Exhibit 02a4. VA CBOC IT Systems Specifications_v05.23.pdf
PDF 8 MB Posted
- Solicitation number
- 36C24W26R0017
- Issued by
-
Department of Veterans Affairs
About this file
This document is a technical specification and design template for Community Based Outpatient Clinic (CBOC) Inside Plant Information Transport Systems, developed by the Department of Veterans Affairs Office of Information and Technology. The specification (RLP No. 36C24W26R0017, Exhibit 02, Appendix A.4) provides comprehensive design standards for telecommunications infrastructure in VA healthcare facilities ranging from 1,000 to 25,000+ square feet.
The specification details telecommunications room configurations, equipment requirements, and cabling standards across multiple facility sizes. For facilities 1-3,000 sq ft, a standard 26U telecommunications enclosure is required; 3,001-6,000 sq ft requires a 1-rack TR (80 SF); 6,001-10,000 sq ft requires a 2-rack TR (100 SF); 10,001-25,000 sq ft requires a 3-rack TR (120 SF); and facilities exceeding 25,000 sq ft require additional TRs. Equipment specifications include Category 6A copper patch panels (48-port, angled), fiber distribution panels with OM4/OS1/OS2 multimode and single-mode fiber, and server cabinets (45U, 24"x48" nominal with square punched rails). Power distribution requires redundant A-side and B-side circuits with zone PDUs supporting 5KW per rack for 1-rack TRs up to 10KW for 4-rack configurations. The design mandates bonding per ANSI/TIA-607-D standards, with 6 AWG telecommunications equipment bonding conductors connecting to rack bonding busbars. Work area outlets must support minimum four Category 6A 8P8C outlets per location with T568B termination. The specification includes detailed floor plans, rack elevations, cable management requirements (wire mesh cable trays minimum 6"x12"), and HVAC cooling specifications (17,000 BTU per telecommunications rack minimum). All labeling must comply with ANSI/TIA/EIA-606C standards with black lettering on white background.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT:
DRAWING No:
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 1 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
COVER
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
DEVELOPED BY:
DATA CENTER AND INFRASTRUCTURE ENGINEERING
COMMUNITY BASED OUTPATIENT CLINIC (CBOC)
INSIDE PLANT
INFORMATION TRANSPORT SYSTEMS SPECIFICATIONS
RLP No. 36C24W26R0017 Exhibit 02, Appendix A.4
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 2 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
LEGEND
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
LEGEND
ELECTRICAL
NOTES
TYP
DETAIL NUMBER
TYPICAL THROUGHOUT THIS
SHEET
ELECTRICAL
BONDING BUSBAR
ARCHITECTURAL
TELECOMMUNICATIONS TELECOMMUNICATIONS
ARCHITECTURAL
DETAIL NUMBER#
TYP
DETAIL NUMBER
DETAIL NUMBER
TYPICAL THROUGHOUT THIS SHEET
40" TELECOMMUNICATIONS CABINET WITH HORIZONTAL CABLE
CUTOUTS AND APPROPRIATE CABLE MANAGEMENT
ACCESSORIES, SUPPORTING 5KW REDUNDANT
DEMO WALL
NEW WALL
MECHANICAL MECHANICAL
CHANGES TO DESIGN WILL REQUIRE A NEW COMPUTATIONAL FLUID
DYNAMICS (CFD) ANALYSIS TO BE PERFORMED
FLOORPLANS ARE NOT TO SCALE
DOCUMENTS ARE NOT TO BE USED FOR CONSTRUCTION
COLD AISLE CONTAINMENT (PVC CURTAIN)
1 SERVICE PROVIDER ENTRANCE POINT
SERVICE BACKBONE (ENTRANCE ROOM-MAIN COMPUTER
ROOM)
MAIN CROSS CONNECT (CAMPUS/BUILDING DISTRIBUTOR) –
BACKBONE CABLING (MCR-TELECOMMUNCIATIONS ROOMS)
ENTRANCE ROOM (TR) INTERCONNECT
HORIZONTAL DISTRIBUTION TO WORK AREA OUTLETS (WAO)
ADDITIONAL CABINETS OR TELECOMMUNICATIONS RACKS TO
MEET REQUIREMENTS.
7 HORIZONTAL DISTRIBUTION AREA – SIDE A
8 HORIZONTAL DISTRIBUTION AREA – SIDE B
9 MAIN DISTRIBUTION AREA – SIDE A
10 MAIN DISTRIBUTION AREA – SIDE B
STANDARD DENSITY CABINET SUPPORTING 5KW
REDUNDANT
12 HIGH DENSITY CABINET SUPPORTING 10KW REDUNDANT
WIRE MESH CABLE TRAY MINIMUM OF 6"X 12" WITH SECOND
LEVEL OF FIBER CHANNEL PATHWAY (4" X 4")
BLUE CABLE TRAY PATH FOR CABLES TO THE A-SIDE MDA/
HDA
YELLOW CABLE TRAY PATH FOR CABLES TO THE B-SIDE MDA/
HDA
17 TELECOMMUNICATIONS CHANNEL RACK
SECONDARY BONDING BUSBAR PLACEMENT DETERMINED BY
OTHERS
PRIMARY BONDING BUSBAR PLACEMENT DETERMINED BY
OTHERS
MINIMUM TWO 110V 20A CONVENIENCE BUILDING POWER
OUTLETS PER WALL; PLACEMENT DETERMINED BY OTHERS. 1
30 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE
(L21-30R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE
INSTALLATION LOCATION WITH TELECOMMUNICATIONS
CONTRACTOR
20 AMP 208 VOLT THREE-PHASE TWIST LOCK RECEPTACLE (L21-
20R);8.5 FT AFF {WYE (5-WIRE)} COORDINATE INSTALLATION
LOCATION WITH TELECOMMUNICATIONS CONTRACTOR
SERVICE PANEL FOR B-SIDE POWER, GENERATOR BACKED IF
POSSIBLE. SHALL BE EQUIPPED WITH POWER METER; PLACEMENT
PER OTHERS
SERVICE PANEL FOR A-SIDE POWER, GENERATOR BACKED IF
THE FACILITY HAS GENERATION CAPABILITIES. SHALL BE
EQUIPPED WITH POWER METER; PLACEMENT PER OTHERS
1. LED LIGHTING PLACED IN AISLES DIRECTLY IN FRONT OF
AND BEHIND CABINET ROWS
2. LIGHTING OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION
3. 500 LUX IN THE HORIZONTAL PLANE AND 200 LUX IN THE
VERTICAL PLANE REQUIRED MEASURED AT 3 FT AFF IN
FRONT OF AND BEHIND EQUIPMENT CABINETS
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM A SIDE SOURCE
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT TEN [10] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM B SIDE SOURCE
