This file is a Room Data Matrix (RDM) appendix that serves as a detailed specification template for the Community Based Outpatient Clinic lease requirement in Twin Falls, Idaho. The RDM is a planning and documentation tool designed to capture comprehensive spatial and functional requirements for the proposed 20,250 rentable square feet facility. It functions as a specifications framework rather than a standalone deliverable, establishing the baseline architectural and operational parameters that prospective lessors must meet or accommodate.
The matrix appears structured to document room-by-room requirements including space allocations, functional uses, equipment specifications, and operational considerations necessary for Veterans Affairs clinical operations. As an appendix to the solicitation, this RDM serves as reference documentation for potential offerors to understand the Department of Veterans Affairs' detailed space programming needs and facility design expectations for the outpatient clinic. Prospective lessors would use this matrix to ensure their proposed property can accommodate the specified clinical and administrative functions, making it a critical evaluation tool for determining property suitability and compliance with the lease solicitation requirements.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RDM Org
| ROOM DATA MATRIX | INTERIOR CONSTRUCTION | DOORS AND HARDWARE | MECHANICAL | ELECTRICAL | IT | ||||||||||||||||||||
| -- | -- | -- | -- | -- | FLOOR | WALLS | CEILING | NOTES | -- | -- | -- | -- | -- | -- | -- | Note: Use parameters within FGI Guidelines for the noted FGI Equivalent category, unless noted otherwise. | POWER | LIGHTING | -- | ||||||
| DEPARTMENT | ROOM NAME | ROOM NAMES (VA) | FGI EQUIVALENT FOR ASHRAE 170 | FGI EQUIVALENT FOR TABLE 1.2-5 Minimum Sound Isolation | Floor Finish | Base | Wall Finish | Wainscot Material | Wainscot Height | STC | Ceiling Finish | Height | Notes | Size (Width) | Type | Material | Glazing | Rating | Hardware Group | Hardware Notes | Indoor Temperature | ||||
| Cooling F | Indoor Temperature | ||||||||||||||||||||||||
| Heating F | Indoor Relative Humidity | ||||||||||||||||||||||||
| % RH Max | Indoor Relative Humidity | ||||||||||||||||||||||||
| % RH Min | Minimum Total ACH | Minimum OA ACH | Room Air Return | ||||||||||||||||||||||
| Gen. Exh G Spec Exh S | Maximum Noise | ||||||||||||||||||||||||
| Level NC | Room Air Balance | HVAC Notes | # Duplex Receptacles | # Quad Receptacles | Power - Notes | Fixture Type | Controls | Lighting - Special Requirements | Lighting - Notes | # Data Outlets (standard density WAO) | |||||||||||||||
| General Rooms/Spaces | Exam Room | PACT Exam | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 10 | 3'-0" |
| 3'-6" | Flush | Wood | _ | _ | 12 SE | 3 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 8 | 1 | -- | -- | Multilevel Switching, Dimming & Occupancy | Multi-level switching or manual dimming | N/A | 3 | |||||||||||||||
| General Rooms/Spaces | Exam Room | Exam Room - Multi-Specialty, Exam / Treatment, Exam - Consult, Consult Room - PACT, Exam/Consult Room (Mental Health/Social Work), Exam Room EMG/EEG, Exam Room-Cardiology, Exam/Consult, Nurse Practitioner, Women's Health Exam, Tele-Health Exam, Optometry Exam Treatment Room, Eye Lane, Tele-Retinal, TECHS, Hearing Aid Fitting Room, Fitting Room, Physical Therapy Room, Occupational Treatment Room | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 10 | 3'-6" | Flush | Wood | _ | _ | 12 S | -- | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 8 | 1 | -- | -- | Multilevel Switching, Dimming & Occupancy | Multi-level switching or manual dimming | N/A | 3 | |
| General Rooms/Spaces | Consult Room | Consult Room, Audiology Rehabilitation Counseling Room, Dental Consult Room | -- | CONSULTATION | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | 75 | 70 | 60 | - | 4 | 2 | Return | 40 | NR | -- | 6 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Multi-level switching or manual dimming | N/A | 1 | |
| General Rooms/Spaces | Procedure Room | Procedure Room, General, Urology, Gynecology, Specialty Care, Multi-Specialty Care, Cast Room | PROCEDURE | TREATMENT | WSF | WSF | EP | RWC | 4'-0" | SEE FGI | AT | 9'-0" | 3 | 3'-0" |
| 3'-6" | Flush | Wood | -- | -- | 12 SE | 3 | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 7 | -- | P13 | -- | Multilevel Switching, Dimming & Occupancy | Wall mounted exam light | N/A | 2 | |||||||||||||||
| General Rooms/Spaces | Laboratory | Laboratory (Typical) | LABORATORY WORKROOM | __ | WSF | WSF | EP | -- | -- | 40 | AT-SP | 9'-0" | 3 | 3'-0" | Flush | Wood | _ | _ | 15 AG | 4 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | P3, P4 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 5 | |
| General Rooms/Spaces | Conference Room | Conference Room, Multi-Purpose Room, Group Room, Shared Medical Appointment Room, Education Room, Staff Training Room, Classroom | -- | __ | CPT | RB | P | RWC | 4'-0" | 40 | AT | 9'-0" | 17 | 3'-6" | Flush | Wood | _ | _ | 15 S | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | M2 | 8 | -- | P14 | -- | Multilevel Switching, Dimming & Occupancy | Provide 4 scene preset dimmable lighting for a variety of tasks. Consider placement and optics to mitigate glare and ceiling reflections. | N/A | 4 | |
| General Rooms/Spaces | TOILET | General Toilet, Patient - Toilet, Toilet - Police, Toilet - Family, Toilet - Female Staff, Toilet - Male Staff, Toilet - Procedure Room, Toilet - Public, Toilet - RF Patient, Toilet - Women's Health, Toilet - Female, Toilet - Family Assist, Specimen Collection Toilet | TOILET ROOM | TOILET ROOM | PT | PT | P | CT | 7'-0" | SEE FGI | AT | 9'-0" | 1,2 | 3'-6" | Flush | Wood | _ | _ | 11 | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | Downlights/Mirror or vanity | Occupancy Sensor | N/A | N/A | -- | |
| General Rooms/Spaces | OFFICE | Any Office | -- | CONSULTATION | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 CS | -- | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 4 | 1 | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| General Rooms/Spaces | WAITING | Waiting - Family - PACT, Waiting - PACT 3, Waiting - General - 20 People, Waiting - General - 10 People, Waiting - General - 6 People, Waiting-General | -- | EXAM - PUBLIC SPACE | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 10, 17 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | M4 | -- | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| General Rooms/Spaces | RECEPTION | Reception, Information Desk, Travel Window, Reception - Accessible | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush w/ narrow vision | Wood | _ | _ | 12 CG | 3 | _ | _ | _ | _ | _ | _ | _ | _ | _ | M4 | 1 | 1 | -- | Downlights, pendants, decorative, and accent | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 10 | |
| General Rooms/Spaces | COPY ALCOVE | Copy Alcove, Copier - Workroom, Copy / Office Supply Room, Copy Room | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 6 | _ | _ | _ | _ | _ | _ | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 3 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 3 | |
