This document provides details for a federal solicitation to renovate a behavioral health clinic located at a Veterans Affairs medical center. The project scope includes renovating approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor to consolidate behavioral health services. Renovations will address electrical, HVAC, plumbing, fire protection, data/voice systems, and interior finishes. The design allows for a phased construction approach to minimize disruptions to patient care in an active facility. The project cost is estimated between $2-5 million. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and utilize the Lowest Price Technically Acceptable source selection process. The North American Industry Classification Code is 236220 and small business size standard is $39.5 million. Proposals are due around July 9, 2021.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

ABBR: DESCRIPTION:

TYP TYPICAL

C CONDUIT

GFI GROUND FAULT INTERRUPTER

1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR

SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT

NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL

EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.

2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE

LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET 1-E-500.

3. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

4. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND

OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.

5. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN

EMERGENCY CIRCUIT.

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

EWC ELECTRIC WATER COOLER

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG

1 = CIRCUIT NUMBER

a = SWITCH DESIGNATION

NL = SUBSCRIPT (IF APPLICABLE)

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: F1 / 1 / a / NL

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS

ON THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN

EACH PHASE.

3. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN A SEPARATE

RACEWAY FROM ALL OTHER CIRCUITS.

4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE

DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED

WHEN CONDUIT IS SPECIFIED EXPOSED.

5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM

FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND

OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX

CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED

DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO

BE INSTALLED.

8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)

EXCEPT WHERE OTHERWISE NOTED.

9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED

FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE

NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.

10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS

SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN

GRILLE.

11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE

EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

13. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE

EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH

IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

15. ELECTRICAL INDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR

COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

NORMAL BRANCH LUMINAIRE

EMERGENCY CRITICAL BRANCH LUMINAIRE

EMERGENCY LIFE SAFETY BRANCH LUMINAIRE

UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE'

LUMINAIRE SYMBOL KEY

SYMBOL: DESCRIPTION:

26 29 21MX-# DISCONNECT SWITCH, REFER TO DISCONNECT AND STARTER

SCHEDULE

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:

RELATED

SPECIFICATION

28 31 00 FIRE ALARM VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

V1 V3

V7 VH

28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

A1 A3

A7 AH

AS

28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE -

CEILING MOUNTED A

SD 28 31 00 FIRE ALARM DOOR HOLD SMOKE

DETECTOR - CEILING MOUNTED

SD 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

28 31 00 FIRE ALARM MANUAL PULL STATIONF

28 31 00 FIRE ALARM SMOKE, FIRE/SMOKE DAMPERSD

VS

26 09 23 SWITCH - SINGLE POLE

SWITCH - OCCUPANCY SENSOR

WALL SWITCH

O

OC OCCUPANCY SENSOR - ULTRASONIC 360

DEGREE COVERAGEU

OC OCCUPANCY SENSOR - DUAL TECHNOLOGY

D

CEILING MOUNTED OCCUPANCY SENSOR

EXTENDED RANGE

LS DAYLIGHT LEVEL SENSOR

26 09 23

26 09 23

26 09 23

26 09 23

26 28 16 DISCONNECT, REFER TO DISC/STA SCHEDULE

26 09 23

DIMMER - LED26 09 23

SYMBOL:

SPEC

SECTION:

DESCRIPTION:

ELECTRICAL SYMBOL LIST

SYMBOL: DESCRIPTION:

26 05 33 JUNCTION BOX

J

J

26 05 33 ELECTRICAL CONNECTION

E

E

SYMBOL:

SPEC

SECTION:

DESCRIPTION:

TROFFER

DOWNLIGHT LUMINAIRE

INDUSTRIAL LUMINAIRE

SINGLE FACE EXIT SIGN

DOUBLE FACE EXIT SIGN

SYMBOL:

SPEC

SECTION:

DESCRIPTION:

WALL/CEILING EMERGENCY EXIT SIGN

26 27 26 DUPLEX RECEPTACLE, 125V

26 27 26 DUPLEX GFI RECEPTACLE, 125V

26 27 26 QUAD RECEPTACLE, 125V

SYMBOL:

SPEC

SECTION:

DESCRIPTION:

REFER TO

LUMINAIRE

SCHEDULE

28 31 00 SMOKE, FIRE/SMOKE DAMPER

CONTROLLER

ARD

SPEC

SECTION:

26 27 26 SIMPLEX RECEPTACLE, 6-20R, 250V

ELECTRICAL SYMBOL LIST

ELECTRICAL SYMBOL LIST

ELECTRICAL SYMBOL LIST

ELECTRICAL SYMBOL LIST

OC

E

SW WALL CONTROL STATION26 09 23

DIMMER - WALL DIMMER OCCUPANCY

SENSOR

26 09 23 O

SWITCH - THREE WAY - KEY LOCK

K3

26 09 23

VC VACANCY SENSOR - DUAL TECHNOLOGY

D

26 09 23

SWITCH - SINGLE POLE - KEY LOCK

K

26 09 23

DIMMER - LED - VACANCY SENSOR WALL

SWITCH

26 09 23 V

28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

A3

28 31 00 FIRE ALARM ELECTROMAGNETIC DOOR HOLD

DEVICE

DH

SD 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING

MOUNTED

DH

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING

CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS

BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING

FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK

AND SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES

ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF

WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF

ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.

CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH

CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH

HIS/HER WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

ELECTRICAL PHASING NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO

GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS, PHASING SCHEDULES AND

FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS

DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND

TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE

REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

FIRE PROTECTION CONTRACTORF.P.C.

AUTOMATIC TEMPERATURE CONTROL CONTRACTORA.T.C.

HEATING CONTRACTORH.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

CONSTRUCTION MANAGERC.M.

NOT ALL MAY APPLY

SUGGESTED MATRIX OF RESPONSIBILITY

ITEM: SHOWN ON:

FURNISHED

BY:

INSTALLED

BY: NOTES:

TECHNOLOGY ROUGH-IN, REFER TO

GENERAL TECHNOLOGY EQUIPMENT

SCHEDULE AND SPECIFICATIONS FOR

DEFINITION

T-SERIES E.C. E.C. 3. 4.

INFORMATION OUTLET FACEPLATES,

JACKS, AND TERMINATIONS

T-SERIES T.C. T.C.

CONDUIT SLEEVES (WHEN SHOWN ON

DRAWINGS)

T-SERIES E.C. E.C.

CONDUIT SLEEVES (NOT SHOWN BUT

REQUIRED FOR PROPER INSTALLATION

OF SYSTEM)

N/A T.C. T.C. 2. 4.

