Drawings 26 50_Part11.pdf

PDF 3 MB Posted

Attached to
Y1DZ--Correct FCA Deficiencies Building 1| Federal contract opportunity
Solicitation number
36C24222B0031_1
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This solicitation is for a construction project to correct deficiencies in Building 1 at the VA New Jersey Healthcare System located in Lyons, New Jersey. The contractor shall demolish existing structures, prepare the site for building operations, and furnish labor and materials to perform work defined by the attached architecture and engineering drawings and specifications. The North American Industry Classification System code is 236220 with a business size of $39.5 million or less. This is a Service-Disabled Veteran Owned Small Business set-aside procurement with a construction magnitude between $1 million and $5 million. The completion time is 365 days from the notice to proceed date. A pre-bid walkthrough is scheduled for June 2, 2022 at 9:00 AM Eastern Time.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--Correct FCA Deficiencies Building 1|, newest first.
File Type Posted
36C24222B0031 0003 Amendment.docx DOCX document
Responses to Requests for Information for Solicitation 36C24222B0031.docx DOCX document
36C24222B0031 0002.docx DOCX document
36C24222B0031 0001.docx DOCX document
Drawings 26 50_Part7.pdf PDF
Drawings 26 50_Part1.pdf PDF
Drawings 26 50_Part4.pdf PDF
561A4 15 102 Specifications_Part1.pdf PDF
561A4 15 102 Specifications_Part2.pdf PDF
36C24222B0031_1.docx DOCX document
Drawings 1 25.pdf PDF
Drawings 26 50_Part2.pdf PDF
Drawings 26 50_Part5.pdf PDF
Drawings 26 50_Part9.pdf PDF
Drawings 26 50_Part10.pdf PDF
561A4 15 102 Specifications_Part3.pdf PDF
561A4 15 102 Specifications_Part4.pdf PDF
561A4 15 102 Specifications_Part7.pdf PDF
561A4 15 102 Specifications_Part8.pdf PDF
561A4 15 102 Specifications_Part9.pdf PDF
561A4 15 102 Specifications_Part5.pdf PDF
Drawings 26 50_Part3.pdf PDF
Drawings 26 50_Part6.pdf PDF
Drawings 26 50_Part8.pdf PDF
561A4 15 102 Specifications_Part6.pdf PDF
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT

NORTH

AREA OF

WORK

RECESSED LED 2'X2' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

RECESSED LED 2'X4' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

DEMOLISHED RECESSED LED LIGHTING FIXTURE

DEMOLISHED PENDANT LIGHT BULB

LINEAR LED LIGHTING FIXTURE. MOUNTING METHOD AS SHOWN ON THE PLAN. CONNECT TO EMERGENCY LIFE SAFETY CIRCUIT AS INDICATED

EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.

CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.

EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.

CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.

NOTE: REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.

UPPER LETTER INDICATES LIGHTING FIXTURE TYPE. LOWER LETTER INDICATES CONTROL GROUP.

ELECTRICAL LEGEND

20A-1P-120/277V WALL SWITCH . MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.

LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH AND OCCUPANCY SENSOR (WHERE SHOWN). PROVIDE DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. CABLING (CAT6A) TO CONNECT TO SWITCHING AND OCCUPANCY AND UTILIZES STANDARD LOW-VOLTAGE CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE MANUFACTURER.

LOW VOLTAGE SINGLE POLE LARGE PADDLE SWITCH. MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.

DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECT TO ROOM CONTROLLER. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL OCCUPANCY SENSORS

FOR HVAC SWITCHING. COORDINATE MOUNTING WITH MANUFACTURER'S RECOMMENDATIONS.

EXTERIOR SINGLE HEAD LED EMERGENCY LIGHT. CONNECT TO LIFE SAFETY POWER PANEL.

208/120V ELECTRICAL PANEL. SURFACE MOUNTED. X=EXISTING TO REMAIN.

