This document provides details for a federal contract solicitation to renovate a behavioral health clinic and outpatient area at a Veterans Affairs medical center. The scope of work involves renovating approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor, including demolition and construction of clinical spaces, offices, public areas, and building systems. The project will be conducted in multiple phases to minimize disruption to patients. The estimated value is between $2-5 million. As a Service-Disabled Veteran-Owned Small Business set-aside, the solicitation will be open to SDVOSBs. The North American Industry Classification code is 236220. The contract duration is 800 calendar days from notice to proceed. Proposals are due around July 9, 2021 and the solicitation package will be available around June 1, 2021.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING LIST
VICINITY MAP
PROJECT TEAMBUILDING SUMMARYGENERAL NOTES
1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE
LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT
DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GENERAL
CONTRACTOR AND ALL SUBCONTRACTORS SHALL REVIEW ALL DRAWINGS AND
SPECIFICATIONS.
2. IT IS HIGHLY RECOMMENDED THAT THE GENERAL CONTRACTOR ATTEND THE
PRE-BID MEETING TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING
PERFORMED BEFORE SUBMITTING COST QUOTATIONS FOR WORK.
3. NOTIFY THE COTR PROMPTLY OF ANY ERRORS, OMISSIONS,
INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT
DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A
RESOLUTION CAN BE PROVIDED PRIOR TO CONTINUING WITH WORK.
4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM
THE ARCHITECT.
5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING
FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE
EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND
SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER,
THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL
CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING
SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS,
INSPECTIONS, AND CERTIFICATES TO THE OWNER.
6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE
DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE
GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT
BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION
THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-
REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL
CONDITION AT THE CONTRACTOR'S EXPENSE.
7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM
THE JOB SITE ON A DAILY BASIS.
8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE
SUBMITTED TO THE COTR AND ARCHITECT IN WRITING AND WILL BE
CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE
ADVANTAGEOUS TO THE OWNER WITH RESPECT TO DELIVERY DATE, QUALITY,
AND/OR COST. SUBSTITUTION REQUESTS MUST BE MADE PRIOR TO BID.
9. THE MEANS AND METHODS OF CONSTRUCTION, TEMPORARY STRUCTURES
AND FACILITIES ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE
ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S
MEANS AND METHODS, TEMPORARY STRUCTURES OR FACILITIES.
10. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR DEMOLISHING AND
REMOVING EXISTING CONSTRUCTION ONLY TO THE EXTENT REQUIRED BY NEW
CONSTRUCTION AND AS INDICATED. USE METHODS REQUIRED TO COMPLETE
THE WORK WITHIN LIMITATIONS OF GOVERNING REGULATIONS.
11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE
GENERAL CONTRACTOR. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE
FOR MEETING OSHA & NFPA REGULATIONS DURING CONSTRUCTION.
12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND
PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM
INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GENERAL
CONTRACTOR SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR
STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED
TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED
TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL
BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.
PROJECT INFORMATION
PROJECT NAME: RENOVATE BEHAVIORAL HEALTH CLINIC
PROJECT NUMBER: 589A4-19-103
PROJECT LOCATION: 800 HOSPITAL DRIVE, COLUMBIA, MO 65201
PROJECT PURPOSE/USE: PHASE 1:THE PROJECT WILL RENOVATE APPROXIMATELY 5,089 SQUARE FOOT ON THE FOURTH FLOOR OF VA TRUMAN MEMORIAL VETERANS BUILDING IN COLUMBIA, MISSOURI.
THIS WILL INCLUDE PROCEDURE ROOMS, PAIN EXAM ROOMS, PM&R EXAM ROOMS, NURSE WORK
ROOMS, MSA CHECKIN, SWAMP ROOMS, EMG/SCI ROOM, PAIN BH, AND PAIN PHARM ROOMS.
PHASE 2-4: THE PROJECT WILL RENOVATE APPROXIMATELY 9,706 SQUARE FOOT OF STATE-OF-THE-ART
OUT-PATIENT BEHAVIORAL HEALTH CLINIC LOCATED ON THE SECOND FLOOR OF VA TRUMAN
MEMORIAL VETERANS BUILDING IN COLUMBIA, MISSOURI. THIS WILL INCLUDE GROUP ROOMS,
ADMINISTRATIVE OFFICES, CLINICAL OFFICES WHICH DOUBLE AS COUNSELING ROOMS, PUBLIC
RESTROOMS, A CENTRAL CHECK-IN/WAITING ROOM AND A STAFF BREAK ROOM.
VA LEADERSHIP SIGNATURES
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
NOT FOR
PERMITTING OR
CONSTRUCTION
A/E:Consultant:
EE
ES
S
OF
M
R C
D
T
T T
II
N
U A
A A
V
RAP
M
N
T
T
OF
E E
D
R S
I
FA
A
N T
S R
F
AEE
Fully Sprinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:4
:5
A
M
SHEET INDEX & GENERAL INFORMATION
RCO EM
Columbia, Missouri
5/13/2021
STATION: Columbia, Missouri
BUILDING NUMBER: 1
1-GI100
589A4-19-103
Columbia Harry S. Truman Memorial Veterans Hospital
BID DOCUMENTS Columbia Harry S. Truman
Memorial Veterans Hospital
BID DOCUMENTS
5/13/2021
PROJECT LOCATION: 800 HOSPITAL DRIVE, COLUMBIA, MO
