esvEH_singledual_2023_V2.pdf

PDF 267 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813727R0002
Issued by

About this file

This document is a product specification and selection guide for Titus electric heating coils designed for single and dual duct VAV (Variable Air Volume) terminal units, specifically models PESV, AESV, and DESV.

The electric coils are available in two heat configurations: staged heat and Lynergy heat. For staged heat applications, the document provides a comprehensive selection table with maximum recommended kilowatt (kW) capacities across inlet sizes ranging from 4 to 24x16 inches, with heating cfm ranges from 55 to 8000 cfm. Available voltage options include 120V, 208V, 240V, and 277V single-phase configurations, as well as 208V and 480V three-phase configurations. The staged heat table indicates the number of available heating steps (1-3 steps) for each inlet size, with corresponding kW ranges that vary by voltage type and phase configuration. The Lynergy heat configuration provides simpler capacity specifications without staged steps, offering broader kW ranges across the same inlet sizes and voltage options. The document establishes critical selection criteria requiring that coil discharge temperatures not exceed 100°F for proper operation, with recommended maximum discharge temperatures of 15°F above desired room temperatures. A key operational constraint specifies that minimum airflow limits must satisfy the formula kW ≤ cfm × 0.0142 to limit temperature rise to 45°F and ensure the airflow sensing switch functions correctly. The document also notes that the 480V three-phase configuration is standard 4-wire wye, with 3-wire configuration available upon request.

View the file

Other files

File Type Posted
250063_ATT 13_Prebid RFI Responses Round 1.pdf PDF
250063_ATT 8_Liquidated Damages.pdf PDF
250063_ATT 4_ODS.pdf PDF
2026 TAFB Mechanical Standard_signed.pdf PDF
2026 TAFB FIRE PROTECTION STANDARD.pdf PDF
SOW Att 04_Automated Casting Cell.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
250063_ATT 10_Submittal Register.pdf PDF
23 00 00.pdf PDF
08 11 13.pdf PDF
08 33 23.pdf PDF
10 22 13.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 71 00.pdf PDF
01 33 00.pdf PDF
01 50 00.pdf PDF
ufc_3_260_01_2019_c1.pdf PDF
EM_385-1-1.pdf PDF
dafi21-101_afmcsup_afmcgm2023-01.pdf PDF
ufc_3_601_02_2021.pdf PDF
tinkerafbi13-204.pdf PDF
afman32-7003.pdf PDF
afman91-203_oc-alcsup.pdf PDF
afi48-104.pdf PDF
dodio-2000.16v1_afi10-245-o.pdf PDF
007200_Attch7b_Monthly Hazardous Usage Report.pdf PDF
007200_Attch9_EMS Awareness Training.pdf PDF
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
250063_ Redline A-502.pdf PDF
HE05IN_Dimension_Drawing.pdf PDF
lrad331965pd_spec.pdf PDF
ELECTRICAL COMBINED.pdf PDF
4500-MUG.pdf PDF
220042 As Built Drawings.pdf PDF
Solicitation - FA813727R0002.pdf PDF
2026 TAFB Electrical Standard - Signed.pdf PDF
SOW Att 02c_Controlled Area Training - Certificate.pdf PDF
250063_ATT 3_RMDF.pdf PDF
23 05 15.pdf PDF
23 09 13.pdf PDF
09 90 00.pdf PDF
26 20 00.pdf PDF
08 51 23.pdf PDF
07 92 00.pdf PDF
07 14 00.pdf PDF
08 71 00.pdf PDF
23 05 93.pdf PDF
07 84 00.pdf PDF
03 01 00.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Redefine your com fort zone. ™

| w w w .titus-hvac.com single / dual duct terminals

M23

M

ELECTRIC COILS

SELECTION AND CAPACITIES

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)

Useful formulas: cfm x ΔT cfm ΔT kW x 3160kW x 3160 kW = or ΔT = or cfm =

Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts.

Must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F.

To make a coil selection:

1. Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.)

2. Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.)

3. Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.)

Recommended Coil Selection Data The table at the right describes the maximum recommended kW capacities and number of stages available for Titus single duct terminals.

These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits kW ≤ cfm x 0.0142

Where ΔT = air temperature rise.

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. 3-wire configuration is available.

ELECTRIC COILS

Inlet Size Heating cfm

Range

Number of Steps

Available

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 1 0.5

5.0 0.5

3.0 1.0

3.0 1.0

3.0 1.5 3.0 2.5 3.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

5 85-350 1 0.5

5.0 0.5

5.0 1.0

5.0 1.0

5.0 1.5 5.0 2.5 5.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

6 105-500 1 0.5

5.0 0.5

7.5 1.0

7.5 1.0

7.5 1.5 7.5 2.5 7.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

7 135-650 1 0.5

5.0 0.5

9.5 1.0

9.5 1.0

9.5 1.5 9.5 2.5 9.52 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

8 190-900 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 13.0 2.5 13.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

9 225-1050 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 16.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

10 300-1400 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 21.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

12 425-2000 1 0.5

5.0 0.5

9.5 1.0

11.0 1.0

13.0 1.5 16.0 2.5 30.02 1.0 1.0 1.5 1.5 3 1.5 1.5 2.0 2.5

14 575-3000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

16 750-4000 1 0.5

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 3.0 36.02 1.0 2.0 2.0 2.0 2.0 3 1.5 3.0 3.0 3.0 3.0

24x16 1800-8000 1 1.0

5.0 1.0

9.5 1.0

11.0 1.5

13.0 1.5

16.0 4.0 36.02 2.0 2.0 2.0 3.0 2.0 3 3.0 3.0 3.0 4.5 3.0 www.

Re de fin e yo ur c om fo rt zo ne w w w .ti tu s-hv ac

.c om single / dual duct terminals

M24

M

ELECTRIC COILS

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)

EL

EC

TR

IC

C

OI

LS

Inlet Size

Heating cfm Range

120V 1 Phase kW Range

208V 1 Phase kW Range

240V 1 Phase kW Range

277V 1 Phase kW Range

208V 3 Phase kW Range

480V 3 Phase kW Range

Min Max Min Max Min Max Min Max Min Max Min Max

4 55-225 0.5 2.5 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0

5 85-350 0.5 4.5 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0

6 105-500 0.5 5.0 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5

7 135-650 0.5 5.0 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5

8 190-900 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0

9 225-1050 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0

10 300-1400 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0

12 425-2000 0.5 5.0 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0

14 575-3000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

16 750-4000 0.5 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

24x16 1800-8000 2.0 5.0 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0 www.