This solicitation is for a construction project to correct deficiencies in Building 1 at the VA New Jersey Healthcare System located in Lyons, New Jersey. The contractor shall demolish existing structures, prepare the site for building operations, and furnish labor and materials to perform work defined by the attached architecture and engineering drawings and specifications. The North American Industry Classification System code is 236220 with a business size of $39.5 million or less. This is a Service-Disabled Veteran Owned Small Business set-aside procurement with a construction magnitude between $1 million and $5 million. The completion time is 365 days from the notice to proceed date. A pre-bid walkthrough is scheduled for June 2, 2022 at 9:00 AM Eastern Time.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT
NORTH
AREA OF
WORK
RECESSED LED 2'X2' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
RECESSED LED 2'X4' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
DEMOLISHED RECESSED LED LIGHTING FIXTURE
DEMOLISHED PENDANT LIGHT BULB
LINEAR LED LIGHTING FIXTURE. MOUNTING METHOD AS SHOWN ON THE PLAN. CONNECT TO EMERGENCY LIFE SAFETY CIRCUIT AS INDICATED
EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.
CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.
EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.
CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.
NOTE: REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.
UPPER LETTER INDICATES LIGHTING FIXTURE TYPE. LOWER LETTER INDICATES CONTROL GROUP.
ELECTRICAL LEGEND
20A-1P-120/277V WALL SWITCH . MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.
LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH AND OCCUPANCY SENSOR (WHERE SHOWN). PROVIDE DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. CABLING (CAT6A) TO CONNECT TO SWITCHING AND OCCUPANCY AND UTILIZES STANDARD LOW-VOLTAGE CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE MANUFACTURER.
LOW VOLTAGE SINGLE POLE LARGE PADDLE SWITCH. MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECT TO ROOM CONTROLLER. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL OCCUPANCY SENSORS
FOR HVAC SWITCHING. COORDINATE MOUNTING WITH MANUFACTURER'S RECOMMENDATIONS.
EXTERIOR SINGLE HEAD LED EMERGENCY LIGHT. CONNECT TO LIFE SAFETY POWER PANEL.
208/120V ELECTRICAL PANEL. SURFACE MOUNTED. X=EXISTING TO REMAIN.
FIRE ALARM CONTROL PANEL
TAMPER SWITCH
WATER FLOW SWITCH
WIFI ACCESS POINT. RE= REMOVE AND REINSTALL ON NEW CONSTRUCTION
OS
RC
LV
X
TS
FACP
WB
a
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-ED101
EAST STAIR LIGHTING DEMOLITION PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
GROUND FLOOR DEMOLITION-EAST STAIR
1/4" = 1'-0"2
LEVEL 1 DEMOLITION-EAST STAIR
1/4" = 1'-0"3
LEVEL 2 DEMOLITION-EAST STAIR
1/4" = 1'-0"4
LEVEL 3 DEMOLITION-EAST STAIR
1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL
DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL BE DISPOSED OF BY THE
ELECTRICAL CONTRACTOR.
3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.
4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE
NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO ACHIEVE SAME.
5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL
CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY MANNER.
LIGHTING DEMOLITION GENERAL NOTES
KEY PLAN
Revisions: Date:
DTB
TS
TS
TS
WB
WB
3 3
1 (TYP. FOR 3)
1 (TYP. FOR 2)
PROJECT
NORTH
AREA OF
WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-ED102
CENTER STAIR LIGHTING DEMOLITION PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
BASEMENT DEMOLITION-CENTER STAIR AND MECHANICAL ROOM
1/4" = 1'-0"2
GROUND FLOOR DEMOLITION-CENTER STAIR
1/4" = 1'-0"3
LEVEL 1 DEMOLITION-CENTER STAIR
1/4" = 1'-0"4
LEVEL 2 DEMOLITION-CENTER STAIR
1/4" = 1'-0"5
LEVEL 3 DEMOLITION-CENTER STAIR
1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL
DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.
4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY
TO ACHIEVE SAME.
5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A
TIMELY MANNER.
LIGHTING DEMOLITION GENERAL NOTES
KEY PLAN
LIGHTING DEMOLITION KEYED NOTES
EXISTING TAMPER SWITCH AND FLOW SWITCH SHALL BE DEMOLISHED PER THE FIRE PROTECTION
DEMOLITION WORK.
Revisions: Date:
RE
RE
PROJECT
NORTH
AREA OF
WORK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-ED103
WEST STAIR LIGHTING DEMOLITION PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
BASEMENT DEMOLITION-WEST STAIR
1/4" = 1'-0"2
GROUND FLOOR DEMOLITION-WEST STAIR
1/4" = 1'-0"3
LEVEL 1 DEMOLITION-WEST STAIR
1/4" = 1'-0"4
LEVEL 2 DEMOLITION-WEST STAIR
1/4" = 1'-0"5
LEVEL 3 DEMOLITION-WEST STAIR
1. ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC IN SCOPE SHALL BE DISCONNECTED AND DEMOLISHED UNLESS OTHERWISE NOTED. EXISTING CIRCUITRY SHALL BE REMOVED BACK TO SOURCE AND MARK 'SPARE'. ELECTRICAL EQUIPMENT SHOWING 'X' INDICATES EXISTING TO REMAIN. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL
DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
2. ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
3. REFER TO ELECTRICAL SYMBOL LIST FOR ALL SYMBOL DESIGNATIONS.
4. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY
TO ACHIEVE SAME.
5. THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A
TIMELY MANNER.
LIGHTING DEMOLITION GENERAL NOTES
KEY PLAN
Revisions: Date:
OS
LV
RC
OS
OS
LV
OS
LV
RC
OS
LV
a,b a a a a a
A
D
G
F
4 D b b b b b
A
A b c,dcc c c c
B
B B1 c
D d d d d
B
B
PROJECT
NORTH
AREA OF
WORK
LIGHTING FIXTURE SCHEDULE
TYPE
A
B
C
MANUFACTURER
COLUMBIA LIGHTING
MODEL NUMBER
LJT22-35MWG-FSA12-EDU
WATTAGE
18W
31W
LUMENS
CCT DESCRIPTION
COLUMBIA LIGHTING 2' X 4' TROFFER
2' X 2' TROFFER RECESSED MOUNTED3500K
3500K
F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT
LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370
LJT24-35MWG-FSA12-EDU
D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404
HUBBELL
G DUAL LITE LECSGWA 4W EXIT SIGN
COLUMBIA LIGHTING
RECESSED LED 2'X2' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
RECESSED LED 2'X4' LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
DEMOLISHED RECESSED LED LIGHTING FIXTURE
DEMOLISHED PENDANT LIGHT BULB
LINEAR LED LIGHTING FIXTURE. MOUNTING METHOD AS SHOWN ON THE PLAN. CONNECT TO EMERGENCY LIFE SAFETY CIRCUIT AS INDICATED
EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.
CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.
EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.
CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.
NOTE: REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.
UPPER LETTER INDICATES LIGHTING FIXTURE TYPE. LOWER LETTER INDICATES CONTROL GROUP.
ELECTRICAL LEGEND
20A-1P-120/277V WALL SWITCH . MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.
LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH AND OCCUPANCY SENSOR (WHERE SHOWN). PROVIDE DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. CABLING (CAT6A) TO CONNECT TO SWITCHING AND OCCUPANCY AND UTILIZES STANDARD LOW-VOLTAGE CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE MANUFACTURER.
LOW VOLTAGE SINGLE POLE LARGE PADDLE SWITCH. MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECT TO ROOM CONTROLLER. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL OCCUPANCY SENSORS
FOR HVAC SWITCHING. COORDINATE MOUNTING WITH MANUFACTURER'S RECOMMENDATIONS.
EXTERIOR SINGLE HEAD LED EMERGENCY LIGHT. CONNECT TO LIFE SAFETY POWER PANEL.
208/120V ELECTRICAL PANEL. SURFACE MOUNTED. X=EXISTING TO REMAIN.
FIRE ALARM CONTROL PANEL
TAMPER SWITCH
WATER FLOW SWITCH
WIFI ACCESS POINT. RE= REMOVE AND REINSTALL ON NEW CONSTRUCTION
OS
RC
LV
X
TS
FACP
WB
a
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-E101
EAST STAIR LIGHTING NEW WORK PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
GROUND FLOOR NEW WORK-EAST STAIR
1/4" = 1'-0"2
LEVEL 1 NEW WORK-EAST STAIR
1/4" = 1'-0"3
LEVEL 2 NEW WORK-EAST STAIR
1/4" = 1'-0"4
LEVEL 3 NEW WORK-EAST STAIR
KEY PLAN
LIGHTING NEW WORK GENERAL NOTES
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.
2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING
HEIGHTS.
3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY
ALL CHANGES PRIOR TO ROUGH-IN.
4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE
FOR ADDITIONAL INFORMATION.
5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE
BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.
LIGHTING NEW WORK KEYED NOTES
ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.
COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.
EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.
EXTERIOR LIGHT SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL . THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V. THE MOUNTING HEIGHT SHALL MATCH WITH EXISTING.
NEW LIGHTING FIXTURE TO REPLACE EXISTING, MOUNTING HEIGHT TO MATCH EXISTING.
Revisions: Date:
RC
L V
TS
TS
TS
WB
WB
OS
L V
OSRC
L V
OS
L
V OS
L V a,b a a a
A
C
PANEL '1LS4'
X
5 (TYP. FOR 3)
5 (TYP. FOR 2)
A a b b b b
C C
G
F2
EXISTING
FACP
(ROOM 5A)
b
A c,d c c c c B
B
6 RE
A c d d d
A
A d d d d
A
D d
PROJECT
NORTH
AREA OF
WORK
LIGHTING FIXTURE SCHEDULE
TYPE
A
B
C
MANUFACTURER
COLUMBIA LIGHTING
MODEL NUMBER
LJT22-35MWG-FSA12-EDU
WATTAGE
18W
31W
LUMENS
CCT DESCRIPTION
COLUMBIA LIGHTING 2' X 4' TROFFER
2' X 2' TROFFER RECESSED MOUNTED3500K
3500K
F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT
LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370
LJT24-35MWG-FSA12-EDU
D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404
HUBBELL
G DUAL LITE LECSGWA 4W EXIT SIGN
COLUMBIA LIGHTING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-E102
CENTER STAIR LIGHTING NEW WORK PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
BASEMENT NEW WORK-CENTER STAIR AND MECHANICAL ROOM
1/4" = 1'-0"2
GROUND FLOOR NEW WORK-CENTER STAIR
1/4" = 1'-0"3
LEVEL 1 NEW WORK-CENTER STAIR
1/4" = 1'-0"4
LEVEL 2 NEW WORK-CENTER STAIR
1/4" = 1'-0"5
LEVEL 3 NEW WORK-CENTER STAIR
KEY PLAN
LIGHTING NEW WORK GENERAL NOTES
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.
2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING
HEIGHTS.
3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY
ALL CHANGES PRIOR TO ROUGH-IN.
4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE
OR ADDITIONAL INFORMATION.
5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE
BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.
LIGHTING NEW WORK KEYED NOTES
ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT CENTER STAIR NEW WORK PLAN FOR LOCATION. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT
BREAKER @120V. COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.
EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.
EXTERIOR LIGHT SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V. THE MOUNTING HEIGHT SHALL MATCH WITH EXISTING.
CONNECT TO EXISTING LIGHTING CIRCUITING AND SWITCHING.
INSTALL NEW TAMPER SWITCH ON NEW GATE VALVE AND NEW FLOW SWITCH ON WET PIPE VALVE PER FIRE PROTECTION NEW WORK. REFER TO FIRE PROTECTION RISER DIAGRAM FOR DETAILS. NEW TAMPER SWITCH AND FLOW SWITCH SHALL MATCH WITH EXISTING AND INTERLOCK WITH EXISTING FIRE ALARM SYSTEM. EXISTING FIRE ALARM CONTROL PANEL IS LOCATED IN ROOM A5 ON GROUND LEVEL. CONDUIT, WIRE AND GROUNDING SHALL MATCH WITH
EXISTING.
REINSTALL EXISTING WIFI ACCESS DEVICE. EXISTING TELECOMMUNICATION CABLE AND CONNECTION TO REMAIN.
NEW WALL MOUNTED LIGHTING FIXTURE TO REPLACE EXISTING PENDANT LIGHT, MOUNTING HEIGHT REFER TO
ARCHITECTURAL DRAWINGS.
Revisions: Date:
OS RC
LV
OS
LV
OS RC
LV
OS
LV
OS
LV
a,b a a a
A b b b
A
G
A b c,dc c c
A
3RE
D c
A c d d dd d
B
BB
d D d d d d B
B
3RE
PROJECT
NORTH
AREA OF
WORK
LIGHTING FIXTURE SCHEDULE
TYPE
A
B
C
MANUFACTURER
COLUMBIA LIGHTING
MODEL NUMBER
LJT22-35MWG-FSA12-EDU
WATTAGE
18W
31W
LUMENS
CCT DESCRIPTION
COLUMBIA LIGHTING 2' X 4' TROFFER
2' X 2' TROFFER RECESSED MOUNTED3500K
3500K
F 02-F-W-R-11-09-11 18W EXTERIOR WALL MOUNTED LIGHT
LAW4-35XW-EU 4' LIGHTING FIXTURE, SURFACE MOUNTED3500K19W 2370
LJT24-35MWG-FSA12-EDU
D 67L-W-D-4-4-SQ-C1-35KNDM-1C-UNVHUBBELL 4' LIGHTING FIXTURE, WALL MOUNTED3500K18W 2404
HUBBELL
G DUAL LITE LECSGWA 4W EXIT SIGN
COLUMBIA LIGHTING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-E103
WEST STAIR LIGHTING NEW WORK PLANS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
1/4" = 1'-0"1
BASEMENT NEW WORK-WEST STAIR
1/4" = 1'-0"2
GROUND FLOOR NEW WORK-WEST STAIR
1/4" = 1'-0"3
LEVEL 1 NEW WORK-WEST STAIR
1/4" = 1'-0"4
LEVEL 2 NEW WORK-WEST STAIR
1/4" = 1'-0"5
LEVEL 3 NEW WORK-WEST STAIR
KEY PLAN
LIGHTING NEW WORK GENERAL NOTES
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.
2. REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING
HEIGHTS.
3. WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY
ALL CHANGES PRIOR TO ROUGH-IN.
4. REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE
OR ADDITIONAL INFORMATION.
5. A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE
BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
6. NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.
LIGHTING NEW WORK KEYED NOTES
ROOM CONTROLLER SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.
COORDINATE WITH THE COR REGARDING CONTROLLER SETTINGS.
EXIT SIGN SHALL CONNECT TO LIFE SAFETY PANEL '1LS4' IN THE BASEMENT LEVEL AHEAD OF SWITCHING. REFER TO BASEMENT PARTIAL PLAN FOR DETAILS. THE TOTAL LOAD SHALL NOT EXCEED 1800VA WITH A 20A-1P CIRCUIT BREAKER @120V.
REINSTALL EXISTING WIFI ACCESS DEVICE. EXISTING TELECOMMUNICATION CABLE AND CONNECTION TO REMAIN.