65201
SHEET
NUMBER SHEET TITLE
1-MD201 LEVEL 02- VENTILATION DEMOLITION
1-MD202 LEVEL 03 - VENTILATION DEMOLITION
1-MD203 LEVEL 04 - VENTILATION DEMOLITION
1-MH101 LEVEL 02 - VENTILATION
1-MH102 LEVEL 03 - VENTILATION
1-MH103 LEVEL 04 - VENTILATION
1-MH300 VENTILATION DETAILS
1-MH400 VENTILATION DIAGRAMS
1-MH500 VENTILATION SCHEDULES
1-MH501 VENTILATION SCHEDULES
1-E-000 ELECTRICAL COVER SHEET
1-ED101 LEVEL 02 - ELECTRICAL DEMOLITION
1-ED102 LEVEL 04 - ELECTRICAL DEMOLITION
1-E101 LEVEL 03 - ELECTRICAL
1-EL101 LEVEL 02 - ELECTRICAL LIGHTING
1-EL103 LEVEL 04 - ELECTRICAL LIGHTING
1-EP101 LEVEL 02 - ELECTRICAL POWER
1-EP102 LEVEL 04 - ELECTRICAL POWER
1-FA101 LEVEL 02 - FIRE ALARM
1-FA102 LEVEL 04 - FIRE ALARM
1-E-300 ELECTRICAL DETAILS
1-E-500 ELECTRICAL SCHEDULES
1-E-501 ELECTRICAL SCHEDULES
1-ET-000 TELECOMMUNICATIONS COVERSHEET
1-TD101 LEVEL 02 - TELECOMMUNICATIONS DEMOLITION
1-TD102 LEVEL 04 -TELECOMMUNICATIONS DEMOLITION
1-ET101 LEVEL 01 - TELECOMMUNICATIONS
1-ET102 LEVEL 02 - TELECOMMUNICATIONS
1-ET103 LEVEL 03 - TELECOMMUNICATIONS
1-ET104 LEVEL 04 - TELECOMMUNICATIONS
1-ET201 ENLARGED PLANS - TELECOMMUNICATIONS
1-T-300 TELECOMMUNICATIONS DETAILS
1-T-400 TELECOMMUNICATIONS DIAGRAMS
1-T-500 TELECOMMUNICATIONS SCHEDULES
SHEET
NUMBER SHEET TITLE
1-AE706 CEILING DETAILS SUSPENDED GYPSUM
1-AE707 SECOND FLOOR WINDOW, DOOR & STAIR DETAILS
1-AF101 SECOND FLOOR DOOR & WINDOW SCHEDULES
1-AF102 FOURTH FLOOR DOOR SCHEDULE & DETAILS
1-AF103 SECOND FLOOR FINISH PLAN & SCHEDULES
1-AF104 FOURTH FLOOR FINISH PLAN & SCHEDULES
1-AF105 SECOND FLOOR WALL TYPES
1-AF106 FOURTH FLOOR WALL TYPES
1-AW101 SECOND AND FOURTH FLOOR SIGNAGE PLAN
1-AW102 SIGNAGE PLAN DETAILS
1-AW103 SIGNAGE PLAN DETAILS
1-FX000 FIRE PROTECTION COVERSHEET
1-FD101 LEVEL 02 - FIRE PROTECTION DEMOLITION
1- FD102 LEVEL 04 - FIRE PROTECTION DEMOLITION
1-FX101 LEVEL 02 - FIRE PROTECTION
1- FX102 LEVEL 04 - FIRE PROTECTION
1-P-000 PLUMBING COVER SHEET
1-PD100 PIPE BASEMENT - PLUMBING DEMOLITION
1-PD101 LEVEL 01 - PLUMBING DEMOLITION
1-PD102 LEVEL 02 - PLUMBING DEMOLITION
1- PD103 LEVEL 03 - PLUMBING DEMOLITION
1- PD104 LEVEL 04 - PLUMBING DEMOLITION
1-PL100 BASEMENT-PLUMBING
1-PL101 LEVEL 01 - PLUMBING
1-PL102 LEVEL 02 - PLUMBING
1- PL103 LEVEL 03 - PLUMBING
1- PL104 LEVEL 04 - PLUMBING
1- P-300 PLUMBING DETAILS
1- P-400 PLUMBING RISERS
1- P-401 PLUMBING RESTROOM RISER
1-MP000 PIPING COVERSHEET
1-MD101 LEVEL 02 - MECHANICAL PIPING DEMOLITION
1-MD102 LEVEL 03 - MECHANICAL PIPING DEMOLITION
1-MD103 LEVEL 04 - MECHANICAL PIPING DEMOLITION
1-MP101 LEVEL 02 - MECHANICAL PIPING
1-MP102 LEVEL 03 - MECHANICAL PIPING
1-MP103 LEVEL 04 - MECHANICAL PIPING
1-MP300 MECHANICAL PIPING DETAILS
1-MP400 MECHANICAL PIPING DIAGRAMS
1-MH000 VENTILATION COVERSHEET
SHEET
NUMBER SHEET TITLE
1-GI100 SHEET INDEX & GENERAL INFORMATION
1-GI101 BUILDING CODE
1-GI102 ABBREVIATIONS & SYMBOLS
1-GI103 SECOND FLOOR LIFE SAFETY PLAN
1-GI104 FOURTH FLOOR LIFE SAFETY PLAN
1-GC101 SECOND & FOURTH FLOOR PHASING & INTERIM LIFE SAFETY PLANS
1-GC102 THIRD FLOOR PHASING PLAN
1-AD101 FIRST FLOOR RCP DEMOLITION PLAN & REFLECTED CEILING PLAN
1-AD102 SECOND FLOOR RCP DEMOLITION PLAN
1-AD103 SECOND FLOOR DEMOLITION PLAN
1-AD104 THIRD FLOOR RCP DEMOLITION PLAN & REFLECTED CEILING PLAN
1-AD105 FOURTH FLOOR RCP DEMOLITION PLAN
1-AD106 FOURTH FLOOR DEMOLITION PLAN
1-AE101 OVERALL SECOND FLOOR PLAN
1-AE102 ENLARGED SECOND FLOOR PLAN
1-AE103 OVERALL FOURTH FLOOR PLAN
1-AE104 ENLARGED FOURTH FLOOR PLAN
1-AE105 SECOND FLOOR DIMENSION PLAN
1-AE106 FOURTH FLOOR DIMENSION PLAN
1-AE107 SECOND FLOOR REFLECTED CEILING PLAN
1-AE108 FOURTH FLOOR REFLECTED CEILING PLAN
1-AE109A SECOND FLOOR EQUIPMENT PLAN
1-AE109B ENLARGED SECOND FLOOR TMS ROOM EQUIPMENT PLAN &
ELEVATIONS
1-AE110A FOURTH FLOOR EQUIPMENT PLAN
1-AE110B FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS
1-AE110C FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS
1-AE110D FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS
1-AE110E FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS
1-AE110F FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS
1-AE401 SECOND FLOOR ENLARGED TOILET PLANS AND ELEVATIONS
1-AE402 SECOND FLOOR ENLARGED TOILET PLANS AND ELEVATIONS
1-AE403 FOURTH FLOOR ENLARGED TOILET PLANS AND ELEVATIONS
1-AE501 SECOND FLOOR MILLWORK PLAN & ELEVATIONS
1-AE502 FOURTH FLOOR MILLWORK PLAN & ELEVATIONS
1-AE503 SECOND FLOOR MILLWORK SECTIONS
1-AE504 FOURTH FLOOR MILLWORK ELEVATIONS & SECTIONS
1-AE702 MISCELLANEOUS DETAILS
1-AE703 SECOND FLOOR CEILING DETAILS
1-AE704 FOURTH FLOOR CEILING DETAILS
1-AE705 METAL STUD DETAILS
ARCHITECT:
Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX
Rebecca Olson, AIA, ACHA Rebecca.olson@romanykconsulting.com
855-424-3838 ext.302 602-430-1265 cell
MECHANICAL ENGINEER:
IMEG
15 Sunnen Drive Suite 104 St. Lois, MO
Scott Przybysz Scott.R.Przybysz@imegcorp.com
314-951-2535
ELECTRICAL ENGINEER:
IMEG
15 Sunnen Drive Suite 104 St. Louis, MO
Mark T. Harris marc.t.harris@imegcorp.com
314-951-2509 314-249-8634
PLUMBING ENGINEER:
IMEG
15 Sunnen Drive Suite 104 St.Louis, MO
Scott Przybysz Scott.R.Przybysz@imegcorp.com
314-951-2535
OWNER:
Department of Veteran Affairs Harry S. Truman Memorial Veterans' Hospital 800 Hospital Drive, Columbia, MO 65201
Jeanette Mathena Jeanette.Mathena@va.gov
Jason Bavlnka jason.bavlnka@va.gov
TECHNOLOGY:
IMEG
15 Sunnen Drive Suite 104 St.Louis, MO
Scott Thomas scott.b.thomas@imegcorp.com
FIRE PROTECTION:
IMEG
15 Sunnen Drive Suite 104 St.Louis, MO
Scott Przybysz Scott.R.Przybysz@imegcorp.com
314-951-2535
INTERIOR DESIGN:
OCULUS INC.
