BLR8-% Boiler 8 Effective Command 59 Blr8 Iso Valve CL HCV-CL Heating/Cooling Valve Closed Status 60 Blr8 Iso Valve OP HCV-OP Heating/Cooling Valve Open Status 61 Blr8 LO BLR8-LO Boiler 8 Lockout Switch 62 Blr8 OL BLR8-OL Boiler 8 Overload 63 Boiler Mixing Valve MIX-% Mixing Valve Effective Command 64 Boiler Pressure STM-P Steam Pressure 65 Boiler1 BLR1-C Boiler 1 Command 66 Boiler1 BLR1-O Boiler 1 Output 67 Boiler1 Circ Pmp BP1-BYPASS Boiler Pump 1 Bypass Drive 68 Boiler1 Circ Pmp BP1-C Boiler Pump 1 Command 69 Boiler1 Circ Pmp BP1-HOA Boiler Pump 1 Control Mode

APPENDIX B

70 Boiler1 Circ Pmp BP1-% Boiler Pump 1 Eff Command 71 Boiler1 Circ Pmp BP1-FAULT Boiler Pump 1 Fault Code 72 Boiler1 Circ Pmp BP1-HZ Boiler Pump 1 Output Frequency 73 Boiler1 Circ Pmp BP1-KWH Boiler Pump 1 Kilowatt Hours 74 Boiler1 Circ Pmp BP1-RPM Boiler Pump 1 Motor Speed 75 Boiler1 Circ Pmp BP1-O Boiler Pump 1 Output 76 Boiler1 Circ Pmp BP1-DP Boiler Pump 1 Diff Pressure 77 Boiler1 Circ Pmp BP1-RESET Boiler Pump 1 Reset Drive Fault 78 Boiler1 Circ Pmp BP1-% Boiler Pump 1 Speed Feedback 79 Boiler1 Circ Pmp BP1-S Boiler Pump 1 Status 80 Boiler1 Circ Pmp BP1-DO% Boiler Pump 1 Drive Output Percent 81 Boiler1 Circ Pmp OL BP1-OL Boiler Pump 1 Overload 82 Boiler1 Ena BLR1-EN Boiler 1 Enable 83 Boiler1 Entering BLR1EW-T Boiler 1 Entering Water Temperature 84 Boiler1 Flow BLR1-FS Boiler 1 Flow Switch 85 Boiler1 GAlarm BLR1-A Boiler 1 Alarm 86 Boiler1 HTemp BLR1HT-A Boiler 1 High Temperature Alarm 87 Boiler1 Iso Status BLR1ISOV-S Boiler 1 Isolation Valve Status 88 Boiler1 Iso Valve BLR1ISOV-C Boiler 1 Isolation Valve Command 89 Boiler1 Leaving BLR1LW-T Boiler 1 Leaving Water Temperature 90 Boiler1 MS BLR1-MS Boiler 1 Maintenance Switch 91 Boiler1 SP BLR1SP-O Boiler 1 Setpoint Output 92 Boiler1 Status BLR1-S Boiler 1 Status 93 Boiler2 BLR2-C Boiler 2 Command 94 Boiler2 BLR2-O Boiler 2 Output 95 Boiler2 Circ Pmp BP2-BYPASS Boiler Pump 2 Bypass Drive 96 Boiler2 Circ Pmp BP2-C Boiler Pump 2 Command 97 Boiler2 Circ Pmp BP2-HOA Boiler Pump 2 Control Mode 98 Boiler2 Circ Pmp BP2-% Boiler Pump 2 Eff Command 99 Boiler2 Circ Pmp BP2-FAULT Boiler Pump 2 Fault Code

100 Boiler2 Circ Pmp BP2-HZ Boiler Pump 2 Output Frequency 101 Boiler2 Circ Pmp BP2-KWH Boiler Pump 2 Kilowatt Hours 102 Boiler2 Circ Pmp BP2-RPM Boiler Pump 2 Motor Speed 103 Boiler2 Circ Pmp BP2-O Boiler Pump 2 Output 104 Boiler2 Circ Pmp BP2-DP Boiler Pump 2 Diff Pressure 105 Boiler2 Circ Pmp BP2-RESET Boiler Pump 2 Reset Drive Fault 106 Boiler2 Circ Pmp BP2-% Boiler Pump 2 Speed Feedback 107 Boiler2 Circ Pmp BP2-S Boiler Pump 2 Status 108 Boiler2 Circ Pmp BP2-DO% Boiler Pump 2 Drive Output Percent 109 Boiler2 Circ Pmp OL BP2-OL Boiler Pump 2 Overload 110 Boiler2 Ena BLR2-EN Boiler 2 Enable 111 Boiler2 Entering BLR2EW-T Boiler 2 Entering Water Temperature 112 Boiler2 Flow BLR2-FS Boiler 2 Flow Switch 113 Boiler2 GAlarm BLR2-A Boiler 2 Alarm 114 Boiler2 HTemp BLR2HT-A Boiler 2 High Temperature Alarm 115 Boiler2 Iso Status BLR2ISOV-S Boiler 2 Isolation Valve Status 116 Boiler2 Iso Valve BLR2ISOV-C Boiler 2 Isolation Valve Command 117 Boiler2 Leaving BLR2LW-T Boiler 2 Leaving Water Temperature 118 Boiler2 MS BLR2-MS Boiler 2 Maintenance Switch 119 Boiler2 SP BLR2SP-O Boiler 2 Setpoint Output 120 Boiler2 Status BLR2-S Boiler 2 Status 121 Boiler3 BLR3-C Boiler 3 Command 122 Boiler3 BLR3-O Boiler 3 Output 123 Boiler3 Circ Pmp BP3-BYPASS Boiler Pump 3 Bypass Drive 124 Boiler3 Circ Pmp BP3-C Boiler Pump 3 Command 125 Boiler3 Circ Pmp BP3-HOA Boiler Pump 3 Control Mode 126 Boiler3 Circ Pmp BP3-% Boiler Pump 3 Eff Command 127 Boiler3 Circ Pmp BP3-FAULT Boiler Pump 3 Fault Code 128 Boiler3 Circ Pmp BP3-HZ Boiler Pump 3 Output Frequency 129 Boiler3 Circ Pmp BP3-KWH Boiler Pump 3 Kilowatt Hours 130 Boiler3 Circ Pmp BP3-RPM Boiler Pump 3 Motor Speed 131 Boiler3 Circ Pmp BP3-O Boiler Pump 3 Output 132 Boiler3 Circ Pmp BP3-DP Boiler Pump 3 Diff Pressure 133 Boiler3 Circ Pmp BP3-RESET Boiler Pump 3 Reset Drive Fault 134 Boiler3 Circ Pmp BP3-% Boiler Pump 3 Speed Feedback 135 Boiler3 Circ Pmp BP3-S Boiler Pump 3 Status 136 Boiler3 Circ Pmp BP3-DO% Boiler Pump 3 Drive Output Percent 137 Boiler3 Circ Pmp OL BP3-OL Boiler Pump 3 Overload 138 Boiler3 Ena BLR3-EN Boiler 3 Enable

