ESBD_474660_1767973672884_Attachment 7- Project Drawings.pdf
PDF 13 MB Posted
- Attached to
- Fort Worth 1st Floor Restroom Renovation
- Solicitation number
- 3202600095
- Issued by
- Tarrant County, Texas
About this file
This document consists of project drawings for the Fort Worth 1st Floor Restrooms Renovation located at 307 W 13th St., Fort Worth, TX 76102. The project is being managed by BHB Inc., a TBPELS-licensed firm, with project number 2025.011.001. The scope of work encompasses mechanical, plumbing, and electrical renovations for first-floor restroom facilities. The mechanical work includes demolition and replacement of air handling equipment, ductwork, and exhaust systems, with specific CFM requirements and rebalancing specifications noted throughout. The plumbing scope involves installation of new fixtures including water closets, urinals, lavatories, sinks, and a filtered bottle filler station, all requiring low water consumption compliance with Texas state requirements. New piping for cold water, hot water, recirculated hot water, waste, and vent systems must be installed with specific insulation and accessibility requirements per ADA standards. The electrical work includes demolition and installation of lighting fixtures (primarily LED troffers and undercabinet lights), power circuits for mechanical equipment and appliances, fire alarm modifications, occupancy sensors, and lighting controls featuring Acuity Nlight components.
The drawings specify detailed fixture schedules with manufacturer model numbers and performance specifications. Mechanical demolition plans indicate existing equipment to be removed and capped, with contractor verification of airflow prior to demolition required. Plumbing notes emphasize field verification of existing utility locations, installation of new floor-mounted wall carriers for fixtures, replacement of damaged insulation, water hammer arrestors where required, and compliance with IECC energy code standards for hot water recirculation. Electrical demolition plans identify all existing devices to be removed, with several circuits made available for new equipment through demolition of existing receptacles. The project requires coordination among trades, particularly for equipment installation locations, and submission of approved plans by fire alarm installers in accordance with applicable state codes. The drawings include general notes referencing architectural documents for abatement requirements, with insulation and piping replacements required for any materials removed during abatement work.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FAN ROOM
HALL
HALL
JANITOR
WOMEN
LOUNGE
CORRIDOR
VESTIBULE
MEN
ELECTRICAL
OPEN OFFICE BREAK ROOM
OPEN OFFICE
14/10 EXH.
14/10 EXH.
(E) 14/12 EXHAUST
DUCT UP IN CHASE14/10 EXH.
T
EXISTING
AC-1
18/610/6 12/6
6/6
24/18 OA
46/30
24/16 EXH. EXH.
FAN
RR
RR
EXISTING
VAV-1-1
12"Ø10"Ø
Fort Worth 1st Floor
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
1ST FLOOR - MECHANICAL
DEMOLITION PLAN
M1.0
1ST FLOOR - MECHANICAL DEMOLITION PLAN
0 4' 8' 12'1
1. REMOVE EXISTING AIR DEVICE AND BRANCH DUCT AS INDICATED.
2. REMOVE EXISTING DUCTWORK AND CAP AT MAIN.
NOTES BY SYMBOL: " " #
1. REFER TO ARCHITECTURAL DOCUMENTS FOR ABATEMENT REQUIREMENTS. ALL DUCTWORK
INSULATION REMOVED DURING ABATEMENT SHALL BE REPLACED UNDER THIS CONTRACT.
VERIFY DUCT SIZES AND LENGTHS IN FIELD.
2. CONTRACTOR SHALL TEST AND DOCUMENT AIRFLOW AT EACH EXISTING SUPPLY AND
EXHAUST AIR DEVICE ASSOCIATED WITH THE REMODEL WORK PRIOR TO ANY DEMOLITION.
REPORT SHALL BE ISSUED TO THE ARCHITECT/ENGINEER PRIOR TO ANY DEMOLITION WORK.
GENERAL NOTES:
HVAC LEGEND
EXISTING (E)
DEMOLITION
NEW DUCTWORK
SUPPLY AIR DIFFUSER
RETURN OR EXHAUST AIR GRILLE
ROUND FLEXIBLE DUCTWORK
VOLUME DAMPER
CONNECT TO EXISTING
DIFFUSER OR GRILLE DESIGNATION
EX: EXISTINGTYPE CFM
A 150
01/05/2026
14/10 EXH.
14/10 EXH.
(E) 14/12 EXHAUST
DUCT UP IN CHASE14/10 EXH.
T
EXISTING
AC-1
18/610/6 12/6
6/6
24/18 OA
46/30
24/16 EXH.
EXIST.
EXH.
