Exhibit F--Beatty Health Center--Electrical COMcheck--2026-09-05.pdf

PDF 607 KB Posted

Attached to
RFP-KTHFS-2026-002 - Beatty Health Center Project
Solicitation number
S-Q10089-00017927
Issued by
Oregon

About this file

This is an Electrical Compliance Certificate report prepared for the Klamath Tribal Health Center in Beatty, Oregon, a new construction healthcare facility project. The document demonstrates compliance with the 90.1 (2022) Standard energy code for a single-floor clinic building with a total area of 4,065 square feet located at 24110 Godowa Springs Road, Beatty, Oregon 97621. The project is owned by Jordan Arredondo and designed by Steele Associates (2738 NW Potts Ct, Bend, Oregon 97703). The compliance certificate addresses three primary areas: interior lighting, exterior lighting, and electrical systems through an inspection checklist covering plan review, rough-in electrical inspection, and final inspection requirements. The interior lighting design exceeds code requirements by 67%, with proposed watts of 1,802 against an allowed 5,406 watts, utilizing LED fixtures with local control and automatic full-off capabilities at 50% efficiency. The exterior lighting design exceeds code requirements by 50%, with proposed tradable watts of 200 against an allowed 565.6 watts, also employing LED fixtures with daylight shutoff controls.

The project achieved 47.0 energy credits against a requirement of 41.8 credits through measures including occupancy sensor controls, reduced lighting power, cooling and heating efficiency improvements, energy monitoring, and efficient kitchen equipment provisions. The electrical engineer Kennedy Davidson certified the design on September 4, 2026, confirming consistency with building plans and specifications. All inspection checklist requirements are marked as compliant or not applicable, including mandatory provisions for receptacle controls, energy measurement devices, automatic lighting controls, and as-built documentation delivery within 90 days of system acceptance. The compliance documentation confirms that proposed electrical systems and lighting installations meet or exceed all applicable energy code standards and mandatory requirements.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 1 of 10

Compliance Certificate

Project Information

Energy Code:

Project Title:

Location:

Climate Zone:

Project Type:

Project No:

Performance Sim. Specs:

Project Sub Type:

All Electric:

Is Renewable:

Has Battery:

Has Charger:

Has Heat Pump

90.1 (2022) Standard Klamath Tribal Health Chiloquin, Oregon 5b New Construction 162136 EnergyPlus 24.1.0 (EPW: TBD) New Building/Complete false false false false false

Construction Site: Owner/Agent: Designer/Contractor:

24110 Godowa Springs Rd Beatty , Oregon 97621

Jordan Arredondo Steele Associates 2738 NW Potts Ct Bend , Oregon 97703

Notes:

Energy Credits

Description Credit

L03 Occupancy Sensor Control Areas 1.0

L06 Reduced lighting power 18.0

H03 5% cooling efficiency improvement 16.4

H02 5% heating efficiency improvement 3.4

P01 Energy monitoring 3.0

Q02 Efficient kitchen equipment 0.0

G01 Lighting Load Management 0.0

G02 HVAC Load Management 0.0

W05 Point of Use Water Heater 0.0

E01 Improved Envelope Performance 0.0

Credits: 47.0 Required 41.8 Proposed

Renewable energy

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 2 of 10

Number of Floors:

Area of Three Largest Floors:

Proposed Capacity:

Required Capacity:

Exception:

Building effective floor area is less than 10,000 ft2.

Renewables Pass: Exception: Building effective floor area is less than 10,000 ft2.

Building Area

Description Floor Area

1-Health Care-Clinic (Health Care-Clinic) : Nonresidential 4065

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 3 of 10

Interior Lighting Compliance Certificate

Project Information

Energy Code:

Project Title:

Location:

Climate Zone:

Project Type:

90.1 (2022) Standard Klamath Tribal Health Chiloquin, Oregon 5b New Construction

Construction Site: Owner/Agent: Designer/Contractor:

24110 Godowa Springs Rd Beatty , Oregon 97621

Jordan Arredondo Steele Associates 2738 NW Potts Ct Bend , Oregon 97703

Allowed Interior Lighting Power

A B C D

Area Category Floor Area (ft2) Allowed Watts / ft2 Allowed Watts

1-Health Care-Clinic (Healthcare Facility:Exam/Treatment) 4065 1.33 5406

Total Allowed Watts: 5406

Proposed Interior Lighting Power

A B C D

Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast

# of Fixture Fixture Watt. (B X C)

1-Health Care-Clinic (Healthcare Facility:Exam/Treatment)

