Drawings Boiler Replacement_Part1.pdf

PDF 15 MB Posted

Attached to
Z1DA--Coal Boiler Replacement and Plant Improvements (VA-21-00039435)
Solicitation number
36C25921R0071
Issued by

About this file

This solicitation notice is for a coal boiler replacement and plant improvements project at a Veterans Affairs medical center. The contractor shall provide all necessary materials, labor, tools, equipment, and supervision to replace coal boilers in building 90 and conduct related work. The project value is between $1 million and $5 million. The solicitation number is 36C25921R0071 and will be set aside 100% for Service-Disabled Veteran-Owned Small Businesses. The point of contact is Joseph Wingfield of the Veterans Affairs Healthcare System in Sheridan, Wyoming. Offerors must be verified and listed in the Vendor Information Pages database to be considered eligible for award. The work will be performed at the Sheridan Veterans Affairs Medical Center for the Veterans Integrated Service Network 19 of the Department of Veterans Affairs.

View the file

Other files

File Type Posted
36C25921R0071 0012.docx DOCX document
CONTRACTOR spaces- 1-1-2022.pdf PDF
36C25921R0071 0011.docx DOCX document
36C25921R0071 0011.docx DOCX document
36C25921R0071 0010.docx DOCX document
Amendment 10 - Sheridan Boiler RFI responses.pdf PDF
Amendment 10 - B3 water level warrick dwg.pdf PDF
Amendment 10 - Hays Boiler 3 Mechanical.pdf PDF
Amendment 10 - Condensate Tank.pdf PDF
Amendment 10 - Submittal 36 B3 Burner_Part1.pdf PDF
Amendment 10 - Condensate tank specs.pdf PDF
Amendment 10 - Deaerator specs.pdf PDF
Amendment 10 - Submittal 36 B3 Burner_Part2.pdf PDF
Amendment 10 - Deaerator tank.pdf PDF
Amendment 10 - Final B3 fire eye loops.pdf PDF
Amendment 10 - S02 - Calculation Worksheet for Self-Performed and Subcontracted Work.docx DOCX document
36C25921R0071 0009.docx DOCX document
36C25921R0071 0008.docx DOCX document
36C25921R0071 0007.docx DOCX document
Instructions to Offerors - Coal Boilers Sheridan.pdf PDF
36C25921R0071 0006.docx DOCX document
36C25921R0071 0005.docx DOCX document
IMG_0217.jpg JPG image
Pre Bid Sign In Sheridan Boiler.pdf PDF
36C25921R0071 0004.docx DOCX document
2226.04_SHERIDAN BOILER_CONSTRUCTION DOCUMENTS - Geotech Samples.pdf PDF
IMG_0219.jpg JPG image
Pics - 1.docx DOCX document
Pics - 2.docx DOCX document
Pics - 3.docx DOCX document
IMG_0218.jpg JPG image
Pre Bid Sign In Sheridan Boiler 2.pdf PDF
Questions for Replace Coal Boilers and VA Answers Updated 10-15.docx DOCX document
DSC02962.jpg JPG image
36C25921R0071 0003.docx DOCX document
36C25921R0071 0002.docx DOCX document
36C25921R0071 0001.docx DOCX document
Drawings Boiler Replacement_Part2.pdf PDF
36C25921R0071_1.docx DOCX document
Specifications Boiler Replacement.pdf PDF
S02 - Calculation Worksheet for Self-Performed and Subcontracted Work.docx DOCX document
2015-06-05 Past Performance Questionnaire.docx DOCX document
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RENDERED IMAGEAREA OF WORK SHEET INDEX

SHERIDAN VA MEDICAL CENTER

SHERIDAN, WY

VAMC PROJECT #: 666-18-114

BUILDING 90 REPLACE COAL BOILERS DESIGN

North

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 DD RT

GI001

COVER SHEET

BLDG. 90

BOILER PLANT

BLDG. 90

BOILER PLANT

North

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SCALE OF FEET

Valhalla Engineer 5 Snapshot

O

O

O

O

O O

O O

O O

O

O

O

01/15/2020 BRD DJD

C-001

CIVIL GENERAL NOTES

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

N NORTH

NA NOT APPLICABLE

NAT NATURAL

NATL NATIONAL

NBC NATIONAL BUILDING CODE

NE NOT EXCEEDING

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NORM NORMAL

NRCP NON-REINFORCED CONCRETE PIPE

NTP NOTICE TO PROCEED

NTS NOT TO SCALE

OC ON CENTER

OFD OVERFLOW DRAIN

OPNG OPENING

OZ OUNCE

P PUMP

PA PIPE ANCHOR

PB PULL BOX

PC POINT OF CURVE

PCA PORTLAND CEMENT ASSOCIATION

PCC PRECAST CONCRETE

PCCP CONCRETE PAVEMENT

PCT PERCENT

PED PEDESTAL

PEN PENETRATE

PERF PERFORATED

PERIM PERIMETER

PERM PERMANENT

PERP PERPENDICULAR

PG PRESSURE GAGE OR PROFILE GRADE

PH PHASE

PHWR PRIMARY HOT WATER RETURN

PHWS PRIMARY HOT WATER SUPPLY

PI POINT OF INTERSECTION

PIV POST INDICATOR VALVE

PL PROPERTY LINE

PLAS PLASTIC OR PLASTER

PMPSCT PUMP SUCTION

PN PART NUMBER

PNEU PNEUMATIC

PO POST OFFICE OR PURCHASE ORDER

POLY POLYETHYLENE (PLASTIC)

PORT PORTABLE

POTW POTABLE WATER

POW LN POWER LINE

PP POLYPROPYLENE (PLASTIC)

PR PUMPED RETURN

PRCST PRECAST

PREFMD PREFORMED

PRELIM PRELIMINARY

PREP PREPARATION

PROP PROPERTY

PRV PRESSURE REGULATOR VALVE OR

PRESSURE RELIEF VALVE

PS CONC PRESTRESSED CONCRETE

PSI POUNDS PER SQUARE INCH

PSL PIPE SLEEVE

PT POST-TENSIONED

PT CONC POST-TENSIONED CONCRETE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

PV PAVED

PVC POLYVINYL CHLORIDE (PLASTIC)

QTR QUARTER

QTY QUANTITY

QUAD QUADRANT

QUAL QUALITY

R RADIUS OR RANGE

RAD RADIAN

RC REINFORCED CONCRETE

RCB REINFORCED CONCRETE BOX

RCCP REINFORCED CONCRETE CULVERT PIPE

RCP REINFORCED CONCRETE PIPE

RD ROAD OR ROOF DRAIN

RDC REDUCER

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

RFI REQUEST FOR INFORMATION

RFP REQUEST FOR PROPOSAL

ROW RIGHT OF WAY

RT RIGHT

RV RELIEF VALVE

RW ROADWAY

RWL RAIN WATER LEADER

RWR RECESSED WASTE RECEPTACLE

SAMP SAMPLE

SAN SANITARY

SB SPLASH BLOCK

SCHED SCHEDULE

SCP SCUPPER

SD STORM DRAIN

SDL SADDLE

SDMH STORM DRAIN MANHOLE

SECT SECTION

SEG SEGMENT

ABAN ABANDON

ABBRV ABBREVIATION

ABC AGGREGATE BASE COURSE

AC ASPHALTIC CONCRETE

ACP ASPHALTIC CONCRETE PAVING

ADA AMERICANS WITH DISABILITIES ACT

AGGR AGGREGATE

ALT ALTERNATE OR ALTITUDE

AMT AMOUNT

APPROX APPROXIMATE

ASB ASBESTOS

ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS

ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION

ASPH ASPHALT

ASSY ASSEMBLY

AVE AVENUE

AWWA AMERICAN WATER WORKS ASSOCIATION

B&F BELL AND FLANGE

B&S BELL AND SPIGOT

BC BACK OF CURB

BCV BUTTERFLY CHECK VALVE

BDRY BOUNDARY

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BITUM BITUMINOUS

BL BASE LINE

BLDG BUILDING

BLT BUILT

BLVD BOULEVARD

BM BEAM OR BENCHMARK

BN BULLNOSE

BRG BEARING

BSTR BOOSTER

BV BALL VALVE

BW BOTH WAYS

BWG BIRMINGHAM WIRE GAUGE

CAP CAPACITY

CB CATCH BASIN OR CEMENT BASE

CD CONSTRUCTION DOCUMENTS OR CONTRACT

DOCUMENTS

CDW CHILLED DRINKING WATER

CDWR CHILLED DRINKING WATER RETURN

CDWS CHILLED DRINKING WATER SUPPLY

CEM CEMENT OR CEMETERY

CF CONTRACTOR FURNISHED

CFS CUBIC FEET PER SECOND

CHFR CHAMFER

CHK CHECK

CHKV CHECK VALVE

CI CAST IRON OR CURB INLET

CIP CAST-IN-PLACE OR CAST IRON PIPE

CJ CONSTRUCTION JOINT OR CONTROL JOINT

CL CENTER LINE, CLASS, OR CLOSE

CLL CONTRACT LIMIT LINE

CLOS CLOSURE

CMP CORRUGATED METAL PIPE

CND CONDUIT

CNDS CONDENSATE

CO CERTIFICATE OF OCCUPANCY, CLEANOUT,

COMPANY, OR CUTOUT

CONC CONCENTRIC OR CONCRETE

CONSTR CONSTRUCTION

CONSULT CONSULTANT

CONTR CONTRACT OR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S REPRESENTATIVE

