This document provides details for a federal contract solicitation to renovate a behavioral health clinic and outpatient area at a Veterans Affairs medical center. The scope of work involves renovating approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor, including demolition and construction of clinical spaces, offices, public areas, and building systems. The project will be conducted in multiple phases to minimize disruption to patients. The estimated value is between $2-5 million. As a Service-Disabled Veteran-Owned Small Business set-aside, the solicitation will be open to SDVOSBs. The North American Industry Classification code is 236220. The contract duration is 800 calendar days from notice to proceed. Proposals are due around July 9, 2021 and the solicitation package will be available around June 1, 2021.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING LIST

VICINITY MAP

PROJECT TEAMBUILDING SUMMARYGENERAL NOTES

1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE

LOCATION. THESE DRAWINGS ARE A COMPOSITE SET OF CONTRACT

DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GENERAL

CONTRACTOR AND ALL SUBCONTRACTORS SHALL REVIEW ALL DRAWINGS AND

SPECIFICATIONS.

2. IT IS HIGHLY RECOMMENDED THAT THE GENERAL CONTRACTOR ATTEND THE

PRE-BID MEETING TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING

PERFORMED BEFORE SUBMITTING COST QUOTATIONS FOR WORK.

3. NOTIFY THE COTR PROMPTLY OF ANY ERRORS, OMISSIONS,

INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT

DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A

RESOLUTION CAN BE PROVIDED PRIOR TO CONTINUING WITH WORK.

4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM

THE ARCHITECT.

5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING

FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE

EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND

SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER,

THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL

CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING

SUCH PERMITS AND CERTIFICATES AND SHALL FURNISH COPIES OF PERMITS,

INSPECTIONS, AND CERTIFICATES TO THE OWNER.

6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE

DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE

GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT

BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION

THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-

REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL

CONDITION AT THE CONTRACTOR'S EXPENSE.

7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM

THE JOB SITE ON A DAILY BASIS.

8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE

SUBMITTED TO THE COTR AND ARCHITECT IN WRITING AND WILL BE

CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE

ADVANTAGEOUS TO THE OWNER WITH RESPECT TO DELIVERY DATE, QUALITY,

AND/OR COST. SUBSTITUTION REQUESTS MUST BE MADE PRIOR TO BID.

9. THE MEANS AND METHODS OF CONSTRUCTION, TEMPORARY STRUCTURES

AND FACILITIES ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE

ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S

MEANS AND METHODS, TEMPORARY STRUCTURES OR FACILITIES.

10. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR DEMOLISHING AND

REMOVING EXISTING CONSTRUCTION ONLY TO THE EXTENT REQUIRED BY NEW

CONSTRUCTION AND AS INDICATED. USE METHODS REQUIRED TO COMPLETE

THE WORK WITHIN LIMITATIONS OF GOVERNING REGULATIONS.

11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE

GENERAL CONTRACTOR. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE

FOR MEETING OSHA & NFPA REGULATIONS DURING CONSTRUCTION.

12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND

PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM

INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GENERAL

CONTRACTOR SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR

STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED

TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED

TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL

BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.

PROJECT INFORMATION

PROJECT NAME: RENOVATE BEHAVIORAL HEALTH CLINIC

PROJECT NUMBER: 589A4-19-103

PROJECT LOCATION: 800 HOSPITAL DRIVE, COLUMBIA, MO 65201

PROJECT PURPOSE/USE: PHASE 1:THE PROJECT WILL RENOVATE APPROXIMATELY 5,089 SQUARE FOOT ON THE FOURTH FLOOR OF VA TRUMAN MEMORIAL VETERANS BUILDING IN COLUMBIA, MISSOURI.

THIS WILL INCLUDE PROCEDURE ROOMS, PAIN EXAM ROOMS, PM&R EXAM ROOMS, NURSE WORK

ROOMS, MSA CHECKIN, SWAMP ROOMS, EMG/SCI ROOM, PAIN BH, AND PAIN PHARM ROOMS.

PHASE 2-4: THE PROJECT WILL RENOVATE APPROXIMATELY 9,706 SQUARE FOOT OF STATE-OF-THE-ART

OUT-PATIENT BEHAVIORAL HEALTH CLINIC LOCATED ON THE SECOND FLOOR OF VA TRUMAN

MEMORIAL VETERANS BUILDING IN COLUMBIA, MISSOURI. THIS WILL INCLUDE GROUP ROOMS,

ADMINISTRATIVE OFFICES, CLINICAL OFFICES WHICH DOUBLE AS COUNSELING ROOMS, PUBLIC

RESTROOMS, A CENTRAL CHECK-IN/WAITING ROOM AND A STAFF BREAK ROOM.