139 Boiler3 Entering BLR3EW-T Boiler 3 Entering Water Temperature 140 Boiler3 Flow BLR3-FS Boiler 3 Flow Switch 141 Boiler3 GAlarm BLR3-A Boiler 3 Alarm 142 Boiler3 HTemp BLR3HT-A Boiler 3 High Temperature Alarm 143 Boiler3 Iso Status BLR3ISOV-S Boiler 3 Isolation Valve Status 144 Boiler3 Iso Valve BLR3ISOV-C Boiler 3 Isolation Valve Command 145 Boiler3 Leaving BLR3LW-T Boiler 3 Leaving Water Temperature 146 Boiler3 MS BLR3-MS Boiler 3 Maintenance Switch 147 Boiler3 SP BLR3SP-O Boiler 3 Setpoint Output 148 Boiler3 Status BLR3-S Boiler 3 Status 149 Boiler4 BLR4-C Boiler 4 Command 150 Boiler4 BLR4-O Boiler 4 Output 151 Boiler4 Circ Pmp BP4-BYPASS Boiler Pump 4 Bypass Drive 152 Boiler4 Circ Pmp BP4-C Boiler Pump 4 Command 153 Boiler4 Circ Pmp BP4-HOA Boiler Pump 4 Control Mode 154 Boiler4 Circ Pmp BP4-% Boiler Pump 4 Eff Command 155 Boiler4 Circ Pmp BP4-FAULT Boiler Pump 4 Fault Code 156 Boiler4 Circ Pmp BP4-HZ Boiler Pump 4 Output Frequency 157 Boiler4 Circ Pmp BP4-KWH Boiler Pump 4 Kilowatt Hours 158 Boiler4 Circ Pmp BP4-RPM Boiler Pump 4 Motor Speed 159 Boiler4 Circ Pmp BP4-O Boiler Pump 4 Output 160 Boiler4 Circ Pmp BP4-DP Boiler Pump 4 Diff Pressure 161 Boiler4 Circ Pmp BP4-RESET Boiler Pump 4 Reset Drive Fault 162 Boiler4 Circ Pmp BP4-% Boiler Pump 4 Speed Feedback 163 Boiler4 Circ Pmp BP4-S Boiler Pump 4 Status 164 Boiler4 Circ Pmp BP4-DO% Boiler Pump 4 Drive Output Percent 165 Boiler4 Circ Pmp OL BP4-OL Boiler Pump 4 Overload 166 Boiler4 Ena BLR4-EN Boiler 4 Enable 167 Boiler4 Entering BLR4EW-T Boiler 4 Entering Water Temperature 168 Boiler4 Flow BLR4-FS Boiler 4 Flow Switch 169 Boiler4 GAlarm BLR4-A Boiler 4 Alarm 170 Boiler4 HTemp BLR4HT-A Boiler 4 High Temperature Alarm 171 Boiler4 Iso Status BLR4ISOV-S Boiler 4 Isolation Valve Status 172 Boiler4 Iso Valve BLR4ISOV-C Boiler 4 Isolation Valve Command 173 Boiler4 Leaving BLR4LW-T Boiler 4 Leaving Water Temperature 174 Boiler4 MS BLR4-MS Boiler 4 Maintenance Switch 175 Boiler4 SP BLR4SP-O Boiler 4 Setpoint Output 176 Boiler4 Status BLR4-S Boiler 4 Status 177 Boiler5 BLR5-C Boiler 5 Command 178 Boiler5 BLR5-O Boiler 5 Output 179 Boiler5 Circ Pmp BP5-BYPASS Boiler Pump 5 Bypass Drive 180 Boiler5 Circ Pmp BP5-C Boiler Pump 5 Command 181 Boiler5 Circ Pmp BP5-HOA Boiler Pump 5 Control Mode 182 Boiler5 Circ Pmp BP5-% Boiler Pump 5 Eff Command 183 Boiler5 Circ Pmp BP5-FAULT Boiler Pump 5 Fault Code 184 Boiler5 Circ Pmp BP5-HZ Boiler Pump 5 Output Frequency 185 Boiler5 Circ Pmp BP5-KWH Boiler Pump 5 Kilowatt Hours 186 Boiler5 Circ Pmp BP5-RPM Boiler Pump 5 Motor Speed 187 Boiler5 Circ Pmp BP5-O Boiler Pump 5 Output 188 Boiler5 Circ Pmp BP5-DP Boiler Pump 5 Diff Pressure 189 Boiler5 Circ Pmp BP5-RESET Boiler Pump 5 Reset Drive Fault 190 Boiler5 Circ Pmp BP5-% Boiler Pump 5 Speed Feedback 191 Boiler5 Circ Pmp BP5-S Boiler Pump 5 Status 192 Boiler5 Circ Pmp BP5-DO% Boiler Pump 5 Drive Output Percent 193 Boiler5 Circ Pmp OL BP5-OL Boiler Pump 5 Overload 194 Boiler5 Ena BLR5-EN Boiler 5 Enable 195 Boiler5 Entering BLR5EW-T Boiler 5 Entering Water Temperature 196 Boiler5 Flow BLR5-FS Boiler 5 Flow Switch 197 Boiler5 GAlarm BLR5-A Boiler 5 Alarm 198 Boiler5 HTemp BLR5HT-A Boiler 5 High Temperature Alarm 199 Boiler5 Iso Status BLR5ISOV-S Boiler 5 Isolation Valve Status 200 Boiler5 Iso Valve BLR5ISOV-C Boiler 5 Isolation Valve Command 201 Boiler5 Leaving BLR5LW-T Boiler 5 Leaving Water Temperature 202 Boiler5 MS BLR5-MS Boiler 5 Maintenance Switch 203 Boiler5 SP BLR5SP-O Boiler 5 Setpoint Output 204 Boiler5 Status BLR5-S Boiler 5 Status 205 Boiler6 BLR6-C Boiler 6 Command 206 Boiler6 BLR6-O Boiler 6 Output 207 Boiler6 Circ Pmp BP6-BYPASS Boiler Pump 6 Bypass Drive

