| 502 CONS/JBKAE | Exhibit 4 |
| JBSA Lackland, TX | Swing Space for SWTW |
25 May 2022
QUESTIONS & ANSWERS
Cutoff date for contractor questions is 10 am CST, 31 May 2022.
Question 63: Please confirm if the fire alarm wiring, when routed above ceiling can be plenum installed, open cabling on j-hooks in lieu of conduit system.
Government Response: Yes.
Plenum rated wires compliant with applicable codes and standards may be used.