TELECOMMUNICATION SYSTEMS

ROUGH-IN

T-SERIES E.C. E.C. 1.

TELECOMMUNICATION EQUIPMENT,

CABLING, AND TERMINATIONS

T-SERIES T.C. T.C.

NURSE CALL ROUGH-IN T-SERIES E.C. E.C.

NURSE CALL EQUIPMENT, CABLING,

AND TERMINATIONS

T-SERIES T.C. T.C.

GROUNDING LUGS ON TECHNOLOGY

EQUIPMENT

T-SERIES T.C. E.C. 6.

CONNECTION OF TECHNOLOGY

BONDING SYSTEM TO THE ELECTRICAL

GROUND SYSTEM

T-SERIES E.C. E.C.

LINE VOLTAGE POWER (+120V OR

GREATER)

E-SERIES E.C. E.C.

LINE VOLTAGE POWER (NOT SHOWN

BUT REQUIRED FOR PROPER

INSTALLATION OF SYSTEM)

N/A T.C. E.C. 2. 4.

LINE VOLTAGE POWER FOR DOOR

HARDWARE POWER SUPPLIES

ARCH SPEC E.C. E.C.

LOW VOLTAGE CABLING FOR

TECHNOLOGY SYSTEMS

T-SERIES T.C. T.C.

CABLE HANGERS AND SUPPORTS OR

OTHER CABLE ROUTING METHODS

(OTHER THAN CONDUIT AND CABLE

TRAY)

T-SERIES T.C. T.C. 5.

SUGGESTED MATRIX OF RESPONSIBILITY NOTES

1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION

OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR

ADDITIONAL INFORMATION.

2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL

REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE

MANUFACTURERS.

3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS

INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE

CONTRACT DOCUMENTS.

4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF

THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM

CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED

IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.

5. UNLESS TRADE RULES DICTATE OTHERWISE.

6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR

INSTALLATION IN THE FIELD.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:4

P

M

ELECTRICAL COVERSHEET

MARHAR EVAMIL

BID DOCUMENTS 589A4-19-103

1-E-000

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01Revisions: Date:

ADDENDUM#1 07/16/2021

E

E

E

E

E

E

E

E

E

E

EE

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

NaN M L

2.8

3.7

4.6

5.5

6.3

K J H G F E

CLINIC OFFICE

A200

CLINIC OFFICE

A203

CLINIC OFFICE

A204

CLINIC OFFICE

A202

OBSERVATION

A201B CORRIDOR 2

C2A02

PSYCH. RES

A201

PSYCH. RES

A206

EXIST. STRG

A206A

CORRIDOR 1

C2A01 PSYCH. RES

A205

EXIST. ELEC

A207

CORRIDOR 3

C2A04

CORRIDOR 4

C2A03

TMS ROOM

A208

TMS ROOM

A210

EXIST. SOC WRK

A212

EXIST. SOC WRK

A213

CORRIDOR 5

C2A05

CARE COORDINATOR

A209

CARE COORDINATOR

A211

STAFF RESTROOM

A214

HAC

A215

EXIST. IT

A217

WOMEN'S

A221

MEN'S

A222

EXIST. ELEC. CLO.

A216

CORRIDOR 6

C2A07

CORRIDOR 8

C2A08

GROUP ROOM WAITING AREA

A226

WAITING 2

A224

WAITING 1

A223

WORK AREA

A223B

COPIER/PAPER STORAGE AREA

A223C

MAIL AREA

A223D

CHECKOUT/CHECK IN

A223A

GROUP ROOM

A219

GROUP ROOM

A218

GROUP ROOM

A220

VESTIBULE

A200A

EWC

A

EX. TEMPERATURE

CONTROL TRANSFORMER

EX. LP2-L4-120VN

(SECT.1)

EX. LP2-L4-120VN

(SECT. 2)

EX. LP2-L4-277VN

EX. T2-L4-120VN

EWC/14

A

A

+72"

MONITOR

+72"

MONITOR

EX. LP2-JB4.4-120VC

EX. T2-JB4.4-120VC

EX. DS2-JB4.4-480VC

EX. SECURITY PANEL

EX. SECURITY PANEL

KIOSK

KIOSK

SSU-1

VAV

CONTROLS

PLP2-L4-208VN-29

DS-30-120

1-EF61

18 VAV CONTROLS

KIOSK

+72"

MONITOR

KIOSK

A/28

A/28

A/28

A/28

VAV

CONTROLS

U.C. REFRIGERATOR

PRINTER

VAV

CONTROLS

VAV

CONTROLS/29

11 11

5 3

9 9

WORKSTATION

24 24

A

A

19 15 15

WORKSTATION

WORKSTATION

25 25 25

EX. LP2-R6-277VE

MONITOR/23

OVERHEAD PROJECTOR/23

OVERHEAD PROJECTOR/13 OVERHEAD PROJECTOR/13

MONITOR/11

MONITOR/11

+72"/SMARTBOARD/17

+72"/SMARTBOARD/9

+72"/SMARTBOARD/21

120V:24V TRANSFORMER

120V:24V TRANSFORMER

EX. LP2-JB4.4-120VC-21

EX. LP2-JB4.4-120VC-21

DS-30-120

DS-30-120

MONITOR

AC-SEC-CON

EX. LP2-JB4.4-120VC-22

EX. LP2-JB4.4-120VC-25,27EX. LP2-JB4.4-120VC-25,27

ALL 120/208V BRANCH CIRCUITS IN

THIS AREA SHALL BE FED FROM

PANEL LP2-L4-120VN (SECT. 2)

UNLESS NOTED OTHERWISE

ALL 120/208V BRANCH CIRCUITS IN

THIS AREA SHALL BE FED FROM

PANEL P2LP-L4-208VN UNLESS

NOTED OTHERWISE

15 17

AUTOMATIC DOOR OPERATOR

AUTOMATIC DOOR OPERATOR

AUTOMATIC DOOR OPERATOR

1-F/SDPR1

AUTOMATIC DOOR OPERATOR/32

AUTOMATIC DOOR OPERATOR/34

AUTOMATIC DOOR OPERATOR/36

PLP2-L4-208VN

AUTOMATIC DOOR OPERATOR/31

38,40

CU-1

FDS-30-208

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:0

P

M

LEVEL 02 - ELECTRICAL POWER

MARHAR EVAMIL

BID DOCUMENTS 589A4-19-103

1-EP101

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

N

O R HT

1/8" = 1'-0"1

LEVEL 02 - ELECTRICAL POWER

KEYNOTES:

1. 1-EF61 MOUNTED ON 3RD FLOOR ROOF.