RD4: RD4: LED: 6 15 90

RT1: RT1: LED: 51 32 1632

S1: S1: LED: 2 40 80

Total Proposed Watts: 1802

Proposed Interior Lighting Controls

Fixture Lighting Control

1-Health Care-Clinic (Healthcare Facility:Exam/Treatment)

RD4: RD4: LED: Local Control, Restricted Manual On, Auto Full Off(50%)

RT1: RT1: LED: Local Control, Restricted Manual On, Auto Full Off(50%)

S1: S1: LED: Local Control, Restricted Manual On, Auto Full Off(50%)

Interior Lighting PASSES: Design 67% better than code

Interior Lighting Compliance Statement

Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 90.1 (2022) Standard

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 4 of 10 requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.

Name - Title Signature Date

Kennedy Davidson - Electrical Engineer 9/4/26

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 5 of 10

Exterior Lighting Compliance Certificate

Project Information

Energy Code:

Project Title:

Location:

Climate Zone:

Project Type:

Exterior Lighting Zone:

90.1 (2022) Standard Klamath Tribal Health Chiloquin, Oregon 5b New Construction Residential mixed use area (LZ2)

Construction Site: Owner/Agent: Designer/Contractor:

24110 Godowa Springs Rd Beatty , Oregon 97621

Jordan Arredondo Steele Associates 2738 NW Potts Ct Bend , Oregon 97703

Allowed Exterior Lighting Power

A B C D E

Area/Surface Category Quantity Allowed Watts / ft2 Tradable Wattage

Allowed Watts (B X C)

Ext Area (Pedestrian and vehicular entrances and exits)

12 ft of door width

9.80 No 117.60000000000001

EXTERIOR WALL (Illuminated length of facade wall or surface)

70 ft 2.40 No 168.0

Total Tradable Watts (a): 117.6

Base Site Allowance (b): 280

Total Allowed Watts: 565.6

(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.

(b) A base site allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.

Proposed Exterior Lighting Power

A B C D

Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast

# of Fixture Fixture Watt. (B X C)

Ext Area (Pedestrian and vehicular entrances and exits, 12 ft of door width): Tradeable Wattage

WP1: WP1: LED: 4 50 200

EXTERIOR WALL (Illuminated length of facade wall or surface, 70 ft): Tradeable Wattage

WP1: WP1: LED: 3 50 150

Total Tradable Proposed Watts: 200

Proposed Exterior Lighting Controls

Fixture Lighting Control

Ext Area (Pedestrian and vehicular entrances and exits, 12 ft of door width)

WP1: WP1: LED: Daylight Shutoff, Facade or Landscape

EXTERIOR WALL (Illuminated length of facade wall or surface, 70 ft)

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 6 of 10

Fixture Lighting Control

WP1: WP1: LED: Daylight Shutoff, Facade or Landscape

Exterior Lighting PASSES: Design 50% better than code

Exterior Lighting Compliance Statement

Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been designed to meet the 90.1 (2022) Standard requirements in COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist.

Name - Title Signature Date

Kennedy Davidson - Electrical Engineer 9/4/26

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 7 of 10

Inspection Checklist

Energy Code: 90.1 (2022) Standard

Requirements: 73% were addressed directly in the COMcheck software

Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.

Plan Review

Section # & Req.ID Plan Review Complies? Comments/Assumptions

4.2.2, 8.4.1.1, 8.4.1.2, 8.7

[PR6]2

Plans, specifications, and/or calculations provide all information with which compliance can be determined for the electrical systems and equipment and document where exceptions are claimed. Feeder connectors sized in accordance with approved plans and branch circuits sized for maximum drop of 3%.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: TBD

4.2.2, 9.4.3,

9.7 [PR4]1

Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: LIGHTING PLAN

9.7 [PR8]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the exterior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include exterior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: LIGHTING PLAN

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 8 of 10

Rough-In Electrical Inspection

Section

& Req.ID Rough-In Electrical Inspection Complies? Comments/Assumptions

8.4.2

[EL10]2

At least 50% of all 125 volt 15- and 20-Amp receptacles are controlled by an automatic control device.

Complies

Does Not Comply

Not Observable

Not Applicable

Exception: Receptacles intended for 24 hour operation of equipment.