208 Boiler6 Circ Pmp BP6-C Boiler Pump 6 Command 209 Boiler6 Circ Pmp BP6-HOA Boiler Pump 6 Control Mode 210 Boiler6 Circ Pmp BP6-% Boiler Pump 6 Eff Command 211 Boiler6 Circ Pmp BP6-FAULT Boiler Pump 6 Fault Code 212 Boiler6 Circ Pmp BP6-HZ Boiler Pump 6 Output Frequency 213 Boiler6 Circ Pmp BP6-KWH Boiler Pump 6 Kilowatt Hours 214 Boiler6 Circ Pmp BP6-RPM Boiler Pump 6 Motor Speed 215 Boiler6 Circ Pmp BP6-O Boiler Pump 6 Output 216 Boiler6 Circ Pmp BP6-DP Boiler Pump 6 Diff Pressure 217 Boiler6 Circ Pmp BP6-RESET Boiler Pump 6 Reset Drive Fault 218 Boiler6 Circ Pmp BP6-% Boiler Pump 6 Speed Feedback 219 Boiler6 Circ Pmp BP6-S Boiler Pump 6 Status 220 Boiler6 Circ Pmp BP6-DO% Boiler Pump 6 Drive Output Percent 221 Boiler6 Circ Pmp OL BP6-OL Boiler Pump 6 Overload 222 Boiler6 Ena BLR6-EN Boiler 6 Enable 223 Boiler6 Entering BLR6EW-T Boiler 6 Entering Water Temperature 224 Boiler6 Flow BLR6-FS Boiler 6 Flow Switch 225 Boiler6 GAlarm BLR6-A Boiler 6 Alarm 226 Boiler6 HTemp BLR6HT-A Boiler 6 High Temperature Alarm 227 Boiler6 Iso Status BLR6ISOV-S Boiler 6 Isolation Valve Status 228 Boiler6 Iso Valve BLR6ISOV-C Boiler 6 Isolation Valve Command 229 Boiler6 Leaving BLR6LW-T Boiler 6 Leaving Water Temperature 230 Boiler6 MS BLR6-MS Boiler 6 Maintenance Switch 231 Boiler6 SP BLR6SP-O Boiler 6 Setpoint Output 232 Boiler6 Status BLR6-S Boiler 6 Status 233 Boiler7 BLR7-C Boiler 7 Command 234 Boiler7 BLR7-O Boiler 7 Output 235 Boiler7 Circ Pmp BP7-BYPASS Boiler Pump 7 Bypass Drive 236 Boiler7 Circ Pmp BP7-C Boiler Pump 7 Command 237 Boiler7 Circ Pmp BP7-HOA Boiler Pump 7 Control Mode 238 Boiler7 Circ Pmp BP7-% Boiler Pump 7 Eff Command 239 Boiler7 Circ Pmp BP7-FAULT Boiler Pump 7 Fault Code 240 Boiler7 Circ Pmp BP7-HZ Boiler Pump 7 Output Frequency 241 Boiler7 Circ Pmp BP7-KWH Boiler Pump 7 Kilowatt Hours 242 Boiler7 Circ Pmp BP7-RPM Boiler Pump 7 Motor Speed 243 Boiler7 Circ Pmp BP7-O Boiler Pump 7 Output 244 Boiler7 Circ Pmp BP7-DP Boiler Pump 7 Diff Pressure 245 Boiler7 Circ Pmp BP7-RESET Boiler Pump 7 Reset Drive Fault 246 Boiler7 Circ Pmp BP7-% Boiler Pump 7 Speed Feedback 247 Boiler7 Circ Pmp BP7-S Boiler Pump 7 Status 248 Boiler7 Circ Pmp BP7-DO% Boiler Pump 7 Drive Output Percent 249 Boiler7 Circ Pmp OL BP7-OL Boiler Pump 7 Overload 250 Boiler7 Ena BLR7-EN Boiler 7 Enable 251 Boiler7 Entering BLR7EW-T Boiler 7 Entering Water Temperature 252 Boiler7 Flow BLR7-FS Boiler 7 Flow Switch 253 Boiler7 GAlarm BLR7-A Boiler 7 Alarm 254 Boiler7 HTemp BLR7HT-A Boiler 7 High Temperature Alarm 255 Boiler7 Iso Status BLR7ISOV-S Boiler 7 Isolation Valve Status 256 Boiler7 Iso Valve BLR7ISOV-C Boiler 7 Isolation Valve Command 257 Boiler7 Leaving BLR7LW-T Boiler 7 Leaving Water Temperature 258 Boiler7 MS BLR7-MS Boiler 7 Maintenance Switch 259 Boiler7 SP BLR7SP-O Boiler 7 Setpoint Output 260 Boiler7 Status BLR7-S Boiler 7 Status 261 Boiler8 BLR8-C Boiler 8 Command 262 Boiler8 BLR8-O Boiler 8 Output 263 Boiler8 Circ Pmp BP8-BYPASS Boiler Pump 8 Bypass Drive 264 Boiler8 Circ Pmp BP8-C Boiler Pump 8 Command 265 Boiler8 Circ Pmp BP8-HOA Boiler Pump 8 Control Mode 266 Boiler8 Circ Pmp BP8-% Boiler Pump 8 Eff Command 267 Boiler8 Circ Pmp BP8-FAULT Boiler Pump 8 Fault Code 268 Boiler8 Circ Pmp BP8-HZ Boiler Pump 8 Output Frequency 269 Boiler8 Circ Pmp BP8-KWH Boiler Pump 8 Kilowatt Hours 270 Boiler8 Circ Pmp BP8-RPM Boiler Pump 8 Motor Speed 271 Boiler8 Circ Pmp BP8-O Boiler Pump 8 Output 272 Boiler8 Circ Pmp BP8-DP Boiler Pump 8 Diff Pressure 273 Boiler8 Circ Pmp BP8-RESET Boiler Pump 8 Reset Drive Fault 274 Boiler8 Circ Pmp BP8-% Boiler Pump 8 Speed Feedback 275 Boiler8 Circ Pmp BP8-S Boiler Pump 8 Status 276 Boiler8 Circ Pmp BP8-DO% Boiler Pump 8 Drive Output Percent