1 South Memorial Drive Suite 1500 St.Louis, MO
Carolyn Fava carolynf@oculusinc.com
314-450-5368
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
PROJECT NAME: RENOVATE BEHAVIORAL HEALTH CLINIC
PROJECT NUMBER: 589A4-19-103
Revisions: Date:
Revision 1 Date 1
NOTE: THESE DRAWINGS DO NOT
INCLUDE IBC BUILDING CODE
INFORMATION
CODE NOTES - 2ND FLOOR
1. DRAWING PURPOSE : NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:
A. 2018 NFPA 101 LIFE SAFETY CODE
a. CHAPTER 4 - GENERAL
b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS
c. CHAPTER 7 - MEANS OF EGRESS
d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY
3. OWNER:
HARRY S. TRUMAN MEMORIAL HOSPITAL
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PH (573) 814-6000
4. ARCHITECT:
ROMANYK CONSULTING
3308 PRESTON ROAD
SUITE 350-164
PLANO, TEXAS
5. ARCHITECT SEAL: SEE STAMP IN TITLEBLOCK
6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT
7. INSPECTION: JCHO; CITY OF COLUMBIA
8. OCCUPANCY GROUP TYPE:
a. OCCUPANCY 1/ BUILDING 1/ 2ND FLOOR: EXISTING HEALTHCARE OCCUPANCY
9. CONSTRUCTION TYPE:
CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)
10. BUILDING 1 - OCCUPANCY 1 GROSS FLOOR AREAS - 2ND FLOOR AREA ACTUAL: 63,736 SF (TOTAL FLOOR)
9,706 SF (AREA OF WORK)
11. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
HEALTH CARE OCCUPANCY:
ALLOWABLE HEIGHT/ 4 OR MORE
STORIES
ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES
12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
CONSTRUCTION TYPE II (222)
HEALTHCARE
OCCUPANCY
BEARING WALLS:
A. EXTERIOR 2 HR
B. INTERIOR 2 HR
C. INT/EXT (ROOF ONLY) 1 HR
NON-BEARING WALLS:
A. EXTERIOR 0 HR
B. INTERIOR NON-COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS 2 HR
B. SUPPORT ROOF ONLY 1 HR
BEAMS/GIRDER/TRUSSES:
A. EXTERIOR: 2 HR
B. INTERIOR: 1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
13. ACTIVE FIRE SAFETY FEATURES:
a. AUTOMATIC SUPPRESSION SYSTEMS:
• SPRINKLER SYSTEM (FULLY SPRINKLED)
• AUTOMATIC AIR-HANDLING SHUT-DOWN
b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP
c. GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR POWERED
d. EXIT LIGHTING.
e. PORTABLE EXTINGUISHERS
f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND MISC
AREAS AS REQ'D (ALSO IN SOME DUCTS)
14. WATER SUPPLY: CITY OF COLUMBIA
15. SPRINKLERS: FULLY SPRINKLERED
16. TOTAL OCCUPANTS
TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
USE (FT2 /PERSON)
HEALTHCARE USE
INPATIENT TREATMENT DEPARTMENTS 240
SLEEPING DEPARTMENTS 120
AMBULATORY HEALTH CARE 150
OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)
BUILDING 1
2ND FLOOR (AREA OF WORK): 9,706/240 = 40" (MEANS OF EGRESS WIDTH CANNOT BE LOWER THAN THIS)
17. MEANS OF EGRESS: TWO MEANS OF EGRESS, AS A MINIMUM REQUIRED (4.5.3.1).
ACTUAL MEANS OF EGRESS (2ND FLOOR): 2 MEANS OF EGRESS
18. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN
32" IN CLEAR WIDTH (7.2.1.2.3.2). DOOR OPENINGS IN PROJECT ARE 42".
19. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET (TABLE A.7.6)
ACTUAL PROJECT DEAD END CORRIDOR (2ND FLOOR) = 24 FEET.
20. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,
SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)
21. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED
FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN
44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).
ACTUAL CORRIDOR WIDTH (2ND FLOOR): 72 INCHES (MIN.)
22. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.
23. TRAVEL DISTANCE TO EXITS= THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). ACTUAL TRAVEL DISTANCE 147 FEET (2ND FLOOR).
24. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)
TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT
(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)
EXISTING HEALTH CARE NO REQUIREMENT 30 FEET 200 FEET
CODE NOTES - 4TH FLOOR
1. DRAWING PURPOSE : NFPA CODE COMPLIANCE
2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:
A. 2018 NFPA 101 LIFE SAFETY CODE
a. CHAPTER 4 - GENERAL
b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS
c. CHAPTER 7 - MEANS OF EGRESS
d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY
3. OWNER:
HARRY S. TRUMAN MEMORIAL HOSPITAL
800 HOSPITAL DRIVE
COLUMBIA, MO 65201
PH (573) 814-6000
4. ARCHITECT:
ROMANYK CONSULTING
3308 PRESTON ROAD
SUITE 350-164
PLANO, TEXAS
5. ARCHITECT SEAL: SEE STAMP AREA IN TITLEBLOCK
6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT
7. INSPECTION: TJC; CITY OF COLUMBIA
8. OCCUPANCY GROUP TYPE: OCCUPANCY 1/ BUILDING 1/ 4TH FLOOR: EXISTING HEALTHCARE OCCUPANCY
9. CONSTRUCTION TYPE: CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)
10. BUILDING GROSS FLOOR AREA: 4TH FLOOR AREA: 23,409 SF (TOTAL FLOOR AREA)
5,089 SF (AREA OF WORK)
11. HEIGHT & AREA LIMITATIONS:
ALLOWABLE AREA: UNLIMITED
HEALTH CARE OCCUPANCY:
ALLOWABLE HEIGHT/ 4 OR MORE
STORIES
ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES
12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):
HEALTHCARE
OCCUPANCY
CONSTRUCTION TYPE II (222)
BEARING WALLS:
A. EXTERIOR 2 HR
B. INTERIOR 2 HR
C. INT/EXT (ROOF ONLY) 1 HR
NON-BEARING WALLS:
A. EXTERIOR 0 HR
B. INTERIOR NON-COMBUSTIBLE
COLUMNS:
A. SUPPORT FLOORS 2 HR
B. SUPPORT ROOF ONLY 1 HR
BEAMS/GIRDER/TRUSSES:
A. EXTERIOR: 2 HR
B. INTERIOR: 1 HR
FLOOR CONSTRUCTION: 2 HR
ROOF CONSTRUCTION: 1 HR
13. ACTIVE FIRE SAFETY FEATURES:
a. AUTOMATIC SUPPRESSION SYSTEMS:
• SPRINKLER SYSTEM (FULLY SPRINKLED)
• AUTOMATIC AIR-HANDLING SHUT-DOWN
b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP
c. GENERATOR POWERED EMERGENCY LIGHTING
d. EXIT LIGHTING.
e. PORTABLE EXTINGUISHERS
f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND
AREAS AS REQ'D.
