This document is a product specification and performance data sheet for Titus PESV, AESV, and DESV single/dual duct terminal units used in HVAC systems.

The document provides comprehensive performance data for variable air volume (VAV) terminal units across multiple inlet sizes (4 through 24x16) and operating conditions. Key specifications include recommended primary air CFM ranges stratified by control type (pneumatic Titus II and I controllers, analog electronic TA1 controller, and digital electronic controllers), with minimum and maximum airflow settings documented for each control configuration. Radiated and discharge sound performance data are presented in octave band sound power levels (dB) across four static pressure drop conditions (0.5" to 2.0" ΔPs), with NC (noise criteria) ratings provided. Hot water heating coil capacity tables specify MBH (thousands of BTU per hour) outputs for 1-row through 4-row coil configurations across various airflow rates, water flow rates (gpm), and head loss specifications. Electric heating coil selection data document available kW capacities across six voltage configurations (120V, 208V, 240V, 277V single-phase and 208V/480V three-phase) for staged heat and Lynergy heat options, with minimum airflow limits and thermal rise constraints specified. AHRI certified performance ratings are provided for select unit sizes at standard test conditions including rated CFM at 2000 fpm inlet velocity, minimum static pressure drop, and 1.5 in wg operating pressure. The document includes correction factors for hot water coil performance at temperature differentials other than the standard 125°F condition and establishes maximum recommended heating capacities to prevent thermal stratification and nuisance thermal cutout activation.

View the file

Other files

File Type Posted
250063_ATT 14_Prebid RFI Responses Round 2.pdf PDF
250063_ATT 9_SOW.pdf PDF
250063_ATT 6_OPSEC Review Memo.pdf PDF
2020 TAFB Facility Standard.pdf PDF
250063_SOW.pdf PDF
23 09 23.02.pdf PDF
22 00 00.pdf PDF
23 31 13.00 40.pdf PDF
09 67 23.15.pdf PDF
23 03 00.pdf PDF
10 14 00.20.pdf PDF
05 40 00.pdf PDF
23 64 26.pdf PDF
00 72 00.pdf PDF
01 78 00.pdf PDF
01 45 00.00 10.pdf PDF
01 32 16.00 20.pdf PDF
00 80 05.pdf PDF
00 80 00.pdf PDF
ufc_3_535_01_2017_c4.pdf PDF
ufc_3_600_01_2016_c6.pdf PDF
dafi21-101.pdf PDF
ufc_3_260_04_2018.pdf PDF
dafi13-213_tinkerafbsup.pdf PDF
007200_Attch13_AF487.pdf PDF
013300_Attch1_TAFBF3000.pdf PDF
HELICAL PILES NOTES.docx DOCX document
Door_Window_Schedule.xlsx XLSX spreadsheet
PILE SCHEDULE.xlsx XLSX spreadsheet
esvEH_singledual_2023_V2.pdf PDF
REACT VII SA-01.pdf PDF
lk406gn05t4_spec.pdf PDF
TAFB B9001 VAV Schedule.pdf PDF
ARCH-COMBINED.pdf PDF
250063_ATT 13_Prebid RFI Responses Round 1.pdf PDF
250063_ATT 8_Liquidated Damages.pdf PDF
250063_ATT 4_ODS.pdf PDF
2026 TAFB Mechanical Standard_signed.pdf PDF
2026 TAFB FIRE PROTECTION STANDARD.pdf PDF
SOW Att 04_Automated Casting Cell.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
250063_ATT 10_Submittal Register.pdf PDF
23 00 00.pdf PDF
08 11 13.pdf PDF
08 33 23.pdf PDF
10 22 13.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 71 00.pdf PDF
01 33 00.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Re de fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

.c om single / dual duct terminals

M16

M

PERFORMANCE DATA

RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS

Control Types:

PESV / Pneumatic AESV / Analog Electronic DESV / Digital Electronic

QUICK SELECTION PROCEDURE

1. Select unit inlet size based upon acoustic parameters and/ or maximum pressure drop requirements, using pages M15-M16

2. Check inlet size selection against cfm control limits based on control type shown on this page

3. Select accessories (multi-outlets, attenuators) as required

4. Select reheat coil, if required. Make your selection using the actual heating flow rate, not cooling.

Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls mounted on an FMA basis are calibrated in the field.

PE

RF

OR

M

AN

CE

D

AT

A

Inlet Size Total CFM

Range

CFM Ranges of Minimum and Maximum Settings

PESV - Pneumatic

Titus II Controller

PESV - Pneumatic

Titus I Controller

AESV - Analog Electronic

TA1 Controller

DESV - Digital

Typical Controller

Minimum Maximum Minimum Maximum Minimum Maximum Minimum Maximum

4 0-225 50-210 90-225 65-210 90-225 50-225 50-225 30-225 30-225

5 0-350 70-300 125-350 90-300 125-350 70-350 70-350 40-350 40-350

6 0-500 80-345 145-500 100-345 145-500 80-500 80-500 45-500 45-500

7 0-650 120-515 210-650 150-515 210-650 120-650 120-650 70-650 70-650

8 0-900 160-700 285-900 205-700 285-900 160-900 160-900 90-900 90-900

9 0-1050 205-900 370-1050 260-900 370-1050 205-1050 205-1050 120-1050 120-1050

10 0-1400 250-1110 455-1400 325-1110 455-1400 250-1400 250-1400 145-1400 145-1400

12 0-2000 330-1460 600-2000 425-1460 600-2000 330-2000 330-2000 190-2000 190-2000

14 0-3000 525-2335 955-3000 675-2335 955-3000 525-3000 525-3000 300-3000 300-3000

16 0-4000 665-2970 1215-4000 860-2970 1215-4000 665-4000 665-4000 385-4000 385-4000

24 X 16 0-8000 1245-5555 2270-8000 1605-5555 2270-8000 1245-8000 1245-8000 720-8000 720-8000 www.

Redefine your com fort zone. ™

| w w w .titus-hvac.com

M17

M

PERFORMANCE DATA

PESV, AESV, DESV / RADIATED SOUND PERFORMANCE

• Radiated sound is the noise transmitted through the unit casing
• Min ΔPs is the static pressure drop from the unit inlet to the unit

outlet with primary damper full open

• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density

fiberglass lining

• All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011

• All NC levels determined using AHRI 885-2008 Appendix E.

