Attachment 3 Sigonella Campus FCAR 2020.pdf
PDF 6 MB Posted
- Attached to
- Sources Sought Notice and Request for Information (RFI) for Total Maintenance Contract (TMC), Italy
- Solicitation number
- DODEAHQ-SS-001
- Issued by
-
Department of Defense Education Activity
About this file
This is a Facility Condition Assessment Report (FCAR) for the Sigonella Campus in Italy, documenting the physical condition of four DoDEA school buildings as of April 28, 2020.
The report provides comprehensive facility condition data for Buildings 211, 213, 216, 218, and 220 at Sigonella Elementary School and Sigonella Middle/High School. Building descriptions include stucco exteriors with clay tile roofs, ceramic tile and carpet flooring, painted hard surface walls, acoustical ceiling tiles, and package boiler HVAC systems with chilled water distribution. Key deficiencies identified include: roof flashing and drainage installation issues at Buildings 211, 216, 218, and 220 causing water damage and leaks; corroded exterior stucco and metal trim with crumbled areas and blistered paint at Buildings 211, 218, and 220; missing locker doors and water damage in Building 216; upheaving carpet and partition water damage in Building 218, Room 129; and cracked partition walls in Building 211. Additional observations document corroded HVAC distribution piping and motors in Building 213, severely corroded air separators in Building 216, corroded plumbing fixtures throughout restrooms, deteriorated fan coil units and air handling units, and regular power outages affecting fire suppression systems and VAV units. The assessment utilized the BUILDER Engineered Management System (EMS) Version 3 methodology with Direct Rating condition assessments for all component-sections. Work items are detailed by building across fiscal years 2015-2020, specifying required maintenance actions (paint, replace, repair) for exterior enclosure, roofing, interior finishes, HVAC, plumbing, electrical, and fire protection systems with associated square footages and quantities. All five buildings maintained their Q-Ratings (Q-1 or Q-2) from the previous assessment, indicating no structural changes to the facility inventory.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
"identification only"
II. SCHOOL PHYSICAL DESCRIPTION
The summary below provides a physical description of the campus. When multiple systems or materials are present, the predominant system or material observed during the facility condition assessment is shown.
a. STRUCTURAL/EXTERIOR ENCLOSURE: The building exterior is stucco. Roof coverings are clay tiles.
Exterior doors are pre-finished aluminum with glazing. Window systems are pre-finished aluminum with double-glazing.
b. INTERIORS: Floor finishes used include ceramic tile and carpet. Walls are painted hard surfaces. Ceilings are acoustical lay-in tiles.
c. MECHANICAL: Campus facilities have heating, which is provided by package boilers. All campus facilities have air conditioning, which is provided by chilled water. The campus has four elevators.
d. ELECTRICAL: No electrical upgrades have been completed and most wiring appears to be original.
Lighting is typically surface mounted fixtures with fluorescent lamps. Ground-fault circuit interrupter (GFCI) receptacles appear to be present in required locations. The campus has an intercom system. There is a security system, and security cameras are present.
e. PLUMBING: Plumbing fixtu es have been partially upgraded and piping appears to be original. Domestic hot water is provided by gas-fired storage water heaters.
f. SITE: The Sigonella Campus doe not have dedicated parking for privately owned vehicles. In addition, Sigonella Elementary School has four playg ounds.
g. LIFE SAFETY: A fire safety inspection report was not available for review.
III. OBSERVATIONS
The following observations were made: Exterior door security was not reported to be a problem. However, in Building 218, some of the second-floor egress doors have conflicting hardware installation as well as the egress doors at the second-floor elevated catwalk adjoining Buildings 216 and 220. This has resulted in some corridors having keyed entry locksets installed next to panic hardware, that can allow unrestricted entry.
The roof flashing and drainage systems at Buildings 211, 216, 218, and 220, appear to have installation issues and several maintenance repairs are evident of previous and possibly current roof covering leaks. The exterior walls (stucco) at Buildings 211, 218, and 220, appear to have the following installation issues: general exposure corrosion of metal edge trim, crumbled wall stucco areas, and blistered paint finish at numerous locations.
Overall, the interior construction systems throughout the campus are of various ages and in good to fair condition. The only major deficiencies observed in Building 218, Room 129, were upheaving carpet and significant water damage of the partitions. It was reported, all damaged carpet throughout the campus is going to be phased out and replaced with ceramic tile. On A-Floor of Building 211, there are major sections of wall tile missing; and it was reported, the hallway wall tile is being used to repair other sections of broken tile. In Building 211, Stairwell S102.2, there are major areas of surface cracking of the partition wall finish. In Building 216, there are a total of 29 missing doors on the lockers. Also, in Building 216, there is moderate water damage below the sink in the Central Supply Room. It was reported there is an active work order submitted to fix it; however, the direct condition rating will reflect the field findings.
It appears outside air is being introduced into the HVAC system. The distribution pump motors and connected distribution piping were found moderately corroded in Building 213. The campus is reported to have regular power outages, these power surges significantly affect the major systems on-site, specifically the fire suspension system, VAV units in classrooms to switch off, and the fan coil units, which are also corroded.
