Amd 02 Exhibit 2.2 RFI's & Responses 04.27.20.docx

DOCX document 1 MB Posted

Attached to
911 Fed Bldg Electrical System Upgrade Design Build Federal contract opportunity
Solicitation number
EQ10PCP-20-0005
Issued by
General Services Administration Public Buildings Service Region 10

About this file

This document contains a request for information and responses related to a federal solicitation for electrical system upgrade design-build services at the 911 Federal Building in Portland, Oregon. The scope of work includes replacing all medium and low-voltage switchgear, switchboards, and panel boards throughout the eight-story building; replacing the motor control centers; replacing the 150kW emergency generator with a 250kW unit; and installing a new lightning protection system. Ten federal agencies occupy the building, including the U.S. Congress, Department of the Interior, Department of Labor, General Services Administration, and Department of Energy. The responses provide details on the existing fuel storage tanks and pumps, fire alarm and sprinkler system maintenance contractors, and confirm that electrical and IT closets have sprinkler coverage and the design-build contractor should include installing sprinkler heads in the revised closets.

View the file

Other files for this federal contract opportunity

Other files attached to 911 Fed Bldg Electrical System Upgrade Design Build, newest first.
File Type Posted
Amd 02 Exhibit 1.2 911 Fed Bldg Electrical Upgrade Design Build SOW (Final) 4.24.20.docx DOCX document
Amd 02 Exhibit 6 Price and Services Schedule 4.24.20.docx DOCX document
Amd 02 Division 01 Specifications-20200427T224125Z-001 (1).zip ZIP file
Amd 02 911 Fed Bldg Electrical Upgrade Design Build - Agreement 4.27.20 (Conformed).docx DOCX document
Amd 02 SF30.pdf PDF
Amd 02 Exhibit 7 Wage Determination Gen Decision OR20200029 Mod 3 04172020.pdf PDF
911 Electrical Site Visit Attendance Sheet.docx DOCX document
911 Electrical Agenda (Pre-Proposal Conference) (6).docx DOCX document
Exhibit 9 Key Personnel Resume Format.docx DOCX document
SF30 Amd 01.pdf PDF
Amd 01 911 Fed Bldg Electrical Upgrade Design Build - Solicitation 4.2.20 (Conformed).docx DOCX document
Amd 01 Exhibit 1.2 911 Fed Bldg Electrical Upgrade Design Build SOW (Draft) 4.6.20.docx DOCX document
Amd 01 Exhibit 9 CD-2020-05 - Digital Signatures for Bonds.pdf PDF
Amd 01 Exhibit 2 Pre-Proposal Conference Job Walk 4.2.20 (Conformed).docx DOCX document
Amd 01 Exhibit 6 Price and Services Schedule 4.2.20.docx DOCX document
Amd 01 911 Fed Bldg Electrical Upgrade Design Build - Agreement 4.6.20 (Conformed).docx DOCX document
Exhibit 2 Pre-Proposal Conference Job Walk.docx DOCX document
Exhibit 6 Price and Services Schedule.docx DOCX document
Exhibit 8 Offerors Representations and Certifications.docx DOCX document
911 Fed Bldg Electrical Upgrade Design Build - Agreement 3.23.20.docx DOCX document
911 Fed Bldg Electrical Upgrade Design Build - Solicitation 3.23.20.docx DOCX document
Exhibit 00 SF1442.pdf PDF
Exhibit 1.1 911 FB Seismic-NOAA-Electrical Milestone Schedule 1.27.20.pdf PDF
Exhibit 1 911 Fed Bldg Electrical Upgrade Scope Summary.docx DOCX document
Exhibit 0 SBU Document.docx DOCX document
Exhibit 7 Wage Determination Gen Decision OR20200029 Mod 2 03062020.pdf PDF
Exhibit 4 Performance Evaluation Survey - Commercial Client.docx DOCX document
Exhibit 3 Project Experience.docx DOCX document
Exhibit 5 GACA - GSA Affiliated Customer Accounts May 2014.docx DOCX document
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

911 Federal Building Electrical Upgrade Design-Build GSA Solicitation No. EQ10PCP-20-0005 RFI Log

1. What are the dimensions & storage capacity of the existing fuel storage tank?

ANSWER: The Eastside Federal Complex (Building 905/BPA and the 911 Federal Building) has two interconnected fuel storage tanks in the B1 level of the 911 FB. One 8,000 USG tank, and one 12,000 USG tank. BPA maintains both tanks. GSA has a 25 USG day-tank connected to the 911FB emergency generator, located in the mechanical penthouse. Approximate dimensions of the 25 USG day-tank assembly are 17”x26”x39”.

2. Where is the storage tank and fuel pump located in the basement so that we can determine a cost plan for replacement if it needs to be upsized?

ANSWER: We have two interconnected fuel storage tanks (8,000USG and 12,000USG) in the B1 level of the 911 FB. GSA does not expect the 911FB Electrical DB Contractor to replace these (2) large storage tanks under this project. However, the emergency generator’s day-tank shall be replaced, properly sized for the new generator that’s also installed under the project.

3. What are the existing fuel pump specs?

ANSWER: Refer to the (4) pictures from the pumps, attached.

4. What are the fuel line sizes from the tank to the pump to the generator?

ANSWER: 1-1/4” (exterior) pipe size. See piping picture, attached.

5. Who is the current Fire Alarm provider for the building – name and phone number?

ANSWER: GSA has an Edwards EST-3 Fire Alarm panel in the 911 FB. Our O&M Contractor, Team BRCS, operates and maintains it, and we have a separate FA monitoring company. Team BRCS Building Engineer POC info:

Ray Korfel TeamBRCS Chief Engineer 911 NE 11th AVE Portland, OR 97232 503-516-8127 rkorfel@teamgov.com

6. Who does Operations & Maintenance on the fire sprinkler system - name and phone number?

ANSWER: Our O&M contractor, Team BCRS, maintains the system. Team BCRS Building Engineer POC info:

Ray Korfel TeamBRCS Chief Engineer 911 NE 11th AVE Portland, OR 97232 503-516-8127 rkorfel@teamgov.com

7. Lightning protection upgrade questions:

a. Code UL-96A requires the use of an exterior, buried ground ring - this would involve tear out and replacement of sidewalks, planters, etc.; is this what the owner is envisioning

b. Install ground rods underground inside the basement area to tie in the roof down wires to – is this an acceptable solution?

ANSWER: Start here.

8. Pacific Power (PP&L) is requesting additional customer information before we can obtain pricing on any service modifications or further coordination/interaction. Please provide additional customer information so we can further engage with PP&L.

ANSWER: Customer Name:US GENERAL SVC ADMIN
Service Address:911 NE 11TH AVE
PORTLAND OR 97232-4128
Account Number:01673911-003 5

9. Do existing electrical closets / rooms have sprinkler coverage? Note that PBS P100 specs call for it.

a. If so, do we need to have a provision in our quote to install a sprinkler head in the I/T closets once the closet build-outs are complete (firewall installation)?

ANSWER (4/27/2020): Electrical closets (East & West side) have sprinkler coverage. Offerors should include work to provide sprinkler head coverage in the revised IT/data closet side of the space once East & West side closet build-outs are complete.