COTG CLEANOUT TO GRADE

COV COVER OR CUT OFF VALVE

COV PL COVER PLATE

CPLG COUPLING

CPP CORRUGATED PLASTIC PIPE

CRP CONDENSATE RETURN PUMP

CRT YD COURTYARD

CSB CONCRETE SPLASH BLOCK

CSI CONSTRUCTION SPECIFICATIONS INSTITUTE

CSP CONCRETE SEWER PIPE

CSTL CAST STEEL

CU COPPER OR CUBIC

CU FT CUBIC FEET

CU IN CUBIC INCH

CU YD CUBIC YARD

CV CONTROL VALVE

CW CLOCKWISE

DA DRAINAGE AREA

DAT DATUM

D-B DESIGN-BUILD

DBA UNIT OF SOUND LEVEL

DEG DEGREE

DEL DELETE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DEV DEVELOPMENT

DHW DOMESTIC HOT WATER

DI DROP INLET

DIA DIAMETER

DIFF DIFFERENCE OR DIFFERENTIAL

DIM DIMENSION

DIP DUCTILE IRON PIPE

DOM DOMESTIC

DR DRAIN OR DRIVE

DS DOWNSPOUT

DSBL DISABLE

DW DOMESTIC WATER

DWG DRAWING

DWR DOMESTIC WATER RETURN OR DRAWER

DWS DOMESTIC WATER SUPPLY

SEP TNK SEPTIC TANK

SF SQUARE FOOT (FEET)

SJ SCORED JOINT

SLV SLEEVE

SM SILTY SAND

SMH STEAM MANHOLE

SMP SUMP PUMP

SOV SHUT OFF VALVE

SP STANDPIPE OR SUMP PIT

SP EL SPOT ELEVATION

SPEC SPECIFICATION

SPKLR SPRINKLER

SPLY SUPPLY

SPR SPRINKLER LINE

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SR STEAM RETURN

SS SANITARY SEWER, STEAM SUPPLY, OR

STORM SEWER

SSP STAINLESS STEEL PIPE

SST STAINLESS STEEL

ST STREET OR STORM DRAIN

ST W STORM WATER

STA STATION

STD STANDARD

STM STEAM

SURV SURVEY

SUTK SUMP TANK

SW SIDEWALK

SWG SEWAGE

SWR SEWER

SYM SYMBOL

T&M TIME AND MATERIALS

TAN TANGENT

TBM TEMPORARY BENCHMARK

TB-XX TEST BORING-XX (E.G., TB-01)

TCP TRAFFIC CONTROL PLAN

TD TRENCH DRAIN

TE TOP ELEVATION

TEMP TEMPORARY

THK THICKNESS

THRU THROUGH

TMH TOP OF MANHOLE

TN TRUE NORTH

TNL TUNNEL

TO TOP OF ___

TO FDN TOP OF FOUNDATION

TOB TOP OF BEAM

TOC TOP OF CONCRETE OR TOP OF CURB

TOC FTG TOP OF CONCRETE FOOTING

TOC WALL TOP OF CONCRETE WALL

TOF TOP OF FOOTING

TOP TOP OF PAVEMENT

TOPO TOPOGRAPHY

TOS TOP OF SLAB

TR TOP OF RIM

TWR TREATED WATER RETURN

TWS TREATED WATER SUPPLY

TYP TYPICAL

UFC UNIFORM FIRE CODE

UGND UNDERGROUND

UON UNLESS OTHERWISE NOTED

UP UTILITY POLE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

VA VETERAN AFFAIRS

VAR VARIES

VHA VETERANS HEALTH ADMINISTRATION

VB VALVE BOX

VC VERTICAL CURVE

VCO VACUUM CLEANER OUTLET

VCT VITRIFIED CLAY TILE VINYL COMPOSITION

TILE

VERT VERTICAL

VIC VICINITY

VIF VERIFY IN FIELD

VOL VOLUME

W WASTE, WEST, OR WIDE

W/ WITH

W/O WITHOUT

WI WROUGHT IRON

WL WATER LINE

WM WATER METER WIRE MESH

WM WIRE MESH WATER METER

WO WORK ORDER

WP WATER PUMP

WT WATER TABLE

WT EL WATER ELEVATION

WTR WATER

WW WASTE WATER

XFMR TRANSFORMER

EC EDGE OF CURB

EJ EXPANSION JOINT

EL EASEMENT LINE OR ELEVATION

ENGR ENGINEER

EOS EDGE OF SLAB

EP EDGE OF PAVEMENT (PAVING)

EPA ENVIRONMENTAL PROTECTION AGENCY

EPT EXTERNAL PIPE THREAD

EQ EQUAL

EQL SP EQUALLY SPACED

ERD EXISTING ROOF DRAIN

ESMT EASEMENT

EST ESTIMATE

EXIST EXISTING

EXP EXPANSION

EXST GR EXISTING GRADE

EXT EXTERIOR

EXT GR EXTERIOR GRADE

F FAHRENHEIT, FEMALE, FIRE LINE

F METER FLOWMETER

FD FLOOR DRAIN

FF EL FINISH FLOOR ELEVATION

FH FIRE HYDRANT

FIL FILLET

FIN FINISH

FLG FLANGE

FLRD FLARED

FLTR FILTER

FLUOR FLUORESCENT

FN FENCE

FOC FACE OF CURB

FP FIRE PROTECTION OR FLAGPOLE

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPW FIRE PROTECTION WATER SUPPLY

FSP FIRE STANDPIPE

FSS FLOW SENSING SWITCH

FT FEET OR FOOT

FTG FOOTING

FW FLOOD WALL

G GROUND OR NATURAL GAS

G LN GAS LINE

GA GAGE

GAL GALLON

GC GENERAL CONTRACTOR

GCO GRADE CLEANOUT

GDR GUARD RAIL

GI GALVANIZED IRON

GIP GALVANIZED IRON PIPE

GL GROUND LEVEL

GPD GALLONS PER DAY

GTV GATE VALVE

GUT GUTTER

H&CW HOT AND COLD WATER

HAZ MAT HAZARDOUS MATERIALS

HB HOSE BIBB

HDPE HIGH DENSITY POLYETHYLENE

HNDRL HANDRAIL

HP HIGH PRESSURE

HV HOSE VALVE

HYD HYDRANT

HYDR HYDRAULIC

ID INSIDE DIAMETER OR INSIDE DIMENSION

IMH INLET MANHOLE

INCL INCLUDED

INCR INCREMENT

INSTL INSTALL

INV INVERT

INV EL INVERT ELEVATION

IP IRON PIPE

IPS IRON PIPE SIZE

IPT IRON PIPE THREADED

IW IRRIGATION WATER

L ANGLE

LAT LATITUDE

LF LINEAR FEET (FOOT)

LIN LINEAR

LNG LONGITUDE

LOC LOCATION

LONG LONGITUDINAL

LOS LINE OF SIGHT

LP LIQUID PROPANE

LPA LIQUID PROPANE AIR MIXTURE

LPT LOW POINT

LS LUMP SUM

LT LIGHT

LTG LIGHTING

MAINT MAINTENANCE

MAX MAXIMUM

MED MEDIUM

MER MERIDIAN

MFD MANUFACTURED

MFG MANUFACTURING

MGT MANAGEMENT

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

ML MATERIALS LIST

MN MAGNETIC NORTH

MOD MODEL OR MODIFY

MON MONUMENT

MTG MEETING

MULT MULTIPLE

MUNIC MUNICIPAL

SITE ABBREVIATIONS

SCALE: 1" = 30'

0 15' 30' 60' 90' 120'7'-6"

VICINITY MAP

Pl an

N or th

True North

GENERAL

1. REFERENCES WITHIN THIS DRAWING SET TO PHASE 3 ARE REFERRING TO THE SHERIDAN

VAMC BOILER UPGRADE PHASE 3 (PROJECT NUMBER 666-16-117). COORDINATE WITH

PHASE 3 DRAWINGS AND VHA COR FOR ADDITIONAL PROJECT REQUIREMENTS.

2. ALL QUANTITIES ARE CONSIDERED APPROXIMATE AND ARE FOR ESTIMATING PURPOSES

ONLY.

3. THE CONTRACTOR SHALL INCLUDE ALL MATERIALS, TOOLS, EQUIPMENT, LABOR AND

APPURTENANT ITEMS TO COMPLETE THE WORK WITHIN THE BID PRICE.

4. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE SITE PRIOR TO BIDDING AND

CONSTRUCTION.

EXISTING UTILITIES

1. UTILITY LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE BASED ON RECORDS

OF VETERANS AFFAIRS. ALL UTILITY LOCATIONS ARE SUBJECT TO THE ACCURACY OF THE

LOCATION METHOD AND ARE SUBJECT TO RELOCATION FROM THE TIME THAT THE

DRAWINGS WERE PREPARED. NO EXCAVATION WAS PERFORMED.

2. THE CONTRACTOR MUST NOTIFY THE VHA COR OF ALL UTILITIES ENCOUNTERED DURING

CONSTRUCTION AND MUST NOT BACKFILL UNTIL THE CONTRACTOR HAS MADE RECORD

OF ITS TYPE, SIZE AND LOCATION.

3. CONTRACTOR MUST CONTACT THE ENGINEERING DIVISION OF VETERANS AFFAIRS

AND/OR APPROVED THIRD PARTY FOR ANY NEEDED LOCATES.

ENVIRONMENTAL

1. WORK SITE AND EXCAVATIONS GENERAL CONTRACTOR IS RESPONSIBLE FOR

INSTALLING TEMPORARY ENVIRONMENTAL CONTROLS AROUND EXCAVATED AREAS

AND SOIL STOCK PILES TO ENSURE THAT RUNOFF IS CONTROLLED.

2. ALL DISTURBED AREAS MUST BE RECLAIMED WITH VIABLE TOPSOIL PER SECTION

2.3 PLANTING SOILS IN 32 90 00 PLANTING SPECIFICATION PRIOR TO THE

PLACEMENT OF SEED.