| General Rooms/Spaces | CLEAN UTILITY | Clean Utility, Clean Supply, Clean Workroom, Clean Linen, Sterile Storage, CBOC Sterile Supply Storage Room, Clean Scope, Dental Clean Cart, Central Sterile | -- | -- | RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | 45 MIN | 121 AG | _ | 66 | 75 | 55 | 30 | 4 | _ | _ | _ | (+) | _ | 1 | -- | -- | -- | Occupancy Sensor | N/A | N/A | -- | |
| General Rooms/Spaces | SOILED UTILITY | Soiled Utility Room, Recycled Material, Soiled Holding, Soiled Linen, Soiled Workroom, Soiled Supply, Soiled Cart | SOILED HOLDING / SOILED WORK ROOM | -- | WSF | WSF | P | RWC | 4'-0" | -- | AT | 9'-0" | 3 | 3'-0" | Flush | Wood | -- | 45 MIN | 121 AG | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 2 | -- | -- | -- | Occupancy Sensor | N/A | N/A | -- | |
| General Rooms/Spaces | STORAGE | Storage - Medical Equipment, Storage - Shared Medical Appointments, DME - Prosthetics Storage, Storage - Homeless, EMS Storage, Storage - Bistro/Coffee Bar, Storage - Patient Clothing and Luggage, Laundry / Storage, Tray Cart Storage Area, Bulk Storage, General Storage, Secure Storage, | CLEAN WORKROOM/CLEAN SUPPLY | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 35 AG | -- | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 1 per wall, not to exceed 12' spacing | -- | -- | Surface or chain mounted 1' x 4' | Occupancy Sensor | N/A | N/A | -- | |
| General Rooms/Spaces | JANITOR'S CLOSET | Housekeeping Aides Closet (HAC) | ENVIRONMENTAL SERVICES ROOM | -- | CS | RB | P | FRP | 4'-0" | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 34 A | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | -- | Occupancy Sensor | N/A | N/A | -- | |
| General Rooms/Spaces | KITCHENETTE | Social Activities Space/ Kitchen | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | 17 | 3'-0" | Flush | Wood | -- | -- | 15 A | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 4 | -- | -- | -- | Multilevel switching/dimming/occupancy | N/A | N/A | -- | |
| General Rooms/Spaces | EQUIPMENT ALCOVE | AED Alcove, Height and Weight Alcove, Scale Alcove, Stretcher Alcove, Med Alcove, Portable Patient Lift Alcove, Wheelchair Alcove, My Health eVet, Kiosk, | -- | -- | Match Adjacent | Match Adjacent | Match Adjacent | RWC | 4'-0" | -- | AT | Match Adjacent | 3 | -- | -- | -- | -- | -- | -- | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| General Rooms/Spaces | STAFF LOUNGE | Staff Lounge | -- | -- | RSF | RB | P | -- | -- | 40 | AT | 9'-0" | 4 | 3'-0" | Flush w/ narrow vision | Wood | -- | -- | 13 | _ | _ | _ | _ | _ | _ | _ | Exh. (G) | _ | (-) | _ | 8 | -- | P7 | ||||||
| -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |||||||||||||||||||||||||||||||||||
| General Rooms/Spaces | MEDICATION ROOM | Medication Room | MEDICATION ROOM | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 34 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 5 | 1 | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| General Rooms/Spaces | LACTATION ROOM | Employee Wellness, Lactation Room, Quiet Room | -- | -- | RFT | RB | P | -- | -- | 50 | AT | 9'-0" | 10 | 3'-0" | Flush | Wood | -- | -- | 12 CS | -- | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| General Rooms/Spaces | LOCKER ROOM | Locker Room, Locker Room (Male/ Female) Locker - Staff Personal Property, Locker Room - Staff | -- | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | Push/Pull | -- | -- | -- | -- | -- | -- | -- | Exh. (G) | -- | (-) | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| General Rooms/Spaces | OFFICE, CUBICLE, Open Office | Cubicle - Administrative, Data Processing, Workstation - Extended Team, Homeless, Workstation - MICHM, Workstation - Suicide Prevention, Workstation - VOC Rehab, Workstation - Rad Tech, Workstation - Shipping / Receiving, Workstation, Administration (MSA MH; Rad, LPN), Workstation-Sleep Tech, Work Station, Call Center (MSA), Workstation-Cart Case Dispatch, Workstation-Clerical, | -- | -- | CPT | RB | P | -- | -- | -- | AT | 9'-0" | -- | -- | -- | -- | -- | -- | -- | -- | _ | _ | _ | _ | _ | _ | _ | _ | _ | _ | 2 per workstation | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| General Rooms/Spaces | SUB-WAITING | Sub-Waiting, MRI Sub-Waiting, CT Sub-Waiting, Mammo Sub-Waiting, Sub-Waiting - Diagnostic Patient, Sub-Waiting - Dilation Patient, CT Vestibule, Waiting, Waiting-Zone 1, Sub-Waiting-Zone 2 | -- | -- | CPT | RB | P | -- | -- | -- | AT | 9'-0" | 10, 17 | -- | -- | -- | -- | -- | - | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | M4 | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| General Rooms/Spaces | VENDING | Vending Machine Area | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | -- | -- | -- | -- | -- | -- | 6 | _ | _ | _ | _ | _ | _ | _ | _ | _ | M4 | 8 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| General Rooms/Spaces | TOILET/SHOWER ROOM | Toilet/Shower-Staff, Toilet/Shower-Patient, Toilet/Shower-Female Staff, Toilet/Shower-Male Staff | TOILET ROOM | TOILET ROOM | PT | PT | CT | -- | -- | SEE FGI | GWB/P | 9'-0" | 2, 19 | 3'-6" | Flush | Wood | -- | -- | 11 G | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 2 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| General Rooms/Spaces | CHANGING ROOM | Dressing room | -- | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 11 K | -- | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| Primary Care, Specialty Care, PACT | PACT TEAM WORK SPACE | PACT Team Work Space, Team Work Area- Home Based Primary Care | -- | -- | CPT | RB | P | -- | -- | -- | AT | 9'-0" | -- | _ | _ | _ | _ | _ | 14 MP | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | M3 | 2 per workstation | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting. | N/A | 1 per workstation | |
| Primary Care, Specialty Care, PACT | EXAM ROOM, AIRBORNE INFECTION ISOLATION | Exam, Isolation, Negative Pressure | AII Room | EXAMINATION | WSF | WSF | P | -- | -- | SEE FGI | GWB:P | 9'-0" | 3,7 | 3'-6" | Flush | Wood | -- | -- | 12 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Sealed fixture, flat lens surface on exterior | N/A | 1 | |
| Audiology and SLP | AUDIOLOGY HEARING AID TESTING | Hearing Aid Lab, Hearing Aid Processing, Hearing Aid Repair | -- | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-0" | Flush | Wood | _ | _ | 15 S | _ | 75 | 70 | 60 | - | -- | -- | Exh. (G) | -- | (-) | -- | 7 | 0 | P4 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Audiology and SLP | AUDIOLOGY HEARING AID FITTING | Audiology Programming / Fitting, Hearing Aid Fitting Room, Cerumen Management Room, Speech Language Pathology Assistive Technology Room, Speech Language Pathology Voice Treatment Room | EXAM | -- | CPT | RB | P | -- | -- | 60 | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | -- | 12 S | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Audiology and SLP | AUDIOMETRIC EXAM BOOTH | Audiometric Exam Suite, Exam - Audiometric Booth, : Suite - Audiometric Exam, Hearing/Diagnostics, Booth, 1-Person | EXAM | -- | Pre-Fab | Pre-Fab | Pre-Fab | -- | -- | SEE EQUIP LIST |
tc={3272519D-F8B5-498A-87B1-A9440939E78B}: [Threaded comment]
Your version of Excel allows you to read this threaded comment; however, any edits to it will get removed if the file is opened in a newer version of Excel. Learn more: https://go.microsoft.com/fwlink/?linkid=870924