FIRE ALARM CONTROL PANEL

TAMPER SWITCH

WATER FLOW SWITCH

WIFI ACCESS POINT. RE= REMOVE AND REINSTALL ON NEW CONSTRUCTION

OS

RC

LV

X

TS

FACP

WB

a

A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-ED101

EAST STAIR LIGHTING DEMOLITION PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

GROUND FLOOR DEMOLITION-EAST STAIR

1/4" = 1'-0"2

LEVEL 1 DEMOLITION-EAST STAIR

1/4" = 1'-0"3

LEVEL 2 DEMOLITION-EAST STAIR

1/4" = 1'-0"4

LEVEL 3 DEMOLITION-EAST STAIR

1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL

DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL BE DISPOSED OF BY THE

ELECTRICAL CONTRACTOR.

3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.

4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE

NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO ACHIEVE SAME.

5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL

CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY MANNER.

LIGHTING DEMOLITION GENERAL NOTES

KEY PLAN

Revisions: Date:

DTB

TS

TS

TS

WB

WB

3 3

1 (TYP. FOR 3)

1 (TYP. FOR 2)

PROJECT

NORTH

AREA OF

WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-ED102

CENTER STAIR LIGHTING DEMOLITION PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

BASEMENT DEMOLITION-CENTER STAIR AND MECHANICAL ROOM

1/4" = 1'-0"2

GROUND FLOOR DEMOLITION-CENTER STAIR

1/4" = 1'-0"3

LEVEL 1 DEMOLITION-CENTER STAIR

1/4" = 1'-0"4

LEVEL 2 DEMOLITION-CENTER STAIR

1/4" = 1'-0"5

LEVEL 3 DEMOLITION-CENTER STAIR

1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL

DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER

SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.

4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY

TO ACHIEVE SAME.

5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A

TIMELY MANNER.

LIGHTING DEMOLITION GENERAL NOTES

KEY PLAN

LIGHTING DEMOLITION KEYED NOTES

EXISTING TAMPER SWITCH AND FLOW SWITCH SHALL BE DEMOLISHED PER THE FIRE PROTECTION

DEMOLITION WORK.

Revisions: Date:

RE

RE

PROJECT

NORTH

AREA OF

WORK

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-ED103

WEST STAIR LIGHTING DEMOLITION PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

BASEMENT DEMOLITION-WEST STAIR

1/4" = 1'-0"2

GROUND FLOOR DEMOLITION-WEST STAIR

1/4" = 1'-0"3

LEVEL 1 DEMOLITION-WEST STAIR

1/4" = 1'-0"4

LEVEL 2 DEMOLITION-WEST STAIR

1/4" = 1'-0"5

LEVEL 3 DEMOLITION-WEST STAIR

1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL

DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER

SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.

4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY

TO ACHIEVE SAME.

5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A

TIMELY MANNER.

LIGHTING DEMOLITION GENERAL NOTES

KEY PLAN

Revisions: Date:

OS

LV

RC

OS

OS

LV

OS

LV

RC

OS

LV

a,b a a a a a

A

D

G

F

4 D b b b b b

A

A b c,dcc c c c

B

B B1 c

D d d d d

B

B

PROJECT

NORTH

AREA OF

WORK

LIGHTING FIXTURE SCHEDULE

TYPE

A

B

C

MANUFACTURER

COLUMBIA LIGHTING

MODEL NUMBER

LJT22-35MWG-FSA12-EDU

WATTAGE

18W

31W

LUMENS

CCT DESCRIPTION

COLUMBIA LIGHTING 2' X 4' TROFFER

2' X 2' TROFFER RECESSED MOUNTED3500K

3500K

F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT

LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370

LJT24-35MWG-FSA12-EDU

D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404

HUBBELL

G DUAL LITE LECSGWA 4W EXIT SIGN

COLUMBIA LIGHTING

RECESSED LED 2'X2' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

RECESSED LED 2'X4' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.