3. WDEQ CONSTRUCTION PERMIT REQUIREMENTS: "THE SMALL CONSTRUCTION

GENERAL PERMIT (SCGP) COVERS STORM WATER DISCHARGES FROM

CONSTRUCTION ACTIVITIES THAT DISTURB AT LEAST ON ACRE, BUT LESS THAN FIVE

ACRES. SMALL CONSTRUCTION ACTIVITIES ALSO INCLUDE DISTURBANCES OF LESS

THAN 1 ACRE WHEN THAT DISTURBANCE IS PART OF A LARGER COMMON PLAN OF

DEVELOPMENT OR SALE THAT WILL ULTIMATELY DISTURB BETWEEN ONE AND FIVE

ACRES."

LIMIT OF WORK

LIMIT OF WORK

LIMIT OF W

ORKLIMIT OF W

ORK

LOCATION OF

CONSTRUCTION

TRAILER

BUILDING 90

01/15/2020 BRD DJD

CD101

CIVIL DEMOLITION PLAN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

SCALE:

1" = 10' 5' 10' 20' 30' 40'2'-6"

CIVIL DEMOLITION PLAN

Pl an

N or th

True North

GENERAL NOTES

1. REFERENCE PHASE PHASE 3 PLANS FOR LIMIT OF EXISTING LANDSCAPE

TO BE REMOVED.

2. SAW-CUT AND REMOVE EXISTING CONCRETE AND EXCAVATE AS

REQUIRED TO BURY PROPANE TANK FOOTER AND SUPPORTS.

REFERENCE PROPANE TANK MANUFACTURERS' SPECIFICATION FOR

DIMENSIONS.

3. EXCAVATE AS REQUIRED TO BURY PROPANE TANK FOOTER AND

SUPPORTS. REFERENCE PROPANE TANK MANUFACTURERS

SPECIFICATIONS AND DETAILS ON CS501.

4. EXCAVATION FOR BURIED LPA LINE REFER TO CS101.

5. NOT USED.

6. CONFIRM LOCATION OF EXISTING BURIED UTILITIES.

7. REFERENCE PHASE 3 PLANS FOR LIMIT OF EXISTING FENCE TO BE

REMOVED.

8. REMOVE BOLLARD AND CONCRETE FOUNDATION.

LEGEND

XKEYNOTES

LEGEND

CONCRETE SAW-CUT LINE

UTILITY TRENCH TRENCHING

FOOTING EXCAVATION

EXISTING LINE TYPE

EXISTING SANITARY STORM LINE

EXISTING NATURAL GAS LINE

EXISTING UNDERGROUND

ELECTRIC

EXISTING FENCE LINE

EXISTING RETAINING WALL

LIMIT OF EXISTING DRIVE

A. REFERENCE NOTES UNDER EXISTING UTILITIES ON SHEET C-001.

B. UTILITY DISRUPTION WILL BE IN ACCORDANCE WITH SPECIFICATIONS 01 00

00 GENERAL REQUIREMENT AND THE VHA COR.

C. DEMOLITION SHALL BE IN ACCORDANCE WITH SECTION 02 41 00.

D. EXCAVATION AND BACKFILL WILL BE IN ACCORDANCE WITH 31 20 00

EARTHWORK.

EXISTING

COAL PIT

BUILDING 90

EXISTING

DRIVE

AutoCAD SHX Text M

O

O O

O O

O O

O O

O O

O O

O O

O O

O O

O O

O

O

O

O

O

O

O

O

O

O

LPA

LPA

LPA

LPA

LPA

LPA

LPA

LPA

LPA

LP

LP

LP

LP LP

LP

LP

01/15/2020 BRD DJD

CS101

CIVIL SITE PLAN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

1. COORDINATE WITH PHASE 3 PLANS FOR LOCATION OF NEW FENCE.

2. COORDINATE WITH PHASE 3 PLANS FOR LOCATION OF NEW DRIVE.

3. COORDINATE WITH PHASE 3 PLANS FOR NEW ENTRANCE GATE.

4. INSTALL VAPORIZER/MIXER CONCRETE PAD AT DIMENSIONS PROVIDED BY

MANUFACTURER. REFERENCE CIVIL DETAIL 02/CS501.

5. PLACE BOLLARDS (7) AROUND CONCRETE PAD @ 5' OC MAX BETWEEN

POLES. REFERENCE CIVIL DETAILS 01-02/CS501.

6. NEW LIQUID PROPANE LINE TO VAPORIZER AT PUMP STATION.

7. DOUBLE WYE CONNECTION TO EXISTING STORM DRAIN; DAYLIGHT STORM

DRAIN FOLLOWING EXISTING SLOPE.

8. INSTALL REMOVABLE PANEL PRE-CAST CONCRETE WALL WITH

"H"-COLUMNS (TYP).

9. NEW CONCRETE PAD TO EXTEND EXISTING FOR UNDER THE PROPANE

TANK; REFERENCE CONCRETE CONNECTION DETAIL 10/CS501.

10. GABION WALL AND SLOPED BERM, REFERENCE DETAILS CS501 AND

GRADING PLAN CG101.

11. ROUTE OF LPA LINE. REFERENCE MECHANICAL DRAWINGS.

12. COORDINATE WITH NATURAL GAS COMPANY PRIOR TO INSTALLATION.

13. TANK BERM 12'x4" HINGED LOUVER ACCESS DOOR. REFERENCE DETAIL

09/CS501.

14. BELOW GABION STORM DRAIN; REFERENCE DETAIL 07/CS501.

15. CAP ENDS OF NEW 4" STORM DRAIN AT END LOCATIONS SHOWN.

16. LOCATION OF LP PUMP SKID.

17. PLACE BOLLARDS (2) AROUND FILL STATION @ 5' OC MAX BETWEEN POLES.

REFERENCE CIVIL DETAILS 01-02/CS501.

A. CONTRACTOR IS RESPONSIBLE FOR RETURNING SITE TO ITS PREVIOUS

CONDITION, OR BETTER, INCLUDING BUT NOT LIMITED TO SOD,

CONCRETE, GRAVEL ROADS, DRAINAGE SWALES, ETC.

B. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VA COR BEFORE PROCEEDING

WITH WORK.

C. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL TEMPORARY SIGNAGE,

INCLUDING BUT NOT LIMITED TO CONSTRCUTION ACCESS, PARKING LOT

CLOSURES AND EXITS/ENTRANCES.

SCALE:

1" = 10' 5' 10' 20' 30' 40'2'-6"

CIVIL SITE PLAN

Pl an

N or th

True North

LPALPA

LPLP

LEGEND

GENERAL NOTES

XKEYNOTES

LEGEND

NEW LIQUID PROPANE AIR LINE

NEW LIQUID PROPANE

EXISTING STORM DRAIN

NEW STORM DRAIN

EXISTING FENCE LINE

PHASE 3 FENCING

EXISTING NATURAL GAS LINE

EXISTING UNDERGROUND

ELECTRIC LINE

CS501

15' MIN.

20' 20'

20'

20"

COORDINATE NEW DRIVE

WITH PHASE 3 PLANS

BUILDING 90

25'-6"

3'-0" MIN CLEARANCE

BETWEEN TANK AND

RETAINING WALL (TYP)

AutoCAD SHX Text M

CS501

CIVIL SITE DETAILS

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

11'

14'

EXISTING

CONCRETE

COAL PIT

5'

3'

"H" BEAM VERTICAL

EMBEDDED IN CONCRETE;

DIMENSIONS SET BY

MANUFACTURER

14'

SCALE: NO SCALE

PARTIALLY BURIED TANK

SCALE: NO SCALE

"H" PANEL CONCRETE WALL

PRE-CAST REMOVABLE

CONCRETE PANEL

NUMBER AND HEIGHT

SET BY MANUFACTURER

SECTION

PLAN

SCALE: NO SCALE

BOLLARD DETAIL

SCALE: NO SCALE

CONCRETE PUMP PAD DETAILS

SCALE: NO SCALE

UTILITY TRENCH DETAIL

SCALE: NO SCALE

TANK BERM SECTION DETAIL

3'

3"

12"

4'

TOP OF POST ELEVATIONS

TO MATCH

6" IPS x 7'0" STANDARD IRON

PIPE POST BARRICADE

CONCRETE FILLED

EXTERIOR OF PIPE TO BE COATED

WITH 2 COATS EPOXY 16-20 MIL DFM.

COLOR TO BE "SAFETY YELLOW."

CONCRETE PER

SPECIFICATION 03 30 00

3' x 3' GABION

BLOCK (TYP.)

REF: 08/CS501

14'

40'-0"

EXISTING

COAL PIT

NEW BERM

SEE CIVIL

GRADE PLAN

CS501

5' MAX. TYP

LOCATION

OF LPA PIPE

TURN-UP

SCALE: NO SCALE

CONCRETE PUMP PAD SECTION

4" FINISHED GRADE

COORDINATE WITH

PHASE 3 PLANS

4"

1/2" CHAMFER

ON ABOVE

GRADE EDGES

6"x6" NO. 6 PLACED

UNIFORMLY IN CENTER

OF CONCRETE

1'-0"

6"

4' MIN.

EXISTING FINISHED GRADE

GRAVEL DRIVE

BACKFILL TRENCH

TO 95 PERCENT ASTM

D698 COMPACTION

UTILITY MARKING TAPE

BEDDING IN

ACCORDANCE TO SPEC

31 20 00 EARTHWORK

LPA PIPE

SCALE: NO SCALE

WYOMING DOT GABION DETAILS

BOLLARDS;

REFERENCE SITE

PLAN AND DETAIL

01/CS501

COORDINATE WITH PUMP

STATION MANUFACTURER

FOR SIZE AND LOCATION

OF TURN-UP

REFERENCE

MANUFACTURER DATA

FOR SUPPORT DETAILS

AND DIMENSIONS

1' MAX. TYP

6" SUBBASE AASHTO

M147; GRADE C

5'-6"

27'-6"

SHEER STAKES

REF: 08/CS501

REF: MANUFACTURER SPECS

AND DRAWINGS FOR SIZES

SUBBASE AGGREGATE

PER SPEC 32 05 23

SOIL COMPACTION

PER SPEC 31 20 00

4'-6" 4'-3"

3" 2'-6"

2'

6'

NON-WOVEN

GEOTEXTILE FABRIC;

BETWEEN GABION

AND SOIL TYPICAL.

4" PERFORATED DR 13.5 HDPE PIPE (TYP)

WRAPPED IN GEOTEXTILE FABRIC, 2% SLOPED

TO STORMWATER CONNECTION; 2'x2' TRENCH

FILLED 14" MINUS AGGREGATE

CONCRETE PER

SPECIFICATION 03 30 00

NOTE:

SEE SPECIFICATION 31 20 00 EARTHWORK

FOR SIZES OF ROCKS TO BE USED IN

GABION UNITS.

8" REINFORCED

CONCRETE W/ 12"x12"

NO 4 @ E.W.O.C.

8" AGGREGATE BASE COURSE COMPACTED

TO MINIMUM 95% MAX. DENSITY,

±3% OPTIMUM MOISTURE CONTENT

PER ASTM D698SCARIFY AND RECOMPACT SUBGRADE TO 12"

COMPACTED TO MINIMUM 95% MAX. DENSITY,

±3% OPTIMUM MOISTURE CONTENT PER ASTM D698

4"

8"

9" 9"

DRILLED

HOLE

18" LONG EPOXY COATED NO 4 SMOOTH

DOWEL @12" C.C. GREASE ONE END,

ANCHOR OTHER END IN HOLE W/ EPOXY

RESIN ADHESIVE.

SCALE: NO SCALE

NEW CONCRETE COAL SLAB CONNECTION

EXISTING COAL PIT SLAB

PLACING AND FASTENING

ADJACENT BASKETS

6'-3"

SCARIFY AND RECOMPACT SUBGRADE

TO 8" COMPACTED TO MINIMUM 95%

MAX. DENSITY, ±3% OPTIMUM MOISTURE

CONTENT PER ASTM D698

6" AGGREGATE BASE COURSE

COMPACTED TO MINIMUM 95% MAX.

DENSITY, ±3% OPTIMUM MOISTURE

CONTENT PER ASTM D698

SCALE: NO SCALE

ACCESS DOOR DETAIL

4'-0"

12'-0"

2"x2" TUBULAR GATE

FRAME

HSS 6"x6"x3/8" GATE SUPPORT

FRAME (PRIMED & FINISH

PAINTED TO MATCH GATE)

PROVIDE GATE HINGES & GATE

SELF-CLOSING MECHANISM

PER MANUFACTURER (WELDED

TO GATE SUPPORT FRAME)

4'-0"

1'-8" DIA CONC

BASE TYP

4'-6"

VERTICAL "H" BEAM

WALL SUPPORT

GATE EXIT DEVICE WITH LEVER & CYLINDER LOCK

KEYED TO MATCH EXISTING BOILER PLANT SYSTEM

(BASIS OF DESIGN: VON DUPRIN 98/9952L EXTERIOR

POOL GATE EXIT DEVICE WITH LEVER)

AMETCO CUSTOM FABRICATED GATE WITH SHADOW 100

GALVANIZED STEEL LOUVER PANELS POWDER POLYESTER

COATED AS DIRECTED BY VHA COR (OR APPROVED EQUAL)

(FABRICATE FOR EXIT DEVICE & INTEGRAL MORTISE LOCK & LEVER)

GATE BASIS OF DESIGN:

2" MAX

2" MAX

3'-0"

CL EXIT DEVICE TO

TOP OF CONCRETE PAD

4" (TYP)

SLOPED 2%

TO MATCH

CONC

01/15/2021 BRD DJD

CG101

CIVIL GRADING AND EROSION

CONTROL PLAN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

SCALE:

1" = 10' 5' 10' 20' 30' 40'2'-6"

CIVIL GRADING AND EROSION CONTROL PLAN

Pl an

N or th

True North

GENERAL NOTES

1. GRADING PLAN INDICATES FINISHED GRADES. PROPOSED CONTOURS AND

SPOT ELEVATIONS ARE TO FINISHED GRADE. SLOPES SHOWN ARE

HORIZONTAL:VERTICAL (H:V).

2. ANY CONSTRUCTION DEBRIS OR MUD TRACKING IN THE VA RIGHT-OF-WAY

RESULTING FROM THIS DEVELOPMENT SHALL BE REMOVED IMMEDIATELY BY

THE CONTRACTOR.

3. SEE SHEET LP101 AND SPECIFICATION 32 90 00 FOR PLANTING DETAILS.

4. ALL EROSION CONTROL WILL BE DONE IN CONFORMANCE WITH

SPECIFICATION 01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS.

5. SPOT ELEVATIONS ARE SHOWN TO TOP OF FINISHED CONCRETE. FINISHED

ELEVATION HAS A TOLERANCE OF +/- 1".

LEGEND

NEW CONTOUR LINE - MAJOR

NEW CONTOUR LINE - MINOR

EXISTING CONTOUR LINE - MAJOR

EXISTING CONTOUR LINE - MINOR

SILT FENCE

EXISTING STORM SEWER

STORM SEWER EXTENSION

LIMITS OF EXISTING DRIVE

SPOT ELEVATION

3:1

3:1

3:1

1. INSTALL SILT FENCE PRIOR TO CONSTRUCTION; REFERENCE CG501

2. EXTEND STORM DRAIN AT DESIGNATED SLOPE UNTIL IT MEETS

EXISTING GRADE AT DRAINAGE SWALE.

3. CONCRETE PUMP PAD 4 INCHES ABOVE PARKING LOT GRADE. SLOPED

2%. COORDINATE WITH PHASE 3 PLANS FOR FINISHED ELEVATIONS OF

NEW DRIVE. PUMP PAD TO BE 4" ABOVE FINISHED GRADE.

4. MATCH NEW GRADE TO EXISTING (TYPICAL).

5. BERM TO BE SEEDED AND STABILIZED; REFERENCE LP101.

6. COORDINATE WITH PHASE 3 PLANS FOR LIMITS AND ELEVATIONS OF

NEW DRIVE.

7. INSTALL NEW STORM WATER DRAINAGE PIPE; REFERENCE DETAIL

07/501. STORM DRAIN TO SLOPE 2% UNDERNEATH GABION WALL.

8. AT PIPE CHANGE OF DIRECTION, SLOPE NEW STORM LINE TO MEET

CONNECTION AT EXISTING STORM DRAIN.

XKEYNOTES

BUILDING 90

EXISTING

DRIVE

2%

2%

3862.5'+

XXXX.X' +

3860.8'+

3862.3'+

AutoCAD SHX Text M

6"

CG501

502C

CIVIL EROSION CONTROL DETAILS

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

SCALE: NO SCALE

SILT FENCE DETAIL

NOTE:

THE MAXIMUM

LENGTH OF SLOPE

ABOVE A ROW OF

SILT FENCE IS 110'

1. SILT FENCE SHOULD BE LIMITED TO SITUATIONS IN WHICH ONLY SHEET FLOW

IS EXPECTED

2. SILT FENCE SHOULD BE INSTALLED PRIOR TO MAJOR SOIL DISTURBANCE.

3. SILT FENCE SHOULD BE PLACED ACROSS THE BOTTOM OF A SLOPE ALONG A

LINE OF UNIFORM ELEVATION PERPENDICULAR TO THE DIRECTION OF FLOW.

4. SYNTHETIC FILTER FABRIC SHALL BE A PERVIOUS SHEET OF PROPYLENE,

NYLON, POLYESTER OR ETHYLENE YARN AND SHALL BE CERTIFIED BY THE

MANUFACTURER OR SUPPLIER AS CONFORMING TO THE REQUIREMENTS

NOTED IN WV DOT DOH SPECIFICATIONS OR APPROVAL OF THE VHA COR.

5. IF STEEL POSTS (STANDARD “U” OR “T” SECTION) ARE UTILIZED FOR SILT

FENCE CONSTRUCTION, THEY MUST HAVE A MINIMUM WEIGHT OF 1.25

POUNDS PER LINEAR FOOT AND SHOULD HAVE A MINIMUM LENGTH OF 5

FEET.

MAINTENANCE

1. SILT FENCES SHALL BE INSPECTED IMMEDIATELY AFTER EACH RAINFALL OF

0.5 INCH OR GREATER. ANY REQUIRED REPAIRS OR MAINTENANCE SHALL BE

MADE IMMEDIATELY.

2. SHOULD THE FABRIC ON A SILT FENCE DECOMPOSE OR BECOME

INEFFECTIVE PRIOR TO THE END OF THE EXPECTED USABLE LIFE AND THE

BARRIER STILL IS NECESSARY, THE FABRIC SHALL BE REPLACED PROMPTLY.

SEDIMENT DEPOSITS SHOULD BE REMOVED AFTER EACH STORM EVENT.

THEY MUST BE REMOVED WHEN DEPOSITS REACH APPROXIMATELY ONE

HALF THE HEIGHT OF THE BARRIER.

SILT FENCE NOTES

EROSION

CONTROL

FABRIC

PLACE ON

CONTOUR

COMPACTED SOIL

EROSION CONTROL FABRIC

ATTACH W/2 TIES

6"x6" TRENCH WITH

MIN 6" FABRIC

BURIED INTO IT

DIRECTION

OF FLOW

DIRECTION

OF FLOW

8' MAX.

30" MAX

8" TOP W/

2 TIES

18" MIN

POST MIN 2"x2" X 4'-6"

OR STEEL POSTS 4'-6"

WEIGHING 1.25LBS/FT

6"

18" MIN

EROSION CONTROL NOTES:

EROSION CONTROL DETAILS ARE FROM THE WYOMING DEPARTMENT

OF TRANSPORTATION POLLUTION CONTROLS AND BMP FOR STORM

WATER DURING CONSTRUCTION. CONFIRM SELECTION FROM FIELD

GUIDE WITH VHA COR BEFORE IMPLEMENTATION. ADDITION

REQUIREMENTS MAY BE REQUIRED BASED ON SITE CONDITIONS AND

AT REQUEST OF THE VHA COR.

LIM

IT

O F

W

OR

K

LIMIT OF WORK

LIM

IT

O F

W

OR

K

01/15/2021 RAG MLH

LP101

PLANTING PLAN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

SCALE:

1" = 10' 5' 10' 20' 30' 40'2'-6"

PLANTING PLAN

Pl an

N or th

True North

GENERAL NOTES

A. AREA DISTURBED DURING CONSTRUCTION IS TO BE SEEDED WITH NATIVE

GRASSES. SEE SPECIFICATION SECTION 32 90 00 PLANTING FOR DETAILS .

B. AFTER SEEDING, AREA IS TO BE PROTECTED WITH EXTENDED TERM EROSION

CONTROL BLANKETS. SEE SPECIFICATION SECTION 32 90 00 PLANTING FOR

DETAILS.

LEGEND

NATIVE GRASS SEED

NEW CONTOURS - MAJOR

NEW CONTOURS - MINOR

EXISTING CONTOURS - MAJOR

EXISTING CONTOURS - MINOR

SILT FENCE

EXISTING STORM SEWER

STORM SEWER EXTENSION

1. STORM DRAIN EXTENSION TO DAYLIGHT AT NEWLY GRADED SLOPE.

2. 14' HIGH GABION WALL. SEE CIVIL SHEETS FOR CONSTRUCTABILITY.

3. NEW CONCRETE PAD WITH CONCRETE PANEL ENCLOSURE.

XKEYNOTES2

BUILDING 90

EXISTING

DRIVE

AutoCAD SHX Text M

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD CEK

S-001

STRUCTURAL GENERAL NOTES

GENERAL

1. ALL WORK SHALL CONFORM WITH THE REQUIREMENTS OF THE PROJECT SPECIFICATIONS.

2. NOTES AND DETAILS ON THE PLANS SHALL TAKE PRECEDENCE OVER GENERAL NOTES, TYPICAL

DETAILS.

3. CONTRACTOR SHALL COMPARE ALL DISCREPANCIES ON DRAWINGS AT THE SITE.

4. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ARCHITECTURAL, MECHANICAL AND

ELECTRICAL DRAWINGS.

5. ENGINEER OF RECORD'S APPROVAL MUST BE SECURED FOR ALL SUBSTITUTIONS.

6. VERIFY ALL OPENINGS THROUGH FLOOR, ROOF AND WALLS WITH MECHANICAL AND ELECTRICAL

CONTRACTORS

7. ALL DIMENSIONS AND EXISTING CONDITIONS SHOWN SHALL BE FIELD VERIFIED BY THE

CONTRACTOR. IT IS THE CONTRACTOR'S RESPONSIBILITY TO IMMEDIATELY NOTIFY THE ENGINEER OF RECORD SHOULD ANY EXISTING CONDITION NOT BE SHOWN, OR IF ANY EXISTING CONDITION

DIFFERS FROM THOSE SHOWN ON THE DRAWINGS.

8. DURING ERECTION OF THE STRUCTURES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR

TEMPORARY BRACING TO WITHSTAND ALL LOADS TO WHICH THE STRUCTURE MAY BE SUBJECTED, INCLUDING LATERAL LOADS, STOCKPILES OF MATERIALS AND EQUIPMENT. SUCH BRACING SHALL BE LEFT IN PLACE AS LONG AS REQUIRED FOR SAFETY AND UNTIL ALL STRUCTURAL FRAMING IS IN

PLACE WITH CONNECTIONS COMPLETED.

9. DO NOT REPRODUCE CONTRACT DOCUMENTS, COPY STANDARD PRINTED INFORMATION, OR USE

ELECTRONIC CAD FILES AS THE BASIS FOR SHOP DRAWINGS.

10. THE ENGINEER OF RECORD DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION.

11. SEE PROJECT SPECIFICATIONS FOR INSPECTION SCHEDULE.

12. SIGNIFICANT PERMANENT EQUIPMENT SIZES, WEIGHTS AND LOCATIONS ARE INDICATED ON THE

DRAWINGS AS PROVIDED TO THE ENGINEER DURING DESIGN. CHANGES IN SIZES, WEIGHTS, OR

LOCATIONS MUST BE SUBMITTED IN WRITING FOR REVIEW BY THE STRUCTURAL ENGINEER.

REQUIRED SUPPORTS OR BRACES NOT SHOWN ON THE DRAWINGS ARE THE RESPONSIBILITY OF

THE EQUIPMENT SUPPLIER.

13. EXISTING BUILDING:

13.1. 1947: ORIGINAL CONSTRUCTION.

13.2. 1973 REMODEL: SOUTH MASONRY-ENCLOSED GAS-FIRED BOILER ENCLOSURE, AUXILIARY

GENERATOR ROOM AND EQUIPMENT MEZZANINE.

13.3. 1984 REMODEL: REPLACEMENT OF EQUIPMENT MEZZANINE WITH STEEL FRAMING, STEEL

DECK AND CONCRETE SLAB; ADDITION OF MULTILEVEL METAL BUILDING ENCLOSURE AT

SOUTHWEST CORNER; ADDITION OF CONTROL ROOM AND OFFICES.

13.4. 2011 REMODEL: REPLACE THREE BOILERS (ONE GAS FIRED, TWO COAL FIRED) AND OTHER

RELATED EQUIPMENT.

1. ALL WORK IS DESIGNED AND SHALL BE CONSTRUCTED IN CONFORMANCE WITH THE PROJECT

SPECIFICATIONS.

2. LOADING CONDITIONS

2.1. DEAD LOAD................................. 10 PSF

2.2. LIVE LOAD................................... 40 PSF

2.3. NOTIONAL LOAD........................ 1% OF TOTAL GRAVITY

2.4. SOIL BEARING PRESSURE........ 1500 PSF

1. SPREAD FOOTINGS SHALL BEAR ENTIRELY UPON SUITABLE NATURAL SOILS OR GRANULAR

STRUCTURAL FILL EXTENDING TO SUITABLE NATURAL SOILS, AS DETERMINED BY THE

GEOTECHNICAL ENGINEER OF RECORD. SEE DESIGN CRITERIA FOR SOIL BEARING INFORMATION.

2. BOTTOM OF FOOTING SHALL BE 66 INCHES BELOW LOWEST ADJACENT FINAL GRADE. SEE

FOUNDATION PLAN FOR TOP OF FOOTING ELEVATIONS. NOTE THAT ALL TOP OF FOOTING

ELEVATIONS ARE ESTIMATES BASED ON ARCHITECTURAL AND CIVIL DRAWINGS. CONTRACTOR

SHALL FIELD VERIFY ALL TOP OF FOOTING ELEVATIONS WITH EXPECTED FINISH GRADE TO ENSURE

ADEQUATE FROST PROTECTION.

3. ALL WATER SHALL BE REMOVED FROM EXCAVATION PRIOR TO PLACING CONCRETE. DO NOT PLACE

CONCRETE UNDER WATER OR ON FROZEN GROUND. CONTRACTOR IS RESPONSIBLE FOR

PROTECTING FOOTINGS AND SURROUNDING SOILS AGAINST FROST DURING CONSTRUCTION

4. ALL FILL AND BACKFILL SHALL BE COMPACTED ACCORDING TO THE REQUIREMENTS SET FORTH IN

THE GEOTECHNICAL REPORT.

5. ANY UNUSUAL SOIL CONDITIONS (WATER, SOFT LAYERS, ROCK OUTCROPPINGS, EXISTING

STRUCTURES, ETC.) ENCOUNTERED DURING EXCAVATION FOR FOOTINGS SHALL BE IMMEDIATELY

BROUGHT TO THE ATTENTION OF THE VHA COR, STRUCTURAL ENGINEER, AND GEOTECHNICAL

ENGINEER PRIOR TO PROCEEDING.

SOILS

STRUCTURAL STEEL

1. STRUCTURAL STEEL MINIMUM YIELD STRENGTH:

TUBE STEEL: A500 GRADE B STEEL (Fy = 46 KSI) WIDE FLANGE SECTIONS: A992 STEEL (Fy = 50 KSI) CHANNELS AND ANGLES: A36 STEEL (Fy = 36 KSI) PLATES: A36 STEEL (Fy = 36 KSI)

BOLTS: FOR STEEL, USE A325

ANCHOR BOLTS: A307 OR A36

2. CONTRACTOR SHALL MEET OSHA REQUIREMENTS AND PROJECT SPECIFICATIONS.

3. ALL STRUCTURAL STEEL AND STRUCTURAL STEEL WORK SHALL COMPLY WITH "SPECIFICATIONS

FOR THE DESIGN, FABRICATIONS, AND ERECTIONS OF STRUCTURAL STEEL FOR BUILDINGS OF THE

A.I.S.C. CODE OF STANDARD PRACTICE" AND PROJECT SPECIFICATIONS.

4. ALL WELDS AND WELDING SHALL BE IN ACCORDANCE WITH THE SPECIFICATIONS OF THE "THE

AMERICAN WELDING SOCIETY."

5. WELDING ELECTRODES SHALL BE ASTM E70XX. THE MINIMUM FILLET WELD SIZE SHALL BE 3/16".

6. A CERTIFIED WELDER IN ACCORDANCE WITH AWS SHALL PERFORM ALL WELDING.

7. SHOP DRAWINGS FOR ALL STEEL INDICATED ON THE STRUCTURAL DRAWINGS SHALL BE

SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION.

8. ALL STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE GALVANIZED OR PAINTED WITH A

HIGH-PERFORMANCE PAINT SYSTEM PER PROJECT SPECIFICATIONS.

9. ALL MEMBERS SHALL BE ERECTED WITH NATURAL MILL CAMBER OR INDUCED CAMBER UP, UNO.

10. NO CUTTING OR BURNING OF STRUCTURAL STEEL IS ALLOWED WITHOUT WRITTEN AUTHORIZATION

FROM THE STRUCTURAL ENGINEER.

11. NO HOLES OTHER THAN THOSE SPECIFICALLY DETAILED ARE ALLOWED IN THE STRUCTURAL STEEL.

12. EXISTING BUILDING

12.1. 1947 BASE BUILDING IS MOST LIKELY A7

12.2. 1973 AND 1984 ADDITIONS ARE A36

1. ALL CONCRETE MATERIALS SHALL COMPLY WITH THE STANDARDS REFERENCED IN THE

PROJECT SPECIFICATIONS.

2. WORKABILITY ADMIXTURES MAY BE USED, PROVIDED THAT BATCH PROPORTIONS ARE

DETERMINED AS PRESCRIBED IN THE SPECIFICATIONS.

3. ANY CONCRETE THAT FAILS TO MEET SPECIFICATIONS SHALL BE REMOVED & REPLACED AT

THE EXPENSE OF THE CONTRACTOR.

4. REINFORCEMENT & DETAILING: ALL REINFORCING INCLUDING WWF SHALL BE DETAILED,

BOLSTERED, & SUPPORTED TO COMPLY WITH ACI 315, "MANUAL OF STANDARD PRACTICE

FOR DETAILING REINFORCING CONCRETE STRUCTURES" & CRSI RECOMMENDATIONS.

REINFORCING BARS SHALL NOT BE WELDED UNLESS SPECIFICALLY SHOWN ON DRAWINGS.

STRUCTURAL DESIGN CRITERIA

CONCRETE

1. DEFORMED REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60. REINFORCING

TO BE WELDED OR FIELD BENT SHALL BE ASTM A706, GRADE 60. EPOXY COATED

REINFORCING SHALL CONFORM TO ASTM A775 AND SHALL BE COATED PRIOR TO

FABRICATION.

2. WELDED WIRE REINFORCING (WWR) SHALL CONFORM TO ASTM A185, GRADE 65. WWR

MUST LAP ONE FULL MESH AND SHALL BE WIRED TOGETHER. WWR SHALL BE PLACED IN

THE CENTER OF SLABS ON GRADE.

3. WELDING OF REINFORCING SHALL CONFORM TO AWS D1.4, USING PROPER LOW

HYDROGEN ELECTRODES.

4. DETAIL BARS IN ACCORDANCE WITH THE CURRENT ACI DETAILING MANUAL AND ACI

BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.

5. DETAIL BARS IN ACCORDANCE WITH THE CURRENT ACI 530 FOR CONCRETE MASONRY

BLOCK.

6. ALL REINFORCING BAR BENDS SHALL BE MADE COLD WITH A BAR BENDER ACCORDING TO

ACI 350 BAR BEND RADIUS.

7. LAP ALL HORIZONTAL BARS AT CORNERS, INTERSECTIONS AND SPLICES.

8. AT LOCATIONS WHERE ALL REINFORCING WITHIN A STRUCTURAL ELEMENT WILL BE

SPLICED, THE SPLICES MUST BE STAGGERED.

9. DOWELS FOR WALL AND COLUMNS SHALL BE THE SAME SIZE AND SPACING AS THE WALL

OR COLUMN REINFORCING, UNO.

10. AT ENDS OF BEAMS, SLABS, JOINS, WALLS AND GRADE BEAMS, TERMINATE TOP

REINFORCING WITH STANDARD HOOKS UNLESS SHOWN OTHERWISE ON THE

CONSTRUCTION DOCUMENTS.

11. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORCING AT POSITIONS

SHOWN ON THE PLANS.

REINFORCING STEEL

BAR

SIZE

NOTES

1. THE SCHEDULE SHOWN APPLIES TO REGULAR WEIGHT CONCRETE WITH 60ksi GRADE

REINFORCING BARS.

2. TOP BARS ARE HORIZONTAL BARS WITH 12" (OR MORE), OF FRESH CAST BELOW THE

BARS.

3. CLASS "A" SPLICES SHALL BE USED WHEN 50% (OR LESS) OF BARS SPLICED WITHIN LAP.

4. CLASS "B" SPLICES SHALL BE USED FOR ALL ELSE, TYPICALLY WITH SHEARWALLS,

COLUMNS, BEAMS, AND SLABS.

5. FOR EPOXY COATED BARS, INCREASE LAP LENGTHS AS FOLLOWS: TOP BARS - Ld x 1.7, REGULAR BARS - Ld x 1.5.

6. FOR BUNDLED BARS, INCREASE LAP LENGTHS AS FOLLOWS: BUNDLED BARS THREE OR

LESS - Ld x 1.2, BUNDLED BARS FOUR OR MORE - Ld x 1.33. INDIVIDUAL BAR SPLICES

WITHIN A BUNDLE SHALL NOT OVERLAP.

7. LAP SPLICES ARE NOT ALLOWED FOR TIES AND STIRRUPS.

TENSION BARS "Ld"

#3 #4 #5 #6 #7 #8 #9 #10 #11

Fc = 3000 psi

REBAR LAP SCHEDULE

Fc = 4000 psi

REG.

CLASS

A B

TOP

CLASS

REG.

CLASS

TOP

CLASS

BABABA

17" 22" 22" 28" 15" 19" 19" 24"

33" 42" 50" 71" 81" 92"

103" 114"

26" 32" 39" 55" 63" 71" 79" 88"

25"19" 31" 37" 55" 63" 71" 79" 88"68"

61" 54" 48" 42" 29" 24"

38" 48" 58" 82" 93"

105" 118" 131"101"

91" 81" 72" 63" 45" 37" 29"29"

36" 43" 63" 72" 81" 91"

101"78" 70" 62" 55" 48" 33" 28" 22"

Fc = 5000 psi

14" 18" 18" 24" 29" 36" 44" 64" 74" 81" 91"

101"

23" 29" 34" 50" 57" 62" 70" 78"

22"18" 28" 34" 50" 56" 64" 70" 78"60"

54" 48" 44" 28" 26" 22"

REG.

CLASS

TOP

CLASS

BABA

1. WELDED CONNECTIONS

1.1. ALL WELDING SHALL CONFORM TO ANSI/AWS D1.1, LATEST EDITION.

1.2. FILLET WELDS WITH NO SIZE SPECIFIED SHALL BE 3/16 INCH OR MINIMUM SIZE

REQUIRED BY AISC, WHICHEVER IS LARGER.

2. BOLTED CONNECTIONS

2.1. UNLESS OTHERWISE NOTED ON THE STRUCTURAL DRAWINGS, BOLTS SHALL BE 3/4"

DIAMETER AND CONFORM TO ASTM A325. BOLTS SHALL BE DESIGNED USING VALUES

FOR BEARING TYPE BOLTS WITH THREAD ALLOWED IN THE SHEAR PLANE.

2.2. BOLTS SHALL BE TIGHTENED TO 'SNUG TIGHT' AS DEFINED BY AISC, UNO.

3. STRUCTURAL STEEL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE STRUCTURAL

DRAWINGS SHALL BE DESIGNED AND DETAILED BY THE CONTRACTOR UNDER THE DIRECT

SUPERVISION OF A PROFESSIONAL ENGINEER LICENSED IN THE STATE HAVING

JURISDICTION AT THE PROJECT SITE. SEALED CALCULATIONS FOR ALL CONNECTIONS

DESIGNED BY THE CONTRACTOR SHALL BE SUBMITTED FOR THE ARCHITECT'S FILES.

4. MOMENT CONNECTIONS

4.1. WHERE INDICATED, MOMENT CONNECTIONS SHALL BE DESIGNED FOR THE

SCHEDULED MOMENT ENVELOPE. THE MOMENT IS INDICATED ON THE STRUCTURAL

DRAWINGS AS "(M=)". THE SHEAR IS INDICATED ON THE STRUCTURAL DRAWINGS AS

"(R=)".

4.2. IF NOT INDICATED ON THE STRUCTURAL DRAWINGS, MOMENT CONNECTIONS SHALL

BE WELDED TO DEVELOP THE FULL CAPACITY OF THE MEMBER.

5. ALL BEAM SHEARS, REACTIONS, MEMBER FORCES, MOMENTS, ETC, SHOWN ON THE

STRUCTURAL DRAWINGS ARE LRFD LOADS.

5.1. ANCHOR RODS ARE TO BE ASTM F1554 36 KSI, UNLESS NOTED OTHERWISE.

STRUCTURAL STEEL CONNECTIONS

ABBREVIATIONS

AB ANCHOR BOLT

ADDL ADDITIONAL

AFF ABOVE FINISH FLOOR

ALT ALTERNATE

ARCH ARCHITECT

BCE BOTTOM CHORD EXTENSION

BO BOTTOM OF

BLDG BUILDING

BM BEAM

BOTT BOTTOM

BRG BEARING

BSMT BASEMENT

BP BEARING PLATE

BTWN BETWEEN

CL CENTERLINE

CANT CANTILEVER

CJ CONSTRUCTION JOINT

CMU CONCRETE MASONRY UNIT

CNTR CENTER/CENTERED

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONT CONTINUOUS

COORD COORDINATE

Ø DIAMETER

DTL DETAIL

DWG DRAWING

(E) EXISTING

EA EACH

EF EACH FACE

EL ELEVATION

ELECT ELECTRICAL

ELEV ELEVATOR

EMBED EMBEDMENT

EOD EDGE OF DECK

EOS EDGE OF SLAB

EQ EQUAL

EQUIP EQUIPMENT

EW EACH WAY

EWB EACH WAY BOTTOM

EWT EACH WAY TOP

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

FDN FOUNDATION

FIN FINISH

FLR FLOOR

FT FEET

FTG FOOTING

GA GAUGE

GALV GALVANIZED

GB GRADE BEAM

HP HIGH POINT

HORIZ HORIZONTAL

IF INSIDE FACE

IN INCHES

INFO INFORMATION

INT INTERIOR

JT JOINT

K KIP

K-FT KIP-FEET

LP LOW POINT

LW LIGHT WEIGHT

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LWB LONG WAY BOTTOM

MAX MAXIMUM

MECH MECHANICAL

MEZZ MEZZANINE

MEP MECHANICAL ELECTRICAL PLUMBING

MFG MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MP MASONRY PIER

MST METAL STUD TRUSS

NBL NON BEARING LINTEL

(N) NEW

NTS NOT TO SCALE

NW NORMAL WEIGHT

OC ON CENTER

PAF POWDER ACTUATED FASTENER

PL PLATE

PLUMB PLUMBING

PC PILE CAP

PRCST PRECAST

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PTN PARTITION

REINF REINFORCEMENT

REQD REQUIRED

RETG RETAINING

SF STEP FOOTING

SOG SLAB ON GRADE

SCHED SCHEDULE

SECT SECTION

SIM SIMILAR

SL SLOPE

SPECS SPECIFICATIONS

STL STEEL

STIFF STIFFENER

STRUC STRUCTURAL

SWB SHORT WAY BOTTOM

T&B TOP AND BOTTOM

T TOP

T/O TOP OF

TOC TOP OF CONCRETE

TOS TOP OF STEEL

TS THICKENED SLAB

TCELE TOP CHORD EXTENSION LEFT END

TCERE TOP CHORD EXTENSION RIGHT END

TDS TURN DOWN SLAB

THK THICK OR THICKENED

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VIF VERIFY IN FIELD

VERT VERTICAL

WRT WOOD ROOF TRUSS

W/ WITH

WC WET COLUMN

WP WALL PLATE

WWF WELDED WIRE FABRIC

Reid Dumas Colorado PE

DN

UP

DN

UP

32 4 5 6 7 81

A

B B

E

G

C

D

1.1

D.9

F

F.9

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD CEK

SD101

STRUCTURAL FOUNDATION DEMO

PLAN

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

STRUCTURAL FOUNDATION DEMO PLAN

P l a n

N o r t h

True North

KEY NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING

WITH WORK.

B. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH FLOOR AND

ROOF STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

C. TOP OF SLAB ELEVATION = 52'-0" UNLESS NOTED OTHERWISE

D. PADS ARE 4" THICK HOUSEKEEPING PADS REINFORCED WITH ONE

LAYER W.W.F. 6X6-W2.9XW2.9 UNLESS NOTED OTHERWISE

E. REFERENCE ARCHITECTURAL, MECHANICAL, ELECTRICAL AND

PLUMBING DRAWINGS FOR LOCATIONS, DIMENSIONS AND ELEVATIONS

OF MAJOR EQUIPMENT AND FOR COORDINATION WITH SUPPORTING

STRUCTURAL ELEMENTS SHOWN HERE.

GENERAL STRUCTURAL NOTES:

1. PATCH & REPAIR PENETRATION.

2. PATCH AND REPAIR EXISTING CONCRETE PADS

3. DEMOLISH EXTERIOR TRENCH COVER AND AUGER.

4. SAW-CUT AND REMOVE CONCRETE SLAB ON GRADE FOR NEW

CONCRETE COLUMN FOOTERS. REFERENCE 02/S-501 FOR PATCH

BACK.

5. CUT AND GRIND ALL STRUCTURAL MEMBERS AND MATERIALS THAT

ARE REMOVED, FLUSH WITH EXISTING SLAB (TYPICAL THROUGHOUT).

2 2

2 2 2

(E) HSS 4X4X1

4 TYP. (E) HSS 4X4X1

4 TYP. (E) HSS 4X4X1

4 TYP.

(E) HSS 4X4X1

4 TYP.(E) HSS 4X4X1

4 TYP.(E) HSS 4X4X1

4 TYP.

(E) HSS 6X6X5

8 TYP.

(E) HSS 6X6X5

8 TYP.

(E) HSS 6X6X5

8 TYP.

(E) HSS 6X6X5

8 TYP. (E) HSS 6X6X5

8 TYP.

(E) HSS 6X6X5

8 TYP.

16" THICK CONCRETE

PAD FOR BOILERS

EXISTING 6" CONCRETE

SLAB-ON-GRADE

REINFORCED W/ #4

@ 16" O.C. E.W.

16" THICK CONCRETE

PAD FOR BOILERS

(E) 52'-4"

(E ) S

LA

B-

ON

-G

RA

DE

(E) 52'-4"

REMOVE EXISTING FOUNDATION

LEGEND:

DN

DN

DN

DN

DN

DNDNDN DN

DN

DN

DN

DN

32 4 5 6 7 81

A

B B

E

G

C

D

1.1

D.9

F

F.9

DN

DN

DN

DN

DN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD CEK

SD102

STRUCTURAL FRAMING DEMO

PLAN

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

STRUCTURAL FRAMING DEMO PLAN

P l a n

N o r t h

True North

KEY NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING

WITH WORK.

B. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH FLOOR AND

ROOF STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

GENERAL STRUCTURAL NOTES:

1. DEMO REFERENCE MECHANICAL DRAWINGS

REMOVE EXISTING CATWALK

CATWALK TO REMAIN

LEGEND:

17.

18.

SUCH

CEILIN

OFF.

CEILIN

EMPL

UNLE

TOOL

CAUS

UP

DN

UP

32 4 5 6 7 81

A

B B

E

G

C

D

1.1

D.9

F

F.9

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD CEK

S-101

STRUCTURAL FOUNDATION PLAN

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

STRUCTURAL FOUNDATION PLAN

P l a n

N o r t h

True North

KEY NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING

WITH WORK.

B. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH FLOOR

STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

C. TOP OF SLAB ELEVATION = 0'-0" UNLESS NOTED OTHERWISE

D. PADS ARE 4" THICK HOUSEKEEPING PADS REINFORCED WITH ONE

LAYER W.W.F. 6X6-W2.9XW2.9 UNLESS NOTED OTHERWISE

E. REFERENCE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS

FOR LOCATIONS, DIMENSIONS AND ELEVATIONS OF MAJOR

EQUIPMENT AND FOR COORDINATION WITH SUPPORTING

STRUCTURAL ELEMENTS SHOWN HERE.

GENERAL STRUCTURAL NOTES:

S-501

F1 F1 F1

F1F1F1

F1

F1

F1

F1

S-501

S-501

S-501

S-501

1. EXTEND TRENCH COVER TO COVER BUCKET ELEVATOR.

2. PATCH AND SEAL AUGER TRENCH WALL PENETRATION THROUGH

FOUNDATION WALL.

3. INFILL EXTERIOR TRENCH WITH CONCRETE UNTIL FLUSH WITH

EXISTING PAD. FINISH PER SPECS.

32 4 5 6 7 81

A

B B

E

G

C

D

1.1

D.9

F

F.9

DN

DN

DN

DN

DN

DN

DN

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD RT

S-102

STRUCTURAL FRAMING PLAN

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

STRUCTURAL FRAMING PLAN

P l a n

N o r t h

True North

1. PATCH & REPAIR PENETRATION, MATCH EXISTING FINISH;

SEE DETAIL 11/S-502

2. PATCH & REPAIR PENETRATION, MATCH EXISTING FINISH;

SEE DETAIL 1/S-503

KEY NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING

WITH WORK.

B. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH FLOOR AND

ROOF STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

C. GENERAL CONTRACTOR WILL COORDINATE FINAL CATWALK

ELEVATION.

D. PATCH EXISTING MASONRY AT EXISTING OPENINGS WITH BRICK,

BACKED UP WITH CMU TO MATCH EXISTING WALL CONSTRUCTION.

GENERAL STRUCTURAL NOTES:

S-301

S-301

S-301

S-301

HSS 4X4X1/4"

HSS 4X4X1/4"

HSS 4X4X1/4" HSS 4X4X1/4"HSS 4X4X1/4"

HSS 4X4X1/4"HSS 4X4X1/4"

HSS 4X4X1/4"

C6X8.2

C6X8.2

C6X8.2C6X8.2

C6X8.2

C6X8.2 C6X8.2

C6X8.2

S-502

EQ EQ EQ

S-502

S-502

S-502

32 4 5 61 1.1

3 2456

D

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD RT

S-301

STRUCTURAL SECTIONS

SCALE:

2' 4' 8' 16' 32'

1/8" = 1'-0"

CATWALK SECTION D

SCALE:

2' 4' 8' 16' 32'

1/8" = 1'-0"

CATWALK SECTION C

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

CATWALK SECTION A

SCALE: 1/4" = 1'-0"

1' 2' 4' 8' 16'0

CATWALK SECTION B

KEY NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND

REPORT ANY DISCREPANCIES TO THE VHA COR BEFORE PROCEEDING

WITH WORK.

B. COORDINATE ALL FLOOR AND ROOF PENETRATIONS WITH FLOOR AND

ROOF STRUCTURE. REFER TO STRUCTURAL DRAWINGS.

C. CG WILL COORDINATE FINAL CATWALK ELEVATION.

D. PATCH EXISTING MASONRY AT EXISTING OPENINGS WITH BRICK,

BACKED UP WITH CMU TO MATCH EXISTING WALL CONSTRUCTION.

GENERAL STRUCTURAL NOTES:

10'

(E1984) 63.5 TS

11' - 6"

(E1984) 58.5 MEZZ

6' - 6"

TOP OF SLAB

0' - 0"

UPPER MEZZ

21' - 7 1/2"

(E1973) 77.4 TOS

25' - 4 1/2"

S-301

S-301

TOP OF SLAB

0' - 0"

(E1984) 58.5 MEZZ

6' - 6"

(E1984) 63.5 TS

11' - 6"

TOP OF SLAB

0' - 0"

(E1984) 58.5 MEZZ

6' - 6"

(E1984) 63.5 TS

11' - 6"

TOP OF PARAPET

TOP OF PARAPET

S-301

GUY WIRE 14" Ø ATTACH

TO PRIMARY ROOF

STRUCTURE (4) E.W.

S-502

S-502

S-502

S-502

S-502

S-502

FOR CONNECT TO

EXISTING CMU WALL

RE: 02/S-502

S-502

6'- 6"

'-1

1/ 2"

UPPER MEZZ

21' - 7 1/2"

86.1 PENTHOUSE FLOOR

34' - 1 1/2"

(E1973) 77.4 TOS

25' - 4 1/2"

UPPER MEZZ

21' - 7 1/2"

86.1 PENTHOUSE FLOOR

34' - 1 1/2"

(E1973) 77.4 TOS

25' - 4 1/2"

S-502

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2020 BRD RT

S-501

STRUCTURAL FOUNDATION

DETAILS

SCALE: NO SCALE

FOUNDATION DETAIL - F1

BASE PL

1/2"x10"x0'-10"

SCALE: NO SCALE

FOUNDATION INTERFACE WITH EXISTING

EXISTING

WALL

BASE

PL 5 8"x8"x8" 3

(N) HSS 4x4 COLUMN

EMBED PL 5 6"x14"x1'-6" W/ 2-#4 A706X

#4 @ 12" O.C. EACH

WAY BOTTOM

3-#4x3'-0" SPAED @ 6" O.C.

THROUGH EMBED PLATE ASSEMBLY

DRILL 6" INTO (E)

AND USE EPOXY

ADHESIVE (TYPICAL)

1'- 2"

EXISTING

SLAB

17.

18.

SUCH

CEILIN

OFF.

CEILIN

EMPL

UNLE

TOOL

CAUS

EXTEND ANGLE 1'-6" MIN OR

3 RIBS BEYOND OPENING

DECK SPAN

16 GA PLATE SCREW

TO DECK W/ #10 TEK

SCREWS @6" OC

SEE DETAILS

1-10 THIS SHEET

1/8 1.5-6

TYP ADJACENT

TO EA CUT

FLUTE

6" OR LESS JOIST

JOIST

JOIST

8" TO 12"

1'-6" MIN OR 3 RIBS

L1 3/4X 1 3/4X 1/4 REINFORCING

L1 3/4X 1 3/4X 1/4 REINFORCING

8" T

O

NO REINF

REQUIRED

GI

RD

ER

/B

EA

M

GI

RD

ER

/B

EA

M

6" TO 8"

1'-0" TO 5'-6"

1'- 0"

T O

5'- 6"

VEG 20.07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

Project Director

Issued: Date:

750 W HAMPDEN AVE

SUITE #300

ENGLEWOOD CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

666-18-114

VAMC SHERIDAN, WYOMING

CONSULTANTS: ARCHITECT/ENGINEERS: STAMP: 100% CONSTRUCTION

DOCUMENTS

BUILDING 90 REPLACE COAL

BOILERS DESIGN

01/15/2021 BRD RT

S-502

STRUCTURAL FRAMING DETAILS

SCALE: NO SCALE

GRATING ATTACHMENT DETAIL A

SCALE: NO SCALE

GRATING ATTACHMENT DETAIL B

SCALE: NO SCALE

COLUMN - BEAM ATTACHMENT DETAIL

SCALE: NO SCALE

STAIR STRINGER DETAIL TYPICAL

SCALE: NO SCALE

HANDRAIL ATTACHMENT DETAIL

SCALE: NO SCALE

GENERAL ROOF DECK PENETRATION REINFORCEMENT

(N) C6

1-3/4" Ø A325-N BOLT

(N) C12 STAIR

STRINGER

HANDRAIL

(N) STEEL GRATING

(N) STEEL GRATING

(N) CHANNEL

4"

2-1/4"

(N) STEEL GRATING

(N) C6

(N) CHANNEL SEE

PLAN

9"

EDGE OF

EXISTING

CMU WALL

(N) STEEL GRATING

WORK POINT

(N) STEEL COLUMN

W/ CAP PLATE

1-3/4" Ø A325-N BOLT

(N) CHANNEL

SEE PLAN

(N) STEEL ANGLE

L 3 12" X 2 12" X 14"

2-83/16

CONT. BENT

PL 1/4 x

CJP

3/16 4 PL 1/4"x6"

3/16 4 PL 1/4"

3/16 4 CJP

PL 1/4"x5"

33/16

TOOTH IN NEW BRICK UNITS

(MATCH EXISTING BRICK UNITS,

BOND PATTERN & MORTAR JOINTS)

PERIMETER OF EXISTING OPENING

(REMOVE SLEEVE WHEN EXISTING)

EXISTING BRICK FACE

SCALE: NO SCALE

TYPICAL MASONRY OPENING PATCH

MASONRY PATCHING NOTES

1. PROVIDE DOCUMENTED 5-YEARS EXPERIENCE IN COMPLETION OF WORK, SIMILAR IN

DESIGN, MATERIAL, AND EXTENT SPECIFIED FOR APPROVAL BY COR.

2. CLOSE (PATCH) EXISTING MASONRY OPENING(S) TO MATCH EXISTING ADJACENT

MASONRY WHERE DEMOLITION OPERATIONS RESULTS IN AN UNUSED OPENING.

3. OPENING SIZES VARY. DETAIL INDICATES GENERAL INTENT & NOT LIMITS OF

PATCH BRICK WORK. PROVIDE MASONRY PATCH WORK TO COVER THE ENTIRE

EXTENTS OF ANY OPENING NOT USED DUE TO PROJECT DEMOLITION &

CONSTRUCTION WORK.

4. PREPARE MOCKUP IN SIZE AND LOCATION DIRECTED BY COR, DEMONSTRATING QUALITY

AND AESTHETICS OF TUCK POINTING, MASONRY UNIT REPLACEMENT, AND CLEANING FOR

APPROVAL BY COR. APPROVED MOCKUP SHALL SET THE STANDARD FOR WORK AT

OTHER PROJECT LOCATIONS. MOCKUP MAY BECOME A PERMANENT PART OF THE WORK

WHEN APPROVED BY THE COR OTHERWISE DISPOSE OF MOCKUP WHEN DIRECTED BY

COR.

5. BRICK FACING (VENEER) CONFORMING TO ASTM C216, SHALL MATCH ADJACENT EXISTING

BRICK FACING SIZE, SHAPE, COLOR, AND TEXTURE AND SHALL BE ACCEPTABLE TO THE

COR.

6. CONCRETE MASONRY UNITS (CMU) SHALL MATCH ADJACENT EXISTING CMU SIZE, SHAPE,

COLOR, AND TEXTURE AND SHALL BE ACCEPTABLE TO THE COR.

7. JOINT MORTAR SHALL MATCH EXISTING ADJACENT JOINT MORTAR COLOR AND TEXTURE.

RECOMMEND MORTAR MIX COMPATIBLE WITH EXISTING AND MORTAR MATERIAL

SOURCES REQUIRED TO MATCH EXISTING COLOR AND TEXTURE.

8. LAY UP MASONRY UNITS IN THE SAME BOND AND COURSE PATTERN AS THE EXISTING

ADJACENT MASONRY. TOOTH IN THE MASONRY UNITS TO BLEND IN THE WALL, UNLESS

OTHERWISE APPROVED BY THE COR. MAXIMUM OUT OF PLANE TOLERANCE SHALL BE

1/4-INCH CUMULATIVE TOTAL.

9. TOOL EXPOSED JOINTS (EXTERIOR AND INTERIOR) TO MATCH ADJACENT EXISTING

MASONRY JOINTS. JOINT TOOLING SHALL BE ACCEPTABLE TO THE COR.

10.KEEP FINISH WORK FREE FROM MORTAR SMEARS OR SPATTERS AND LEAVE NEAT AND

CLEAN.

11.BEFORE CONNECTING NEW MASONRY WITH EXISTING MASONRY, REMOVE EXISTING

LOOSENED MASONRY OR MORTAR, AND CLEAN AND WET WORK IN PLACE. TUCK AND

POINT EXISTING ADJACENT MASONRY UP TO 2-FEET BEYOND PATCH WORK.

12.TEST AND WET BRICK ACCORDING TO BIA TN 11B. 2. DO NOT WET CONCRETE MASONRY

UNITS BEFORE LAYING.

13.COMPLY WITH THE REQUIREMENTS STATED IN TMS 602 FOR HOT AND COLD WEATHER

CONSTRUCTION. WHEN TEMPERATURES EXCEED 100 OR 90 WITH WIND VELOCITY > 8 MPH

IMPLEMENT HOT WEATHER REQUIREMENTS OR WHEN TEMPERATURES ARE BELOW 40

IMPLEMENT COLD WEATHER REQUIREMENTS.

SCALE: NO SCALE

TYPICAL BEAM CONNECTION

(N) STEEL CHANNEL

C 6X8.2

T.O. STEEL

RE: PLAN

SCALE: NO SCALE

BRACE FRAME CONNECTION

SCALE: NO SCALE

CATWALK CHANNEL TO EXISTING TYPICAL

3/16

SCALE: NO SCALE

CATWALK POST CONNECTION

EXISTING CATWALK

PL 1/4"x6"

3/16

(N) KICK PLATE

(N) KICK…

This is the start of the file's text. The full file is on GovTribe.