Attachment 8 - MAHG171095 Renovate Stennis Hall - Additional Specifications .pdf
PDF 134 KB Posted
- Attached to
- MAHG 17-1095 Stennis Hall
- Solicitation number
- FA301026R0010
About this file
This document contains technical specification sections for the Stennis Hall Renovation project at Keesler Air Force Base in Biloxi, Mississippi. The specifications cover gypsum board installation (Section 09 29 00), paints and coatings (Section 09 90 00), unit masonry (Section 04 20 00), and related finishes and structural work.
The gypsum board specification requires mold-resistant Type X gypsum board at 5/8 inch thickness for all interior areas, with recycled paper facings. Materials must be asbestos-free, and installation must comply with ASTM C 840 and GA 216 standards. Finishing requirements range from Level 1 (plenum areas) to Level 5 (general walls and ceilings), with specific finishing protocols for various surface conditions. The paints and coatings specification mandates use of MPI-approved products with environmentally friendly ratings (minimum E3), restricted lead and chromate content, and compliance with SSPC and ASTM standards. Specific coating systems are prescribed for different substrates including exterior metal (waterborne light industrial systems), interior concrete masonry (latex block fillers with institutional low-odor latex), interior metal (high-performance architectural latex), and gypsum board (institutional low-odor or epoxy systems depending on application). The unit masonry specification requires concrete masonry units (CMU) conforming to ASTM C 90 and C 129 standards with specified compressive strength of 2000 psi, Type N or S mortar for non-load-bearing interior masonry, and ASTM C 476 grout with minimum 2000 psi strength. All materials must be tested and certified for compliance, with field testing required during construction for mortar and grout quality control.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MAHG 17-1095 STENNIS HALL RENOVATION
KEESLER AFB, BILOXI, MS
SECTION 09 29 00
GYPSUM BOARD
05/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C 1002 (2007) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C 1047 (2010a) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C 1396/C 1396M (2009a) Standard Specification for Gypsum Board
ASTM C 475/C 475M (2002; R 2007) Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C 514 (2004; R 2009e1) Standard Specification for Nails for the Application of Gypsum Board
ASTM C 840 (2008) Application and Finishing of Gypsum Board
ASTM C 954 (2010) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from
0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness
GYPSUM ASSOCIATION (GA)
GA 214 (2007) Recommended Levels of Gypsum Board Finish
GA 216 (2010) Application and Finishing of Gypsum Panel Products
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval.Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SECTION 09 29 00 Page 1
FA301026R0010
Attachment 7
SD-03 Product Data
Accessories
Submit for each type of gypsum board.
Gypsum Board
SD-07 Certificates
Asbestos Free Materials ; G SD-08 Manufacturer's Instructions
Material Safety Data Sheets
1.3 DELIVERY, STORAGE, AND HANDLING
1.3.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.3.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions. Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range. Gypsum wallboard shall not be stored with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives.
1.3.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.4 ENVIRONMENTAL CONDITIONS
1.4.1 Temperature
Maintain a uniform temperature of not less than 50 degrees F in the structure for at least 48 hours prior to, during, and following the application of gypsum board, and joint treatment materials, or the bonding of adhesives.
1.4.2 Exposure to Weather
Protect gypsum board and cementitious backer unit products from direct exposure to rain, snow, sunlight, and other extreme weather conditions.
1.5 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a
SECTION 09 29 00 Page 2 minimum of 3 years of documented successful experience.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only. Submit Material Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Gypsum Board
ASTM C 1396/C 1396M . Paper facings shall be recycled paper.
2.1.1.1 Regular
2.1.1.2 Foil-Backed
48 inch wide, 5/8 inch thick, tapered edges. Provide single layer at SCIF boundry locations.
2.1.2 Mold Resistant Gypsum Board
Mold and Mildew Resistant Gypsum Board: ASTM C 1396, of thickness indicated below to resist mold and mildew; in maximum lengths available to minimize end-to-end butt joints. Board shall score minimum 10 when tested per ASTM D 3273.
Type X, 5/8 inch thick, for fire-resistant rated assemblies and where indicated.
Provide at ALL interior areas unless noted otherwise.
2.1.3 Joint Treatment Materials
ASTM C 475/C 475M .
2.1.3.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.3.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.3.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
SECTION 09 29 00 Page 3
2.1.3.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.3.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
2.1.4 Fasteners
2.1.4.1 Nails
ASTM C 514 .
2.1.4.2 Screws
ASTM C 1002 , Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.033 inch thick. ASTM C 954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch thick. Provide cementitious backer unit screws with a polymer coating.
2.1.5 Adhesives
Do not use adhesive containing benzene, carbon tetrachloride, or trichloroethylene. Adhesive must meet the requirements of LEED low emitting materials credit.
2.1.6 Accessories
ASTM C 1047 . Fabricate from corrosion protected steel or plastic designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges shall be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
2.1.7 Water
Provide clean, fresh, and potable water.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Gypsum Board and Framing
Verify that surfaces of gypsum board and framing to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do
SECTION 09 29 00 Page 4 not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Masonry Walls
Verify that surfaces of masonry walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C 840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may be bonded together with an adhesive, except where prohibited by fire rating(s).
Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer.
Provide type of gypsum board for use in each system specified herein as indicated.