277 Boiler8 Circ Pmp OL BP8-OL Boiler Pump 8 Overload 278 Boiler8 Ena BLR8-EN Boiler 8 Enable 279 Boiler8 Entering BLR8EW-T Boiler 8 Entering Water Temperature 280 Boiler8 Flow BLR8-FS Boiler 8 Flow Switch 281 Boiler8 GAlarm BLR8-A Boiler 8 Alarm 282 Boiler8 HTemp BLR8HT-A Boiler 8 High Temperature Alarm 283 Boiler8 Iso Status BLR8ISOV-S Boiler 8 Isolation Valve Status 284 Boiler8 Iso Valve BLR8ISOV-C Boiler 8 Isolation Valve Command 285 Boiler8 Leaving BLR8LW-T Boiler 8 Leaving Water Temperature 286 Boiler8 MS BLR8-MS Boiler 8 Maintenance Switch 287 Boiler8 SP BLR8SP-O Boiler 8 Setpoint Output 288 Boiler8 Status BLR8-S Boiler 8 Status 289 Box Heating HTG-A Heating Alarm 290 Box Heating HTG-C Heating Command 291 Box Heating HTG-% Heating Effective Command 292 Box Heating HTG-O Heating Output 293 Box Heating HTG-O Heating Output 294 Box Heating HTG-POS Heating Position 295 Box Heating HTG1-C Heating Stage 1 Command 296 Box Heating HTG2-C Heating Stage 2 Command 297 Box Heating HTG3-C Heating Stage 3 Command 298 Box Heating HTG-S Heating Status 299 Box Heating 2 Position HTG-EC Heating Effective Command 300 Box Heating CL HTG-CL Heating Closed Status 301 Box Heating Enable HTG-EN Heating Enable 302 Box Heating OP HTG-OP Heating Open Status 303 Box Heating Stage 1 HTG1-EC Heating Effective Stage 1 Command 304 Box Heating Stage 2 HTG2-EC Heating Effective Stage 2 Command 305 Box Heating Stage 3 HTG3-EC Heating Effective Stage 3 Command 306 BTU 1 BLDG1-L Building 1 Load 307 BTU 2 BLDG2-L Building 2 Load 308 BTU 3 BLDG3-L Building 3 Load 309 BTU 4 BLDG4-L Building 4 Load 310 BTU 5 BLDG5-L Building 5 Load 311 BTU 6 BLDG6-L Building 6 Load 312 Building Load BLDG-L Building Load 313 Building Pressure BP-P Building Pressure Pressure 314 Building Static BLDG-P Building Static Pressure 315 Bypass Loop BYPV-O Bypass Valve Output 316 Calibration ACSOL-C Autocalibration Solenoid Command 317 Chemical CHEM-A Chemical Treatment Alarm 318 Chilled Water Entering CHWE-T Chilled Water Entering Temperature 319 Chilled Water Leaving CHWL-T Chilled Water Leaving Temperature 320 Chiller 1 CHW Iso Valve CH1CHWISOV-C Chiller 1 CHW Isolation Valve Command 321 Chiller 1 CW Iso Valve CH1CWISOV-C Chiller 1 CW Isolation Valve Command 322 Chiller 2 CHW Iso Valve CH2CHWISOV-C Chiller 2 CHW Isolation Valve Command 323 Chiller 2 CW Iso Valve CH2CWISOV-C Chiller 2 CW Isolation Valve Command 324 Chiller 3 CHW Iso Valve CH3CHWISOV-C Chiller 3 CHW Isolation Valve Command 325 Chiller 3 CW Iso Valve CH3CWISOV-C Chiller 3 CW Isolation Valve Command 326 Chiller 4 CHW Iso Valve CH4CHWISOV-C Chiller 4 CHW Isolation Valve Command 327 Chiller 4 CW Iso Valve CH4CWISOV-C Chiller 4 CW Isolation Valve Command 328 Chiller 5 CHW Iso Valve CH5CHWISOV-C Chiller 5 CHW Isolation Valve Command 329 Chiller 5 CW Iso Valve CH5CWISOV-C Chiller 5 CW Isolation Valve Command 330 Chiller 6 CHW Iso Valve CH6CHWISOV-C Chiller 6 CHW Isolation Valve Command 331 Chiller 6 CW Iso Valve CH6CWISOV-C Chiller 6 CW Isolation Valve Command 332 Chiller 7 CHW Iso Valve CH7CHWISOV-C Chiller 7 CHW Isolation Valve Command 333 Chiller 7 CW Iso Valve CH7CWISOV-C Chiller 7 CW Isolation Valve Command 334 Chiller 8 CHW Iso Valve CH8CHWISOV-C Chiller 8 CHW Isolation Valve Command 335 Chiller 8 CW Iso Valve CH8CWISOV-C Chiller 8 CW Isolation Valve Command 336 Chiller1 CH1-%FLA Chiller 1 Percent Full Load Amps 337 Chiller1 CH1-AMPS Chiller 1 Amps 338 Chiller1 CH1-EN Chiller 1 Enable 339 Chiller1 Alarm CH1-A Chiller 1 Alarm 340 Chiller1 CHW CH1CHW-F Chiller 1 CHW Flow 341 Chiller1 CHW Entering CH1CHWE-T Chiller 1 CHW Entering Temperature 342 Chiller1 CHW Flow CH1CHW-FS Chiller 1 CHW Flow Switch 343 Chiller1 CHW Iso Status CH1CHWISOV-S Chiller 1 CHW Isolation Valve Status 344 Chiller1 CHW Iso Valve CH1CHWISOV-C Chiller 1 CHW Isolation Valve Command 345 Chiller1 CHW Iso Valve CH1CHWISOV-O Chiller 1 CHW Isolation Valve Output

346 Chiller1 CHW IsoVlv MS CH1CHWISOV-MS Chiller 1 CHW Isolation Valve Maint Sw 347 Chiller1 CHW Leaving CH1CHWL-T Chiller 1 CHW Leaving Temperature 348 Chiller1 CurrLim CH1CL-O Chiller 1 Current Limit Output 349 Chiller1 CW CH1CW-F Chiller 1 CW Flow 350 Chiller1 CW Entering CH1CWE-T Chiller 1 CW Entering Temperature 351 Chiller1 CW Flow CH1CW-FS Chiller 1 CW Flow Switch 352 Chiller1 CW Iso Status CH1CWISOV-S Chiller 1 CW Isolation Valve Status 353 Chiller1 CW Iso Valve CH1CWISOV-C Chiller 1 CW Isolation Valve Command 354 Chiller1 CW Iso Valve CH1CWISOV-O Chiller 1 CW Isolation Valve Output 355 Chiller1 CW IsoVlv MS CH1CWISOV-MS