Comment:
find out how booths are specified and what is the min requirement for VA. Pre-Fab 8'-0" -- 3'-0"
| 3'-6" | Pre-Fab | Pre-Fab | _ | _ | 1 | 2,4 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 9 | -- | P1 | -- | Typically pre-packaged unit including lighting and switching | N/A | L1 | 5 | |||||||||||||||
| Audiology and SLP | ELECTROPHYSIOLOGY | Electrophysiology, Posturography, Vestibulography | EXAM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | P2, P3, P14 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 3 | |
| Dental Service | SPECIALTY EQUIPMENT MECHANICAL ROOM | Dental Equipment Mech. Room, Mechanical Rooms - Electrical | -- | -- | CS | -- | P | -- | -- | 60 | EXP | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 14 S | -- | -- | -- | -- | -- | -- | -- | Exh. (G) | -- | (-) | -- | 2 | -- | P3 | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | 1 | |
| Dental Service | DENTAL PROSTHETICS LABORATORY | Laboratory, Dental Prosthetics | -- | -- | WSF | WSF | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 15 AG | -- | 75 | 70 | 60 | 20 | 6 | 2 | Return |
Exh. (G)
| 45 | (-) | M13 | 7 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 5 | |||||||||||||||||||||||||||||
| Dental Service | DENTAL TREATMENT ROOM | Dental Treatment Room (DTR), Multi-Functional (4/Hygiene), Special Needs Patient, Bariatric | EXAM | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 CS | -- | -- | -- | -- | -- | -- | -- | -- | -- | (+) | -- | 7 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Dental Service | DENTAL X-RAY ROOM | X-Ray Room, Panoramic / Cephalometric (Cone Beam) | CLASS 1 IMAGING ROOM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 17 AGL | 8 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Optometry | FITTING & DISPENSING, EYEGLASSES | Fitting & Dispensing, Eyeglasses | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | 6 | 75 | 70 | 60 | - | 4 | 2 | Return | 40 | NR | -- | 2 | -- | -- | Downlights and accent/display | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Optometry | LOW VISION EXAM/ THERAPY/ TRAINING | Low Vision Exam/ Therapy/ Training | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting. | N/A | 3 | |
| Optometry | PRE-TESTING/ INTAKE | Pre-Testing/ Intake | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | 1 | -- | -- | Multilevel Switching, Dimming & Occupancy | Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting. | N/A | 2 | |
| Optometry | VISUAL FIELDS ROOM | Visual Fields Room, Photography Room, Ultrasound Room, Tomography Room, Imaging Room, OCT Laser | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | _ | _ | 12 S | _ | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Provide dimming and switching to provide various light levels. Provide switching in refraction desk to control overhead lighting. | N/A | 2 | |
| Mental Health | QUIET ROOM | Quiet Room for Patients | EXAM | TREATMENT | CPT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 35 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Mental Health | BIOFEEDBACK TREATMENT ROOM | Biofeedback Treatment Room | EXAM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 15 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Specialty Care Services | PULMONARY FUNCTION ROOM | Pulmonary Function - Analysis | EXAM | TREATMENT | WSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 G | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Specialty Care Services | TREADMILL ROOM | Treadmill Room | EXAM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 MS | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | P9 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Specialty Care Services | EKG TESTING ROOM | EKG Testing Room | EXAM | EXAMINATION | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0 | -- | 3'-6" | Flush | Wood | -- | -- | 12 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Recreation Therapy | GROUP THERAPY ROOM, MUSIC | Creative Arts - Group Therapy Room - Music | -- | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 CG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 8 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Recreation Therapy | GROUP THERAPY ROOM, ART | Creative Arts - Group Therapy Room - Large | -- | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 CG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 8 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Recreation Therapy | WEIGHT ROOM, SMALL | Recreation Therapy Exercise / Weight Room - Small | -- | TREATMENT | RF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 34 AG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 12 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| PHYSICAL THERAPY | PHYSICAL THERAPY GYM | Treatment Exercise Area (includes workstations therapists) | EXAM | TREATMENT | RF | RB | P | -- | -- | SEE FGI | AT | 10'0" | -- | 3'-6" | Flush | Wood | -- | -- | 14 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 14 | -- | P14 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| PHYSICAL THERAPY | Activities Daily Living (ADL) Training | ADL Evaluation and Training Center, Toilet, Tub, Bed, Kitchen, Laundry | EXAM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0 | -- | 3'-6" | Flush | Wood | -- | -- | 15 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| Imaging Services | RADIOLOGY | Radiology, ES: General Purpose Radiology Room | CLASS 1 IMAGING ROOM | TREATMENT | WSF | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 4'-0" | Flush | Wood | -- | LEAD LINED | 15 LS | 8 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 5 | -- | P3, P13 | -- | Fully dimmable, occupancy sensor | N/A | L2 | 2 | |
| Imaging Services | C.T. CONTROL ROOM | CT Control Area, X-Ray - Computed Tomography - Control | -- | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-0" | Flush | Wood | -- | LEAD LINED | 12 LS | -- | -- | -- | -- | -- | -- | -- | -- | 45 | -- | M14 | 6 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| Imaging Services | C.T. EQUIPMENT ROOM | CT Equipment Room, X-Ray - Computed Tomography - Indep View Console | -- | -- | WSF | WSF | P | -- | -- | -- | AT | 9'-0" | 5 | 6'-0" | Flush | Wood | -- | -- | 45 AG | 7 | -- | -- | -- | -- | -- | -- | -- | 50 | -- | M14 | 7 | -- | P3, P13 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Imaging Services | C.T. SCAN ROOM | CT Scanning Room (Ceiling Lift), X-Ray - Computed Tomography - Scanner | CLASS 1 IMAGING ROOM | TREATMENT | WSF | WSF | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 4'-0" | Flush | Wood | -- | LEAD LINED | 15 ALG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3, P13 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Imaging Services | MAMMOGRAPHY SCAN ROOM | Mammo - X-ray, Mammography Room | CLASS 1 IMAGING ROOM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 12 LS | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Imaging Services | RADIOGRAPHIC / FLOURO SCAN ROOM | Radiographic / Fluoroscopic (R/F) Room | CLASS 1 IMAGING ROOM | TREATMENT | WSF | WSF | P | - | - | SEE FGI | AT | 9'-0" | 5 | 3'-6" | Flush | Wood | -- | LEAD LINED | 15 AGL | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3, P13 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Imaging Services | ULTRASOUND SCAN ROOM | Ultrasound Room | CLASS 1 IMAGING ROOM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 12 S | ||||||||||||||||||||