DEMOLISHED RECESSED LED LIGHTING FIXTURE

DEMOLISHED PENDANT LIGHT BULB

LINEAR LED LIGHTING FIXTURE. MOUNTING METHOD AS SHOWN ON THE PLAN. CONNECT TO EMERGENCY LIFE SAFETY CIRCUIT AS INDICATED

EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.

CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.

EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.

CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.

NOTE: REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.

UPPER LETTER INDICATES LIGHTING FIXTURE TYPE. LOWER LETTER INDICATES CONTROL GROUP.

ELECTRICAL LEGEND

20A-1P-120/277V WALL SWITCH . MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.

LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH AND OCCUPANCY SENSOR (WHERE SHOWN). PROVIDE DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. CABLING (CAT6A) TO CONNECT TO SWITCHING AND OCCUPANCY AND UTILIZES STANDARD LOW-VOLTAGE CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE MANUFACTURER.

LOW VOLTAGE SINGLE POLE LARGE PADDLE SWITCH. MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.

DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECT TO ROOM CONTROLLER. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL OCCUPANCY SENSORS

FOR HVAC SWITCHING. COORDINATE MOUNTING WITH MANUFACTURER'S RECOMMENDATIONS.

EXTERIOR SINGLE HEAD LED EMERGENCY LIGHT. CONNECT TO LIFE SAFETY POWER PANEL.

208/120V ELECTRICAL PANEL. SURFACE MOUNTED. X=EXISTING TO REMAIN.

FIRE ALARM CONTROL PANEL

TAMPER SWITCH

WATER FLOW SWITCH

WIFI ACCESS POINT. RE= REMOVE AND REINSTALL ON NEW CONSTRUCTION

OS

RC

LV

X

TS

FACP

WB

a

A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-E101

EAST STAIR LIGHTING NEW WORK PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

GROUND FLOOR NEW WORK-EAST STAIR

1/4" = 1'-0"2

LEVEL 1 NEW WORK-EAST STAIR

1/4" = 1'-0"3

LEVEL 2 NEW WORK-EAST STAIR

1/4" = 1'-0"4

LEVEL 3 NEW WORK-EAST STAIR

KEY PLAN

LIGHTING NEW WORK GENERAL NOTES

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING

HEIGHTS.

3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY

ALL CHANGES PRIOR TO ROUGH-IN.

4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE

FOR ADDITIONAL INFORMATION.

5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.

LIGHTING NEW WORK KEYED NOTES

ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.

COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.

EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.

EXTERIOR LIGHT SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL . THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V. THE MOUNTING HEIGHT SHALL MATCH WITH EXISTING.

NEW LIGHTING FIXTURE TO REPLACE EXISTING, MOUNTING HEIGHT TO MATCH EXISTING.

Revisions: Date:

RC

L V

TS

TS

TS

WB

WB

OS

L V

OSRC

L V

OS

L

V OS

L V a,b a a a

A

C

PANEL '1LS4'

X

5 (TYP. FOR 3)

5 (TYP. FOR 2)

A a b b b b

C C

G

F2

EXISTING

FACP

(ROOM 5A)

b

A c,d c c c c B

B

6 RE

A c d d d

A

A d d d d

A

D d

PROJECT

NORTH

AREA OF

WORK

LIGHTING FIXTURE SCHEDULE

TYPE

A

B

C

MANUFACTURER

COLUMBIA LIGHTING

MODEL NUMBER

LJT22-35MWG-FSA12-EDU

WATTAGE

18W

31W

LUMENS

CCT DESCRIPTION

COLUMBIA LIGHTING 2' X 4' TROFFER

2' X 2' TROFFER RECESSED MOUNTED3500K

3500K

F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT

LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370

LJT24-35MWG-FSA12-EDU

D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404

HUBBELL

G DUAL LITE LECSGWA 4W EXIT SIGN

COLUMBIA LIGHTING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-E102

CENTER STAIR LIGHTING NEW WORK PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

BASEMENT NEW WORK-CENTER STAIR AND MECHANICAL ROOM

1/4" = 1'-0"2

GROUND FLOOR NEW WORK-CENTER STAIR

1/4" = 1'-0"3

LEVEL 1 NEW WORK-CENTER STAIR

1/4" = 1'-0"4

LEVEL 2 NEW WORK-CENTER STAIR

1/4" = 1'-0"5

LEVEL 3 NEW WORK-CENTER STAIR

KEY PLAN

LIGHTING NEW WORK GENERAL NOTES

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING

HEIGHTS.