PROVIDE STEEL CHANNEL SUPPORT FOR

MOUNTING OF DISCONNECT SWITCH.

COORDINATE EXACT LOCATION WITH M.C.

2. COORDINATE EXACT LOCATION OF

MECHANICAL CONTROLS WITH M.C.

3. TIE NEW RECEPTACLES INTO NEARBY

EXISTING RECEPTACLE CIRCUIT IN THIS

SPACE.

4. PROVIDE 120V:24V TRANSFORMER AND

ASSOCIATED DISCONNECT SWITCH IN CEILING

FOR LOCAL VAV CONTROLS. CONTRACTOR

MAY DEFER FROM PLANS WHEN LOCATING

TRANSFORMER ABOVE CEILING, LOCATION

SHOWN IS FOR DESIGN INTENT ONLY.

COORDINATE FINAL INSTALLATION LOCATION

WITH EXISTING ABOVE-CEILING CONDITIONS

AND FINAL LOCATIONS OF MECHANICAL

CONTROLS TO MINIMIZE TOTAL CONDUCTOR

AND CONDUIT LENGTHS. REFER TO

MECHANICAL SHEET 1-MH101 - LEVEL 02 -

VENTILATION FOR VAV LOCATIONS.

5. INDOOR UNIT SSU-1 IS POWERED BY THE

OUTDOOR UNIT THROUGH FIELD SUPPLIED

INTERCONNECTED WIRING.

6. MOUNT RECEPTACLES TO RACK. COORDINATE

WITH OIT EQUIPMENT INSTALLER.

7. INSTALL AUTOMATIC FLUSH VALVE POWER

CONVERTER. VERIFY REQUIRED POWER

CONVERTER QUANTITY AND VALVE

CONNECTIONS WITH PLUMBING CONTRACTOR.

8. RECESS QUAD RECEPTACLE FOR

SMARTBOARD. COORIDNATE EXACT BOARD

LOCATION WITH ARCHITECT.

9. EXTEND 120V EMERGENCY CIRCUIT FROM

EXISTING FIRE SMOKE DAMPER. VERIFY

AVAILABLE CIRCUIT AMPACITY AND CONDITION

OF EXISTING CONDUIT AND CONDUCTORS

PRIOR TO EXTENDING.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01Revisions: Date:

E

E

E

E

Na N M L

2.8

3.7

4.6

5.5

6.3

K J H G F DE

7.2

8.3

9.1

EMG/SCI

NURSE NAVIGATOR

PAIN & PMR VVC/TM

PAIN BH

PAIN PHARM

PAIN EXAM ROOM 2

PAIN EXAM ROOM 3

PAIN EXAM ROOM 4

WORKSTATION

TOILET

PAIN SWAMP

EXISTING ELEC.

492A

SOILED HOLDING

TOILET

PAIN EXAM

PM&R SWAMP

PM&R EXAM ROOM 4

PM&R EXAM ROOM 3

PM&R EXAM ROOM 1

PM&R EXAM ROOM 2

MSA CHECKIN/OUT

PROCEDURE ROOM

CLEAN SUPPLY

PROCEDURE ROOM

OIT

CORRIDOR

C498

Room

A200BBBRoom

A200CCC

NURSES

CORRIDOR

C498

CORRIDOR

C496

CORRIDOR

C499

C O

R R

ID

O

R

C

EX. LP4-L4-120VC

EX. LP4-L4-277VN

EX. T4-L4-120VNDS4-L4

EX. T4-L4-120VE

EX. DP4-L4-277VE

HATCHED AREA NOT

IN PROJECT SCOPE

A/23

A/23

A/8

EXAM LIGHT/19

A/5

EXAM LIGHT/19

A/21

A/20

A/19

A/17

+48"

+48"/2

A

COPIER

A

COPIER

A/15

+48"/2

A/33

A/16 A/18

+46"/21

EXAM LIGHT

+42"

OTOSCOPE

+46"/20

EXAM LIGHT

+42"

OTOSCOPE

+46"/19

EXAM LIGHT

+42"

OTOSCOPE

+46"

EXAM LIGHT

+42"

OTOSCOPE

+42"

OTOSCOPE

ELECTROMYOGRAPH

OTOSCOPE

+46"

EWC

+46"

SCALE

A/8A/8

OTOSCOPE/11

A

A

OTOSCOPE

+46"/5

+46"/33

+46"/18

+46"/16

+42"

OTOSCOPE

EXAM LIGHT

LP4-L4-120VE

LP4-L4-277VE

SSU-2

+42"/21

+42"

OTOSCOPE

+42"

OTOSCOPE

28 28

29 29

11 21 4

1119 19

30 30 31 31

15 18 15

35 32 32

373434 36

EX. LP2-JB4.4-120VC-28,30EX. LP2-JB4.4-120VC-28,30

249 24 249

22 22

10 10

EXAM LIGHT

EXAM LIGHT

EXAM LIGHT

12,14

CU-2

A U

T O

M A

T

IC

D O

O R

O P

E R

A T O

R

FDS-30-208

DS-400-208

LP4-L4-120VN

AUTOMATIC DOOR OPERATOR/40

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:0

P

M

LEVEL 04 - ELECTRICAL POWER

SCOPRZ ANUSHA

BID DOCUMENTS 589A4-19-103

1-EP102

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

N

O R HT

1/8" = 1'-0"1

LEVEL 04 - ELECTRICAL POWER

GENERAL SHEET NOTES:

1. ALL NORMAL POWER CIRCUITS SHALL BE FED

FROM EX. LP4-L4-120VN. ALL CRITICAL POWER

CIRCUITS SERVING SHADED DEVICES SHALL

BE FED FROM EX. LP4-L4-120VC.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01

KEYNOTES:

1. NEW PANELBOARD TO REPLACE EXISTING.

REROUTE AND RECONNECT EXISTING

CONDUIT AND CONDUCTORS. E.C. TO

CONFIRM CIRCUITS SERVING AREAS OUTSIDE

AREA OF WORK. THESE CIRCUITS SHALL

REMAIN ENERGIZED DURING REPLACEMENT

OF PANELBOARD. COORDINATE ANY

REQUIRED DOWNTIME WITH CONTRACTING

OFFICER. PROVIDE NEW CIRCUIT BREAKERS

FOR ALL BRANCH CIRCUITS. REFER TO SHEET

1-ED101 - ELECTRICAL DEMOLITION FOR

INFORMATION ABOUT REMOVAL OF THE

EXISTING PANELBOARD. REFER TO PANEL

SCHEUDLES ON SHEET 1-E-501 - ELECTRICAL

SCHEDULES FOR PANEL RATING.