3.3 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C 840 , GA 214 and GA 216 . Finish plenum areas above ceilings to Level 1 in accordance with GA 214 . Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214 . Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with GA 214 . Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214 . Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.3.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.4 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS Apply material with exposed surface flush with gypsum
SECTION 09 29 00 Page 5 board or cementitious backer units.
3.4.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing
Apply silicone sealant in a 3/8 inch bead to all joints and trowel flat.
Apply enough of the same sealant to all fasteners penetrating through the glass mat gypsum board surface to completely cover the penetration when troweled flat. Do not place [construction and materials behind sheathing until a visual inspection of sealed joints during daylight hours has been completed by Contracting Officer. 3.5 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
-- End of Section --
SECTION 09 29 00 Page 6
SECTION 09 90 00
PAINTS AND COATINGS
08/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
ACGIH 0100Doc (2005) Documentation of the Threshold Limit Values and Biological Exposure Indices
ASTM INTERNATIONAL (ASTM)
ASTM D 2092 (1995; R 2001e1) Standard Guide for Preparation of Zinc-Coated (Galvanized) Steel Surfaces for Painting
ASTM D 235 (2002; R 2008) Mineral Spirits (Petroleum Spirits) (Hydrocarbon Dry Cleaning Solvent)
ASTM D 4214 (2007) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films
ASTM D 4263 (1983; R 2005) Indicating Moisture in Concrete by the Plastic Sheet Method
ASTM D 4444 (2008) Use and Calibration of Hand-Held Moisture Meters
ASTM D 523 (2008) Standard Test Method for Specular Gloss
ASTM F 1869 (2004) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
MASTER PAINTERS INSTITUTE (MPI)
MPI 101 (Jan 2004) Epoxy Anti-Corrosive Metal Primer
MPI 107 (Jan 2004) Rust Inhibitive Primer (Water-Based)
MPI 108 (Jan 2004) High Build Epoxy Coating, Low Gloss
MPI 134 (Jan 2004) Galvanized Primer (Waterbased)
SECTION 09 90 00 Page 1
MPI 139 (Jan 2004) Interior High Performance Latex, MPI Gloss Level 3
MPI 141 (Jan 2004) Interior High Performance Latex MPI Gloss Level 5
MPI 144 (Jan 2004) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 2
MPI 145 (Jan 2004) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 3
MPI 163 (Jan 2006) Exterior W.B. Light Industrial Coating, Semi-Gloss, MPI Gloss Level 5
MPI 4 (Jan 2004) Interior/Exterior Latex Block Filler
MPI 47 (Jan 2004) Interior Alkyd, Semi-Gloss, MPI Gloss Level 5
MPI 50 (Jan 2004) Interior Latex Primer Sealer
MPI 77 (Jan 2004) Epoxy Gloss
MPI 79 (Jan 2004) Alkyd Anti-Corrosive Metal Primer
MPI 95 (Jan 2004) Quick Drying Primer for Aluminum
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC PA 1 (2000; E 2004) Shop, Field, and Maintenance Painting
SSPC PA Guide 3 (1982; E 1995) A Guide to Safety in Paint Application
SSPC SP 1 (1982; E 2004) Solvent Cleaning
SSPC SP 10 (2007) Near-White Blast Cleaning
SSPC SP 12 (2002) Surface Preparation and Cleaning of Metals by Waterjetting Prior to Recoating
SSPC SP 2 (1982; E 2004) Hand Tool Cleaning
SSPC SP 3 (2004; E 2004) Power Tool Cleaning
SSPC SP 6 (2007) Commercial Blast Cleaning
SSPC SP 7 (2007) Brush-Off Blast Cleaning
SSPC VIS 1 (2002; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Dry Abrasive Blast Cleaning
SSPC VIS 3 (2004) Visual Standard for Power-and Hand-Tool Cleaned Steel
SECTION 09 90 00 Page 2
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2008) Safety and Health Requirements Manual
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
EPA Method 24 (2000) Determination of Volatile Matter Content, Water Content, Density, Volume Solids, and Weight Solids of Surface Coatings
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-313 (Rev D; Am 1) Material Safety Data, Transportation Data and Disposal Data for Hazardous Materials Furnished to Government Activities
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
The current MPI, "Approved Product List" which lists paint by brand, label, product name and product code as of the date of contract award, will be used to determine compliance with the submittal requirements of this specification. The Contractor may choose to use a subsequent MPI "Approved Product List", however, only one list may be used for the entire contract and each coating system is to be from a single manufacturer. All coats on a particular substrate must be from a single manufacturer. No variation from the MPI Approved Products List is acceptable.
Samples of specified materials may be taken and tested for compliance with specification requirements.
SD-02 Shop Drawings
Piping identification
Submit color stencil codes
SD-03 Product Data
Coating ; G
Manufacturer's Technical Data Sheets
SECTION 09 90 00 Page 3
SD-04 Samples
Color ; G
Submit manufacturer's samples of paint colors. Cross reference color samples to color scheme as indicated.
SD-08 Manufacturer's Instructions
Application instructions Manufacturer's Material Safety Data Sheets
Submit manufacturer's Material Safety Data Sheets for coatings, solvents, and other potentially hazardous materials, as defined in
FED-STD-313 .
