TAFB B9001 VAV Schedule.pdf

PDF 6 KB Posted

Attached to
WWYK250063 - INSTALL REACT VII FACILITY, B9001, POST V19
Solicitation number
FA813727R0002
Issued by

About this file

This document is a Single Duct Terminal Unit Schedule specifying HVAC equipment selections and performance specifications.

The schedule details four Variable Air Volume (VAV) terminal units manufactured by Titus, designated VAV-01 through VAV-04, with DESV model designations (08 and 06 sizes). The units are configured with the following specifications: maximum CFM ratings ranging from 400 to 900; minimum CFM values of 200 to 250; NC (Noise Criteria) levels of 1; static pressure inlet of 0.25 inches water gauge; electric heat coil discharge CFM between 20 and 27; heating capacity between 2.5 and 3 kilowatts; three-phase 480-volt electrical service; modulating SCR heaters; and rated ampacity (MCA) of 3.8 to 4.5 with maximum overcurrent protection (MOP) of 15 amperes. All units are right-hand discharge configurations. Performance data has been corrected for altitude and validated according to ASHRAE 130-2008 and AHRI 880-2011 standards, with NC levels determined per AHRI 885-2008 Appendix E. The document includes a disclaimer that these results serve as an aid to designers only and do not substitute for professional design services, with all data subject to change without notice as of September 24, 2025.

View the file

Other files

File Type Posted
250063_ATT 13_Prebid RFI Responses Round 1.pdf PDF
250063_ATT 8_Liquidated Damages.pdf PDF
250063_ATT 4_ODS.pdf PDF
2026 TAFB Mechanical Standard_signed.pdf PDF
2026 TAFB FIRE PROTECTION STANDARD.pdf PDF
SOW Att 04_Automated Casting Cell.pdf PDF
SOW Att 02a_Controlled Area Training.pptx PPTX presentation
250063_ATT 10_Submittal Register.pdf PDF
23 00 00.pdf PDF
08 11 13.pdf PDF
08 33 23.pdf PDF
10 22 13.pdf PDF
10 44 16.pdf PDF
07 21 16.pdf PDF
00 71 00.pdf PDF
01 33 00.pdf PDF
01 50 00.pdf PDF
ufc_3_260_01_2019_c1.pdf PDF
EM_385-1-1.pdf PDF
dafi21-101_afmcsup_afmcgm2023-01.pdf PDF
ufc_3_601_02_2021.pdf PDF
tinkerafbi13-204.pdf PDF
afman32-7003.pdf PDF
afman91-203_oc-alcsup.pdf PDF
afi48-104.pdf PDF
dodio-2000.16v1_afi10-245-o.pdf PDF
007200_Attch7b_Monthly Hazardous Usage Report.pdf PDF
007200_Attch9_EMS Awareness Training.pdf PDF
JOIST SPECIAL INSPECTIONS.xlsx XLSX spreadsheet
250063_ Redline A-502.pdf PDF
HE05IN_Dimension_Drawing.pdf PDF
lrad331965pd_spec.pdf PDF
ELECTRICAL COMBINED.pdf PDF
4500-MUG.pdf PDF
220042 As Built Drawings.pdf PDF
Site Visit Meet Up Location.png PNG image
SOW Att 05_SMS Builder Equipment List_v0 2023 0817.xlsx XLSX spreadsheet
250063_ATT 10_Submittal Register.xlsx XLSX spreadsheet
23 08 00.pdf PDF
21 13 13.pdf PDF
23 07 00.pdf PDF
23 36 00.00 40.pdf PDF
23 05 48.00 40.pdf PDF
10 14 00.10.pdf PDF
08 81 00.pdf PDF
28 31 76.pdf PDF
06 41 16.00 10.pdf PDF
01 42 00.pdf PDF
01 33 16.00 10.pdf PDF
HAZMAT Reporting at Tinker AFB FEB 2025.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Single Duct Terminal Unit Schedule

Tag AHU Room Model Size CFM Static Pressure NC Levels Electric Heat Coil Electrical Unit Information

Tag Unit Outlet Max Min Inlet Down Min Rad. Disch. CFM KW Volts/Ph. Steps EAT LAT MCA MOP Hand

VAV-01 DESV 08 12x10 500 250 1 0.25 0.02 20 27 250 3 480/3 S 55 92.9 4.5 15 RH

VAV-02 DESV 06 12x8 400 200 1 0.25 0.13 24 25 200 2.5 480/3 S 55 94.5 3.8 15 RH

VAV-03 DESV 08 12x10 900 200 1 0.25 0.07 27 28 200 2.5 480/3 S 55 94.5 3.8 15 RH

VAV-04 DESV 06 12x8 450 200 1 0.25 0.16 27 27 200 2.5 480/3 S 55 94.5 3.8 15 RH

1. Selections are based on Titus as Manufacturer.

2. All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011.

3. All NC levels determined using AHRI 885-2008 Appendix E.

4. All airflow, pressure losses and heating performance values have been corrected for altitude.

5. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).

6. In the "Steps" column, code "S" denotes a modulating SCR heater.

7. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.

Notes:

9/24/2025 2:44 PM

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

All data subject to change without notice. 1 of 1

File details come from the government source that posted it. Updated .