VA LEADERSHIP SIGNATURES

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

EE

ES

S

OF

M

R C

D

T

T T

II

N

U A

A A

V

RAP

M

N

T

T

OF

E E

D

R S

I

FA

A

N T

S R

F

AEE

Fully Sprinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:4

:5

A

M

SHEET INDEX & GENERAL INFORMATION

RCO EM

Columbia, Missouri

5/13/2021

STATION: Columbia, Missouri

BUILDING NUMBER: 1

1-GI100

589A4-19-103

Columbia Harry S. Truman Memorial Veterans Hospital

BID DOCUMENTS Columbia Harry S. Truman

Memorial Veterans Hospital

BID DOCUMENTS

5/13/2021

PROJECT LOCATION: 800 HOSPITAL DRIVE, COLUMBIA, MO

65201

SHEET

NUMBER SHEET TITLE

1-MD201 LEVEL 02- VENTILATION DEMOLITION

1-MD202 LEVEL 03 - VENTILATION DEMOLITION

1-MD203 LEVEL 04 - VENTILATION DEMOLITION

1-MH101 LEVEL 02 - VENTILATION

1-MH102 LEVEL 03 - VENTILATION

1-MH103 LEVEL 04 - VENTILATION

1-MH300 VENTILATION DETAILS

1-MH400 VENTILATION DIAGRAMS

1-MH500 VENTILATION SCHEDULES

1-MH501 VENTILATION SCHEDULES

1-E-000 ELECTRICAL COVER SHEET

1-ED101 LEVEL 02 - ELECTRICAL DEMOLITION

1-ED102 LEVEL 04 - ELECTRICAL DEMOLITION

1-E101 LEVEL 03 - ELECTRICAL

1-EL101 LEVEL 02 - ELECTRICAL LIGHTING

1-EL103 LEVEL 04 - ELECTRICAL LIGHTING

1-EP101 LEVEL 02 - ELECTRICAL POWER

1-EP102 LEVEL 04 - ELECTRICAL POWER

1-FA101 LEVEL 02 - FIRE ALARM

1-FA102 LEVEL 04 - FIRE ALARM

1-E-300 ELECTRICAL DETAILS

1-E-500 ELECTRICAL SCHEDULES

1-E-501 ELECTRICAL SCHEDULES

1-ET-000 TELECOMMUNICATIONS COVERSHEET

1-TD101 LEVEL 02 - TELECOMMUNICATIONS DEMOLITION

1-TD102 LEVEL 04 -TELECOMMUNICATIONS DEMOLITION

1-ET101 LEVEL 01 - TELECOMMUNICATIONS

1-ET102 LEVEL 02 - TELECOMMUNICATIONS

1-ET103 LEVEL 03 - TELECOMMUNICATIONS

1-ET104 LEVEL 04 - TELECOMMUNICATIONS

1-ET201 ENLARGED PLANS - TELECOMMUNICATIONS

1-T-300 TELECOMMUNICATIONS DETAILS

1-T-400 TELECOMMUNICATIONS DIAGRAMS

1-T-500 TELECOMMUNICATIONS SCHEDULES

SHEET

NUMBER SHEET TITLE

1-AE706 CEILING DETAILS SUSPENDED GYPSUM

1-AE707 SECOND FLOOR WINDOW, DOOR & STAIR DETAILS

1-AF101 SECOND FLOOR DOOR & WINDOW SCHEDULES

1-AF102 FOURTH FLOOR DOOR SCHEDULE & DETAILS

1-AF103 SECOND FLOOR FINISH PLAN & SCHEDULES

1-AF104 FOURTH FLOOR FINISH PLAN & SCHEDULES

1-AF105 SECOND FLOOR WALL TYPES

1-AF106 FOURTH FLOOR WALL TYPES

1-AW101 SECOND AND FOURTH FLOOR SIGNAGE PLAN

1-AW102 SIGNAGE PLAN DETAILS

1-AW103 SIGNAGE PLAN DETAILS

1-FX000 FIRE PROTECTION COVERSHEET

1-FD101 LEVEL 02 - FIRE PROTECTION DEMOLITION

1- FD102 LEVEL 04 - FIRE PROTECTION DEMOLITION

1-FX101 LEVEL 02 - FIRE PROTECTION

1- FX102 LEVEL 04 - FIRE PROTECTION

1-P-000 PLUMBING COVER SHEET

1-PD100 PIPE BASEMENT - PLUMBING DEMOLITION

1-PD101 LEVEL 01 - PLUMBING DEMOLITION

1-PD102 LEVEL 02 - PLUMBING DEMOLITION

1- PD103 LEVEL 03 - PLUMBING DEMOLITION

1- PD104 LEVEL 04 - PLUMBING DEMOLITION

1-PL100 BASEMENT-PLUMBING

1-PL101 LEVEL 01 - PLUMBING

1-PL102 LEVEL 02 - PLUMBING

1- PL103 LEVEL 03 - PLUMBING

1- PL104 LEVEL 04 - PLUMBING

1- P-300 PLUMBING DETAILS

1- P-400 PLUMBING RISERS

1- P-401 PLUMBING RESTROOM RISER

1-MP000 PIPING COVERSHEET

1-MD101 LEVEL 02 - MECHANICAL PIPING DEMOLITION

1-MD102 LEVEL 03 - MECHANICAL PIPING DEMOLITION

1-MD103 LEVEL 04 - MECHANICAL PIPING DEMOLITION

1-MP101 LEVEL 02 - MECHANICAL PIPING

1-MP102 LEVEL 03 - MECHANICAL PIPING

1-MP103 LEVEL 04 - MECHANICAL PIPING

1-MP300 MECHANICAL PIPING DETAILS

1-MP400 MECHANICAL PIPING DIAGRAMS

1-MH000 VENTILATION COVERSHEET

SHEET

NUMBER SHEET TITLE

1-GI100 SHEET INDEX & GENERAL INFORMATION

1-GI101 BUILDING CODE

1-GI102 ABBREVIATIONS & SYMBOLS

1-GI103 SECOND FLOOR LIFE SAFETY PLAN

1-GI104 FOURTH FLOOR LIFE SAFETY PLAN

1-GC101 SECOND & FOURTH FLOOR PHASING & INTERIM LIFE SAFETY PLANS

1-GC102 THIRD FLOOR PHASING PLAN

1-AD101 FIRST FLOOR RCP DEMOLITION PLAN & REFLECTED CEILING PLAN

1-AD102 SECOND FLOOR RCP DEMOLITION PLAN

1-AD103 SECOND FLOOR DEMOLITION PLAN

1-AD104 THIRD FLOOR RCP DEMOLITION PLAN & REFLECTED CEILING PLAN

1-AD105 FOURTH FLOOR RCP DEMOLITION PLAN

1-AD106 FOURTH FLOOR DEMOLITION PLAN

1-AE101 OVERALL SECOND FLOOR PLAN

1-AE102 ENLARGED SECOND FLOOR PLAN

1-AE103 OVERALL FOURTH FLOOR PLAN

1-AE104 ENLARGED FOURTH FLOOR PLAN

1-AE105 SECOND FLOOR DIMENSION PLAN

1-AE106 FOURTH FLOOR DIMENSION PLAN

1-AE107 SECOND FLOOR REFLECTED CEILING PLAN

1-AE108 FOURTH FLOOR REFLECTED CEILING PLAN

1-AE109A SECOND FLOOR EQUIPMENT PLAN

1-AE109B ENLARGED SECOND FLOOR TMS ROOM EQUIPMENT PLAN &

ELEVATIONS

1-AE110A FOURTH FLOOR EQUIPMENT PLAN

1-AE110B FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS

1-AE110C FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS

1-AE110D FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS

1-AE110E FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS

1-AE110F FOURTH FLOOR EQUIPMENT PLAN INTERIOR ELEVATIONS

1-AE401 SECOND FLOOR ENLARGED TOILET PLANS AND ELEVATIONS

1-AE402 SECOND FLOOR ENLARGED TOILET PLANS AND ELEVATIONS

1-AE403 FOURTH FLOOR ENLARGED TOILET PLANS AND ELEVATIONS

1-AE501 SECOND FLOOR MILLWORK PLAN & ELEVATIONS

1-AE502 FOURTH FLOOR MILLWORK PLAN & ELEVATIONS

1-AE503 SECOND FLOOR MILLWORK SECTIONS

1-AE504 FOURTH FLOOR MILLWORK ELEVATIONS & SECTIONS

1-AE702 MISCELLANEOUS DETAILS

1-AE703 SECOND FLOOR CEILING DETAILS

1-AE704 FOURTH FLOOR CEILING DETAILS

1-AE705 METAL STUD DETAILS

ARCHITECT:

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX

Rebecca Olson, AIA, ACHA Rebecca.olson@romanykconsulting.com

855-424-3838 ext.302 602-430-1265 cell

MECHANICAL ENGINEER:

IMEG

15 Sunnen Drive Suite 104 St. Lois, MO

Scott Przybysz Scott.R.Przybysz@imegcorp.com

314-951-2535

ELECTRICAL ENGINEER:

IMEG

15 Sunnen Drive Suite 104 St. Louis, MO

Mark T. Harris marc.t.harris@imegcorp.com

314-951-2509 314-249-8634

PLUMBING ENGINEER:

IMEG

15 Sunnen Drive Suite 104 St.Louis, MO

Scott Przybysz Scott.R.Przybysz@imegcorp.com

314-951-2535

OWNER:

Department of Veteran Affairs Harry S. Truman Memorial Veterans' Hospital 800 Hospital Drive, Columbia, MO 65201

Jeanette Mathena Jeanette.Mathena@va.gov

Jason Bavlnka jason.bavlnka@va.gov

TECHNOLOGY:

IMEG

15 Sunnen Drive Suite 104 St.Louis, MO

Scott Thomas scott.b.thomas@imegcorp.com

FIRE PROTECTION:

IMEG

15 Sunnen Drive Suite 104 St.Louis, MO

Scott Przybysz Scott.R.Przybysz@imegcorp.com

314-951-2535

INTERIOR DESIGN:

OCULUS INC.

1 South Memorial Drive Suite 1500 St.Louis, MO

Carolyn Fava carolynf@oculusinc.com

314-450-5368

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

PROJECT NAME: RENOVATE BEHAVIORAL HEALTH CLINIC

PROJECT NUMBER: 589A4-19-103

Revisions: Date:

Revision 1 Date 1

NOTE: THESE DRAWINGS DO NOT

INCLUDE IBC BUILDING CODE

INFORMATION

CODE NOTES - 2ND FLOOR

1. DRAWING PURPOSE : NFPA CODE COMPLIANCE

2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:

A. 2018 NFPA 101 LIFE SAFETY CODE

a. CHAPTER 4 - GENERAL

b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS

c. CHAPTER 7 - MEANS OF EGRESS

d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY

3. OWNER:

HARRY S. TRUMAN MEMORIAL HOSPITAL

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

PH (573) 814-6000

4. ARCHITECT:

ROMANYK CONSULTING

3308 PRESTON ROAD

SUITE 350-164

PLANO, TEXAS

5. ARCHITECT SEAL: SEE STAMP IN TITLEBLOCK

6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT

7. INSPECTION: JCHO; CITY OF COLUMBIA

8. OCCUPANCY GROUP TYPE:

a. OCCUPANCY 1/ BUILDING 1/ 2ND FLOOR: EXISTING HEALTHCARE OCCUPANCY

9. CONSTRUCTION TYPE:

CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)

10. BUILDING 1 - OCCUPANCY 1 GROSS FLOOR AREAS - 2ND FLOOR AREA ACTUAL: 63,736 SF (TOTAL FLOOR)

9,706 SF (AREA OF WORK)

11. HEIGHT & AREA LIMITATIONS:

ALLOWABLE AREA: UNLIMITED

HEALTH CARE OCCUPANCY:

ALLOWABLE HEIGHT/ 4 OR MORE

STORIES

ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES

12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):

CONSTRUCTION TYPE II (222)

HEALTHCARE

OCCUPANCY

BEARING WALLS:

A. EXTERIOR 2 HR

B. INTERIOR 2 HR

C. INT/EXT (ROOF ONLY) 1 HR

NON-BEARING WALLS:

A. EXTERIOR 0 HR

B. INTERIOR NON-COMBUSTIBLE

COLUMNS:

A. SUPPORT FLOORS 2 HR

B. SUPPORT ROOF ONLY 1 HR

BEAMS/GIRDER/TRUSSES:

A. EXTERIOR: 2 HR

B. INTERIOR: 1 HR

FLOOR CONSTRUCTION: 2 HR

ROOF CONSTRUCTION: 1 HR

13. ACTIVE FIRE SAFETY FEATURES:

a. AUTOMATIC SUPPRESSION SYSTEMS:

• SPRINKLER SYSTEM (FULLY SPRINKLED)

• AUTOMATIC AIR-HANDLING SHUT-DOWN

b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP

c. GENERATOR POWERED EMERGENCY LIGHTING, GENERATOR POWERED

d. EXIT LIGHTING.

e. PORTABLE EXTINGUISHERS

f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND MISC

AREAS AS REQ'D (ALSO IN SOME DUCTS)

14. WATER SUPPLY: CITY OF COLUMBIA

15. SPRINKLERS: FULLY SPRINKLERED

16. TOTAL OCCUPANTS

TABLE 7.3.1.2 OCCUPANT LOAD FACTOR

USE (FT2 /PERSON)

HEALTHCARE USE

INPATIENT TREATMENT DEPARTMENTS 240

SLEEPING DEPARTMENTS 120

AMBULATORY HEALTH CARE 150

OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)

BUILDING 1

2ND FLOOR (AREA OF WORK): 9,706/240 = 40" (MEANS OF EGRESS WIDTH CANNOT BE LOWER THAN THIS)

17. MEANS OF EGRESS: TWO MEANS OF EGRESS, AS A MINIMUM REQUIRED (4.5.3.1).

ACTUAL MEANS OF EGRESS (2ND FLOOR): 2 MEANS OF EGRESS

18. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN

32" IN CLEAR WIDTH (7.2.1.2.3.2). DOOR OPENINGS IN PROJECT ARE 42".

19. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET (TABLE A.7.6)

ACTUAL PROJECT DEAD END CORRIDOR (2ND FLOOR) = 24 FEET.

20. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,

SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)

21. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED

FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN

44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).

ACTUAL CORRIDOR WIDTH (2ND FLOOR): 72 INCHES (MIN.)

22. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON

EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.

23. TRAVEL DISTANCE TO EXITS= THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). ACTUAL TRAVEL DISTANCE 147 FEET (2ND FLOOR).

24. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)

TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT

(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)

EXISTING HEALTH CARE NO REQUIREMENT 30 FEET 200 FEET

CODE NOTES - 4TH FLOOR

1. DRAWING PURPOSE : NFPA CODE COMPLIANCE

2. FACILITY REVIEWED FOR COMPLIANCE WITH THE FOLLOWING CODES:

A. 2018 NFPA 101 LIFE SAFETY CODE

a. CHAPTER 4 - GENERAL

b. CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD CONTENTS

c. CHAPTER 7 - MEANS OF EGRESS

d. CHAPTER 19 - EXISTING HEALTHCARE OCCUPANCY

3. OWNER:

HARRY S. TRUMAN MEMORIAL HOSPITAL

800 HOSPITAL DRIVE

COLUMBIA, MO 65201

PH (573) 814-6000

4. ARCHITECT:

ROMANYK CONSULTING

3308 PRESTON ROAD

SUITE 350-164

PLANO, TEXAS

5. ARCHITECT SEAL: SEE STAMP AREA IN TITLEBLOCK

6. FIRE SERVICE: CITY OF COLUMBIA FIRE DEPARTMENT

7. INSPECTION: TJC; CITY OF COLUMBIA

8. OCCUPANCY GROUP TYPE: OCCUPANCY 1/ BUILDING 1/ 4TH FLOOR: EXISTING HEALTHCARE OCCUPANCY

9. CONSTRUCTION TYPE: CONSTRUCTION TYPE II - NFPA TYPE 222, (TABLE 19.1.6.1)

10. BUILDING GROSS FLOOR AREA: 4TH FLOOR AREA: 23,409 SF (TOTAL FLOOR AREA)

5,089 SF (AREA OF WORK)

11. HEIGHT & AREA LIMITATIONS:

ALLOWABLE AREA: UNLIMITED

HEALTH CARE OCCUPANCY:

ALLOWABLE HEIGHT/ 4 OR MORE

STORIES

ACTUAL HEIGHT/STORIES 7 OCCUPIABLE STORIES

12. MINIMUM CONSTRUCTION REQUIREMENTS (A.8.2.1.2):

HEALTHCARE

OCCUPANCY

CONSTRUCTION TYPE II (222)

BEARING WALLS:

A. EXTERIOR 2 HR

B. INTERIOR 2 HR

C. INT/EXT (ROOF ONLY) 1 HR

NON-BEARING WALLS:

A. EXTERIOR 0 HR

B. INTERIOR NON-COMBUSTIBLE

COLUMNS:

A. SUPPORT FLOORS 2 HR

B. SUPPORT ROOF ONLY 1 HR

BEAMS/GIRDER/TRUSSES:

A. EXTERIOR: 2 HR

B. INTERIOR: 1 HR

FLOOR CONSTRUCTION: 2 HR

ROOF CONSTRUCTION: 1 HR

13. ACTIVE FIRE SAFETY FEATURES:

a. AUTOMATIC SUPPRESSION SYSTEMS:

• SPRINKLER SYSTEM (FULLY SPRINKLED)

• AUTOMATIC AIR-HANDLING SHUT-DOWN

b. FIRE ALARM SYSTEM - SIMPLEX, ADDRESSABLE, AUTO DIAL-UP

c. GENERATOR POWERED EMERGENCY LIGHTING

d. EXIT LIGHTING.

e. PORTABLE EXTINGUISHERS

f. SMOKE DETECTORS AT ALL CORRIDORS, ALL SMOKE DOORS AND

AREAS AS REQ'D.

14. WATER SUPPLY: CITY OF COLUMBIA

15. SPRINKLERS: FULLY SPRINKLERED

16. TOTAL OCCUPANTS

TABLE 7.3.1.2 OCCUPANT LOAD FACTOR

USE (FT2 /PERSON)

HEALTHCARE USE

INPATIENT TREATMENT DEPARTMENTS 240

SLEEPING DEPARTMENTS 120

AMBULATORY HEALTH CARE 150

OCCUPANT LOAD = FLOOR AREA/OCCUPANT LOAD FACTOR (TABLE 7.3.1.2)

BUILDING 1

4TH FLOOR (AREA OF WORK): 5,089/150 = 34 TOTAL OCCUPANTS

17. EXIT WIDTH: TABLE 7.3.3.1 CAPACITY FACTORS

EXIT WIDTH STAIRS: 34 OCCUPANTS X.3 INCHES = 10.2" (SCOPE OF WORK)

EXIT WIDTH LEVEL COMPONENTS: 34 X .2 INCHES = 6.8" (SCOPE OF WORK)

18. MEANS OF EGRESS: MINIMUM REQUIRED TWO MEANS OF EGRESS (4.5.3.1)

ACTUAL MEANS OF EGRESS (4TH FLOOR): 2 MEANS OF EGRESS

19. DOOR OPENINGS IN MEANS OF EGRESS: SHALL BE NO LESS THAN 32" IN CLEAR WIDTH (7.2.1.2.3.2).

DOOR OPENINGS IN PROJECT ARE 42" MINIMUM.

20. DEAD END CORRIDORS: DEAD END CORRIDORS SHALL NOT EXCEED 30 FEET. (TABLE A.7.6)

ACTUAL PROJECT DEAD END CORRIDOR (4TH FLOOR) = 12'

21. TABLE 7.3.3.1 CAPACITY FACTORS: STAIRWAY (WIDTH/PERSON), HEALTHCARE,

SPRINKLERED = .2 INCHES (LEVEL COMPONENTS AND RAMPS)

22. CORRIDOR WIDTH: AISLES, CORRIDORS, AND RAMPS IN ADJUNCT AREAS NOT INTENDED

FOR THE HOUSING, TREATMENT, OR USE OF INPATIENTS SHALL BE NOT LESS THAN

44 INCHES IN CLEAR AND UNOBSTRUCTED WIDTH (19.2.3.4).

ACTUAL CORRIDOR WIDTH (4TH FLOOR): 72"

23. NUMBER OF EXITS FOR EACH STORY: NOT LESS THAN TWO EXITS SHALL BE PROVIDED ON

EACH STORY 19.2.4.2). ACTUAL PROJECT EXITS = 2.

24. TRAVEL DISTANCE TO EXITS: THE TRAVEL DISTANCE BETWEEN ANY POINT IN A ROOM AND

AN EXIT SHALL NOT EXCEED 150 FEET(19.2.6.2.1). 19.2.6.2.2

THE MAXIMUM TRAVEL DISTANCE SPECIFIED IN 19.2.6.2.1

SHALL BE PERMITTED TO INCREASE BY 50 FEET IN BUILDINGS

PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER

SYSTEM IN ACCORDANCE WITH 19.3.5.7.

ACTUAL MAX TRAVEL DISTANCE: 173'- 6" (4TH FLOOR).

25. TABLE A.7.6 COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (BY OCCUPANCY)

TYPE OF OCCUPANCY COMMON PATH LIMIT DEAD END LIMIT TRAVEL DISTANCE LIMIT

(SPRINKLERED) (SPRINKLERED) (SPRINKLERED)

EXISTING NO REQUIREMENT 30 FEET 200 FEET

NOTE: THESE DRAWINGS DO NOT

INCLUDE IBC BUILDING CODE

INFORMATION

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:4

:5

A

M

BUILDING CODE

RCO EM

BID DOCUMENTS 589A4-19-103

1-GI101

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02Revisions: Date:

1i

0 GRID / COLUMN LINE DESIGNATOR

EQUIPMENT NUMBER

DOOR NUMBER

Ga5xFB1

WALL TYPE

WINDOW TYPE

ROOM NAME

ROOM NAME / NUMBER

REVISION TAG

NORTH

NORTH ARROW WITH TRUE

NORTH INDICATION

EGRESS ROUTE ID AND

SECTION LENGTH

ROOM

ROOM OCCUPANCY

150 SF

EGRESS : EGRESS ID

Egress Length

ROOM OCCUPANCY & AREA

ELEVATION NUMBER

SECTION

INTERIOR ELEVATION

ENLARGEMENT,

DETAIL

SPOT ELEVATION

Name Elevation

FLOOR LEVEL &

NAME

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

SHEET KEYNOTE

A101

SIM

EXTERIOR ELEVATION

A-101

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

A101

A101

ANNOTATION DRAWING SYMBOLS

INDEX OF DRAWINGS

202-A101

DISCIPLINE:

G - GENERAL

A - ARCHITECTURE

I - INTERIORS

F- FIRE PROTECTION

P - PLUMBING

M - MECHANICAL

E - ELECTRICAL

T - TELECOM

V - VENTILATION

SHEET TYPE

DESIGNATOR

BUILDING NUMBER

SHEET NUMBER

WITHIN SERIES

ARCHITECTURAL SYMBOLS

LEGEND

CONCRETE/ PRECAST

CONCRETE

SOIL

SAND, EIFS FINISH COAT,

OR CEMENT PLASTER

BRICK

CMU

STONE

FIBERGLASS BATT

INSULATION

EXPANDED POLYSTYRENE

RIGID INSULATION

EXTRUDED POLYSTYRENE

RIGID INSULATION

POLYISOCYANURATE RIGID

INSULATION

GYPSUM BOARD

EXTERIOR GYPSUM

SHEATHING

EXTERIOR CEMENT

BOARD

COATED GLASS MAT

WATER RESISTANT

GYP BD

PLYWOOD

COVER BOARD

MATERIALS

CEILING SYMBOLS

MECHANICAL SUPPLY DIFFUSER

MECHANICAL RETURN GRILLE

MECHANICAL EXHAUST GRILLE

24" X 24" ACOUSTICAL CEILING

PANEL AND GRID

GYPSUM BOARD CEILING OR

SOFFIT

2' x 2' LED FLUORESCENT

FIXTURE - EMERGENCY NIGHT

LIGHT

RECESSED CAN DOWNLIGHT

CEILING ELEVATION A.F.F.X'-X"

EXIT SIGN

LED LIGHT

1' x 4' LED FLUORESCENT

FIXTURE

2' x 4' LED FLUORESCENT

FIXTURE

INDUSTRIAL LUMINAIRE

EMERGENCY LIGHT

2' x 2' LED FLUORESCENT

FIXTURE

OC

NURSE CALL DOME LIGHT WALL

MOUNTED

A

FIRE ALARM AUDIO/VISUAL

NOTIFICATION DEVICE-CEILING

MOUNTED.

CAM

LS

OCCUPANCY SENSOR

A1 A3

DAYLIGHT LEVEL SENSOR

CLOSED CIRCUIT CAMERA (CCTV)

CEILING MOUNTED

N

S SPEAKER

CLOSED CIRCUIT CAMERA (CCTV)CAM

VC VACANCY SENSOR

WAP CEILING INFORMATION OUTLET

FIRE ALARM VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

V1

WALL CONTROL STATIONSW

NURSE CALL STATIONN

SMOKE,FIRE/SMOKE

DAMPER CONTROLLER

ARD

FIRE ALARM MANUAL PULL

STATION

F

FIRE ALARM SMOKE,

SMOKE DAMPER

SD

SD FIRE ALARM DUCT SMOKE

DETECTOR

D DIMMER LED

A FIRE ALARM AUDIO/VISUAL

NOTIFICATION DEVICE- WALL

MOUNTED.

A1 A3

S SWITCH

{LD}

{LS}

LIGHT DIMMER

LIGHT SENSOR

ARCHITECTURAL DRAWING ABBREVIATIONS

A ---------------------

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

ACC ACCESSIBLE

ACS AUTOMATIC CONTROL SYSTEM

ACS DR ACCESS DOOR

ACS PNL ACCESS PANEL

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

ADMIN ADMINISTRATION

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGGR AGGREGATE

AHU AIR HANDLING UNIT

AIB AIR INFILTRATION BARRIER

ALT ALTERNATE

ALG ALUMINUM AND GLASS

AL ALUMINUM

ALUM ALUMINUM

ANOD ANODIZE

APC ACOUSTICAL PANEL CEILING

APPROX APPROXIMATE

AR AS REQUIRED

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

ASSY ASSEMBLY

ATC ACOUSTICAL TILE CEILING

AVG AVERAGE

AW ARCHITECTURAL WOODWORK

AWT ACOUSTICAL WALL TREATMENT

B ---------------------

B LABEL CLASS B DOOR

BALC BALCONY

BB BASEBOARD

BC BOOKCASE

BD BOARD

BDRY BOUNDARY

BFF BELOW FINISH FLOOR

BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BN BULLNOSE

BOS BOTTOM OF STEEL

BOT BOTTOM

BP BUILDING PAPER

BRKT BRACKET

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

C ---------------------

C CONC CAST CONCRETE

C LABEL CLASS C DOOR

CAB CABINET

CATW CATWALK

CAV CAVITY

CBB CEMENTITIOUS (BACKER) BOARD

CD CONSTRUCTION DOCUMENTS

CDW CHILLED DRINKING WATER

CEM PLAS CEMENT PLASTER

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CFLG COUNTERFLASHING

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL FRAMING

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CI CAST IRON

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG DIFF CEILING DIFFUSER

CLG HT CEILING HEIGHT

CLL COLUMN LINE

CLO CLOSET

CLR COLOR

CLRM CLASSROOM

CMU CONCRETE MASONRY UNIT

CNDS CONDENSATE

CDR CARD READER

CO CLEANOUT

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONC FLR CONCRETE FLOOR

CONF CONFERENCE

CONT CONTINUE

COORD COORDINATE

CORR CORRIDOR

CP CONCRETE PIPE

CPT CARPET

CR CONTROL ROOM

CS CAST STONE

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTR CENTER

CU FT CUBIC FEET

CW CASEMENT WINDOW

D ---------------------

D DEPTH

D LABEL CLASS D DOOR

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

E ---------------------

E LABEL CLASS E DOOR

EA EACH

EF EACH FACE

EIFS EXTERIOR INSULATION AND FINISH SYSTEM

EJ EXPANSION JOINT

ES EACH SIDE

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

ELEV EQ ELEVATOR EQUIPMENT

ENTR ENTRANCE

EPS EXPANDED POLYSTYRENE BOARD (INSULATION)

EQ EQUAL

EWC ELECTRIC WATER COOLER

EXP EXPOSED

EXT EXTERIOR

EXT EXTINGUISHER

EXT GR EXTERIOR GRADE

F ---------------------

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FAS BD FASCIA BOARD

FC BRK FACE BRICK

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FF INSUL FOIL BACKED INSULATION

FGL FIBERGLASS

FH FIRE HOSE

FHP FULL HEIGHT PARTITION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FM FACTORY MUTUAL

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FR FIRE RESISTANT

FRG FIBER REINFORCED GYPSUM

FRMG FRAMING

FRP FIBERGLASS REINFORCED PLASTIC

FRTW FIRE RETARDANT TREATED WOOD

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET

FTG FOOTING

FWC FABRIC WALLCOVERING

G ---------------------

G NATURAL GAS

GALV GALVANIZED

GB GRAB BAR

GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED INSTALLED BY GOVERNMENT

GFRG GLASS-FIBER-REINFORCED GYPSUM

GLZ GLAZING

GR FL GROUND FLOOR

GSF GROSS SQUARE FEET

GUT GUTTER

GYP BD GYPSUM BOARD

GYP PLAS GYPSUM PLASTER

H ---------------------

HAC HOUSE AID KEEPING CLOSET

HB HOSE BIBB

HDPE HIGH DENSITY POLYETHYLENE

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HMD HOLLOW METAL DOOR

HMF HOLLOW METAL FRAME

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION, AND AIR CONDITIONING

HYDR HYDRAULIC

I ---------------------

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

ISO ISOLATION

J ---------------------

JAN JANITOR

K ---------------------

KPD KEYPAD

KIT KITCHEN

KPL KICKPLATE

L ---------------------

LAM LAMINATE

LAV LAVATORY

LBR LUMBER

LBS POUND

LDG LANDING

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LIB LIBRARY

LIN LINEAR

LKR LOCKER

LOC LOCATION

LT LIGHT

LVDR LOUVER DOOR

LVR LOUVER

M ---------------------

MACH RM MACHINE ROOM

MATL MATERIAL

MAX MAXIMUM

MC MOISTURE CONTENT

MD METAL DECK

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MEMB MEMBRANE

MF MILL FINISH

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM, MINUTE

MIRR MIRROR

MISC MISCELLANEOUS

MLDG MOLDING (MOULDING)

MO MASONRY OPENING

MOD MODIFY

MB MOISTURE BARRIER

MTG MOUNTING

MTL METAL

MVBL MOVABLE

MWP MEMBRANE WATERPROOFING

N ---------------------

N NORTH

NA NOT APPLICABLE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NP NO PAINT

NRC NOISE REDUCTION COEFFICIENT

NTS NOT TO SCALE

O -------------------

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OFF OFFICE

OGL OBSCURE GLASS

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPQ OPAQUE

OWSJ OPEN WEB STEEL JOIST

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P --------------------

PA PUBLIC ADDRESS

PAR PARAPET

PAT PATTERN

PB PULL BOX

PBD PARTICLEBOARD

PCC PRECAST CONCRETE

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PH PHASE

PIL PILASTER

PL PROPERTY LINE

PL GL PLATE GLASS

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLG PILING

PLYWD PLYWOOD

PNL PANEL

PP PL PUSH/PULL PLATE

PR PAIR

PRCST PRECAST

PRKG PARKING

PS CONC PRESTRESSED CONCRETE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTDR PAPER TOWEL DISPENSER AND RECEPTACLE

PTN PARTITION

PWR POWER

Q --------------------

QT QUARRY TILE

QTY QUANTITY

R --------------------

RB RESILIENT BASE

RBM REINFORCED BRICK MASONRY

RBR RUBBER

RC REINFORCED CONCRETE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RDG INS RIGID INSULATION, SOLID

REC RECESSED

REC ROOM RECREATION ROOM

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

REST RESTROOM

RF RESILIENT FLOORING

RFG ROOFING

RH ROOF HATCH

RHR RIGHT HAND REVERSE

RL ROOF LEADER

RLG RAILING

RM ROOM

RO ROUGH OPENING

RSD ROLLING STEEL DOOR

RV ROOF VENT

RVL REVEAL

S --------------------

SB SPLASH BLOCK

SCHED SCHEDULE

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SFTWD SOFTWOOD

SGL SINGLE

SHT MTL FLASH SHEET METAL (FLASHING)

SHTHG SHEATHING

SHWR SHOWER

SHV SHELVING

SIM SIMILAR

SJ SCORED JOINT

SKLT SKYLIGHT

SLNT SEALANT

SMK SMOKE

SMLS SEAMLESS

SP EL SPOT ELEVATION

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SST STAINLESS STEEL

ST STAIRS

STD STANDARD

STL JST STEEL JOIST

STL RF DK STEEL ROOF DECK

STOR STORAGE

STR STRINGERS

STRB/HRN STROBE/HORN

SUB FL SUBFLOOR

SV SHEET VINYL

SW SIDEWALK

T --------------------

T TREAD

T/S TUB/SHOWER

TC TERRA COTTA

TD TRENCH DRAIN

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZZO

TFF TOP OF FINISH FLOOR

THK THICKNESS

TK BD TACKBOARD

TMPD GL TEMPERED GLASS

TN TRUE NORTH

TOF TOP OF FOOTING

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOPO TOPOGRAPHY

TOS TOP OF SLAB

TRANS TRANSOM

TRTD TREATED

TV TELEVISION

SEE OTHER DISCIPLINES FOR

ADDITIONAL ABREVIATIONS

NOTE: NOT ALL MAY BE USED

ARCHITECTURAL SYMBOLS

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:4

:5

A

M

ABBREVIATIONS & SYMBOLS

RCO EM

BID DOCUMENTS 589A4-19-103

1-GI102

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

A

A1

A1

A3

A1

A3

A3

A

A1

V1

A

A3

A1

A1

A1 A1

A1

F

UP

UP

FDFD

FD

FD

FEC

F E

C

F E

C

FEC

FEC

FEC

F E

C

FEC

F E

C

LIFE SAFETY NOTES

FEC

AREA PLAN LEGEND

BARRIER LEGEND

Na

N

N

M

M

L

L

2.82.8

3.73.7

4.64.6

5.55.5

6.36.3

K

K

J

J

H

H

G

G

F

F

7.27.2

8.38.3

9.19.1

CONTROLLED ACCESS

CONTROLLED ACCESS

CONTROLLED ACCESS

204 SF

A200

CLINIC

OFFICE

154 SF

A203

CLINIC

OFFICE

182 SF

A204

CLINIC

OFFICE

152 SF

A202

CLINIC

OFFICE

94 SF

A201B

OBSERVATION

63 SF

C2A02

CORRIDOR

197 SF

A201

PSYCH.

RES

183 SF

A206

PSYCH.

RES

24 SF

A206A

EXIST.

STRG

295 SF

C2A01

CORRIDOR

178 SF

A205

PSYCH.

RES

49 SF

A207

EXIST.

ELEC

368 SF

C2A04

CORRIDOR

154 SF

C2A03

CORRIDOR

169 SF

A208

TMS

ROOM

163 SF

A210

TMS

ROOM

64 SF

A212

EXIST.

SOC

WRK

63 SF

A213

EXIST.

SOC

WRK

143 SF

C2A05

CORRIDOR

112 SF

A209

CARE

COORDINATOR

111 SF

A211

CARE

COORDINATOR

74 SF

A214

STAFF

RESTROOM

72 SF

A215

HAC

308 SF

A217

EXIST. IT

173 SF

A221

WOMEN'S

185 SF

A222

MEN'S

96 SF

A216

EXIST.

ELEC.

CLO.

861 SF

C2A07

CORRIDOR

567 SF

C2A08

CORRIDOR

1235 SF

A226

GROUP

ROOM

WAITING

AREA

372 SF

A224

WAITING

398 SF

A223

WAITING

89 SF

A223B

WORK

AREA

64 SF

A223C

COPIER/PAPER

STORAGE

AREA

MAIL AREA

A223D

125 SF

A223A

CHECKOUT/CHECK

IN

307 SF

A219

GROUP

ROOM

320 SF

A218

GROUP

ROOM

515 SF

A220

GROUP

ROOM

TRAVEL DISTANCE: 91' - 4"

TRAVEL DISTANCE: 93' - 0"

STAIR #1

65 SF

VESTIBULE

A200A

COMPLIANCE NOTE

PER 7.5.1.6

EXIT ACCESS FROM ROOMS OR SPACES SHALL BE

PERMITTED TO BE THROUGH

ADJOINING OR INTERVENING ROOMS OR AREAS,

PROVIDED THAT SUCH ROOMS OR AREAS ARE

ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES,

AND RECEPTION ROOMS. CONSTRUCTED AS

REQUIRED FOR CORRIDORS SHALL NOT BE

CONSTRUED AS INTERVENING ROOMS.

SC1 SUITE (PATIENT

CARE NON-SLEEPING):

1,882 SF

98"

EXISTING

STAIRS #1

EXISTING BUILDING #1 - OCCUPANCY #1 - 2ND FLOOR = 63,705 SF

OCCUPANCY TYPE - HEALTHCARE

TYPE II (222) CONSTRUCTION

TOTAL OCCUPANTS 670

FULLY SPRINKLERED

3 3 4

22 21

2 2

SMOKE COMPARTMENT

12,212 SF

670/3 20.6" 46.5"

406/3

22.4"

EXISTING

STAIRS #2

670/8 25"

40.5"

SMOKE

COMPARTMENT

12,212 SF

COMPLIANCE NOTE

PER NFPA 19.3.7.9

DOOR OPENINGS IN SMOKE BARRIERS SHALL BE

PROTECTED USING ONE OF THE FOLLOWING

METHODS:

(1) SWINGING DOOR PROVIDING A CLEAR WIDTH OF

NOT LESS THAN 32 INCHES.

STAIR #2

COMPLIANCE NOTE

PER 7.5.1.6

EXIT ACCESS FROM ROOMS OR SPACES SHALL BE

PERMITTED TO BE THROUGH

ADJOINING OR INTERVENING ROOMS OR AREAS,

PROVIDED THAT SUCH ROOMS OR AREAS ARE

ACCESSORY TO THE AREA SERVED. FOYERS, LOBBIES,

AND RECEPTION ROOMS. CONSTRUCTED AS

REQUIRED FOR CORRIDORS SHALL NOT BE

CONSTRUED AS INTERVENING ROOMS.

COMPLIANCE NOTE

PER NFPA 19.2.3.4

ANY REQUIRED AISLE, CORRIDOR, OR RAMP SHALL BE

NOT LESS THAN 48 INCHES IN CLEAR WIDTH WHERE

SERVING AS MEANS OF EGRESS FROM PATIENT

SLEEPING ROOMS, UNLESS OTHERWISE PERMITTED BY

ONE OF THE FOLLOWING:

(4) PROJECTIONS INTO THE REQUIRED WIDTH SHALL

BE PERMITTED FOR WHEELED EQUIPMENT, PROVIDED

THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:

(C) THE WHEELED EQUIPMENT IS LIMITED TO THE

FOLLOWING:

I. EQUIPMENT IN USE AND CARTS IN USE

II. MEDICAL EMERGENCY EQUIPMENT NOT IN USE

III. PATIENT LIFT AND TRANSPORT EQUIPMENT

19.2.5.7.3.1 PATIENT CARE NON-SLEEPING SUITE

MEANS OF EGRESS.

(C) FOR SUITES REQUIRING TWO EXIT ACCESS DOORS,

ONE OF THE EXIT DOORS SHALL BE PERMITTED TO BE ONE

OF THE FOLLOWING:

(4) ANOTHER SUITE, PROVIDED THAT THE SEPARATION

BETWEEN THE SUITES COMPLIES WITH THE CORRIDOR

REQUIREMENTS OF 19.3.6.2 THROUGH 19.3.6.5

203 SF

CORRIDOR 7

C2A09

COMPLIANCE NOTE

PER NFPA TABLE A.7.6

TRAVEL DISTANCE LIMIT=200' FOR

EXISTING HEALTH CARE SPRINKLERED

BUILDINGS

TABLE A.7.6

COMMON PATH OF TRAVEL-NO

REQUIREMENT FOR EXISTING HEALTH

CARE SPRINKLERED BUILDINGS

T R

A V

E L D

IS

T

A N

C E

TEMPORARY CONSTRUCTION

BARRIER

T R

A V

E L D

IS

T

A N

C E

1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.

2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13

AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE

DETECTION SYSTEM.

3. WALL TYPES ARE DETAILED ON 1-AF105 AND INDICATED ON THE

DIMENSIONED FLOOR PLAN ON 1-AE109.

4. REFER TO THIS DRAWING FOR MEANS OF EGRESS.

5. REFER TO THIS DRAWING FOR DOOR CAPACITIES.

6. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE

MARSHAL.

7. ALL SMOKE BARRIERS/PARTITIONS & FIRE RATED WALLS/ASSEMBLY

SHALL BE PAINTED (IN RED LETTERS) W/APPROPRIATE LABEL &

RATING.

FIRE EXTINGUISHER CABINET

ILLUMINATED EXIT SIGN

A

FIRE ALARM AUDIO/VISUAL

NOTIFICATION DEVICE-CEILING

MOUNTED

A1 A3

FIRE ALARM VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

V1

A1

FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE-WALL MOUNTED

FIRE ALARM MANUAL PULL

STATION

F

AREA NOT IN CONTRACT

LEGEND

BUILDING & LIFE SAFETY REQUIREMENTS

DESCRIPTION

NEW

PARTITION KEY

NFPA

101-2015

OPENINGS DAMPERS

RATING RFRNC. TYPE RFRNC.

BUILDING SEPARATION:

FIRE BARRIER

(FIRE WALL IN IBC)

2 HR 90 MIN

OCCUPANCY/AREA SEPARATION

FIRE BARRIER

90 MIN

HORIZONTAL EXIT (& REFUGE AREA)

FIRE BARRIER

2 HR 90 MIN

VERT. OPG. (EXIT ENCLSR/SHAFT)

FIRE BARRIER

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES)1 HR

2 HR

60 MIN

90 MIN

HAZ./INCIDENTAL USE

FIRE BARRIER

45 MIN

HAZ./INCIDENTAL USE

SMOKE PARTITIONS (SPRINKLERED)

NR

SELF OR AUTO

CLOSING

SUBDIVIDING SPACES

SMOKE BARRIER (I-2 OCCUPANCY)

20 MIN

1/2

HR

1 HR

SUITE SEPARATION

SMOKE PARTITION

EXIT ACCESS CORRIDORS (I-2)

SMOKE PARTITIONS (SPRINKLERED)

NR

EXIT ACCESS CORRIDORS (B & AHC)

NON-RATED PARTITIONS

NR

VERT. OPG. (SHAFT)

FIRE BARRIER

60 MIN

[D]

1 HR

2 HR

60 MIN

90 MIN

EXIT PASSAGEWAY (HORIZ.)

FIRE BARRIER

8.7

NFPA 6.1.14.4.1

18.1.3.5.1 19.1.3.5.1

NFPA 7.2.A.3.1 (1)

NFPA 18.1.3.8/

19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1

NFPA 19.3.1.1

NFPA 8.6.2

8.6.5

NFPA 18.3.2.1.2

NFPA 8.4.1.1

19.3.2.1

NFPA 8.4.2 (3)

18.3.2.1.3 19.3.2.1.2

NFPA 8.5.2

18.3.7.3 19.3.7.3

NFPA 8.4.2

18.2.5.7.1.4 19.2.5.7.1.1

NFPA 8.4.2

18.3.6.2 19.3.6.2

21.3.6 39.3.6

NFPA 19.3.1.1

19.2.2.7 8.6.2 8.6.5(3) & 2

NFPA 7.2.6

19.2.2.7 18.2.2.7

NFPA 221

8.2.1.3

EXIST SOL.

CORE WD.

NFPA 7.2.1.4.1

7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4

8.3.4.2 TBL

18.4.4.7.2.2

7.1.3.2.9 (9)

NFPA 8.3.4.2 TBL

19.3.2.1.3,5

NFPA 8.3.4.2 TBL

8.5.4 18.3.7.8

NFPA 8.3.4.2 TBL

8.3.4.2 TBL

8.3.4.2 TBL

NFPA 8.3.4.2 TBL

8.3.4.2 8.4.3 19.3.2.1.4,3,5

8.4.3

8.4.3 18.3.6.4.1 19.3.6.4.1

N/A

FIRE

90 MIN

FIRE

90 MIN

VARIES

SMOKE

90 MIN

VARIES

VARIES

NONE

N/A

NOT

ALLOWED

NFPA 90

8.3.5.7 9.2.1

NFPA 8.3.5.7

9.2.1 7.2.4.3.5

N/A

8.5.5.2 18.3.7.3(2) 19.3.7.3(2)

8.6.4.5

N/A

N/A

8.4.4.1 8.4.6.2

8.4.4.1 8.4.6.2

8.4.4.1 8.4.6.2 18.3.6.4.1

N/A

WALL

RATING

RATED UL

ASSEMBLIES

2 HR

1 HR

1 HR

NR-

RESIST

SMK

NR

NR-

RESIST

SMK

NR

8.3

UL U412

UL U419

UL U412

UL U419

UL U412

UL U419

UL U412

UL U419

UL U415 (A)

UL U412

UL U419

UL U415 (A)

UL U412

UL U419

UL U412

UL U419

UL U415 (A)

NR

SELF OR AUTO

CLOSING

FIRE

90 MIN

FIRE

90 MIN

NOT

ALLOWED

UNLESS

SERVING

STAIR ONLY

NFPA 90

8.3.5.7 9.2.1

A

C

E

B

SECOND FLOOR KEY PLAN

AREA OF

WORK

TRAVEL

PATH

STARTING

LOCATION

TD = XX

TRAVEL DISTANCE

NO. OF OCC./

NO. OF EXITS

ACTUAL

EXIT

WIDTH

OCC.

LOAD

FACTOR

LIFE SAFETY SYMBOLS

10/1

2"

34"

1:50

NO. OCC. EXITING

(SMALLER ROOMS)

MAXIMUM OCCUPANCY

AREA

REQ'D. EXIT WIDTH

NO. OF OCC. EXITING FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER- 1 HOUR

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

SEE AF105 FOR WALL TYPE CONSTRUCTION

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:5

:4

A

M

SECOND FLOOR LIFE SAFETY PLAN

RCO EM

BID DOCUMENTS 589A4-19-103

1-GI103

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered

1/8" = 1'-0"

LEVEL 02 - LIFE SAFETY PLAN- PHASE 01

NORTH

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

FEC

AREA PLAN LEGEND

LIFE SAFETY NOTES

A1

A1

V1

A1

V1 V1

V1

V1

A

V1

V1

V1

V1

V1

A1

A1

FEC

F E

C

FEC

FEC

BARRIER LEGEND

AREA OF

WORK

FOURTH FLOOR KEY PLAN

FIRE EXTINGUISHER CABINET

ILLUMINATED EXIT SIGN

A

FIRE ALARM AUDIO/VISUAL

NOTIFICATION DEVICE-CEILING

MOUNTED

A1 A3

FIRE ALARM VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

V1

A1

FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE-WALL MOUNTED

FIRE ALARM MANUAL PULL

STATION

F

TRAVEL

PATH

STARTING

LOCATION

TD = XX

TRAVEL DISTANCE

NO. OF OCC./

NO. OF EXITS

ACTUAL

EXIT

WIDTH

OCC.

LOAD

FACTOR

LIFE SAFETY SYMBOLS

10/1

2"

34"

1:50

NO. OCC. EXITING

(SMALLER ROOMS)

MAXIMUM OCCUPANCY

AREA

REQ'D. EXIT WIDTH

NO. OF OCC. EXITING

LEGEND

BUILDING & LIFE SAFETY REQUIREMENTS

DESCRIPTION

NEW

PARTITION KEY

NFPA

101-2015

OPENINGS DAMPERS

RATING RFRNC. TYPE RFRNC.

BUILDING SEPARATION:

FIRE BARRIER

(FIRE WALL IN IBC)

2 HR 90 MIN

OCCUPANCY/AREA SEPARATION

FIRE BARRIER

90 MIN

HORIZONTAL EXIT (& REFUGE AREA)

FIRE BARRIER

2 HR 90 MIN

VERT. OPG. (EXIT ENCLSR/SHAFT)

FIRE BARRIER

(2 HR = 4 OR MORE STORIES)

(1 HR = LESS THAN 4 STORIES)1 HR

2 HR

60 MIN

90 MIN

HAZ./INCIDENTAL USE

FIRE BARRIER

45 MIN

HAZ./INCIDENTAL USE

SMOKE PARTITIONS (SPRINKLERED)

NR

SELF OR AUTO

CLOSING

SUBDIVIDING SPACES

SMOKE BARRIER (I-2 OCCUPANCY)

20 MIN

1/2

HR

1 HR

SUITE SEPARATION

SMOKE PARTITION

EXIT ACCESS CORRIDORS (I-2)

SMOKE PARTITIONS (SPRINKLERED)

NR

EXIT ACCESS CORRIDORS (B & AHC)

NON-RATED PARTITIONS

NR

VERT. OPG. (SHAFT)

FIRE BARRIER

60 MIN

[D]

1 HR

2 HR

60 MIN

90 MIN

EXIT PASSAGEWAY (HORIZ.)

FIRE BARRIER

8.7

NFPA 6.1.14.4.1

18.1.3.5.1 19.1.3.5.1

NFPA 7.2.A.3.1 (1)

NFPA 18.1.3.8/

19.1.3.8 18.2.2.5/19.2.25 7.1.3.2.1

NFPA 19.3.1.1

NFPA 8.6.2

8.6.5

NFPA 18.3.2.1.2

NFPA 8.4.1.1

19.3.2.1

NFPA 8.4.2 (3)

18.3.2.1.3 19.3.2.1.2

NFPA 8.5.2

18.3.7.3 19.3.7.3

NFPA 8.4.2

18.2.5.7.1.4 19.2.5.7.1.1

NFPA 8.4.2

18.3.6.2 19.3.6.2

21.3.6 39.3.6

NFPA 19.3.1.1

19.2.2.7 8.6.2 8.6.5(3) & 2

NFPA 7.2.6

19.2.2.7 18.2.2.7

NFPA 221

8.2.1.3

EXIST SOL.

CORE WD.

NFPA 7.2.1.4.1

7.2.4.3.7 8.3.4 18.2.2.5.3,4,5,6,7 19.2.2.5,3,4

8.3.4.2 TBL

18.4.4.7.2.2

7.1.3.2.9 (9)

NFPA 8.3.4.2 TBL

19.3.2.1.3,5

NFPA 8.3.4.2 TBL

8.5.4 18.3.7.8

NFPA 8.3.4.2 TBL

8.3.4.2 TBL

8.3.4.2 TBL

NFPA 8.3.4.2 TBL

8.3.4.2 8.4.3 19.3.2.1.4,3,5

8.4.3

8.4.3 18.3.6.4.1 19.3.6.4.1

N/A

FIRE

90 MIN

FIRE

90 MIN

VARIES

SMOKE

90 MIN

VARIES

VARIES

NONE

N/A

NOT

ALLOWED

NFPA 90

8.3.5.7 9.2.1

NFPA 8.3.5.7

9.2.1 7.2.4.3.5

N/A

8.5.5.2 18.3.7.3(2) 19.3.7.3(2)

8.6.4.5

N/A

N/A

8.4.4.1 8.4.6.2

8.4.4.1 8.4.6.2

8.4.4.1 8.4.6.2 18.3.6.4.1

N/A

WALL

RATING

RATED UL

ASSEMBLIES

2 HR

1 HR

1 HR

NR-

RESIST

SMK

NR

NR-

RESIST

SMK

NR

8.3

UL U412

UL U419

UL U412

UL U419

UL U412

UL U419

UL U412

UL U419

UL U415 (A)

UL U412

UL U419

UL U415 (A)

UL U412

UL U419

UL U412

UL U419

UL U415 (A)

NR

SELF OR AUTO

CLOSING

FIRE

90 MIN

FIRE

90 MIN

NOT

ALLOWED

UNLESS

SERVING

STAIR ONLY

NFPA 90

8.3.5.7 9.2.1

AREA NOT IN CONTRACT

1. THIS PLAN IS FOR LIFE SAFETY INFORMATION ONLY.

2. BUILDING IS FULLY SPRINKLERED IN ACCORDANCE WITH NFPA 13

AND IS PROTECTED WITH A SUPERVISED AUTOMATIC SMOKE

DETECTION SYSTEM.

3. WALL TYPES ARE DETAILED ON 1-AF106 AND INDICATED ON THE

DIMENSIONED FLOOR PLAN ON 1-AE104.

4. REFER TO THIS DRAWING FOR MEANS OF EGRESS.

5. REFER TO THIS DRAWING FOR DOOR CAPACITIES.

6. FINAL LOCATION OF FAAP PANEL TO BE COORDINATED WITH FIRE

MARSHAL.

7. ALL SMOKE BARRIERS/PARTITIONS & FIRE RATED WALLS/ASSEMBLY

SHALL BE PAINTED (IN RED LETTERS) W/APPROPRIATE LABEL &

RATING.

Na

Na

N

N

M

M

L

L

K

K

J

J

H

H

G

G

F

F

4.4

5.45.4

5.7

6.26.2

6.76.7

10.110.1

2.92.9

Ea

Ea

Fa

Fa

GaJaLaMa

Ma HbJb

189 SF

EMG/SCI

71 SF

NURSE NAVIGATOR

74 SF

PAIN & PMR VVC/TM

97 SF

PAIN BH

99 SF

PAIN PHARM

119 SF

PAIN EXAM ROOM 2

122 SF

PAIN EXAM ROOM 3

126 SF

PAIN EXAM ROOM 4

52 SF

WORKSTATION

54 SF

TOILET

145 SF

PAIN SWAMP

47 SF

EXISTING ELEC.

492A

103 SF

SOILED HOLDING

53 SF

TOILET

125 SF

PAIN EXAM

171 SF

PM&R SWAMP

148 SF

PM&R EXAM ROOM 4

156 SF

PM&R EXAM ROOM 3

150 SF

PM&R EXAM ROOM 1

150 SF

PM&R EXAM ROOM 2

106 SF

MSA CHECKIN/OUT

234 SF

PROCEDURE ROOM

124 SF

CLEAN SUPPLY

259 SF

PROCEDURE ROOM

180 SF

OIT

180 SF

CORRIDOR

C498

BLDG 1 - OCCUPANCY 1 - 4TH FLOOR =

5,089 SF (AREA OF WORK)

OCCUPANCY TYPE - AMBULATORY

TYPE II (222) CONSTRUCTION

TOTAL OCCUPANTS = 34

FULLY SPRINKLERED

TRAVEL DISTANCE: 86' - 6"

TRAVEL DISTANCE: 173' - 6"

T R

A V

E L D

IS

T

A N

C E

T R

A V

E L D

IS

T

A N

C E

443 SF

Room

A200BBB

387 SF

Room

A200CCC

SUITE

(PATIENT CARE

NON-SLEEPING)

5,089 SF

EXIT

ACCESS

DOOR

ROOF BELOW ROOF BELOW

EXIT

ACCESS

DOOR

EXISTING

SMOKE

COMP 4-2

11,434 SF

1 1 1 1 1

EXISTING

SMOKE

COMP 4-1

11,372 SF

1:150

1:50

1:50

1:50

1:50

1:50

1:150

1:50

1:150

1:150

1:150

1:150

1:150

1:150

1:50

1:150

1:150

1:150

1:150

1:150

EXISTING

SMOKE

COMP 4-2

11,434 SF

EXISTING

SMOKE

COMP 4-1

11,372 SF

EXISTING

STAIR #1

44.5"

218/2

21.8"

EXISTING

STAIR #2

44.5"

218/2

21.8"

TRAVEL DISTANCE: 100' - 0"

144 SF

NURSES

180 SF

CORRIDOR

C498

321 SF

CORRIDOR

C496

259 SF

CORRIDOR

C499

S F

C O

R R

ID

O

R

C

TEMPORARY CONSTRUCTION

BARRIER

COMPLIANCE NOTE

PER NFPA TABLE A.7.6

TRAVEL DISTANCE LIMIT=200' FOR

EXISTING HEALTH CARE SPRINKLERED

BUILDINGS

TABLE A.7.6

COMMON PATH OF TRAVEL-NO

REQUIREMENT FOR EXISTING HEALTH

CARE SPRINKLERED BUILDINGS

COMPLIANCE NOTE

PER NFPA TABLE A.7.6

TRAVEL DISTANCE LIMIT=200' FOR

EXISTING HEALTH CARE SPRINKLERED

BUILDINGS

TABLE A.7.6

COMMON PATH OF TRAVEL-NO

REQUIREMENT FOR EXISTING HEALTH

CARE SPRINKLERED BUILDINGS

COMPLIANCE NOTE

PER NFPA TABLE A.7.6

TRAVEL DISTANCE LIMIT=200' FOR

EXISTING HEALTH CARE SPRINKLERED

BUILDINGS

TABLE A.7.6

COMMON PATH OF TRAVEL-NO

REQUIREMENT FOR EXISTING HEALTH

CARE SPRINKLERED BUILDINGS

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

SB1 = SMOKE BARRIER

NON-RATED INTERIOR PARTITION WALL

NON-RATED INTERIOR PARTITION WALL (WITH

INSULATION)

EXISTING WALL TO REMAIN

SEE AF105 FOR WALL TYPE CONSTRUCTION

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:5

:5

A

M

FOURTH FLOOR LIFE SAFETY PLAN

RCO EM

BID DOCUMENTS 589A4-19-103

1-GI104

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered

1/8" = 1'-0"

LEVEL 04 - LIFE SAFETY PLAN

NORTH

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

AREA PLAN LEGEND

189 SF

EMG/SCI

71 SF

NURSE NAVIGATOR

74 SF

PAIN & PMR VVC/TM

97 SF

PAIN BH

99 SF

PAIN PHARM

119 SF

PAIN EXAM ROOM 2

122 SF

PAIN EXAM ROOM 3

126 SF

PAIN EXAM ROOM 4

52 SF

WORKSTATION

54 SF

TOILET

145 SF

PAIN SWAMP

180 SF

OIT

259 SF

PROCEDURE ROOM

124 SF

CLEAN SUPPLY

234 SF

PROCEDURE ROOM

103 SF

SOILED HOLDING

47 SF

EXISTING ELEC.

492A

125 SF

PAIN EXAM

171 SF

PM&R SWAMP

53 SF

TOILET

106 SF

MSA CHECKIN/OUT

150 SF

PM&R EXAM ROOM 1

150 SF

PM&R EXAM ROOM 2

156 SF

PM&R EXAM ROOM 3

148 SF

PM&R EXAM ROOM 4

144 SF

NURSES

180 SF

CORRIDOR

C498

321 SF

CORRIDOR

C496

316 SF

CORRIDOR

C495

259 SF

CORRIDOR

C499

TRAVEL DISTANCE: 87' - 0"

TRAVEL DISTANCE: 173' - 6"

T R

A V

E L D

IS

T

A N

C E

T R

A V

E L D

IS

T

A N

C E

TRAVEL DISTANCE: 100' - 6"

TEMPORARY CONSTRUCTION

BARRIER

320 SF

A218

GROUP

ROOM

307 SF

A219

GROUP

ROOM

182 SF

A204

CLINIC

OFFICE

154 SF

A203

CLINIC

OFFICE

204 SF

A200

CLINIC

OFFICE

94 SF

A201B

OBSERVATION

197 SF

A201

PSYCH.

RES

183 SF

A206

PSYCH.

RES

24 SF

A206A

EXIST.

STRG

49 SF

A207

EXIST.

ELEC

163 SF

A210

TMS

ROOM

63 SF

A213

EXIST.

SOC

WRK

64 SF

A212

EXIST.

SOC

WRK

308 SF

A217

EXIST. IT

96 SF

EXIST. ELEC. CLO.

A216

185 SF

A222

MEN'S

173 SF

A221

WOMEN'S

398 SF

A223

WAITING

125 SF

A223A

CHECKOUT/CHECK

IN

372 SF

A224

WAITING

515 SF

A220

GROUP

ROOM

169 SF

A208

TMS

ROOM

74 SF

A214

STAFF

RESTROOM

72 SF

A215

HAC

111 SF

A211

CARE

COORDINATOR

112 SF

A209

CARE

COORDINATOR

64 SF

A223C

COPIER/PAPER

STORAGE

AREA

89 SF

A223B

WORK

AREA

152 SF

A202

CLINIC

OFFICE

178 SF

A205

PSYCH.

RES

1235 SF

A226

GROUP

ROOM

WAITING

AREA

567 SF

C2A08

CORRIDOR

861 SF

C2A07

CORRIDOR

154 SF

C2A03

CORRIDOR

143 SF

C2A05

CORRIDOR

295 SF

CORRIDOR 1

C2A01

63 SF

CORRIDOR 2

C2A02

368 SF

C2A04

CORRIDOR

65 SF

VESTIBULE

A200A

MAIL

AREA

WALKWAY NEEDS TO STAY OPEN

DURING 7AM TO 5PM OPERATING

HOURS

NIGHTS/WEEKENDS FOR WORK

AVAILABLE

PHASE II-GROUP ROOMS,

RESTROOMS AND WAITING ROOM

WILL BE DONE AT THE SAME TIME

THIS ENTRANCE MUST TO

STAY OPEN

DURING 7AM TO 5PM

OPERATING HOURS

NIGHTS/WEEKENDS FOR

WORK AVAILABLE

TO ACCESS ELEVATORS

THIS ENTRANCE MUST TO STAY

OPEN DURING 7AM TO 5PM

OPERATING HOURS

NIGHTS/WEEKENDS FOR WORK

AVAILABLE

PH 4

P H

P H

PH2

PH2

PH 4

PH3

PH3

PH2

WORK SHALL BE NIGHTS/WEEKENDS

AND COORDINATED WITH COR 2 WEEKS

AHEAD OF TIME. 4TH FLOOR:

PHASE 1

PHASE 4 WORK OCCURS IN

CORRIDORS WHICH MUST

REMAIN OPEN 7AM TO 5PM.

WORK IN THE SPACES TO BE

CONDUCTED ON

NIGHTS/WEEKENDS

PHASE IV WORK OCCURS IN

CORRIDORS WHICH MUST

REMAIN OPEN 7AM TO 5PM.

WORK IN THE SPACES TO BE

CONDUCTED ON

NIGHTS/WEEKENDS

TEMPORARY CONSTRUCTION

BARRIER

TEMPORARY CONSTRUCTION

BARRIER

TEMPORARY CONSTRUCTION

BARRIER

TEMPORARY CONSTRUCTION

BARRIER

TRAVEL DISTANCE: 91' - 4"

T R

A V

E L D

IS

T

A N

C E

TEMPORARY CONSTRUCTION

BARRIER

A

C

E

B

SECOND FLOOR KEY PLAN

AREA OF

WORK

AREA OF

WORK

FOURTH FLOOR KEY PLAN

AREA NOT IN CONTRACT

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:4

:4

A

M

SECOND & FOURTH FLOOR PHASING &

INTERIM LIFE SAFETY PLANS

KM EM

BID DOCUMENTS 589A4-19-103

1-GC101

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered

3/32" = 1'-0"

PHASE 1 - FOURTH FLOOR PLAN

3/32" = 1'-0"

PHASE 2 - SECOND FLOOR PLAN

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

NORTH

C3A2

A313

A312 A318A A318 A322 A323 A326

A321A

A319

A317

C A

A353A354

D334A

D335 D336D334

D333BD333A

A356

A358

D333

A318

A320

A314

C3A6

C3A4

A

A316 A321

B304 B302

B315 B316 B317 B318

B325 B303 B301 B300

B323 B322

B321

B320

B338

B347

B345 A A

B344

B342

B341

C3B5

C3B1 B304A B302A

B340

B315BB315A

B316A

B316B

B317A B318A

B301AB303A

C3B4

B339

B

A300

B

D332

STR #1

#2#3 #1

D N

U P

U P

AREA PLAN LEGEND

AREA NOT IN CONTRACT

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Spinklered

PLAN NORTH

B

IM

/V

IS

N

B e h a v io ra l H e a lt h

C lin ic R e n o v a ti o n /B

H C lin ic

R e n o v a ti o n .r v t

/1

/2

:4

:4

A

M

THIRD FLOOR PHASING PLAN

MK EM

BID DOCUMENTS 589A4-19-103

1-GC102

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

5/13/2021

Fully Sprinklered15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.02

3/32" = 1'-0"

LEVEL 03 - PHASING PLAN

PH 1 PH 2

RCP DEMO NOTES

RCP DEMO LEGEND

RCP DEMO KEY NOTES

RCP NOTES

RCP LEGEND

1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT

OF ANY DIMENSIONAL DISCREPANCIES

DISCOVERED DURING CONSTRUCTION.

2. REFER TO ELECTRICAL DRAWINGS FOR MORE

INFORMATION.

AREA NOT IN CONTRACT

EXISTING WALL AND ASSOCIATED COMPONENTS

SHALL BE REMOVED - REFER TO DEMOLITION

KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC

CONDITIONS.

EXISTING DOOR, FRAME, HARDWARE AND

ASSOCIATED COMPONENTS SHALL BE REMOVED

-REFER TO DEMOLITION KEYNOTES FOR

ADDITIONAL DETAILS AT SPECIFIC CONDITIONS

EXISTING WALL SHALL REMAIN

EXISTING DOOR, FRAME AND HARDWARE

SHALL REMAIN

1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT

OF ANY DIMENSIONAL DISCREPANCIES

DISCOVERED DURING CONSTRUCTION.

2. REFER TO ELECTRICAL DRAWINGS FOR LOCATION

OF EMERGENCY LIGHTING.

3. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS

WHERE REQUIRED TO ACCESS ABOVE CEILING

EQUIPMENT. (SEE SPECS)

4. REFER TO FINISH DRAWINGS FOR CEILING GRID

AND PANEL TYPE AND SIZE.

5. ALL PARTITION WALLS SHALL EXTEND TO

UNDERSIDE OF DECK ABOVE U.N.O.

24" X 24" ACOUSTICAL CEILING

PANEL AND GRID

L

2.8

3.7

4.6

5.5

6.3

K J H G

7.2

ELEV ELEV ELEV

STORAGE

A157

CORR

SCAN

DRESSING

ELECT CLOSET

NOT KNOWN

SURG. WAITING

STORAGE

IT CLOSET

NURSE…