This document provides details on a federal solicitation to correct deficiencies in Building 1 at the VA New Jersey Healthcare System located in Lyons, New Jersey. The solicitation is for a construction project requiring the contractor to prepare the site for building operations including demolition and removal of existing structures. The contractor will furnish all labor, materials, and services to perform the work defined in the project drawings and specifications. This is a set-aside procurement only for Service-Disabled Veteran Owned Small Businesses. The work must be completed within 365 days of the notice to proceed date. The pre-bid walkthrough is scheduled for June 2, 2022 and interested parties should review the attached solicitation for additional requirement details such as the scope of work, procurement terms, and evaluation factors. The estimated value of the construction is between $1,000,000 to $5,000,000.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1-FD101
REMOVE AND REPLACE
EXISTING 6" FIRE SERVICE
PIPE TO EXISTING POST
INDICATOR VALVE, SEE
SHEET 1-AS101.
REMOVE AND REPLACE
EXISTING 6" SPRINKLER
PIPE TO AND INCLUDING
WET PIPE VALVE AND TRIM
REMOVE AND REPLACE
EXISTING 6" SPRINKLER
PIPE TO AND INCLUDING
DRY PIPE VALVE AND TRIM
A
VIEWPOINT
FOR
PICTURE
GROUND FLOOR
294' - 0"
BASEMENT
283' - 0"
REMOVE AND REPLACE EXISTING 6" FIRE
SERVICE PIPE TO EXISTING POST
INDICATOR VALVE, SEE SHEET 1-AS101.
REMOVE AND REPLACE
EXISTING DOUBLE ELBOW AT
BASE OF RISER
REMOVE AND REPLACE EXISTING
DRAIN VALVE AND DRAIN SPOUT
REMOVE AND REPLACE EXISTING 6" SPRINKLER
PIPE, WET AND DRY PIPE OS&Y GATE VALVES
AND ASSOCIATED TAMPER SWITCHES
REMOVE AND REPLACE ALL EXISTING
SPRINKLER PIPE, FITTINGS, FLANGES,
ELBOWS, VALVES AND CONTROLS
FROM INCOMING SERVICE
CONNECTION TO DESIGNATED
TERMINATION/CONNECTION POINTS
REMOVE AND REPLACE EXISTING 6"
SPRINKLER PIPE UP TO AND INCLUDING
WET PIPE VALVE, TRIM, AND ASSOCIATED
FLOW SWITCH
REMOVE AND REPLACE EXISTING 6"
SPRINKLER PIPE UP TO AND INCLUDING
DRY PIPE VALVE, TRIM, AND ASSOCIATED
LOW/HIGH AIR PRESSURE MONITOR
REMOVE AND REPLACE EXISTING 6"
OS&Y GATE VALVE AND ASSOCIATED
TAMPER SWITCH
REMOVE AND REPLACE EXISTING
CONCRETE FLOOR SUPPORTS
REMOVE AND REPLACE
EXISTING SPRINKLER PIPE
TO AND INCLUDING DOUBLE
ELBOW AT BASE OF RISER REMOVE AND REPLACE ALL EXISTING
SPRINKLER PIPE, FITTINGS, FLANGES,
ELBOWS, VALVES AND CONTROLS
FROM INCOMING SERVICE
CONNECTION TO DESIGNATED
TERMINATION/CONNECTION POINTS
REMOVE AND REPLACE EXISTING 6"
OS&Y GATE VALVE AND ASSOCIATED
TAMPER SWITCH
REMOVE AND REPLACE EXISTING 6"
SPRINKLER PIPE UP TO AND INCLUDING
DRY PIPE VALVE, TRIM, AND ASSOCIATED
LOW/HIGH AIR PRESSURE MONITOR
REMOVE AND REPLACE EXISTING 6"
SPRINKLER PIPE UP TO AND INCLUDING
WET PIPE VALVE, TRIM, AND ASSOCIATED
FLOW SWITCH
REMOVE AND REPLACE EXISTING 6" FIRE
SERVICE PIPE TO EXISTING POST
INDICATOR VALVE, SEE SHEET 1-AS101.