| -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3, P13 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |||||||||||||||||||||
| Imaging Services | PACS SERVER ROOM | X-Ray - Storage - Digital Files, Viewing Room - Picture Archiving and Communication System (PACS) | -- | -- | RFT | RB | P | - | - | - | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 15 GK | -- | -- | -- | -- | -- | -- | -- | -- | 50 | -- | -- | 4 | -- | P3, P13 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| Imaging Services | MRI CONTROL ROOM | MRI Control Room, X-Ray - Magnetic Resonance - Control, MRI Zone 3 | CLASS 1 IMAGING ROOM | EXAM - MRI | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 12 GS | -- | -- | -- | -- | -- | -- | -- | -- | 45 | -- | M14 | 6 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| Imaging Services | MRI EQUIPMENT ROOM | MRI System Component Room, X-Ray - Magnetic Resonance - System Component | -- | TREATMENT | RFT | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | 11 | 4'-0" | Flush | Wood | -- | -- | 35 AG | -- | -- | -- | -- | 40 | -- | -- | -- | 50 | -- | M14 | 7 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Imaging Services | MRI FERROMAGNETIC DETECTION | X-Ray - Magnetic Resonance - Ferromagnetic Detection, MRI Zone 2, MRI Viewing Room | -- | EXAM - MRI | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | 11, 16 | 4'-0" | Flush | Wood | -- | -- | 15 G | -- | 75 | 70 | 60 | 40 | 12 | 2 | Return | 40 | NR | -- | 1 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| Imaging Services | MRI SCAN ROOM | MRI Scanning, X-Ray - Magnetic Resonance - Scanner, | -- | EXAM - MRI | WSF | RB | P | -- | -- | SEE FGI | AT | VARIES | 11,13,16 | 4'-0" | Flush | Wood | -- | R/F Shielded | 1 | -- | 75 | 70 | 60 | 40 | 12 | 2 | Return | ||||||||||||
| Exh. (S) | 50 | NR | M17 | 2 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | MRI rated fixtures | N/A | 1 | ||||||||||||||||||||||||||||
| Imaging Services | READING ROOM | MRI Viewing Room, X-Ray - Magnetic Resonance - Viewing | -- | -- | CPT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 12 GS | -- | -- | -- | -- | -- | -- | -- | -- | 40 | -- | -- | 6 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 6 | |
| Imaging Services | BONE DENSITOMETRY | Bone Densitometer | EXAM | TREATMENT | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 35 S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 7 | -- | P3 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Pathology and Laboratory Medicine | SPECIMEN COLLECTION | Blood Specimen Collection, Alcove - Specimen Collection Point of Care (also for Substance Abuse plus Coumadin), Blood Draw Alcove, Support Area, Laboratory-Satellite, Laboratory-Venipuncture, Blood Draw | EXAM | __ | WSF | WSF | EP | -- | -- | -- | AT | 9'-0" | 3 | -- | _ | _ | _ | _ | _ | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Multi-level switching or manual dimming | N/A | 2 | |
| Pathology and Laboratory Medicine | SPECIMEN ACCESSIONING, PROCESSING & DISTRIBUTION ROOM | Specimen Accessioning, Processing & Distribution Room | LABORATORY WORK ROOM | -- | WSF | WSF | EP | -- | -- | -- | GYP/EP or AT-SP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall, 6' spacing, one adjacent to sink | One at each workstation | -- | -- | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | One at each workstation | |
| Pharmacy Service | PHARMACY | Pharmacy, Pharmacy, PACT 3 (Controlled Substance) (w/3 Auto Dispensing) | PHARMACY | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | -- | 6'-0" | Flush | Metal | - | - | 200 AS | 7 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 15 | -- | P5 | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 9 | |
| Pharmacy Service | PHARMACY DISPENSING WINDOW | Dispense/Consult Window, Workroom, Pharmacist | PHARMACY | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | -- | - | - | - | - | - | - | OPEN | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 12 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 5 | |
| Pharmacy Service | CLEAN ROOM, COMPOUNDING | Pharmacy - Clean Room - Chemotherapy Compounding | -- | -- | RF | RF | P | -- | -- | -- | GWB:P | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | -- | 68 | 68 | 60 | 20 | 30 | 2 | Exh. (S) | 55 | (-) | M12 | 14 | -- | P10 | ||||||
| -- | Multilevel Switching, Dimming & Occupancy | Sealed fixture, flat lens surface on exterior | N/A | 5 | |||||||||||||||||||||||||||||||||||
| Pharmacy Service | IV ADMIXTURE | Pharmacy - IV Admixture - Low Volume | -- | -- | RF | RF | P | -- | -- | -- | GWB:P | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | -- | 68 | 68 | 60 | 20 | 30 | 2 | Return | 55 | (++) | M12 | 14 | -- | P10 | ||||||
| -- | Multilevel Switching, Dimming & Occupancy | Sealed fixture, flat lens surface on exterior | N/A | 5 | |||||||||||||||||||||||||||||||||||
| Pharmacy Service | PRESCRIPTION DISPENSING AREA | Prescription Dispensing Area - OmniCell Station | -- | -- | RF | RF | P | -- | -- | -- | AT | 9'-0" | 3 | -- | -- | -- | -- | -- | - | 6 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 8 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 2 | |
| Pharmacy Service | SECURE STORAGE VAULT | Secure Storage, Vault | CLEAN WORK ROOM/ CLEAN SUPPLY | -- | RFT | RB | P | RWC | 4'-0" | -- | GWB:P | 9'-0" | -- | 3'-0" | Flush | Hollow Metal | -- | -- | 1 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| Pharmacy Service | ANTEROOM | Anteroom, Compound Sterile Preparation | -- | -- | WSF | WSF | EP | -- | -- | -- | GWB:SP | 9'-0" | 3 | 7'-0" | Single Slide Auto Sliding Door | Aluminum/ Glass | Yes | -- | 850 | -- | 68 | 68 | 60 | 20 | 30 | 2 | Return | 55 | (+) | M12 | 2 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Sealed fixture, flat lens surface on exterior | N/A | -- | |
| Business Office | SECURE CASH ROOM | Secure Money Handling Room | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0 | -- | 3'-0" | Flush w/ 1-Way Viewer | Steel | -- | -- | 200 GV | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel switching/dimming/occupancy | N/A | N/A | 1 | |
| Engineering | BIOMED. REPAIR SHOP | Repair Shop, Biomedical Eng. | -- | -- | RF | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 35 AG | -- | -- | -- | -- | -- | -- | -- | Exh. (G) | -- | (-) | M7 | 10 | -- | P4, P6 | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | 2 | |
| Logistics | LOADING DOCK | Receiving/ Shipping Dock | -- | -- | CS | RB | EP | -- | -- | -- | EXP. | -- | 8 | 6'-0" | Flush | Wood | -- | -- | 44 APW | 7 | - | 60 | - | - | -- | -- | Exh. (G) | -- | (+) | M5 | 2 | -- | -- | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | 2 | |
| Logistics | MAIL ROOM | Support: Mail Room and Dist. Center, Mailing Room - Prosthetic Appliances | -- | -- | RF | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 15 G | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| Logistics | GAS CYLINDER STORAGE | Storage - Gas Cylinders - MRI, Storage - Gas Cylinders - Interior | -- | -- | WSF | RB | P | RWC | 4'-0" | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | 45 MIN | 34 G | -- | -- | -- | -- | -- | -- | -- | Exh. (S) | ||||||||||||
