This document is a presolicitation notice for a construction project to renovate behavioral health clinics at the VA Truman Memorial Veterans Hospital in Columbia, Missouri. The project scope includes renovating approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor to consolidate behavioral health services. The work involves demolition, new construction of electrical, HVAC, plumbing, fire protection, data/voice systems, and interior finishes. The design allows for phasing to minimize disruption to ongoing patient care. The estimated price range is $2,000,000 to $5,000,000. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and use the Lowest Price Technically Acceptable source selection process. The NAICS code is 236220 and size standard is $39.5 million. The performance period is up to 800 calendar days from notice to proceed. The solicitation is expected to be available for download on or about June 1, 2021 with a proposal due date on or about July 9, 2021.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Romanyk Consulting Corp. Copyright © 2016

PRIVILEGED AND CONFIDENTIAL PROPRIETARY INFORMATION

Specifications Volume 1 Div 00 – Div 14

RENOVATE BEHAVIORAL

HEALTH CLINIC

COLUMBIA VA MEDICAL CENTER

Columbia, Missouri

Addendum #1 July 16, 2021

Project Number: 589A4‐19‐103 Contract Number: VA255‐17‐D‐0084

Task Order: 36C25519N0285

07/16/2021 Addendum #1 Renovate Behavioral Health Clinic Project Number 589A4‐19‐103

VA 02‐01‐21

00 01 10‐1

DEPARTMENT OF VETERANS AFFAIRS

VHA MASTER SPECIFICATIONS

TABLE OF CONTENTS

Section 00 01 10

SECTION NO. DIVISION AND SECTION TITLES DATE

Volume 1

DIVISION 07 ‐ THERMAL AND MOISTURE PROTECTION

07 95 13 Expansion Joint Cover Assemblies 01‐21

DIVISION 08 ‐ OPENINGS

08 71 00 Door Hardware 01‐21

Volume 2

DIVISION 27 – COMMUNICATIONS

27 15 00 Communications Structured Cabling 01‐16

27 52 23 Nurse Call and Code Blue Systems 12‐20

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

28 05 00 Common Work Results for Electronic Safety and Security 04‐18

28 13 00 Physical Access Control System 10‐11

05/13/2021

Bid Documents

Renovate Behavioral Health Clinic

Project Number 589A4-19-103

VA 08-01-18

07 95 13 - 1

SECTION 07 95 13

EXPANSION JOINT COVER ASSEMBLIES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Prefabricated floor, wall, ceiling,seismic, and building expansion joint assemblies.

a. Metal plate covers at floor, wall,and ceilingjoints.

1.2 RELATED WORK

A. Section 05 50 00, METAL FABRICATIONS: Steel Plate Expansion Joint Covers.

B. Section 09 06 00, SCHEDULE FOR FINISHES: Color of Elastomer Inserts, Filler Strips, Exterior Wall

Seals and Metal Finishes.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this Section.

B. American Society of Civil Engineers (ASCE):

ASCE/SEI 7-10 - Minimum Design Loads For Buildings and Other Structures.

C. ASTM International (ASTM):

A36/A36M-19 - Structural Steel.

A240/A240M-20 - Chromium and Chromium-Nickel Stainless Steel Plate, Sheet and Strip for Pressure

Vessels and for General Applications.

A283/A283M-18 - Low and Intermediate Tensile Strength Carbon Steel Plates.

A786/A786M-15 - Hot-Rolled Carbon, Low-Alloy, High-Strength Low-Alloy, and Alloy Steel Floor Plates.

B36/B36M-18 - Brass, Plate, Sheet, Strip, and Rolled Bar.

B121/B121M-16 - Leaded Brass Plate, Sheet, Strip and Rolled Bar.

B209-14 - Aluminum and Aluminum-Alloy Sheet and Plate.

B209M-14 - Aluminum and Aluminum-Alloy Sheet and Plate (Metric).

B221-14 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.

B221M-13 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes (Metric).

B455/B455M-20 - Copper-Zinc-Lead Alloy (Leaded-Brass) Extruded Shapes.