REMOVE AND REPLACE EXISTING 6" FIRE
SERVICE PIPE TO SERVICE CONNECTION
APPROX. 15' OUTSIDE EXTERIOR WALL.
CONTRACTOR SHALL VERFY EXACT
LOCATION WITH ENGINEER AND COR.
REMOVE AND REPLACE EXISTING
SPRINKLER PIPE TO AND INCLUDING
DOUBLE ELBOW AT BASE OF RISER
REMOVE AND REPLACE EXISTING 6" SPRINKLER
PIPE UP TO AND INCLUDING DRY PIPE VALVE,
TRIM, AND ASSOCIATED LOW/HIGH AIR
PRESSURE MONITOR
REMOVE AND REPLACE EXISTING SPRINKLER PIPE
UP TO AND INCLUDING WET PIPE VALVE, TRIM, AND
ASSOCIATED FLOW SWITCH
REMOVE AND REPLACE EXISTING
DRAIN VALVE AND DRAIN SPOUT
REMOVE AND REPLACE EXISTING
6" SPRINKLER PIPE, WET AND DRY
PIPE OS&Y GATE VALVES AND
ASSOCIATED TAMPER SWITCHES
REMOVE AND REPLACE ALL EXISTING SPRINKLER PIPE,
FITTINGS, FLANGES, ELBOWS, VALVES AND CONTROLS
FROM INCOMING SERVICE CONNECTION TO
DESIGNATED TERMINATION/CONNECTION POINTS
REMOVE AND REPLACE EXISTING 6"
OS&Y GATE VALVE AND ASSOCIATED
TAMPER SWITCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
C U s e rs \b p e re ir a
\D o c u m e n ts
\2 -U
S D
V A
-0 P
L U
M B
IN
G b p e re ir a
N M
M N
.r v t
/2 /2
:4
:0
P M
1-FD101
BASEMENT FIRE PROTECTION PLAN
ACELA
561A4-15-102CORRECT FCA F RATED
DEFICIENCIES BUILDING 1
1/4" = 1'-0"1
ENLARGED PARTIAL BASEMENT FIRE PROTECTION - DEMOLITION / NEW WORK
1/4" = 1'-0"2
FIRE SERVICE RISER SECTION VIEW - DEMOLITION / NEW WORK
NOTES:
1. NEW AND EXISTING SPRINKLER PIPING IN MECHANICAL ROOM TO BE PAINTED RED AND PROVIDED WITH A NEW HYDRAULIC
NAMEPLATE AT BASE OF RISER.
2. REMOVE AND REPLACE EXISTING CONCRETE PIPING FLOOR SUPPORTS AND PAINT YELLOW.
3. SEAL FOUNDATION CRACKS AND OPENINGS FROM EXTERIOR AROUND THE SPRINKLER PIPES AFTER EXCAVATION OCCURS
TO REPLACE THE 15 FEET OF PIPING.
4. PROVIDE GRAY EPOXY FLOOR PAINT BELOW AND 6 FEET IN FRONT OF NEW SPRINKLER PIPING.
5. REMOVE AND REPLACE EXISTING FIRE ALARM SPRINKLER TAMPER / SUPERVISORY SWITCHES AND FLOW SWITCHES
ASSOCIATED WITH SPRINKLER RISER.
6. REMOVE AND REPLACE EXISTING LOW/HIGH AIR PRESSURE MONITOR MODULES ASSOCIATED WITH THE DRY-PIPE SYSTEM.
7. REPLACE ALL DRAIN PIPING ASSOCIATED WITH THE SPRINKLER RISER.
FIRE SERVICE RISER ISOMETRIC
1/4" = 1'-0"A
FIRE SERVICE RISER PICTURE
Revisions: Date:
10/18/2021 DTB
100% FINAL DOCUMENTS