In Building 216, in Rooms 10 and 22, new circulating pumps were installed in FY2018. The air separators in Building 216, Room 10 and Room 22, are severely corroded on the units and piping. In addition, the air handling units in Building 216 are deteriorated on the intake pipes with minor fin corrosion inside the units.
The plumbing fixtures in most restrooms are corroded underneath the handles and on the faucets.
The Facility Utilization Survey (FUS) drawings have been updated to reflect the assessment findings, including room-use and room number changes observed throughout the campus. No buildings were added or removed from the site since the time of the previous assessment. Sigonella MS/HS Building 211 is shared between Sigonella Elementary School and Sigonella Middle/High School. Finally, it was observed that one of the concrete stairwells leading down to the track has a large chunk of concrete that had broken off underneath the initial landing which could pose a potential safety hazard.
Building 211 remained a Q-1.
Building 213 remained a Q-1.
Building 216 remained a Q-2.
Building 218 remained a Q-1.
Building 220 remained a Q-1.
Appendix A
Site Plan
Appendix B
Overview of Sustainment Management System (SMS) and
BUILDER™ Engineered Management System (EMS)
Overview of Sustainment Management System (SMS) and BUILDER™ Engineered Management System (EMS)
Sustainment Management System (SMS)
The Sustainment Management System (SMS) is a suite of web-based software applications developed by the
United States Army Corps of Engineers - Engineer Research Development Center - Construction Engineering
Research Laboratory (USACE-ERDC-CERL) to help facility engineers, technicians, and managers decide when, where, and how to best maintain the built environment. The SMS modules include BUILDER™ and
ROOFER™ for assessing building conditions, PAVER™ for pavements, and RAILER™ for railroad infrastructure.
Because real property assets are so vast and diverse, a "knowledge-based" philosophy drives the SMS process. The process starts with the automated download of real property data, and then more detailed system inventory is modeled and/or collected which identifies components and their key life cycle attributes such as the age and material.
From this inventory, Condition Index (CI) measures for each component are predicted based on its expected stage in the life cycle. Objective and repeatable inspections can then be performed on various components to verify their condition with respect to he expected life cycle deterioration. The level of detail and frequency of these inspections are not fixed like other processes; they are dependent on knowledge of component criticality, the expected and measured condition and rate of deterioration, and remaining maintenance and service life. This "knowledge-based" inspect on focuses attention to the most critical components at the time.
In addition to these condition assessments, functionality assessments can be performed to evaluate user requirement changes, compliance and obsolesce ce issues. This provides a comprehensive picture of the overall performance of real property assets and their key components.
BUILDER Engineered Management System (EMS)
In September 2013, the Under Secretary of Defense, Frank Kendall, issued a memo indicating the Department of Defense requires a standardized process for facility condition assessments to ensure consistent and reliable data necessary for sound strategic investment decisions in managing the Department's built environment.
Establishing a DoD-wide facility condition assessment process will contribute to a more credible DoD asset management program and will support better buying power by allowing Department leadership to better target fiscal resources to those facilities most in need of investment. Further, adopting a standard process will help ensure that condition data will be audit-ready in accordance with the Under Secretary of Defense (Comptroller)'s "Financial Improvement and Readiness Guidance" issued in March 2013.
The facility condition assessment process used to generate this report is based on BUILDER Engineered Management System (EMS) Version 3. BUILDER EMS was developed by the Engineer Research and Development Center.
The facility condition assessment process addresses the requirements necessary for routine building facility management activities, including long range budgeting and sustainment/restoration/modernization (SRM) planning. This assessment approach provides an objective and generalized framework to help to identify problem areas that will require more investigation through detailed or specialized assessments. There may be times when detailed engineering assessments may be required to diagnose specific problems.
BUILDER is a software application for building asset life cycle management. The primary focus of BUILDER is work plan development. BUILDER stores real property building information and more detailed system inventory is modeled and/or collected which identifies building components and their key life cycle attributes such as the age, material and capacity. Inspections are then performed on the various components to determine an objective and repeatable Condition Index (CI) measure, which relates the general physical health of the asset.
With information about condition and remaining service life, BUILDER guides the development of short- and long-range work plans based on sound investment strategies, prioritization criteria, and budget constraints.
BUILDER consolidates a variety of building-related management issues into a single decision-support package.
The system gives functional managers and decision-makers instant access to building inventory, current building condition indices, and probabilities condition prediction models. It also employs a patented knowledge-based inspection scheduling process. BUILDER improves the allocation process and return of building life cycle investments by directing resources to the most condition critical components to avoid costly repair penalty costs, as well as, the most mission critical components to manage risks of failure.