2. NEW PANELBOARD TO REPLACE EXISTING.

REROUTE EXISTING CONDUIT AND

CONDUTORS TO NEW 400A NON-FUSED

DISCONNECT SWITCH. CONNECT DISCONNECT

SWITCH TO RELOCATED PANEL. PROVIDE NEW

CIRCUIT BREAKERS FOR ALL BRANCH

CIRCUITS. REFER TO SHEET 1-ED101 -

ELECTRICAL DEMOLITION FOR INFORMATION

ABOUT REMOVAL OF THE EXISTING

PANELBOARD. REFER TO PANEL SCHEUDLES

ON SHEET 1-E-501 - ELECTRICAL SCHEDULES

FOR PANEL RATING.

3. INDOOR UNIT SSU-2 IS POWERED BY THE

OUTDOOR UNIT THROUGH FIELD SUPPLIED

INTERCONNECTED WIRING.

4. MOUNT RECEPTACLES TO RACK. COORDINATE

WITH OIT EQUIPMENT INSTALLER.

Revisions: Date:

A

A1

F

A1

F A

S D

S D

A R

D

A3 A1

A1A1

A1 A1 A1

A1

A1

A3

A1

A A1

A1

A

A

A3

V1

V1

A

A3

A1

A1

A1 A1

A1

A

A

SD

AR DH

DH

ARDH

DH

SD ARDSD

SD SD SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SD

SDSD

SD

SD SD

SD

NaN M L

2.8

3.7

4.6

5.5

6.3

K J H G F E

CLINIC OFFICE

A200

CLINIC OFFICE

A203

CLINIC OFFICE

A204

CLINIC OFFICE

A202

OBSERVATION

A201B CORRIDOR 2

C2A02

PSYCH. RES

A201

PSYCH. RES

A206

EXIST. STRG

A206A

CORRIDOR 1

C2A01 PSYCH. RES

A205

EXIST. ELEC

A207

CORRIDOR 3

C2A04

CORRIDOR 4

C2A03

TMS ROOM

A208

TMS ROOM

A210

EXIST. SOC WRK

A212

EXIST. SOC WRK

A213

CORRIDOR 5

C2A05

CARE COORDINATOR

A209

CARE COORDINATOR

A211

STAFF RESTROOM

A214

HAC

A215

EXIST. IT

A217

WOMEN'S

A221

MEN'S

A222

EXIST. ELEC. CLO.

A216

CORRIDOR 6

C2A07

CORRIDOR 8

C2A08

GROUP ROOM WAITING AREA

A226

WAITING 2

A224

WAITING 1

A223

WORK AREA

A223B

COPIER/PAPER STORAGE AREA

A223C

MAIL AREA

A223D

CHECKOUT/CHECK IN

A223A

GROUP ROOM

A219

GROUP ROOM

A218

GROUP ROOM

A220

VESTIBULE

A200A

1 1

DH

DH DH

DH

1 1

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:0

P

M

LEVEL 02 - FIRE ALARM

MARHAR EVAMIL

BID DOCUMENTS 589A4-19-103

1-FA101

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

N O R

HT

1/8" = 1'-0"1

LEVEL 02 - FIRE ALARM

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01

KEYNOTES:

1. CONTRACTOR TO VERIFY EXISTING ELEVATOR

LOBBY SMOKE DETECTOR. IF AN EXISTING

DETECTOR IS PRESENT CREDIT COST OF NEW

SMOKE DETECTOR BACK TO OWNER.

2. OPERATION OF A SMOKE DETECTOR AT A

CORRIDOR DOOR USED FOR AUTOMATIC

CLOSING SHALL ALSO RELEASE ONLY THE

MAGNETIC DOOR HOLDERS IN THAT SMOKE

ZONE.

GENERAL SHEET NOTES:

1. COORDINATE ALL DEVICE LOCATIONS ON

CEILING WITH ALL OTHER TRADES. VERIFY ANY

MODIFIED DEVICE LOCATIONS CAUSED BY

COORDINATION, NOT SHOWN ON THIS SHEET,

STILL COMPLY WITH ALL APPLICABLE CODES

AND GUIDELINES.

2. VERIFY CORRECT OPERATION OF EXISTING

FIRE ALARM SYSTEM SYSTEM PRIOR TO

MAKING ANY MODIFICATIONS.

3. COORDINATE ALL MODIFICATIONS, INCLUDING

DEVICE TERMINATIONS AND ANY

PROGRAMMING CHANGES, WITH THE

CONTRACTOR RESPONSIBLE FOR

MAINTENANCE OF THE EXISTING SYSTEM.

ENGAGE SERVICES OF THAT CONTRACTOR

UNDER THIS CONTRACT AS NEEDED.

Revisions: Date:

A1

A1

A1

A1

A1 V1

V1

V1

A

V1

V1

V1

V1

A1

A1

A1

A

A

ARD

A R

D

F

SD

SD SD

SD

SD

SD

SD

SD

Na N M L

2.8

3.7

4.6

5.5

6.3

K J H G F

7.2

8.3

9.1

EMG/SCI

NURSE NAVIGATOR

PAIN & PMR VVC/TM

PAIN BH

PAIN PHARM

PAIN EXAM ROOM 2

PAIN EXAM ROOM 3

PAIN EXAM ROOM 4

WORKSTATION

TOILET

PAIN SWAMP

EXISTING ELEC.

492A

SOILED HOLDING

TOILET

PAIN EXAM

PM&R SWAMP

PM&R EXAM ROOM 4

PM&R EXAM ROOM 3

PM&R EXAM ROOM 1

PM&R EXAM ROOM 2

MSA CHECKIN/OUT

PROCEDURE ROOM

CLEAN SUPPLY

PROCEDURE ROOM

OIT

CORRIDOR

C498

Room

A200BBBRoom

A200CCC

NURSES

CORRIDOR

C498

CORRIDOR

C496

CORRIDOR

C499

C O

R R

ID

O

R

C

HATCHED AREA NOT

IN PROJECT SCOPE

1 1

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:0

P

M

LEVEL 04 - FIRE ALARM

SCOPRZ ANUSHA

BID DOCUMENTS 589A4-19-103

1-FA102

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

N

O R HT

1/8" = 1'-0"1

LEVEL 04 - FIRE ALARM

GENERAL SHEET NOTES:

1. COORDINATE ALL DEVICE LOCATIONS ON

CEILING WITH ALL OTHER TRADES. VERIFY ANY

MODIFIED DEVICE LOCATIONS CAUSED BY

COORDINATION, NOT SHOWN ON THIS SHEET,

STILL COMPLY WITH ALL APPLICABLE CODES

AND GUIDELINES.