WIRE MESH CABLE TRAY SIZE COMMENSURATE
WITH REQUIREMENTS
SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
CONDUIT WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND
INNERDUCT FOR FIBER
TELECOMMUNICATIONS CHANNEL RACK, 19" RAILS, #12-24
TAPPED EIA HOLE PATTERN, 30" DEEP CHANNEL MINIMUM, 7'
HIGH, 45RU, WHITE
VERTICAL CABLE MANAGER WITH DOOR, 6" WIDE MINIMUM
SERVER CABINET, 45U, 24"X48" (NOMINAL), SQUARE
PUNCHED RAIL, SINGLE PERFORATED FRONT DOOR, SOLID
REAR DOOR (VERTICAL EXHAUST DUCT IMPLEMENTATION),
DOUBLE PERFORATED REAR DOOR (NO VED), TWO-POINT
KEYED LOCKS, WHITE,SOLID SIDE PANELS
OR
TELECOMMUNICATIONS CABINET, 7' HIGH, 45U, 40"X48"
(NOMINAL), SQUARE PUNCHED RAIL, SINGLE
PERFORATED FRONT DOOR, SOLID REAR DOOR
(VERTICAL EXHAUST DUCT IMPLEMENTATION), TWO-
POINT KEYED LOCKS, WHITE,SOLID SIDE PANELS
OR WIRE MESH CABLE TRAY SIZE COMMENSURATE WITH
REQUIREMENTS
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT FIVE [5] SINGLE BREAKER 208V, 20 AMP, L21-20R
BUSWAY TAPS) FED FROM A SIDE SOURCE
POWER BUS BAR (VOLTAGE AND AMPERAGE SUFFICIENT TO
SUPPORT FIVE [5] 208V, 20 AMP, L21-20R BUSWAY TAPS) FED
FROM B SIDE SOURCE
BLUE CABLE PATH FOR A-SIDE UPS12
YELLOW CABLE PATH FOR B-SIDE UPS13
LIGHTING:
RETURN AIR DUCT
COMPUTER ROOM AIR CONDITIONER (SEE COMPUTATIONAL
FLUID DYNAMICS REPORT FOR SIZING)
REQUIRED CLEARANCE AROUND CRACS
ELECTRICAL SERVICE PANEL
OVERHEAD POWER DROP CORD WITH L21-20 RECEPTACLE
POWER BUSWAY TAP WITH SINGLE BREAKER 3' DROP
CORD WITH L21-20R FOR STANDARD-DENSITY CABINETS
POWER BUSWAY TAP WITH DUAL BREAKER AND TWO 3'
DROP CORDS WITH L21-20R FOR HIGH DENSITY CABINETS
TYPICAL UNSWITCHED 110 VOLT, 20 AMP DUPLEX
CONVENIENCE OUTLET
AC
SPLIT PACKAGE AIR CONDITIONER OR EQUIVALENT 24/7
SUPPLY AIR TO REJECT 5KW (17,000 BTU PER
TELECOMMUNICATIONS RACK)
AC
ADDITIONAL SPLIT PACKAGE AIR CONDITIONER OR LARGER
UNIT TO REJECT HEAT FROM ADDITIONAL RACKS (17,000
BTU PER TELECOMMUNICATIONS RACK)
4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT FOR SERVICE PROVIDER / SECURITY /
VIDEO / ET CETERA
3 FT WIDE, 8 FT HIGH DOOR, FIRE RESISTANT TO ¾ HOUR OR
MORE PER AHJ
6 FT WIDE, 8 FT HIGH DOOR, NO CENTER MULLION, FIRE
RESISTANT TO ¾ HOUR OR MORE PER AHJ
STANDARD 25% OPEN PERFORATED FLOOR TILE
C R
A C
MODULAR UPS CABINET (POWER MODULES, BATTERIES,
POWER PANELS)
LED LIGHTING
POWER BUSWAY WITH METERED HEADEND FOR B SIDE
POWER DISTRIBUTION
POWER BUSWAY WITH METERED HEADEND FOR A SIDE
POWER DISTRIBUTION
C FIXED CAMERA, PAN/TILT/ZOOM, PASSIVE INFRARED
CAMERA - DUAL TECHNOLOGY”
PIV ENABLED TWO-FACTOR AUTHENTICATION KEYPAD
M
CEILING MOUNTED MOTION SENSOR (LOCATIONS AS
REQUIRED FOR FULL ROOM COVERAGE)
MOTION SENSOR LIGHT SWITCH
J
OVERHEAD POWER DROP CORD WITH L21-30 RECEPTACLE
POWER JUNCTION BOX FOR 60A CONNECTION
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 3 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
SPECIFICATIONS
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
GENERIC TELECOMMUNICATIONS MEDIA AND INTERFACE SPECIFICATIONS FOR TELECOMMUNICATION SPACES
SPECIFICATIONPRIMARY ATTRIBUTEID SECONDARY ATTRIBUTE
1 COPPER PATCH PANELS
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE)
POSITION COUNT 48
FORM FACTOR ANGLED
SIZE ONE RACK UNIT (RU)
JACK COLOR CODING
A-SIDE BLUE / B-SIDE YELLOW FOR DUAL PATH DISTRO WITHIN COMPUTER ROOMS
(DATA CENTERS); UTP DISTRO TO WAOS IS EXCLUDED
CASSETTE CAPACITY 12 CASSETTES OR 6 DOUBLE CASSETTES
CASSETTE USER INTERFACES LC DUPLEX CONNECTORS / MPO-8
FIBER DISTRIBUTION PANELS CASSETTE BACKBONE INTERFACES MPO-24/ MPO-12
PERFORMANCE CHARACTERISTICS
OM4 LASER OPTIMIZED 50/125 MULTIMODE (MM) / OS1(OS2) 9/125 SINGLE MODE
(SM)
FORM FACTOR ONE RU
3 UNSHIELDED TWISTED PAIR (UTP) (HORIZONTAL AND FIRST LEVEL BACKBONE)
PERFORMANCE CATEGORY CATEGORY 6A (10 GBE); 24-26 GAUGE
PERFORMANCE SPECIFICATIONS MEETS OR EXCEEDS TIA-EIA-568-C.2-10, TSB-155.
PERFORMANCE CATEGORY OM4 LASER OPTIMIZED / OS1 / OS2
PERFORMANCE SPECIFICATIONS
LASER OPTIMIZED 50/125 MM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /
OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)
FIBER (HORIZONTAL AND FIRST LEVEL BACKBONE)
MODE MULTIMODE/SINGLE MODE
JACKET COLOR AQUA (OM4) / LIME (OM5) / YELLOW (SM) / BLACK (OSP)
MEDIA CONNECTOR
PRE-TERMINATE WITH MULTI-FIBER PUSH ON (MPO), (FIELD TERMINATION
AUTHORIZED FOR DISTRIBUTION LEAVING THE COMPUTER ROOM)
STRAND COUNT 12 OR 24
BUNDLING LOOSE TUBE (OUTDOOR)/TIGHT BUFFERED (INDOOR)
5 UTP PATCH CORDS
PERFORMANCE CATEGORY CATEGORY 6A, 26-28 GAUGE, STRANDED
PERFORMANCE SPECIFICATIONS CENTER TUNED TO HORIZONTAL MEDIA
6 FIBER PATCH CORDS MODE MULTIMODE/SINGLE MODE
MEDIA CONNECTOR PRE-TERMINATED WITH DUPLEX LC / MPO-8
JACKET COLOR AQUA (OM4) / LIME (OM5) / YELLOW (SM)
PERFORMANCE SPECIFICATIONS
LASER OPTIMIZED 50/125 MM FIBERS WITH AT LEAST 4,700 MHZ·KM AT 850 NM /
OS1 9/125 SM FIBERS (INTRA-BUILDING) / OS2 9/125 SM (INTER-BUILDING)
PERFORMANCE CATEGORY OM5/ OM4 / OS1 / OS2
TERMINATION METHOD FACTORY PRE-TERMINATED
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 4 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
GENERIC HEALTH CARE FACILITY
EQUIPMENT ROOM
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY EQUIPMENT ROOM 1
AC
SERVICE PANEL FOR A-SIDE
POWER, GENERATOR BACKED
IF THE FACILITY HAS
GENERATION CAPABILITIES.