See Terminal Unit Engineering Guidelines.

• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. See page M23 for

AHRI Certified Performance Listings.

• Sound performance for seismic and valve package configurations are equal to the above

PERFORM

ANCE DATA

Size CFM Min ΔPs

Octave Band Sound Power, Lw 0.5” ΔPs 1.0” ΔPs 1.5” ΔPs 2.0” ΔPs

2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC

100 0.02 49 45 36 33 31 26 11 52 48 39 36 35 31 15 53 50 41 37 37 34 17 55 51 43 38 39 36 18 125 0.03 52 49 39 36 32 27 16 55 52 42 38 36 32 20 57 54 44 40 39 36 22 58 55 45 41 40 38 23 150 0.04 55 52 41 37 34 28 20 58 55 44 40 38 34 23 60 57 46 41 40 37 25 61 58 47 42 42 39 27 175 0.06 58 55 42 39 35 29 23 61 58 46 42 39 34 27 63 59 48 43 41 38 28 64 61 49 44 43 40 30 200 0.08 60 57 44 40 36 30 25 63 60 47 43 40 35 29 65 62 49 44 42 38 31 66 63 51 45 44 41 33

150 0.01 49 44 36 32 31 25 10 53 49 41 36 35 30 16 55 51 43 38 37 33 18 57 53 45 39 39 35 21 200 0.02 53 48 39 35 34 27 15 56 53 44 38 37 32 21 59 55 46 40 40 35 23 60 57 48 42 41 37 25 250 0.03 55 52 41 37 35 29 20 59 56 46 40 39 34 24 62 59 49 42 41 37 28 63 61 51 44 43 39 30 300 0.04 58 54 43 39 37 30 22 62 59 48 42 41 35 28 64 61 50 44 43 38 30 65 63 52 45 44 40 33 350 0.06 60 56 45 40 38 31 24 63 61 49 43 42 36 30 66 63 52 45 44 39 33 67 65 54 47 45 41 35

300 0.07 55 49 40 35 32 28 16 59 54 45 39 37 33 22 61 57 48 41 39 36 25 63 59 50 42 41 38 28 350 0.10 57 52 42 37 34 29 20 60 57 47 41 38 34 25 62 59 50 43 40 37 28 64 62 52 44 42 39 31 400 0.13 58 53 44 39 35 30 21 61 58 49 42 39 35 27 63 61 52 44 42 38 30 65 63 54 46 43 40 33 450 0.16 59 55 45 40 36 31 23 62 60 50 44 40 36 29 64 63 53 46 43 39 33 66 65 55 47 45 41 35 500 0.20 59 56 47 42 37 32 24 63 61 51 45 41 37 30 65 64 54 47 44 40 34 67 67 56 49 46 42 37

450 0.07 59 48 42 38 33 24 20 61 54 48 42 38 30 23 62 57 51 45 41 33 25 63 59 53 46 43 35 28 500 0.09 60 50 43 39 34 24 22 62 55 49 43 39 30 24 63 58 52 46 42 34 27 64 60 54 48 44 36 29 550 0.10 60 51 44 40 35 25 22 63 57 50 45 40 31 25 64 59 53 47 43 34 28 66 62 55 49 45 37 31 600 0.12 61 53 45 42 35 25 23 63 58 51 46 41 31 27 65 61 54 48 44 35 30 66 63 56 50 46 37 33 650 0.15 62 54 46 43 36 26 24 64 59 52 47 41 32 28 65 62 55 49 44 35 31 66 64 57 51 46 38 34

600 0.02 59 50 44 40 38 32 20 62 55 49 43 43 39 24 64 58 52 46 45 44 27 65 60 54 47 47 47 29 650 0.02 60 51 44 41 39 32 22 63 56 50 44 44 40 25 65 59 53 47 46 45 28 66 61 55 48 48 48 30 700 0.02 60 52 45 42 40 33 22 63 57 50 45 44 41 25 65 60 53 47 47 45 29 67 62 56 49 49 48 31 750 0.02 61 53 46 43 40 34 23 64 58 51 46 45 41 27 66 61 54 48 48 46 30 67 63 56 50 50 49 33 800 0.03 62 54 47 43 41 34 24 65 59 52 47 46 42 28 66 62 55 49 48 47 31 68 64 57 51 50 50 34

800 0.04 58 47 43 36 34 30 19 61 53 49 42 40 35 23 62 57 52 46 44 38 26 63 59 55 48 47 40 29 850 0.04 58 48 43 37 34 31 19 61 54 49 43 41 35 23 63 58 53 46 45 38 27 64 60 55 49 47 40 29 900 0.05 59 49 44 37 35 31 20 62 55 50 43 41 35 24 64 58 53 47 45 38 27 65 61 56 49 48 40 30 950 0.06 59 50 44 37 35 31 20 62 56 50 43 42 36 24 64 59 54 47 45 38 28 65 62 56 49 48 40 31

1000 0.06 60 50 44 38 36 31 22 63 56 50 44 42 36 25 65 60 54 47 46 39 29 66 62 57 50 48 40 31

900 0.01 60 50 47 45 42 29 22 63 57 53 50 48 37 27 65 60 57 53 52 41 31 67 63 59 56 54 44 34 1000 0.01 60 51 48 46 43 30 22 64 58 54 51 49 38 28 66 61 57 54 53 42 31 67 64 59 56 55 45 34 1100 0.01 61 52 48 47 44 32 23 65 58 54 52 50 39 28 67 62 57 55 54 43 31 68 64 60 57 56 46 35 1200 0.01 62 53 48 47 45 32 24 65 59 54 53 51 40 28 67 63 58 56 55 44 33 69 65 60 58 57 47 35 1300 0.01 63 54 49 48 45 33 25 66 60 55 53 52 41 29 68 63 58 56 55 45 33 69 66 61 58 58 48 36