2. VERIFY CORRECT OPERATION OF EXISTING

FIRE ALARM SYSTEM SYSTEM PRIOR TO

MAKING ANY MODIFICATIONS.

3. COORDINATE ALL MODIFICATIONS, INCLUDING

DEVICE TERMINATIONS AND ANY

PROGRAMMING CHANGES, WITH THE

CONTRACTOR RESPONSIBLE FOR

MAINTENANCE OF THE EXISTING SYSTEM.

ENGAGE SERVICES OF THAT CONTRACTOR

UNDER THIS CONTRACT AS NEEDED.

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01Revisions: Date:

SEE ARCHITECTURAL

PLANS FOR WALL CONSTRUCTION

PLASTER RING TO COME

WITHIN 1/8" OF FINAL SURFACE

STUD

MOUNTING BRACKET SHALL PROVIDE

SUPPORT FROM STUD AND BACK OF

WALL OR TWO STUDS.

NOTES :

1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY

MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR

WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE

MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES

THE SAME RESULTS.

2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE

WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.

3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23.

MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# .

FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-

LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.

4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON

COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE

DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT

OPENINGS WITH MOUNTING BRACKETS.

1 5/64"12"

WALL WITH INSULATION

FLANGES ON EACH SIDE

OF WALL. CAULK AT

WALL AND SLEEVE.

CONDUIT

SHEET METAL SLEEVE, 2"

LARGER THAN CONDUIT

OVERALL DIAMETER.

PACK AROUND CONDUIT WITH

FIBERGLASS INSULATION

ESCUTCHEON PLATES

ON BOTH SIDES

FIXTURE

CEILING T'S LAY-IN CEILING

CEILING TIE WIRE

THREADED ROD

SUPPORT 1 PER

LUMINAIRE

4" BOX

ADJUSTABLE SUPPORT BRACKET,

2 PER LUMINAIRE. (ATTACH TO

CEILING GRID CHANNELS)

SUPPORT BOX AND CONDUIT

FROM STRUCTURE

FLEX CONDUIT

LENGTH: 4'-0" MIN. 6'-0" MAX.

RATED WALL

(CONSTRUCTION VARIES)

NOTE 2

FIRE SEALANT

NOTE 3

FIRE SEALANT

PENETRATING ITEM

NOTE 4

NOTE 3

NOTE 2

PENETRATING ITEM

NOTE 4

NOTE 3

RATED FLOOR

(CONSTRUCTION VARIES)

NOTES :

1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR

FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL

MOVEMENT. REFER TO SPECIFICATION SECTION 07 84 00 FOR SELECTION OF THROUGH

PENETRATION FIRE STOPPING.

2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH

CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND

DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND

SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR

SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE

SELECTED FIRE STOP SYSTEM.

3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE

STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING.

SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM

WITHOUT MOVEMENT OF FIRE BARRIER.

4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF

WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO

FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE

PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.

OC

LS

LOCAL

LIGHTING

CONTROLLER

S

D

NORMAL POWER

TRANSFER SWITCH, INVERTER,

OR EQUIVALENT UL 1008

NORMAL PANEL

BOARD

EMERGENCY/LIFE

SAFETY PANEL

BOARD

LIGHTING SENSORS, SWITCHES, AND

DIMMERS. REFER TO PLANS FOR

APPLICABLE DEVICES IN EACH SPACE (TYP)

TYPICAL OF LOCAL LIGHTING CONTROLLER,

REFER TO MANUFACTURER INSTRUCTIONS

AND REQUIREMENTS

NORMAL LUMINAIRES

EMERGENCY LUMINAIRES

ALCR

0-10V DIMMING CONTROL TO

LUMINARES WHEN APPLICABLE (TYP)

NOTES:

1. THE ALCR RELAY DIAGRAM IS INTENDED TO CONVEY INTENDED OPERATION AND

SPECIFICALLY DOES NOT INDICATE QUANTITIES, ALL DEVICES, WIRING, AND CONNECTIONS

REQUIRED. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND

REQUIREMENTS.

2. MOUNT LOCAL LIGHTING CONTROLLERS ABOVE FINISHED CEILING NEAR ROOM ENTRANCE.

IN A CORRIDOR, MOUNT NEAR ONE END OF CORRIDOR AND ADJACENT TO FIRST SENSOR OR

CONTROL DEVICE.

3. MOUNT ALCR ADJACENT TO LIGHTING CONTROLLER ABOVE ACCESSIBLE FINISHED CEILING.

4. FIRE ALARM ADDRESSABLE RELAY SHALL OVERRIDE LOCAL LIGHTING CONTROLS UPON FIRE

ALARM OR TEST.

EMERGENCY POWER(1) - STAINLESS

STEEL DRAW BAND

PRE-MOLDED RUBBER

PIPE FLASHING

ROOF INSULATION

CONDUIT,

BY E.C.SEALANT (URETHANE)

ROOF DECK

TOP OF STEEL JOIST

NOTES:

1. CONDUIT SHALL BE SUPPORTED WITHIN 24 INCHES ABOVE AND BELOW ROOF.

2. VERIFY FINAL REQUIREMENTS WITH GENERAL CONTRACTOR (G.C.) AND

ROOFING INSTALLER PRIOR TO INSTALLATION.

SYSTEM INPUTS

SEQUENCE OF

OPERATION

P A

N E

L /A

N N

U N

C

IA

T O

R A

L A

R M

I N

D

IC

A T

IO

N

P A

N E

L /A

N N

U N

C

IA

T O

R S

U P

E R

V

IS

O R

Y I N

D

IC

A T

IO

N

P A

N E

L /A

N N

U N

C

IA

T O

R T R

O U

B L E

I N

D

IC

A T

IO

N

A U

D

IB

L E

A L A

R M

S

Q U

E N

C E

V

IS

U A

L A

L A

R M

Q U

E N

C E

S M

O K

E D

A M

P

R

C O

N T R

O L S

E Q

U E

N C

E

D O

O R

H O

L D

E R

S E

Q U

E N

C E

ARARD

MANUAL PULL STATION

SMOKE DETECTOR

SMOKE DETECTOR

FOR HVAC CONTROL

SMOKE DETECTOR FOR

SMOKE DAMPER CONTROL

SMOKE DETECTORS IN

ELEVATOR LOBBIES

F

SD

SD SD

D

SD SD

D

SD

X

X

X

X

X

X X

X

X

X

X X X

X

X X

X

X

X

NOTES:

1. ALL SYSTEM EVENTS SHALL BE LOGGED, PRINTED, AND DISPLAYED ON THE GRAPHICAL

INTERFACE, IF APPLICABLE. SEE SPECIFICATIONS FOR MORE INFORMATION AND

DESCRIPTIONS OF SEQUENCES OF OPERATION.

2. PARTIAL EVACUATION OR RELOCATION OF OCCUPANTS IS THE STANDARD OPERATING

PROCEDURE FOR THIS FACILITY IN THE EVENT OF AN ALARM. THEREFORE, ALL

NOTIFICATION APPLIANCE CIRCUITS MUST BE INSTALLED AND PROTECTED IN

ACCORDANCE WITH THE CIRCUIT SURVIVABILITY REQUIREMENTS DESCRIBED IN NFPA

72. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

X

X

X

X

X

X

X

NEPCI

C I

SIGNAL LINE CIRCUIT

(SLC)

NOTIFICATION APPLIANCE CIRCUIT (NAC)

AR

ARD

TO DOOR HOLD DEVICES (TYP)

TO FIRE/SMOKE DAMPER CONTROL

DH

RI SD

F SD

V

KEYNOTES:

1. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE.

REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

2. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT

AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

3. PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF

NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS

AND ACCEPTABLE MOUNTING LOCATIONS.

EXISTING

FIRE ALARM

CONTROL

PANEL

NOTES:

1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS

AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR

DISTANCES.

2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND

MANUFACTURER'S RECOMMENDATIONS.

3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE

VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF

CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.

4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE

CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.

5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR

PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.

A

SD

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:0

:4

P

M

ELECTRICAL DETAILS

MARHAR EVAMIL

BID DOCUMENTS 589A4-19-103

1-E-300

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

NO SCALE

BACKBOX MOUNTING DETAIL

5 NO SCALE

CONDUIT WALL PENETRATION

NO SCALE

EXIT SIGN MOUNTING DETAIL

NO SCALE

FIRE BARRIER PENETRATION

NO SCALE

AUTOMATIC LOAD CONTROL RELAY DIAGRAM [ALCR]

15 SUNNEN DR SUITE 104

SAINT LOUIS, MO 63143

314.645.1132 FAX: 314.645.1173

www.imegcorp.com # 17002665.01

NO SCALE

CONDUIT ROOF PENETRATION

NO SCALE7

FIRE ALARM OPERATION MATRIX

NO SCALE8

FIRE ALARM RISER

Revisions: Date:

BRANCH CIRCUIT WIRING KEY

WIRE

ID 2 WIRE 3 WIRE 4 WIRE

THHW/THWN COPPER

CONDUCTORS

EQUIPMENT

GROUNDING

CONDUCTOR CONDUIT

A# 2#12 3#12 4#12 1#12 3/4"

B# 2#10 3#10 4#10 1#10 3/4"

C# 2#8 3#8 4#8 1#10 3/4"

D# 2#6 3#6 4#6 1#10 1"

E# 2#4 3#4 4#4 1#8 1 1/4"

G# 2#2 3#2 4#2 1#8 1 1/4"

H# 2#1 3#1 4#1 1#6 1 1/2"

J# 2#1/0 3#1/0 4#1/0 1#6 2"

ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND

CONDUCTOR

F# 2#3 3#3 4#3 1#8 1 1/4"

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic

S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:Consultant:

Sprinklered

Fully Sprinklered

C R e v it L o c a l F ile s \M

E P

T

.0

B H

C lin ic R e n o v a ti o n

C

E v a n

.H .M ill e r.

rv t

/1

/2

:2

:5

P

M

ELECTRICAL SCHEDULES

MARHAR EVAMIL

BID DOCUMENTS 589A4-19-103

1-E-500

Columbia Harry S. Truman Memorial

Veterans Hospital

Columbia, Missouri

05/13/2021

REFER TO SPECIFICATION SECTION LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

INTERIOR CORRELATED COLOR TEMPERATURE 3500K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.

CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.

UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE MOUNTING

HEIGHTS.

DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)

DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE

0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC

(TYPE) DRIVER:

PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED

P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED

FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER

CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE

CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED

(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP

CFSA - COLOR-FINISH SELECTION BY ARCHITECT

PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)

FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR

RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC

RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE

FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE

FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR

(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC

LED LUMINAIRE SCHEDULE

ITEM DESCRIPTION L/L MTG

DIMENSIONS WATT LED DRIVER

BASIS OF DESIGNL W H DIA.

ANSI

WATTS PER TYPE QTY

ABSOLUTE

LUMENS

(MIN) VOLTS TYPE

EM1 EMERGENCY UNIT, TWO ADJUSTABLE 6 VOLT

HEADS, WHITE THERMOPLASTIC HOUSING.

O WL 1'-2" 6" 3

51/64"

7 W FIX IN 2 6 VOLT (2

INCLUDED)

277 V EM DUAL-LITE LZ2

F1 6" CLEAR, SELF-FLANGED DOWNLIGHT WITH

MEDIUM WIDE DISTRIBUTION. REQUIRED

DRYWALL CONSTRUCTION KIT IN.

O RE 7" 6" 15 W FIX LED 1 L.E.D. 277 V 0-10V CALCULITE LED GEN 3 6"

F2 4' WALL-MOUNTED VANITY FIXTURE, FROSTED

ACRYLIC LENS.

O WL 2'-0" 6 1/2" 5 3/4" 0 W FIX LED 1 L.E.D. 277 V 0-10V WMA LED ARCHITECTURAL WALL

MOUNT

F3 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11

51/64"

1'-11 51/64"

39/64"

25 W FIX LED 1 3470 277 V 0-10V CREE LIGHTING ZR22

F3A 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11

51/64"

1'-11 51/64"

39/64"

29 W FIX LED 1 4050 277 V 0-10V CREE LIGHTING ZR22

F3B SAME AS F3 WITH DRY WALL CONSTRUCTION

KIT.

O RE 1'-11

51/64"

1'-11 51/64"

39/64"

29 W FIX LED 1 4050 277 V 0-10V CREE LIGHTING ZR22

F3C 2X2 RECESSED TROFFER FIXTURE. 5000K,

85CRI.

O RE 2'-0" 2'-0" 3 1/4" 35 W FIX LED 1 4940 277 V 0-10V CREE LIGHTING ZR22

F3D 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11

51/64"

1'-11 51/64"

39/64"

35 W FIX LED 1 4940 277 V 0-10V CREE LIGHTING ZR22

F3R REUSED 2x2 TROFFER FIXTURE. O RE 2'-0" 2'-0" 3 1/4" 35 W FIX LED 1 L.E.D. 277 V 0-10V RELOCATED LED 2x2 FIXTURE

F4 2X4 DIRECT/INDIRECT LIGHT FIXTURE. 5000K,

85 CRI.

O RE 4'-0" 2'-0" 3 1/4" 40 W FIX LED 1 4800 277 V 0-10V LITHONIA 2VTL4

F5 4" RECESSED DOWNLIGHT. O RE 7" 4" 15 W FIX LED 1 1500 277 V 0-10V CALCULITE LED GEN 3 4"

F6 4' INDUSTRIAL WITH 10% UPLIGHT, BAKED

ENAMEL FINISH. 3500K. 80CRI.

O SP 4'-0" 1'-0" 4 1/4" 22 W FIX LED 2 3119 277 V EM METALUX SNLED

X1 EDGE-LIT SINGLE FACED EXIT SIGN,

INJECTION MOLDED ACRYLIC MIRROR LENS

AND EXTRUDED ALUMINUM HOUSING.

HOUSING FINISH AND COLORS SELECTED BY

ARCHITECT. VERIFY RECESSED END, BACK OR

CEILING MOUNTING AND ARROWS WITH

PLANS.

O CL 1'-1" 2" 9" 4 W FIX LED 1 L.E.D. 277 V EM LITHONIA 202 LT 0 - EDG 1R

(SINGLE FACE) OR APPROVED

EQUAL

X2 EDGE-LIT DOUBLE FACED EXIT SIGN,

INJECTION MOLDED ACRYLIC MIRROR LENS

AND EXTRUDED ALUMINUM HOUSING.

HOUSING FINISH AND COLORS SELECTED BY

ARCHITECT. VERIFY RECESSED END, BACK OR

CEILING MOUNTING AND ARROWS WITH

PLANS.

O CL 1'-1" 2" 9" 4 W FIX LED 1 L.E.D. 277 V EM LITHONIA 202 LT 0 - EDG 2R

(DOUBLE FACE) OR APPROVED

EQUAL

LIGHTING SEQUENCE OF OPERATION

PLAN ID LIGHTING SWITCHED

{LD1} Sequence: Dimmed lights are controlled in this space ON: The luminaries turn on via vacancy sensor or occupancy sensor. If applicable, UL924 devices shall be used control emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.

ADJUST: If applicable, the day lighting zone luminaries will continuously adjust to the presence of daylight to 30 foot candles at working desk level OFF: The lights turn off manually using the wall controller. After the space has been vacant for 20 minutes, the lights will automatically turn off.ntrol emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.

{LD2} Sequence: Dimmed lights are controlled in this space.

ON: The luminaires turn on via wall control station.

OFF: The lights turn off using the wall control station.

{LS1} Sequence: Switched lights are controlled in this space ON: The lights turn on using the key switches or occupancy sensor. UL924 devices shall be used control emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.

OFF: The lights turn off using the key switches. After the space has been vacant for 20 minutes, the lights will automatically turn off.

{LS2} Sequence: Switched lights are controlled in this space ON: The lights turn on using switches or occupancy sensor.

OFF: The lights turn off manually using the wall controller. After the space has been vacant for 20 minutes, the lights will automatically turn off.

{LS3} Sequence: Switched lights are controlled in this space.

ON: The normal lights turn on by occupancy sensors in the corridor. Night lights will remain on at all times. Existing lighting control panel shall override occupancy sensors during central schedule ON conditions.

OFF: The normal lights turn off after the space has been vacant for 20 minutes. Existing lighting control panel shall override occupancy sensors during central schedule OFF conditions.

{LS4} Sequence: Switched lights are controlled in this space.

ON: The lights turn on via switches or occupancy sensor. UL924 devices shall be used to control emergency luminaries with normal. The emergency luminaires (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.

OFF: The lights turn off using the switches. After the space has been vacant for 20 minutes, the lights will automatically shut off.

{LS5} Sequence: Switched lights are controlled in this space.

ON: The lights turn on using switches.

OFF: The lights turn off manually using switches.

[Key...

Total Additional Amps:

50.83 67.91 46.5

Total Additional Load:

6.03 kVA 8.08 kVA 5.58 kVA

-- 41 -- -- -- -- 0 0 -- 1 20 A SPARE 42

-- 39 -- -- -- -- 0 0.52 -- -- -- -- 40 --

37 EXISTING MAIN 20 A 3 -- 0 0.52 A2 2 15 A CU-1 38

35 SPARE 20 A 1 -- 0 0.72 A2 1 20 A DOOR OPERATOR MEN A222 36

33 CORRIDOR C2A08 24V XFMR 20 A 1 A2 0 0.72 A2 1 20 A DOOR OPERATOR WOMEN A221 34

31 2ND FL VAV CONTROLS EAST 20 A 1 A2 0 0.72 A2 1 20 A DOOR OPERATORS C2A03 32

29 RECS - CORRIDOR 20 A 1 A2 1.26 0.72 A2 1 20 A DOOR OPERATORS C2A08 30

27 RECS - C2A08 MONITOR, KIOSK 20 A 1 A2 1.08 1.44 A2 1 20 A RECS - 223B 28

25 RECS - A224 20 A 1 A2 1.08 1.44 A2 1 20 A RECS - 223A 26

23 GROUP A220 PROJEC, MONITOR 20 A 1 A2 0 1.62 A2 1 20 A RECS - 223A, A223 24

21 RECS - A220 20 A 1 A2 1.62 0.54 A2 1 20 A RECS - CORRIDOR 22

19 RECS - A218 EAST 20 A 1 A2 0.9 0.83 A2 1 20 A ROOF - EF-1 20

17 RECS - A219 EAST 20 A 1 A2 0.9 0 A2 1 20 A AUTO FLUSH VALVES MENS 221 18

15 RECS - A219 WEST 20 A 1 A2 0.9 0 A2 1 20 A AUTO FLUSH WOMENS 221 16

13 GROUP A218, A219 OVERHEAD 20 A 1 A2 0 0.54 A2 1 20 A REC - A221,A222 EWC 14

11 GROUP A218, A219 MONITOR 20 A 1 A2 0 0.36 A2 1 20 A RCPT - A217 OIT RACK QUAD 1 12

9 RECS - A218 WEST 20 A 1 A2 0.9 0.36 A2 1 20 A RCPT - A217 OIT RACK QUAD 1 10

7 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 8

5 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 6

3 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 4

1 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 2

CKT

NO. LOAD DESCRIPTION

OVERCURRET

PROTECTION

AMPS P

WIRE

ID

A B C

WIRE

ID

OVERCURRET

PROTECTION

P AMPS LOAD DESCRIPTION

CKT

NO.

Panel Notes: SECTION 2 OF 2. EXISTING PANEL. NEW BREAKERS SHALL MATCH MANUFACTURER AND SCCR RATING OF EXISTING PANEL. ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS OTHERWISE NOTED. TOTALS AT BOTTOM OF SCHEDULE REFLECT ADDITIONAL LOAD ONLY.

LOCATION: EXIST. ELEC A207 WIRE: 4

FED FROM: EXISTING GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 100 A/MCB

PANEL NAME: EX. LP2-L4-120VN (SECT.2) CONNECTED 19.7 kVA

[Key...

Total Additional Amps:

8.63 9.74 0

Total Additional Load:

2.07 kVA 2.38 kVA 0 kVA

-- 41 -- -- -- -- 0 0 -- -- -- SPACE 42 --

-- 39 -- -- -- -- 0 0 -- -- -- SPACE 40 --

37 MAIN 100 A 3 -- 0 0 -- -- -- SPACE 38 --

-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --

-- 33 SPACE -- -- -- 0 0 -- -- -- SPACE 34 --

-- 31 SPACE -- -- -- 0 0 -- -- -- SPACE 32 --

-- 29 SPACE -- -- -- 0 0 -- -- -- SPACE 30 --

27 LGTS -CORR. C2A08,A226 20 A 1 A2 1.1 1.28 A2 1 20 A LGTS - WAITING A223, A224 28

25 LGTS - PSYCH A205,A208,A210 20 A 1 A2 1.61 0.46 A2 1 20 A LGTS - CORR. C2A03 26

-- 23 -- -- -- -- 0 0 -- -- -- -- 24 --

-- 21 -- -- -- -- 0 0 -- -- -- -- 22 --

19 EXISTING 15 A 3 -- 0 0 -- 3 70 A EXISTING 20

17 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 18 --

15 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 16 --

13 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 14 --

11 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 12 --

9 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 10

7 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 8

5 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 6

3 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 4

1 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 2

CKT

NO. LOAD DESCRIPTION

OVERCURRET

PROTECTION

AMPS P

WIRE

ID

A B C

WIRE

ID

OVERCURRET

PROTECTION

P AMPS LOAD DESCRIPTION

CKT

NO.

Panel Notes: EXISTING PANEL. ANY ADDITIONS SHALL MATCH MANUFACTURER AND SCCR RATING. ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS

OTHERWISE NOTED. TOTALS AT BOTTOM OF SCHEDULE REFLECT ADDITIONAL LOAD ONLY.

LOCATION: EXIST. ELEC A207 WIRE: 4

FED FROM: EXISTING GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 480/277 Wye

TYPE: BOLT-ON MAIN: 100 A/MCB

PANEL NAME: EX. LP2-L4-277VN CONNECTED 4.5 kVA

[Key...

Total Amps: 44.15 45.99 25.5

Total Load: 5 kVA 5.22 kVA 3.06 kVA

-- 59 SPACE -- -- -- 0 0 -- -- -- SPACE 60 --

-- 57 SPACE -- -- -- 0 0 -- -- -- SPACE 58 --

-- 55 SPACE -- -- -- 0 0 -- -- -- SPACE 56 --

53 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 54

51 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 52

49 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 50

47 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 48

45 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 46

43 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 44

41 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 42

39 RCPTS - CARE COORD. A209 20 A 1 A2 0.9 0 -- 1 20 A SPARE 40

37 RCPTS - CARE COORD. A209 20 A 1 A2 0.9 0 -- 1 20 A SPARE 38

35 RCPTS - TMS ROOM A208 20 A 1 A2 0.9 0 -- 1 20 A SPARE 36

33 RCPTS - TMS ROOM A210 20 A 1 A2 0.9 0 -- 1 20 A SPARE 34

31 DOOR OPERATOR C2A07 20 A 1 A2 0.86 0.72 A2 1 20 A RCPTS - A214, A215 32

29 2ND FL VAV CONTROLS WEST 20 A 1 A2 0 0 -- 1 20 A EXISTING LOAD 30

27 CORRIODR C2A04 24V XFMR 20 A 1 A2 0 0 -- 1 20 A EXISTING LOAD 28

25 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 26

23 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 24

21 RCPTS - CORR C2A03, C2A04 20 A 1 A2 1.08 0 -- 1 20 A EXISTING LOAD 22

19 RCPTS - CORR C2A01, C200A 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 20

17 RCPTS - PSYCH. RES A206 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 18

15 RCPTS - PSYCH. RES A201 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 16

13 EWC - CORRIDOR 20 A 1 A2 0.18 0 -- 1 20 A EXISTING LOAD 14

11 RCPTS - OBSERVATION A201B 20 A 1 A2 0.72 0 -- -- -- -- 12 --

9 RCPTS - CLINIC OFFICE A200 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 3 10

7 RCPTS - CLINIC OFFICE A202 20 A 1 A2 0.9 0 -- -- -- -- 8 --

5 RCPTS - CLINIC OFFICE A203 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 2 6

3 RCPTS - CLINIC OFFICE A204 20 A 1 A2 0.9 0 -- -- -- -- 4 --

1 RCPTS - PSYCH. RES A205 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 1 2

CKT

NO. LOAD DESCRIPTION

OVERCURRET

PROTECTION

AMPS P

WIRE

ID

A B C

WIRE

ID

OVERCURRET

PROTECTION

P AMPS LOAD DESCRIPTION

CKT

NO.

Panel Notes: ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS OTHERWISE NOTED.

SCCR: 22,000

LOCATION: EXIST. ELEC A207 WIRE: 4

FED FROM: EXISTING GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 100 A/MCB

PANEL NAME: PLP2-L4-208VN CONNECTED 13.3 kVA

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. &...

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE... TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1...

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES *... PF - PHASE LOSS PROTECTION (5 HP OR...

DISCONNECT TYPE: REMARKS:

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

E - DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING CIRCUIT

VOLTAGE POLES

NEMA

ENCLOSURE REMARKS BASIS OF DESIGNTYPE RATING

DS-30-120 NF 30 A 120 V 3 1 SQUARE D

DS-400-208 NF 400 A 208 V 3 1 SQUARE D

FDS-30-208 F 30 A 208 V 3 1 PROVIDE 15A FUSE SQUARE D

[Key...

Total Additional Amps:

2.79 4.55 0

Total Additional Load:

0.67 kVA 1.16 kVA 0 kVA

-- 29 -- -- -- -- 0 0 -- 1 20 A SPARE 30

-- 27 -- -- -- -- 0 0 -- 1 20 A SPARE 28

25 MAIN 20 A 3 -- 0 0 -- 1 20 A SPARE 26

23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24

21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22

19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20

17 SPARE 20 A 1 -- 0 0…