Renovate Behavioral Health Clinic

07 95 13 - 2

C864-05(2019) - Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers.

D1187/D1187M-97(2018) - Asphalt-Base Emulsions for Use as Protective Coatings for Metal.

E1399/E1399M-97(2017) - Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems.

E1966-15(2019) - Standard Test Method for Fire-Resistive Joint Systems.

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06 - Metal Finishes Manual.

E. UL LLC (UL):

2079-15 - Standard for Tests for Fire Resistance of Building Joint Systems.

1.4 PREINSTALLATION MEETINGS

A. Conduct preinstallation meeting at project site minimum 30 days before beginning Work of this

Section.

1. Required Participants:

a. Contracting Officer's Representative (COR)

b. Architect/Engineer.

c. Inspection and Testing Agency.

d. Contractor.

e. Installer.

f. Manufacturer's field representative.

2. Meeting Agenda: Distribute agenda to participants minimum 3 days before meeting.

a. Installation schedule.

b. Installation sequence.

c. Preparatory work.

d. Protection before, during, and after installation.

e. Installation.

f. Terminations.

g. Transitions and connections to other work.

h. Other items affecting successful completion.

Renovate Behavioral Health Clinic

07 95 13 - 3

3. Document and distribute meeting minutes to participants to record decisions affecting installation.

1.5 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Include large-scale details indicating profiles of each type of expansion joint cover, splice joints between joint sections, transitions to other assemblies, terminations, anchorages, fasteners, and relationship to adjoining work and finishes.

2. Show size, configuration, and fabrication and installation details.

3. Include composite drawings showing work specified in other Sections coordinated with expansion joints.

C. Manufacturer's Literature and Data:

1. Description of each product specified.

2. Show movement capability of each cover assembly and suitability of material used in exterior seals for ultraviolet exposure .

3. Description of materials and finishes.

4. Installation instructions.

D. Samples: Submit 300 mm (12 inch) long samples.

1. Each type and color of metal finish for each required thickness and alloy.

2. Each type and color of flexible seal.

E. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

2. Low Pollutant-Emitting Materials:

a. Identify volatile organic compound types and quantities.

F. Qualifications: Substantiate qualifications comply with specifications.

1. Installer with a minimum of five (5) years’ of experience in type of work required by this section.

G. Certificates: Indicate products comply with specifications.

1. Fire rated expansion joint cover assemblies.

Renovate Behavioral Health Clinic

07 95 13 - 4

H. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

1.6 QUALITY ASSURANCE

A. Installer Qualifications:

1. Regularly installs specified products.

2. Installed specified products with satisfactory service on five similar installations for minimum five years.

1.7 SUBMIT INSTALLER QUALIFICATIONS.DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.8 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight facility.

B. Protect products from damage during handling and construction operations.

1.9 FIELD CONDITIONS

A. Field Measurements: Verify field conditions affecting expansion joint cover assembly fabrication and installation. Show field measurements on Submittal Drawings.

1. Coordinate field measurement and fabrication schedule to avoid delay.

1.10 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

A. Provide joint cover assemblies that permit unrestrained movement of joint without disengagement of cover, and, where applicable, maintain moisture, watertight and fire-rated protection.

B. Provide templates to related trades for location of support and anchorage items.

2.2 SYSTEM PERFORMANCE

A. Design expansion joint cover assemblies complying with specified performance.

Renovate Behavioral Health Clinic

07 95 13 - 5

B. Joint Movement: ASTM E1399.

1. Nominal Joint Width: _2 inches).

2. Minimum Movement Capability: 25 percent.

3. Movement Type: Thermal,wind,and seismic.

C. Floor Joints: Live loads, including rolling loads.

1. Load Resistance: ASCE/SEI 7; Design criteria as indicated on Drawings.

2. Maximum Deflection: 1/360 of span, maximum.

D. Fire Rated Joints: ASTM E1399, ASTM E1966, or UL 2079, including hose stream test at full-rated period.

1. Fire rating: Match adjacent floor, wall, and ceiling construction.

2. System: Capable of anticipated movement while maintaining fire rating.

3. Coverless Applications: Maintain fire rating without joint cover system.

2.3 MATERIALS

A. Stainless Steel: ASTM A240/A240M, Type 302 or 304.

B. ----Elastomeric Sealant: As specified in Section 07 92 00, JOINT SEALANTS.

C. Elastomeric Seals:

1. Flexible extruded polyvinyl chloride, meeting a Shore A hardness of 75 with UV stabilizer.

Manufacturer's standard colors.