| -- | (-) | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |||||||||||||||||||||||||||||
| Logistics | BIO-HAZARD STORAGE | Storage - Bio Hazardous Material, Storage - Hazardous Material, Infectious / Hazardous Waste | REGULATED WASTE | -- | WSF | WSF | EP | RWC | 4'-0" | -- | GWB:SP | 9'-0" | 3 | 3'-6" | Flush | Hollow Metal | -- | -- | 34 G | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| Logistics | STORAGE WAREHOUSE | Bulk Storage, General Storage, Warehouse | CLEAN WORKROOM/CLEAN SUPPLY | -- | CS | RB | P | -- | -- | -- | Exp | 10'-0" | -- | 6'-0" | Flush | Wood | -- | -- | 45 AG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | minimum, 1 per wall, not to exceed 12' spacing | -- | -- | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | -- | |
| Logistics | BREAK DOWN | Break Down | CLEAN WORKROOM/CLEAN SUPPLY | -- | RPT | RB | EP | -- | -- | -- | AT | 9'-0" | 8 | 4'-0" | Flush | Wood | -- | -- | 34 AG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | -- | |
| Police Service | POLICE HOLDING ROOM | Holding Room | -- | -- | CS | RB | P | -- | -- | -- | GWB-PT | 9'-0" | 3,15 | 3'-6" | Flush | Hollow Metal | Half Glass w/ Laminated Glass | -- | 18 P | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 0 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Tamperproof fixture design | N/A | -- | |
| Police Service | OPERATIONS ROOM | Operations Room | -- | -- | RFT | RB | P | -- | -- | 40 | AT | 9'-0" | -- | 3'-6" | Flush | Hollow Metal | -- | -- | 200 APS | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | M15 | 0 | 8 | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 4 | |
| Police Service | SECURE STORAGE | Small Arms Armory, Storage - Secure | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush | Hollow Metal | -- | -- | 200 P | -- | 75 | 70 | 60 | - | 4 | 2 | Return | NR | NR | -- | 1 | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | N/A | N/A | 1 | |
| VCS | RETAIL AREA | Retail Area | -- | EXAM - PUBLIC SPACE | RFT | RB | P | -- | -- | SEE FGI | AT | 9'-0 | 17 | 6'-0" | Flush w/ Full Vision | Wood | Full Vision | -- | 47 KM | 7, 9 | -- | -- | -- | -- | -- | -- | -- | -- | -- | M4 | One per wall, 6' spacing | -- | -- | -- | Multilevel Switching, Dimming & Occupancy | Track or adjustable accent lighting for retail displays. | L5 | 3 | |
| OI&T | TELECOMMUNICATIONS ROOM | Telecommunications Room/ Closet, IT Telecommunications Room | -- | -- | RFT | RB | P | -- | -- | -- | EXP. | 12'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 34 AS | -- | 75 | 64 | 55 | 30 | - | - | - | - | NR | -- | 6 | -- | P15 | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | -- | |
| OI&T | MAIN COMPUTER ROOM | Central Server Room, Server Room, Main Computer Room | -- | -- | RFT | RB | P | -- | -- | -- | EXP. | 12'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 34 AS | -- | 81 | 72 | 60 | 30 | -- | -- | -- | -- | -- | M8 | 10 | -- | P15 | Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | -- | |
| OI&T | I.T. WORKROOM | IT Workroom, Equip. Configuration/ Repair | -- | -- | RFT | RB | P | -- | -- | -- | AT | 9'-0" | -- | 3'-0" | Flush | Wood | -- | -- | 35 AG | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 10 | -- | P4, P6 | ||||||
| Surface or chain mounted 1' x 4' | Occupancy/vacancy | N/A | N/A | 8 | |||||||||||||||||||||||||||||||||||
| SPS | ANTEROOM, SOILED TRANSITION | Anteroom, Soiled Transition/Drop-Off | DECONTAM | ||||||||||||||||||||||||||||||||||||
| ROOM | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 72 | 60 | 30 | 10 | 10 | Exhaust (G) | 40 | (-) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 2 | ||||
| SPS | DECONTAMINATION ROOM | Decontamination Work Room, Scope Decontamination Room | DECONTAM | ||||||||||||||||||||||||||||||||||||
| ROOM | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 72 | 60 | 30 | 6 | 6 | Exhaust (G) | 40 | (--) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 4 | ||||
| SPS | Cart Wash | Cart Wash | -- | -- | RES | RES | CT | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 70 | 75 | -- | -- | 10 | 10 | Exhaust (S) | 40 | (-) | M18, M19 | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | -- | |
| SPS | Water Treatment Storage Room | Water Treatment Storage Room | -- | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush | Steel | -- | -- | 15 AG | -- | 70 | 75 | -- | -- | 10 | 10 | Exhaust (G) | 40 | (-) | M18, M19 | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 1 | |
| SPS | REPROCESSING ROOM, SCOPE | Reprocessing Room, Scope | -- | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 72 | 60 | 30 | 6 | 6 | Exhaust (G) | 40 | (-) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 2 | |
| SPS | Instrument Assembly | Instrument Assembly | -- | -- | WSF | WSF | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 72 | 60 | 30 | 4 | 4 | Exhaust (G) | 40 | (++) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 4 | |
| SPS | Sterilization Area | Steam Sterilization Area, Low Temp Sterilization Area | -- | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 75 | 60 | 30 | 10 | 10 | Exhaust (G) | 40 | (++) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 2 | |
| SPS | Cooling Area | Cooling Area | -- | -- | RES | RES | EP | -- | -- | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | 15 AG | -- | 66 | 75 | 60 | 30 | 10 | 10 | Exhaust (G) | 40 | (++) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 1 | |
| SPS | Equipment Room, Steam Generator | Equipment Room, Steam Generator | -- | -- | RFT | RB | EP | -- | -- | -- | ACT-SP | 9'-0 | 3, 7 | 3'-6" | Flush | Steel | -- | -- | 15 AG | -- | 85 | -- | -- | -- | 10 | 10 | Exhaust (G) | 45 | (-) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | -- | |
| SPS | Clean Dispatch | Clean Dispatch | -- | -- | RFT | RB | EP | -- | -- | -- | ACT-SP | 9'-0 | 3, 7 | -- | -- | -- | -- | -- | -- | -- | 70 | 75 | 60 | 30 | 4 | 4 | Exhaust (G) | 40 | -- | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | 1 | |
| SPS | STORAGE, CLEAN SCOPE | Storage, Clean Scope | CLEAN SUPPLY | -- | RES | RES | EP | RWC | 4'-0" | -- | GYP-EP | 9'-0 | 3, 7 | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 15 AG | -- | 66 | 75 | 55 | 30 | 4 | -- | -- | -- | (+) | -- | One per wall | -- | -- | 2 X 2 recessed lensed | Multilevel Switching, Dimming & Occupancy | Gyp ceiling - lights to be sealed type/flange mounted | N/A | -- | |
| CLC/Small House (House) | RESIDENT BATHROOM | Patient Toilet/Shower - Residential; Toilet | Toilet/Bathing Room | Resident Room/Dwelling Unit | PT/CT or poured epoxy | PT / CT or integral epoxy | GWB P/ CT | PT / CT | -- | STC 45 | GWB P | 9'-0 | Grab bars need to be provided at the toilet | 3'-6" | Barn/Sliding | Wood - no Lite | -- | -- | 11 | Sliding Pull | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | F1, F2, F3 | Occupancy | N/A | Coordinate lighting with plumbing fixtures, vanities & wall-mounted equipment | 0 | |
