MECHANICAL Amendment 1 changes.docx
DOCX document 25 KB Posted
- Solicitation number
- 36C25521R0089
About this file
This document outlines amendments to mechanical, electrical, and technology drawings and specifications for the renovation of a behavioral health clinic, as well as details for a related federal contract opportunity.
The amendments remove and revise several mechanical drawings to adjust equipment locations and piping details. Electrical drawings are updated to add smoke detectors, door operators, and connections for a new condensing unit. Technology specifications have articles removed.
The federal contract opportunity is to renovate approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor of a Veterans Affairs medical building to upgrade behavioral health clinics. The project will replace various systems and finish materials. Work will occur in phases to allow for ongoing care with minimal disruption. The estimated budget range is $2,000,000 to $5,000,000. As a Service-Disabled Veteran-Owned Small Business set-aside, the NAICS code is 236220 and small business size is $39.5 million. The duration is up to 800 days. The solicitation and drawings will be available on June 1st with proposals due July 9th to be evaluated using Best Value Lowest Price Technical Acceptable.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL/ELECTRICAL/TECHNOLOGY ADDENDUM # 1
MECHANICAL:
SPECIFICATION ITEMS
1. None.
DRAWING ITEMS
1. Drawing 1-MP101: a. ADD CU-1 to the Northwest corner on the first floor roof outside of Room A200.
b. REVISE the refrigerant piping for the adjusted equipment location.
c. REFER to the attached drawing.
2. Drawing 1-MP102: REMOVE refrigerant and suction piping as indicated on attached drawing.
3. Drawing 1-MP103: REMOVE CU-1 and refrigerant and suction piping as indicated on attached drawing.
4. Drawing 1-MP300: a. REMOVE detail 5.
b. ADJUST the numbering of the Exterior Wall Penetration detail.
c. REFER the attached drawing.
ELECTRICAL:
SPECIFICATION ITEMS
2. Section 28 31 00: DELETE section 1.6 - GUARANTY PERIOD SERIVCES.
DRAWING ITEMS
5. Drawing 1-E-000 - ELECTRICAL COVERSHEET: ADD fire alarm door hold smoke detector.
6. Drawing1-EP101 - LEVEL 02 - ELECTRICAL POWER: a. ADD automatic door operator connections.
b. ADD fire alarm door hold smoke detectors.
c. ADD keynote #2.
d. ADD electrical connection for condensing unit CU-1 and associated fused disconnect switch.
7. Drawing 1- EP102 - LEVEL 04 - ELECTRICAL POWER: a. ADD automatic door operator connections.
b. REMOVE electrical connection for condensing unit CU-1 and associated fused disconnect switch.
8. Drawing 1-FA101 - LEVEL 02 - FIRE ALARM: a. ADD smoke detectors.
b. REMOVE two (2) corridor audio/visual devices.
9. Drawing 1-FA102 - LEVEL 04 - FIRE ALARM: ADD smoke detectors.
10. Drawing 1-E-300 - ELECTRICAL DETAILS: REVISE 1/1-E-300.
11. Drawing 1-E-500 - ELECTRICAL SCHEDULES: a. REVISE kVA load on panel PLP2-L4-208VN circuit 31.
b. ADD circuit 36, 40 and revise circuit information.
c. REVISE E-CONNECT AND STARTER SCHEDULE FDS-30-208 description.
12. Drawing 1-E-501 - ELECTRICAL SCHEDULES: REVISE kVA load and description on panel LP4-L4-120VN circuit 12, 14.
TECHNOLOGY:
VA Truman Exp.- Reno Behavioral Health IMEG # 17002665.01 Addendum # 1 Page 2 of 2
SPECIFICATION ITEMS
1. Section 271500: DELETE article 3.3 MAINTENANCE.
2. Section 275223: a. ADD the following note to page 1: “THIS SECTION FOR REFERENCE ONLY. THE SYSTEM IS VA PROVIDED AND INSTALLED. GC IS RESPONSIBLE ONLY FOR INSTALLING BACKBONE (CONDUIT AND BACKBOXES)”.
b. DELETE article 4.2 paragraphs B.4 and C.
3. Section 280500: DELETE article 1.20 WARRANTY.
4. Section 283100: DELETE article 1.6
END OF MECHANICAL/ELECTRICAL/TECHNOLOGY ADDENDUM # 1