Chiller 1 CW Isolation Valve Maint Sw 356 Chiller1 CW Leaving CH1CWL-T Chiller 1 CW Leaving Temperature 357 Chiller1 MS CH1-MS Chiller 1 Maintenance Switch 358 Chiller1 Setpoint CH1SP-O Chiller 1 Setpoint Output 359 Chiller1 Status CH1-S Chiller 1 Status 360 Chiller2 CH2-%FLA Chiller 2 Percent Full Load Amps 361 Chiller2 CH2-AMPS Chiller 2 Amps 362 Chiller2 CH2-EN Chiller 2 Enable 363 Chiller2 Alarm CH2-A Chiller 2 Alarm 364 Chiller2 CHW CH2CHW-F Chiller 2 CHW Flow 365 Chiller2 CHW Entering CH2CHWE-T Chiller 2 CHW Entering Temperature 366 Chiller2 CHW Flow CH2CHW-FS Chiller 2 CHW Flow Switch 367 Chiller2 CHW Iso Status CH2CHWISOV-S Chiller 2 CHW Isolation Valve Status 368 Chiller2 CHW Iso Valve CH2CHWISOV-C Chiller 2 CHW Isolation Valve Command 369 Chiller2 CHW Iso Valve CH2CHWISOV-O Chiller 2 CHW Isolation Valve Output 370 Chiller2 CHW IsoVlv MS CH2CHWISOV-MS Chiller 2 CHW Isolation Valve Maint Sw 371 Chiller2 CHW Leaving CH2CHWL-T Chiller 2 CHW Leaving Temperature 372 Chiller2 CurrLim CH2CL-O Chiller 2 Current Limit Output 373 Chiller2 CW CH2CW-F Chiller 2 CW Flow 374 Chiller2 CW Entering CH2CWE-T Chiller 2 CW Entering Temperature 375 Chiller2 CW Flow CH2CW-FS Chiller 2 CW Flow Switch 376 Chiller2 CW Iso Status CH2CWISOV-S Chiller 2 CW Isolation Valve Status 377 Chiller2 CW Iso Valve CH2CWISOV-C Chiller 2 CW Isolation Valve Command 378 Chiller2 CW Iso Valve CH2CWISOV-O Chiller 2 CW Isolation Valve Output 379 Chiller2 CW IsoVlv MS CH2CWISOV-MS Chiller 2 CW Isolation Valve Maint Sw 380 Chiller2 CW Leaving CH2CWL-T Chiller 2 CW Leaving Temperature 381 Chiller2 MS CH2-MS Chiller 2 Maintenance Switch 382 Chiller2 Setpoint CH2SP-O Chiller 2 Setpoint Output 383 Chiller2 Status CH2-S Chiller 2 Status 384 Chiller3 CH3-%FLA Chiller 3 Percent Full Load Amps 385 Chiller3 CH3-AMPS Chiller 3 Amps 386 Chiller3 CH3-EN Chiller 3 Enable 387 Chiller3 Alarm CH3-A Chiller 3 Alarm 388 Chiller3 CHW CH3CHW-F Chiller 3 CHW Flow 389 Chiller3 CHW Entering CH3CHWE-T Chiller 3 CHW Entering Temperature 390 Chiller3 CHW Flow CH3CHW-FS Chiller 3 CHW Flow Switch 391 Chiller3 CHW Iso Status CH3CHWISOV-S Chiller 3 CHW Isolation Valve Status 392 Chiller3 CHW Iso Valve CH3CHWISOV-C Chiller 3 CHW Isolation Valve Command 393 Chiller3 CHW Iso Valve CH3CHWISOV-O Chiller 3 CHW Isolation Valve Output 394 Chiller3 CHW IsoVlv MS CH3CHWISOV-MS Chiller 3 CHW Isolation Valve Maint Sw 395 Chiller3 CHW Leaving CH3CHWL-T Chiller 3 CHW Leaving Temperature 396 Chiller3 CurrLim CH3CL-O Chiller 3 Current Limit Output 397 Chiller3 CW CH3CW-F Chiller 3 CW Flow 398 Chiller3 CW Entering CH3CWE-T Chiller 3 CW Entering Temperature 399 Chiller3 CW Flow CH3CW-FS Chiller 3 CW Flow Switch 400 Chiller3 CW Iso Status CH3CWISOV-S Chiller 3 CW Isolation Valve Status 401 Chiller3 CW Iso Valve CH3CWISOV-C Chiller 3 CW Isolation Valve Command 402 Chiller3 CW Iso Valve CH3CWISOV-O Chiller 3 CW Isolation Valve Output 403 Chiller3 CW IsoVlv MS CH3CWISOV-MS Chiller 3 CW Isolation Valve Maint Sw 404 Chiller3 CW Leaving CH3CWL-T Chiller 3 CW Leaving Temperature 405 Chiller3 MS CH3-MS Chiller 3 Maintenance Switch 406 Chiller3 Setpoint CH3SP-O Chiller 3 Setpoint Output 407 Chiller3 Status CH3-S Chiller 3 Status 408 Chiller4 CH4-%FLA Chiller 4 Percent Full Load Amps 409 Chiller4 CH4-AMPS Chiller 4 Amps 410 Chiller4 CH4-EN Chiller 4 Enable 411 Chiller4 Alarm CH4-A Chiller 4 Alarm 412 Chiller4 CHW CH4CHW-F Chiller 4 CHW Flow 413 Chiller4 CHW Entering CH4CHWE-T Chiller 4 CHW Entering Temperature 414 Chiller4 CHW Flow CH4CHW-FS Chiller 4 CHW Flow Switch