1.3 QUALITY ASSURANCE
1.3.1 Field Samples and Tests
The Contracting Officer may choose up to two coatings that have been delivered to the site to be tested at no cost to the Government. Take samples of each chosen product as specified in the paragraph "Sampling Procedures." Test each chosen product as specified in the paragraph "Testing Procedure." Products which do not conform, shall be removed from the job site and replaced with new products that conform to the referenced specification. Testing of replacement products that failed initial testing shall be at no cost to the Government. 1.3.1.1 Sampling Procedure
The Contracting Officer will select paint at random from the products that have been delivered to the job site for sample testing. The Contractor shall provide one quart samples of the selected paint materials. The samples shall be taken in the presence of the Contracting Officer, and labeled, identifying each sample. Provide labels in accordance with the paragraph "Packaging, Labeling, and Storage" of this specification.
1.3.1.2 Testing Procedure
Provide Batch Quality Conformance Testing for specified products, as defined by and performed by MPI. As an alternative to Batch Quality Conformance Testing, the Contractor may provide Qualification Testing for specified products above to the appropriate MPI product specification, using the third-party laboratory approved under the paragraph "Qualification Testing" laboratory for coatings. The qualification testing lab report shall include the backup data and summary of the test results. The summary shall list all of the reference specification requirements and the result of each test. The summary shall clearly indicate whether the tested paint meets each test requirement. Note that Qualification Testing may take 4 to 6 weeks to perform, due to the extent of testing required.
Submit name, address, telephone number, FAX number, and e-mail address of the independent third party laboratory selected to perform testing of coating samples for compliance with specification requirements. Submit documentation that laboratory is regularly engaged in testing of paint samples for conformance with specifications, and that employees performing testing are qualified. If the Contractor chooses MPI to perform the Batch Quality Conformance testing, the above submittal information is not required, only a letter is required from the Contractor stating that MPI
SECTION 09 90 00 Page 4 will perform the testing. 1.4 REGULATORY REQUIREMENTS
1.4.1 Environmental Protection
In addition to requirements specified elsewhere for environmental protection, provide coating materials that conform to the restrictions of the local Air Pollution Control District and regional jurisdiction.
Notify Contracting Officer of any paint specified herein which fails to conform.
1.4.2 Lead Content
Do not use coatings having a lead content over 0.06 percent by weight of nonvolatile content.
1.4.3 Chromate Content
Do not use coatings containing zinc-chromate or strontium-chromate.
1.4.4 Asbestos Content
Materials shall not contain asbestos.
1.4.5 Mercury Content
Materials shall not contain mercury or mercury compounds.
1.4.6 Silica
Abrasive blast media shall not contain free crystalline silica.
1.4.7 Human Carcinogens
Materials shall not contain ACGIH 0100Doc and ACGIH 0100Doc confirmed human carcinogens (A1) or suspected human carcinogens (A2).
1.5 PACKAGING, LABELING, AND STORAGE
Paints shall be in sealed containers that legibly show the contract specification number, designation name, formula or specification number, batch number, color, quantity, date of manufacture, manufacturer's formulation number, manufacturer's directions including any warnings and special precautions, and name and address of manufacturer. Pigmented paints shall be furnished in containers not larger than 5 gallons. Paints and thinners shall be stored in accordance with the manufacturer's written directions, and as a minimum, stored off the ground, under cover, with sufficient ventilation to prevent the buildup of flammable vapors, and at temperatures between 40 to 95 degrees F.
1.6 SAFETY AND HEALTH
Apply coating materials using safety methods and equipment in accordance with the following:
Work shall comply with applicable Federal, State, and local laws and regulations, and with the ACCIDENT PREVENTION PLAN, including Appendix A of EM 385-1-1 . The Activity Hazard Analysis shall include analyses of the potential impact of painting operations on painting personnel and on others involved in and adjacent to the work zone.
SECTION 09 90 00 Page 5
1.6.1 Safety Methods Used During Coating Application
Comply with the requirements of SSPC PA Guide 3 .
1.6.2 Toxic Materials
To protect personnel from overexposure to toxic materials, conform to the most stringent guidance of:
a. The applicable MSDS or local regulation.
b. 29 CFR 1910.1000 .
c. ACGIH 0100Doc , threshold limit values.
1.7 ENVIRONMENTAL CONDITIONS
Comply, at minimum, with manufacturer recommendations for space ventilation during and after installation.
1.7.1 Coatings
Do not apply coating when air or substrate conditions are:
a. Less than 5 degrees F above dew point;
b. Below 50 degrees F or over 95 degrees F, unless specifically pre-approved by the Contracting Officer and the product manufacturer. Under no circumstances shall application conditions exceed manufacturer recommendations.
1.8 COLOR SELECTION
Colors of finish coats shall be as indicated or specified. Where not indicated or specified, colors shall be selected by the Contracting Officer. Manufacturers' names and color identification are used for the purpose of color identification only. Named products are acceptable for use only if they conform to specified requirements. Products of other manufacturers are acceptable if the colors approximate colors indicated and the product conforms to specified requirements.
Tint each coat progressively darker to enable confirmation of the number of coats.
Color, texture, and pattern of wall coating systems shall be as indicated .
1.9 LOCATION AND SURFACE TYPE TO BE PAINTED
1.9.1 Painting Included
Where a space or surface is indicated to be painted, include the following unless indicated otherwise.
a. Surfaces behind portable objects and surface mounted articles readily detachable by removal of fasteners, such as screws and bolts.
b. New factory finished surfaces that require identification or color
SECTION 09 90 00 Page 6 coding and factory finished surfaces that are damaged during performance of the work.
c. Existing coated surfaces that are damaged during performance of the work.