| CLC/Small House (House) | RESIDENT BEDROOM | Patient Room Residential; Transitional Rehab Resident Bedroom | Resident Room | Resident Room/Dwelling Unit | RFT | PRB / RB | GWB P | -- | -- | STC 45 | GWB P | 9'-0 | -- | 4'-0" | Flush | Wood - no Lite | -- | -- | 17S | -- | 75 | 70 | 60 | 30 | 4 | 2 | Return | 35 | (o) | -- | 6 | -- | -- | F4, F5, F6 | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | 2 | |
| CLC/Small House (House) | LIVING ROOM | Day Room | Resident Living | Community Space | CPT/ LRT/ RSF | PRB / RB | GWB P / Wood / Tile / Stone | -- | -- | -- | GWB P | 10'-0 | -- | -- | -- | -- | -- | -- | -- | -- | 75 | 70 | 60 | 30 | 4 | 2 | Return | 40 | (o) | Provide a project-specific unoccupied mode for unoccupied hours | 4 (incl. 2 floor mount) | -- | -- | F7, F4, F5, F8, F6 | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | 0 | |
| CLC/Small House (House) | DINING ROOM | Canteen | Resident Dining | Community Space | PT/ LRT/ PT/ CT/ Wood/ RSF | PT / PRB / Wood | GWB P / Wood | -- | -- | -- | GWB P | 10'-0 | -- | 3'-6" (if any) | Flush (if any) | Wood (if any) | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 2 (incl. 2 floor mount) | -- | -- | F7, F4, F8, F9, F10 | Multilevel Switching (CFL), Dimming (LED) | Local controls accessible by staff only. Lamps must be fully-enclosed by luminaire | N/A | 1 | |
| CLC/Small House (House) | KITCHEN | Canteen; Kitchen & Servery | -- | Community Space | PT/ LRT/ ET/ Tile or Wood | PT/ PRB | GWB P | -- | -- | -- | GWB P | 10'-0 | -- | None (open room) | None (open room) | -- | -- | -- | -- | -- | 75 | 70 | 60 | -- | 6 | 2 | Exhaust (G) & (S) | 40 | (-) | Kitchen Hood Exhaust, comply with applicable version of NFPA 101 | 14 | -- | One dedicated receptacle per stove and one per oven | F7, F4, F8, F9, F10 | Multilevel Switching (CFL), Dimming (LED) | Lamps must be fully-enclosed by luminaire | N/A | 1 | |
| CLC/Small House (House) | DEN | Office | -- | Community Space | CPT/ LRT / Carpet | PCT/ PRB | GWB P | -- | -- | STC 45 | GWB P | 9'-0 | -- | 3'-6" | French with blinds & side lite | Steel w/ lite | -- | -- | 12S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 5 | -- | -- | F7, F11, F12, F13 | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | 1 | |
| CLC/Small House (House) | LAUNDRY | Laundry Room; Residential Rehab Treatment Program - Living Area, Dining Area, Kitchenette | Laundry | -- | RT/ RSF | RB/ PRB | GWB P | -- | -- | STC 45 | ACT | 9'-0 | -- | 4'-0" | Flush | Wood - no Lite | -- | -- | 12KS | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | One dedicated outlet per dryer | F1, F13 | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | 0 | |
| CLC/Small House (House) | BATHING ROOM | Bathing Suite; Patient Toilet/Shower | -- | Toilet Room | CT/ PT | CT/ PT | GWB P/ CT | CT / PT | -- | STC 45 | GWB P | 9'-0 | Grab bars need to be provided at the toilet | 3'-6" (toilet) |
| 4'-0 (shower) | Flush | Wood - no Lite | -- | -- | 11 | -- | 75 | 82 | 60 | -- | 10 | 2 | Exhaust (S) | 40 | (-) | -- | 5 | -- | -- | F1, F2, F3 | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | 0 | |||||||||||||||
| CLC/Small House (House) | FOYER | -- | -- | Corridor (with entrance) | PT/ LRT | PT/ PRB | GWB P | -- | -- | -- | GWB P | 9'-0 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 2 min. | -- | -- | -- | Multilevel Switching (FL), Dimming (LED) | N/A | N/A | -- | |
| CLC/Small House (House) | CORRIDOR / SITTING ALCOVE | Primary Corridor | -- | Corridor | CPT/ LRT | PRB | GWB P | -- | -- | -- | GWB P | 9'-0 | -- | -- | None (open room) | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | Per NEC | -- | -- | F7, F4, F8, F5 | Multilevel Switching (CFL), Dimming (LED) | N/A | Refer to NFPA 101 for egress lighting requirements | 1 | |
| CLC/Small House (House) | PANTRY | Canteen | Dietary Storage | -- | PT/ LRT/ ET | PT/ PRB | GWB P | -- | -- | -- | ACT | 9'-0 | -- | 3' 0" | Flush | Wood | -- | -- | 14 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | 2 X 4 recessed lensed, efficient lighting | Multilevel Switching (CFL), Dimming (LED) | N/A | N/A | -- | |
| CLC/Small House (House) | GARAGE / RECEIVING | Maintenance Garage; Loading Dock | -- | -- | RT/ RSF/ EP | RB/ EP | GWB P | -- | -- | -- | GWB P | 10'-0 | -- | 3'-6 (passage) |
| 10'-0 (roll up) | Flush | Steel | -- | -- | 14 | -- | -- | 60 | 60 | 15 | -- | 1 | Exhaust (S) | 50 | (-) | Ref. VA HVAC Design Guide | One per wall | -- | -- | F14, F15, F19 | Multilevel Switching (FL), Dimming (LED) & Occupancy | N/A | If industrial lights, provide lap shield or guard. | -- | |||||||||||||||
| CLC/Small House (House) | HOUSE STAFF OFFICE | Offices; Administrative Office; Home Office | -- | -- | CPT | PRB/ RB | GWB P | -- | -- | STC 35 | ACT | 9'-0 | -- | 3'-6" | French with blinds & side lite | Wood | Narrow Vision | -- | 12S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | F14, F11, F12, F13, 2 x 2 CLF | Multilevel Switching (FL), Dimming (LED) | N/A | Under-cabinet task lights and desk lights shall be controlled with integrated switches. | 4 | |
| CLC/Small House (Neighborhood) | NEIGHBORHOOD CENTER LOBBY | Main Entrance Lobby; Main Lobby | Resident Living | Community Space | PT/ LRT | PT/ PRB | GWB P | -- | -- | -- | GWB P | 9'-0 min. | -- | 3'-6" | Flush w/ Narrow Vision | Steel | Narrow Vision | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall min. | -- | -- | F4, F7, F8, F9 | Multilevel Switching (FL), Dimming (LED) | N/A | Wall-mounted sconces must be ADA compliant. |
Consider luminaire maintenance requirements when locating luminaires in high ceilings.
| Local controls shall only be accessible to staff. | 1 per workstation plus 1 for lobby | ||||||||||||||||||||||||||||||||||||||
| CLC/Small House (Neighborhood) | MULTIPURPOSE ACTIVITY ROOM | Multipurpose Room | Resident Activity | Community Space | CPT/ LRT | PRB | GWB P | -- | -- | STC 45 | ACT-SP | 10'-0 | -- | 4'-0" w/ 2'-0 leaf | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 10 | -- | -- | F7, F4, F8 | Multilevel Switching (FL), Dimming (LED) | N/A | -- | 6 | |
| CLC/Small House (Neighborhood) | MULTIPURPOSE ACTIVITY STORAGE | Multipurpose Storage; Storage | -- | -- | RT | PRB | GWB P | -- | -- | STC 30 | ACT-SP | 8'-0 | -- | 3'-6" | Flush | Wood | -- | -- | 14 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 1 | -- | -- | F14, F15, F16 | Multilevel Switching (FL), Dimming (LED) | N/A | If industrial fixtures, provide with lamp shield or guard | -- | |
| CLC/Small House (Neighborhood) | CONFERENCE ROOM | -- | -- | -- | CPT | PRB | GWB P | -- | -- | -- | GWB P | 9'-0 min. | -- | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall min. | -- | -- | F7, F4, F17, F18 | Multilevel Switching (FL), Dimming (LED) | N/A | Consider luminaire placement and optics to mitigate glare and veiling reflections especially at presentation screen. | 2 | |
| CLC/Small House (Community Center) | COMMUNITY CENTER LOBBY | Main Entrance Lobby; Main Lobby | Resident Living | Community Space | PT/ LRT | PT/ PRB | GWB P | -- | -- | -- | GWB P | 9'-0 min. | -- | 4'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall min. | -- | -- | F4, F7, F8, F9 | Multilevel Switching (FL), Dimming (LED) | N/A | Wall-mounted sconces must be ADA compliant. |
Consider luminaire maintenance requirements when locating luminaires in high ceilings.