3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY

ALL CHANGES PRIOR TO ROUGH-IN.

4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE

OR ADDITIONAL INFORMATION.

5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.

LIGHTING NEW WORK KEYED NOTES

ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT CENTER STAIR NEW WORK PLAN FOR LOCATION. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT

BREAKER @120V. COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.

EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.

EXTERIOR LIGHT SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V. THE MOUNTING HEIGHT SHALL MATCH WITH EXISTING.

CONNECT TO EXISTING LIGHTING CIRCUITING AND SWITCHING.

INSTALL NEW TAMPER SWITCH ON NEW GATE VALVE AND NEW FLOW SWITCH ON WET PIPE VALVE PER FIRE PROTECTION NEW WORK. REFER TO FIRE PROTECTION RISER DIAGRAM FOR DETAILS. NEW TAMPER SWITCH AND FLOW SWITCH SHALL MATCH WITH EXISTING AND INTERLOCK WITH EXISTING FIRE ALARM SYSTEM. EXISTING FIRE ALARM CONTROL PANEL IS LOCATED IN ROOM A5 ON GROUND LEVEL. CONDUIT, WIRE AND GROUNDING SHALL MATCH WITH

EXISTING.

REINSTALL EXISTING WIFI ACCESS DEVICE. EXISTING TELECOMMUNICATION CABLE AND CONNECTION TO REMAIN.

NEW WALL MOUNTED LIGHTING FIXTURE TO REPLACE EXISTING PENDANT LIGHT, MOUNTING HEIGHT REFER TO

ARCHITECTURAL DRAWINGS.

Revisions: Date:

OS RC

LV

OS

LV

OS RC

LV

OS

LV

OS

LV

a,b a a a

A b b b

A

G

A b c,dc c c

A

3RE

D c

A c d d dd d

B

BB

d D d d d d B

B

3RE

PROJECT

NORTH

AREA OF

WORK

LIGHTING FIXTURE SCHEDULE

TYPE

A

B

C

MANUFACTURER

COLUMBIA LIGHTING

MODEL NUMBER

LJT22-35MWG-FSA12-EDU

WATTAGE

18W

31W

LUMENS

CCT DESCRIPTION

COLUMBIA LIGHTING 2' X 4' TROFFER

2' X 2' TROFFER RECESSED MOUNTED3500K

3500K

F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT

LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370

LJT24-35MWG-FSA12-EDU

D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404

HUBBELL

G DUAL LITE LECSGWA 4W EXIT SIGN

COLUMBIA LIGHTING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-E103

WEST STAIR LIGHTING NEW WORK PLANS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

1/4" = 1'-0"1

BASEMENT NEW WORK-WEST STAIR

1/4" = 1'-0"2

GROUND FLOOR NEW WORK-WEST STAIR

1/4" = 1'-0"3

LEVEL 1 NEW WORK-WEST STAIR

1/4" = 1'-0"4

LEVEL 2 NEW WORK-WEST STAIR

1/4" = 1'-0"5

LEVEL 3 NEW WORK-WEST STAIR

KEY PLAN

LIGHTING NEW WORK GENERAL NOTES

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL

EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.

2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING

HEIGHTS.

3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY

ALL CHANGES PRIOR TO ROUGH-IN.

4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE

OR ADDITIONAL INFORMATION.

5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE

BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.

6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.

LIGHTING NEW WORK KEYED NOTES

ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.

COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.

EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.

REINSTALL EXISTING WIFI ACCESS DEVICE. EXISTING TELECOMMUNICATION CABLE AND CONNECTION TO REMAIN.

NEW LIGHTING FIXTURE TO REPLACE EXISTING, MOUNTING HEIGHT TO MATCH EXISTING.

Revisions: Date:

NXRC-2R

BA

CAT5 Cable

OCC

PC

B u il d in g

A u to m a ti o n H

U B

B E

L L

R

Red 24VDC

Yellow Black

18AWG standard low voltage wire

NXDS-U

Photo Sensor

(As required per Room)

S V

C

P W

R S

V C

P

IN

NXSW SERIES

(As required per Room)

(As required per Room)

OCC

PC

B u il d in g

A u to m a ti o n H

U B

B E

L L

R

Red 24VDC

Blue

Black

18AWG standard low voltage wire

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

Low Voltage

Occupancy Sensor

(OMNI)

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

S V

C

P W

R S

V C

P

IN

Low Voltage Occupancy Sensor

(NX-OS-LODTR)

ROOM

CONTROLLER

2 OUTPUT

ON/OFF

H1 N

Load #1

H2 N

B la c k

/2

/3

V

A C

W h it e

N e u tr a l)

R e d

B lu e

White

W h it e

Load #2

Typical Mounting

HubNET Network

NX Bridge Module (Typical)

(As required) Junction Box

CAT5 Cable

To next bridge

From previous bridge

CAT5 Cable

CAT5 Cable

WALL

PHONE

6"

WALL

JOIST

8'-0"

18"

4'-0"

LIGHT

SWITCHES

3"

TSTAT/SENSOR

OR

ANNUNCIATOR

EXIT

RECEPTACLE

6'-6" TO

TOP OF

MCB

ELEC.

PANEL

1'-0"

FLOOR

CEILING

DETAIL NOTES :

1. COORDINATE ALL LOCATIONS OF ELECTRICAL EQUIPMENT WITH ARCHITECTURAL

DRAWINGS.

2. USE THESE DEVICE MOUNTING HEIGHTS UNLESS OTHERWISE INDICATED ON ARCHITECTURAL

DRAWINGS.

3. DEVICE HEIGHTS SHOWN FOR INFORMATIONAL PURPOSES ONLY. HEIGHTS APPLY FOR INSTALLED DEVICES AND

EQUIPMENT.

RECEPTACLE(S)

VOICE/DATA JACKS

AND JBOXES CENTER

BETWEEN JOISTS

44" MAX

STANDARD MOUNTING HEIGHTS

NTS

LUMINAIRE MOUNTING - LAY-IN CEILING

NTS

LUMINAIRE

SUSPENSION

WIRES REFER TO

SPECIFICATION

SECTION

26 51 00

3 TWIST

MINIMUM

(TYP)

FIXTURE WHIP FROM

JUNCTION BOX

(1829mm (6') LONG

MAX.)

LUMINAIRE.

REFER TO

SCHEDULE

LUMINAIRE MANUFACTURER'S

MOUNTING

HARDWARE

REFER TO SPECIFICATION SECTION 26

51 00

ACOUSTICAL CEILING

TILE

(TYP)

ARCHITECTURAL

CEILING GRID

LUMINAIRE.

REFER TO

SCHEDULE

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND USING

THE RECOMMENDED MOUNTING HARDWARE.

TYPICAL DUAL OUTPUT ON/OFF ROOM CONTROLLER DETAIL

NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

Z

P ro je c ts

\2 -U

S D

V A

-0 \3

-C A

D D ra w in g s \3

.4 -M

E P

\2 -U

S D

V A

-0 E

L E

C .r v t

/1

/2

:0 :4

P

M

1-E201

ELECTRICAL DETAILS

10/18/2021 BZ

561A4-15-102CORRECT FCA F RATED DEFICIENCIES

BUILDING 1

100% Final Documents

Revisions: Date:

File details come from the government source that posted it. Updated .