1.9.1.1 Exterior Painting
Includes new surfaces of the building and appurtenances. Also included are existing coated surfaces made bare by cleaning operations.
1.9.1.2 Interior Painting
Includes new surfaces of the building and appurtenances as indicated and existing coated surfaces made bare by cleaning operations. Where a space or surface is indicated to be painted, include the following items, unless indicated otherwise.
a. Exposed columns, girders, beams, joists, and metal deck; and
b. Other contiguous surfaces.
1.9.2 Painting Excluded
Do not paint the following unless indicated otherwise.
a. Surfaces concealed and made inaccessible by panelboards, fixed ductwork, machinery, and equipment fixed in place.
b. Surfaces in concealed spaces. Concealed spaces are defined as enclosed spaces above suspended ceilings, furred spaces, attic spaces, crawl spaces, elevator shafts and chases.
c. Steel to be embedded in concrete.
d. Copper, stainless steel, aluminum, brass, and lead except existing coated surfaces.
e. Hardware, fittings, and other factory finished items.
1.9.3 Mechanical and Electrical Painting
Includes field coating of interior and exterior new and existingsurfaces.
a. Where a space or surface is indicated to be painted, include the following items unless indicated otherwise.
(1) Exposed piping, conduit, and ductwork;
(2) Supports, hangers, air grilles, and registers;
(3) Miscellaneous metalwork and insulation coverings.
b. Do not paint the following, unless indicated otherwise:
(1) New zinc-coated, aluminum, and copper surfaces under insulation
(3) New interior ferrous piping under insulation.
SECTION 09 90 00 Page 7
1.9.3.1 Fire Extinguishing Sprinkler Systems
Clean, pretreat, prime, and paint new fire extinguishing sprinkler systems including valves, piping, conduit, hangers, supports, miscellaneous metalwork, and accessories. Apply coatings to clean, dry surfaces, using clean brushes. Clean the surfaces to remove dust, dirt, rust, and loose mill scale. Immediately after cleaning, provide the metal surfaces with one coat primer per schedules. Shield sprinkler heads with protective covering while painting is in progress. Upon completion of painting, remove protective covering from sprinkler heads. Remove sprinkler heads which have been painted and replace with new sprinkler heads. Provide primed surfaces with the following:
a. Piping in Unfinished Areas: Provide primed surfaces with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of 1.0 mil in attic spaces, spaces above suspended ceilings, crawl spaces, pipe chases, mechanical equipment room, and spaces where walls or ceiling are not painted or not constructed of a prefinished material.
b. Piping in Finished Areas: Provide primed surfaces with two coats of paint to match adjacent surfaces, except provide valves and operating accessories with one coat of red alkyd gloss enamel applied to a minimum dry film thickness of 1.0 mil. Provide piping with 2 inch wide red enamel bands or self-adhering red plastic bands spaced at maximum of 20 foot intervals throughout the piping systems. 1.9.4 Definitions and Abbreviations
1.9.4.1 Qualification Testing
Qualification testing is the performance of all test requirements listed in the product specification. This testing is accomplished by MPI to qualify each product for the MPI Approved Product List, and may also be accomplished by Contractor's third party testing lab if an alternative to Batch Quality Conformance Testing by MPI is desired.
1.9.4.2 Batch Quality Conformance Testing
Batch quality conformance testing determines that the product provided is the same as the product qualified to the appropriate product specification. This testing shall only be accomplished by MPI testing lab.
1.9.4.3 Coating
A film or thin layer applied to a base material called a substrate. A coating may be a metal, alloy, paint, or solid/liquid suspensions on various substrates (metals, plastics, wood, paper, leather, cloth, etc.).
They may be applied by electrolysis, vapor deposition, vacuum, or mechanical means such as brushing, spraying, calendaring, and roller coating. A coating may be applied for aesthetic or protective purposes or both. The term "coating" as used herein includes emulsions, enamels, stains, varnishes, sealers, epoxies, and other coatings, whether used as primer, intermediate, or finish coat. The terms paint and coating are used interchangeably.
1.9.4.4 DFT or dft
Dry film thickness, the film thickness of the fully cured, dry paint or
SECTION 09 90 00 Page 8 coating.
1.9.4.5 DSD
Degree of Surface Degradation, the MPI system of defining degree of surface degradation. Five (5) levels are generically defined under the Assessment sections in the MPI Maintenance Repainting Manual.
1.9.4.6 EPP
Environmentally Preferred Products, a standard for determining environmental preferability in support of Executive Order 13101.
1.9.4.7 EXT
MPI short term designation for an exterior coating system.
1.9.4.8 INT
MPI short term designation for an interior coating system.
1.9.4.9 micron / microns
The metric measurement for 0.001 mm or one/one-thousandth of a millimeter.
1.9.4.10 mil / mils
The English measurement for 0.001 in or one/one-thousandth of an inch, equal to 25.4 microns or 0.0254 mm.
1.9.4.11 mm
The metric measurement for millimeter, 0.001 meter or one/one-thousandth of a meter.
1.9.4.12 MPI Gloss Levels
MPI system of defining gloss. Seven (7) gloss levels (G1 to G7) are generically defined under the Evaluation sections of the MPI Manuals.
Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss refers to G5, and Gloss refers to G6.