14. WATER SUPPLY: CITY OF COLUMBIA
15. SPRINKLERS: FULLY SPRINKLERED
16. TOTAL OCCUPANTS
TABLE 7.3.1.2 OCCUPANT LOAD FACTOR
USE (FT2 /PERSON)
HEALTHCARE USE
INPATIENT TREATMENT DEPARTMENTS 240
SLEEPING DEPARTMENTS 120
AMBULATORY HEALTH CARE 150
OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)
BUILDING 1
4TH FLOOR (AREA OF WORK): 5,089/150 = 34 TOTAL OCCUPANTS
17. EXIT WIDTH: TABLE 7.3.3.1 CAPACITY FACTORS
EXIT WIDTH STAIRS: 34 OCCUPANTS X.3 INCHES = 10.2" (SCOPE OF WORK)
EXIT WIDTH LEVEL COMPONENTS: 34 X .2 INCHES = 6.8" (SCOPE OF WORK)
18. MEANS OF EGRESS: MINIMUM REQUIRED TWO MEANS OF EGRESS (4.5.3.1)
ACTUAL MEANS OF EGRESS (4TH FLOOR): 2 MEANS OF EGRESS
19. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN 32" IN CLEAR WIDTH (7.2.1.2.3.2).
DOOR OPENINGS IN PROJECT ARE 42" MINIMUM.
20. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET. (TABLE A.7.6)
ACTUAL PROJECT DEAD END CORRIDOR (4TH FLOOR) = 12'
21. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,
SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)
22. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED
FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN
44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).
ACTUAL CORRIDOR WIDTH (4TH FLOOR): 72"
23. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON
EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.
24. TRAVEL DISTANCE TO EXITS: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND
AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). 19.2.6.2.2
THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1
SHALL BE PERMITTED TO INCREASE BY 50 FEET IN BUILDINGS
PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH 19.3.5.7.
ACTUAL MAX TRAVEL DISTANCE: 173'- 6" (4TH FLOOR).
25. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)
TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT
(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)
EXISTING NO REQUIREMENT 30 FEET 200 FEET
NOTE: THESE DRAWINGS DO NOT
INCLUDE IBC BUILDING CODE
INFORMATION
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:4
:5
A
M
BUILDING CODE
RCO EM
BID DOCUMENTS 589A4-19-103
1-GI101
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02Revisions: Date:
1i
0 GRID / COLUMN LINE DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
Ga5xFB1
WALL TYPE
WINDOW TYPE
ROOM NAME
ROOM NAME / NUMBER
REVISION TAG
NORTH
NORTH ARROW WITH TRUE
NORTH INDICATION
EGRESS ROUTE ID AND
SECTION LENGTH
ROOM
ROOM OCCUPANCY
150 SF
EGRESS : EGRESS ID
Egress Length
ROOM OCCUPANCY & AREA
ELEVATION NUMBER
SECTION
INTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name Elevation
FLOOR LEVEL &
NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
SHEET KEYNOTE
A101
SIM
EXTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS DRAWN
A101
A101
ANNOTATION DRAWING SYMBOLS
INDEX OF DRAWINGS
202-A101
DISCIPLINE:
G - GENERAL
A - ARCHITECTURE
I - INTERIORS
F- FIRE PROTECTION
P - PLUMBING
M - MECHANICAL
E - ELECTRICAL
T - TELECOM
V - VENTILATION
SHEET TYPE
DESIGNATOR
BUILDING NUMBER
SHEET NUMBER
WITHIN SERIES
ARCHITECTURAL SYMBOLS
LEGEND
CONCRETE/ PRECAST
CONCRETE
SOIL
SAND, EIFS FINISH COAT,
OR CEMENT PLASTER
BRICK
CMU
STONE
FIBERGLASS BATT
INSULATION
EXPANDED POLYSTYRENE
RIGID INSULATION
EXTRUDED POLYSTYRENE
RIGID INSULATION
POLYISOCYANURATE RIGID
INSULATION
GYPSUM BOARD
EXTERIOR GYPSUM
SHEATHING
EXTERIOR CEMENT
BOARD
COATED GLASS MAT
WATER RESISTANT
GYP BD
PLYWOOD
COVER BOARD
MATERIALS
CEILING SYMBOLS
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
24" X 24" ACOUSTICAL CEILING
PANEL AND GRID
GYPSUM BOARD CEILING OR
SOFFIT
2' x 2' LED FLUORESCENT
FIXTURE - EMERGENCY NIGHT
LIGHT
RECESSED CAN DOWNLIGHT
CEILING ELEVATION A.F.F.X'-X"
EXIT SIGN
LED LIGHT
1' x 4' LED FLUORESCENT
FIXTURE
2' x 4' LED FLUORESCENT
FIXTURE
INDUSTRIAL LUMINAIRE
EMERGENCY LIGHT
2' x 2' LED FLUORESCENT
FIXTURE
OC
NURSE CALL DOME LIGHT WALL
MOUNTED
A
FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE-CEILING
MOUNTED.
CAM
LS
OCCUPANCY SENSOR
A1 A3
DAYLIGHT LEVEL SENSOR
CLOSED CIRCUIT CAMERA (CCTV)
CEILING MOUNTED
N
S SPEAKER
CLOSED CIRCUIT CAMERA (CCTV)CAM
VC VACANCY SENSOR
WAP CEILING INFORMATION OUTLET
FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1
WALL CONTROL STATIONSW
NURSE CALL STATIONN
SMOKE,FIRE/SMOKE
DAMPER CONTROLLER
ARD
FIRE ALARM MANUAL PULL
STATION
F
FIRE ALARM SMOKE,
SMOKE DAMPER
SD
SD FIRE ALARM DUCT SMOKE
DETECTOR
D DIMMER LED
A FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE- WALL
MOUNTED.
A1 A3
S SWITCH
{LD}
{LS}
LIGHT DIMMER
LIGHT SENSOR
ARCHITECTURAL DRAWING ABBREVIATIONS
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALG ALUMINUM AND GLASS
AL ALUMINUM
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ELEV EQ ELEVATOR EQUIPMENT
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED INSTALLED BY GOVERNMENT
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GSF GROSS SQUARE FEET
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HAC HOUSE AID KEEPING CLOSET
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
ISO ISOLATION
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL FLASH SHEET METAL (FLASHING)
SHTHG SHEATHING
SHWR SHOWER
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
SEE OTHER DISCIPLINES FOR
ADDITIONAL ABREVIATIONS
NOTE: NOT ALL MAY BE USED
ARCHITECTURAL SYMBOLS
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:4
:5
A
M
ABBREVIATIONS & SYMBOLS
RCO EM
BID DOCUMENTS 589A4-19-103
1-GI102
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
A
A1
A1
A3
A1
A3
A3
A
A1
V1
A
A3
A1
A1
A1 A1
A1
F
UP
UP
FDFD
FD
FD
FEC
F E
C
F E
C
FEC
FEC
FEC
F E
C
FEC
F E
C
LIFE SAFETY NOTES
FEC
AREA PLAN LEGEND
BARRIER LEGEND
Na
N
N
M
M
L
L
2.82.8
3.73.7
4.64.6
5.55.5
6.36.3
K
K
J
J
H
H
G
G
F
F
7.27.2
8.38.3
9.19.1
CONTROLLED ACCESS
CONTROLLED ACCESS
CONTROLLED ACCESS
204 SF
A200
CLINIC
OFFICE
154 SF
A203
CLINIC
OFFICE
182 SF
A204
CLINIC
OFFICE
152 SF
A202
CLINIC
OFFICE
94 SF
A201B
OBSERVATION
63 SF
C2A02
CORRIDOR
197 SF
A201
PSYCH.
RES
183 SF
A206
PSYCH.
RES
24 SF
A206A
EXIST.
STRG
295 SF
C2A01
CORRIDOR
178 SF
A205
PSYCH.
RES
49 SF
A207
EXIST.