D. Thermoplastic Rubber:

1. ASTM C864.

2. Dense Neoprene or other material standard with expansion joint manufacturers having the same physical properties.

E. Compression Seals: Pre-compressed secondary sealant using preformed expanding foam sealant; open-cell polyurethane foam impregnated with polymer-modified acrylic adhesive.

F. Water Barrier Sheets: Neoprene or EPDM flexible sheet materials minimum 45 mils thick.

1. Provide with drain tubes for horizontal applications.

G. Vinyl Invertor Sealant Waterstops: Manufacturer's standard shapes and grade.

H. Moisture Barrier: Fabric reinforced clear vinyl sheet material sized to accommodate opening.

Renovate Behavioral Health Clinic

07 95 13 - 6

I. Flexible Membrane: 1.5 mm (60 mil) EPDM sheet, with manufacturer's standard support foam.

J. Fire Barrier: Labeled by an approved independent testing laboratory for fire resistance rating indicated for maximum joint width.

a. Thermal Insulation: Manufacturer's standard with factory cut miters and transitions.

b. Fire Barrier Lengths:

1) Joint widths up to and including 150 mm (6 inches): Maximum 15 m (50 feet) to minimize field splicing.

2) Other Joint widths: 3 m (10 foot) with overlapping ends for field splicing.

K. Ceramic Blanket: Manufacturer's standard joint filler to achieve fire rating indicated.

L. Butyl Caulk Tape: Self adhering double sided butyl rubber sealant tape with easy-release silicone coated paper.

2.4 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer.

1. Provide ceiling and wall expansion joint cover assemblies design matching floor to wall and floor to floor expansion joint cover design.

2. Provide expansion joint cover assembly designs, profiles, materials and configuration indicated, as required to accommodate joint size variations in adjacent surfaces, and anticipated movement.

C. Sustainable Construction Requirements:

1. Stainless Steel Recycled Content: 70 percent total recycled content, minimum.

2. Low Pollutant-Emitting Materials: Maximum VOC content by weight.

a. Non-Flooring Adhesives and Sealants.

2.5 FABRICATION

A. Fabricate Expansion Joint Cover Assemblies:

1. As complete assembly ready for installation.

2. In longest practicable lengths to minimize number of end joints.

3. With factory mitered corners where joint changes directions or abuts other materials.

Renovate Behavioral Health Clinic

07 95 13 - 7

a. With closure materials and transition pieces, tee-joints, corners, curbs, cross-connections and other assemblies.

4. Joints within enclosed spaces such as chase walls, include 1 mm (0.04 inch) thick galvanized steel cover where conventional expansion joint cover is not used.

5. Where floor slab is fire rated provide ceramic blanket at joints.

6. Seal Strip: Factory-formed and bonded to metal frames and anchor members.

7. Compression Seals: Fabricate from expanding foam as secondary seal and elastomeric sealant to sizes and profiles shown.

B. Floor-to-Floor Metal Plate Joints:

1. Frames: Metal, continuous on both sides of joint designed to support cover plate.

a. Flush Design: Seating surface and raised floor rim to accommodate adjacent flooring.

b. Anchorage: Concealed bolt and steel anchors for embedment in concrete.

2. Cover Plate: Metal, matching frames where exposed.

a. Supported Load: 19.2 MPa (400 psf), minimum.

b. Rattle-free due to traffic.