Gloss levels are defined by MPI as follows:
Gloss Description Units Units Level @ 60 degrees @ 85 degrees
G1 Matte or Flat 0 to 5 10 max G2 Velvet 0 to 10 10 to 35 G3 Eggshell 10 to 25 10 to 35 G4 Satin 20 to 35 35 min G5 Semi-Gloss 35 to 70 G6 Gloss 70 to 85 G7 High Gloss
Gloss is tested in accordance with ASTM D 523 . Historically, the Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and Gloss (G6).
SECTION 09 90 00 Page 9
1.9.4.13 MPI System Number
The MPI coating system number in each Division found in either the MPI Architectural Painting Specification Manual or the Maintenance Repainting Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN).
The Division number follows the CSI Master Format.
1.9.4.14 Paint
See Coating definition.
1.9.4.15 REX
MPI short term designation for an exterior coating system used in repainting projects or over existing coating systems.
1.9.4.16 RIN
MPI short term designation for an interior coating system used in repainting projects or over existing coating systems.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to the coating specifications and standards referenced in PART 3.
Submit manufacturer's technical data sheets for specified coatings and solvents. Comply with applicable regulations regarding toxic and hazardous materials.
PART 3 EXECUTION
3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED
Prior to surface preparation and coating applications, remove, mask, or otherwise protect, hardware, hardware accessories, machined surfaces, radiator covers, plates, lighting fixtures, public and private property, and other such items not to be coated that are in contact with surfaces to be coated. Following completion of painting, workmen skilled in the trades involved shall reinstall removed items. Restore surfaces contaminated by coating materials, to original condition and repair damaged items.
3.2 SURFACE PREPARATION
Remove dirt, splinters, loose particles, grease, oil, and other foreign matter and substances deleterious to coating performance as specified for each substrate before application of paint or surface treatments. Oil and grease shall be removed prior to mechanical cleaning. Cleaning shall be programmed so that dust and other contaminants will not fall on wet, newly painted surfaces. Exposed ferrous metals such as nail heads on or in contact with surfaces to be painted with water-thinned paints, shall be spot-primed with a suitable corrosion-inhibitive primer capable of preventing flash rusting and compatible with the coating specified for the adjacent areas.
SECTION 09 90 00 Page 10
3.2.1 Additional Requirements for Preparation of Surfaces With Existing Coatings
Before application of coatings, perform the following on surfaces covered by soundly-adhered coatings, defined as those which cannot be removed with a putty knife:
b. Wipe previously painted surfaces to receive solvent-based coatings, except stucco and similarly rough surfaces clean with a clean, dry cloth saturated with mineral spirits, ASTM D 235 .
Allow surface to dry. Wiping shall immediately precede the application of the first coat of any coating, unless specified otherwise.
c. Sand existing glossy surfaces to be painted to reduce gloss.
Brush, and wipe clean with a damp cloth to remove dust.
d. The requirements specified are minimum. Comply also with the application instructions of the paint manufacturer.
e. Previously painted surfaces damaged during construction shall be thoroughly cleaned of all grease, dirt, dust or other foreign matter.
f. Blistering, cracking, flaking and peeling or other deteriorated coatings shall be removed.
g. Chalk shall be removed so that when tested in accordance with ASTM D 4214, the chalk resistance rating is no less than 8.
h. Slick surfaces shall be roughened. Damaged areas such as, but not limited to, nail holes, cracks, chips, and spalls shall be repaired with suitable material to match adjacent undamaged areas.
i. Edges of chipped paint shall be feather edged and sanded smooth.
j. Rusty metal surfaces shall be cleaned as per SSPC requirements.
Solvent, mechanical, or chemical cleaning methods shall be used to provide surfaces suitable for painting.
k. New, proposed coatings shall be compatible with existing coatings.
3.2.2 Existing Coated Surfaces with Minor Defects
Sand, spackle, and treat minor defects to render them smooth. Minor defects are defined as scratches, nicks, cracks, gouges, spalls, alligatoring, chalking, and irregularities due to partial peeling of previous coatings. Remove chalking by sanding so that when tested in accordance with ASTM D 4214 , the chalk rating is not less than 8. 3.2.3
Removal of Existing Coatings
Remove existing coatings from the following surfaces:
a. Surfaces containing large areas of minor defects;
b. Surfaces containing more than 20 percent peeling area; and
SECTION 09 90 00 Page 11
c. Surfaces designated by the Contracting Officer, such as surfaces where rust shows through existing coatings. 3.2.4 Substrate Repair
a. Repair substrate surface damaged during coating removal;
b. Sand edges of adjacent soundly-adhered existing coatings so they are tapered as smooth as practical to areas involved with coating removal; and
c. Clean and prime the substrate as specified. 3.3 PREPARATION OF
METAL SURFACES
3.3.1 Existing andNew Ferrous Surfaces
a. Ferrous Surfaces including Shop-coated Surfaces and Small Areas That Contain Rust, Mill Scale and Other Foreign Substances:
Solvent clean in accordance with SSPC SP 1 to remove oil and grease. Where shop coat is missing or damaged, clean according to , SSPC SP 6 . Shop-coated ferrous surfaces shall be protected from corrosion by treating and touching up corroded areas immediately upon detection.
b. Surfaces With More Than 20 Percent Rust, Mill Scale, and Other Foreign Substances: Clean entire surface in accordance with
SSPC SP 6 / SSPC SP 12 WJ-3
3.3.2 Final Ferrous Surface Condition:
For tool cleaned surfaces, the requirements are stated in SSPC SP 2 and SSPC SP 3 . As a visual reference, cleaned surfaces shall be similar to photographs in SSPC VIS 3 .
For abrasive blast cleaned surfaces, the requirements are stated in SSPC SP 7 , SSPC SP 6 , and SSPC SP 10 . As a visual reference, cleaned surfaces shall be similar to photographs in SSPC VIS 1 .
3.3.3 Galvanized Surfaces
a. New or Existing Galvanized Surfaces With Only Dirt and Zinc Oxidation Products: Clean with solvent, in accordance with SSPC SP 1 . If the galvanized metal has been passivated or stabilized, the coating shall be completely removed by brush-off abrasive blast. New galvanized steel to be coated shall not be "passivated" or "stabilized" If the absence of hexavalent stain inhibitors is not documented, test as described in ASTM D 2092 , Appendix X2, and remove by one of the methods described therein.
3.3.4 Non-Ferrous Metallic Surfaces
Aluminum and aluminum-alloy, lead, copper, and other nonferrous metal surfaces.
a. Surface Cleaning: Solvent clean in accordance with SSPC SP 1 and wash with mild non-alkaline detergent to remove dirt and water soluble contaminants.
3.3.5 Terne-Coated Metal Surfaces
Solvent clean surfaces with mineral spirits, ASTM D 235 . Wipe dry with
SECTION 09 90 00 Page 12 clean, dry cloths.
3.4 PREPARATION OF CONCRETE AND CEMENTITIOUS SURFACE
3.4.1 Concrete and Masonry
a. Curing: Concrete, stucco and masonry surfaces shall be allowed to cure at least 30 days before painting, except concrete slab on grade, which shall be allowed to cure 90 days before painting.
b. Surface Cleaning: Remove the following deleterious substances.
(1) Dirt, Chalking, Grease, and Oil: Wash new surfaces with a solution composed of 1/2 cup trisodium phosphate, 1/4 cuphousehold detergent, and 4 quarts of warm water. Then rinse thoroughly with fresh water. For large areas, water blasting may be used.
(2) Fungus and Mold: Wash new surfaces with a solution composed of 1/2 cup trisodium phosphate, 1/4 cup household detergent, 1 quart 5 percent sodium hypochlorite solution and 3 quarts of warm water. Rinse thoroughly with fresh water.
(3) Paint and Loose Particles: Remove by wire brushing.
(4) Efflorescence: Remove by scraping or wire brushing followed by washing with a 5 to 10 percent by weight aqueous solution of hydrochloric (muriatic) acid. Do not allow acid to remain on the surface for more than five minutes before rinsing with fresh water. Do not acid clean more than 4 square feet of surface, per workman, at one time.
c. Cosmetic Repair of Minor Defects: Repair or fill mortar joints and minor defects, including but not limited to spalls, in accordance with manufacturer's recommendations and prior to coating application.
d. Allowable Moisture Content: Latex coatings may be applied to damp surfaces, but not to surfaces with droplets of water. Do not apply epoxies to damp vertical surfaces as determined by ASTM D 4263 or horizontal surfaces that exceed 3 lbs of moisture per 1000 square feet in 24 hours as determined by ASTM F 1869 . In all cases follow manufacturers recommendations. Allow surfaces to cure a minimum of 30 days before painting.
3.4.2 Gypsum Board, Plaster, and Stucco
a. Surface Cleaning: Plaster and stucco shall be clean and free from loose matter; gypsum board shall be dry. Remove loose dirt and dust by brushing with a soft brush, rubbing with a dry cloth, or vacuum-cleaning prior to application of the first coat material.
A damp cloth or sponge may be used if paint will be water-based.
b. Repair of Minor Defects: Prior to painting, repair joints, cracks, holes, surface irregularities, and other minor defects with patching plaster or spackling compound and sand smooth.
c. Allowable Moisture Content: Latex coatings may be applied to damp surfaces, but not surfaces with droplets of water. Do not apply epoxies to damp surfaces as determined by ASTM D 4263 . New
SECTION 09 90 00 Page 13 plaster to be coated shall have a maximum moisture content of 8 percent, when measured in accordance with ASTM D 4444 , Method A, unless otherwise authorized. In addition to moisture content requirements, allow new plaster to age a minimum of 30 days before preparation for painting.
3.5 APPLICATION
3.5.1 Coating Application
Painting practices shall comply with applicable federal, state and local laws enacted to insure compliance with Federal Clean Air Standards. Apply coating materials in accordance with SSPC PA 1 . SSPC PA 1 methods are applicable to all substrates, except as modified herein.
At the time of application, paint shall show no signs of deterioration.
Uniform suspension of pigments shall be maintained during application.
Unless otherwise specified or recommended by the paint manufacturer, paint may be applied by brush, roller, or spray. Use trigger operated spray nozzles for water hoses. Rollers for applying paints and enamels shall be of a type designed for the coating to be applied and the surface to be coated. Wear protective clothing and respirators when applying oil-based paints or using spray equipment with any paints.
Paints, except water-thinned types, shall be applied only to surfaces that are completely free of moisture as determined by sight or touch.
Thoroughly work coating materials into joints, crevices, and open spaces.
Special attention shall be given to insure that all edges, corners, crevices, welds, and rivets receive a film thickness equal to that of adjacent painted surfaces.
Each coat of paint shall be applied so dry film shall be of uniform thickness and free from runs, drops, ridges, waves, pinholes or other voids, laps, brush marks, and variations in color, texture, and finish.
