The schedule details four Variable Air Volume (VAV) terminal units manufactured by Titus, designated VAV-01 through VAV-04, with DESV model designations (08 and 06 sizes). The units are configured with the following specifications: maximum CFM ratings ranging from 400 to 900; minimum CFM values of 200 to 250; NC (Noise Criteria) levels of 1; static pressure inlet of 0.25 inches water gauge; electric heat coil discharge CFM between 20 and 27; heating capacity between 2.5 and 3 kilowatts; three-phase 480-volt electrical service; modulating SCR heaters; and rated ampacity (MCA) of 3.8 to 4.5 with maximum overcurrent protection (MOP) of 15 amperes. All units are right-hand discharge configurations. Performance data has been corrected for altitude and validated according to ASHRAE 130-2008 and AHRI 880-2011 standards, with NC levels determined per AHRI 885-2008 Appendix E. The document includes a disclaimer that these results serve as an aid to designers only and do not substitute for professional design services, with all data subject to change without notice as of September 24, 2025.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Single Duct Terminal Unit Schedule
Tag AHU Room Model Size CFM Static Pressure NC Levels Electric Heat Coil Electrical Unit Information
Tag Unit Outlet Max Min Inlet Down Min Rad. Disch. CFM KW Volts/Ph. Steps EAT LAT MCA MOP Hand
VAV-01 DESV 08 12x10 500 250 1 0.25 0.02 20 27 250 3 480/3 S 55 92.9 4.5 15 RH
VAV-02 DESV 06 12x8 400 200 1 0.25 0.13 24 25 200 2.5 480/3 S 55 94.5 3.8 15 RH
VAV-03 DESV 08 12x10 900 200 1 0.25 0.07 27 28 200 2.5 480/3 S 55 94.5 3.8 15 RH
VAV-04 DESV 06 12x8 450 200 1 0.25 0.16 27 27 200 2.5 480/3 S 55 94.5 3.8 15 RH
1. Selections are based on Titus as Manufacturer.
2. All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011.
3. All NC levels determined using AHRI 885-2008 Appendix E.
4. All airflow, pressure losses and heating performance values have been corrected for altitude.
5. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).
6. In the "Steps" column, code "S" denotes a modulating SCR heater.
7. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.
Notes:
9/24/2025 2:44 PM
The results of this program are only an aid to the designer, and are not a substitute for professional design services.
Titus accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice. 1 of 1