FAN
EXISTING
VAV-1-1
12"Ø10"Ø
EX 100 EX 100
S1 75
S2 200
S2 200
S1 50
S1 50
EX 90
S1 75
E1 300
E1 300
REBALANCE FOR
940 CFM MAX.
/14
8"Ø
6"Ø
10"Ø
6"Ø
8"Ø
10"Ø
8"Ø
E2 100
E2 100
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
1ST FLOOR -
MECHANICAL PLAN
M2.0
1ST FLOOR - MECHANICAL PLAN
0 4' 8' 12'1
1. UTILIZE EXISTING TAP AND EXTEND 6"Ø SUPPLY DUCT TO NEW AIR DEVICE.
NOTES BY SYMBOL: " " #
1. CONTRACTOR SHALL REPAIR OR REPLACE ANY DAMAGED INSULATION FOR EXISTING
SUPPLY DUCTWORK DOWNSTREAM OF (E) VAV-1-1; REFER TO 230713, 3.05.
GENERAL NOTES:
24"x24" SQ. LOUVERED FACE
CEILING DIFFUSER, 8"Ø NECK
NOTES:
1. ALL SUPPLY DIFFUSERS LISTED AS LOUVERED FACE TYPE SHALL BE (4) CONE LOUVER
TYPE, NO OPPOSED BLADE DAMPER.
2. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
3. NEW AIR DEVICES INSTALLED IN GYP BOARD, PLASTER, OR OTHER HARD CEILINGS
SHALL HAVE A SEPARATE MOUNTING FRAME.
WHITE ENAMEL
AIR DEVICE SCHEDULE
TYPE DESCRIPTION FINISH PRICE MODEL NO.
SCDS2
24"x24" PERFORATED FACE CEILING EXHAUST GRILLE, 22"x22" NECK WHITE ENAMELE1 PDDR
24"x24" SQ. LOUVERED FACE
CEILING DIFFUSER, 6"Ø NECK WHITE ENAMEL SCDS1
EXISTING TO REMAINEX
12"x12" PERFORATED FACE CEILING EXHAUST GRILLE, 10"x10" NECK WHITE ENAMELE2 PDDR
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
PLUMBING NOTES
AND SCHEDULES
P0.1
PLUMBING LEGEND
COLD WATER (CW)
HOT WATER (HW)
HOT WATER RETURN (HWR)
WASTE (SANITARY SEWER) (W)
VENT (SANITARY SEWER) (V)
BALL VALVE
NEW TO EXISTING CONNECTION
EXISTING (E)
V
FCO FLOOR CLEANOUT
WCO WALL CLEANOUT
VTR VENT THRU ROOF
DEMOLITION
NOTES:
1. ALL FIXTURES SHALL MEET LOW WATER CONSUMPTION REQUIREMENTS FOR THE STATE OF TEXAS.
2. PROVIDE STOPS AT ALL FIXTURES.
3. PROVIDE INSULATION KIT FOR ALL ACCESSIBLE LAVATORIES & SINKS WITH EXPOSED PIPING (TRUBRO LAV-GUARD OR APPROVED EQUAL).
4. PROVIDE NEW FLOOR MOUNTED WALL CARRIERS FOR ALL WALL MOUNTED FIXTURES.
5. ALL 'ACCESSIBLE' FIXTURES AND INSTALLATIONS SHALL COMPLY WITH TAS.
ACCESSIBLE
1/2"
1/2"
2"
LAVATORY
UNDERMOUNTL-1 2" 2"
1/2"
PLUMBING FIXTURE SCHEDULE
CW
ROUGH-IN SIZE
FLOOR MOUNTED
WATER CLOSET
WC-1
TAG FIXTURE
4"
W
2"
V HW
1" -
DESCRIPTION
ACCESSIBLE
AMERICAN STANDARD #3461.001, VITREOUS CHINA ELONGATED TOILET WITH EVERCLEAN.
SLOAN ROYAL #111 MANUAL FLUSH VALVE, 1.28 GPF, CHROME FINISH.
CHURCH #9500SSCT OPEN FRONT SEAT WITH SELF-SUSTAINING STA-TITE HINGES, NO COVER.
FLUSH VALVE SHALL BE MOUNTED TO OPERATE FROM WIDE SIDE OF STALL. TOP OF SEAT 17-1/2" A.F.F.
BOTTLE FILLER
FILTERED, ACCESSIBLE
REMOTE CHILLER
AMERICAN STANDARD #0496200.020. VITREOUS CHINA UNDERMOUNT LAVATORY.
DELTA #22C101 CENTERSET SINGLE LEVER FAUCET, GRID STRAINER & P-TRAP. ADA INSULATION PACKAGE.
-FD-1 -FLOOR DRAIN
HALSEY TAYLOR #HTHBGRN8-WF, BARRIER FREE, SINGLE STATION WALL MOUNTED BOTTLE FILLING STATION.
CABINET SHALL BE STAINLESS STEEL. COOLER SHALL HAVE AN INTEGRAL WATER FILTER AND DELIVER 8.0 GPH OF 50°F DRINKING WATER, 115/1Ø/60HZ, UTILIZE R-134A REFRIGERANT. PROVIDE WITH (2) ADDITIONAL WATER FILTERS.
REMOTE CHILLER SHALL BE INSTALLED ABOVE CEILING WITH PIPING AS REQUIRED.
SQUARE STRAINER 3"
AMERICAN STANDARD #6590.001EC VITREOUS CHINA, ELONGATED RIM WITH TOP SPUD.
SLOAN ROYAL #186-0.5 MANUAL FLUSH VALVE (0.5 GPF). MOUNT RIM 17" AFF.3/4"UR-1 -
URINAL, WALL HUNG
FLUSH VALVE 2" 2"
WATTS FD-100-M COATED CAST IRON WITH ADJUSTABLE SQUARE NICKEL BRONZE STRAINER.
FLOOR DRAIN SHALL HAVE NO HUB CONNECTION AND PROSET TRAP GUARD.
BF-1 1-1/2"
AMERICAN STANDARD #6590.001EC VITREOUS CHINA, ELONGATED RIM WITH TOP SPUD.
SLOAN ROYAL #186-0.5 MANUAL FLUSH VALVE (0.5 GPF). MOUNT RIM 24" AFF.3/4"UR-2 -URINAL, WALL HUNG
FLUSH VALVE 2" 2"
ACCESSIBLE
2"
1/2"
SINK, SINGLE COMPARTMENT
DROP-INS-1 2" 2" 1/2"
ACCESSIBLE
1/2"S-2 2" 2" 1/2"
SINK, SINGLE COMPARTMENT
DROP-IN
ACCESSIBLE
ELKAY #LRAD-2522-65-PD-2, 18 GA. STAINLESS STEEL 25" x 22" x 6-1/2" DEEP COUNTERTOP SINK WITH 2 FAUCET HOLES. DRAIN OPENING TO BE IN THE CENTER REAR LOCATION. DELTA #27C4944 FAUCET WITH LEVER HANDLES, GOOSENECK SPOUT, AERATOR, STRAINER AND P-TRAP. ADA INSULATION PACKAGE.
ELKAY #LRAD-1919-65-PD-2, 18 GA. STAINLESS STEEL 19" x 19" x 6-1/2" DEEP COUNTERTOP SINK WITH 2 FAUCET HOLES. DRAIN OPENING TO BE IN THE CENTER REAR LOCATION. DELTA #27C4944 FAUCET WITH LEVER HANDLES, GOOSENECK SPOUT, AERATOR, STRAINER AND P-TRAP. ADA INSULATION PACKAGE.
1. CONTRACTOR SHALL FIELD VERIFY LOCATIONS OF ALL EXISTING UTILITIES REQUIRED FOR
CONNECTIONS TO NEW PLUMBING FIXTURES.
2. REFER TO PLUMBING FIXTURE SCHEDULE FOR REQUIRED UTILITY CONNECTION SIZES.
3. REFER TO ARCHITECTURAL DOCUMENTS FOR ABATEMENT REQUIREMENTS. ALL PIPING
INSULATION REMOVED DURING ABATEMENT SHALL BE REPLACED. VERIFY PIPE SIZES AND
LENGTHS IN FIELD.
4. ALL PVC WASTE AND VENT PIPING ABOVE CEILING SHALL BE ASTM E84 INSULATED, RATED
AND APPROVED FOR USE IN PLENUM APPLICATIONS.
5. HOT WATER PIPING TO LAVATORIES SHALL BE RECIRCULATED TO COMPLY WITH APPLICABLE
ENERGY CODE (IECC). CIRCULATED HW PIPE SHALL BE ROUTED HORIZONTALLY WITHIN WALL
BEHIND EACH FIXTURE TO COMPLY WITH MAXIMUM PIPING LENGTH.
6. REMOVE ALL EXISTING WALL CARRIERS AND INSTALL NEW FLOOR MOUNTED WALL CARRIERS
FOR NEW WALL HUNG FIXTURES.
7. ALL PIPING WITHIN WALLS AND CHASES SERVING NEW PLUMBING FIXTURES SHALL BE NEW
WITH NEW INSULATION.
8. THE CONTRACTOR SHALL REPLACE ANY DAMAGED PIPE INSULATION FOR DOMSTIC HOT AND
COLD WATER SYSTEMS BELOW FLOOR OR ABOVE CEILING THAT SERVE THESE RESTROOMS -
REFER TO 220716, 3.05.
9. REPLACE EXISTING WALL CLEAN OUT COVERS WITH NEW STAINLESS STEEL ROUND COVER
WITH SCREW, EQUAL TO MIFAB C1400-RD (QTY. 4 ON THIS PROJECT).
10. REMOVE ALL EXISTING TRAP PRIMER VALVES AND PIPING SERVING EXISTING FLOOR DRAINS.
INSTALL A NEW PROSET TRAP GUARD FOR ALL NEW FLOOR DRAINS.
11. FURNISH AND INSTALL A PDI WATER HAMMER ARRESTOR WHERE INDICATED ON PLANS
AND/OR AS REQUIRED BY ASSE 1010 AND PDI.
GENERAL PLUMBING NOTES
WHA WATER HAMMER ARRESTOR
FAN ROOM
RESTROOM
HALL
HALL
RESTROOM
JANITOR WOMEN
LOUNGE
CORRIDOR
VESTIBULE
MEN
ELECTRICAL
OPEN OFFICE BREAK ROOM
OPEN OFFICE
AB
AN
DO
NE
D 8"
S
AN
. S
EW
ER
(E ) 5
" S
AN
. S
EW
ER
(E) 5"W FROM ABOVE
(E) 3" CW
(E) FIRE RISER
(E) FD
(E) 3" CW (E) 3" CW UP
(E) 1-1/2" HW FROM ABOVE
(E) 1-1/2" HW
(E) 1-1/2" HW
(E) 4" SAN. SEWER
(E) 5" SAN. SEWER
(E) 3/4" HWR UP
(E) FCO
(E) WCO
(E) WCO
(E) 2" CW
(E ) 3
/4" H
W R
(E) WCO
(E) WCO
(E) FIRE HOSE CABINET
(E) JAN. SINK
NOTE: CONFIRM EXISTING
ROUTING OF UTILITIES TO THIS
SINK TO MAINTAIN SERVICE.
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
1ST FLOOR - PLUMBING
DEMOLITION PLAN
P1.0
1ST FLOOR - PLUMBING DEMOLITION PLAN
0 4' 8' 12'1
1. REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL ASSOCIATED PIPING WITHIN THE WALL.
REMOVE EXISTING WALL CARRIER FOR URINALS. PLUG WASTE PIPING BELOW FLOOR AND
CAP VENT/WATER PIPING ABOVE CEILING. REPAIR AND SEAL FLOOR OPENINGS TO MATCH
EXISTING.
2. REMOVE EXISTING SINK AND PREPARE PIPING FOR INSTALLATION OF A NEW SINK AT THIS
APPROXIMATE LOCATION.
NOTES BY SYMBOL: " " #
WOMEN
JANITOR
CORRIDOR
MEN
VESTIBULE
HALL
BREAK ROOM
OPEN OFFICE
QUIET
HALL
ELECTRICAL
(E) 3" CW (E) 3" CW
(E) 1-1/2" HW
(E) 1-1/2" HW
(E) 2" CW
(E ) 3
/4" H
W R
FAN ROOM
L-13
WC-11
WC-1
UR-22
UR-1
L-13
WC-1
WC-1
L-1 3
L-1
L-1 3
L-1 3
S-1 4
S-2 5
BF-16
(E) FIRE HOSE CABINET
(E) JAN. SINK
(E) 3" CW UP
(E) 1-1/2" HW FROM ABOVE
(E) 3/4" HWR UP
WC-1 1
NEW ICE MAKER
(E)1/2"
2"
1/2"
2"
2"
INSTALL NEW
SHUT-OFF VALVE
(E) FIRE RISER
WC-2
WC-2
WC-2
WHA 'B'
WHA 'A'
WHA 'A'
WHA 'A'
WHA 'A'
WHA 'A' (TYP. 2)
3/4"
FLO-1
FLO-1
3/4"
1"
1"
PROVIDE
REDUCER TO 1"
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001 P2.0
1ST FLOOR - PLUMBING PLAN - WATER SUPPLY
0 4' 8' 12'1
1. PROVIDE AND INSTALL NEW WATER CLOSET. CORE DRILL NEW OPENINGS IN SLAB FOR
WASTE CONNECTIONS AS REQUIRED. EXTEND 4"W, 2"V AND 1" CW TO NEW FIXTURE.
2. PROVIDE AND INSTALL NEW URINAL WITH A NEW FLOOR MOUNTED WALL CARRIER. EXTEND
2"W, 2"V AND 3/4" CW TO NEW FIXTURE.
3. PROVIDE AND INSTALL NEW LAVATORY AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO EACH NEW FIXTURE. INSTALL A NEW FLOW SPLITTER ON THE EXISTING MAIN RECIRC LINE;
REDUCE BRANCH LINES FROM 1" TO 3/4", THEN EXTEND 3/4" RECIRCULATED HW DOWN IN
WALL BEHIND FIXTURE TO COMPLY WITH MAX PIPING LENGTH PER 2015 IECC.
4. PROVIDE AND INSTALL NEW SINK AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO
NEW FIXTURE.
5. PROVIDE AND INSTALL NEW SINK AND FAUCET. RECONNECT 2"W, 2"V, 1/2" CW AND 1/2" HW TO
NEW FIXTURE; EXTEND 1/2" CW WITH SHUT-OFF VALVE BELOW COUNTER TO NEW ICE MAKER.
6. PROVIDE AND INSTALL NEW BOTTLE FILLER. EXTEND 2"W, 1-1/2"V AND 1/2" CW TO NEW
FIXTURE. INSTALL FLOOR MOUNTED FRAME AND INSTALL REMOTE CHILLER ABOVE CEILING
PER MANUFACTURER'S INSTRUCTIONS.
NOTES BY SYMBOL: " " #
1ST FLOOR - PLUMBING
WATER SUPPLY
FLOW SPLITTERS
FLO-1
TAG MAIN PIPE SIZE BRANCH SIZE
NOTES:
1. FLOW SPLITTERS SHALL BE MANUFACTURED BY KEMPER
WATER CONTROL SYSTEMS WITH STOP VALVES (# 651 06).
1-1/2" 1"
WOMEN
JANITOR
CORRIDOR
MEN
VESTIBULE
HALL
BREAK ROOM
OPEN OFFICE
QUIET
HALL
ELECTRICAL
L-13
WC-11
WC-11
WC-11
WC-11
WC-11
UR-22
UR-12
L-13
WC-1
WC-1
L-1 3
L-1 3 L-1 3
L-1 3
S-1 4
S-2 4BF-15
(E ) 5
" S
AN
. S
EW
ER
(E) 4" SAN. SEWER
(E) 5" SAN. SEWER
(E) FIRE HOSE CABINET
FAN ROOM
(E) JAN. SINK
(E) 5"W FROM ABOVE
(E) FCO
(E) WCO
(E) WCO(E) WCO
FD-1
WC-1 1
NEW ICE MAKER
FD-1
FD-1
(E) FD
6 6
2"
2-1/2" 2"
(E) WCO
3"W, 2"V (TYP. FD)
SEE GENERAL NOTE 9 (TYP.)
1ST FLOOR - PLUMBING
WASTE & VENT
P2.1
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
1ST FLOOR - PLUMBING PLAN - WASTE & VENT
0 4' 8' 12'1
1. PROVIDE AND INSTALL NEW WATER CLOSET. CORE DRILL NEW OPENINGS IN SLAB FOR
WASTE CONNECTIONS AS REQUIRED. EXTEND 4"W, 2"V AND 1" CW TO NEW FIXTURE.
2. PROVIDE AND INSTALL NEW URINAL WITH A NEW FLOOR MOUNTED WALL CARRIER. EXTEND
2"W, 2"V AND 3/4" CW TO NEW FIXTURE.
3. PROVIDE AND INSTALL NEW LAVATORY AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW
TO NEW FIXTURE. THE HW RECIRCULATED LINE SHALL BE EXTENDED IN WALL BEHIND
FIXTURE TO COMPLY WITH MAX PIPING LENGTH PER 2015 IECC.
4. PROVIDE AND INSTALL NEW SINK AND FAUCET. EXTEND 2"W, 2"V, 1/2" CW AND 1/2" HW TO
NEW FIXTURE.
5. PROVIDE AND INSTALL NEW BOTTLE FILLER. EXTEND 2"W, 1-1/2"V AND 1/2" CW TO NEW
FIXTURE. INSTALL FLOOR MOUNTED FRAME AND INSTALL REMOTE CHILLER ABOVE CEILING
PER MANUFACTURER'S INSTRUCTIONS.
6. EXTEND NEW VENT LINE ABOVE CEILING AND CONNECT TO NEAREST EXISTING VENT MAIN.
NOTES BY SYMBOL: " " #
Restrooms Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
E INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN
CONDUIT WITH ONE PHASE, ONE NEUTRAL, AND ONE GROUND
FIRE ALARM SPEAKER/STROBE UNIT
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION
FIRE ALARM STROBE ONLY
JUNCTION BOX
GFI RECEPTACLE
DUPLEX RECEPTACLE
PUSHBUTTON
GROUND
CONDUIT AND HOMERUN TO PANEL - NOTE 2
208/120 V PANELBOARD
LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING
EMERGENCY LIGHTING UNIT WITH 2 LAMPS
LED LIGHT FIXTURE (2'X2', 2'X4') - REFER TO NOTE 1
NOTES:
1. LETTER ADJACENT TO FIXTURE DENOTES FIXTURE TYPE. REFER TO FIXTURE SCHEDULE.
2. WHEN NO HASH MARKS ARE SHOWN, PROVIDE ONE PHASE, ONE NEUTRAL, AND ONE GROUND CONDUCTOR.
3. SOME OF THESE SYMBOLS AND ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS.
XR INDICATES EXISTING DEVICE OR EQUIPMENT TO BE RELOCATED
PP
OS
CEILING MOUNTED POWER PACK
CEILING MOUNTED OCCUPANCY SENSOR
ELECTRICAL SYMBOL LIST
& IECC DOCUMENTS
E0.1
XN INDICATES NEW LOCATION OF EXISTING DEVICE OR EQUIPMENT
LOW VOLTAGE SWITCH WITH ON/OFF CONTROL
ER INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION LAMPS
A4
A2 2'X2' TROFFER, SMOOTH REFLECTOR, 3300 LUMENS, CURVED & RIBBED DIFFUSER, UNIVERSAL 120-277
VOLTAGE, 0-10V DIMMING, 82CRI, 3500K CCT
LITHONIA #2BLT2-33L-ADP-EZ1-LP835
26.6 W LED
WITH UNIT
2'X4' TROFFER, SMOOTH REFLECTOR, 4000 LUMENS, CURVED & RIBBED DIFFUSER, UNIVERSAL 120-277
VOLTAGE, 0-10V DIMMING, 82CRI, 3500K CCT
LITHONIA #2BLT4-40L-ADP-EZ1-LP835
30.5 W LED
WITH UNIT
C RECESSED LINEAR, 381 LUMENS/FT, 3500K CCT, 120V, REFER TO DRAWING FOR EACH FIXTURE LENGTH, COORDINATE MOUNTING SELECTION WITH ARCHITECT
FINELITE #HP-4R-D-[LENGTH]-S-835-F-96LG-277-SC-FC-10%-[MOUNTING]
3.6 W/FT LED
WITH UNIT
D 18" LONG UNDERCABINET LIGHT, 100% FROSTED LENS, [FINISH], 3500K CCT, 480 LUMENS/FT, 0-10V DIMMING, NO FEED, INDOOR LISTING, UNIVERSAL VOLTAGE, NO ROCKER SWITCH, NO OCCUPANCY SENSOR, HARDWIRED
ALUZ LIGHTING #A1-ZADY-STN-F-[FINISH], 35K-5W-10V-NF-DRY-UNV-18"
5 W/FT LED
WITH UNIT
WOMEN
JANITOR
CORRIDOR
MEN
VESTIBULE
HALL
BREAK ROOM
OPEN OFFICE
QUIET
HALL
ELECTRICAL
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
ER
E
ER
ER
ER
E
E
XR
E E
E
XR
XR
CLG
CLG
CLG
XR
CLG
E
F
XR
CLG
F
XR
CLG
F
E
CLG
F
E
CLG
F
F
E
CLG
F
E
CLG
F
E
E
CLG
E
PANEL A1
E
PANEL A2
E
E
E
E
E
E
E
E
E
E
E
E
CLG
F
E E
CLG
F
ER* *
E
E
E E E
E E
EE
EE
EE
EE
E
E
E
E
XR
CLG
F
ER *
Restrooms
Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
1ST FLOOR - ELECTRICAL
DEMOLITION PLAN
E1.0
NOTE BY SYMBOL: " "
1. CONTRACTOR SHALL REMOVE EXISTING LIGHT FIXTURE AND PREPARE EXISTING EXISTING
LIGHTING CIRCUIT FOR NEW LIGHT FIXTURES IN THE SAME ROOM. REFER TO SHEET E2.0 FOR
ADDITIONAL INFORMATION.
2. ALL LIGHTING AND LIGHTING CONTROLS IN THIS ROOM ARE EXISTING TO REMAIN.
3. INTERCEPT RECEPTACLE CIRCUIT AND EXTEND TO NEW DEVICE AS NOTED BY NOTE BY
SYMBOL #3, SHEET E2.0 FOR NEW LOCATION.
4. INTERCEPT RECEPTACLE CIRCUIT AND EXTEND TO NEW DEVICE AS NOTED BY NOTE BY
SYMBOL #4, SHEET E2.0 FOR NEW LOCATION.
1ST FLOOR - ELECTRICAL DEMOLITION PLAN
0 4' 8' 12'1
WOMEN
JANITOR
CORRIDOR
MEN
VESTIBULE
HALL
BREAK ROOM
OPEN OFFICE
QUIET
HALL
ELECTRICAL
E
E
E E
E
E
PANEL A1
E
PANEL A2
LA-6
LA-23
LA-21
E
PANEL LA
LA-10
E *
E
LA-24
LA-12
LA-12
LA-22LA-19
LA-18
Restrooms
Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
SHEET NOTES:
1. CONTRACTOR SHALL DEMOLISH ALL DEVICES SHOWN ON DETAIL 1, SHEET E1.0 UNLESS
OTHERWISE NOTED.
2. FIRE ALARM LAYOUT IS SCHEMATIC AND INTENDED TO ILLUSTRATE THE APPROXIMATE
LOCATIONS OF DEVICES. SUBMIT APPROVED PLANS IN ACCORDANCE WITH APPLICABLE
STATE CODES AND INSTALL FIRE ALARM SYSTEM BY AN APPROVED FIRE ALARM INSTALLER.
REFER TO FIRE ALARM SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
3. VERIFY FINAL LENGTHS OF ALL TYPE 'C' LIGHT FIXTURES WITH ARCHITECT.
NOTE BY SYMBOL: " "
1. POWER FOR ICE MAKER. PROVIDE A NEW 20A/1P GFI PROTECTED CIRCUIT BREAKER IN
EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL
FINAL CONNECTIONS.
2. POWER FOR UNDERCOUNTER REFRIGERATOR. PROVIDE A NEW 20A/1P GFI PROTECTED
CIRCUIT BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN
3/4"C. AND MAKE ALL FINAL CONNECTIONS.
3. NEW LOCATION OF EXISTING CIRCUIT MADE AVAILABLE BY DEMOLITION OF EXISTING
RECEPTACLE. REFER TO NOTE BY SYMBOL #3, SHEET E1.0 FOR EXISTING LOCATION.
4. NEW LOCATION OF EXISTING CIRCUIT MADE AVAILABLE BY DEMOLITION OF EXISTING
RECEPTACLE. REFER TO NOTE BY SYMBOL #4, SHEET E1.0 FOR EXISTING LOCATION.
5. POWER FOR BOTTLE FILLER CONDENSER IN CEILING. PROVIDE A NEW 20A/1P GFI PROTECTED
CIRCUIT BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN
3/4"C. AND MAKE ALL FINAL CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND
CONNECTION REQUIREMENTS WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.
6. POWER FOR HAND DRYER. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT BREAKER IN
EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL CONNECTIONS.
7. COORDINATE AUTOMATIC DOOR SWING ACTIVATOR SELECTION AND LOCATION WITH
ARCHITECT. PROVIDE 3/4" CONDUIT WITH PULL STRING BETWEEN ACTIVATOR AND SWING
DOOR OPERATOR PER MANUFACTURER'S SPECIFICATIONS.
8. POWER FOR SWING DOOR OPERATOR AT WOMEN 105. CONNECT TO TO AN EXISTING 20A/1P
CIRCUIT BREAKER IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL
FINAL CONNECTIONS.
9. POWER FOR SWING DOOR OPERATOR AT VESTIBULE 102. PROVIDE 2#12, 1#12G., IN 3/4"C. TO
DOOR OPENER AT WOMEN 105 AND MAKE ALL FINAL CONNECTIONS.
10. POWER FOR MICROWAVE ABOVE COUNTER. PROVIDE A NEW 20A/1P GFI PROTECTED CIRCUIT
BREAKER IN EXISTING SPACE IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND
MAKE ALL FINAL CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND CONNECTION
REQUIREMENTS WITH PLUMBING CONTRACTOR PRIOR TO ROUGH-IN.
11. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT BREAKER IN EXISTING PANEL 'LA' AND
EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL CONNECTIONS.
1ST FLOOR - ELECTRICAL
POWER PLAN
E2.0
1ST FLOOR - ELECTRICAL POWER PLAN
WOMEN
JANITOR
CORRIDOR
MEN
VESTIBULE
HALL
BREAK ROOM
OPEN OFFICE
QUIET
HALL
ELECTRICAL
C
(9'-11")
C
(6'-0")
C
(6'-0")
A2
A4 a a a b b a,b a,b a,b a,b
A4
A4 A4 A4 a,ba,b
C
(15'-11")
C
(8'-9")
A4
A4
A4 a a a b b a,ba,b a,b a,b
E
E
E
E
XN
E
XN
CLG
CLG
E
CLG
F
E
CLG
F
E
E
E
E
E
CLG
F
E E
CLG
F
E
E E E
E E
EE
EE
EE
EE
E
E
E
E
XN
CLG
F
XN
CLG
F
XN
CLG
F
LA-20
XN
CLG
F
E
CLG
XN
CLGF
D b D b
D a D aD aD a a a
Restrooms
Renovation
307 W 13th St., Fort Worth, TX.
76102
6300 Ridglea Place, Suite 700 Fort Worth, TX 76116 mail@bhbinc.com • 817.338.1277 • bhbinc.com
TBPELS Firm #44, #10011300, #1001302, #10194146
BHB PROJECT # 2025.011.001
PP OS
CAT-5E CABLE
LINE VOLTAGE
TO LIGHT FIXTURES
ACUITY NLIGHT NPODMA SERIES
WALLPOD SWITCH. NUMBER OF
DEVICES AS SHOWN ON DETAIL 2,
SHEET E1.0.
LIGHTING CONTROL DETAIL
1ST FLOOR - ELECTRICAL
LIGHTING PLAN
E3.0
ACUITY NLIGHT NPP16
POWER/RELAY PACK. NUMBER
OF DEVICES AS SHOWN ON
DETAIL 2, SHEET E1.0.
ACUITY NLIGHT NCM PDT 10 RJB
CEILING MOUNT SENSOR.
NUMBER OF DEVICES AS SHOWN
ON DETAIL 2, SHEET E1.0.
NOTE BY SYMBOL: " "
1. CONNECT TO EXISTING LIGHTING CIRCUIT MADE SPARE BY DEMOLITION OF EXISTING
LIGHTING IN THIS AREA. REFER TO DETAIL 2, SHEET E3.0 FOR ADDITIONAL INFORMATION
REGARDING LIGHTING CONTROL REQUIREMENTS IN THIS ROOM.
2. POWER FOR VANITY MIRROR LIGHTING. CONNECT TO AN EXISTING SPARE 20A/1P CIRCUIT
BREAKER IN EXISTING PANEL 'LA' AND EXTEND 2#12, 1#12G., IN 3/4"C. AND MAKE ALL FINAL
CONNECTIONS. CONFIRM EXACT INSTALLATION LOCATION AND CONNECTION REQUIREMENTS
WITH GENERAL CONTRACTOR PRIOR TO ROUGH-IN.
3. CONNECT TO EXISTING LIGHTING CIRCUIT AS DIRECTED IN APPLICABLE NOTE BY SYMBOLS
SHOWN AT EACH LIGHTING POWER PACK.
4. INTERCEPT EXISTING UN-SWITCHED LIGHTING CIRCUIT IN THIS ROOM TO POWER NEW UNDER
CABINET LIGHTING IN THIS ROOM. REFER TO DETAIL 2, SHEET E3.0 FOR ADDITIONAL
INFORMATION REGARDING LIGHTING CONTROL REQUIREMENTS IN THIS AREA.
SHEET NOTES:
1. CONTRACTOR SHALL DEMOLISH ALL DEVICES SHOWN ON DETAIL 1, SHEET E1.0 UNLESS
OTHERWISE NOTED.
2. FIRE ALARM LAYOUT IS SCHEMATIC AND INTENDED TO ILLUSTRATE THE APPROXIMATE
LOCATIONS OF DEVICES. SUBMIT APPROVED PLANS IN ACCORDANCE WITH APPLICABLE
STATE CODES AND INSTALL FIRE ALARM SYSTEM BY AN APPROVED FIRE ALARM INSTALLER.
REFER TO FIRE ALARM SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
3. VERIFY FINAL LENGTHS OF ALL TYPE 'C' LIGHT FIXTURES WITH ARCHITECT.
1ST FLOOR - ELECTRICAL LIGHTING PLAN
| G0.0 |
| G0.1 |
| G0.2 |
| G0.3 |
| A1.1 |
| A2.1 |
| A2.2 |
| A5.1 |
| A6.1 |
| A9.1 |
| Mech-Plum |
| M1.0 |
| Electrical |
| E0.1 |
| E1.0 |
| E1.0 |
| E2.0 |
| E3.0 |
File details come from the government source that posted it. Updated .