| Local controls shall only be accessible to staff. | 1 per workstation plus 1 for lobby | |||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | CONCIERGE STATION | -- | -- | -- | CPT | PRB | GWB P | -- | -- | STC 35 | GWB P | 9'-0 | -- | None (open room) | None (open room) | Wood (if any) | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 9 | -- | -- | F4, F7, F8, F9 | Multilevel Switching (FL), Dimming (LED) | N/A | Wall-mounted sconces must be ADA compliant. |
Consider luminaire maintenance requirements when locating luminaires in high ceilings.
| Local controls shall only be accessible to staff. | 3 | ||||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | GREAT ROOM | Multi-Purpose Activity Room | Resident Activity | Community Space | CPT | PRB/ RB | GWB P | -- | -- | STC 35 | GWB P | 12'-0 (or taller) | -- | 3'-6" double doors (if any) or cased openings | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 11 | -- | -- | F7, F4, F8 | Multilevel Switching (FL), Dimming (LED) & Occupancy | N/A | N/A | 1 | |
| CLC/Small House (Community Center) | RETAIL STORE | Gift Shop (Retail Store); Veterans Canteen Service and Gift Store | Resident Activity | Community Space | LRT/ CPT | PRB | GWB P | -- | -- | STC 35 | ACT | 9'-0 | -- | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | As needed per retail layout; minimum one per wall | -- | -- | F7, F4, F8, F20 | Multilevel Switching (FL), Dimming (LED) | N/A | Coordinate general and accent lights with merchandise displays |
| Local controls shall only be accessible to staff. | As needed per retail layout; minimum 1 per cash register | |||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | POST OFFICE | Mailroom, Lgstcs Service; Mail Rooms; | Resident Activity | Community Space | RT/ CPT | PRB | GWB P | -- | -- | STC 35 | ACT | 9'-0 | -- | 4'-0" | Flush | Wood | -- | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall plus min. one per work station (if any) | -- | -- | F14, F15, F19 | Multilevel Switching (FL), Dimming (LED) | N/A | If using industrial fixtures, provide lamp with shield or guard. |
Coordinate luminaire placement with overhead cabinets & shelving. Do not install luminaire directly above.
| Coordinate luminaire placement with equipment. | 1 per workstation min. | |||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | THEATER | Auditoriums & Theaters | Resident Activity | Community Space | CPT/ LRT | PRB | GWB P | -- | -- | STC 45 | ACT | 10'-0 | -- | 4'-0" | Flush | Wood | -- | -- | 13S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | See Lighting Notes | See Lighting Notes | N/A | No guideline reference. Use Illumination levels as a guide. A/E shall follow the most appropriate lighting guidance based on area/ room function, latest code requirements, industry and professional design practices. |
Vary illumination levels by dimming control devices in accordance with specific
| project requirements. | 1 | |||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | LIBRARY | -- | Resident Activity | Community Space | CPT | PRB | GWB P | -- | -- | STC 30 | ACT | 10'-0 | -- | 4'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 4 | -- | -- | See Lighting Notes | See Lighting Notes | N/A | No guideline reference. Use Illumination levels as a guide. A/E shall follow the most appropriate lighting guidance based on area/ room function, latest code requirements, industry and professional design practices. |
Vary illumination levels by dimming control devices in accordance with specific
| project requirements. | 3 | ||||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | HAIR CARE SALON | Hair Care (Barber/Beauty Salon); Barber Shop | Hair Salon | Community Space | LRT/ RSF | PRB | GWB P | -- | -- | STC 35 | ACT | 10'-0 | -- | 4'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | At least 1 per work station (min 1 per wall) | -- | -- | F7, F1, F2 | Multilevel Switching (FL), Dimming (LED) | N/A | Coordinate luminaires with equipment and vanities. | 1 | |
| CLC/Small House (Community Center) | MEDITATION CHAPEL | Chapel/Meditation/Quiet Room; Chapel | Resident Activity | Community Space | CPT | PRB | GWB P | -- | -- | STC 45 | GWB P | 10'-0 | -- | 3'-6" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13S | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall | -- | -- | See Lighting Notes | See Lighting Notes | N/A | No guideline reference. Use Illumination levels as a guide. A/E shall follow the most appropriate lighting guidance based on area/ room function, latest code requirements, industry and professional design practices. |
Vary illumination levels by dimming control devices in accordance with specific
| project requirements. | -- | ||||||||||||||||||||||||||||||||||||||
| CLC/Small House (Community Center) | PT / OT EXERCISE GYM | Rehabilitation Therapy Gym; Physical/Occupational Therapy | Physical Therapy | -- | RBS | RB | GWB P | -- | -- | -- | ACT | 10'-0 | -- | 3'-6 double doors | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | 6 | -- | -- | F7, F4, F8, F17, F13 | Multilevel Switching (FL), Dimming (LED) | N/A | Under-cabinet task lights shall be controlled with integrated switches. | 1 | |
| CLC/Small House (Community Center) | TEAM WORKROOM | Multi-purpose Room; Team/Break Room | -- | -- | CPT | PRB/ RB | GWB P | -- | -- | -- | ACT | 9'-0 | -- | 3'-6" | Flush | Steel | -- | -- | 13 | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | One per wall min. | -- | -- | F7, F4, F17, F8, F13 | Multilevel Switching (FL), Dimming (LED) | N/A | Under-cabinet task lights and desk lights shall be controlled with integrated switches. | 1 min. | |
| DIGESTIVE DISEASES - ENDOSCOPY SERVICE | Endoscopy Procedure | Procedure Room, Endoscopy | Endoscopy Procedure | Procedure | WSF | WSF | GWB SC | -- | -- | -- | AT SP | 9'-0" | -- | 4'0" | Flush | Wood | -- | -- | 13AHS | -- | 68 | 73 | 50 | 30 | 10 | 2 | Exhaust (G) | 35 | (o) | -- | 7 | 1 | Ceiling Mounted Boom | ALL LEDs |
Two (2) Fixtures (2'x4')
| Ten (10) recessed can, down lights (dimmable) | Dimming (LED) | Variable 10-100fc | Under Cabinet Light. Room 3500k | 3 min on walls, Ceiling Mounted Boom, wall mounted telephone | ||||||||||||||||||||||||||||
| DIGESTIVE DISEASES - ENDOSCOPY SERVICE | Endoscopic Ultrasound Procedure | Procedure Room, ERCP/Endoscopic | ||||||||||||||||||||||||||||||
| Ultrasound | Endoscopy Procedure | Procedure | WSF | WSF | GWB SC | -- | -- | -- | AT SP | 9'-0" | -- | 4'-0" | Flush | Wood | -- | -- | 13AHS | -- | 68 | 73 | 60 | 30 | 6 | 2 | Return | 35 | (o) | -- | 7 | 1 | Ceiling Mounted Boom | ALL LEDs |
Two (2) Fixtures (2'x4')
| Ten (10) recessed can, down lights (dimmable) | Dimming (LED) | Variable 10-100fc | Under Cabinet Light. Room 3500k | 4 min on walls, Ceiling Mounted Boom, wall mounted telephone | |||||||||||||||||||||||||||||||
| DIGESTIVE DISEASES - ENDOSCOPY SERVICE | Scope Reprocess | Reprocessing Room, Scope | Instrument Processing room | -- | WSF | WSF | GWB SC | S | 5'-0" | -- | AT SP | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 34S | -- | 66 | 72 | 60 | 30 | 10 | 10 | Exhaust (G) | 40 | (-) | -- | 6 | -- | Washer equipment may require hardwired connections. | ALL LEDs | |
| Two (2) Fixtures (2'x4'), Gasketed Lens | -- | -- | -- | 2 min, wall mounted telephone | |||||||||||||||||||||||||||||||
| DIGESTIVE DISEASES - ENDOSCOPY SERVICE | Prep and Recovery | Prep / Recovery Room | Pre-procedure patient care room | -- | WSF | WSF | GWB P | RWC | 4'-0" | -- | AT SP | 9'-0" | -- | 8'-0" | Sliding | Glass | Glass | -- | Push/Pull | -- | 75 | 70 | 60 | 30 | 6 | 2 | Return | 35 | (0) | -- | 7 | -- | -- | Two (2) 1'x4' | |
| One (1) recessed can | -- | -- | Patient Control for Multi-Function and Down Light | ||||||||||||||||||||||||||||||||
| Fixtures | 2 min, wall mounted telephone | ||||||||||||||||||||||||||||||||||
| SURGICAL SUITE | Pre-Operative Holding / Phase II Recovery Patient Bay | Patient Bay, Pre-Operative | |||||||||||||||||||||||||||||||||
| Holding / Phase II Recovery | Phase II recovery | -- | WSF | WSF | GWB SC | -- | -- | -- | AT SP | 9'-0" | -- | -- | Curtain | -- | -- | -- | -- | -- | 75 | 70 | 60 | 30 | 6 | 2 | Return | 35 | (+) | M28 | 8 | -- | emergency power required | -- | -- | VA Lighting Design Manual section |
4.2.15 - Pre-Operative and Post- Anesthetic Care
| (PACU) | -- | 2 min, wall mounted telephone | ||||||||||||||||||||||||||||||||
| SURGICAL SUITE | Pre-Operative Holding / Phase II Recovery Patient Room | Patient Room, Pre-Operative | ||||||||||||||||||||||||||||||||
| Holding / Phase II Recovery | Phase II recovery | Exam | WSF | WSF | GWB SC | -- | -- | 35 | AT SP | 9'-0" | -- | 8'-0" | Sliding | Glass | Glass | -- | Push/Pull | -- | 75 | 70 | 60 | 30 | 6 | 2 | Return | 35 | (+) | M28 | 8 | -- | emergency power required | -- | -- | VA Lighting Design Manual section |
4.2.15 - Pre-Operative and Post- Anesthetic Care
| (PACU) | -- | 2 min, wall mounted telephone | ||||||||||||||||||||||||||||||||||||
| SURGICAL SUITE | Anesthesia Clean Room | Clean Workroom, Anesthesia | -- | -- | RES | RES | GWB SC | -- | -- | -- | GWB SC | 9'-0" | -- | 3'-6" | Flush | Wood | -- | -- | 34S | -- | 75 | 70 | 60 | 30 | 6 | 2 | Return | 40 | (o) | Individual room control | 6 | -- | -- | -- | -- | -- | Anesthesia Work Room has similar lighting |
design consideration as Exam & Treatment Room. Refer to the VA Lighting Design Manual
| section 4.2.1 - Examination and Treatment Room - for lighting design consideration. | 3 min. | ||||||||||||||
| SURGICAL SUITE | General Operating Room | Orthopedic Operating Room, Urology / Cystoscopy Operating Room, Cardiothoracic Operating Room, Cardiothoracic / Hybrid OR pump Room, Neurosurgical Operating Room, Robotics Operating Room, Transplant Operating Room, Monoplane Hybrid Operating Room, Biplane Hybrid Operating Room | Operating Room | Operating Room | RES | RES | GWB SC | -- | -- | -- | GWB SC | 10'-0" | -- | Double 6'-0" -------------- | |
| Single 4'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 43LS |
33AHLS -- 66 75 60 30 20 4 Return 40 (++) M20 17 -- Normal Power: Connect selected receptacles and equipment to Normal power IPS.
Emergency Power: Connect selected receptacles and equipment to Critical Branch emergency IPS.
Provide Isolation Power Supply, Lazer receptacle, connections for articulating utility columns.
| -- | -- | -- | Refer to the VA Lighting Design Manual section 4.2.13 - Surgery/Operating Room - for lighting design consideration. | 3 min, wall mounted telephone | |||||||||||
| SURGICAL SUITE | Hybrid OR Control Room | -- | -- | -- | RES | RES | GWB SC | -- | -- | -- | GWB SC | 9'-0" | -- | 3'-0" | |
| -------------- 3'-0" | Flush w/ Narrow Vision | Wood | -- | -- | 33AHLS | ||||||||||
| --------------- 43LS | -- | 75 | 70 | 60 | 30 | 8 | 2 | Return | 40 | (o) | VAV, individual room control. | ||||
| Unoccupied ACH 4 | 7 | -- | Emergency Power: Critical branch of the EES to be connected to selected receptacles and equipment. Notes: |
1) Provide a duplex receptacle per computer
| and location connected to Emergency. 2) Provide convenience duplex receptacle on normal power. | -- | -- | -- | Refer to the VA Lighting Design Manual section | |||||||||||
| 4.2.13 – Surgery/Operating Room – Design Parameter – Control Room - for lighting design consideration. | 6 min. | ||||||||||||||
| SURGICAL SUITE | Cardiac Catheterization Laboratory | -- | Laboratory work room | Procedure | RES | RES | GWB SC | -- | -- | -- | GWB SC | 10'-2" | -- | Double 6'-0" -------------- | |
| Single 4'-0" | Flush w/ Narrow Vision | Wood | Narrow Vision | -- | 43LS |
| 33AHLS | -- | 66 | 75 | 60 | 30 | 20 | 4 | Return | 40 | (++) | M21 |
| Unoccupied ACH 10 | 24 | -- | Emergency Power: |
Connect selected recep tacles and equipment to Normal power IPS.
Connect selected recep tacles and equipment to Critical Branch emergency
IPS.
Notes:
1) Provide IPS power & ground modules – 3 duplex receptacles & 3 ground jacks 2) IPS Power & ground modules mounted at +24” AFF
3) Provide Laser Receptacle Module. Module shall be connected to Special Equipment IPS located outside the Surgery Room. 4)Provide power connections for articulating utility columns. -- -- -- Refer to the VA Lighting Design Manual section
4.2.13 - Surgery/Operating Room - for lighting
| design consideration. | 11 min |