SHALL BE EQUIPPED WITH
POWER METER; PLACEMENT
PER OTHERS
SERVICE PANEL FOR B-SIDE
POWER, GENERATOR BACKED
IF POSSIBLE. SHALL BE
EQUIPPED WITH POWER
METER; PLACEMENT PER
OTHERS
TWO (2) CONDUITS
INTERCONNECTING NETWORK
SUPPORT CENTER WITH
ENTRANCE FACILITY. TRADE SIZE
CONDUIT OR SLEEVES WITH BUSHING AND
FIRESTOP OR OTHER AHJ-APPROVED
PENETRATION FOR HORIZONTAL
DISTRIBUTION FROM WORK AREA OUTLETS
AND TELECOMMUNICATION ROOMS
PRIMARY OR
SECONDARY BONDING
BUSBAR (PBB/SBB)
WIRE MESH CABLE TRAY SIZE
COMMENSURATE WITH
REQUIREMENTS
VERTICAL CABLE MANAGER WITH
DOOR, 6" WIDE
TYPICAL UNSWITCHED DUPLEX
CONVENIENCE OUTLETS
SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU/H)
AC
ADDITIONAL SPLIT PACKAGE AIR
CONDITIONER (32,600 BTU) WHEN
NECESSARY
T
AIR CONDITIONER THERMOSTAT
TELECOMMUNICATIONS CHANNEL
RACK, 19" RAILS, #12-24 TAPPED
EIA HOLE PATTERN, MINIMUM 30"
DEEP, 7' HIGH, 45RU, WHITE
SERVER CABINET, 45U, 24"X48"
(NOMINAL), SQUARE PUNCHED
RAIL, SINGLE PERFORATED FRONT
DOOR, SOLID REAR DOOR, TWO-
POINT KEYED LOCKS, WHITE,SOLID
SIDE PANELS
3'-0"
RK-1 RK-2 RK-3 RK-4
C
PIV/
KEYPAD
4'X 8' AC GRADE ¾” TRADE
SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE
WITH TWO COATS OF FIRE
RESISTANT PAINT FOR
SERVICE PROVIDER
EQUIPMENT
4'X 8' AC GRADE ¾” TRADE
SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE
WITH TWO COATS OF FIRE
RESISTANT PAINT FOR
SECURITY EQUIPMENT
MINIMUM 170 FT2
STATIC DISSIPATING FLOOR
NO DROP CEILING
SLAB TO DECK ABOVE 12 FT
MINIMUM (16 FT PREFERRED)
WALLS FULL HEIGHT TO DECK
ABOVE
TYP
J J
NOTE:
THREE FEET CLEARANCE FROM WALL MOUNTED EQUIPMENT MUST BE MAINTAINED.
30" WIDE BY 36"
FRONT CLEARANCE
REQUIRED AROUND
120/208V ELECTRICAL
PANEL BOARDS
TWO L21-20 BRANCH CIRCUITS PER RACK CAN BE USED FOR ALL RACKS
ELIMINATING THE NEED FOR ZONE PDUs IF BREAKER SPACE IS NOT AN ISSUE (ALTERNATELY, zPDUs CAN SUPPORT EITHER TWO OR THREE RACKS EACH)
36" CLEARANCE
REQUIRED AROUND
FRONT, BACK AND
SIDES OF RACKS
AND CABINETS
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 5 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS ROOMS
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
AC AC
TYP
T
AC
TYP
T
AC
TYP
T
GENERIC FLOOR PLAN FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS 2
GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (TWO RACK REQUIREMENT)
(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA OUTLETS)
GENERIC FLOOR PLAN FOR TELECOMMUNICATIONS ROOMS (ONE RACK REQUIREMENT)
(TELECOMMUNICATIONS SPACE SUPPORTING NETWORK DISTRIBUTION TO WORK AREA OUTLETS )
TELECOMMUNICATION ROOM NOTES1
M
C
M
C
J J
TYP
'-0
'-0
15'-5 7/16"
8'-0"10'-0"
MINIMUM REQUIREMENT FOR HEALTHCARE FACILITY REMODELS
'-0
NOTE:
THERE SHALL BE A MINIMUM OF ONE TELECOMMUNICATIONS ROOM (TR) PER FLOOR.
ADDITIONAL ROOMS SHOULD BE PROVIDED WHEN THE HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK AREA EXCEEDS 90 M (295
FT) OR THE ROOM SIZE CAN’T SUPPORT ALL WORK AREA OUTLETS.
FLOOR SPACE REQUIREMENT:
1. FOR FACILITIES FROM 1 TO 3,000 SQ. FT., PROVIDE A STANDARD 26U TELECOMMUNICATIONS ENCLOSURE LOCATED IN A SECURED SPACE THAT IS NOT NECESSARILY DEDICATED TO TELECOMMUNICATIONS PURPOSES. SEE SHEETS 16-19.
2. FOR FACILITIES FROM 3,001 TO 6,000 SQ. FT., PROVIDE A 1-RACK TR (80SF, 10’X8’ FORM FACTOR).
3. FOR FACILITIES FROM 6,001 TO 10,000 SQ. FT., PROVIDE A 2-RACK TR (100SF, 10’X10’ FORM FACTOR).
4. FOR FACILITIES FROM 10,001 TO 25,000 SQ. FT., PROVIDE A 3-RACK TR (120SF, 10’X12’ FORM FACTOR).
5. FOR FACILITIES GREATER THAN 25,000 SQ. FT., PROVIDE TRS IN ADDITION TO THE MCR PER THE SIZING AND QUANTITY DETERMINED BY THE TR DESIGN CHECKLIST IN ACCORDANCE WITH THE SERVING ZONE SIZE OF EACH PLANNED TR.
6. 3' OF CLEARANCE ON THREE SIDES OF THE RACKS MUST BE MAINTAINED.
7. THE FOURTH SIDE MUST BE AT LEAST 12" FROM A WALL.
8. 30" WIDE BY 36" FRONT CLEARANCE REQUIRED AROUND ELECTRICAL PANEL BOARDS.
A MINIMUM OF FIVE METRIC DESIGNATOR 103 (TRADE SIZE 4) CONDUITS OR SLEEVES SHOULD BE PROVIDED TO SERVICE UP TO 40,000 SQ FT OF USABLE FLOOR SPACE. ONE ADDITIONAL CONDUIT OR SLEEVE SHOULD BE PROVIDED FOR EACH ADDITIONAL 40,000 SQ FT OF
USABLE FLOOR SPACE.
EACH RACK MUST BE CAPABLE OF SUPPORTING 5KW OF LOAD. HOWEVER, IN AGGREGATE FOR TRS WITH MORE THAN ONE RACK, THE FULL
5KW OF HEAT REJECTION PER RACK IS NOT REQUIRED. SEE BELOW:
1 RACK TR = 5KW COOLING
2 RACK TR = 7KW COOLING
3 RACK TR = 8.5KW COOLING
4 RACK TR = 10KW COOLING
TWO L21-20 BRANCH CIRCUITS PER RACK CAN BE USED FOR ALL RACKS ELIMINATING THE NEED FOR ZONE PDUS IF BREAKER SPACE IS NOT
AN ISSUE (ALTERNATELY, ZPDUS CAN SUPPORT EITHER TWO OR THREE RACKS EACH)
C
'-6
/8
'-2
/4
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 6 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL BACKBOARD
RESERVATIONS
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
AC AC T
RESERVED
VIDEO DISTRIBUTION
WAN/DEMARC
SECURITY POWER METERING
FIRE ALARM/
ANNOUNCIATOR
3'-0"
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 7 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK ELEVATION
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 18 18 19 19 20 20 21 21 22 22 23 23 24 24 25 25 26 26 27 27 28 28 29 29 30 30 31 31 32 32 33 33 34 34 35 35 36 36 37 37 38 38 39 39 40 40 41 41 42 42 43 43 44 44 45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
M AIN
POWER
POWER
ON
GROUP B
0FF
0N
2 0
M AIN
POWER
POWER
ON
GROUP A
0FF
0N
2 0
GROUP A
0FF
0N
2 0
A
0FF
0N
2 0
B
0FF
0N
2 0
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
2 0
A
0FF
0N
2 0
B
0FF
0N
2 0
C
0FF
0N
2 0
0FF
0N
2 0
0FF
0N
2 0
A B CA B C
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
BladeUPS
Powerware
M AIN
POWER
POWER
ON
GROUP B
0FF
0N
2 0
M AIN
POWER
POWER
ON
GROUP A
0FF
0N
2 0
GROUP A
0FF
0N
2 0
A
0FF
0N
2 0
B
0F F
0N
C
0FF
0N
2 0
0FF
0N
2 0
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
2 0
C
0FF
0N
0FF
0N
2 0
0FF
0N
2 0
A B CA B C
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE
CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE
CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
RK-1
MAXIMUM OF 12 ANGLED CATEGORY 6A, 24 PORT
PATCH PANELS PER RACK. IF MORE THAN TWELVE (12)
PATCH PANELS ARE REQUIRED, INSTALL NEXT SET IN
RK-3.
1 RU BLANKING PANELS BETWEEN LOWEST
PATCH PANEL AND RU32
1 RU CABLE MANAGER. SIX POSITION
SPACING WITH DOOR AT RU31
POE LAN SWITCH WITH 1100 WATT POWER
SUPPLIES. MAX OF SIX (6) PER RACK.
2 RU CABLE MANAGER. SIX POSITION
SPACING WITH DOOR.
1 RU CABLE MANAGER. SIX
POSITION SPACING WITH DOOR.
ZONE PDU
UPS
RK-2 RK-3
RK-4
TYPICAL RACK ELEVATION FOR HEALTH CARE FACILITY TELECOMMUNICATIONS ROOMS
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE
CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE
CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
MODE CONSOLE
37X
Cat aly st 38 50 48 Po E+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XP S
STACK
S-P WR
C3850-N M-4- 10G
G1 G2 G3 G4
NET W ORK M ODULE
T E3 T E4T E1 T E2
SPACE
RESERVED
FOR WAN
ROUTERS, IP
PBX,
SECURITY
EQUIPMENT,
ETC.
SPACE
RESERVED
FOR
SERVERS.
SERVICE PROVIDER MAIN CROSS CONNECT
FIRST LEVEL BACKBONE (FIBER)
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 8 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK DETAIL
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
6" WIDE VERTICAL CABLE MANAGEMENT
P/N: OR-MM20VMD706 (OR EQUIVALENT)
MM20 VERTICAL CABLE MANAGEMENT "CAGE", WITH
DOOR, 6" X 8.61" X 7' , BLACK
CAPACITY: 350 CATEGORY 6 PATCH CORDS OR 245
CATEGORY 6A PATCH CORDS
6 in
TYPICAL RACK DIMENSIONS AND SPECIFICATIONS
NTS
P/N: OR-MM2073038-W (OR EQUIVALENT)
MIGHTY MO 20 CABLE MANAGEMENT RACK
30" CHANNEL DEPTH, 7' HIGH, WHITE FINISH OR EQUIVALENT
DIMENSIONS:
USABLE HEIGHT: 45RU
DEPTH (US): 30
HEIGHT (US): 7'
WIDTH (US): 23.75"
STATIC LOAD CAPACITY: 2000 LBS
SQUARE HOLE
FRONT AND REAR HEAVY DUTY PERFORATED SECURITY DOOR (OR-
MM20724PDHD-W)1
SECURITY DOOR FRONT
MOUNTING HARDWARE (OR-
MM2024DMFHD-W) OR
EQUIVALENT4
SECURITY DOOR REAR
MOUNTING HARDWARE (OR-
MM2024DMRHD-W) OR
EQUIVALENT5
PDU MOUNTING BRACKET KIT
(TWO KITS PER RACK)
P/N: OR-MM20PDUMB1D2W-W
OR EQUIVALENT6
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 9 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL CABINET DETAIL
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
TYPICAL SERVER CABINET SPECIFICATION1TYPICAL SERVER CABINET FRONT 2TYPICAL SERVER CABINET SIDE VIEW3
TYPICAL SERVER CABINET TOP VIEW WITH FOUR (4)
BRUSHED GROMMET CABLE OPENINGS
.6
23.6"
43.3" OR SIMILAR (48" MAX)
23.6" (24" NOMINAL)
NOTE: SERVER CABINETS MAY ONLY HOUSE SERVER AND STORAGE
EQUIPMENT AND SUPPORTING PATCH PANELS. SERVER
CABINETS MAY NOT HOUSE TELECOMMUNICATIONS
(NETWORK) EQUIPMENT
CHATSWORTH ZETAFRAMETM CABINET (PN:ZB14-A222A-E1)
OR EQUIVALENT
23.6IN(600MM)W X 43.3IN(1100MM)D X 45RMU;GLACIER WHITE;(1) CASTER ONLY KIT;(1) LEVELER ONLY KIT;(4) SQUARE PUNCHED RAILS WITH NO CABLE OPENINGS;(2) SOLID SIDE PANEL;(1) ZETAFRAME PERFORATED METAL DOOR, GLACIER WHITE;(1) SINGLE-POINT KEYED LOCK;(1) DOUBLE PERFORATED METAL DOOR;(1) THREE-POINT KEYED LOCK;(1) TOP PANEL WITH FOUR (4) BRUSH- SEALED CABLE OPENINGS;(1) BOTTOM PANEL WITH TWO (2) BRUSHED-SEALED CABLE OPENINGS ;(1) AIR DAM KIT;(1) STANDARD DUAL 2-PIECE PDU BRACKET KIT;(1) COMMON PARTS KIT, ZF, UL;(1)
PACKAGING KIT
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 10 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL WORK AREA OUTLETS
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
TYPICAL WORK FLOOR MOUNT OUTLET4TYPICAL WALL MOUNT PHONE VOIP OUTLET3
ONE CATEGORY 6A
8P8C OUTLET ACTIVE
FOR TELEPHONY
TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY 6A
COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45). EACH
CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A HORIZONTAL
CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS ROOM AS SPECIFIED
ELSEWHERE IN THIS DESIGN PACKAGE.
ALL HORIZONTAL UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.
TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.
FACEPLATE MATERIAL AND COLOR DETERMINED BY OTHERS.
THIS SHEET DETAILS A GENERIC FACEPLATE SPECIFICATION.
NOTES:
ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING ON WHITE
FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON ADMINISTRATION MAY BE
SPECIFIED IN OTHER SECTIONS OF THIS DESIGN PACKAGE.
HIGH DENSITY WALL MOUNTED WORK AREA OUTLET
CONFIGURATION2
TYPICAL STANDARD DENSITY WALL MOUNTED WORK AREA
OUTLET CONFIGURATION1
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS.
SINGLE GANG
WORKBOX WITH ONE
CONNECTOR CHASSIS.
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
TWO CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
FOUR POSITION FACEPLATE MOUNTED
ON SINGLE GANG WORKBOX.
FACEPLATE COLOR SPECIFIED BY
OTHERS.
MINIMUM OF FOUR
CATEGORY 6A 8P8C
OUTLETS FOR DATA OR
TELEPHONY
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 11 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TYPICAL RACK POWER
DISTRIBUTION
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
NOTIONAL POWER SCHEMATIC FOR INFORMATION ONLY – NOT FOR CONSTRUCTION
TYPICAL ZONE PDU UNIT WITH REAR DETAIL AND ADAPTORS REQUIRED FOR VERTICAL PDU5
30 Amp 3-Phase PDU BASE UNIT – FRONT
(ZONIT ZON-C-ZPDU1)
REQUIRES TWO 30 AMP 3-PHASE (WYE) CIRCUITS
WITH L21-30R RECEPTACLES
(OR EQUIVALENT)
30 Amp 3-Phase PDU BASE UNIT – REAR
FOUR (4) L21-20R
SIX (6) NEMA 5-15/20 T-SLOT
(OR EQUIVALENT)
120 Volt PDU FOR PLACEMENT AS NEEDED4
PDU INPUTS REQUIRE
TWO L21-30Rs
POWER SCHEMATIC FOR POWER RACK- LEVEL REDUNDANCY1
THE CORRECT SPECIFICATION FOR THE PDU IS TO FEED IT WITH A TWO POWER SOURCES. POWER INPUTS SHOULD ORIGINATE FROM TWO INDEPENDENT POWER SOURCES. EACH INPUT WILL USE IDENTICAL SPECS:
WYE (5-WIRE) CONFIGURED, 208V, 30A, THREE-PHASE, TERMINATING IN A NEMA L21-30R LOCKING RECEPTACLE. THE NEUTRAL CONDUCTOR SHOULD BE UPSIZED ONE GAUGE TO MATCH THE UPSIZED NEUTRAL CONDUCTORS IN THE PDU UNITS. THE NEUTRAL "UPSIZING" SHOULD IDEALLY BE CONTINUED IN THE POWER DISTRIBUTION SYSTEM BACK TO THE UPS OR TRANSFORMER WINDING POLE. THIS INCREASES THE EFFICIENCY OF THE POWER DISTRIBUTION SYSTEM AND SUPPRESSES HARMONICS IN THE SYSTEM.
NOTE:
ONE ZONE PDU FOR TWO
SERVER CABINETS/
NETWORK RACKS
NOTE:
THIS DESIGN PROVIDES DIVERSE POWER INPUTS FOR ACTIVE EQUIPMENT BY SPLITTING THE
SOURCE POWER ACROSS TWO INPUTS ON THE ZONE PDU. EACH INPUT WILL SUPPORT TWO
EQUIPMENT-FACING PDUs. EACH SERVER CABINET WILL CONTAIN A MINIMUM OF TWO EQUIPMENT- FACING PDUs – EACH WILL BE ENERGIZED BY SEPARATE ZONE PDU INPUTS.
208 VOLT PDU FOR EQUIPMENT POWER – TO BE ENERGIZED BY ZONE PDU3
REQUIRES ONE (1) L21-
20R
20 A 120 /208V
Y
DUAL 3-PHASE 480 VOLT INPUTS
TRANSFORMER
BUS OR FEEDER
3-PHASE 208-VOLT 30-AMP PDU
PDU PDU
COMPUTER
ZONE PDU
“ZERO U” VERTICAL PDU
DUAL POWER SUPPLY
480-208V TRANSFORMER
UPS RACK MOUNT UPS
MAIN
POWER
POWER
ON
GROUP B
0FF
0N
MAIN
POWER
POWER
ON
GROUP A
0FF
0N
GROUP A
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
GROUP B
0FF
0N
A
0FF
0N
B
0FF
0N
C
0FF
0N
0FF
0N
0FF
0N
A B CA B C
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B L EG 1
L EG 2 GRP A
GRP B L EG 1
L EG 2 GRP A
GRP B L EG 1
L EG 2
APC AP8861 RPDU OR EQUIVALENT; RACK PDU 2G, METERED; L21-20 PLUG;
THREE PHASE; 120/208V INPUT; 20A; ZERO U,
5.7 KW, 208V, (36) C13 & (6) C19 & (2) 5-20 OUTLETS; FOR USE IN
TELECOMMUNCIATION ROOMS AND LOCATIONS WITH LEGACY 110V ONLY
EQUIPMENT
RACK/ENCLOSURE
ZONE PDU
RACK/ENCLOSURE
PDU
B
PDU
A
BUS A BUS B
RACKED
EQUIPMENT
PS1 PS2
RACKED
EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACK-MOUNT
UPS
RACK-MOUNT
UPS
LEG2LEG1
Rack
PDU
APC AP9560 OR EQUIVALENT RACK MOUNT PDU; L5-30 PLUG; (10) NEMA 5-20 OUTLETS; 1 RU;
TWO PER ENCLOSURE; ONE ENERGIZED BY UPS; ONE ENERGIZED BY WALL OUTLET
USED IN TELECOMMUNICATIONS ENCLOSURES ONLYNOTE:
REQUIRES ONE L5-30R
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHASE Y PHASE X
GRP A
GRP B L EG 1
L EG 2 GRP A
GRP B LEG 1
LEG 2 GRP A
GRP B LEG 1
LEG 2
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 12 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
POWER DISTRIBUTION (1-3 RACK
TR)
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
RACK/ENCLOSURE
ZONE PDU
LEG1
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
RACK/ENCLOSURE
ZONE PDU
RACK/ENCLOSURE
POWER ELEVATION AND SCHEMATIC FOR A TWO RACK TR
L21-30P SIDE A
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-30R
LOCKING RECEPTACLE.
L21-30P SIDE B
REQUIRES A 208V, 30A, THREE-PHASE
CIRCUIT, TERMINATING IN A NEMA L21-30R
LOCKING RECEPTACLE.
POWER ELEVATION AND SCHEMATIC FOR A ONE RACK TR1
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
PDU
B
PDU
A
BUS A BUS B
RACKED
EQUIPMENT
PS1 PS2
RACKED
EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACK-MOUNT
UPS
RACK-MOUNT
UPS
RACK/ENCLOSURE
PDU
B
PDU
A
BUS A BUS B
RACKED
EQUIPMENT
PS1 PS2
RACK-MOUNT
UPS
PDU
B
PDU
A
LEG2
BUS A BUS B
RACK/ENCLOSURE
RACKED EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACKED EQUIPMENT
PS1 PS2
RACK/ENCLOSURE
RACKED EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACK-MOUNT UPS RACK-MOUNT UPSRACK-MOUNT UPS
A
B
OZ
GROUP B
OX OY
OX
GROUP A
OY OZ
OY
GROUP B
OZ OX
OZ
GROUP A
OX OY
LEG 1 LEG 2 LEG 2LEG 1
PHASE Z PHA SE Y P HASE X
GRP A
GRP B L EG 1
L EG 2 G RP A
G RP B L EG 1
L EG 2 GRP A
GRP B L EG 1
L EG 2
ZONE PDU
30A 3-PHASE ZONE PDU BASE UNIT
– REQUIRES TWO 30A 3-PHASE
(WYE) CIRCUITS WITH L21-30R
RECEPTACLES; OPTIONALLY, UPSs AND B-SIDE rPDUs MAY BE
POWERED DIRECTLY WITH L21-20
OUTLETS
A
/ 2
8V 3
Y
A
/ 2
8V 3
Y
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
L21-20P SIDE A
REQUIRES A 208V, 20A, THREE-
PHASE CIRCUIT, TERMINATING IN
A NEMA L21-20R LOCKING
RECEPTACLE.
L21-20P SIDE B
REQUIRES A 208V, 20A,
THREE-PHASE CIRCUIT,
TERMINATING IN A NEMA L21-
20R LOCKING RECEPTACLE.
LEG2LEG1
J
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
J
A
B
O Z
GR
OU
P
BO
X
O Y
O X
GR
OU
P
AO
Y
O Z
O Y
GR
OU
P
BO
Z
O X
O Z
GR
OU
P
AO
X
O Y
L E G
L E G
L E G
L E G
O Z
GR
OU
P
BO
X
O Y
O X
GR
OU
P
AO
Y
O Z
L E G
L E G
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
RACK-MOUNTED 5 KW,
208V UNINTERRUPTIBLE
POWER SUPPLY (UPS)
WITH NEMA 20A L21-20P
INPUT AND L21-20R
OUTPUT
RACK-MOUNTED 5 KW, 208V
UNINTERRUPTIBLE POWER SUPPLY (UPS)
WITH NEMA 20A L21-20P INPUT AND L21-
20R OUTPUT
RACK-MOUNTED 5 KW, 208V
UNINTERRUPTIBLE POWER SUPPLY
(UPS) WITH NEMA 20A L21-20P INPUT
AND L21-20R OUTPUT
ZONE PDU
60A 3-PHASE ZONE PDU BASE UNIT
– REQUIRES TWO 60A 3-PHASE
(WYE) CIRCUITS HARD-WIRED IN
JUNCTION BOX; OPTIONALLY, UPSs AND B-SIDE rPDUs MAY BE
POWERED DIRECTLY WITH L21-20
OUTLETS
POWER ELEVATION AND SCHEMATIC FOR A THREE RACK TR
SIDE A
REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,
TERMINATING IN A HARD-WIRED JUNCTION BOX.
SIDE B
REQUIRES A 208V, 60A, THREE-PHASE CIRCUIT,
TERMINATING IN A HARD-WIRED JUNCTION BOX
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 13 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
POWER DISTRIBUTION (4 RACK
TR)
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
POWER ELEVATION AND SCHEMATIC FOR A FOUR RACK TR
ONE ZONE PDU
60A 3-PHASE ZONE PDU BASE UNIT –
REQUIRES TWO 60A 3-PHASE (WYE)
CIRCUITS HARD-WIRED IN JUNCTION BOX TO
SUPPORT THREE RACKS
RACK/ENCLOSURE
ZONE PDU
LEG1
PDU
B
PDU
A
LEG2
BUS A BUS B
RACK/ENCLOSURE
RACKED
EQUIPMENT
PDU
B
PDU
A PS1 PS2
RACKED
EQUIPMENT
PS1 PS2
RACK/ENCLOSURE
RACKED
EQUIPMENT
PDU
BPS1 PS2
RACK-MOUNT
UPS
RACK-MOUNT
UPS
RACK-MOUNT
UPS
REQUIRES TWO 20A 3-
PHASE (WYE) CIRCUITS
TERMINATING IN L21-20Rs
RACK/ENCLOSURE
PDU
B
PDU
A
BUS A BUS B
RACKED
EQUIPMENT
PS1 PS2
RACK-MOUNT
UPS
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
J C
H A
T S
W O
R T
H P
R O
D U
C T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
T em p /H um idi ty O ut
In
IO
IO
IO
0/
R es e t
W ar ni ng
O K
C ri tic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
J
A
B
O Z
GR
OU
P
BO
X
O Y
O X
GR
OU
P
AO
Y
O Z
O Y
GR
OU
P
BO
Z
O X
O Z
GR
OU
P
AO
X
O Y
L E G
L E G
L E G
L E G
O Z
GR
OU
P
BO
X
O Y
O X
GR
OU
P
AO
Y
O Z
L E G
L E G
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
SIDE A
REQUIRES A 208V, 60A,
THREE-PHASE CIRCUIT,
TERMINATING IN A
JUNCTION BOX.
SIDE B
REQUIRES A 208V, 60A,
THREE-PHASE CIRCUIT,
TERMINATING IN A
JUNCTION BOX
RACK-MOUNTED 5 KW, 208V
UNINTERRUPTIBLE POWER SUPPLY (UPS)
WITH NEMA 20A L21-20P INPUT AND L21-
20R OUTPUT PER RACK
A 12 0/ 2
08V
Y
A 12 0/ 2
08V
Y
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
30 30
31 31
32 32
33 33
34 34
35 35
36 36
37 37
38 38
39 39
40 40
41 41
42 42
43 43
44 44
45 45
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
L21-20P SIDE A
REQUIRES A 208V,
20A, THREE-
PHASE CIRCUIT,
TERMINATING IN A
NEMA L21-20R
LOCKING
RECEPTACLE.
L21-20P SIDE B
REQUIRES A 208V,
20A, THREE-PHASE
CIRCUIT,
TERMINATING IN A
NEMA L21-20R
LOCKING
RECEPTACLE.