Hiding shall be complete.
Touch up damaged coatings before applying subsequent coats. Interior areas shall be broom clean and dust free before and during the application of coating material.
a. Drying Time: Allow time between coats, as recommended by the coating manufacturer, to permit thorough drying, but not to present topcoat adhesion problems. Provide each coat in specified condition to receive next coat.
b. Primers, and Intermediate Coats: Do not allow primers or intermediate coats to dry more than 30 days, or longer than recommended by manufacturer, before applying subsequent coats.
Follow manufacturer's recommendations for surface preparation if primers or intermediate coats are allowed to dry longer than recommended by manufacturers of subsequent coatings. Each coat shall cover surface of preceding coat or surface completely, and there shall be a visually perceptible difference in shades of successive coats.
c. Finished Surfaces: Provide finished surfaces free from runs, drops, ridges, waves, laps, brush marks, and variations in colors.
SECTION 09 90 00 Page 14
3.5.2 Mixing and Thinning of Paints
Reduce paints to proper consistency by adding fresh paint, except when thinning is mandatory to suit surface, temperature, weather conditions, application methods, or for the type of paint being used. Obtain written permission from the Contracting Officer to use thinners. The written permission shall include quantities and types of thinners to use.
When thinning is allowed, paints shall be thinned immediately prior to application with not more than 1 pint of suitable thinner per gallon. The use of thinner shall not relieve the Contractor from obtaining complete hiding, full film thickness, or required gloss. Thinning shall not cause the paint to exceed limits on volatile organic compounds. Paints of different manufacturers shall not be mixed.
3.5.3 Two-Component Systems
Two-component systems shall be mixed in accordance with manufacturer's instructions. Any thinning of the first coat to ensure proper penetration and sealing shall be as recommended by the manufacturer for each type of substrate.
3.5.4 Coating Systems
a. Systems by Substrates: Apply coatings that conform to the respective specifications listed in the following Tables:
Table Division 5. Exterior Metal, Ferrous and Non-Ferrous Paint Table Division 4. Interior Concrete Masonry Units Paint Table Division 5. Interior Metal, Ferrous and Non-Ferrous Paint Table
Division 9: Interior Gypsum Board Paint Table
b. Minimum Dry Film Thickness (DFT): Apply paints, primers, varnishes, enamels, undercoats, and other coatings to a minimum dry film thickness of 1.5 mil each coat unless specified otherwise in the Tables. Coating thickness where specified, refers to the minimum dry film thickness.
c. Coatings for Surfaces Not Specified Otherwise: Coat surfaces which have not been specified, the same as surfaces having similar conditions of exposure.
d. Existing Surfaces Damaged During Performance of the Work, Including New Patches In Existing Surfaces: Coat surfaces with the following:
(1) One coat of primer.
(2) One coat of undercoat or intermediate coat.
(3) One topcoat to match adjacent surfaces.
3.6 COATING SYSTEMS FOR METAL
Apply coatings of Tables in Division 5 for Exterior and Interior.
SECTION 09 90 00 Page 15
a. Apply specified ferrous metal primer on the same day that surface is cleaned, to surfaces that meet all specified surface preparation requirements at time of application.
b. Inaccessible Surfaces: Prior to erection, use one coat of specified primer on metal surfaces that will be inaccessible after erection.
c. Shop-primed Surfaces: Touch up exposed substrates and damaged coatings to protect from rusting prior to applying field primer.
e. Pipes and Tubing: The semitransparent film applied to some pipes and tubing at the mill is not to be considered a shop coat, but shall be overcoated with the specified ferrous-metal primer prior to application of finish coats.
f. Exposed Nails, Screws, Fasteners, and Miscellaneous Ferrous Surfaces. On surfaces to be coated with water thinned coatings, spot prime exposed nails and other ferrous metal with latex primer
MPI 107 .
3.7 COATING SYSTEMS FOR WOOD AND PLYWOOD
a. Apply coatings of Tables in Division 6 for Interior.
b. Prior to erection, apply two coats of specified primer to treat and prime wood and plywood surfaces which will be inaccessible after erection.
c. Apply stains in accordance with manufacturer's printed instructions.
3.8 INSPECTION AND ACCEPTANCE
In addition to meeting previously specified requirements, demonstrate mobility of moving components, including swinging and sliding doors, cabinets, and windows with operable sash, for inspection by the Contracting Officer. Perform this demonstration after appropriate curing and drying times of coatings have elapsed and prior to invoicing for final payment.
3.9 WASTE MANAGEMENT
As specified in the Waste Management Plan and as follows. Do not use kerosene or any such organic solvents to clean up water based paints.
Properly dispose of paints or solvents in designated containers. Close and seal partially used containers of paint to maintain quality as necessary for reuse. Store in protected, well-ventilated, fire-safe area at moderate temperature. Place materials defined as hazardous or toxic waste in designated containers. Set aside extra paint for future color matches or reuse by the Government.
3.10 PAINT TABLES
All DFT's are minimum values. Use only materials with a GPS green check mark having a minimum MPI "Environmentally Friendly" E3 rating based on VOC ( EPA Method 24 ) content levels. Acceptable products are listed in the MPI Green Approved Products List, available at http://www.specifygreen.com/APL/ProductIdxByMPInum.asp .