415 Chiller4 CHW Iso Status CH4CHWISOV-S Chiller 4 CHW Isolation Valve Status 416 Chiller4 CHW Iso Valve CH4CHWISOV-C Chiller 4 CHW Isolation Valve Command 417 Chiller4 CHW Iso Valve CH4CHWISOV-O Chiller 4 CHW Isolation Valve Output 418 Chiller4 CHW IsoVlv MS CH4CHWISOV-MS Chiller 4 CHW Isolation Valve Maint Sw 419 Chiller4 CHW Leaving CH4CHWL-T Chiller 4 CHW Leaving Temperature 420 Chiller4 CurrLim CH4CL-O Chiller 4 Current Limit Output 421 Chiller4 CW CH4CW-F Chiller 4 CW Flow 422 Chiller4 CW Entering CH4CWE-T Chiller 4 CW Entering Temperature 423 Chiller4 CW Flow CH4CW-FS Chiller 4 CW Flow Switch 424 Chiller4 CW Iso Status CH4CWISOV-S Chiller 4 CW Isolation Valve Status 425 Chiller4 CW Iso Valve CH4CWISOV-C Chiller 4 CW Isolation Valve Command 426 Chiller4 CW Iso Valve CH4CWISOV-O Chiller 4 CW Isolation Valve Output 427 Chiller4 CW IsoVlv MS CH4CWISOV-MS Chiller 4 CW Isolation Valve Maint Sw 428 Chiller4 CW Leaving CH4CWL-T Chiller 4 CW Leaving Temperature 429 Chiller4 MS CH4-MS Chiller 4 Maintenance Switch 430 Chiller4 Setpoint CH4SP-O Chiller 4 Setpoint Output 431 Chiller4 Status CH4-S Chiller 4 Status 432 Chiller5 CH5-%FLA Chiller 5 Percent Full Load Amps 433 Chiller5 CH5-AMPS Chiller 5 Amps 434 Chiller5 CH5-EN Chiller 5 Enable 435 Chiller5 Alarm CH5-A Chiller 5 Alarm 436 Chiller5 CHW CH5CHW-F Chiller 5 CHW Flow 437 Chiller5 CHW Entering CH5CHWE-T Chiller 5 CHW Entering Temperature 438 Chiller5 CHW Flow CH5CHW-FS Chiller 5 CHW Flow Switch 439 Chiller5 CHW Iso Status CH5CHWISOV-S Chiller 5 CHW Isolation Valve Status 440 Chiller5 CHW Iso Valve CH5CHWISOV-C Chiller 5 CHW Isolation Valve Command 441 Chiller5 CHW Iso Valve CH5CHWISOV-O Chiller 5 CHW Isolation Valve Output 442 Chiller5 CHW IsoVlv MS CH5CHWISOV-MS Chiller 5 CHW Isolation Valve Maint Sw 443 Chiller5 CHW Leaving CH5CHWL-T Chiller 5 CHW Leaving Temperature 444 Chiller5 CurrLim CH5CL-O Chiller 5 Current Limit Output 445 Chiller5 CW CH5CW-F Chiller 5 CW Flow 446 Chiller5 CW Entering CH5CWE-T Chiller 5 CW Entering Temperature 447 Chiller5 CW Flow CH5CW-FS Chiller 5 CW Flow Switch 448 Chiller5 CW Iso Status CH5CWISOV-S Chiller 5 CW Isolation Valve Status 449 Chiller5 CW Iso Valve CH5CWISOV-C Chiller 5 CW Isolation Valve Command 450 Chiller5 CW Iso Valve CH5CWISOV-O Chiller 5 CW Isolation Valve Output 451 Chiller5 CW IsoVlv MS CH5CWISOV-MS Chiller 5 CW Isolation Valve Maint Sw 452 Chiller5 CW Leaving CH5CWL-T Chiller 5 CW Leaving Temperature 453 Chiller5 MS CH5-MS Chiller 5 Maintenance Switch 454 Chiller5 Setpoint CH5SP-O Chiller 5 Setpoint Output 455 Chiller5 Status CH5-S Chiller 5 Status 456 Chiller6 CH6-%FLA Chiller 6 Percent Full Load Amps 457 Chiller6 CH6-AMPS Chiller 6 Amps 458 Chiller6 CH6-EN Chiller 6 Enable 459 Chiller6 Alarm CH6-A Chiller 6 Alarm 460 Chiller6 CHW CH6CHW-F Chiller 6 CHW Flow 461 Chiller6 CHW Entering CH6CHWE-T Chiller 6 CHW Entering Temperature 462 Chiller6 CHW Flow CH6CHW-FS Chiller 6 CHW Flow Switch 463 Chiller6 CHW Iso Status CH6CHWISOV-S Chiller 6 CHW Isolation Valve Status 464 Chiller6 CHW Iso Valve CH6CHWISOV-C Chiller 6 CHW Isolation Valve Command 465 Chiller6 CHW Iso Valve CH6CHWISOV-O Chiller 6 CHW Isolation Valve Output 466 Chiller6 CHW IsoVlv MS CH6CHWISOV-MS Chiller 6 CHW Isolation Valve Maint Sw 467 Chiller6 CHW Leaving CH6CHWL-T Chiller 6 CHW Leaving Temperature 468 Chiller6 CurrLim CH6CL-O Chiller 6 Current Limit Output 469 Chiller6 CW CH6CW-F Chiller 6 CW Flow 470 Chiller6 CW Entering CH6CWE-T Chiller 6 CW Entering Temperature 471 Chiller6 CW Flow CH6CW-FS Chiller 6 CW Flow Switch 472 Chiller6 CW Iso Status CH6CWISOV-S Chiller 6 CW Isolation Valve Status 473 Chiller6 CW Iso Valve CH6CWISOV-C Chiller 6 CW Isolation Valve Command 474 Chiller6 CW Iso Valve CH6CWISOV-O Chiller 6 CW Isolation Valve Output 475 Chiller6 CW IsoVlv MS CH6CWISOV-MS Chiller 6 CW Isolation Valve Maint Sw 476 Chiller6 CW Leaving CH6CWL-T Chiller 6 CW Leaving Temperature 477 Chiller6 MS CH6-MS Chiller 6 Maintenance Switch 478 Chiller6 Setpoint CH6SP-O Chiller 6 Setpoint Output 479 Chiller6 Status CH6-S Chiller 6 Status 480 Chiller7 CH7-%FLA Chiller 7 Percent Full Load Amps 481 Chiller7 CH7-AMPS Chiller 7 Amps 482 Chiller7 CH7-EN Chiller 7 Enable 483 Chiller7 Alarm CH7-A Chiller 7 Alarm

484 Chiller7 CHW CH7CHW-F Chiller 7 CHW Flow 485 Chiller7 CHW Entering CH7CHWE-T Chiller 7 CHW Entering Temperature 486 Chiller7 CHW Flow CH7CHW-FS Chiller 7 CHW Flow Switch 487 Chiller7 CHW Iso Status CH7CHWISOV-S Chiller 7 CHW Isolation Valve Status 488 Chiller7 CHW Iso Valve CH7CHWISOV-C Chiller 7 CHW Isolation Valve Command 489 Chiller7 CHW Iso Valve CH7CHWISOV-O Chiller 7 CHW Isolation Valve Output 490 Chiller7 CHW IsoVlv MS CH7CHWISOV-MS Chiller 7 CHW Isolation Valve Maint Sw 491 Chiller7 CHW Leaving CH7CHWL-T Chiller 7 CHW Leaving Temperature 492 Chiller7 CurrLim CH7CL-O Chiller 7 Current Limit Output 493 Chiller7 CW CH7CW-F Chiller 7 CW Flow 494 Chiller7 CW Entering CH7CWE-T Chiller 7 CW Entering Temperature 495 Chiller7 CW Flow CH7CW-FS Chiller 7 CW Flow Switch 496 Chiller7 CW Iso Status CH7CWISOV-S Chiller 7 CW Isolation Valve Status 497 Chiller7 CW Iso Valve CH7CWISOV-C Chiller 7 CW Isolation Valve Command 498 Chiller7 CW Iso Valve CH7CWISOV-O Chiller 7 CW Isolation Valve Output 499 Chiller7 CW IsoVlv MS CH7CWISOV-MS Chiller 7 CW Isolation Valve Maint Sw 500 Chiller7 CW Leaving CH7CWL-T Chiller 7 CW Leaving Temperature 501 Chiller7 MS CH7-MS Chiller 7 Maintenance Switch 502 Chiller7 Setpoint CH7SP-O Chiller 7 Setpoint Output 503 Chiller7 Status CH7-S Chiller 7 Status 504 Chiller8 CH8-%FLA Chiller 8 Percent Full Load Amps 505 Chiller8 CH8-AMPS Chiller 8 Amps 506 Chiller8 CH8-EN Chiller 8 Enable 507 Chiller8 Alarm CH8-A Chiller 8 Alarm 508 Chiller8 CHW CH8CHW-F Chiller 8 CHW Flow 509 Chiller8 CHW Entering CH8CHWE-T Chiller 8 CHW Entering Temperature 510 Chiller8 CHW Flow CH8CHW-FS Chiller 8 CHW Flow Switch 511 Chiller8 CHW Iso Status CH8CHWISOV-S Chiller 8 CHW Isolation Valve Status 512 Chiller8 CHW Iso Valve CH8CHWISOV-C Chiller 8 CHW Isolation Valve Command 513 Chiller8 CHW Iso Valve CH8CHWISOV-O Chiller 8 CHW Isolation Valve Output 514 Chiller8 CHW IsoVlv MS CH8CHWISOV-MS Chiller 8 CHW Isolation Valve Maint Sw 515 Chiller8 CHW Leaving CH8CHWL-T Chiller 8 CHW Leaving Temperature 516 Chiller8 CurrLim CH8CL-O Chiller 8 Current Limit Output 517 Chiller8 CW CH8CW-F Chiller 8 CW Flow 518 Chiller8 CW Entering CH8CWE-T Chiller 8 CW Entering Temperature 519 Chiller8 CW Flow CH8CW-FS Chiller 8 CW Flow Switch 520 Chiller8 CW Iso Status CH8CWISOV-S Chiller 8 CW Isolation Valve Status 521 Chiller8 CW Iso Valve CH8CWISOV-C Chiller 8 CW Isolation Valve Command 522 Chiller8 CW Iso Valve CH8CWISOV-O Chiller 8 CW Isolation Valve Output 523 Chiller8 CW IsoVlv MS CH8CWISOV-MS Chiller 8 CW Isolation Valve Maint Sw 524 Chiller8 CW Leaving CH8CWL-T Chiller 8 CW Leaving Temperature 525 Chiller8 MS CH8-MS Chiller 8 Maintenance Switch 526 Chiller8 Setpoint CH8SP-O Chiller 8 Setpoint Output 527 Chiller8 Status CH8-S Chiller 8 Status 528 Chlr1 CHW Iso Valve CH1CHWISOV-POS Chiller 1 CHW Isolation Valve Position 529 Chlr1 CHW Iso Valve CL CH1CHWISOV-CL Chiller 1 CHW Iso Valve Closed Status 530 Chlr1 CHW Iso Valve OP CH1CHWISOV-OP Chiller 1 CHW Iso Valve Open Status 531 Chlr1 Curr Limit CH1CL-% Chiller 1 Current Limit Eff Command 532 Chlr1 CW Iso Valve CH1CWISOV-POS Chiller 1 CW Isolation Valve Position 533 Chlr1 CW Iso Valve CL CH1CWISOV-CL Chiller 1 CW Iso Valve Closed Status 534 Chlr1 CW Iso Valve OP CH1CWISOV-OP Chiller 1 CW Iso Valve Open Status 535 Chlr1 LO CHLR1-LO Chiller 1 Lockout Switch 536 Chlr1 OL CHLR1-OL Chiller 1 Overload 537 Chlr1 Setpoint CH1SP-% Chiller 1 Setpoint Effective Command 538 Chlr2 CHW Iso Valve CH2CHWISOV-POS Chiller 2 CHW Isolation Valve Position 539 Chlr2 CHW Iso Valve CL CH2CHWISOV-CL Chiller 2 CHW Iso Valve Closed Status 540 Chlr2 CHW Iso Valve OP CH2CHWISOV-OP Chiller 2 CHW Iso Valve Open Status 541 Chlr2 Curr Limit CH2CL-% Chiller 2 Current Limit Eff Command 542 Chlr2 CW Iso Valve CH2CWISOV-POS Chiller 2 CW Isolation Valve Position 543 Chlr2 CW Iso Valve CL CH2CWISOV-CL Chiller 2 CW Iso Valve Closed Status 544 Chlr2 CW Iso Valve OP CH2CWISOV-OP Chiller 2 CW Iso Valve Open Status 545 Chlr2 LO CHLR2-LO Chiller 2 Lockout Switch 546 Chlr2 OL CHLR2-OL Chiller 2 Overload 547 Chlr2 Setpoint CH2SP-% Chiller 2 Setpoint Effective Command 548 Chlr3 CHW Iso Valve CH3CHWISOV-POS Chiller 3 CHW Isolation Valve Position 549 Chlr3 CHW Iso Valve CL CH3CHWISOV-CL Chiller 3 CHW Iso Valve Closed Status 550 Chlr3 CHW Iso Valve OP CH3CHWISOV-OP Chiller 3 CHW Iso Valve Open Status 551 Chlr3 Curr Limit CH3CL-% Chiller 3 Current Limit Eff Command 552 Chlr3 CW Iso Valve CH3CWISOV-POS Chiller 3 CW Isolation Valve Position

553 Chlr3 CW Iso Valve CL CH3CWISOV-CL Chiller 3 CW Iso Valve Closed Status 554 Chlr3 CW Iso Valve OP CH3CWISOV-OP Chiller 3 CW Iso Valve Open Status 555 Chlr3 LO CHLR3-LO Chiller 3 Lockout Switch 556 Chlr3 OL CHLR3-OL Chiller 3 Overload 557 Chlr3 Setpoint CH3SP-% Chiller 3 Setpoint Effective Command 558 Chlr4 CHW Iso Valve CH4CHWISOV-POS Chiller 4 CHW Isolation Valve Position 559 Chlr4 CHW Iso Valve CL CH4CHWISOV-CL Chiller 4 CHW Iso Valve Closed Status 560 Chlr4 CHW Iso Valve OP CH4CHWISOV-OP Chiller 4 CHW Iso Valve Open Status 561 Chlr4 Curr Limit CH4CL-% Chiller 4 Current Limit Eff Command 562 Chlr4 CW Iso Valve CH4CWISOV-POS Chiller 4 CW Isolation Valve Position 563 Chlr4 CW Iso Valve CL CH4CWISOV-CL Chiller 4 CW Iso Valve Closed Status 564 Chlr4 CW Iso Valve OP CH4CWISOV-OP Chiller 4 CW Iso Valve Open Status 565 Chlr4 LO CHLR4-LO Chiller 4 Lockout Switch 566 Chlr4 OL CHLR4-OL Chiller 4 Overload 567 Chlr4 Setpoint CH4SP-% Chiller 4 Setpoint Effective Command 568 Chlr5 CHW Iso Valve CH5CHWISOV-POS Chiller 5 CHW Isolation Valve Position 569 Chlr5 CHW Iso Valve CL CH5CHWISOV-CL Chiller 5 CHW Iso Valve Closed Status 570 Chlr5 CHW Iso Valve OP CH5CHWISOV-OP Chiller 5 CHW Iso Valve Open Status 571 Chlr5 Curr Limit CH5CL-% Chiller 5 Current Limit Eff Command 572 Chlr5 CW Iso Valve CH5CWISOV-POS Chiller 5 CW Isolation Valve Position 573 Chlr5 CW Iso Valve CL CH5CWISOV-CL Chiller 5 CW Iso Valve Closed Status 574 Chlr5 CW Iso Valve OP CH5CWISOV-OP Chiller 5 CW Iso Valve Open Status 575 Chlr5 LO CHLR5-LO Chiller 5 Lockout Switch 576 Chlr5 OL CHLR5-OL Chiller 5 Overload 577 Chlr5 Setpoint CH5SP-% Chiller 5 Setpoint Effective Command 578 Chlr6 CHW Iso Valve CH6CHWISOV-POS Chiller 6 CHW Isolation Valve Position 579 Chlr6 CHW Iso Valve CL CH6CHWISOV-CL Chiller 6 CHW Iso Valve Closed Status 580 Chlr6 CHW Iso Valve OP CH6CHWISOV-OP Chiller 6 CHW Iso Valve Open Status 581 Chlr6 Curr Limit CH6CL-% Chiller 6 Current Limit Eff Command 582 Chlr6 CW Iso Valve CH6CWISOV-POS Chiller 6 CW Isolation Valve Position 583 Chlr6 CW Iso Valve CL CH6CWISOV-CL Chiller 6 CW Iso Valve Closed Status 584 Chlr6 CW Iso Valve OP CH6CWISOV-OP Chiller 6 CW Iso Valve Open Status 585 Chlr6 LO CHLR6-LO Chiller 6 Lockout Switch 586 Chlr6 OL CHLR6-OL Chiller 6 Overload 587 Chlr6 Setpoint CH6SP-% Chiller 6 Setpoint Effective Command 588 Chlr7 CHW Iso Valve CH7CHWISOV-POS Chiller 7 CHW Isolation Valve Position 589 Chlr7 CHW Iso Valve CL CH7CHWISOV-CL Chiller 7 CHW Iso Valve Closed Status 590 Chlr7 CHW Iso Valve OP CH7CHWISOV-OP Chiller 7 CHW Iso Valve Open Status 591 Chlr7 Curr Limit CH7CL-% Chiller 7 Current Limit Eff Command 592 Chlr7 CW Iso Valve CH7CWISOV-POS Chiller 7 CW Isolation Valve Position 593 Chlr7 CW Iso Valve CL CH7CWISOV-CL Chiller 7 CW Iso Valve Closed Status 594 Chlr7 CW Iso Valve OP CH7CWISOV-OP Chiller 7 CW Iso Valve Open Status 595 Chlr7 LO CHLR7-LO Chiller 7 Lockout Switch 596 Chlr7 OL CHLR7-OL Chiller 7 Overload 597 Chlr7 Setpoint CH7SP-% Chiller 7 Setpoint Effective Command 598 Chlr8 CHW Iso Valve CH8CHWISOV-POS Chiller 8 CHW Isolation Valve Position 599 Chlr8 CHW Iso Valve CL CH8CHWISOV-CL Chiller 8 CHW Iso Valve Closed Status 600 Chlr8 CHW Iso Valve OP CH8CHWISOV-OP Chiller 8 CHW Iso Valve Open Status 601 Chlr8 Curr Limit CH8CL-% Chiller 8 Current Limit Eff Command 602 Chlr8 CW Iso Valve CH8CWISOV-POS Chiller 8 CW Isolation Valve Position 603 Chlr8 CW Iso Valve CL CH8CWISOV-CL Chiller 8 CW Iso Valve Closed Status 604 Chlr8 CW Iso Valve OP CH8CWISOV-OP Chiller 8 CW Iso Valve Open Status 605 Chlr8 LO CHLR8-LO Chiller 8 Lockout Switch 606 Chlr8 OL CHLR8-OL Chiller 8 Overload 607 Chlr8 Setpoint CH8SP-% Chiller 8 Setpoint Effective Command 608 CHW Bypass Loop CHWBYPV-O Chilled Water Bypass Valve Output 609 CHW Bypass Valve CHWBYPV-% Chilled Water Bypass Valve Eff Command 610 CHW Bypass Valve CHWBYPV-POS Chilled Water Bypass Valve Position 611 CHW Bypass Valve CHWBYPV-S…