C H
A T
S W
O R
T H
P R
O D
U C
T
Te m p/ H um id ity O ut
In
IO
IO
IO
/1
R es et
W a rn in g O
K
C rit ic al
CB2
CB2
CB1
CB1
CB1
CB1
CB3
CB3
CB3
CB3
CB2
CB2
O F
F
O
O N I
C B
O F
F
O
O N I
C B
O F
F
O
O N I
C B
ZONE PDU
60A 3-PHASE
ZONE PDU BASE
UNIT – REQUIRES
TWO 60A 3-
PHASE (WYE)
CIRCUITS HARD-
WIRED IN
JUNCTION BOX;
OPTIONALLY,
UPSs AND B- SIDE rPDUs MAY
BE POWERED
DIRECTLY WITH
L21-20 OUTLETS
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 14 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
BONDING
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
12" min
4"
ANSI/EIA/TIA COMPLIANT BUSBAR
CHATSWORTH P/N: 40158-012
TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB)
ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND
IN COMPLIANCE WITH LOCAL CODES.
ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.
NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR OR
OPERATE THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND CONDUCTOR.
THESE DEVICES WILL BE BONDED TO THE RACK BONDING BUSBAR (RBB) IN THE SAME RACK.
EACH DEVICE WILL HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT BE
SHARED.
RACK BONDING
CONDUCTOR (RBC) - 6
AWG
TELECOMMUNICATIONS EQUIPMENT
BONDING CONDUCTOR (TEBC) – 6 AWG
INDIVIDUAL EQUIPMENT BONDING
CONDUCTORS FROM EACH PIECE
OF EQUIPMENT AND RACK TO THE
RACK BONDING CONDUCTOR
RACK BONDING CONDUCTOR (RBC)
EXTENDED TO BOTTOM OF RACK
TO ACCOMMODATE FUTURE
GROWTH
RACK ISOLATION
PADS (IF
APPLICABLE)
SERVER
CABINET
NETWORK
RACK
TO PBB/
SBB
TO PBB/SBB
PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS
EARTHING EXAMPLES
Ref: CISCO PRODUCT INSTALLATION GUIDE
NOTES:
CISCO NEXUS 95108/95180
TWO-HOLE COMPRESSION LUGS
(RACKS SHALL NOT BE MODIFIED
IF ONLY ONE-HOLE IS PROVIDED;
USE ONE-HOLE COMPRESSION
LUGS IN THIS CASE)
TOP-MOUNTED RACK BONDING
BUSBAR (RBB)
UNIT BONDING
CONDUCTOR (UBC) - 6
AWG
GROUNDING TERMINAL
(TYPICAL EACH PIECE
OF EQUIPMENT)
IRREVERSIBLE CRIMP
CONNECTOR
TELECOMMUNICATIONS EQUIPMENT
BONDING CONDUCTOR (TEBC) – 6
AWG
RACK BONDING CONDUCTOR
(RBC) - 6 AWG
IRREVERSIBLE CRIMP
CONNECTOR
IRREVERSIBLE CRIMP
CONNECTOR CABLE TRAY BONDING
CONDUCTOR. TYPICAL
AT EACH SECTION
CONNECTION POINT
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) –
6 AWG
PWR
FAN
DCIN
PWR
FAN
DCIN
AC T
STS
BC N
ACT
STS
BCN
UBC
TWO-HOLE
COMPRESSION
LUG
SCREWS
(M4)
SYSTEM GROUND LOCATION
SYSTEM GROUND LOCATION
PER MANUFACTURER’S INSTRUCTIONS, WHEN ATTACHING A
GROUNDING CABLE TO THE CHASSIS, YOU WILL NEED TO BEND
ONE OF THE RACK-MOUNT RAILS SLIGHTLY TO ALLOW THE
GROUNDING LUG TO GO BEHIND THE RAIL. ONLY ONE SIDE OF
THE CHASSIS NEEDS TO BE BONDED.
CISCO NEXUS 9508
UBC
TWO-HOLE
COMPRESSION
LUG
SCREWS
(M4)
SYSTEM GROUND LOCATION
O
I
O
I
Catalyst 9600 Series
RFID
C9606R
C9606-FAN
RFID
O
I
O
I
C9600-SUP-1
SS
SS
Catalyst 9600 Series Superviso r Module
C9600-SUP-1
SS
SS
Catalyst 9600 Series Superviso r Module
C9600-LC- 48YLCatalyst 9600 Series Ethernet Switchin g Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
C9600-LC-24CCatalyst 9600 Series Ethernet Switchin g Module
17 18 19 20 21 22 23 249 10 11 12 13 14 15 161 2 3 4 5 6 7 8
C9600-LC- 48YLCatalyst 9600 Series Ethernet Switchin g Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
C9600-LC- 48YLCatalyst 9600 Series Ethernet Switchin g Module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
CISCO 9606
SYSTEM GROUND
LOCATION
TWO-HOLE
COMPRESSION LUG
GROUNDING PAD
UBC
CISCO 6509
TWO-HOLE
COMPRESSION
LUG
UBC
SYSTEM
GROUND
LOCATION
SCREWS
(M4)
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 15 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
CBOC ITS NAMING STANDARDS
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
RACK = RK1 THROUGH RK4. LABELED LEFT TO RIGHT WHEN LOOKING AT THE FRONT OF THE RACK. APPLIES TO RACKS AND CABINETS.
UTP PATCH PANEL = CPL-RACK NAME-01 THROUGH 45. EXAMPLE: CPL-RK1-01 FOR THE PANEL LOCATED IN RACK UNIT #1 IN RACK #1.
UTP PATCH PANEL POSITION = PANEL ID.01 THROUGH 24. EXAMPLE CPL-RK1-01.01
FIBER DISTRIBUTION PANEL = FDP-RACK NAME-01 THROUGH 45. EXAMPLE: FDP-RK1-01 FOR THE PANEL IN RACK UNIT #1 RACK #1.
FIBER DISTRIBUTION CASSETTE = FDC-RACK NAME-01 THROUGH 45.1 THROUGH 3. EXAMPLE: FDC-RK1-01.1 FOR THE CASSETTE IN POSITION #1 IN
PANEL LOCATED IN RACK UNIT #1 IN RACK #1.
UTP PATCH CORDS = CCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE CCA[CPL-RK1-01.01]/[CPL-RK2-02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE COPPER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.
FIBER PATCH CORDS = FCA[SOURCE.PORT]/[DESTINATION.PORT]. EXAMPLE FCA[FDP-RK1-01.01.01]/[FDP-RK2-02.02.02] AS A PATCH CORD CONNECTING PORT #1 IN THE FIBER PATCH PANEL LOCATED IN RACK #1, RACK UNIT #1 WITH PORT 2 LOCATED IN RACK 2, RACK UNIT #2.
FACEPLATE = TR ROOM NUMBER-PATCH PANEL ID.PORT. EXAMPLE. 1A-CPL-RK1-01.1 FOR TELECOMMUNICATIONS ROOM 1, UTP PANEL IN RACK #1, RACK UNIT #1, PORT POSITION #1.
EXAMPLE INSIDE PLANT LABELING REQUIREMENTS1
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 16 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (TOP VIEW)
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
TYPICAL TOP-DOWN VIEW
NTS
RBB
TYPICAL WALL-
MOUNTED CABINET
T
A/C GRADE ¾ TRADE SIZE
PLYWOOD BACKBOARD.