3. Fillers: Resilient material between raised rim of frame and edge of cover plate, where shown.

a. No gaps or bulges over full design range joint movement.

4. Fire Barrier: As required for fire resistance rating.

5. Water Stop: Manufacturer's standard, continuous, full length of joint.

6. Seismic: As required by Code.

7. Finishes: As specified in Section 09 06 00, SCHEDULE FOR FINISHES.

C. Floor-to-Wall Metal Plate Joints:

1. Frames: Metal, continuous on floor side of joint only.

a. Provide wall side frame where required by manufacturer's design.

2. Cover Plates: Angle cover plates with countersunk flat-head exposed fasteners for securing cover plate to wall unless shown otherwise.

a. Fastener Spacing: As recommended by manufacturer.

Renovate Behavioral Health Clinic

07 95 13 - 8

3. Joint Design: Match adjacent floor to floor design.

4. Fire Barrier: As required for fire resistance rating.

5. Water Stop: Manufacturer's standard, continuous, full length of joint.

6. Seismic: As required by Code.

7. Finishes: As specified in Section 09 06 00, SCHEDULE FOR FINISHES.

D. Interior Wall Joint Cover Assemblies:

1. Frame: Metal, surface mounted, concealed fastening to wall on one side of joint.

2. Cover Plate: Metal, smooth surface, lap both sides of joint and permitting free movement on one side.

a. Fabricate with concealed attachment of cover to frame when cover is in close contact with adjacent wall surface finish.

b. Use angle cover plates at intersecting walls.

3. Joint Design: Match adjacent floor to floor design.

4. Fire Barrier: As required for fire resistance rating.

5. Seismic: As required by Code.

6. Finishes: As specified in Section 09 06 00, SCHEDULE FOR FINISHES.

E. Ceiling and Soffit Assemblies:

1. Frames: Metal, continuous on both sides of joint, flush mounted with no exposed fasteners.

2. Flexible Insert: Variable movement semi-rigid vinyl locked into frame.

a. Face Style: Flush or accordion, as shown, to span joint width without sagging.

3. Seismic: As required by Code.

4. Finishes: As specified in Section 09 06 00, SCHEDULE FOR FINISHES.

2.6 -FINISHES

A. Stainless Steel: NAAMM AMP 500, No. 2B bright finish.

2.7 ------ACCESSORIES

A. General: Manufacturer's standard anchors, fasteners, set screws, spaces, protective coating, and filler materials, adhesive and other accessories required for installation.

B. Barrier Coating: ASTM D1187/D1187M.

Renovate Behavioral Health Clinic

07 95 13 - 9

C. Adhesives: Low pollutant-emitting, water based type recommended by adhered product manufacturer for each application.

D. Fasteners: Type and size recommended by expansion joint cover assembly manufacturer.

1. Exterior Applications: Stainless steel.

2. Fasteners for Aluminum: Stainless steel.

3. Other Applications: Galvanized steel or stainless steel.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

1. Provide items embedded in concrete and masonry in time for building into work without delaying work.

B. Protect existing construction and completed work from damage.

C. Apply barrier coating to steel surfaces in contact with dissimilar metals nd cementitious materials to minimum 0.7 mm (30 mils) dry film thickness.

3.2 INSTALLATION

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Install anchorage devices and fasteners for securing expansion joint assemblies to in-place construction where anchors are not embedded in concrete and masonry.

1. Secure with metal fasteners, type and size to suit application.

C. Perform cutting, drilling and fitting required for installation of expansion joint cover assemblies.

D. Install joint cover assemblies aligned and positioned in correct relationship to expansion joint opening and adjoining finished surfaces measured from established lines and levels.

1. Allow for thermal expansion and contraction of metal to avoid buckling.

2. Accommodate joint opening size at time of installation.

E. Set floor covers at elevations flush with adjacent finished flooring, unless shown otherwise.

F. Grout floor frames set in prepared recesses.

Renovate Behavioral Health Clinic

07 95 13 - 10

G. Locate wall, ceiling and soffit covers in continuous contact with adjacent surfaces. Secure with required accessories.

H. Locate anchors at interval recommended by manufacturer, but minimum 75 mm (3 inches) from each end, and, maximum 600 mm (24 inches) on centers.

I. Maintain continuity of expansion joint cover assemblies with end joints held to a minimum and metal members aligned mechanically using splice joints.

J. Cut and fit ends to accommodate thermal expansion and contraction of metal to avoid buckling of frames and cover plates.

K. Flush Metal Cover Plates:

1. Secure flexible filler between frames to allow compression and expansion.

2. Adhere flexible filler materials to frames with adhesive or pressure-sensitive tape as recommended by manufacturer.

L. Waterstops:

1. Install in conjunction with floor joints, and where shown.

2. Install continuously to prevent water damage to finish spaces.

3. Seal waterstop to frames to prevent water leakage.

4. Install drainage tubes from waterstops to discharge collected water in nearest plumbing air gap drain.

M. Fire Barriers:

1. Install in compliance with tested assembly.

2. Install at joints in floors and in fire rated walls.

3. Use fire barrier sealant furnished with expansion joint assembly.

N. Apply sealant where required to prevent water and air infiltration.

O. Vertical Exterior Extruded Thermoplastic Rubber.

1. Install side frames mounted on sealant or butyl caulk tape with appropriate anchors

600 mm (24 inches) on center complete with secondary seal.

2. Install primary seals retained in extruded aluminum side frames.

P. Extruded Thermoplastic Rubber or Seals:

1. For straight sections, install preformed seals in continuous lengths.

Renovate Behavioral Health Clinic

07 95 13 - 11

2. Vulcanize or heat-seal field spliced joints to provide watertight joints as recommended by manufacturer.

Q. Preformed Elastomeric Sealant Joint:

1. Locate joint directly over joints in wall and floor substrates.

2. Fasten full length to substrate using construction adhesive.

3. Install flush or slightly below finish material.

3.3 CLEANING

A. Remove excess adhesive before adhesive sets.

B. Clean exposed metal surfaces. Remove contaminants and stains.

3.4 PROTECTION

A. Cover floor joints with plywood where wheel traffic occurs before Substantial completion.

B. Remove protective covering when adjacent work areas are completed. Clean exposed surfaces in compliance with manufacture's printed instructions.

- - E N D - -

05/13/2021 Bid Documents

VA 01-01-21

08 71 00-1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

Caulking: Section 07 92 00 JOINT SEALANTS.

Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11 13, HOLLOW METAL

DOORS AND FRAMES Section 08 71 13, AUTOMATIC DOOR OPERATORS Section 13 49 00, RADIATION PROTECTION

Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.

Painting: Section 09 91 00, PAINTING.

Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.

Electrical: Division 26, ELECTRICAL.

Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

All hardware shall comply with ABAAS, (Architectural Barriers Act Accessibility Standard) unless specified otherwise.

Provide rated door hardware assemblies where required by most current version of the

International Building Code (IBC).

Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

08 71 00-2

The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

5. Floor closers.

1.4 WARRANTY

Automatic door operators shall be subject to the terms of FAR Clause 52.246-21, except that the

Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND

SAMPLES. Submit 6 copies of the schedule per Section 01 33 23. Submit 2 final copies of the final approved schedules to VAMC Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:

Hardware Item

Quantity Size Reference Publication Type No.

Finish Mfr.

Name and Catalog No.

Key Control Symbols

UL Mark (if fire rated and listed)

ANSI/BHMA

Finish Designation

08 71 00-3

Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers Association shall be submitted for approval.

Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to COR for reference purposes. Tag shall identify items by Project

Specification number and manufacturer's catalog number. These items shall remain on file in

COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including

Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and

Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

08 71 00-4

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

1.10 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

ASTM International(ASTM):

F883-13 ...................................... Padlocks

E2180-18................Standard Test Method for Determining the Activity of Incorporated

Antimicrobial Agent(s) In Polymeric or Hydrophobic Materials

American National Standards Institute/Builders Hardware Manufacturers Association

(ANSI/BHMA):

A156.1-06................................... Butts and Hinges

A156.2-03................................... Bored and Pre-assembled Locks and Latches

A156.3-08................................... Exit Devices, Coordinators, and Auto Flush Bolts

A156.4-08................................... Door Controls (Closers)

A156.5-14................................... Cylinders and Input Devices for Locks.

A156.6-05................................... Architectural Door Trim

A156.8-05................................... Door Controls-Overhead Stops and Holders

A156.11-14................................. Cabinet Locks

A156.12-05 .............Interconnected Locks and Latches

A156.13-05................................. Mortise Locks and Latches Series 1000

A156.14-07 .............Sliding and Folding Door Hardware

A156.15-06................................. Release Devices-Closer Holder, Electromagnetic and

Electromechanical

08 71 00-5

A156.16-08................................. Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06................................. Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09................................. Thresholds

A156.22-05................................. Door Gasketing and Edge Seal Systems

A156.23-04................................. Electromagnetic Locks

A156.24-03................................. Delayed Egress Locking Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06................................. Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.31-07 ................................ Electric Strikes and Frame Mounted Actuators

A156.36-10................................. Auxiliary Locks

A250.8-03................................... Standard Steel Doors and Frames

National Fire Protection Association (NFPA):

80-10 .......................................... Fire Doors and Other Opening Protectives

101-09 ........................................ Life Safety Code

Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type

A2111/A5111 for doors over 900 mm (3 feet) wide. Hinges for exterior outswing doors shall

08 71 00-6 have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless steel material.

2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type

A8111/A5111 for doors over 900 mm (3 feet) wide. Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

Provide quantity and size of hinges per door leaf as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm (4-1/2 inches x 4-1/2 inches) hinges.

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x

114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm

(5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.

See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations;

with components finished after milling and drilling are complete

Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a Teflon-coated 6.35mm

(0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Exterior Hinges: Stainless steel.

2. Base Metal for Interior Hinges: Stainless steel.

3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.

08 71 00-7

4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.

5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.

6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

2.3 DOOR CLOSING DEVICES

Closing devices shall be products of one manufacturer.for each type specified.

2.4 OVERHEAD CLOSERS

Conform to ANSI A156.4, Grade 1.

Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory

08 71 00-8 templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

11. Provide parallel arm closers with heavy duty rigid arm.

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.5 DOOR STOPS

Conform to ANSI A156.16.

Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.

Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251

(rubber pads having concave face) to receive turn piece or button.

Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type

L02121 elsewhere.

Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

Omit stops where floor mounted door holders are required and where automatic operated doors occur.

Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

08 71 00-9

Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

Where the specified wall or floor stop cannot be used, provide concealed overhead stops

(surface-mounted where concealed cannot be used).

2.6 OVERHEAD DOOR STOPS AND HOLDERS

Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type:

stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.

2.7 LOCKS AND LATCHES

Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins . Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.

In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latch sets, except on designated doors in

Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel. Provide sectional (lever x rose) lever design matching existing. No substitute lever material shall be accepted. All locks and latch sets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

08 71 00-10

2. Cylindrical Lock and Latch Sets: levers shall meet ADA (Americans with Disabilities Act) requirements. Cylindrical locksets shall be series 4000 Grade I. All locks and latch sets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)

3. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

Approved Manufacturer: Best 9K x 15D

2.8 PUSH-BUTTON COMBINATION LOCKS

ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.

Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA A156.13, Grade 1.

Lever handles and operating components in compliance with the ABAAS and the ADA

Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.

Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.

2.9 ELECTROMAGNETIC LOCKS

ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product Directory."

1. Type: Full exterior or full interior, as required by application indicated.

2. Strength Ranking: Not less than 1200 lbs.

3. Inductive Kickback Peak Voltage: Not more than 0V.

4. Residual Magnetism: Not more than 0 pound force (0 N) to separate door from magnet.

Delayed-Egress Locks: BHMA A156.24.Listed under Category G in BHMA's "Certified Product

Directory".

1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than

15 pound force (67 N) for not more than 3 seconds, as required by NFPA 101.

2. Security Grade: Activated from secure side of door by initiating device.

08 71 00-11

3. Movement Grade: Activated by door movement as initiating device.

4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.

2.10 ELECTRIC STRIKES

ANSI/ BHMA A156.31 Grade 1.

General: Use fail-secure electric strikes at fire-rated doors.

2.11 KEYS

Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks 100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.12 KEY CABINET

ANSI Standard A156.11. Provide key cabinet made of cold rolled, 1.2 mm (0.0478 inch) thick furniture steel electro-welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam and mechanical pushbutton door lock. Key Cabinet and Key Control System shall accommodate all keys for this project plus 25 percent. Provide minimum number of multiple cabinets where a single cabinet of largest size will not accommodate the required number of keys.

Key tags shall consist of two sets: Permanent self-locking and loan key snaphook type with tag colors as follows: Red fiber marker of the permanent self-locking type approximately 32 mm (1-

1/4 inch) in diameter engraved with the legend "FILE KEY MUST NOT BE LOANED." Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with the legend "LOAN

KEY."

The manufacturer of the lock cylinders and locks shall attach a key tag to keys of each lock cylinder and shall mark thereon the respective item number and key change number. Provide each group of keys in a key gathering envelope (supplied by Key Cabinet Manufacturer) in which

08 71 00-12 the lock manufacturer shall include the following information: Item number, key change number and door number. The contractor shall furnish the Key Cabinet Manufacturer the hardware and keying schedules and change keys.

The Key Cabinet Manufacturer shall set up a three-way cross index system, including master keys, listing the keys alphabetically, the hooks numerically and the key changes numerically on different colored index cards. Index cards shall be typewritten and inserted in a durable binder.

Attach the keys to the two sets of numbered tags supplied with the cabinet. (The permanent tag and the loan key tag). Instruct the owner in proper use of the system. Install cabinet as directed by the COR.

2.13 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

Conform to ANSI Standard A156.6.

Provide protective plates and door edging as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high, match facility standard. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

4. Armor plates for doors are listed under Article "Hardware Sets". Armor plates shall be thickness as noted in the hardware set, 875 mm (35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all

4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each

08 71 00-13 door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard.

Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

2.14 EXIT DEVICES

Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.

Surface vertical rod panics shall only be provided less bottom rod; provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.

Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.

Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.

At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.

08 71 00-14

Exit devices for fire doors shall comply with Underwriters Laboratories, Inc., requirements for Fire

Exit Hardware. Submit proof of compliance.

2.15 FLUSH BOLTS (LEVER EXTENSION)

Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI A156.16, for flush bolts required on lower part of doors.

Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.

Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).

Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.

Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).

2.16 FLUSH BOLTS (AUTOMATIC)

Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).

At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than 20 minutes; provide fire pins as required by auto flush bolt and door fire labels.

Components of Alarm System:

2.17 DOOR PULLS WITH PLATES

Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.

08 71 00-15

2.18 PUSH PLATES

Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by 406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders and turn pieces where required.

2.19 COMBINATION PUSH AND PULL PLATES

Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.

2.20 COORDINATORS

Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with

Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.

2.21 THRESHOLDS

Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

For thresholds at elevators entrances see other sections of specifications.

At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.

08 71 00-16

2.22 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR SOUND CONTROL

DOORS

Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).

2.23 WEATHERSTRIPS (FOR EXTERIOR DOORS)

Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length

(0.000774m3/s/m).

2.24 MISCELLANEOUS HARDWARE

Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types): Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as otherwise specified . Provide cylinders to operate locking devices where specified for following partitions and doors:

1. Folding doors and partitions.

2. Wicket door (in roll-up door assemblies).

3. Slide-up doors.

4. Swing-up doors.

5. Fire-rated access doors-Engineer's key set.

6. Doors from corridor to electromagnetic shielded room.

7. Day gate on vault door.

Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers Type L03011 or L03021, depending on frame material, of white or light gray color,…