SECTION 09 90 00 Page 16
3.10.1 EXTERIOR PAINT TABLES
DIVISION 5: EXTERIOR METAL, FERROUS AND NON-FERROUS PAINT TABLE
STEEL / FERROUS SURFACES
D. New and existingsteel blast cleaned to SSPC SP 10 :
1. Waterborne Light Industrial MPI EXT 5.1R-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 101 MPI 108 MPI 163
System DFT: 8.5 mils
EXTERIOR GALVANIZED SURFACES
F. New Galvanized surfaces:
3. Waterborne Primer / Waterborne Light Industrial Coating MPI EXT 5.3J-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 134 MPI 163 MPI 163
System DFT: 4.5 mils
G. Galvanized surfaces with slight coating deterioration; little or no rusting:
1. Waterborne Light Industrial Coating MPI REX 5.3J-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 134 N/A MPI 163
System DFT: 4.5 mils
3.10.2 [Enter Appropriate Subpart Title Here] DIVISION 4: INTERIOR
CONCRETE MASONRY UNITS PAINT TABLE
A. New and uncoated Existing Concrete masonry:
1.
MPI INT 4.2D-G3 (Eggshell) Filler Primer: Intermediate: Topcoat:
MPI 4 N/A MPI 139 MPI 139
System DFT: 11 mils B. Existing, previously painted Concrete masonry:
MPI RIN 4.2K-G3 (Eggshell) Spot Primer: Intermediate: Topcoat:
MPI 50 MPI 139 MPI 139
System DFT: 4.5 mils
DIVISION 5: INTERIOR METAL, FERROUS AND NON-FERROUS PAINT TABLE
INTERIOR STEEL / FERROUS SURFACES
A. Metal, Mechanical, Electrical, Fire extinguishing sprinkler systems including valves, conduit, hangers, supports,Surfaces adjacent to painted surfaces (Match surrounding finish), and miscellaneous metal items not otherwise specified except floors, hot metal surfaces, and new prefinished equipment:
SECTION 09 90 00 Page 17
INTERIOR STEEL / FERROUS SURFACES
1. High Performance Architectural Latex
MPI INT 5.1R-G3 (Eggshell) Primer: Intermediate: Topcoat:
MPI 79 MPI 139 MPI 139
System DFT: 5 mils
MPI INT 5.1R-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 79 MPI 141 MPI 141
System DFT: 5 mils
C. Metal in high-humidity areas not otherwise specified except floors, hot metal surfaces, and new prefinished equipment:
1.Alkyd
MPI INT 5.1E-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 79 MPI 47 MPI 47
System DFT: 5.25 mils
E. Miscellaneous non-ferrous metal items not otherwise specified:
1. High Performance Architectural Latex
MPI INT 5.4F-G5 (Semigloss) Primer: Intermediate: Topcoat:
MPI 95 MPI 141 MPI 141
System DFT: 5 mils
DIVISION 9: INTERIOR PLASTER, GYPSUM BOARD, TEXTURED SURFACES PAINT
TABLE
A. New and Existing, previously painted Wallboard not otherwise specified:
3. Institutional Low Odor / Low VOC Latex New; MPI INT 9.2M-G2 (Flat) / Existing; MPI RIN 9.2M-G2 (Flat) Primer: Intermediate: Topcoat:
MPI 50 MPI 144 MPI 144
System DFT: 4 mils
New; MPI INT 9.2M-G3 (Eggshell) / Existing; MPI RIN 9.2M-G3 (Eggshell) Primer: Intermediate: Topcoat:
MPI 50 MPI 145 MPI 145
System DFT: 4 mils
B. New Wallboard in restrooms,high humidity areas not otherwise specified.:
3. Epoxy New; MPI INT 9.2E-G6 (Gloss) / Existing; MPI RIN 9.2D-G6 (Gloss) Primer: Intermediate: Topcoat:
SECTION 09 90 00 Page 18
DIVISION 9: INTERIOR PLASTER, GYPSUM BOARD, TEXTURED SURFACES PAINT TABLE
MPI 50 MPI 77 MPI 77
System DFT: 4 mils
SECTION 09 90 00 Page 19
SECTION 04 20 00
UNIT MASONRY
05/25
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONCRETE INSTITUTE (ACI)
ACI SP-66 (2004) ACI Detailing Manual
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2023) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A185/A185M (2007) Standard Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
ASTM A615/A615M (2024) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A641/A641M (2019; R 2025) Standard Specification for Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A653/A653M (2025) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A951/A951M (2011) Standard Specification for Steel Wire for Masonry Joint Reinforcement
ASTM A996/A996M (2016) Standard Specification for Rail-Steel and Axle-Steel Deformed Bars for Concrete Reinforcement
ASTM A1008/A1008M (2024) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A1064/A1064M (2024) Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete
ASTM C90 (2024a) Standard Specification for
SECTION 04 20 00 Page 1
Loadbearing Concrete Masonry Units
ASTM C129 (2025) Standard Specification for Dry-Cast Nonloadbearing Concrete Masonry Units
ASTM C207 (2024) Standard Specification for Hydrated Lime for Masonry Purposes
ASTM C270 (2025a) Standard Specification for Mortar for Unit Masonry
ASTM C476 (2023) Standard Specification for Grout for Masonry
ASTM C494/C494M (2024) Standard Specification for Chemical Admixtures for Concrete
ASTM C641 (2023) Standard Test Method for Iron Staining Materials in Lightweight Concrete Aggregates
ASTM C780 (2025a) Standard Test Methods for…