ELEC
368 SF
C2A04
CORRIDOR
154 SF
C2A03
CORRIDOR
169 SF
A208
TMS
ROOM
163 SF
A210
TMS
ROOM
64 SF
A212
EXIST.
SOC
WRK
63 SF
A213
EXIST.
SOC
WRK
143 SF
C2A05
CORRIDOR
112 SF
A209
CARE
COORDINATOR
111 SF
A211
CARE
COORDINATOR
74 SF
A214
STAFF
RESTROOM
72 SF
A215
HAC
308 SF
A217
EXIST. IT
173 SF
A221
WOMEN'S
185 SF
A222
MEN'S
96 SF
A216
EXIST.
ELEC.
CLO.
861 SF
C2A07
CORRIDOR
567 SF
C2A08
CORRIDOR
1235 SF
A226
GROUP
ROOM
WAITING
AREA
372 SF
A224
WAITING
398 SF
A223
WAITING
89 SF
A223B
WORK
AREA
64 SF
A223C
COPIER/PAPER
STORAGE
AREA
MAIL AREA
A223D
125 SF
A223A
CHECKOUT/CHECK
IN
307 SF
A219
GROUP
ROOM
320 SF
A218
GROUP
ROOM
515 SF
A220
GROUP
ROOM
TRAVEL DISTANCE: 91' - 4"
TRAVEL DISTANCE: 93' - 0"
STAIR #1
65 SF
VESTIBULE
A200A
COMPLIANCE NOTE
PER 7.5.1.6
EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
PERMITTED TO BE THROUGH
ADJOINING OR INTERVENING ROOMS OR AREAS,
PROVIDED THAT SUCH ROOMS OR AREAS ARE
ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES,
AND RECEPTION ROOMS. CONSTRUCTED AS
REQUIRED FOR CORRIDORS SHALL NOT BE
CONSTRUED AS INTERVENING ROOMS.
SC1 SUITE (PATIENT
CARE NON-SLEEPING):
1,882 SF
98"
EXISTING
STAIRS #1
EXISTING BUILDING #1 - OCCUPANCY #1 - 2ND FLOOR = 63,705 SF
OCCUPANCY TYPE - HEALTHCARE
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS 670
FULLY SPRINKLERED
3 3 4
22 21
2 2
SMOKE COMPARTMENT
12,212 SF
670/3 20.6" 46.5"
406/3
22.4"
EXISTING
STAIRS #2
670/8 25"
40.5"
SMOKE
COMPARTMENT
12,212 SF
COMPLIANCE NOTE
PER NFPA 19.3.7.9
DOOR OPENINGS IN SMOKE BARRIERS SHALL BE
PROTECTED USING ONE OF THE FOLLOWING
METHODS:
(1) SWINGING DOOR PROVIDING A CLEAR WIDTH OF
NOT LESS THAN 32 INCHES.
STAIR #2
COMPLIANCE NOTE
PER 7.5.1.6
EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
PERMITTED TO BE THROUGH
ADJOINING OR INTERVENING ROOMS OR AREAS,
PROVIDED THAT SUCH ROOMS OR AREAS ARE
ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES,
AND RECEPTION ROOMS. CONSTRUCTED AS
REQUIRED FOR CORRIDORS SHALL NOT BE
CONSTRUED AS INTERVENING ROOMS.
COMPLIANCE NOTE
PER NFPA 19.2.3.4
ANY REQUIRED AISLE, CORRIDOR, OR RAMP SHALL BE
NOT LESS THAN 48 INCHES IN CLEAR WIDTH WHERE
SERVING AS MEANS OF EGRESS FROM PATIENT
SLEEPING ROOMS, UNLESS OTHERWISE PERMITTED BY
ONE OF THE FOLLOWING:
(4) PROJECTIONS INTO THE REQUIRED WIDTH SHALL
BE PERMITTED FOR WHEELED EQUIPMENT, PROVIDED
THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
(C) THE WHEELED EQUIPMENT IS LIMITED TO THE
FOLLOWING:
I. EQUIPMENT IN USE AND CARTS IN USE
II. MEDICAL EMERGENCY EQUIPMENT NOT IN USE
III. PATIENT LIFT AND TRANSPORT EQUIPMENT
19.2.5.7.3.1 PATIENT CARE NON-SLEEPING SUITE
MEANS OF EGRESS.
(C) FOR SUITES REQUIRING TWO EXIT ACCESS DOORS,
ONE OF THE EXIT DOORS SHALL BE PERMITTED TO BE ONE
OF THE FOLLOWING:
(4) ANOTHER SUITE, PROVIDED THAT THE SEPARATION
BETWEEN THE SUITES COMPLIES WITH THE CORRIDOR
REQUIREMENTS OF 19.3.6.2 THROUGH 19.3.6.5
203 SF
CORRIDOR 7
C2A09
COMPLIANCE NOTE
PER NFPA TABLE A.7.6
TRAVEL DISTANCE LIMIT=200' FOR
EXISTING HEALTH CARE SPRINKLERED
BUILDINGS
TABLE A.7.6
COMMON PATH OF TRAVEL-NO
REQUIREMENT FOR EXISTING HEALTH
CARE SPRINKLERED BUILDINGS
T R
A V
E L D
IS
T
A N
C E
TEMPORARY CONSTRUCTION
BARRIER
T R
A V
E L D
IS
T
A N
C E
1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.
2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE
DETECTION SYSTEM.
3. WALL TYPES ARE DETAILED ON 1-AF105 AND INDICATED ON THE
DIMENSIONED FLOOR PLAN ON 1-AE109.
4. REFER TO THIS DRAWING FOR MEANS OF EGRESS.
5. REFER TO THIS DRAWING FOR DOOR CAPACITIES.
6. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE
MARSHAL.
7. ALL SMOKE BARRIERS/PARTITIONS & FIRE RATED WALLS/ASSEMBLY
SHALL BE PAINTED (IN RED LETTERS) W/APPROPRIATE LABEL &
RATING.
FIRE EXTINGUISHER CABINET
ILLUMINATED EXIT SIGN
A
FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE-CEILING
MOUNTED
A1 A3
FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1
A1
FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE-WALL MOUNTED
FIRE ALARM MANUAL PULL
STATION
F
AREA NOT IN CONTRACT
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
NEW
PARTITION KEY
NFPA
101-2015
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
(FIRE WALL IN IBC)
2 HR 90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR 90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS (SPRINKLERED)
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
VERT. OPG. (SHAFT)
FIRE BARRIER
60 MIN
[D]
1 HR
2 HR
60 MIN
90 MIN
EXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
8.7
NFPA 6.1.14.4.1
18.1.3.5.1 19.1.3.5.1
NFPA 7.2.A.3.1 (1)
NFPA 18.1.3.8/
19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1
NFPA 19.3.1.1
NFPA 8.6.2
8.6.5
NFPA 18.3.2.1.2
NFPA 8.4.1.1
19.3.2.1
NFPA 8.4.2 (3)
18.3.2.1.3 19.3.2.1.2
NFPA 8.5.2
18.3.7.3 19.3.7.3
NFPA 8.4.2
18.2.5.7.1.4 19.2.5.7.1.1
NFPA 8.4.2
18.3.6.2 19.3.6.2
21.3.6 39.3.6
NFPA 19.3.1.1
19.2.2.7 8.6.2 8.6.5(3) & 2
NFPA 7.2.6
19.2.2.7 18.2.2.7
NFPA 221
8.2.1.3
EXIST SOL.