PAINTED WITH TWO COATS
OF FIRE RESISTANT
BRIGHT HIGH-GLOSS WHITE
PAINT.
MULTIPLE DEDICATED 20-A, 120
VAC SINGLE PHASE CIRCUIT
DUPLEX OUTLET TO NEAREST
AVAILABLE POWER PANEL
PBB
ELECTRONIC EQUIPMENT BONDED TO
RBB; RBB BONDED TO TEBC; TEBC
BONDED TO PBB ALL USING A MINIMUM
OF 6 AWG
CONDUIT OR SLEEVES WITH
BUSHING AND FIRESTOP
FOR HORIZONTAL
DISTRIBUTION AS NEEDED
30"
30" OF CLEARANCE
REQUIRED FOR CABINET
SWING FROM THE REAR
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 17 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (ELEVATION VIEW)
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
ELEVATION FOR TELECOMMUNICATIONS ENCLOSURE
Smart-UPS 3000
Esc
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
C5e
MODE
CONSOLE
37 X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
ST ACK
S-P WR
C3850-NM-4- 10G
G 1 G 2 G 3 G 4
NETWO RK MO DULE
TE3 T E4TE1 T E2
LINK
LINK
LINK
LINK
CLASS 1
LA SER
ASR 1001
AUXCO NMGMT
LI NKUSB
BF
MAJ
MIN
CRIT
ST AT
PWR
S
TA
TU
S
S P
A -5
X
G E
-V
A/L
A/L
A/L
A/L
A /L
RACK MOUNT UPS. L5-30 INPUT.
L5-30 OUTPUT. CAPACITY NTE
2880 VA. 2 RU. METERED
(APC SMX3000RMLV2U OR
EQUIVALENT)
RACK MOUNT PDU. L5-30 INPUT. NEMA
5-20 OUTPUT. 1 RU. TWO PER
ENCLOSURE. ONE ENERGIZED BY UPS.
ONE ENERGIZED BY WALL OUTLET.
(SHOWN HERE FRONT FACING, BUT ARE
TO BE INSTALLED ON THE BACK RAIL.)
RESERVED FOR SERVICE
PROVIDER, DVRs, AND OTHER
TELECOMMUNICATIONS
EQUIPMENT.
QUAD OUTLET (5-20)
FOR BACKBOARD
MOUNTED
EQUIPMENT
4 FOOT BY 8 FOOT ¾ INCH PLYWOOD BACKBOARD.
A/C GRADE. PAINTED WHITE WITH FIRE RESISTANT PAINT IF
PERMITTED BY AHJ
CUBE-IT WALL-MOUNT CABINET;
GEN 3; 48"H X 24"W X 30"D
(1220 MM X 610 MM X 760 MM);
26U; #12-24 TAPPED RAILS;
TEMPERED GLASS DOOR; GLACIER
WHITE OR EQUIVALENT
MODE
CONSOLE
37 X
Catalyst 3850 48 PoE+
25X 36X13X 24X01X 12X 48X
PoEDUPLX
ACTV
STAT
SYST
SPEED
XPS
ST ACK
S-P WR
C3850-NM-4- 10G
G 1 G 2 G 3 G 4
NETWO RK MO DULE
TE3 T E4TE1 T E2
TELECOMMUNICATIONS
BONDING BUSBAR
13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12
25 26 27 28 29 30 31 32 33 34 35 36 LEVITON
13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 48
1 2 3 4 5 6 7 8 9 10 11 12
25 26 27 28 29 30 31 32 33 34 35 36 LEVITON
VA ROUTER (FOR NCA MDA ONLY)
PATCH PANELS TO WORK
AREAS
ANALOG TELEPHONY PATCH
PANEL (IF REQUIRED)
VA LAN SWITCH
SHELF FOR NON-RACKMOUNT EQUIPMENT
1 RU CABLE MANAGER
PATCH PANELS TO WORK
AREAS (MAX 96 POSITIONS)
2 RU CABLE MANAGER
2 RU CABLE MANAGER
QUAD OUTLET (5-20) FOR
BACKBOARD MOUNTED
EQUIPMENT
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
IN
O
U T
CAT6
UTP SURGE PROTECTOR
(IF REQUIRED)
2 RU CABLE MANAGER
1 RU CABLE MANAGER
LOCKING 120 VOLT 30 AMP OUTLETS (L5-30) ON THE WALL
BEHIND THE RACK ALIGNED WITH THE CUTOUT ON THE
ENCLOSURE. ONE OUTLET ASSIGNED TO PDU. ONE OUTLET
ASSIGNED TO UPS. EACH ENERGIZED BY SEPARATE ONE-POLE
30 AMP BREAKERS.
OM4 (A SIDE)
OS1 (A SIDE)
OM4 (B-SIDE)
OS1 (B SIDE)
HOOK AND LOOP STRAPS
EVERY 12 INCHES.
CABLE FROM SP AND CABLE
TO OTHER CAMPUS
BUILDINGS (NCA ONLY)
CABLE TO WORK AREA
OUTLETS (WAOS)
FIBER PATCH PANEL FOR INCOMING
CIRCUITS
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN GRZELKA, CTDC
CHECKED BY:
DOC VERSION No:
SHEET TITLE
PRINT DATE: May 19, 2023
ISSUE DATE: May 17, 2023
SHEET: 18 OF 20
CBOC INFORMATION
TRANSPORT SYSTEMS
SPECIFICATIONS
A
B
C
D
2 3 4
1 2 3 4
A
B
C
D
TELECOMMUNICATIONS
ENCLOSURE (ELEVATION)
MICHAEL JULIAN, RCDD
KELLY BATES
DEPARTMENT OF VETERANS
AFFAIRS
ENTERPRISE DATA CENTER
INFRASTRUCTURE COLLABORATION
TEAM
OFFICE OF INFORMATION AND
TECHNOLOGY
INFRASTRUCTURE OPERATIONS –
APPLICATION HOSTING, CLOUD
AND EDGE SOLUTIONS
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
1 BONDING TOPOLOGY FOR TELECOMMUNICATIONS ENCLOSURES
TELECOMMUNICATIONS
BONDING BUSBAR (PBB OR
SBB AS APPROPRIATE)
BONDING CONDUCTOR TO PANEL
BOARD GROUND LUG (ACEG)
RACK BONDING BUSBAR
(RBB)
BOND RBB TO CABINET BONDING LUG. AWG #6
BOND RBB TO PBB.
AWG #6
S-PW R 1
XPS
S-PW R 2
RESET
CONSOL E SERIAL MG MT
AC OK PS OK PWR-C1-11 00WAC AC OK PS OK PWR-C1-11 00WAC
BOND RBB TO EACH SWITCH AND ROUTER
CHASSIS
USE TWO-HOLE LUGS FOR
BONDING CONNECTOR
OTHER CONNECTIONS AS REQUIRED
(BONDING CONDUIT, CABLE TRAYS,
BUILDING STEEL, TO THE PBB OR SBB, ETC.)
DATE
ISSUE:
DESCRIPTIONMARK
FILE: CBOC DESIGN TEMPLATE-v2.vsd
DESIGNED BY: KEVIN…
This is the start of the file's text. The full file is on GovTribe.