BUILDER Facility Condition Assessment Process
Facility Condition Assessment (FCA) is one of the primary processes of a facility life cycle asset management program. The FCA process results in a better understanding of the physical condition and readiness of an organization's buildings along with the reliability of its systems and components. It also facilitates the identification of work candidates for facility SRM repair projects. It is a critical aspect of the shift towards a proactive versus reactive facility management strategy. Instead of keeping facilities operational by relying primarily on corrective repairs (after a system or component has failed due to significant loss of function), it focuses on condition-based repairs which can be planned prior to failure. A condition-based approach can result in higher performing facilities at lower life cycle costs.
Prior to an assessment, knowledge of the building systems and components present is necessary, since assessments are done against these components, not against the building as a whole. This information about the systems and components that make up a building is called the BUILDER Inventory. BUILDER has a vast library of predefined components which an as essor will select from, and the inventory collection process involves identifying the type, quantity, and year installed for all pertinent components. These components are also organized into systems and sub-systems according to the UNIFORMAT classification hierarchy. When a specific instance of a component is recorded, this is called a component-section in BUILDER, and represents a single component assembly or colle tion of like components to be managed as a single unit. The BUILDER facility condition assessment process directly supports the computation of a condition index for building component-sections, known as the Component-Section Condition Index (CSCI), which is the fundamental metric used in BUILDER. The CSCI is aggregated to compute a condition index metric at the system (SCI), building (BCI), and site/organizational levels.
A condition-based facility repair strategy requires condition information be collected at a component level, and that this condition information relate to loss of component function. Every component of a building has a primary function that it performs. This function is the reason that the component was constructed or installed in the building. It may also serve a number of secondary or tertiary functions. For example, for a door component, the primary function is to provide safe entry/egress of authorized movements while limiting unwanted movements of people (security), or other objects (water or moisture). The secondary functions would relate to aesthetics and thermal and air control, among others.
The condition assessment process in BUILDER uses the Direct Rating method.
1. The Direct Rating method uses a single qualitative rating for each component based on condition observations. This also results in a condition index metric, which relates to the level of deterioration and the loss of function. This abbreviated Direct Rating approach is often better suited to initial baseline assessments where the components are inventoried, and data is initially loaded into BUILDER.
BUILDER Report Overview
Outlined below is a summary and description of the reports that are included.
Appendix C - Facility Summary Report – Provides a summation of FCA results. A Building Summary Report is included for each building that is considered permanent or semi-permanent construction and receives a Q-Rating. The purpose of this report is to provide a general overview of the building including key performance indicators. This report was generated using DoDEA's calculated Replacement Cost overwriting the data populated from real property records. This provides a more accurate Replacement Cost due to the inconsistencies with real property reconciliation between DoDEA and the Services. The DoD Facility Pricing Guide and DoDEA measurements for building square footage were used to calculate the Replacement Cost.
Appendix D - System Summary Report – Provides an overview of inspected systems and their condition index rating. A Building System Condition Index (SCI) By System Report is included for each building that is considered permanent or semi-permanent construction and receives a Q-Rating.
Appendix E - Work Items By Building – Provides a list of work items requiring repair or replacement of system/components, including budgets, for project planning purposes. A Work Plan Detail by Year Report is included for each building that is considered permanent or semi-permanent construction and receives a Q- Rating.
Appendix F - Remaining Service Life (RSL) Detail Report – Provides a detailed overview of systems/components, including descr ptions, and their respective age, remaining service life and remaining paint life.
Appendix G - Direct Condition Rating Inspection By Section Report – Provides a summary of direct condition ratings for each component-section collected within each facility.
Appendix H - System Inventory Report – Prov des a list of details for each component-section collected within each facility.
Appendix I - Fire Inspection Safety Report – This appendix is only applicable when a Fire Inspection Safety Report is provided at the time of the assessment for inclusion in the Facility Condition Assessment Report.
The report provides a summary of the recent Fire Inspection to include any deficiencies.
Note: All reports are generated from the DoDEA BUILDER database. n the event line items within a report are compressed and difficult to read, this is a result of how BUILDER generates the report. It is our understanding that CERL is working to update the report format.
Appendix C
Facility Summary Report
Appendix D
System Summary Report
Appendix E
Work Items By Building
B20 EXTERIOR ENCLOSURE2015
2008 B201001 EXTERIOR CLOSURE Stucco 20,305 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201005 EXTERIOR LOUVERS & SCREENS General 351 (SF) Pai t 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201005 EXTERIOR LOUVERS & SCREENS General
2008 B201007 EXTERIOR SOFFITS General 3,790 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFFITS General
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JOINT SEALANT General
B30 ROOFING2015
2008 B301005 GUTTERS & DOWNSPOUTS Downspouts 511 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 2008 B301005 GUTTERS & DOWNSPOUTS Downspouts
C30 INTERIOR FINISHES2015
2008 C302005 CARPETING General 1,695 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING General
B20 EXTERIOR ENCLOSURE2016
2008 B201001 EXTERIOR CLOSURE Stucco 20,305 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Unassigned211 - Sigonella MS/HS Bldg 211
Cost Book: Reference
Work Items by Building Report
Page 1 of 33April 28, 2020
2008 B201005 EXTERIOR LOUVERS & SCREENS General 351 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201005 EXTERIOR LOUVERS & SCREENS General
2008 B201007 EXTERIOR SOFFITS General 3,790 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFF TS General
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JOINT SEALANT General
B30 ROOFING2016
2008 B301005 GUTTERS & DOWNSPOUTS Downspouts 511 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 2008 B301005 GUTTERS & DOWNSPOUTS Downspouts
C30 INTERIOR FINISHES2016
2008 C302005 CARPETING General 1,695 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING General
B20 EXTERIOR ENCLOSURE2017
2008 B201001 EXTERIOR CLOSURE Stucco 20,305 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201005 EXTERIOR LOUVERS & SCREENS General 351 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201005 EXTERIOR LOUVERS & SCREENS General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Unassigned211 - Sigonella MS/HS Bldg 211
Cost Book: Reference
Work Items by Building Report
Page 2 of 33April 28, 2020
2008 B201007 EXTERIOR SOFFITS General 3,790 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFFITS General
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JO NT SEALANT General
B30 ROOFING2017
2008 B301005 GUTTERS & DOWNSPOUTS Downspouts 511 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 2008 B301005 GUTTERS & DOWNSPOUTS Downspouts
C10 INTERIOR CONSTRUCTION2017
2008 C101001 FIXED PARTITIONS Wall - Plaster w/Stud Framing 41,597 (SF) Paint 0.00C1010 PARTITIONS
-- Paint C1010 PARTITIONS 2008 C101001 FIXED PARTITIONS General
2008 C103008 COUNTERS Laminated Plastic 37 (LF) Replace 0.00C1030 SPECIALTIES
-- Replace C1030 SPECIALTIES 2008 C103008 COUNTERS General
C30 INTERIOR FINISHES2017
2008 C302005 CARPETING General 1,695 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING General
B20 EXTERIOR ENCLOSURE2018
2008 B201001 EXTERIOR CLOSURE Stucco 30,536 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Unassigned211 - Sigonella MS/HS Bldg 211
Cost Book: Reference
Work Items by Building Report
Page 3 of 33April 28, 2020
2008 B201005 EXTERIOR LOUVERS & SCREENS General 351 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201005 EXTERIOR LOUVERS & SCREENS General
2008 B201007 EXTERIOR SOFFITS General 3,790 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFF TS General
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT General
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT Genera
C30 INTERIOR FINISHES2019
2008 C302005 CARPETING General 1,695 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING Carpet Tile
B20 EXTERIOR ENCLOSURE2020
2008 A B201010 EXTERIOR JOINT SEALANT General 600 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT General
C30 INTERIOR FINISHES2020
2008 C302005 CARPETING General 1,662 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Unassigned211 - Sigonella MS/HS Bldg 211
Cost Book: Reference
Work Items by Building Report
Page 4 of 33April 28, 2020
1999 B201005 EXTERIOR LOUVERS & SCREENS Gene al 102 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201005 EXTERIOR LOUVERS & SCREENS General
1999 B201006 BALCONY WALLS & HANDRAILS Handrailing 161 (LF) Pai t 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201006 BALCONY WALLS & HANDRAILS Handrailing
1999 B201007 EXTERIOR SOFFITS General 2,127 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
1999 A B201001 EXTERIOR CLOSURE Stucco 5,113 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201010 EXTERIOR JOINT SEALANT General
1999 B B201001 EXTERIOR CLOSURE Stucco 390 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Grey B201001 EXTERIOR CLOSURE Stucco
B30 ROOFING2015
1999 B301005 GUTTERS & DOWNSPOUTS Downspouts 989 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 1999 B301005 GUTTERS & DOWNSPOUTS Downspouts
C20 STAIRS2015
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 5 of 33April 28, 2020
1999 B C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 30 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 1999 Exte ior C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
D30 HVAC2015
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Recip ocating Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS CH York D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
B20 EXTERIOR ENCLOSURE2016
1999 B201005 EXTERIOR LOUVERS & SCREENS General 102 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201005 EXTERIOR LOUVERS & SCREENS Gene al
1999 B201007 EXTERIOR SOFFITS General 2,127 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
1999 A B201001 EXTERIOR CLOSURE Stucco 5,113 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201010 EXTERIOR JOINT SEALANT General
1999 B B201001 EXTERIOR CLOSURE Stucco 390 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Grey B201001 EXTERIOR CLOSURE Stucco
B30 ROOFING2016
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 6 of 33April 28, 2020
1999 B301005 GUTTERS & DOWNSPOUTS Downspouts 989 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 1999 B301005 GUTTERS & DOWNSPOUTS Downspouts
C20 STAIRS2016
1999 B C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 30 (LF) Pai t 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 1999 Exterior C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
D20 PLUMBING2016
1999 D201002 URINALS General 7 (EA) Repair 0.00D2010 PLUMBING FIXTURES
-- Repair D2010 PLUMBING FIXTURES D201002 URINALS General
D30 HVAC2016
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS CH York D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
B20 EXTERIOR ENCLOSURE2017
1999 B201005 EXTERIOR LOUVERS & SCREENS General 102 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201005 EXTERIOR LOUVERS & SCREENS General
1999 B201006 BALCONY WALLS & HANDRAILS Handrailing 161 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201006 BALCONY WALLS & HANDRAILS Handrailing
1999 B201007 EXTERIOR SOFFITS General 2,127 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 7 of 33April 28, 2020
1999 A B201001 EXTERIOR CLOSURE Stucco 5,113 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201010 EXTERIOR JO NT SEALANT General
1999 B B201001 EXTERIOR CLOSURE Stucco 390 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Grey B201001 EXTERIOR CLOSURE Stucco
C10 INTERIOR CONSTRUCTION2017
1999 C101001 FIXED PARTITIONS Wall - Plaster w/Stud Framing 57,948 (SF) Paint 0.00C1010 PARTITIONS
-- Paint C1010 PARTITIONS 1999 C101001 FIXED PARTITIONS General
1999 C103010 CASEWORK General 1,548 (LF) Replace 0.00C1030 SPECIALTIES
-- Replace C1030 SPECIALTIES 1999 C103010 CASEWORK General
C20 STAIRS2017
1999 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 790 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 1999 C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
1999 B C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 30 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 1999 Exterior C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
C30 INTERIOR FINISHES2017
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 8 of 33April 28, 2020
1999 C303002 GYPSUM WALLBOARD CEILING FINISHES General 8,831 (SF) Paint 0.00C3030 CEILING FINISHES
-- Paint C3030 CEILING FINISHES 1999 C303002 GYPSUM WALLBOARD CEILING FINISHES General
1999 C303003 PLASTER CEILING FINISHES General 15,437 (SF) Paint 0.00C3030 CEILING FINISHES
-- Paint C3030 CEILING FINISHES 1999 C303003 PLASTER CEILING FINISHES General
D30 HVAC2017
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS CH York D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
1999 ATTIC D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/6A D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 ATTIC AHU-5 D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/5 D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 ATTIC MAU-6 D304008 AIR HANDLING UNITS Central Station - 10000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS MAHU/6 D304008 AIR HANDLING UNITS Central Station - 10000 CFM
1999 ROOM 22 D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/1 D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 ROOM G61 AHU 2 D304008 AIR HANDLING UNITS Central Station - 5000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/2 D304008 AIR HANDLING UNITS Central Station - 5000 CFM
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 9 of 33April 28, 2020
1999 ROOM G61 AHU 3 D304008 AIR HANDLING UNITS Central Station - 5000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/3 D304008 AIR HANDLING UNITS Central Station - 5000 CFM
1999 ROOM G61 AHU 4 D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Repair 0.00D3040 DISTRIBUTION SYSTEMS
-- Repair D3040 DISTRIBUTION SYSTEMS AHU/4 D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 D305003 FAN COIL UNITS Cab Mount, Four Pipe - 3 ton 24 (EA) Repair 0.00D3050 TERMINAL & PACKAGE UNITS
-- Repair D3050 TERMINAL & PACKAGE UNITS Classroom FCUs D305003 FAN COIL UNITS Cab Mount, Four Pipe - 3 ton
1999 D305003 FAN COIL UNITS Cab Mount, Two Pipe - 1 ton 15 (EA) Repair 0.00D3050 TERMINAL & PACKAGE UNITS
-- Repair D3050 TERMINAL & PACKAGE UNITS Ceiling unit heaters D305003 FAN COIL UN TS Cab Mount, Two Pipe - 1 ton
1999 D306002 ELECTRONIC CONTROLS General 58 (EA) Repair 0.00D3060 CONTROLS & INSTRUMENTATION
-- Repair D3060 CONTROLS & INSTRUMENTATION D306001 HVAC CONTROLS General
D50 ELECTRICAL2017
1999 D503003 INTERCOMMUNICATIONS SYSTEMS 25 stations 1 (EA) Repair 0.00D5030 COMMUNICATIONS & SECURITY
-- Repair D5030 COMMUNICATIONS & SECURITY D503003 INTERCOMMUNICATIONS SYSTEMS 25 stations
1999 D509002 EMERGENCY LIGHTING & POWER Uninterruptible Power Supply - 0.5 kVA 3 (EA) Repair 0.00D5090 OTHER ELECTRICAL SERVICES
-- Repair D5090 OTHER ELECTRICAL SERVICES D509002 EMERGENCY LIGHTING & POWER Uninteruptible Power Supply
B20 EXTERIOR ENCLOSURE2018
1999 B201007 EXTERIOR SOFFITS General 2,127 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 10 of 33April 28, 2020
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 A B201010 EXTERIOR JOINT SEALANT General
1999 B B201001 EXTERIOR CLOSURE Stucco 390 (S ) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B B201001 EXTERIOR CLOSURE Stucco
B30 ROOFING2018
1999 B301003 ROOF INSULATION & FILL General 12,475 (SF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301003 ROOF INSULATION & FILL General
C20 STAIRS2018
1999 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 790 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 1999 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
D20 PLUMBING2018
1999 D203002 VENT PIPE & FITTINGS General 2,365 (EA) Replace 0.00D2030 SANITARY WASTE
-- Replace D2030 SANITARY WASTE 1999 D203002 VENT PIPE & FITTINGS General
D30 HVAC2018
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS 1999 D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
1999 D304003 HOT WATER DISTRIBUTION SYSTEMS General 1,565 (MBH) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304003 HOT WATER DISTRIBUTION SYSTEMS General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 11 of 33April 28, 2020
1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General 157 (TON) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General
1999 D306002 ELECTRONIC CONTROLS General 58 (EA) Replace 0.00D3060 CONTROLS & INSTRUMENTATION
-- Replace D3060 CONTROLS & INSTRUMENTATION 1999 D306002 ELECTRONIC CONTROLS General
D40 FIRE PROTECTION2018
1999 D401001 FIRE ALARM DISTRIBUTION Other 62,613 (SF) Replace 0.00D4010 FIRE ALARM AND DETECTION SYSTEMS
-- Replace D4010 FIRE ALARM AND DETECTION SYSTEMS 1999 D401001 FIRE ALARM DISTRIBUTION Other
D50 ELECTRICAL2018
1999 D501004 PANELBOARDS Main lugs, 200 amp 3 (EA) Repair 0.00D5010 ELECTRICAL SERVICE & DISTRIBUTION
-- Repair D5010 ELECTRICAL SERVICE & DISTRIBUTION 1999 D501004 PANELBOARDS Main lugs, 200 amp
1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General 62,613 (SF) Replace 0.00D5090 OTHER ELECTRICAL SERVICES
-- Replace D5090 OTHER ELECTRICAL SERVICES 1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General
B20 EXTERIOR ENCLOSURE2019
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 A B201010 EXTERIOR JOINT SEALANT General
B30 ROOFING2019
1999 B301003 ROOF INSULATION & FILL General 12,475 (SF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301003 ROOF INSULATION & FILL General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 12 of 33April 28, 2020
D20 PLUMBING2019
1999 D203002 VENT PIPE & FITTINGS General 2,365 (EA) Replace 0.00D2030 SANITARY WASTE
-- Replace D2030 SANITARY WASTE 1999 D203002 VENT PIPE & FITTINGS General
D30 HVAC2019
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS 1999 D303001 CH LLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
1999 D304003 HOT WATER DISTRIBUTION SYSTEMS General 1,565 (MBH) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304003 HOT WATER DISTRIBUTION SYSTEMS General
1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General 157 (TON) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General
1999 D306002 ELECTRONIC CONTROLS General 58 (EA) Replace 0.00D3060 CONTROLS & INSTRUMENTATION
-- Replace D3060 CONTROLS & INSTRUMENTATION 1999 D306002 ELECTRONIC CONTROLS General
D40 FIRE PROTECTION2019
1999 D401001 FIRE ALARM DISTRIBUTION Other 62,613 (SF) Replace 0.00D4010 FIRE ALARM AND DETECTION SYSTEMS
-- Replace D4010 FIRE ALARM AND DETECTION SYSTEMS 1999 D401001 FIRE ALARM DISTRIBUTION Other
D50 ELECTRICAL2019
1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General 62,613 (SF) Replace 0.00D5090 OTHER ELECTRICAL SERVICES
-- Replace D5090 OTHER ELECTRICAL SERVICES 1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 13 of 33April 28, 2020
B20 EXTERIOR ENCLOSURE2020
1999 B201007 EXTERIOR SOFFITS General 2,127 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
1999 A B201010 EXTERIOR JOINT SEALANT General 488 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 A B201010 EXTERIOR JOINT SEALANT General
1999 B B201001 EXTERIOR CLOSURE Stucco 390 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B B201001 EXTERIOR CLOSURE Stucc
B30 ROOFING2020
1999 B301003 ROOF INSULATION & FILL General 12,475 (SF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301003 ROOF INSULATION & FILL General
D20 PLUMBING2020
1999 D203002 VENT PIPE & FITTINGS General 2,365 (EA) Replace 0.00D2030 SANITARY WASTE
-- Replace D2030 SANITARY WASTE 1999 D203002 VENT PIPE & FITTINGS General
D30 HVAC2020
1999 D302004 AUXILIARY EQUIPMENT Chemical Feedwater - 150 lb., 5 gallon, ASME 2 (EA) Replace 0.00D3020 HEAT GENERATING SYSTEMS
-- Replace D3020 HEAT GENERATING SYSTEMS 1999 D302004 AUXILIARY EQUIPMENT Chemical Feedwater - 150 lb., 5 gallon, ASME
1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN 1 (EA) Replace 0.00D3030 COOLING GENERATING SYSTEMS
-- Replace D3030 COOLING GENERATING SYSTEMS 1999 OUTSIDE D303001 CHILLED WATER SYSTEMS Chiller, Reciprocating, Air Cooled - 60 TN
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 14 of 33April 28, 2020
1999 D304001 AIR DISTRIBUTION, HEATING & COOLING Air Separator - Air control, air separator, 4" diameter, includes strainer 2 (EA) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304001 AIR DISTRIBUTION, HEATING & COOLING Air Separator - Air control, air separator, 4" diameter, includes strainer
1999 D304003 HOT WATER DISTRIBUTION SYSTEMS General 1,565 (MBH) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304003 HOT W TER DISTRIBUTION SYSTEMS General
1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General 157 (TON) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 D304006 CHILLED WATER DISTRIBUTION SYSTEMS General
1999 ROOM 22 D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 ROOM 22 D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 ROOM G61 AHU 2 D304008 AIR HANDLING UNITS Central Station - 5000 CFM 1 (EA) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 ROOM G61 AHU 2 D304008 AIR HANDLING UN TS Central Station - 5000 CFM
1999 ROOM G61 AHU 3 D304008 AIR HANDLING UNITS Central Station - 5000 CFM 1 (EA) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 ROOM G61 AHU 3 D304008 AIR HANDLING UNITS Central Station 5000 CFM
1999 ROOM G61 AHU 4 D304008 AIR HANDLING UNITS Central Station - 2000 CFM 1 (EA) Replace 0.00D3040 DISTRIBUTION SYSTEMS
-- Replace D3040 DISTRIBUTION SYSTEMS 1999 ROOM G61 AHU 4 D304008 AIR HANDLING UNITS Central Station - 2000 CFM
1999 D306002 ELECTRONIC CONTROLS General 58 (EA) Replace 0.00D3060 CONTROLS & INSTRUMENTATION
-- Replace D3060 CONTROLS & INSTRUMENTATION 1999 D306002 ELECTRONIC CONTROLS General
D40 FIRE PROTECTION2020
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 15 of 33April 28, 2020
1999 D401001 FIRE ALARM DISTRIBUTION Other 62,613 (SF) Replace 0.00D4010 FIRE ALARM AND DETECTION SYSTEMS
-- Replace D4010 FIRE ALARM AND DETECTION SYSTEMS 1999 D401001 FIRE ALARM DISTRIBUTION Other
D50 ELECTRICAL2020
1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General 62,613 (SF) Replace 0.00D5090 OTHER ELECTRICAL SERVICES
-- Replace D5090 OTHER ELECTRICAL SERVICES 1999 D509006 ENERGY MANAGEMENT CONTROL SYSTEM General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)216 - Sigonella MS/HS Bldg 216
Cost Book: Reference
Work Items by Building Report
Page 16 of 33April 28, 2020
31,466 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201007 EXTERIOR SOFFITS General 3,898 (SF) Pai t 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFFITS General
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JOINT SEALANT General
C20 STAIRS2015
2008 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 100 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 2008 C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
B20 EXTERIOR ENCLOSURE2016
2008 B201001 EXTERIOR CLOSURE Stucco 31,466 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201007 EXTERIOR SOFFITS General 3,898 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFFITS General
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JOINT SEALANT General
C20 STAIRS2016
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)220 - Sigonella MS/HS Bldg 220
Cost Book: Reference
Work Items by Building Report
Page 17 of 33April 28, 2020
2008 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 100 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 2008 C20 090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
B20 EXTERIOR ENCLOSURE2017
2008 B201001 EXTERIOR CLOSURE Stucco 31,466 (SF) Pai t 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201001 EXTERIOR CLOSURE Wall Louver 159 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Wall Louver
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 B201010 EXTERIOR JOINT SEALANT General
B30 ROOFING2017
2008 B301005 GUTTERS & DOWNSPOUTS Downspouts 529 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 2008 B301005 GUTTERS & DOWNSPOUTS Downspouts
2008 B B301004 FLASHINGS & TRIM General 262 (LF) Paint 0.00B3010 ROOF COVERINGS
-- Paint B3010 ROOF COVERINGS 2008 Stucco Fascia B301004 FLASHINGS & TRIM Other
C10 INTERIOR CONSTRUCTION2017
2008 C101001 FIXED PARTITIONS Wall - Drywall w/Stud Framing 58,932 (SF) Paint 0.00C1010 PARTITIONS
-- Paint C1010 PARTITIONS 2008 C101001 FIXED PARTITIONS General
C20 STAIRS2017
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)220 - Sigonella MS/HS Bldg 220
Cost Book: Reference
Work Items by Building Report
Page 18 of 33April 28, 2020
2008 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 100 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 2008 C20 090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
2008 B C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 442 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 2008 - Interior C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
C30 INTERIOR FINISHES2017
2008 C302005 CARPETING Carpet Tile 13,122 (SF) Replace 0.00C3020 FLOOR FINISHES
-- Replace C3020 FLOOR FINISHES 2008 C302005 CARPETING General
B20 EXTERIOR ENCLOSURE2018
2008 B201001 EXTERIOR CLOSURE Stucco 31,466 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 B201007 EXTERIOR SOFFITS General 3,898 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201007 EXTERIOR SOFFITS General
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT General
C20 STAIRS2018
2008 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General 680 (LF) Paint 0.00C2010 STAIR CONSTRUCTION
-- Paint C2010 STAIR CONSTRUCTION 2008 A C201090 STAIR HANDRAILS, GUARDRAILS AND ACCESSORIES General
B20 EXTERIOR ENCLOSURE2019
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)220 - Sigonella MS/HS Bldg 220
Cost Book: Reference
Work Items by Building Report
Page 19 of 33April 28, 2020
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT General
2008 B201001 EXTERIOR CLOSURE Stucco 31,466 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 2008 B201001 EXTERIOR CLOSURE Stucco
2008 A B201010 EXTERIOR JOINT SEALANT General 826 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 2008 A B201010 EXTERIOR JOINT SEALANT General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella MS/HS (HE5515)220 - Sigonella MS/HS Bldg 220
Cost Book: Reference
Work Items by Building Report
Page 20 of 33April 28, 2020
1999 B201001 EXTERIOR CLOSURE Stucco 16,594 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 B201001 EXTERIOR CLOSURE Wall Louver 133 (SF) Pai t 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Wall Louver
1999 B201006 BALCONY WALLS & HANDRAILS Handrailing 144 (LF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Courtyard B201006 BALCONY WALLS & HANDRAILS Handrailing
1999 B201007 EXTERIOR SOFFITS General 2,442 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
1999 A B201010 EXTERIOR JOINT SEALANT General 550 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201010 EXTERIOR JOINT SEALANT General
1999 A B201011 SUN CONTROL DEVICES General 300 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 OHD Area B201011 SUN CONTROL DEVICES General
1999 B B201011 SUN CONTROL DEVICES General 312 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Window Awning B201011 SUN CONTROL DEVICES General
B30 ROOFING2015
1999 B301004 FLASHINGS & TRIM Flashings - Base 1,184 (LF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301004 FLASHINGS & TRIM Flashings - Base
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella ES (HE5555)213 - Sigonella ES Bldg 213
Cost Book: Reference
Work Items by Building Report
Page 21 of 33April 28, 2020
1999 B301090 OTHER ROOFING Walkway Protection 3,534 (SF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301002 LOW SLOPE ROOF SYSTEMS Modified Bitumen
1999 B B301004 FLASHINGS & TRIM Flashings - Flashing Penetrations 3 (EA) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999b B301004 FLASHINGS & TRIM Flashings - Flashing Penetrations
B20 EXTERIOR ENCLOSURE2016
1999 B201001 EXTERIOR CLOSURE Stucco 16,594 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 B201001 EXTERIOR CLOSURE Wall Louver 133 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Wall Louver
1999 B201006 BALCONY WALLS & HANDRAILS Handrailing 144 (LF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Courtyard B201006 BALCONY WALLS & HANDRAILS Handrailing
1999 B201007 EXTERIOR SOFFITS General 2,442 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201007 EXTERIOR SOFFITS General
1999 A B201010 EXTERIOR JOINT SEALANT General 550 (LF) Replace 0.00B2010 EXTERIOR WALLS
-- Replace B2010 EXTERIOR WALLS 1999 B201010 EXTERIOR JOINT SEALANT General
1999 A B201011 SUN CONTROL DEVICES General 300 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 OHD Area B201011 SUN CONTROL DEVICES General
NAS1 Support Area
Year System
Completion Date
Qty (UM) CostActivity
Section Description
Component Status
-- Description
ScoreProject
Sigonella ES (HE5555)213 - Sigonella ES Bldg 213
Cost Book: Reference
Work Items by Building Report
Page 22 of 33April 28, 2020
1999 B B201011 SUN CONTROL DEVICES General 312 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Window Awning B201011 SUN CONTROL DEVICES General
B30 ROOFING2016
1999 B301004 FLASHINGS & TRIM Flashings - Base 1,184 (LF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301004 FLASHINGS & TRIM Flashings - Base
1999 B301090 OTHER ROOFING Walkway Protection 3,534 (SF) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999 B301002 LOW SLOPE ROOF SYSTEMS Modified Bitumen
1999 B B301004 FLASHINGS & TRIM Flashings - Flashing Penetrations 3 (EA) Replace 0.00B3010 ROOF COVERINGS
-- Replace B3010 ROOF COVERINGS 1999b B301004 FLASHINGS & TRIM Flashings - Flashing enetrations
B20 EXTERIOR ENCLOSURE2017
1999 B201001 EXTERIOR CLOSURE Stucco 16,594 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Stucco
1999 B201001 EXTERIOR CLOSURE Wall Louver 133 (SF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 B201001 EXTERIOR CLOSURE Wall Louver
1999 B201006 BALCONY WALLS & HANDRAILS Handrailing 144 (LF) Paint 0.00B2010 EXTERIOR WALLS
-- Paint B2010 EXTERIOR WALLS 1999 Courtyard B201006 BALCONY WALLS & HANDRAILS…
This is the start of the file's text. The full file is on GovTribe.