CORE WD.
NFPA 7.2.1.4.1
7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4
8.3.4.2 TBL
18.4.4.7.2.2
7.1.3.2.9 (9)
NFPA 8.3.4.2 TBL
19.3.2.1.3,5
NFPA 8.3.4.2 TBL
8.5.4 18.3.7.8
NFPA 8.3.4.2 TBL
8.3.4.2 TBL
8.3.4.2 TBL
NFPA 8.3.4.2 TBL
8.3.4.2 8.4.3 19.3.2.1.4,3,5
8.4.3
8.4.3 18.3.6.4.1 19.3.6.4.1
N/A
FIRE
90 MIN
FIRE
90 MIN
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
NFPA 90
8.3.5.7 9.2.1
NFPA 8.3.5.7
9.2.1 7.2.4.3.5
N/A
8.5.5.2 18.3.7.3(2) 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2 18.3.6.4.1
N/A
WALL
RATING
RATED UL
ASSEMBLIES
2 HR
1 HR
1 HR
NR-
RESIST
SMK
NR
NR-
RESIST
SMK
NR
8.3
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
NR
SELF OR AUTO
CLOSING
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
NFPA 90
8.3.5.7 9.2.1
A
C
E
B
SECOND FLOOR KEY PLAN
AREA OF
WORK
TRAVEL
PATH
STARTING
LOCATION
TD = XX
TRAVEL DISTANCE
NO. OF OCC./
NO. OF EXITS
ACTUAL
EXIT
WIDTH
OCC.
LOAD
FACTOR
LIFE SAFETY SYMBOLS
10/1
2"
34"
1:50
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING FB1 = FIRE BARRIER 1HR
FB2 = FIRE BARRIER 2HR
SB1 = SMOKE BARRIER- 1 HOUR
NON-RATED INTERIOR PARTITION WALL
NON-RATED INTERIOR PARTITION WALL (WITH
INSULATION)
EXISTING WALL TO REMAIN
SEE AF105 FOR WALL TYPE CONSTRUCTION
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:5
:4
A
M
SECOND FLOOR LIFE SAFETY PLAN
RCO EM
BID DOCUMENTS 589A4-19-103
1-GI103
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered
1/8" = 1'-0"
LEVEL 02 - LIFE SAFETY PLAN- PHASE 01
NORTH
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
FEC
AREA PLAN LEGEND
LIFE SAFETY NOTES
A1
A1
V1
A1
V1 V1
V1
V1
A
V1
V1
V1
V1
V1
A1
A1
FEC
F E
C
FEC
FEC
BARRIER LEGEND
AREA OF
WORK
FOURTH FLOOR KEY PLAN
FIRE EXTINGUISHER CABINET
ILLUMINATED EXIT SIGN
A
FIRE ALARM AUDIO/VISUAL
NOTIFICATION DEVICE-CEILING
MOUNTED
A1 A3
FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1
A1
FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE-WALL MOUNTED
FIRE ALARM MANUAL PULL
STATION
F
TRAVEL
PATH
STARTING
LOCATION
TD = XX
TRAVEL DISTANCE
NO. OF OCC./
NO. OF EXITS
ACTUAL
EXIT
WIDTH
OCC.
LOAD
FACTOR
LIFE SAFETY SYMBOLS
10/1
2"
34"
1:50
NO. OCC. EXITING
(SMALLER ROOMS)
MAXIMUM OCCUPANCY
AREA
REQ'D. EXIT WIDTH
NO. OF OCC. EXITING
LEGEND
BUILDING & LIFE SAFETY REQUIREMENTS
DESCRIPTION
NEW
PARTITION KEY
NFPA
101-2015
OPENINGS DAMPERS
RATING RFRNC. TYPE RFRNC.
BUILDING SEPARATION:
FIRE BARRIER
(FIRE WALL IN IBC)
2 HR 90 MIN
OCCUPANCY/AREA SEPARATION
FIRE BARRIER
90 MIN
HORIZONTAL EXIT (& REFUGE AREA)
FIRE BARRIER
2 HR 90 MIN
VERT. OPG. (EXIT ENCLSR/SHAFT)
FIRE BARRIER
(2 HR = 4 OR MORE STORIES)
(1 HR = LESS THAN 4 STORIES)1 HR
2 HR
60 MIN
90 MIN
HAZ./INCIDENTAL USE
FIRE BARRIER
45 MIN
HAZ./INCIDENTAL USE
SMOKE PARTITIONS (SPRINKLERED)
NR
SELF OR AUTO
CLOSING
SUBDIVIDING SPACES
SMOKE BARRIER (I-2 OCCUPANCY)
20 MIN
1/2
HR
1 HR
SUITE SEPARATION
SMOKE PARTITION
EXIT ACCESS CORRIDORS (I-2)
SMOKE PARTITIONS (SPRINKLERED)
NR
EXIT ACCESS CORRIDORS (B & AHC)
NON-RATED PARTITIONS
NR
VERT. OPG. (SHAFT)
FIRE BARRIER
60 MIN
[D]
1 HR
2 HR
60 MIN
90 MIN
EXIT PASSAGEWAY (HORIZ.)
FIRE BARRIER
8.7
NFPA 6.1.14.4.1
18.1.3.5.1 19.1.3.5.1
NFPA 7.2.A.3.1 (1)
NFPA 18.1.3.8/
19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1
NFPA 19.3.1.1
NFPA 8.6.2
8.6.5
NFPA 18.3.2.1.2
NFPA 8.4.1.1
19.3.2.1
NFPA 8.4.2 (3)
18.3.2.1.3 19.3.2.1.2
NFPA 8.5.2
18.3.7.3 19.3.7.3
NFPA 8.4.2
18.2.5.7.1.4 19.2.5.7.1.1
NFPA 8.4.2
18.3.6.2 19.3.6.2
21.3.6 39.3.6
NFPA 19.3.1.1
19.2.2.7 8.6.2 8.6.5(3) & 2
NFPA 7.2.6
19.2.2.7 18.2.2.7
NFPA 221
8.2.1.3
EXIST SOL.
CORE WD.
NFPA 7.2.1.4.1
7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4
8.3.4.2 TBL
18.4.4.7.2.2
7.1.3.2.9 (9)
NFPA 8.3.4.2 TBL
19.3.2.1.3,5
NFPA 8.3.4.2 TBL
8.5.4 18.3.7.8
NFPA 8.3.4.2 TBL
8.3.4.2 TBL
8.3.4.2 TBL
NFPA 8.3.4.2 TBL
8.3.4.2 8.4.3 19.3.2.1.4,3,5
8.4.3
8.4.3 18.3.6.4.1 19.3.6.4.1
N/A
FIRE
90 MIN
FIRE
90 MIN
VARIES
SMOKE
90 MIN
VARIES
VARIES
NONE
N/A
NOT
ALLOWED
NFPA 90
8.3.5.7 9.2.1
NFPA 8.3.5.7
9.2.1 7.2.4.3.5
N/A
8.5.5.2 18.3.7.3(2) 19.3.7.3(2)
8.6.4.5
N/A
N/A
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2
8.4.4.1 8.4.6.2 18.3.6.4.1
N/A
WALL
RATING
RATED UL
ASSEMBLIES
2 HR
1 HR
1 HR
NR-
RESIST
SMK
NR
NR-
RESIST
SMK
NR
8.3
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U415 (A)
UL U412
UL U419
UL U412
UL U419
UL U415 (A)
NR
SELF OR AUTO
CLOSING
FIRE
90 MIN
FIRE
90 MIN
NOT
ALLOWED
UNLESS
SERVING
STAIR ONLY
NFPA 90
8.3.5.7 9.2.1
AREA NOT IN CONTRACT
1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.