NEW LIGHTING FIXTURE TO REPLACE EXISTING, MOUNTING HEIGHT TO MATCH EXISTING.
Revisions: Date:
NXRC-2R
BA
CAT5 Cable
OCC
PC
B u il d in g
A u to m a ti o n H
U B
B E
L L
R
Red 24VDC
Yellow Black
18AWG standard low voltage wire
NXDS-U
Photo Sensor
(As required per Room)
S V
C
P W
R S
V C
P
IN
NXSW SERIES
(As required per Room)
(As required per Room)
OCC
PC
B u il d in g
A u to m a ti o n H
U B
B E
L L
R
Red 24VDC
Blue
Black
18AWG standard low voltage wire
Low Voltage
Occupancy Sensor
(OMNI)
Low Voltage
Occupancy Sensor
(OMNI)
Low Voltage
Occupancy Sensor
(OMNI)
S V
C
P W
R S
V C
P
IN
S V
C
P W
R S
V C
P
IN
S V
C
P W
R S
V C
P
IN
Low Voltage Occupancy Sensor
(NX-OS-LODTR)
ROOM
CONTROLLER
2 OUTPUT
ON/OFF
H1 N
Load #1
H2 N
B la c k
/2
/3
V
A C
W h it e
N e u tr a l)
R e d
B lu e
White
W h it e
Load #2
Typical Mounting
HubNET Network
NX Bridge Module (Typical)
(As required) Junction Box
CAT5 Cable
To next bridge
From previous bridge
CAT5 Cable
CAT5 Cable
WALL
PHONE
6"
WALL
JOIST
8'-0"
18"
4'-0"
LIGHT
SWITCHES
3"
TSTAT/SENSOR
OR
ANNUNCIATOR
EXIT
RECEPTACLE
6'-6" TO
TOP OF
MCB
ELEC.
PANEL
1'-0"
FLOOR
CEILING
DETAIL NOTES :
1. COORDINATE ALL LOCATIONS OF ELECTRICAL EQUIPMENT WITH ARCHITECTURAL
DRAWINGS.
2. USE THESE DEVICE MOUNTING HEIGHTS UNLESS OTHERWISE INDICATED ON ARCHITECTURAL
DRAWINGS.
3. DEVICE HEIGHTS SHOWN FOR INFORMATIONAL PURPOSES ONLY. HEIGHTS APPLY FOR INSTALLED DEVICES AND
EQUIPMENT.
RECEPTACLE(S)
VOICE/DATA JACKS
AND JBOXES CENTER
BETWEEN JOISTS
44" MAX
STANDARD MOUNTING HEIGHTS
NTS
LUMINAIRE MOUNTING - LAY-IN CEILING
NTS
LUMINAIRE
SUSPENSION
WIRES REFER TO
SPECIFICATION
SECTION
26 51 00
3 TWIST
MINIMUM
(TYP)
FIXTURE WHIP FROM
JUNCTION BOX
(1829mm (6') LONG
MAX.)
LUMINAIRE.
REFER TO
SCHEDULE
LUMINAIRE MANUFACTURER'S
MOUNTING
HARDWARE
REFER TO SPECIFICATION SECTION 26
51 00
ACOUSTICAL CEILING
TILE
(TYP)
ARCHITECTURAL
CEILING GRID
LUMINAIRE.
REFER TO
SCHEDULE
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND USING
THE RECOMMENDED MOUNTING HARDWARE.
TYPICAL DUAL OUTPUT ON/OFF ROOM CONTROLLER DETAIL
NTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Z
P ro je c ts
\2 -U
S D
V A
-0 \3
-C A
D D ra w in g s \3
.4 -M
E P
\2 -U
S D
V A
-0 E
L E
C .r v t
/1
/2
:0 :4
P
M
1-E201
ELECTRICAL DETAILS
10/18/2021 BZ
561A4-15-102CORRECT FCA F RATED DEFICIENCIES
BUILDING 1
100% Final Documents
Revisions: Date: