This document provides specifications for gypsum board installation and finishing for a federal construction project to repair HVAC systems in dormitory buildings 2405 and 2406 at Joint Base Charleston in South Carolina. The specifications require the use of 5/8 inch thick gypsum wallboard and panels meeting indoor air quality emission limits. Regular, fire-resistant, mold-resistant, and water-resistant gypsum board types must be provided. Fasteners, screws, nails, staples, and adhesives are specified along with requirements for recycled content, low VOC content, and indoor air quality certifications. The specifications outline installation requirements for framing and substrates, application of gypsum board and accessories, finishing levels, sealing, fire-resistant construction, patching and shaftwall framing.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 09 29 00 Page 1
Repair HVAC, Dorm Bldgs 2405-2406 Project No. DKGV Revised Final
1073189 May 15, 2018
SECTION 09 29 00
GYPSUM BOARD
08/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992; Reaffirmed 2005) Specifications for
Interior Installation of Cementitious
Backer Units
ASTM INTERNATIONAL (ASTM)
ASTM C475/C475M (2017) Standard Specification for Joint
Compound and Joint Tape for Finishing
Gypsum Board
ASTM C514 (2004; R 2020) Standard Specification for
Nails for the Application of Gypsum Board
ASTM C557 (2003; R 2017) Standard Specification for
Adhesives for Fastening Gypsum Wallboard to Wood Framing
ASTM C840 (2019b) Standard Specification for
Application and Finishing of Gypsum Board
ASTM C954 (2018) Standard Specification for Steel
Drill Screws for the Application of Gypsum
Panel Products or Metal Plaster Bases to
Steel Studs from 0.033 in. to
0.112 in. in Thickness
ASTM C1002 (2018) Standard Specification for Steel
Self-Piercing Tapping Screws for the
Application of Gypsum Panel Products or
Metal Plaster Bases to Wood Studs or Steel
Studs
ASTM C1047 (2019) Standard Specification for
Accessories for Gypsum Wallboard and
Gypsum Veneer Base
ASTM C1396/C1396M (2017) Standard Specification for Gypsum
Board
ASTM C1766 (2015; R2019) Standard Specification for
Factory-Laminated Gypsum Panel Products
ASTM D2394 (2017) Standard Test Methods for Simulated
SECTION 09 29 00 Page 2
Service Testing of Wood and Wood-Base
Finish Flooring
ASTM D3273 (2016) Standard Test Method for Resistance to Growth of Mold on the Surface of
Interior Coatings in an Environmental
Chamber
ASTM D5420 (2016) Standard Test Method for Impact
Resistance of Flat, Rigid Plastic
Specimen by Means of a Strike Impacted by a Falling Weight (Gardner Impact)
ASTM E84 (2020) Standard Test Method for Surface
Burning Characteristics of Building
Materials
ASTM E90 (2009; R2016) Standard Test Method for
Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and Elements
ASTM E336 (2020) Standard Test Method for
Measurement of Airborne Sound Attenuation between Rooms in Buildings
ASTM E695 (2003; R 2015; E 2015) Measuring Relative
Resistance of Wall, Floor, and Roof
Construction to Impact Loading
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile
Organic Chemical Emissions from Indoor
Sources using Environmental Chambers
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial
Use
GYPSUM ASSOCIATION (GA)
GA 214 (2010) Recommended Levels of Gypsum Board
Finish
GA 216 (2010) Application and Finishing of Gypsum
Panel Products
GA 224 (2008) Installation of Predecorated Gypsum
Board
GA 253 (2012) Application of Gypsum Sheathing
GA 600 (2009) Fire Resistance Design Manual http://www.approvalguide.com/
SECTION 09 29 00 Page 3
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program
For Chemical Emissions For Building
Materials, Finishes And Furnishings
UL Fire Resistance (2014) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section.01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Water-Resistant Gypsum Backing Board
Accessories
Submit for each type of gypsum board and for cementitious backer units.
Gypsum Board
Recycled Content for Gypsum Board; G
VOC Content of Joint Compound; G
SD-07 Certificates
Asbestos Free Materials; G
Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.
Indoor Air Quality for Gypsum Board; G
Indoor Air Quality for Non-aerosol Adhesives; G
Indoor Air Quality for Aerosol Adhesives; G
SD-08 Manufacturer's Instructions
Material Safety Data Sheets
SD-10 Operation and Maintenance Data
Manufacturer Maintenance Instructions
SECTION 09 29 00 Page 4
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
Submit required indoor air quality certifications in one submittal package.
1.3.1.1 Ceiling and Wall Systems
Provide products certified to meet indoor air quality requirements by
UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by
UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.4.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions. Provide adequate ventilation to prevent condensation.
Store per manufacturer's recommendations for allowable temperature and humidity range.Do not store gypsum wallboard with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives. Do not use materials that have visible moisture or biological growth.
1.4.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.5 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
1.6 ENVIRONMENTAL REQUIREMENTS
SECTION 09 29 00 Page 5
Do not expose the gypsum board to excessive sunlight prior to gypsum board application. Maintain a continuous uniform temperature of not less than 50 degrees F and not more than 80 degrees F for at least one week prior to the application of gypsum board work, while the gypsum board application is being done, and for at least one week after the gypsum board is set.
Shield air supply and distribution devices to prevent any uneven flow of air across the plastered surfaces. Provide ventilation to exhaust moist air to the outside during gypsum board application, set, and until gypsum board jointing is dry. In glazed areas, keep windows open top and bottom or side to side 3 to 4 inches. Reduce openings in cold weather to prevent freezing of joint compound when applied. For enclosed areas lacking natural ventilation, provide temporary mechanical means for ventilation.
In unglazed areas subjected to hot, dry winds or temperature differentials from day to night of 20 degrees F or more, screen openings with cheesecloth or similar materials. Avoid rapid drying. During periods of low indoor humidity, provide minimum air circulation following gypsum boarding and until gypsum board jointing complete and is dry.
1.8 FIRE RESISTIVE CONSTRUCTION
Comply with specified fire-rated assemblies for design numbers indicated per UL Fire Resistance or FM APP GUIDE.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only. Submit Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Gypsum Board
ASTM C1396/C1396M. Gypsum board must contain a minimum of 5 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content.Provide data identifying percentage of recycled content for gypsum board. Provide gypsum wall board and panels meeting the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification or validation of indoor air quality for gypsum board.
2.1.1.1 Regular
48 inch wide, 5/8 inch thick, tapered edges.
2.1.1.2 Type X (Special Fire-Resistant)
2.1.1.3 Mold Resistant / Anti-Microbial Gypsum
ASTM D3273. 48 inch wide, 5/8 inch thick, tapered edges.
2.1.2 Regular Water-Resistant Gypsum Backing Board
ASTM C1396/C1396M
2.1.2.1 Regular
SECTION 09 29 00 Page 6
2.1.3 Fasteners
2.1.3.1 Nails
ASTM C514.
2.1.3.2 Screws
ASTM C1002, Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.033 inch thick. ASTM C954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch thick. Provide cementitious backer unit screws with a polymer coating.
2.1.3.3 Staples
No. 16 USS gage flattened galvanized wire staples with 7/16 inch wide crown outside measurement and divergent point for base ply of two-ply gypsum board application. Use as follows:
Length of Legs Thicknes s of Gypsum Board
1-1/8 inches 1/2 inch
1-1/4 inches 5/8 inch
2.1.4 Adhesives
Provide non-aerosol adhesive products used on the interior of the building
(defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168. Provide aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for non-aerosol adhesives applied on the interior of the building (inside of the weatherproofing system). Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building (inside of the weatherproofing system).
2.1.4.1 Adhesive for Fastening Gypsum Board to Metal Framing
Type recommended by gypsum board manufacturer.
2.1.4.2 Adhesive for Fastening Gypsum Board to Wood Framing
ASTM C557.
2.1.5 Gypsum Studs
SECTION 09 29 00 Page 7
Provide one inch minimum thickness and 6 inch minimum width. Studs may be of one inch thick gypsum board or multilayers fastened to required thickness. Conform to ASTM C1396/C1396M for material and
GA 216 for installation.
2.1.6 Accessories
ASTM C1047. Fabricate from corrosion protected steel designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges must be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.1 Gypsum Board and Framing
Verify that surfaces of gypsum board and framing to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.2 Masonry or Concrete Walls
Verify that surfaces of masonry and concrete walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Building Construction Materials
Do not install building construction materials that show visual evidence of biological growth.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with
ASTM C840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece.Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may not be bonded
SECTION 09 29 00 Page 8 together with an adhesive. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Adhesive Application to Interior Masonry or Concrete Walls
Apply in accordance with ASTM C840, System VI or GA 216.
3.2.2 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C840, System VIII or GA 216.
3.3 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C840, GA 214 and
GA 216. Finish plenum areas above ceilings to Level 1 in accordance with
GA 214. Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA
214.
Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with
GA 214. Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214. Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use self-adhering fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.3.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with
GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.4 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00
JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.5 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and ceiling framing in accordance with the specifications contained in
UL Fire Resistance for the Design Number(s) indicated. Joints of fire-rated gypsum board enclosures must be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.6 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
SECTION 09 29 00 Page 9
3.9 SHAFTWALL FRAMING
Install the shaftwall system in accordance with the system manufacturer's published instructions. Coordinate bucks, anchors, blocking and other items placed in or behind shaftwall framing with electrical and mechanical work.
Patch or replace fireproofing materials which are damaged or removed during shaftwall construction.
-- End of Section --