2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13
AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE
DETECTION SYSTEM.
3. WALL TYPES ARE DETAILED ON 1-AF106 AND INDICATED ON THE
DIMENSIONED FLOOR PLAN ON 1-AE104.
4. REFER TO THIS DRAWING FOR MEANS OF EGRESS.
5. REFER TO THIS DRAWING FOR DOOR CAPACITIES.
6. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE
MARSHAL.
7. ALL SMOKE BARRIERS/PARTITIONS & FIRE RATED WALLS/ASSEMBLY
SHALL BE PAINTED (IN RED LETTERS) W/APPROPRIATE LABEL &
RATING.
Na
Na
N
N
M
M
L
L
K
K
J
J
H
H
G
G
F
F
4.4
5.45.4
5.7
6.26.2
6.76.7
10.110.1
2.92.9
Ea
Ea
Fa
Fa
GaJaLaMa
Ma HbJb
189 SF
EMG/SCI
71 SF
NURSE NAVIGATOR
74 SF
PAIN & PMR VVC/TM
97 SF
PAIN BH
99 SF
PAIN PHARM
119 SF
PAIN EXAM ROOM 2
122 SF
PAIN EXAM ROOM 3
126 SF
PAIN EXAM ROOM 4
52 SF
WORKSTATION
54 SF
TOILET
145 SF
PAIN SWAMP
47 SF
EXISTING ELEC.
492A
103 SF
SOILED HOLDING
53 SF
TOILET
125 SF
PAIN EXAM
171 SF
PM&R SWAMP
148 SF
PM&R EXAM ROOM 4
156 SF
PM&R EXAM ROOM 3
150 SF
PM&R EXAM ROOM 1
150 SF
PM&R EXAM ROOM 2
106 SF
MSA CHECKIN/OUT
234 SF
PROCEDURE ROOM
124 SF
CLEAN SUPPLY
259 SF
PROCEDURE ROOM
180 SF
OIT
180 SF
CORRIDOR
C498
BLDG 1 - OCCUPANCY 1 - 4TH FLOOR =
5,089 SF (AREA OF WORK)
OCCUPANCY TYPE - AMBULATORY
TYPE II (222) CONSTRUCTION
TOTAL OCCUPANTS = 34
FULLY SPRINKLERED
TRAVEL DISTANCE: 86' - 6"
TRAVEL DISTANCE: 173' - 6"
T R
A V
E L D
IS
T
A N
C E
T R
A V
E L D
IS
T
A N
C E
443 SF
Room
A200BBB
387 SF
Room
A200CCC
SUITE
(PATIENT CARE
NON-SLEEPING)
5,089 SF
EXIT
ACCESS
DOOR
ROOF BELOW ROOF BELOW
EXIT
ACCESS
DOOR
EXISTING
SMOKE
COMP 4-2
11,434 SF
1 1 1 1 1
EXISTING
SMOKE
COMP 4-1
11,372 SF
1:150
1:50
1:50
1:50
1:50
1:50
1:150
1:50
1:150
1:150
1:150
1:150
1:150
1:150
1:50
1:150
1:150
1:150
1:150
1:150
EXISTING
SMOKE
COMP 4-2
11,434 SF
EXISTING
SMOKE
COMP 4-1
11,372 SF
EXISTING
STAIR #1
44.5"
218/2
21.8"
EXISTING
STAIR #2
44.5"
218/2
21.8"
TRAVEL DISTANCE: 100' - 0"
144 SF
NURSES
180 SF
CORRIDOR
C498
321 SF
CORRIDOR
C496
259 SF
CORRIDOR
C499
S F
C O
R R
ID
O
R
C
TEMPORARY CONSTRUCTION
BARRIER
COMPLIANCE NOTE
PER NFPA TABLE A.7.6
TRAVEL DISTANCE LIMIT=200' FOR
EXISTING HEALTH CARE SPRINKLERED
BUILDINGS
TABLE A.7.6
COMMON PATH OF TRAVEL-NO
REQUIREMENT FOR EXISTING HEALTH
CARE SPRINKLERED BUILDINGS
COMPLIANCE NOTE
PER NFPA TABLE A.7.6
TRAVEL DISTANCE LIMIT=200' FOR
EXISTING HEALTH CARE SPRINKLERED
BUILDINGS
TABLE A.7.6
COMMON PATH OF TRAVEL-NO
REQUIREMENT FOR EXISTING HEALTH
CARE SPRINKLERED BUILDINGS
COMPLIANCE NOTE
PER NFPA TABLE A.7.6
TRAVEL DISTANCE LIMIT=200' FOR
EXISTING HEALTH CARE SPRINKLERED
BUILDINGS
TABLE A.7.6
COMMON PATH OF TRAVEL-NO
REQUIREMENT FOR EXISTING HEALTH
CARE SPRINKLERED BUILDINGS
FB1 = FIRE BARRIER 1HR
FB2 = FIRE BARRIER 2HR
SB1 = SMOKE BARRIER
NON-RATED INTERIOR PARTITION WALL
NON-RATED INTERIOR PARTITION WALL (WITH
INSULATION)
EXISTING WALL TO REMAIN
SEE AF105 FOR WALL TYPE CONSTRUCTION
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:5
:5
A
M
FOURTH FLOOR LIFE SAFETY PLAN
RCO EM
BID DOCUMENTS 589A4-19-103
1-GI104
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered
1/8" = 1'-0"
LEVEL 04 - LIFE SAFETY PLAN
NORTH
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
AREA PLAN LEGEND
189 SF
EMG/SCI
71 SF
NURSE NAVIGATOR
74 SF
PAIN & PMR VVC/TM
97 SF
PAIN BH
99 SF
PAIN PHARM
119 SF
PAIN EXAM ROOM 2
122 SF
PAIN EXAM ROOM 3
126 SF
PAIN EXAM ROOM 4
52 SF
WORKSTATION
54 SF
TOILET
145 SF
PAIN SWAMP
180 SF
OIT
259 SF
PROCEDURE ROOM
124 SF
CLEAN SUPPLY
234 SF
PROCEDURE ROOM
103 SF
SOILED HOLDING
47 SF
EXISTING ELEC.
492A
125 SF
PAIN EXAM
171 SF
PM&R SWAMP
53 SF
TOILET
106 SF
MSA CHECKIN/OUT
150 SF
PM&R EXAM ROOM 1
150 SF
PM&R EXAM ROOM 2
156 SF
PM&R EXAM ROOM 3
148 SF
PM&R EXAM ROOM 4
144 SF
NURSES
180 SF
CORRIDOR
C498
321 SF
CORRIDOR
C496
316 SF
CORRIDOR
C495
259 SF
CORRIDOR
C499
TRAVEL DISTANCE: 87' - 0"
TRAVEL DISTANCE: 173' - 6"
T R
A V
E L D
IS
T
A N
C E
T R
A V
E L D
IS
T
A N
C E
TRAVEL DISTANCE: 100' - 6"
TEMPORARY CONSTRUCTION
BARRIER
320 SF
A218
GROUP
ROOM
307 SF
A219
GROUP
ROOM
182 SF
A204
CLINIC
OFFICE
154 SF
A203
CLINIC
OFFICE
204 SF
A200
CLINIC
OFFICE
94 SF
A201B
OBSERVATION
197 SF
A201
PSYCH.