1200 0.01 58 50 47 41 37 30 20 62 56 52 47 43 37 26 64 59 56 50 46 41 30 66 61 58 53 49 43 32 1400 0.01 60 52 48 42 38 32 22 63 57 54 48 45 39 28 65 60 57 52 48 42 31 67 63 60 54 51 45 35 1600 0.01 61 53 50 43 40 34 24 64 59 55 49 46 40 29 66 62 59 53 50 44 34 68 64 61 55 52 47 36 1800 0.01 61 55 51 44 41 35 25 65 60 56 50 48 41 30 67 63 60 54 51 45 35 69 65 62 56 54 48 37 2000 0.01 62 56 52 45 43 36 26 66 61 57 51 49 43 31 68 64 61 55 52 47 36 69 67 63 57 55 49 38

1500 0.02 56 51 45 43 40 36 18 60 56 50 48 45 41 24 62 59 53 51 48 45 28 64 61 55 53 50 47 30 1800 0.03 58 53 46 44 41 36 21 62 58 51 49 46 42 27 64 60 54 52 49 45 29 66 63 56 54 51 48 33 2100 0.04 59 54 47 45 42 37 22 63 59 52 50 47 43 28 66 62 55 53 50 46 31 67 64 58 55 52 49 34 2400 0.05 60 55 48 46 43 38 23 64 60 53 51 48 43 29 67 63 56 54 51 47 33 69 65 58 56 53 49 35 2700 0.06 62 56 49 47 44 38 24 66 61 54 52 49 44 30 68 64 57 55 52 47 34 70 66 59 57 54 50 36

2000 0.02 55 48 43 41 39 31 36 59 53 47 45 44 38 21 61 56 50 47 47 41 24 63 58 52 49 49 44 27 2400 0.02 57 51 45 43 41 33 18 61 56 49 47 46 39 24 64 59 52 49 49 43 28 65 61 54 51 51 46 30 2800 0.03 59 53 46 44 42 34 21 63 58 51 48 47 41 27 66 61 54 50 50 45 30 67 63 55 52 52 48 33 3200 0.04 61 55 48 46 44 36 23 65 60 52 50 49 42 29 67 62 55 52 52 46 31 69 64 57 53 54 49 34 3600 0.05 62 56 49 47 45 37 24 66 61 54 51 50 44 30 69 64 56 53 53 48 34 71 66 58 55 55 50 36

3900 0.03 70 65 63 59 57 54 38 72 68 66 62 61 58 41 74 69 67 63 63 61 42 75 70 68 64 65 63 43 4600 0.04 73 68 66 62 59 55 41 75 71 68 64 63 60 43 77 72 70 66 65 63 46 78 73 71 67 67 64 47 5300 0.06 75 71 68 64 61 56 43 78 73 71 66 65 61 47 79 74 72 68 67 64 48 80 75 73 69 68 66 49 6000 0.07 77 73 71 66 63 57 47 80 75 73 68 66 62 49 81 76 74 70 68 65 50 82 77 75 71 70 67 51 6700 0.09 79 75 72 67 64 58 48 82 77 75 70 68 63 51 83 78 76 71 70 66 52 84 79 77 72 71 68 53 fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

M18

M

PERFORMANCE DATA

PESV, AESV, DESV / DISCHARGE SOUND PERFORMANCE

• Discharge sound is the noise emitted from the unit discharge into the downstream ductwork

• Min ΔPs is the static pressure drop from the unit inlet to the unit outlet with primary damper full open

• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density

fiberglass lining

• All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011

• All NC levels determined using AHRI 885-2008 Appendix E.

See Terminal Unit Engineering Guidelines.

• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. See page M23 for

AHRI Certified Performance Listings.

• Sound performance for seismic and valve package configurations are equal to the above

PE

RF

OR

M

AN

CE

D

AT

A

Size CFM Min ΔPs

Octave Band Sound Power, Lw 0.5” ΔPs 1.0” ΔPs 1.5” ΔPs 2.0” ΔPs

2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC

100 0.02 70 56 47 42 40 33 28 71 59 51 46 47 41 29 72 61 54 49 50 46 30 73 62 56 51 53 49 31 125 0.03 72 60 50 44 42 35 30 73 63 54 49 49 43 31 74 64 57 52 52 47 33 75 65 59 54 55 51 34 150 0.04 73 63 52 47 44 36 31 75 65 57 51 50 44 34 76 67 60 54 54 49 35 76 68 61 56 57 52 35 175 0.06 75 65 54 48 45 37 34 76 68 59 53 51 45 35 77 69 62 56 55 50 36 78 71 64 58 58 53 38 200 0.08 76 67 56 50 46 38 35 77 70 61 55 53 46 36 78 72 63 58 56 51 38 79 73 65 60 59 54 39

150 0.01 68 53 47 43 41 34 25 70 58 52 47 47 42 28 72 60 55 50 51 46 30 73 62 58 52 53 49 31 200 0.02 71 57 50 46 43 36 29 73 61 56 51 49 44 31 75 64 59 53 53 48 34 76 66 61 55 55 51 35 250 0.03 73 60 53 49 45 38 31 75 65 58 53 51 45 34 77 67 61 56 55 50 36 78 69 63 58 57 53 38 300 0.04 74 62 55 51 47 39 29 77 67 60 55 53 46 33 78 70 63 58 56 51 34 79 72 66 60 59 54 35 350 0.06 76 64 57 52 48 40 31 78 69 62 57 54 47 34 80 72 65 60 57 52 36 81 74 67 61 60 55 38

300 0.07 68 60 54 50 45 39 21 72 65 59 54 51 46 26 75 68 62 57 54 50 30 77 70 64 58 56 53 33 350 0.10 69 62 55 52 47 40 22 74 67 61 56 52 47 29 76 70 64 59 55 51 31 78 72 66 60 58 54 34 400 0.13 71 63 57 54 48 41 25 75 69 62 58 53 48 30 78 72 65 60 57 52 34 79 74 67 62 59 55 35 450 0.16 72 65 58 55 49 42 26 76 70 64 59 54 49 31 79 73 67 62 58 53 35 81 76 69 63 60 56 38 500 0.20 73 66 60 56 50 43 28 77 72 65 61 55 50 33 80 75 68 63 59 54 36 82 77 70 65 61 57 39

450 0.07 71 61 54 51 47 40 25 74 66 59 54 51 46 29 75 70 61 56 54 49 30 77 72 63 58 56 52 33 500 0.09 71 62 55 52 48 40 25 74 68 60 56 52 47 29 76 71 63 58 55 50 31 77 74 64 59 57 53 34 550 0.10 72 64 56 54 49 41 26 75 69 61 57 53 48 30 76 73 64 59 56 51 33 78 75 65 60 58 54 36 600 0.12 72 65 57 55 49 42 26 75 70 62 58 54 48 30 77 74 64 60 57 52 34 78 76 66 61 59 55 37 650 0.15 72 66 58 56 50 43 26 75 72 63 59 55 49 32 77 75 65 61 58 53 36 79 77 67 62 59 55 38

600 0.02 73 63 56 52 48 40 28 76 69 60 55 52 47 31 78 72 62 56 55 51 34 79 75 64 57 57 54 36 650 0.02 74 64 57 53 48 41 29 77 70 61 56 53 47 33 78 73 63 57 55 51 34 79 76 65 58 57 54 37 700 0.02 74 65 57 54 49 41 29 77 71 61 56 53 48 33 79 74 64 58 56 52 35 80 77 65 59 58 55 38 750 0.02 75 66 58 54 49 42 28 77 72 62 57 54 48 31 79 75 64 58 56 52 34 80 78 66 60 58 55 38 800 0.03 75 67 58 55 50 42 28 78 73 63 58 54 49 32 79 76 65 59 57 53 36 81 78 67 60 59 56 38

800 0.04 73 61 57 53 49 43 25 76 66 61 57 54 49 29 77 69 63 59 57 53 30 78 71 65 60 59 56 31 850 0.04 74 62 57 53 49 43 26 76 67 61 57 54 50 29 78 70 63 59 57 54 31 79 72 65 61 59 56 33 900 0.05 74 63 58 54 50 43 26 77 68 62 57 55 50 30 79 70 64 59 57 54 33 80 72 66 61 59 57 34 950 0.06 75 63 58 54 50 44 28 78 68 62 58 55 50 31 79 71 64 60 58 54 33 80 73 66 61 60 57 34

1000 0.06 75 64 59 55 50 44 28 78 69 62 58 55 50 31 80 72 65 60 58 54 34 81 74 66 62 60 57 35

900 0.01 75 62 58 55 50 44 28 77 67 62 59 55 50 30 78 70 65 61 58 54 31 79 73 67 63 61 57 33 1000 0.01 76 63 59 56 50 44 29 78 68 63 60 56 51 31 79 71 66 62 59 55 33 80 74 68 64 61 57 34 1100 0.01 76 63 59 57 51 45 29 79 69 64 61 56 51 33 80 72 66 63 60 55 34 81 74 68 65 62 58 35 1200 0.01 77 64 60 57 52 45 30 79 70 64 61 57 52 33 81 73 67 64 60 56 35 82 75 69 66 63 59 36 1300 0.01 78 65 61 58 52 46 31 80 70 65 62 58 53 34 81 74 68 65 61 56 35 82 76 69 66 63 59 36

1200 0.01 73 64 60 55 53 46 25 76 69 64 59 57 52 29 78 72 66 62 60 56 31 79 74 68 64 62 59 33 1400 0.01 74 65 62 56 54 47 26 77 71 66 61 59 53 30 79 74 68 63 61 57 33 80 76 70 65 63 60 36 1600 0.01 75 66 63 57 55 48 28 78 72 67 62 59 55 31 80 75 69 64 62 58 34 81 77 71 66 64 61 37 1800 0.01 76 68 64 58 55 49 29 79 73 68 63 60 56 33 80 76 71 65 63 59 36 81 78 72 67 65 62 38 2000 0.01 76 69 65 59 56 50 29 79 74 69 64 61 56 33 81 77 72 66 64 60 37 82 79 73 68 66 63 39

1500 0.02 69 57 56 53 50 44 20 72 63 56 59 57 53 24 74 67 56 62 62 59 26 76 69 56 65 65 62 29 1800 0.03 70 59 58 53 50 44 21 73 65 58 59 58 53 25 75 68 58 63 62 59 28 77 71 58 65 65 63 30 2100 0.04 71 60 59 54 51 44 22 74 66 59 60 58 54 26 76 69 59 63 63 59 29 78 72 59 66 66 63 31 2400 0.05 72 61 60 54 51 44 24 75 67 60 60 59 54 28 77 70 60 64 63 59 30 78 73 60 66 66 63 32 2700 0.06 72 62 61 54 51 45 24 76 68 61 61 59 54 29 78 71 61 64 63 60 31 79 74 61 67 66 63 33

2000 0.02 68 59 57 54 52 45 19 71 63 57 58 56 51 22 73 66 57 61 59 54 25 74 68 57 63 61 57 26 2400 0.02 70 62 59 55 53 46 21 73 66 59 60 58 52 25 75 68 59 62 61 56 28 76 70 59 64 62 58 29 2800 0.03 71 64 61 57 55 48 22 75 68 61 61 59 54 28 77 70 61 64 62 57 30 78 72 61 66 64 60 31 3200 0.04 73 65 63 58 56 49 25 76 69 63 62 60 55 29 78 72 63 65 63 59 31 79 73 63 67 65 61 33 3600 0.05 74 67 65 59 57 50 26 77 71 65 63 61 56 30 79 73 65 66 64 60 33 81 75 65 68 66 62 35

3900 0.03 76 70 66 62 61 56 29 81 75 66 67 67 62 35 84 78 66 69 70 66 39 86 80 66 71 72 68 42 4600 0.04 77 71 67 63 63 58 30 82 77 67 68 68 64 37 85 80 67 71 71 67 40 88 82 67 73 74 70 44 5300 0.06 79 73 69 65 64 60 33 84 78 69 69 70 65 39 87 81 69 72 73 69 43 89 83 69 74 75 71 45 6000 0.07 80 74 70 66 65 61 34 85 79 70 71 71 67 40 88 82 70 73 74 70 44 90 84 70 75 76 73 47 6700 0.09 81 75 71 67 67 62 35 86 80 71 72 72 68 42 89 83 71 74 75 71 45 91 85 71 76 77 74 48

| w w

M19

M

PERFORMANCE DATA

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

Performance notes appear at end of table

PERFORM

ANCE DATA

Si ze s 4-

5-

Rows gpm Head Loss

Airflow, CFM 50 100 150 200 250 300 350 400 450

One-Row

1.0 0.48 3.7 5.6 6.8 7.8 8.6 9.3 9.9 10.4 10.8

2.0 1.82 3.8 5.9 7.3 8.5 9.5 10.3 11.0 11.6 12.2

4.0 6.98 3.9 6.1 7.6 8.9 10.0 10.9 11.7 12.4 13.1

5.0 10.75 3.9 6.1 7.7 9.0 10.1 11.0 11.8 12.6 13.3 Airside ΔPs 0.01 0.01 0.02 0.04 0.05 0.07 0.10 0.12 0.15

Two-Row

1.0 0.12 5.0 8.1 10.3 12.0 13.4 14.5 15.5 16.3 17.0

3.0 1.04 5.4 9.0 11.9 14.2 16.2 17.9 19.4 20.7 22.0

5.0 2.80 5.4 9.2 12.2 14.7 16.9 18.8 20.5 22.0 23.4

7.0 5.38 5.5 9.3 12.4 15.0 17.3 19.2 21.0 22.6 24.1 Airside ΔPs 0.01 0.03 0.05 0.08 0.12 0.16 0.21 0.26 0.32

Si ze s 7-

Rows gpm Head Loss

Airflow, CFM 100 200 300 400 500 600 700 800 900

One-Row

1.0 0.64 6.2 8.9 10.7 12.1 13.1 14.0 14.7 15.3 15.9

2.0 2.46 6.6 9.7 11.8 13.5 14.8 16.0 16.9 17.8 18.5

3.0 5.38 6.7 10.0 12.3 14.1 15.5 16.8 17.9 18.8 19.7

4.0 9.39 6.8 10.1 12.5 14.4 15.9 17.2 18.4 19.4 20.3 Airside ΔPs 0.01 0.02 0.05 0.07 0.11 0.15 0.19 0.24 0.30

Two-Row

1.0 0.17 8.8 13.4 16.3 18.5 20.2 21.5 22.6 23.6 24.4

3.0 1.40 9.7 15.6 20.0 23.4 26.3 28.6 30.7 32.5 34.1

5.0 3.77 9.9 16.2 21.0 24.8 28.0 30.8 33.2 35.3 37.2

7.0 7.24 10.0 16.5 21.4 25.5 28.8 31.8 34.4 36.7 38.8 Airside ΔPs 0.02 0.05 0.10 0.16 0.23 0.32 0.41 0.51 0.62

Si ze s 9-

Rows gpm Head Loss

Airflow, CFM

200 300 400 500 600 700 800 900 1000

One-Row

2.0 0.41 11.0 13.5 15.4 17.0 18.3 19.5 20.5 21.3 22.1

3.0 0.90 11.4 14.1 16.3 18.1 19.6 20.9 22.0 23.0 23.9

5.0 2.41 11.8 14.7 17.1 19.0 20.7 22.2 23.5 24.6 25.7

6.0 3.43 11.9 14.9 17.3 19.3 21.0 22.5 23.9 25.1 26.2 Airside ΔPs 0.01 0.02 0.04 0.06 0.08 0.10 0.13 0.15 0.19

Two-Row

2.0 0.47 16.4 21.0 24.5 27.4 29.8 31.8 33.6 35.1 36.5

4.0 1.84 17.6 23.0 27.3 31.0 34.2 36.9 39.4 41.5 43.5

6.0 4.08 18.0 23.8 28.5 32.5 36.0 39.1 41.8 44.3 46.6

8.0 5.00 18.3 24.2 29.1 33.3 37.0 40.3 43.2 45.9 48.3 Airside ΔPs 0.03 0.05 0.09 0.12 0.17 0.22 0.27 0.33 0.40

Si ze

Rows gpm Head Loss

Airflow, CFM

300 500 700 900 1100 1300 1500 1700 1900

One-Row

2.0 0.54 15.5 19.8 22.9 25.2 27.1 28.7 30.1 31.2 32.3

3.0 1.19 16.2 21.0 24.5 27.2 29.5 31.4 33.0 34.5 35.7

5.0 3.18 16.9 22.1 26.0 29.1 31.7 34.0 35.9 37.6 39.2

6.0 4.52 17.0 22.4 26.5 29.7 32.4 34.7 36.7 38.5 40.1 Airside ΔPs 0.01 0.03 0.06 0.09 0.13 0.17 0.22 0.27 0.33

Two-Row

2.0 0.55 23.2 30.8 36.2 40.2 43.5 46.1 48.3 50.2 51.9

4.0 2.15 25.3 34.8 41.9 47.6 52.3 56.3 59.7 62.7 65.4

6.0 4.75 26.1 36.4 44.3 50.7 56.1 60.8 64.8 68.4 71.6

8.0 6.16 26.5 37.2 45.6 52.5 58.3 63.3 67.8 71.7 75.3 Airside ΔPs 0.03 0.07 0.13 0.20 0.27 0.36 0.46 0.57 0.68 fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

M20

M

PERFORMANCE DATA

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

• All coil performance in accordance with AHRI 410-2001
• Heating capacities are in MBH
• Data based on 180°F entering water and 55°F entering air
• For temperature differentials other than 125°, multiply MBH by

correction factors below

• Head loss is in feet of water
• Always supply water to lowest connection pipe to prevent air

entrapment

• Air temperature rise = 927 x MBH/cfm
• Water temperature drop = 2.04 x MBH/gpm

Correction Factors for Other Entering Conditions

• Connection size is ½ OD male solder for 1-row coil sizes 04-08. All other coils have 7/8” OD male solder.

• Coils are not intended for steam applications and are labeled for a maximum water temperature of 200°F

• Coils are tested for leakage at test pressure of 500 psi
• Water volumes less than those shown may result in laminar flow and

reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range.

Note: Airside ΔPs reflects the air pressure drop of the hot water coil

PE

RF

OR

M

AN

CE

D

AT

A

Si ze s

Rows gpm Head Loss

Airflow, CFM 400 700 1000 1300 1600 1900 2200 2500 2800

One-Row

2.0 0.43 20.4 26.3 30.3 33.2 35.5 27.4 39.0 40.4 41.5

3.0 0.96 21.6 28.4 33.2 36.8 39.7 42.0 44.1 45.9 47.4

5.0 2.63 22.7 30.5 36.0 40.3 43.8 47.8 49.3 51.6 53.6

6.0 3.77 23.1 31.0 36.8 41.3 45.0 48.2 50.9 53.3 55.4 Airside ΔPs 0.01 0.03 0.06 0.09 0.13 0.17 0.22 0.27 0.33

Two-Row

2.0 0.39 30.1 40.3 47.0 51.8 55.5 58.5 60.9 62.9 64.7

4.0 1.51 33.5 47.1 56.8 64.3 70.3 75.3 79.6 83.2 86.4

6.0 3.36 34.9 49.9 61.1 69.9 77.2 83.3 88.6 93.2 97.3

8.0 3.95 35.6 51.5 63.5 73.1 81.1 88.0 93.9 99.2 103.8 Airside ΔPs 0.03 0.07 0.12 0.19 0.27 0.36 0.46 0.57 0.69

Si ze s

Rows gpm Head Loss

Airflow, CFM 600 1000 1400 1800 2200 2600 3000 3400 3800

One-Row

3.0 1.07 29.5 37.4 42.8 47.0 50.4 53.1 55.5 57.5 59.3

5.0 2.92 31.4 40.6 47.2 52.3 56.5 60.1 63.1 65.8 68.2

7.0 5.65 32.4 42.1 49.3 55.0 59.7 63.7 67.1 70.2 72.9

9.0 6.48 32.9 43.1 50.6 56.6 61.6 65.9 69.6 72.9 75.9 Airside ΔPs 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30 0.36

Two-Row

3.0 0.53 43.1 55.9 64.7 71.1 76.1 80.1 83.4 86.2 88.6

5.0 1.46 47.0 63.1 74.6 83.5 90.7 96.6 101.6 105.9 109.7

7.0 2.84 49.0 66.8 80.0 90.3 98.8 106.0 112.1 117.5 122.2

9.0 2.54 50.2 69.0 83.3 94.6 104.1 112.1 119.0 125.1 130.5 Airside ΔPs 0.04 0.08 0.14 0.22 0.30 0.40 0.51 0.63 0.76

Si ze s x

Rows gpm Head Loss

Airflow, CFM

600 1200 1800 2400 3000 3600 4200 4800 5400

One-Row

3.0 1.31 35.3 49.4 58.3 64.7 69.6 73.5 76.8 79.6 82.0

5.0 3.57 37.6 54.2 65.2 73.4 79.9 85.3 89.9 93.8 97.3

7.0 6.89 38.7 56.5 68.7 77.9 85.4 91.6 96.9 101.5 105.6

9.0 8.50 39.3 58.0 70.8 80.7 88.7 95.5 101.3 106.4 110.9 Airside ΔPs 0.01 0.02 0.05 0.08 0.11 0.15 0.20 0.25 0.30

Two-Row

3.0 0.59 48.8 70.9 84.3 93.4 100.1 105.3 109.4 112.8 115.7

5.0 1.63 53.1 81.0 99.4 112.9 123.3 131.6 138.5 144.3 149.3

7.0 3.17 55.2 86.2 107.6 123.8 136.6 147.1 155.9 163.5 170.0

9.0 3.06 56.4 89.4 112.8 130.8 145.3 157.3 167.5 176.4 184.2

Airside ΔPs 0.02 0.05 0.10 0.16 0.24 0.32 0.42 0.52 0.63

ΔT 50 60 70 80 90 100 110 125 140 150

Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20

| w w

M21

M

PERFORMANCE DATA

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

Performance notes appear at end of table

PERFORM

ANCE DATA

Si ze s 4-

5-

Rows gpm Head Loss

Airflow, CFM 50 100 150 200 250 300 350 400 450

Three- Row

2.0 0.70 6.1 10.8 14.4 17.5 20.0 22.3 24.2 25.9 27.4

3.0 1.54 6.1 11.0 14.9 18.2 21.0 23.5 25.7 27.6 29.4

5.0 4.14 6.2 11.1 15.2 18.8 21.8 24.6 27.0 29.2 31.3

6.0 5.90 6.2 11.2 15.3 18.9 22.1 24.9 27.4 29.7 31.8 Airside ΔPs 0.01 0.04 0.08 0.12 0.18 0.24 0.31 0.39 0.47

Four- Row

3.0 1.11 6.5 11.9 16.5 20.5 23.9 26.8 29.5 34.8 34.0

4.0 1.95 6.5 12.1 16.8 20.9 24.5 27.7 30.6 33.1 35.5

6.0 4.33 6.5 12.2 17.1 21.4 25.2 25.6 31.7 34.5 37.1

8.0 5.42 6.5 12.2 17.2 21.6 25.5 29.1 32.3 35.3 38.0 Airside ΔPs 0.02 0.05 0.10 0.16 0.24 0.32 0.41 0.52 0.63

Si ze s 7-

Rows gpm Head Loss

Airflow, CFM 100 200 300 400 500 600 700 800 900

Three- Row

2.0 0.50 11.2 18.6 23.8 27.9 31.1 33.7 35.9 37.8 39.4

4.0 1.95 11.6 19.8 26.0 31.1 35.3 38.8 41.9 44.7 47.1

6.0 4.33 11.7 20.2 26.9 32.3 37.0 41.0 44.5 47.6 50.4

8.0 5.42 11.7 20.4 27.3 33.0 37.9 42.1 45.9 49.2 52.2 Airside ΔPs 0.02 0.08 0.15 0.24 0.35 0.47 0.61 0.77 0.93

Four- Row

4.0 1.40 12.4 22.1 29.6 358.0 40.9 45.3 49.1 52.4 55.3

6.0 3.12 12.5 22.5 30.6 37.3 43.0 48.0 52.4 56.3 59.7

8.0 3.53 12.6 22.7 31.1 38.1 44.2 49.5 54.2 58.4 62.2

10.0 5.46 12.6 22.9 31.4 38.6 44.9 50.4 55.4 59.8 63.8 Airside ΔPs 0.03 0.10 0.20 0.32 0.47 0.63 0.82 1.02 1.25

Si ze s 9-

Rows gpm Head Loss

Airflow, CFM

200 300 400 500 600 700 800 900 1000

Three- Row

3.0 0.80 21.0 27.9 33.4 38.0 41.8 45.2 48.1 50.7 52.9

5.0 2.19 21.6 29.2 35.5 40.8 45.5 49.6 53.2 56.5 59.4

7.0 4.26 21.9 29.8 36.5 42.2 47.2 51.7 55.7 59.4 62.7

9.0 4.49 22.1 30.2 37.0 43.0 48.3 53.0 57.3 61.2 64.7 Airside ΔPs 0.04 0.08 0.13 0.19 0.25 0.33 0.41 0.50 0.59

Four- Row

4.0 1.16 23.5 32.2 39.4 45.6 50.9 55.5 59.6 63.2 66.5

5.0 1.80 23.7 32.7 40.4 46.9 52.6 57.7 62.2 66.2 69.8

8.0 2.75 24.1 33.6 41.8 49.0 55.4 61.2 66.4 71.1 75.5

10.0 4.25 24.2 33.9 42.3 49.8 56.4 62.4 67.9 72.9 77.5 Airside ΔPs 0.05 0.11 0.17 0.25 0.34 0.43 0.54 0.66 0.79

Si ze

Rows gpm Head Loss

Airflow, CFM

300 500 700 900 1100 1300 1500 1700 1900

Three- Row

3.0 0.91 30.3 42.2 50.9 57.6 63.0 67.4 71.1 74.3 77.0

4.0 1.61 31.0 44.0 53.8 61.5 67.8 73.1 77.6 81.5 84.9

6.0 3.57 31.8 45.9 56.9 65.8 73.3 79.7 85.2 90.1 94.5

8.0 4.32 32.2 46.9 58.5 68.2 76.3 83.4 89.6 95.1 100.0 Airside ΔPs 0.05 0.11 0.19 0.29 0.41 0.54 0.69 0.85 1.02

Four- Row

4.5 1.63 34.6 50.5 62.9 72.7 80.8 87.6 93.4 98.4 102.8

5.0 2.01 34.8 51.1 63.9 74.2 82.7 89.9 96.0 101.4 106.1

7.0 2.88 35.1 52.6 66.5 78.0 87.7 96.1 103.4 109.8 115.6

9.0 4.11 35.6 53.4 68.0 80.3 90.8 99.9 107.9 115.1 121.5 Airside ΔPs 0.06 0.15 0.26 0.39 0.55 0.72 0.92 1.13 1.36 fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

M22

M

PERFORMANCE DATA

PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

• All coil performance in accordance with AHRI 410-2001
• Heating capacities are in MBH
• Data based on 180°F entering water and 55°F entering air
• For temperature differentials other than 125°, multiply MBH by

correction factors below

• Head loss is in feet of water
• Always supply water to lowest connection pipe to prevent air

entrapment

• Air temperature rise = 927 x MBH/cfm
• Water temperature drop = 2.04 x MBH/gpm

• Connection size is ½ OD male solder for 1-row coil sizes 04-08. All other coils have 7/8” OD male solder.

• Coils are not intended for steam applications and are labeled for a maximum water temperature of 200°F

• Coils are tested for leakage at test pressure of 500 psi
• Water volumes less than those shown may result in laminar flow and

reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range.

Note: Airside ΔPs reflects the air pressure drop of the hot water coil

Correction Factors for Other Entering Conditions

PE

RF

OR

M

AN

CE

D

AT

A

ΔT 50 60 70 80 90 100 110 125 140 150

Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20

Si ze s

Rows gpm Head Loss

Airflow, CFM 400 700 1000 1300 1600 1900 2200 2500 2800

Three- Row

4.0 1.30 41.3 59.8 73.0 83.0 90.9 97.3 102.7 107.3 111.1

5.0 2.01 42.1 61.8 76.3 87.6 96.6 104.1 110.4 115.8 120.5

6.0 2.88 42.6 63.2 78.6 90.8 100.7 109.0 116.1 122.2 127.6

8.0 3.27 43.3 65.0 81.7 95.2 106.3 115.8 124.0 131.2 137.5 Airside ΔPs 0.04 0.10 0.19 0.29 0.41 0.54 0.69 0.86 1.04

Four- Row

6.0 2.06 46.7 71.1 89.5 104.0 115.7 125.5 133.7 140.8 146.9

7.0 2.79 47.1 72.2 91.6 107.1 119.8 130.4 139.5 147.4 154.2

8.0 2.03 47.4 73.1 93.3 109.5 123.0 134.4 144.1 152.7 160.2

10.0 3.15 47.8 74.4 95.6 113.0 127.7 140.2 151.1 160.7 169.2 Airside ΔPs 0.05 0.14 0.25 0.38 0.54 0.72 0.93 1.15 1.39

Si ze s

Rows gpm Head Loss

Airflow, CFM 600 1000 1400 1800 2200 2600 3000 3400 3800

Three- Row

6.0 1.71 58.5 80.9 97.0 109.3 119.2 127.3 134.0 139.9 144.9

8.0 1.51 60.1 84.4 102.5 116.7 128.3 138.0 146.2 153.4 159.6

10.0 2.35 61.1 86.7 106.1 121.6 134.4 145.3 154.6 162.7 169.9

12.0 3.36 61.8 88.2 108.6 125.1 138.8 150.5 160.7 169.6 177.5 Airside ΔPs 0.06 0.14 0.24 0.37 0.51 0.68 0.86 1.06 1.28

Four- Row

9.0 1.58 67.4 97.6 120.6 138.8 153.7 166.2 176.8 185.9 193.9

10.0 1.95 67.9 98.8 122.6 141.6 157.3 170.5 181.8 191.6 200.2

11.0 2.36 68.3 99.7 124.2 144.0 160.3 174.1 186.0 196.4 205.6

12.0 2.80 68.6 100.5 125.6 146.0 162.9 177.3 189.8 200.7 210.3 Airside ΔPs 0.08 0.18 0.32 0.49 0.68 0.90 1.15 1.42 1.71

Si ze s x

Rows gpm Head Loss

Airflow, CFM

600 1200 1800 2400 3000 3600 4200 4800 5400

Three- Row

6.0 1.86 65.0 103.8 129.6 148.2 162.3 173.5 182.5 190.1 196.5

8.0 1.76 66.4 108.6 138.0 160.0 177.3 191.2 202.8 212.6 221.1

10.0 2.74 67.2 111.5 143.4 167.9 187.4 203.4 216.9 228.5 238.6

12.0 3.92 67.8 113.6 147.2 173.4 194.7 212.3 227.3 240.3 251.6 Airside ΔPs 0.03 0.09 0.17 0.27 0.40 0.54 0.70 0.88 1.07

Four- Row

9.0 1.80 72.6 124.0 161.1 189.2 211.2 229.0 243.6 256.0 266.7

10.0 2.22 73.0 125.5 164.1 193.6 217.1 236.2 252.1 265.6 277.2

11.0 2.68 73.3 126.7 166.5 197.3 222.0 242.3 259.3 273.9 286.4

12.0 3.18 73.5 127.7 168.6 200.5 226.3 247.6 265.6 281.1 294.5 Airside ΔPs 0.04 0.12 0.23 0.37 0.53 0.72 0.93 1.17 1.42

| w w

M23

M

ELECTRIC COILS

SELECTION AND CAPACITIES

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)

Useful formulas: cfm x ΔT cfm ΔT kW x 3160kW x 3160 kW = or ΔT = or cfm =

Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts.

Must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F.

To make a coil selection:

1. Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.)

2. Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.)

3. Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.)

Recommended Coil Selection Data The table at the right describes the maximum recommended kW capacities and number of stages available for Titus single duct terminals.

These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits kW ≤ cfm x 0.0142

Where ΔT = air temperature rise.

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. 3-wire configuration is available.

ELECTRIC COILS

Inlet Size Heating cfm

Range

Number of Steps

Available

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 1 0.5

5.0 0.5

3.0 1.0

3.0 1.0

3.0 1.5 3.0 2.5 3.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

5 85-350 1 0.5

5.0 0.5

5.0 1.0

5.0 1.0

5.0 1.5 5.0 2.5 5.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

6 105-500 1 0.5

5.0 0.5

7.5 1.0

7.5 1.0

7.5 1.5 7.5 2.5 7.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

7 135-650 1 0.5

5.0 0.5

9.5 1.0

9.5 1.0

9.5 1.5 9.5 2.5 9.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

8 190-900 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 13.0 2.5 13.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

9 225-1050 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 16.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

10 300-1400 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 21.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

12 425-2000 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 30.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

14 575-3000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

16 750-4000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

24x16 1800-8000 1 1.0

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 4.0 36.02 2.0 2.0 2.0 3.0 2.0 3 3.0 3.0 3.0 4.5 3.0 fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

M24

M

ELECTRIC COILS

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)

EL

EC

TR

IC

C

OI

LS

Inlet Size

Heating cfm Range

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 0.5 2.5 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0

5 85-350 0.5 4.5 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0

6 105-500 0.5 5.0 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5

7 135-650 0.5 5.0 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5

8 190-900 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0

9 225-1050 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0

10 300-1400 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0

12 425-2000 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0

14 575-3000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

16 750-4000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

24x16 1800-8000 2.0 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0

| w w

M25

M

PERFORMANCE DATA

AHRI Directory Of Certified Performance Titus is a charter member company and current participant in the AHRI Directory of Certified Performance. This voluntary certification program was developed by participating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 1990’s. It is currently administrated by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). The purpose of this program is to provide for the independent verification of manufacturers’ published performance data. Only participating products are authorized to bear the AHRI VAV Certification Mark. Certified data may be viewed and downloaded at www.ahrinet.org.

In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types, and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’. These tests are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in AHRI Standard 880 ‘Performance Rating of Air Terminals’.

Any failure to demonstrate the certified performance is punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible expulsion from the Certified Directory.

Product samples provided for certification testing are standard production units with standard ½” dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions:

PESV, EESV, AESV, DESV

• Rated airflow (cfm) – Based on an inlet velocity of 2000 fpm

• Rated Min ΔPs (in wg) – Minimum static pressure drop from the unit inlet to discharge at rated airflow with damper full open

• Rated ΔPs (in wg) – A static pressure drop of 1.5 in wg from unit inlet to discharge

• Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220

PESV, AESV, DESV

PERFORM

ANCE DATA

Inlet Size

Rated

CFM

Min ΔPs

Discharge Radiated Sound Power Discharge Sound Power

H W 2 3 4 5 6 7 2 3 4 5 6 7

04 150 0.04 8 12 60 57 46 41 40 37 76 67 60 54 54 49

05 250 0.03 8 12 62 59 49 42 41 37 77 67 61 56 55 50

06 400 0.13 8 12 63 61 52 44 42 38 78 72 65 60 57 52

07 550 0.10 10 12 64 59 53 47 43 34 76 73 64 59 56 51

08 700 0.02 10 12 65 60 53 47 47 45 79 74 64 58 56 52

09 900 0.05 12.5 14 64 58 53 47 45 38 79 70 64 59 57 54

10 1100 0.01 12.5 14 67 62 57 55 54 43 80 72 66 63 60 55

12 1600 0.01 15 16 66 62 59 53 50 44 80 75 68 64 62 58

14 2100 0.04 17.5 20 66 62 55 53 50 46 76 69 66 63 63 59

16 2800 0.03 18 24 66 61 54 50 50 45 77 70 66 64 62 57

40 5300 0.06 18 38 79 74 72 68 67 64 87 81 77 72 73 69 www.ahrinet.org.