Location on plans/spec: TBD

8.4.3

[EL11]2

New buildings have electrical energy use measurement devices installed. Where tenant spaces exist, each tenant is monitored separately. In buildings with a digital control system the energy use is transmitted to to control system and displayed graphically.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: TBD

9.5.2.2

[EL8]1

Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: LIGHTING PLAN

9.4.1.1

[EL1]2

Automatic control requirements prescribed in Table 9.6.1, for the appropriate space type, are installed. Mandatory lighting controls (labeled as 'REQ') and optional choice controls (labeled as 'ADD1' and 'ADD2') are implemented.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: LIGHTING PLAN

9.4.1.1

[EL2]2

Independent lighting controls installed per approved lighting plans and all manual controls readily accessible and visible to occupants.

Complies

Does Not Comply

Not Observable

Not Applicable

Exception: Remote locations permitted for safety or security if used with a clearly labeled indicator pilot light.

Location on plans/spec: LIGHTING PLAN

9.4.1.1f

[EL13]1

Daylight areas under skylights and roof monitors that have more than 150 W combined input power for general lighting are controlled by photocontrols.

Complies

Does Not Comply

Not Observable

Not Applicable

Exception: Requirement does not apply.

9.4.1.4

[EL3]2

Automatic lighting controls for exterior lighting installed according to Section 9.4.1.4.

Complies

Does Not Comply

Not Observable

Not Applicable

9.4.1.3

[EL4]1

Separate lighting control devices for specific uses installed per approved lighting plans.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: LIGHTING PLAN

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 9 of 10

Final Inspection

Section

& Req.ID Final Inspection Complies? Comments/Assumptions

8.7.3.1

[FI16]3

Furnished as-built drawings for electric power systems within 90 days of system acceptance.

Complies

Does Not Comply

Not Observable

Not Applicable

8.7.3.2

[FI17]3

Furnished O&M instructions for systems and equipment to the building owner or designated representative.

Complies

Does Not Comply

Not Observable

Not Applicable

9.2.2.1

[FI18]1

Interior installed lamp and fixture lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts.

Complies

Does Not Comply

Not Observable

Not Applicable

See the Interior Lighting fixture schedule for values

9.4.2

[FI19]1

Exterior lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts.

Complies

Does Not Comply

Not Observable

Not Applicable

See the Exterior Lighting fixture schedule for values

11.5.2.3.3a

[FI55]2

W05: Point of Use Water Heater energy credit measure requires hot water to be supplied from localized source without recirculation or heat trace. Pipe insulation according to Table 6.8.3- 1 and volume of water in piping limited to 2 oz for nonresidential lavatories or 0.25 oz for all other plumbing fixtures.

Complies

Does Not Comply

Not Observable

Not Applicable

See the Mechanical Systems list for values

11.5.2.4

[FI60]2

P01: Energy Monitoring energy credit measure requires projects that are not required to have electrical energy monitoring systems installed shall be equipped to measure, monitor, record, and report energy consumption data in compliance with Section 8.4.3.

Complies

Does Not Comply

Not Observable

Not Applicable

11.5.2.5.3

[FI62]2

L03: Occupancy Sensors Control Areas energy credit measure requires buildings use “Simplified Building Method Compliance Path,” or in spaces where automatic partial OFF or automatic full OFF is not required, it shall be installed in accordance with Section 11.5.2.5.3.

Complies

Does Not Comply

Not Observable

Not Applicable

See the Interior Lighting fixture schedule for values Location on plans/spec: TBD

11.5.2.7.2

[FI67]2

Q02: Efficient Kitchen Equipment energy credit measure requires buildings with a commercial kitchen with at least one gas or electric fryer and all other cooking appliances comply with Section 11.5.2.7.2.

Complies

Does Not Comply

Not Observable

Not Applicable

Location on plans/spec: TBD

11.5.2.8.1

[FI69]2

G01: Lighting Load Management energy credit measure requires luminaires have dimming capability and load management controls reduce general lighting power with continuous dimming in 75% of the project area during peakprice periods coincident with high building load.

Complies

Does Not Comply

Not Observable

Not Applicable

Energy credit params: Percentage lighting load management (in %): 0.0

11.5.2.8.2

[FI70]2

G02: HVAC Load Management energy credit measure requires load management shall a) increase cooling set point > 3F or reduce cooling capacity to 60% of installed capacity;

b) for electric heating, reduce heating set point > 3F or reduce heating capacity to 60% of installed capacity; and c) provide excess outdoor air and reduce outdoor air in accordance with ASHRAE Standard 62.1, Section 6.2.5.2.

Complies

Does Not Comply

Not Observable

Not Applicable

Report Title: Klamath Tribal Health Report Date: Sep 03, 2026, 04:32 PM (PDT) 10 of 10

File details come from the government source that posted it. Updated .