RES
183 SF
A206
PSYCH.
RES
24 SF
A206A
EXIST.
STRG
49 SF
A207
EXIST.
ELEC
163 SF
A210
TMS
ROOM
63 SF
A213
EXIST.
SOC
WRK
64 SF
A212
EXIST.
SOC
WRK
308 SF
A217
EXIST. IT
96 SF
EXIST. ELEC. CLO.
A216
185 SF
A222
MEN'S
173 SF
A221
WOMEN'S
398 SF
A223
WAITING
125 SF
A223A
CHECKOUT/CHECK
IN
372 SF
A224
WAITING
515 SF
A220
GROUP
ROOM
169 SF
A208
TMS
ROOM
74 SF
A214
STAFF
RESTROOM
72 SF
A215
HAC
111 SF
A211
CARE
COORDINATOR
112 SF
A209
CARE
COORDINATOR
64 SF
A223C
COPIER/PAPER
STORAGE
AREA
89 SF
A223B
WORK
AREA
152 SF
A202
CLINIC
OFFICE
178 SF
A205
PSYCH.
RES
1235 SF
A226
GROUP
ROOM
WAITING
AREA
567 SF
C2A08
CORRIDOR
861 SF
C2A07
CORRIDOR
154 SF
C2A03
CORRIDOR
143 SF
C2A05
CORRIDOR
295 SF
CORRIDOR 1
C2A01
63 SF
CORRIDOR 2
C2A02
368 SF
C2A04
CORRIDOR
65 SF
VESTIBULE
A200A
AREA
WALKWAY NEEDS TO STAY OPEN
DURING 7AM TO 5PM OPERATING
HOURS
NIGHTS/WEEKENDS FOR WORK
AVAILABLE
PHASE II-GROUP ROOMS,
RESTROOMS AND WAITING ROOM
WILL BE DONE AT THE SAME TIME
THIS ENTRANCE MUST TO
STAY OPEN
DURING 7AM TO 5PM
OPERATING HOURS
NIGHTS/WEEKENDS FOR
WORK AVAILABLE
TO ACCESS ELEVATORS
THIS ENTRANCE MUST TO STAY
OPEN DURING 7AM TO 5PM
OPERATING HOURS
NIGHTS/WEEKENDS FOR WORK
AVAILABLE
PH 4
P H
P H
PH2
PH2
PH 4
PH3
PH3
PH2
WORK SHALL BE NIGHTS/WEEKENDS
AND COORDINATED WITH COR 2 WEEKS
AHEAD OF TIME. 4TH FLOOR:
PHASE 1
PHASE 4 WORK OCCURS IN
CORRIDORS WHICH MUST
REMAIN OPEN 7AM TO 5PM.
WORK IN THE SPACES TO BE
CONDUCTED ON
NIGHTS/WEEKENDS
PHASE IV WORK OCCURS IN
CORRIDORS WHICH MUST
REMAIN OPEN 7AM TO 5PM.
WORK IN THE SPACES TO BE
CONDUCTED ON
NIGHTS/WEEKENDS
TEMPORARY CONSTRUCTION
BARRIER
TEMPORARY CONSTRUCTION
BARRIER
TEMPORARY CONSTRUCTION
BARRIER
TEMPORARY CONSTRUCTION
BARRIER
TRAVEL DISTANCE: 91' - 4"
T R
A V
E L D
IS
T
A N
C E
TEMPORARY CONSTRUCTION
BARRIER
A
C
E
B
SECOND FLOOR KEY PLAN
AREA OF
WORK
AREA OF
WORK
FOURTH FLOOR KEY PLAN
AREA NOT IN CONTRACT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:4
:4
A
M
SECOND & FOURTH FLOOR PHASING &
INTERIM LIFE SAFETY PLANS
KM EM
BID DOCUMENTS 589A4-19-103
1-GC101
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered
3/32" = 1'-0"
PHASE 1 - FOURTH FLOOR PLAN
3/32" = 1'-0"
PHASE 2 - SECOND FLOOR PLAN
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
NORTH
C3A2
A313
A312 A318A A318 A322 A323 A326
A321A
A319
A317
C A
A353A354
D334A
D335 D336D334
D333BD333A
A356
A358
D333
A318
A320
A314
C3A6
C3A4
A
A316 A321
B304 B302
B315 B316 B317 B318
B325 B303 B301 B300
B323 B322
B321
B320
B338
B347
B345 A A
B344
B342
B341
C3B5
C3B1 B304A B302A
B340
B315BB315A
B316A
B316B
B317A B318A
B301AB303A
C3B4
B339
B
A300
B
D332
STR #1
#2#3 #1
D N
U P
U P
AREA PLAN LEGEND
AREA NOT IN CONTRACT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Spinklered
PLAN NORTH
B
IM
/V
IS
N
B e h a v io ra l H e a lt h
C lin ic R e n o v a ti o n /B
H C lin ic
R e n o v a ti o n .r v t
/1
/2
:4
:4
A
M
THIRD FLOOR PHASING PLAN
MK EM
BID DOCUMENTS 589A4-19-103
1-GC102
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
5/13/2021
Fully Sprinklered15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
3/32" = 1'-0"
LEVEL 03 - PHASING PLAN
PH 1 PH 2
RCP DEMO NOTES
RCP DEMO LEGEND
RCP DEMO KEY NOTES
RCP NOTES
RCP LEGEND
1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT
OF ANY DIMENSIONAL DISCREPANCIES
DISCOVERED DURING CONSTRUCTION.
2. REFER TO ELECTRICAL DRAWINGS FOR MORE
INFORMATION.
AREA NOT IN CONTRACT
EXISTING WALL AND ASSOCIATED COMPONENTS
SHALL BE REMOVED - REFER TO DEMOLITION
KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC
CONDITIONS.
EXISTING DOOR, FRAME, HARDWARE AND
ASSOCIATED COMPONENTS SHALL BE REMOVED
-REFER TO DEMOLITION KEYNOTES FOR
ADDITIONAL DETAILS AT SPECIFIC CONDITIONS
EXISTING WALL SHALL REMAIN
EXISTING DOOR, FRAME AND HARDWARE
SHALL REMAIN
1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT
OF ANY DIMENSIONAL DISCREPANCIES
DISCOVERED DURING CONSTRUCTION.
2. REFER TO ELECTRICAL DRAWINGS FOR LOCATION
OF EMERGENCY LIGHTING.
3. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS
WHERE REQUIRED TO ACCESS ABOVE CEILING
EQUIPMENT. (SEE SPECS)
4. REFER TO FINISH DRAWINGS FOR CEILING GRID
AND PANEL TYPE AND SIZE.
5. ALL PARTITION WALLS SHALL EXTEND TO
UNDERSIDE OF DECK ABOVE U.N.O.
24" X 24" ACOUSTICAL CEILING
PANEL AND GRID
L
2.8
3.7
4.6
5.5
6.3
K J H G
7.2
ELEV ELEV ELEV
STORAGE
A157
CORR
SCAN
DRESSING
ELECT CLOSET
NOT KNOWN
SURG. WAITING
STORAGE
IT CLOSET
NURSE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .