Amendment 2-08 Electrical_ADD001.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25521R0089
About this file
This document provides details for a federal solicitation to renovate a behavioral health clinic located at a Veterans Affairs medical center. The project scope includes renovating approximately 9,706 square feet on the second floor and 5,089 square feet on the fourth floor to consolidate behavioral health services. Renovations will address electrical, HVAC, plumbing, fire protection, data/voice systems, and interior finishes. The design allows for a phased construction approach to minimize disruptions to patient care in an active facility. The project cost is estimated between $2-5 million. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and utilize the Lowest Price Technically Acceptable source selection process. The North American Industry Classification Code is 236220 and small business size standard is $39.5 million. Proposals are due around July 9, 2021.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
GFI GROUND FAULT INTERRUPTER
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET 1-E-500.
3. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
4. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND
OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.
5. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
EWC ELECTRIC WATER COOLER
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN
EACH PHASE.
3. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN A SEPARATE
RACEWAY FROM ALL OTHER CIRCUITS.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX
CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS
SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN
GRILLE.
11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
13. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE
EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH
IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
15. ELECTRICAL INDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR
COLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
NORMAL BRANCH LUMINAIRE
EMERGENCY CRITICAL BRANCH LUMINAIRE
EMERGENCY LIFE SAFETY BRANCH LUMINAIRE
UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE'
LUMINAIRE SYMBOL KEY
SYMBOL: DESCRIPTION:
26 29 21MX-# DISCONNECT SWITCH, REFER TO DISCONNECT AND STARTER
SCHEDULE
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:
RELATED
SPECIFICATION
28 31 00 FIRE ALARM VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
V1 V3
V7 VH
28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
A1 A3
A7 AH
AS
28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE -
CEILING MOUNTED A
SD 28 31 00 FIRE ALARM DOOR HOLD SMOKE
DETECTOR - CEILING MOUNTED
SD 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
28 31 00 FIRE ALARM MANUAL PULL STATIONF
28 31 00 FIRE ALARM SMOKE, FIRE/SMOKE DAMPERSD
VS
26 09 23 SWITCH - SINGLE POLE
SWITCH - OCCUPANCY SENSOR
WALL SWITCH
O
OC OCCUPANCY SENSOR - ULTRASONIC 360
DEGREE COVERAGEU
OC OCCUPANCY SENSOR - DUAL TECHNOLOGY
D
CEILING MOUNTED OCCUPANCY SENSOR
EXTENDED RANGE
LS DAYLIGHT LEVEL SENSOR
26 09 23
26 09 23
26 09 23
26 09 23
26 28 16 DISCONNECT, REFER TO DISC/STA SCHEDULE
26 09 23
DIMMER - LED26 09 23
SYMBOL:
SPEC
SECTION:
DESCRIPTION:
ELECTRICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
26 05 33 JUNCTION BOX
J
J
26 05 33 ELECTRICAL CONNECTION
E
E
SYMBOL:
SPEC
SECTION:
DESCRIPTION:
TROFFER
DOWNLIGHT LUMINAIRE
INDUSTRIAL LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
SYMBOL:
SPEC
SECTION:
DESCRIPTION:
WALL/CEILING EMERGENCY EXIT SIGN
26 27 26 DUPLEX RECEPTACLE, 125V
26 27 26 DUPLEX GFI RECEPTACLE, 125V
26 27 26 QUAD RECEPTACLE, 125V
SYMBOL:
SPEC
SECTION:
DESCRIPTION:
REFER TO
LUMINAIRE
SCHEDULE
28 31 00 SMOKE, FIRE/SMOKE DAMPER
CONTROLLER
ARD
SPEC
SECTION:
26 27 26 SIMPLEX RECEPTACLE, 6-20R, 250V
ELECTRICAL SYMBOL LIST
ELECTRICAL SYMBOL LIST
ELECTRICAL SYMBOL LIST
ELECTRICAL SYMBOL LIST
OC
E
SW WALL CONTROL STATION26 09 23
DIMMER - WALL DIMMER OCCUPANCY
SENSOR
26 09 23 O
SWITCH - THREE WAY - KEY LOCK
K3
26 09 23
VC VACANCY SENSOR - DUAL TECHNOLOGY
D
26 09 23
SWITCH - SINGLE POLE - KEY LOCK
K
26 09 23
DIMMER - LED - VACANCY SENSOR WALL
SWITCH
26 09 23 V
28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
A3
28 31 00 FIRE ALARM ELECTROMAGNETIC DOOR HOLD
DEVICE
DH
SD 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING
MOUNTED
DH
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE CONSTRUCTION MANAGER PRIOR TO BIDDING IF OTHER UTILITIES
ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF
WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF
ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH
CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH
HIS/HER WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS, PHASING SCHEDULES AND
FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS
DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND
TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE
REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
FIRE PROTECTION CONTRACTORF.P.C.
AUTOMATIC TEMPERATURE CONTROL CONTRACTORA.T.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
NOT ALL MAY APPLY
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
GENERAL TECHNOLOGY EQUIPMENT
SCHEDULE AND SPECIFICATIONS FOR
DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
NURSE CALL ROUGH-IN T-SERIES E.C. E.C.
NURSE CALL EQUIPMENT, CABLING,
AND TERMINATIONS
T-SERIES T.C. T.C.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:4
P
M
ELECTRICAL COVERSHEET
MARHAR EVAMIL
BID DOCUMENTS 589A4-19-103
1-E-000
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01Revisions: Date:
ADDENDUM#1 07/16/2021
E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
NaN M L
2.8
3.7
4.6
5.5
6.3
K J H G F E
CLINIC OFFICE
A200
CLINIC OFFICE
A203
CLINIC OFFICE
A204
CLINIC OFFICE
A202
OBSERVATION
A201B CORRIDOR 2
C2A02
PSYCH. RES
A201
PSYCH. RES
A206
EXIST. STRG
A206A
CORRIDOR 1
C2A01 PSYCH. RES
A205
EXIST. ELEC
A207
CORRIDOR 3
C2A04
CORRIDOR 4
C2A03
TMS ROOM
A208
TMS ROOM
A210
EXIST. SOC WRK
A212
EXIST. SOC WRK
A213
CORRIDOR 5
C2A05
CARE COORDINATOR
A209
CARE COORDINATOR
A211
STAFF RESTROOM
A214
HAC
A215
EXIST. IT
A217
WOMEN'S
A221
MEN'S
A222
EXIST. ELEC. CLO.
A216
CORRIDOR 6
C2A07
CORRIDOR 8
C2A08
GROUP ROOM WAITING AREA
A226
WAITING 2
A224
WAITING 1
A223
WORK AREA
A223B
COPIER/PAPER STORAGE AREA
A223C
MAIL AREA
A223D
CHECKOUT/CHECK IN
A223A
GROUP ROOM
A219
GROUP ROOM
A218
GROUP ROOM
A220
VESTIBULE
A200A
EWC
A
EX. TEMPERATURE
CONTROL TRANSFORMER
EX. LP2-L4-120VN
(SECT.1)
EX. LP2-L4-120VN
(SECT. 2)
EX. LP2-L4-277VN
EX. T2-L4-120VN
EWC/14
A
A
+72"
MONITOR
+72"
MONITOR
EX. LP2-JB4.4-120VC
EX. T2-JB4.4-120VC
EX. DS2-JB4.4-480VC
EX. SECURITY PANEL
EX. SECURITY PANEL
KIOSK
KIOSK
SSU-1
VAV
CONTROLS
PLP2-L4-208VN-29
DS-30-120
1-EF61
18 VAV CONTROLS
KIOSK
+72"
MONITOR
KIOSK
A/28
A/28
A/28
A/28
VAV
CONTROLS
U.C. REFRIGERATOR
PRINTER
VAV
CONTROLS
VAV
CONTROLS/29
11 11
5 3
9 9
WORKSTATION
24 24
A
A
19 15 15
WORKSTATION
WORKSTATION
25 25 25
EX. LP2-R6-277VE
MONITOR/23
OVERHEAD PROJECTOR/23
OVERHEAD PROJECTOR/13 OVERHEAD PROJECTOR/13
MONITOR/11
MONITOR/11
+72"/SMARTBOARD/17
+72"/SMARTBOARD/9
+72"/SMARTBOARD/21
120V:24V TRANSFORMER
120V:24V TRANSFORMER
EX. LP2-JB4.4-120VC-21
EX. LP2-JB4.4-120VC-21
DS-30-120
DS-30-120
MONITOR
AC-SEC-CON
EX. LP2-JB4.4-120VC-22
EX. LP2-JB4.4-120VC-25,27EX. LP2-JB4.4-120VC-25,27
ALL 120/208V BRANCH CIRCUITS IN
THIS AREA SHALL BE FED FROM
PANEL LP2-L4-120VN (SECT. 2)
UNLESS NOTED OTHERWISE
ALL 120/208V BRANCH CIRCUITS IN
THIS AREA SHALL BE FED FROM
PANEL P2LP-L4-208VN UNLESS
NOTED OTHERWISE
15 17
AUTOMATIC DOOR OPERATOR
AUTOMATIC DOOR OPERATOR
AUTOMATIC DOOR OPERATOR
1-F/SDPR1
AUTOMATIC DOOR OPERATOR/32
AUTOMATIC DOOR OPERATOR/34
AUTOMATIC DOOR OPERATOR/36
PLP2-L4-208VN
AUTOMATIC DOOR OPERATOR/31
38,40
CU-1
FDS-30-208
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:0
P
M
LEVEL 02 - ELECTRICAL POWER
MARHAR EVAMIL
BID DOCUMENTS 589A4-19-103
1-EP101
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
N
O R HT
1/8" = 1'-0"1
LEVEL 02 - ELECTRICAL POWER
KEYNOTES:
1. 1-EF61 MOUNTED ON 3RD FLOOR ROOF.
PROVIDE STEEL CHANNEL SUPPORT FOR
MOUNTING OF DISCONNECT SWITCH.
COORDINATE EXACT LOCATION WITH M.C.
2. COORDINATE EXACT LOCATION OF
MECHANICAL CONTROLS WITH M.C.
3. TIE NEW RECEPTACLES INTO NEARBY
EXISTING RECEPTACLE CIRCUIT IN THIS
SPACE.
4. PROVIDE 120V:24V TRANSFORMER AND
ASSOCIATED DISCONNECT SWITCH IN CEILING
FOR LOCAL VAV CONTROLS. CONTRACTOR
MAY DEFER FROM PLANS WHEN LOCATING
TRANSFORMER ABOVE CEILING, LOCATION
SHOWN IS FOR DESIGN INTENT ONLY.
COORDINATE FINAL INSTALLATION LOCATION
WITH EXISTING ABOVE-CEILING CONDITIONS
AND FINAL LOCATIONS OF MECHANICAL
CONTROLS TO MINIMIZE TOTAL CONDUCTOR
AND CONDUIT LENGTHS. REFER TO
MECHANICAL SHEET 1-MH101 - LEVEL 02 -
VENTILATION FOR VAV LOCATIONS.
5. INDOOR UNIT SSU-1 IS POWERED BY THE
OUTDOOR UNIT THROUGH FIELD SUPPLIED
INTERCONNECTED WIRING.
6. MOUNT RECEPTACLES TO RACK. COORDINATE
WITH OIT EQUIPMENT INSTALLER.
7. INSTALL AUTOMATIC FLUSH VALVE POWER
CONVERTER. VERIFY REQUIRED POWER
CONVERTER QUANTITY AND VALVE
CONNECTIONS WITH PLUMBING CONTRACTOR.
8. RECESS QUAD RECEPTACLE FOR
SMARTBOARD. COORIDNATE EXACT BOARD
LOCATION WITH ARCHITECT.
9. EXTEND 120V EMERGENCY CIRCUIT FROM
EXISTING FIRE SMOKE DAMPER. VERIFY
AVAILABLE CIRCUIT AMPACITY AND CONDITION
OF EXISTING CONDUIT AND CONDUCTORS
PRIOR TO EXTENDING.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01Revisions: Date:
E
E
E
E
Na N M L
2.8
3.7
4.6
5.5
6.3
K J H G F DE
7.2
8.3
9.1
EMG/SCI
NURSE NAVIGATOR
PAIN & PMR VVC/TM
PAIN BH
PAIN PHARM
PAIN EXAM ROOM 2
PAIN EXAM ROOM 3
PAIN EXAM ROOM 4
WORKSTATION
TOILET
PAIN SWAMP
EXISTING ELEC.
492A
SOILED HOLDING
TOILET
PAIN EXAM
PM&R SWAMP
PM&R EXAM ROOM 4
PM&R EXAM ROOM 3
PM&R EXAM ROOM 1
PM&R EXAM ROOM 2
MSA CHECKIN/OUT
PROCEDURE ROOM
CLEAN SUPPLY
PROCEDURE ROOM
OIT
CORRIDOR
C498
Room
A200BBBRoom
A200CCC
NURSES
CORRIDOR
C498
CORRIDOR
C496
CORRIDOR
C499
C O
R R
ID
O
R
C
EX. LP4-L4-120VC
EX. LP4-L4-277VN
EX. T4-L4-120VNDS4-L4
EX. T4-L4-120VE
EX. DP4-L4-277VE
HATCHED AREA NOT
IN PROJECT SCOPE
A/23
A/23
A/8
EXAM LIGHT/19
A/5
EXAM LIGHT/19
A/21
A/20
A/19
A/17
+48"
+48"/2
A
COPIER
A
COPIER
A/15
+48"/2
A/33
A/16 A/18
+46"/21
EXAM LIGHT
+42"
OTOSCOPE
+46"/20
EXAM LIGHT
+42"
OTOSCOPE
+46"/19
EXAM LIGHT
+42"
OTOSCOPE
+46"
EXAM LIGHT
+42"
OTOSCOPE
+42"
OTOSCOPE
ELECTROMYOGRAPH
OTOSCOPE
+46"
EWC
+46"
SCALE
A/8A/8
OTOSCOPE/11
A
A
OTOSCOPE
+46"/5
+46"/33
+46"/18
+46"/16
+42"
OTOSCOPE
EXAM LIGHT
LP4-L4-120VE
LP4-L4-277VE
SSU-2
+42"/21
+42"
OTOSCOPE
+42"
OTOSCOPE
28 28
29 29
11 21 4
1119 19
30 30 31 31
15 18 15
35 32 32
373434 36
EX. LP2-JB4.4-120VC-28,30EX. LP2-JB4.4-120VC-28,30
249 24 249
22 22
10 10
EXAM LIGHT
EXAM LIGHT
EXAM LIGHT
12,14
CU-2
A U
T O
M A
T
IC
D O
O R
O P
E R
A T O
R
FDS-30-208
DS-400-208
LP4-L4-120VN
AUTOMATIC DOOR OPERATOR/40
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:0
P
M
LEVEL 04 - ELECTRICAL POWER
SCOPRZ ANUSHA
BID DOCUMENTS 589A4-19-103
1-EP102
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
N
O R HT
1/8" = 1'-0"1
LEVEL 04 - ELECTRICAL POWER
GENERAL SHEET NOTES:
1. ALL NORMAL POWER CIRCUITS SHALL BE FED
FROM EX. LP4-L4-120VN. ALL CRITICAL POWER
CIRCUITS SERVING SHADED DEVICES SHALL
BE FED FROM EX. LP4-L4-120VC.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01
KEYNOTES:
1. NEW PANELBOARD TO REPLACE EXISTING.
REROUTE AND RECONNECT EXISTING
CONDUIT AND CONDUCTORS. E.C. TO
CONFIRM CIRCUITS SERVING AREAS OUTSIDE
AREA OF WORK. THESE CIRCUITS SHALL
REMAIN ENERGIZED DURING REPLACEMENT
OF PANELBOARD. COORDINATE ANY
REQUIRED DOWNTIME WITH CONTRACTING
OFFICER. PROVIDE NEW CIRCUIT BREAKERS
FOR ALL BRANCH CIRCUITS. REFER TO SHEET
1-ED101 - ELECTRICAL DEMOLITION FOR
INFORMATION ABOUT REMOVAL OF THE
EXISTING PANELBOARD. REFER TO PANEL
SCHEUDLES ON SHEET 1-E-501 - ELECTRICAL
SCHEDULES FOR PANEL RATING.
2. NEW PANELBOARD TO REPLACE EXISTING.
REROUTE EXISTING CONDUIT AND
CONDUTORS TO NEW 400A NON-FUSED
DISCONNECT SWITCH. CONNECT DISCONNECT
SWITCH TO RELOCATED PANEL. PROVIDE NEW
CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS. REFER TO SHEET 1-ED101 -
ELECTRICAL DEMOLITION FOR INFORMATION
ABOUT REMOVAL OF THE EXISTING
PANELBOARD. REFER TO PANEL SCHEUDLES
ON SHEET 1-E-501 - ELECTRICAL SCHEDULES
FOR PANEL RATING.
3. INDOOR UNIT SSU-2 IS POWERED BY THE
OUTDOOR UNIT THROUGH FIELD SUPPLIED
INTERCONNECTED WIRING.
4. MOUNT RECEPTACLES TO RACK. COORDINATE
WITH OIT EQUIPMENT INSTALLER.
Revisions: Date:
A
A1
F
A1
F A
S D
S D
A R
D
A3 A1
A1A1
A1 A1 A1
A1
A1
A3
A1
A A1
A1
A
A
A3
V1
V1
A
A3
A1
A1
A1 A1
A1
A
A
SD
AR DH
DH
ARDH
DH
SD ARDSD
SD SD SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SDSD
SD
SD SD
SD
NaN M L
2.8
3.7
4.6
5.5
6.3
K J H G F E
CLINIC OFFICE
A200
CLINIC OFFICE
A203
CLINIC OFFICE
A204
CLINIC OFFICE
A202
OBSERVATION
A201B CORRIDOR 2
C2A02
PSYCH. RES
A201
PSYCH. RES
A206
EXIST. STRG
A206A
CORRIDOR 1
C2A01 PSYCH. RES
A205
EXIST. ELEC
A207
CORRIDOR 3
C2A04
CORRIDOR 4
C2A03
TMS ROOM
A208
TMS ROOM
A210
EXIST. SOC WRK
A212
EXIST. SOC WRK
A213
CORRIDOR 5
C2A05
CARE COORDINATOR
A209
CARE COORDINATOR
A211
STAFF RESTROOM
A214
HAC
A215
EXIST. IT
A217
WOMEN'S
A221
MEN'S
A222
EXIST. ELEC. CLO.
A216
CORRIDOR 6
C2A07
CORRIDOR 8
C2A08
GROUP ROOM WAITING AREA
A226
WAITING 2
A224
WAITING 1
A223
WORK AREA
A223B
COPIER/PAPER STORAGE AREA
A223C
MAIL AREA
A223D
CHECKOUT/CHECK IN
A223A
GROUP ROOM
A219
GROUP ROOM
A218
GROUP ROOM
A220
VESTIBULE
A200A
1 1
DH
DH DH
DH
1 1
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:0
P
M
LEVEL 02 - FIRE ALARM
MARHAR EVAMIL
BID DOCUMENTS 589A4-19-103
1-FA101
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
N O R
HT
1/8" = 1'-0"1
LEVEL 02 - FIRE ALARM
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01
KEYNOTES:
1. CONTRACTOR TO VERIFY EXISTING ELEVATOR
LOBBY SMOKE DETECTOR. IF AN EXISTING
DETECTOR IS PRESENT CREDIT COST OF NEW
SMOKE DETECTOR BACK TO OWNER.
2. OPERATION OF A SMOKE DETECTOR AT A
CORRIDOR DOOR USED FOR AUTOMATIC
CLOSING SHALL ALSO RELEASE ONLY THE
MAGNETIC DOOR HOLDERS IN THAT SMOKE
ZONE.
GENERAL SHEET NOTES:
1. COORDINATE ALL DEVICE LOCATIONS ON
CEILING WITH ALL OTHER TRADES. VERIFY ANY
MODIFIED DEVICE LOCATIONS CAUSED BY
COORDINATION, NOT SHOWN ON THIS SHEET,
STILL COMPLY WITH ALL APPLICABLE CODES
AND GUIDELINES.
2. VERIFY CORRECT OPERATION OF EXISTING
FIRE ALARM SYSTEM SYSTEM PRIOR TO
MAKING ANY MODIFICATIONS.
3. COORDINATE ALL MODIFICATIONS, INCLUDING
DEVICE TERMINATIONS AND ANY
PROGRAMMING CHANGES, WITH THE
CONTRACTOR RESPONSIBLE FOR
MAINTENANCE OF THE EXISTING SYSTEM.
ENGAGE SERVICES OF THAT CONTRACTOR
UNDER THIS CONTRACT AS NEEDED.
Revisions: Date:
A1
A1
A1
A1
A1 V1
V1
V1
A
V1
V1
V1
V1
A1
A1
A1
A
A
ARD
A R
D
F
SD
SD SD
SD
SD
SD
SD
SD
Na N M L
2.8
3.7
4.6
5.5
6.3
K J H G F
7.2
8.3
9.1
EMG/SCI
NURSE NAVIGATOR
PAIN & PMR VVC/TM
PAIN BH
PAIN PHARM
PAIN EXAM ROOM 2
PAIN EXAM ROOM 3
PAIN EXAM ROOM 4
WORKSTATION
TOILET
PAIN SWAMP
EXISTING ELEC.
492A
SOILED HOLDING
TOILET
PAIN EXAM
PM&R SWAMP
PM&R EXAM ROOM 4
PM&R EXAM ROOM 3
PM&R EXAM ROOM 1
PM&R EXAM ROOM 2
MSA CHECKIN/OUT
PROCEDURE ROOM
CLEAN SUPPLY
PROCEDURE ROOM
OIT
CORRIDOR
C498
Room
A200BBBRoom
A200CCC
NURSES
CORRIDOR
C498
CORRIDOR
C496
CORRIDOR
C499
C O
R R
ID
O
R
C
HATCHED AREA NOT
IN PROJECT SCOPE
1 1
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:0
P
M
LEVEL 04 - FIRE ALARM
SCOPRZ ANUSHA
BID DOCUMENTS 589A4-19-103
1-FA102
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
N
O R HT
1/8" = 1'-0"1
LEVEL 04 - FIRE ALARM
GENERAL SHEET NOTES:
1. COORDINATE ALL DEVICE LOCATIONS ON
CEILING WITH ALL OTHER TRADES. VERIFY ANY
MODIFIED DEVICE LOCATIONS CAUSED BY
COORDINATION, NOT SHOWN ON THIS SHEET,
STILL COMPLY WITH ALL APPLICABLE CODES
AND GUIDELINES.
2. VERIFY CORRECT OPERATION OF EXISTING
FIRE ALARM SYSTEM SYSTEM PRIOR TO
MAKING ANY MODIFICATIONS.
3. COORDINATE ALL MODIFICATIONS, INCLUDING
DEVICE TERMINATIONS AND ANY
PROGRAMMING CHANGES, WITH THE
CONTRACTOR RESPONSIBLE FOR
MAINTENANCE OF THE EXISTING SYSTEM.
ENGAGE SERVICES OF THAT CONTRACTOR
UNDER THIS CONTRACT AS NEEDED.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01Revisions: Date:
SEE ARCHITECTURAL
PLANS FOR WALL CONSTRUCTION
PLASTER RING TO COME
WITHIN 1/8" OF FINAL SURFACE
STUD
MOUNTING BRACKET SHALL PROVIDE
SUPPORT FROM STUD AND BACK OF
WALL OR TWO STUDS.
NOTES :
1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY
MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR
WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE
MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES
THE SAME RESULTS.
2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE
WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.
3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23.
MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# .
FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-
LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.
4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON
COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE
DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT
OPENINGS WITH MOUNTING BRACKETS.
1 5/64"12"
WALL WITH INSULATION
FLANGES ON EACH SIDE
OF WALL. CAULK AT
WALL AND SLEEVE.
CONDUIT
SHEET METAL SLEEVE, 2"
LARGER THAN CONDUIT
OVERALL DIAMETER.
PACK AROUND CONDUIT WITH
FIBERGLASS INSULATION
ESCUTCHEON PLATES
ON BOTH SIDES
FIXTURE
CEILING T'S LAY-IN CEILING
CEILING TIE WIRE
THREADED ROD
SUPPORT 1 PER
LUMINAIRE
4" BOX
ADJUSTABLE SUPPORT BRACKET,
2 PER LUMINAIRE. (ATTACH TO
CEILING GRID CHANNELS)
SUPPORT BOX AND CONDUIT
FROM STRUCTURE
FLEX CONDUIT
LENGTH: 4'-0" MIN. 6'-0" MAX.
RATED WALL
(CONSTRUCTION VARIES)
NOTE 2
FIRE SEALANT
NOTE 3
FIRE SEALANT
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 2
PENETRATING ITEM
NOTE 4
NOTE 3
RATED FLOOR
(CONSTRUCTION VARIES)
NOTES :
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR
FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL
MOVEMENT. REFER TO SPECIFICATION SECTION 07 84 00 FOR SELECTION OF THROUGH
PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH
CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND
DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND
SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR
SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE
SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE
STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING.
SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM
WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF
WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO
FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE
PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
OC
LS
LOCAL
LIGHTING
CONTROLLER
S
D
NORMAL POWER
TRANSFER SWITCH, INVERTER,
OR EQUIVALENT UL 1008
NORMAL PANEL
BOARD
EMERGENCY/LIFE
SAFETY PANEL
BOARD
LIGHTING SENSORS, SWITCHES, AND
DIMMERS. REFER TO PLANS FOR
APPLICABLE DEVICES IN EACH SPACE (TYP)
TYPICAL OF LOCAL LIGHTING CONTROLLER,
REFER TO MANUFACTURER INSTRUCTIONS
AND REQUIREMENTS
NORMAL LUMINAIRES
EMERGENCY LUMINAIRES
ALCR
0-10V DIMMING CONTROL TO
LUMINARES WHEN APPLICABLE (TYP)
NOTES:
1. THE ALCR RELAY DIAGRAM IS INTENDED TO CONVEY INTENDED OPERATION AND
SPECIFICALLY DOES NOT INDICATE QUANTITIES, ALL DEVICES, WIRING, AND CONNECTIONS
REQUIRED. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
REQUIREMENTS.
2. MOUNT LOCAL LIGHTING CONTROLLERS ABOVE FINISHED CEILING NEAR ROOM ENTRANCE.
IN A CORRIDOR, MOUNT NEAR ONE END OF CORRIDOR AND ADJACENT TO FIRST SENSOR OR
CONTROL DEVICE.
3. MOUNT ALCR ADJACENT TO LIGHTING CONTROLLER ABOVE ACCESSIBLE FINISHED CEILING.
4. FIRE ALARM ADDRESSABLE RELAY SHALL OVERRIDE LOCAL LIGHTING CONTROLS UPON FIRE
ALARM OR TEST.
EMERGENCY POWER(1) - STAINLESS
STEEL DRAW BAND
PRE-MOLDED RUBBER
PIPE FLASHING
ROOF INSULATION
CONDUIT,
BY E.C.SEALANT (URETHANE)
ROOF DECK
TOP OF STEEL JOIST
NOTES:
1. CONDUIT SHALL BE SUPPORTED WITHIN 24 INCHES ABOVE AND BELOW ROOF.
2. VERIFY FINAL REQUIREMENTS WITH GENERAL CONTRACTOR (G.C.) AND
ROOFING INSTALLER PRIOR TO INSTALLATION.
SYSTEM INPUTS
SEQUENCE OF
OPERATION
P A
N E
L /A
N N
U N
C
IA
T O
R A
L A
R M
I N
D
IC
A T
IO
N
P A
N E
L /A
N N
U N
C
IA
T O
R S
U P
E R
V
IS
O R
Y I N
D
IC
A T
IO
N
P A
N E
L /A
N N
U N
C
IA
T O
R T R
O U
B L E
I N
D
IC
A T
IO
N
A U
D
IB
L E
A L A
R M
S
Q U
E N
C E
V
IS
U A
L A
L A
R M
Q U
E N
C E
S M
O K
E D
A M
P
R
C O
N T R
O L S
E Q
U E
N C
E
D O
O R
H O
L D
E R
S E
Q U
E N
C E
ARARD
MANUAL PULL STATION
SMOKE DETECTOR
SMOKE DETECTOR
FOR HVAC CONTROL
SMOKE DETECTOR FOR
SMOKE DAMPER CONTROL
SMOKE DETECTORS IN
ELEVATOR LOBBIES
F
SD
SD SD
D
SD SD
D
SD
X
X
X
X
X
X X
X
X
X
X X X
X
X X
X
X
X
NOTES:
1. ALL SYSTEM EVENTS SHALL BE LOGGED, PRINTED, AND DISPLAYED ON THE GRAPHICAL
INTERFACE, IF APPLICABLE. SEE SPECIFICATIONS FOR MORE INFORMATION AND
DESCRIPTIONS OF SEQUENCES OF OPERATION.
2. PARTIAL EVACUATION OR RELOCATION OF OCCUPANTS IS THE STANDARD OPERATING
PROCEDURE FOR THIS FACILITY IN THE EVENT OF AN ALARM. THEREFORE, ALL
NOTIFICATION APPLIANCE CIRCUITS MUST BE INSTALLED AND PROTECTED IN
ACCORDANCE WITH THE CIRCUIT SURVIVABILITY REQUIREMENTS DESCRIBED IN NFPA
72. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
X
X
X
X
X
X
X
NEPCI
C I
SIGNAL LINE CIRCUIT
(SLC)
NOTIFICATION APPLIANCE CIRCUIT (NAC)
AR
ARD
TO DOOR HOLD DEVICES (TYP)
TO FIRE/SMOKE DAMPER CONTROL
DH
RI SD
F SD
V
KEYNOTES:
1. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE.
REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
2. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT
AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
3. PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF
NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS
AND ACCEPTABLE MOUNTING LOCATIONS.
EXISTING
FIRE ALARM
CONTROL
PANEL
NOTES:
1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS
AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR
DISTANCES.
2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND
MANUFACTURER'S RECOMMENDATIONS.
3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE
VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF
CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.
4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE
CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR
PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.
A
SD
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:0
:4
P
M
ELECTRICAL DETAILS
MARHAR EVAMIL
BID DOCUMENTS 589A4-19-103
1-E-300
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
NO SCALE
BACKBOX MOUNTING DETAIL
5 NO SCALE
CONDUIT WALL PENETRATION
NO SCALE
EXIT SIGN MOUNTING DETAIL
NO SCALE
FIRE BARRIER PENETRATION
NO SCALE
AUTOMATIC LOAD CONTROL RELAY DIAGRAM [ALCR]
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.01
NO SCALE
CONDUIT ROOF PENETRATION
NO SCALE7
FIRE ALARM OPERATION MATRIX
NO SCALE8
FIRE ALARM RISER
Revisions: Date:
BRANCH CIRCUIT WIRING KEY
WIRE
ID 2 WIRE 3 WIRE 4 WIRE
THHW/THWN COPPER
CONDUCTORS
EQUIPMENT
GROUNDING
CONDUCTOR CONDUIT
A# 2#12 3#12 4#12 1#12 3/4"
B# 2#10 3#10 4#10 1#10 3/4"
C# 2#8 3#8 4#8 1#10 3/4"
D# 2#6 3#6 4#6 1#10 1"
E# 2#4 3#4 4#4 1#8 1 1/4"
G# 2#2 3#2 4#2 1#8 1 1/4"
H# 2#1 3#1 4#1 1#6 1 1/2"
J# 2#1/0 3#1/0 4#1/0 1#6 2"
ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND
CONDUCTOR
F# 2#3 3#3 4#3 1#8 1 1/4"
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
A/E:Consultant:
Sprinklered
Fully Sprinklered
C R e v it L o c a l F ile s \M
E P
T
.0
B H
C lin ic R e n o v a ti o n
C
E v a n
.H .M ill e r.
rv t
/1
/2
:2
:5
P
M
ELECTRICAL SCHEDULES
MARHAR EVAMIL
BID DOCUMENTS 589A4-19-103
1-E-500
Columbia Harry S. Truman Memorial
Veterans Hospital
Columbia, Missouri
05/13/2021
REFER TO SPECIFICATION SECTION LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
INTERIOR CORRELATED COLOR TEMPERATURE 3500K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE MOUNTING
HEIGHTS.
DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)
DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE
0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC
(TYPE) DRIVER:
PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED
P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED
FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER
CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE
CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED
(MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP
CFSA - COLOR-FINISH SELECTION BY ARCHITECT
PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION)
FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR
RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC
RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE
FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE
FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR
(DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC
LED LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATT LED DRIVER
BASIS OF DESIGNL W H DIA.
ANSI
WATTS PER TYPE QTY
ABSOLUTE
LUMENS
(MIN) VOLTS TYPE
EM1 EMERGENCY UNIT, TWO ADJUSTABLE 6 VOLT
HEADS, WHITE THERMOPLASTIC HOUSING.
O WL 1'-2" 6" 3
51/64"
7 W FIX IN 2 6 VOLT (2
INCLUDED)
277 V EM DUAL-LITE LZ2
F1 6" CLEAR, SELF-FLANGED DOWNLIGHT WITH
MEDIUM WIDE DISTRIBUTION. REQUIRED
DRYWALL CONSTRUCTION KIT IN.
O RE 7" 6" 15 W FIX LED 1 L.E.D. 277 V 0-10V CALCULITE LED GEN 3 6"
F2 4' WALL-MOUNTED VANITY FIXTURE, FROSTED
ACRYLIC LENS.
O WL 2'-0" 6 1/2" 5 3/4" 0 W FIX LED 1 L.E.D. 277 V 0-10V WMA LED ARCHITECTURAL WALL
MOUNT
F3 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11
51/64"
1'-11 51/64"
39/64"
25 W FIX LED 1 3470 277 V 0-10V CREE LIGHTING ZR22
F3A 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11
51/64"
1'-11 51/64"
39/64"
29 W FIX LED 1 4050 277 V 0-10V CREE LIGHTING ZR22
F3B SAME AS F3 WITH DRY WALL CONSTRUCTION
KIT.
O RE 1'-11
51/64"
1'-11 51/64"
39/64"
29 W FIX LED 1 4050 277 V 0-10V CREE LIGHTING ZR22
F3C 2X2 RECESSED TROFFER FIXTURE. 5000K,
85CRI.
O RE 2'-0" 2'-0" 3 1/4" 35 W FIX LED 1 4940 277 V 0-10V CREE LIGHTING ZR22
F3D 2X2 RECESSED TROFFER FIXTURE. O RE 1'-11
51/64"
1'-11 51/64"
39/64"
35 W FIX LED 1 4940 277 V 0-10V CREE LIGHTING ZR22
F3R REUSED 2x2 TROFFER FIXTURE. O RE 2'-0" 2'-0" 3 1/4" 35 W FIX LED 1 L.E.D. 277 V 0-10V RELOCATED LED 2x2 FIXTURE
F4 2X4 DIRECT/INDIRECT LIGHT FIXTURE. 5000K,
85 CRI.
O RE 4'-0" 2'-0" 3 1/4" 40 W FIX LED 1 4800 277 V 0-10V LITHONIA 2VTL4
F5 4" RECESSED DOWNLIGHT. O RE 7" 4" 15 W FIX LED 1 1500 277 V 0-10V CALCULITE LED GEN 3 4"
F6 4' INDUSTRIAL WITH 10% UPLIGHT, BAKED
ENAMEL FINISH. 3500K. 80CRI.
O SP 4'-0" 1'-0" 4 1/4" 22 W FIX LED 2 3119 277 V EM METALUX SNLED
X1 EDGE-LIT SINGLE FACED EXIT SIGN,
INJECTION MOLDED ACRYLIC MIRROR LENS
AND EXTRUDED ALUMINUM HOUSING.
HOUSING FINISH AND COLORS SELECTED BY
ARCHITECT. VERIFY RECESSED END, BACK OR
CEILING MOUNTING AND ARROWS WITH
PLANS.
O CL 1'-1" 2" 9" 4 W FIX LED 1 L.E.D. 277 V EM LITHONIA 202 LT 0 - EDG 1R
(SINGLE FACE) OR APPROVED
EQUAL
X2 EDGE-LIT DOUBLE FACED EXIT SIGN,
INJECTION MOLDED ACRYLIC MIRROR LENS
AND EXTRUDED ALUMINUM HOUSING.
HOUSING FINISH AND COLORS SELECTED BY
ARCHITECT. VERIFY RECESSED END, BACK OR
CEILING MOUNTING AND ARROWS WITH
PLANS.
O CL 1'-1" 2" 9" 4 W FIX LED 1 L.E.D. 277 V EM LITHONIA 202 LT 0 - EDG 2R
(DOUBLE FACE) OR APPROVED
EQUAL
LIGHTING SEQUENCE OF OPERATION
PLAN ID LIGHTING SWITCHED
{LD1} Sequence: Dimmed lights are controlled in this space ON: The luminaries turn on via vacancy sensor or occupancy sensor. If applicable, UL924 devices shall be used control emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.
ADJUST: If applicable, the day lighting zone luminaries will continuously adjust to the presence of daylight to 30 foot candles at working desk level OFF: The lights turn off manually using the wall controller. After the space has been vacant for 20 minutes, the lights will automatically turn off.ntrol emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.
{LD2} Sequence: Dimmed lights are controlled in this space.
ON: The luminaires turn on via wall control station.
OFF: The lights turn off using the wall control station.
{LS1} Sequence: Switched lights are controlled in this space ON: The lights turn on using the key switches or occupancy sensor. UL924 devices shall be used control emergency luminaries with normal. The emergency luminaries (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.
OFF: The lights turn off using the key switches. After the space has been vacant for 20 minutes, the lights will automatically turn off.
{LS2} Sequence: Switched lights are controlled in this space ON: The lights turn on using switches or occupancy sensor.
OFF: The lights turn off manually using the wall controller. After the space has been vacant for 20 minutes, the lights will automatically turn off.
{LS3} Sequence: Switched lights are controlled in this space.
ON: The normal lights turn on by occupancy sensors in the corridor. Night lights will remain on at all times. Existing lighting control panel shall override occupancy sensors during central schedule ON conditions.
OFF: The normal lights turn off after the space has been vacant for 20 minutes. Existing lighting control panel shall override occupancy sensors during central schedule OFF conditions.
{LS4} Sequence: Switched lights are controlled in this space.
ON: The lights turn on via switches or occupancy sensor. UL924 devices shall be used to control emergency luminaries with normal. The emergency luminaires (tagged 'SE' on the plans) shall turn on to 100% during the loss of normal power.
OFF: The lights turn off using the switches. After the space has been vacant for 20 minutes, the lights will automatically shut off.
{LS5} Sequence: Switched lights are controlled in this space.
ON: The lights turn on using switches.
OFF: The lights turn off manually using switches.
[Key...
Total Additional Amps:
50.83 67.91 46.5
Total Additional Load:
6.03 kVA 8.08 kVA 5.58 kVA
-- 41 -- -- -- -- 0 0 -- 1 20 A SPARE 42
-- 39 -- -- -- -- 0 0.52 -- -- -- -- 40 --
37 EXISTING MAIN 20 A 3 -- 0 0.52 A2 2 15 A CU-1 38
35 SPARE 20 A 1 -- 0 0.72 A2 1 20 A DOOR OPERATOR MEN A222 36
33 CORRIDOR C2A08 24V XFMR 20 A 1 A2 0 0.72 A2 1 20 A DOOR OPERATOR WOMEN A221 34
31 2ND FL VAV CONTROLS EAST 20 A 1 A2 0 0.72 A2 1 20 A DOOR OPERATORS C2A03 32
29 RECS - CORRIDOR 20 A 1 A2 1.26 0.72 A2 1 20 A DOOR OPERATORS C2A08 30
27 RECS - C2A08 MONITOR, KIOSK 20 A 1 A2 1.08 1.44 A2 1 20 A RECS - 223B 28
25 RECS - A224 20 A 1 A2 1.08 1.44 A2 1 20 A RECS - 223A 26
23 GROUP A220 PROJEC, MONITOR 20 A 1 A2 0 1.62 A2 1 20 A RECS - 223A, A223 24
21 RECS - A220 20 A 1 A2 1.62 0.54 A2 1 20 A RECS - CORRIDOR 22
19 RECS - A218 EAST 20 A 1 A2 0.9 0.83 A2 1 20 A ROOF - EF-1 20
17 RECS - A219 EAST 20 A 1 A2 0.9 0 A2 1 20 A AUTO FLUSH VALVES MENS 221 18
15 RECS - A219 WEST 20 A 1 A2 0.9 0 A2 1 20 A AUTO FLUSH WOMENS 221 16
13 GROUP A218, A219 OVERHEAD 20 A 1 A2 0 0.54 A2 1 20 A REC - A221,A222 EWC 14
11 GROUP A218, A219 MONITOR 20 A 1 A2 0 0.36 A2 1 20 A RCPT - A217 OIT RACK QUAD 1 12
9 RECS - A218 WEST 20 A 1 A2 0.9 0.36 A2 1 20 A RCPT - A217 OIT RACK QUAD 1 10
7 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 8
5 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 6
3 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 4
1 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 2
CKT
NO. LOAD DESCRIPTION
OVERCURRET
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRET
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: SECTION 2 OF 2. EXISTING PANEL. NEW BREAKERS SHALL MATCH MANUFACTURER AND SCCR RATING OF EXISTING PANEL. ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS OTHERWISE NOTED. TOTALS AT BOTTOM OF SCHEDULE REFLECT ADDITIONAL LOAD ONLY.
LOCATION: EXIST. ELEC A207 WIRE: 4
FED FROM: EXISTING GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 100 A/MCB
PANEL NAME: EX. LP2-L4-120VN (SECT.2) CONNECTED 19.7 kVA
[Key...
Total Additional Amps:
8.63 9.74 0
Total Additional Load:
2.07 kVA 2.38 kVA 0 kVA
-- 41 -- -- -- -- 0 0 -- -- -- SPACE 42 --
-- 39 -- -- -- -- 0 0 -- -- -- SPACE 40 --
37 MAIN 100 A 3 -- 0 0 -- -- -- SPACE 38 --
-- 35 SPACE -- -- -- 0 0 -- -- -- SPACE 36 --
-- 33 SPACE -- -- -- 0 0 -- -- -- SPACE 34 --
-- 31 SPACE -- -- -- 0 0 -- -- -- SPACE 32 --
-- 29 SPACE -- -- -- 0 0 -- -- -- SPACE 30 --
27 LGTS -CORR. C2A08,A226 20 A 1 A2 1.1 1.28 A2 1 20 A LGTS - WAITING A223, A224 28
25 LGTS - PSYCH A205,A208,A210 20 A 1 A2 1.61 0.46 A2 1 20 A LGTS - CORR. C2A03 26
-- 23 -- -- -- -- 0 0 -- -- -- -- 24 --
-- 21 -- -- -- -- 0 0 -- -- -- -- 22 --
19 EXISTING 15 A 3 -- 0 0 -- 3 70 A EXISTING 20
17 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 18 --
15 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 16 --
13 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 14 --
11 EXISTING 20 A 1 -- 0 0 -- -- -- EXISTING 12 --
9 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 10
7 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 8
5 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 6
3 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 4
1 EXISTING 20 A 1 -- 0 0 -- 1 20 A EXISTING 2
CKT
NO. LOAD DESCRIPTION
OVERCURRET
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRET
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: EXISTING PANEL. ANY ADDITIONS SHALL MATCH MANUFACTURER AND SCCR RATING. ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS
OTHERWISE NOTED. TOTALS AT BOTTOM OF SCHEDULE REFLECT ADDITIONAL LOAD ONLY.
LOCATION: EXIST. ELEC A207 WIRE: 4
FED FROM: EXISTING GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 480/277 Wye
TYPE: BOLT-ON MAIN: 100 A/MCB
PANEL NAME: EX. LP2-L4-277VN CONNECTED 4.5 kVA
[Key...
Total Amps: 44.15 45.99 25.5
Total Load: 5 kVA 5.22 kVA 3.06 kVA
-- 59 SPACE -- -- -- 0 0 -- -- -- SPACE 60 --
-- 57 SPACE -- -- -- 0 0 -- -- -- SPACE 58 --
-- 55 SPACE -- -- -- 0 0 -- -- -- SPACE 56 --
53 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 54
51 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 52
49 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 50
47 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 48
45 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 46
43 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 44
41 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 42
39 RCPTS - CARE COORD. A209 20 A 1 A2 0.9 0 -- 1 20 A SPARE 40
37 RCPTS - CARE COORD. A209 20 A 1 A2 0.9 0 -- 1 20 A SPARE 38
35 RCPTS - TMS ROOM A208 20 A 1 A2 0.9 0 -- 1 20 A SPARE 36
33 RCPTS - TMS ROOM A210 20 A 1 A2 0.9 0 -- 1 20 A SPARE 34
31 DOOR OPERATOR C2A07 20 A 1 A2 0.86 0.72 A2 1 20 A RCPTS - A214, A215 32
29 2ND FL VAV CONTROLS WEST 20 A 1 A2 0 0 -- 1 20 A EXISTING LOAD 30
27 CORRIODR C2A04 24V XFMR 20 A 1 A2 0 0 -- 1 20 A EXISTING LOAD 28
25 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 26
23 EXISTING LOAD 20 A 1 -- 0 0 -- 1 20 A EXISTING LOAD 24
21 RCPTS - CORR C2A03, C2A04 20 A 1 A2 1.08 0 -- 1 20 A EXISTING LOAD 22
19 RCPTS - CORR C2A01, C200A 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 20
17 RCPTS - PSYCH. RES A206 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 18
15 RCPTS - PSYCH. RES A201 20 A 1 A2 0.54 0 -- 1 20 A EXISTING LOAD 16
13 EWC - CORRIDOR 20 A 1 A2 0.18 0 -- 1 20 A EXISTING LOAD 14
11 RCPTS - OBSERVATION A201B 20 A 1 A2 0.72 0 -- -- -- -- 12 --
9 RCPTS - CLINIC OFFICE A200 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 3 10
7 RCPTS - CLINIC OFFICE A202 20 A 1 A2 0.9 0 -- -- -- -- 8 --
5 RCPTS - CLINIC OFFICE A203 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 2 6
3 RCPTS - CLINIC OFFICE A204 20 A 1 A2 0.9 0 -- -- -- -- 4 --
1 RCPTS - PSYCH. RES A205 20 A 1 A2 0.9 0 -- 2 150 A EXISTING MAIN - 1 2
CKT
NO. LOAD DESCRIPTION
OVERCURRET
PROTECTION
AMPS P
WIRE
ID
A B C
WIRE
ID
OVERCURRET
PROTECTION
P AMPS LOAD DESCRIPTION
CKT
NO.
Panel Notes: ALL NEW BRANCH CIRCUITS SHALL BE IN 3/4" C. UNLESS OTHERWISE NOTED.
SCCR: 22,000
LOCATION: EXIST. ELEC A207 WIRE: 4
FED FROM: EXISTING GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 100 A/MCB
PANEL NAME: PLP2-L4-208VN CONNECTED 13.3 kVA
FS - FUSED SWITCH
MX - MANUAL SWITCH
MS - MANUAL STARTER
SS - SOLID STATE
RV - REDUCED VOLTAGE AUTOXFMR
SW - 2 SPEED, 1 WINDING
TW - 2 SPEED, 2 WINDING
RE - REVERSING HL - HANDLE PADLOCK HASP
YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR
FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. &...
STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS
*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR
CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE... TS - 2 SPEED SELECTOR SWITCH IN DOOR
NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1...
FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES *... PF - PHASE LOSS PROTECTION (5 HP OR...
DISCONNECT TYPE: REMARKS:
NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.
E - DISCONNECT AND STARTER SCHEDULE
ITEM
DISCONNECT TYPE &
RATING CIRCUIT
VOLTAGE POLES
NEMA
ENCLOSURE REMARKS BASIS OF DESIGNTYPE RATING
DS-30-120 NF 30 A 120 V 3 1 SQUARE D
DS-400-208 NF 400 A 208 V 3 1 SQUARE D
FDS-30-208 F 30 A 208 V 3 1 PROVIDE 15A FUSE SQUARE D
[Key...
Total Additional Amps:
2.79 4.55 0
Total Additional Load:
0.67 kVA 1.16 kVA 0 kVA
-- 29 -- -- -- -- 0 0 -- 1 20 A SPARE 30
-- 27 -- -- -- -- 0 0 -- 1 20 A SPARE 28
25 MAIN 20 A 3 -- 0 0 -- 1 20 A SPARE 26
23 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 24
21 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 22
19 SPARE 20 A 1 -- 0 0 -- 1 20 A SPARE 20
17 SPARE 20 A 1 -- 0 0…