DNC-810CM3030_Submission_BD_Plans_Part2.pdf

PDF 19 MB Posted

Attached to
DAYTON NATIONAL CEMETERY: PIC/Admin Bldg, Repair Roads, & Replace Committal Shelter B
Solicitation number
36C78623B0033
Issued by

About this file

This federal contract opportunity notice is for construction services at the Dayton National Cemetery in Ohio. The Department of Veterans Affairs National Cemetery Administration is soliciting proposals under solicitation number 36C78623B0033 to repair and replace several structures at the cemetery. Services required include repairs to roads throughout the cemetery, replacement of the committal shelter building which is used for funeral services, and repairs and renovations to the cemetery's Public Information and Administration building. Proposals are due by the date listed in the solicitation document, and the agency anticipates making an award by the date also specified therein. The opportunity is open to all responsible sources and has no specific set-aside designations.

View the file

Other files

File Type Posted
S06_36C78623B0033 0004.pdf PDF
S02_ Attachment - RFIs and Answers.docx DOCX document
S02_Attachment - 090600SchedFinish.pdf PDF
S06_36C78623B0033 0003.pdf PDF
S02_Attachment - 087100DoorHardware.pdf PDF
S02_Attachment - DNC-810CM3030_Submission_BD_Revised Plan Sheets_Amendment 002.pdf PDF
S02_Attachment - 2023-09-14-DNC Amendment Memo 002.pdf PDF
S02_Attachment - 073113AsphaltShingles.pdf PDF
S02_Attachment - Wage Determination dtd 9.01.2023 (Heavy and Highway).pdf PDF
S06_36C78623B0033 0002.pdf PDF
S02_Attachment - Site Visit Attendance Roster.pdf PDF
S02_Attachment - Davis-Bacon Act Poster.pdf PDF
S06_36C78623B0033 0001.pdf PDF
S02_Attachment - DOL Payroll Form.pdf PDF
S02_Attachment - Wage Determination dtd 8.04.2023 (Building).pdf PDF
S02_Attachment - AE Amendment 001.pdf PDF
S02_Attachment - Standard Form 1413.pdf PDF
S02_36C78623B0033 (updated 8.25.2023).docx DOCX document
S02_Attachment - Wage Determination dtd 8.04.2023 (Heavy and Highway).pdf PDF
DNC-810CM3030-Bid Docs SPECS_Vol I.pdf PDF
DNC-810CM3030_Submission_BD_Plans_Part1.pdf PDF
DNC-810CM3030-Bid Docs SPECS_Vol II.pdf PDF
DNC-810CM3030_Submission_BD_Plans_Part4.pdf PDF
36C78623B0033_2 Dayton IFB Final.docx DOCX document
DNC-810CM3030_Submission_BD_Plans_Part3.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1.5

A B D

E

H3

H4

H5

H6

G

F1

H.2

1" 1/2"

1/2" 1"

3"

1 1/4"

1"

3/4"

3"

2 1/2" 3/4" 3/4"

3/4"

3/4"

1"

2 1/2"

3/4"

2 1/2"

1"

2 1/2"

1" 3/4"

3/4"

1"

2"

3"

3/4"

3/4"

3"

MOP SINK

DRINK FOUNTAIN

3 4

TO REMAIN

TO REMAIN

TO REMAIN

H3.1

H

L

NOT PART OF SCOPE

NOT PART

OF SCOPE

NOT PART OF SCOPE

NOT PART OF SCOPE

NOT PART OF SCOPE

MAINTENANCE BAY

MAINT. BAY

SHOP

PARTS /TOOLS

LUNCH ROOM

CORRIDOR

MECHANICAL

ROOM

ENCLOSED

MAINTENANCE

BAYS134

STORAGE SHED

1302A

MAINT. SHED

SWITCH GEAR

MEN'S

ROOM

WOMEN'S

ROOM

FAMILY

VESTIBULE

HAC

DRINK

FOUNTAIN

OFFICE

FOREMAN

SUPERINTENDENT

OFFICE

SECRETARY

RECEPTION

OPERATIONS

CENTER

LOBBY

VESTIBULE

103A

MEN'S

TOILET

HAC

WOMEN'S

LOCKER ROOM &

TOILET

CORRIDOR

WOMEN'S

TOILET

F

K

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T O

N

C E

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PD101

FIRST FLOOR PLUMBING DEMOLITION

PLAN

ADWX 76 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

A. DEMOLITION WORK SHALL BE PERFORMED

SUCH THAT ALL PIPES, HANGERS, SUPPORTS,

AND VALVES IN SCOPE ARE REMOVED

COMPLETELY TO MAINS. REMOVE ALL ITEMS TO

ENSURE NOTHING IS ABANDONED IN PLACE.

B. NO DEAD ENDS SHALL REMAIN. THE MAXIMUM

LENGTH OF DEAD ENDS SHALL BE TWO PIPE

DIAMETERS FROM THE BRANCH, RISER, OR

MAIN.

C. SEAL ABANDONED SANITARY PIPE AT FLOOR.

NORTH

0 4 8 16

1 DEMOLISH EXISTING HOT WATER HEATER AND

ASSOCIATED EXPANSION TANK.

2 DEMOLISH EXISTING STORM WATER LINE AND

ASSOCIATED FOOR DRAINS.

3 DEMOLISH EXISTING PLUMBING FIXTURE AND

ASSOCIATED DCW, DHW, DHWR, DRAIN AND

VENT PIPING.

4 SEAL EXISTING FLOOR DRAIN AT FLOOR.

5 DEMOLISH EXISTING PIPING SHOWN DASHED.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

PLUMBING DEMOLITION PLAN

DocuSign Envelope ID: ACDB8F61-1CC8-4E44-AE6F-5F4406D3A2C5

7/27/2023

HWH-2

CEILING HUNG

2" DCW

3/4" DHW

3/4" DCW

1 1/4" DCW

2" DCW

1 1/4" DHW

1/2" DCW

1/2" DHW

1/2" DCW

1/2" DHW

1/2" DCW

P-401

P-502

P-401 P-103

P-502

P-201

P-107

P-107 P-107

P-420

P-420 P-420

P-420

P-103

INV.=902.77'

SEE CIVIL DRAWING

CI100 FOR

CONTINUATION

ET-2P-528

4 3

HWH-1ET-1

2 1/2" DCW

1 1/4" DCW

3/4" DHW

1" DCW

1" DCW

1/2" DHW

1/2" DCW

1/2" DHW

MECH./ ELEC.

DIRECTOR'S

OFFICE

OFFICE

OFFICE

CORRIDOR

RECEPTION

101A

GRAVE LOCATOR

RM.

LOBBY

TR

CONFERENCE

ROOM

CORRIDOR

WORK STATIONS

STORAGE

RECORDS

STORAGE

OPERATIONS

CORRIDOR 115

CORRIDOR

CORRIDOR

LUNCH ROOM

STAFF TOILET

STAFF TOILET

HAC

MEN'S

WOMEN'S

HAC

2" DCW

2 1/2" DCW

2.5

A0

A.8

C.9

D.5

C

H9

A.1

2.92.72.32.11.1

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP101

ADMINISTRATION BLDG. DOMESTIC

WATER PLAN

JTWX 77 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

NORTH

0 42 8

Scale: 1/4" = 1'-0"

FIRST FLOOR DOMESTIC WATER PLAN - ADMINISTRATION BUILDING

1 2" UNDERGROUND DCW PIPE WITH ELECTRIC

HEAT TRACE, MIN. 12" BELOW THE FINISHED

GRADE.

2 3/4" DCW DOWN TO URINAL.

3 1/2" DCW AND DHW DOWN TO LAVATORY.

4 1" DCW DOWN TO WATER CLOSETS.

5 WATER METER ASSEMBLY, SEE DETAIL# 10 ON

SHEET P-501.

A B D

H3

H4

H5

H6

H.2

1/2" DHW

1" DCW

3" DCW

2 1/2" DCW

3/4" DHW

2 1/2" DCW

MAINTENANCE BAY

MAINT. BAY

SHOP

PARTS /TOOLS

MUD ROOM

ENCLOSED

MAINTENANCE

BAYS

MECHANICAL

ROOM

WOMEN'S LOCKER

ROOM & TOILET

MEN'S LOCKER

ROOM

TOILET/ SHOWER

SWITCH GEAR

LUNCH ROOM

STORAGE SHED

VEST.

STORAGE SHED

FERTILIZER

STORAGE

CORRIDOR

1"

3/4" 1"

1 1/4"

P-201

3/4" 3/4"

3/4" 3/4"

P-701

2 1/2"

3/4"

3/4"

ET-4

HWH-4

P-701 P-413

P-103

1/2" DCW

1/2" DHW

3/4" DCW

P-8012

ET-5

HWH-5 1

1302A

MAINT. SHED

P-528

3/4" DHW

3/4" DCW

H3.1

H

L

K

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP102

EXIST. ADMINISTRATION BLDG.

DOMESTIC WATER PLAN

JTWX 78 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

1 INSTALL NEW HOT WATER HEATER AND

ASSOCIATED EXPANSION TANK. CONNECT THEM

TO EXISTING PLUMBING SYSTEM.

2 PROVIDE NEW PLUMBING FIXTURES AND

CONNECT TO EXISTING PLUMBING SYSTEM.

3 EXISTING TO REMAIN.

Scale: 1/8" = 1'-0"

FIRST FLOOR DOMESTIC WATER PLAN - EXISTING ADMINISTRATION BUILDING

NORTH

0 4 8 16

HWH-3

H1 H2

H3

H4

H5

H6

1/2" DCW

1/2" DHW

1/2" DHW

1/2" DCW

3/4" DHW

1 1/4" DCW

3/4" DHW

1 1/4" DCW

3/4" DHW

2" DCW

1 1/4" DCW

3/4" DHW

1/2" DHW

1/2" DCW

1" DCW

INV.=903.41'

P-103

P-401

P-103

P-401

P-528

ET-3

H01

LOUNGE

H03

VAULT

H02

CORRIDOR

H04

TOILET

H06

LOCKER ROOM

H05

ADA CHANGE

ROOM

H07

MECH / ELEC

H08

HR LINKS

H08A

TELECOM. CLOSET

H10

WORK LEADER'S

OFFICE

H09

CORRIDOR

H11

TOILET

H12

FOREMAN'S OFFICE

H1.1 H1.9

H3.1

H7

H7.9

H8

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP103

HONOR GUARD BLDG DOMESTIC

WATER PLAN

JTWX 79 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

NORTH

0 4 8 16

Scale: 1/4" = 1'-0"

FIRST FLOOR DOMESTIC WATER PLAN - HONOR GUARD BUILDING

1 WATER METER ASSEMBLY, SEE DETAIL# 10 ON

SHEET P-501.

2 SEE CIVIL DRAWING CI100 FOR CONTINUATION.

3 1/2" DCW AND DHW DOWN TO LAVATORY.

4 1" DCW DOWN TO WATER CLOSET.

FD-C

FD-C

FD-C

P-420

P-420

P-401 P-401 P-502

P-502

P-103P-103

P-107

P-107

P-201

2" V2" V

2" V

2" V

3" SAN

4" SAN

4" SAN

4" SAN

2" V

2" V

1 1/2" V

4" SAN

4" SAN

1 1/2" SAN

4" SAN

P-420 2

INV.=903.34'

FINISHED FLOOR ELEVATION: 907.4'

FD-M

CO

INV.=906.4

HWH-3

P-107

HWH-3

P-528

1%

INV.=905.5

CO

4" SAN

MECH./ ELEC.

DIRECTOR'S

OFFICE 104

OFFICE

OFFICE

RECEPTION

RECEPTION

101A

GRAVE LOCATOR

RM.

TR

LOBBY

CONFERENCE

ROOM

CORRIDOR

CORRIDOR

CORRIDOR

WORK STATIONS115

CORRIDOR

CORRIDOR

RECORDS

STORAGE

STORAGE

LUNCH ROOM

STAFF TOILET

HAC

STAFF TOILET

STORAGE

OPERATIONS

MEN'S

WOMEN'S

HAC

2.5

A0

A.8

C.9

D.5

4" SAN

CO

CO

4" SAN

CO

C

H9

A.1

2.92.72.32.11.1

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP104

ADMINISTRATION BLDG SEWER PLAN

JTWX 80 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

1 UNDERGROUND SANITARY PIPE TO SITE. SEE

CIVIL DRAWINGS CI100 FOR CONTINUATION.

2 1 1/2" SANITARY AND VENT TO LAVATORY.

3 4" SANITARY AND 2" VENT TO WATER CLOSET.

4 2" VENT UP, CHANGE SIZE TO 3" BEFORE

PENETRATE THROUGH THE ROOF, END AT

MIN. 6" ABOVE ROOF.

5 PROVIDE AUTO TRAP PRIMER VALVE TO EACH

FLOOR DRAIN.

6 PROVIDE ELECTRIC HEAT TRACE TO

UNDERGROUND SANITARY PIPE BETWEEN

THE TWO BUILDINGS.

NORTH

0 42 8

Scale: 1/4" = 1'-0"

FIRST FLOOR DRAIN, WASTE, AND VENT PLAN - ADMINISTRATION BUILDING

A. MIN. 1% SLOP FOR SANITARY PIPE 4" AND BIGGER;

B. MIN. 2% SLOP FOR SANITARY PIPE LESS THAN 4".

A B D

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

2" V

3" SAN

4" SAN

4" SAN

2" V

FD-D

FD-D

ENCLOSED

MAINTENANCE

BAYS ?

MECHANICAL

ROOM

CORRIDOR

MUD ROOM

PARTS /TOOLS

MAINTENANCE BAY

6" SAN

4" SAN

3" SAN

3" SAN

3" SAN

6" SAN

3" SAN

4" SAN

1 1/2" SAN

2" SAN

P-103P-413

FD-GFD-G

4" SAN

1%CO

4" SAN 4" SAN

P-528

1 1/2" SAN

P-201

2%

2%

2" SAN

P-701

P-701

H

L

K

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP105

EXIST. ADMINISTRATION BLDG SEWER

PLAN

JTWX 81 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

NORTH

0 42 8

Scale: 1/4" = 1'-0"

FIRST FLOOR DRAIN, WASTE, AND VENT PLAN - EXISTING ADMINISTRATION BUILDING

A. SEAL ALL ABANDONED SANITARY AND VENT

OENNINGS.

1 CONNECT NEW PLUMBING FIXTURE'S SANITARY

AND VENT PIPE TO EXISTING BUILDING SANITARY

AND VENT SYSTEM.

2 SEAL EXISTING FLOOR DRAIN AT FLOOR.

FD-C

P-103

P-103

P-401

P-528

P-528

4" SAN

1 1/2" SAN

4" SAN

2 1/2" V

1 1/2" V

2" V

2 1/2" V

2 1/2" V

1 1/2" V

2 1/2" V

1 1/2" V

1 1/2" SAN

4" SAN

4" SAN

H1 H2

H3

H4

H5

H6

FINISHED FLOOR

ELEVATION: 908.4

CO

INV.=907.4

CO 2%

2%

2%

4" SAN

2%

CO

INV.=904.17'

4" SAN

H01

LOUNGE

H03

VAULT

H02

CORRIDOR

H04

TOILET

H05

ADA CHANGE

ROOM

H06

LOCKER ROOM

H07

MECH / ELEC

H08

HR LINKS H08A

TELECOM. CLOSET

H09

CORRIDOR

H10

WORK LEADER'S

OFFICE

H11

TOILET

H12

FOREMAN'S OFFICE

H1.1 H1.9

H3.1

H7

H7.9

H8

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

PP106

HONOR GUARD BLDG SEWER PLAN

JTWX 82 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

NORTH

0 42 8

Scale: 1/4" = 1'-0"

FIRST FLOOR DRAIN, WASTE, AND VENT PLAN - HONOR GUARD BUILDING

1 UNDERGROUND SANITARY PIPE TO SITE.

SEE CIVIL DRAWINGS CI100 FOR

CONTINUATION.

2 1 1/2" SANITARY AND VENT TO LAVATORY.

3 4" SANITARY AND 2" VENT TO WATER

CLOSET.

4 2-1/2" VENT UP, CHANGE SIZE TO 3" BEFORE

PENETRATE THROUGH THE ROOF, END AT

MIN. 6" ABOVE ROOF.

5 PROVIDE AUTO TRAP PRIMER VALVE TO

EACH FLOOR DRAIN.

INSTALL PER PDI STANDARDS AND

MANUFACTURER'S INSTRUCTIONS.

PROVIDE WHA AT ALL QUICK

CLOSING VALVES.

IF BRANCH IS GREATER THAN

20' LONG, PROVIDE ANOTHER

WHA IN MIDDLE, EACH SIZED

FOR HALF THE FIXTURE UNITS

IF HORIZONTAL BRANCH IS LESS

THAN 20' LONG, PROVIDE ONE

WHA AT END OF LINE

HOT OR COLD WATER SUPPLY

WATER HAMMER

ARRESTER (TYP)

WHA-A

WHA-B

WHA-C

WHA-D

WHA-E

WHA-F

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

1-11

12-32

33-60

61-113

114-154

154-330 FIXTURE WITH QUICK

CLOSING VALVE (TYP)

PDI

SIZE

PIPE

SIZE

FIXTURE

UNIT LOAD

ACCESSIBLE

MAINTENANCE

SHUTOFF (TYP)

NOM. SIZE (IN.)

PIPE (FT.)

TUBING (FT.)

5 FT

THRU 3/4

1 1 1/4

1 1/2

HANGER ROD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR

LOW TEMPERATURE

PIPE)

PROVIDE HIGH

COMPRESSIVE

STRENGTH

INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION SHIELD AT

HANGER

WELD

SADDLE

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE

SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE

SPECIFICATIONS

1/2" DIA. HANGER RODS WITH 36"

MAX. SPACING ON EACH CHANNEL

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2" x 2" x 1/4" ANGLE

NOTES:

SEE SPECIFICATIONS FOR

DETAILED HANGER

REQUIREMENTS. SIDE VIEW TRAPEZE HANGER

FOR UP TO 1000 LB. UNIFORM

LOAD

1" MAX.

PROVIDE INSULATION SHIELD &

INSERT FOR ALL PIPING (8" MIN.)

2 2 1/2 3 4 5 6 8 10 12

11 12 14 16 17 19 22 23

9 10 12 13 14 16 - -

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE

MAXIMUM PIPE/TUBING SUPPORT SPACING

FAUCET SEE

SPECIFICATIONS

LAMINAR FLOW

CONTROL DEVICE

TRAP PARALLEL TO WALL

FINISHED

FLOOR

ESCUTCHEON

LOOSE

KEY STOP

F O

R F

IX

T

U R

E H

E

IG

H T

S S

A

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S 1

/4

8"

WALL MOUNTED

THERMOSTATIC

MIXING VALVE

3/8" FLEX TO FAUCET

OFFSET WASTE

J-BOX WITH TRANSFORMER OR

PLUG-IN ON DUPLEX RECEPTACLE

FAUCET SEE

SPECIFICATIONS

LAMINAR FLOW

CONTROL DEVICE

FINISHED

FLOOR

ESCUTCHEON

LOOSE

KEY STOP

F O

R F

IX

T

U R

E H

E

IG

H T

S S

A

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S 1

/4

TRAP PARALLEL

TO WALL

WALL MOUNTED

THERMOSTATIC

MIXING VALVE

3/8" FLEX TO HW

ON FAUCET

OFFSET WASTE

8"

FINISHED FLOOR

FINISHED WALL

SOLENOID OPERATED

FLUSH VALVE

BACK CHECK

ANGLE STOP

SEE INTERIOR

ELEVATIONS FOR

GRAB BARS IF

APPLICABLE

TRANSFORMER IN

JUNCTION BOX

MOUNT ELECTRONIC

SENSOR IN 12"x16"

PANEL

12"x16" STAINLESS STEEL

ACCESS DOOR WITH

OPERATED CYLINDER

LOCK

FOR FIXTURE

HEIGHTS SEE

PLUMBING

SPECIFICATIONS

BOTTLE FILLER

LOW DRINKING

FOUNTAIN

HIGH DRINKING

FOUNTAIN

H

IG

H S

P O

U T

O U

T L

E T

A

F F

L O

W S

P O

U T

A F

F

FINISHED FLOOR

FINISHED WALL

MANUALLY

OPERATED

FLUSH VALVE

BACK CHECK

ANGLE STOP

FOR FIXTURE

HEIGHTS SEE

PLUMBING

SPECIFICATIONS

SEE INTERIOR

ELEVATIONS FOR

GRAB BARS IF

APPLICABLE

DCW SUPPLY

WALL

VENT PIPING

LOCATED IN WALL

FINISHED FLOOR

COPPER PIPING PASSING THRU

CONCRETE SLAB SHALL BE PROTECTED

BY A PROTECTIVE SHEATING OR

WRAPPING TO PERVENT CORROSION

TO THE COPPER

PROVIDE TRAP PRIMER

CONNECTION ADAPTER SO

THAT TRAP PRIMER LINES

CAN BE ROUTED BELOW

SLAB OR IN FLOOR BELOW

CEILING SPACE FROM

VALVE TO DRAIN

FLOOR DRAIN OR FLOOR SINK

SEE FLOOR PLANS FOR

DRAIN LOCATIONS

WASTE PIPE

TO MAIN

CODE ALLOWED DISTANCE

NO MORE THAN

AUTO TRAP

PRIMER VALVE

4" CONCRETE

HOUSEKEEPING PAD

WATER HEATER DRAIN

VALVE

ASME RATED TEMPERATURE

AND PRESSURE RELIEF

VALVE. PIPE FULL SIZE TO

NEAREST FLOOR DRAIN

TO ELECTRICAL POWER

SOURCE (SEE E-SERIES

DRAWINGS)

TYPICAL THERMOMETER

HOT WATER SUPPLY

TO SYSTEM

FLOOR

FLEXIBLE STAINLESS

STEEL WATER HEATER

CONNECTOR

TYPICAL BALL VALVE

CHECK VALVE

COLD WATER SUPPLY

TO WATER HEATER

HOT WATER

EXPANSION TANK

ELECTRIC

WATER

HEATER

DCW

HWR

DHW

DOMESTIC COLD

WATER MAIN

ISOLATION BALL

VALVE (TYP.)

ELECTRICAL

DISCONNECT

THERMAL EXPANSION TANK

CHECK VALVE

ELECTRIC WATER

HEATER

ALTERNATE SUPPORT SYSTEM,

HUBBARD ENTERPRISES

HOLBRITE MODEL 50-SWHP,

SUSPENDED WATER HEATER

PLATEFOR/DRAIN PAN

ELECTRICAL

ACCESS COVER

COMBINE P/T RELIEF WITH

DRAIN PAN OUTLET AND

TERMINATE

UNI-STRUT SUPPORT

CHANNEL WITH FLAT

WASHER AND DOUBLE

NUTS

ASME APPROVED TEMP. &

PRESSURE RELIEF VALVE

TWO (2) LAYERS OF 3/4"

TREATED PLYWOOD

ALL-THREAD SUPPORT ROD

UNION (TYP.)

TO PLUMBING FIXTURES

SUPPORT FROM TOP OF

STEEL BEAM

PLASTIC DRAIN PAN

BENEATH HEATER

DOUBLE CHECK

VALVE

BUILDING SERVICE (REFERENCE

FLOOR PLANS FOR SIZE)

GATE VALVE

REDUCER

METER

FLANGE

FLOOR

RODS, CLAMPS, BOLTS, WASHERS

SHALL BE MADE OF STEEL

ROD

INCOMING WATER SERVICE

(REFERENCE CIVIL UTILITY

PLAN FOR SIZE)

24"

WATER STOP AND

ANCHOR COLLAR

EXTERIOR WALL

GROUT

WALL SLEEVE

STAINLESS STEEL

NUT AND BOLT

CARRIER PIPE

PRESSURE PLATE

CLOSURE

RUBBER LINK

SECTION

GROUT

Dwg of

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

P-501

PLUMBING DETAILS AND SCHEDULES

ADWX 83 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

Scale: No Scale

WATER HAMMER ARRESTOR DETAIL

Scale: No Scale

PIPE HANGER DETAIL

Scale: No Scale

LAVATORY WALL HUNG - SENSOR OPERATED FAUCET DETAIL

Scale: No Scale

LAVATORY WALL HUNG - WRIST FAUCET DETAIL

Scale: No Scale

WATER CLOSET WALL HUNG - SENSOR OPERATED DETAIL

Scale: No Scale

HIGH LOW DRINKING FOUNTAIN WITH BOTTLE FILLER DETAIL

Scale: No Scale

WATER CLOSET WALL HUNG - MANUAL DETAIL

Scale: No Scale

FLOOR DRAIN & TRAP PRIMER DETAIL

Scale: No Scale

ELECTRIC WATER HEATER DETAIL W/ EXPANSION TANK

Scale: No Scale

WATER HEATER PIPING DETAIL - CEILING HUNG

Scale: No Scale

INCOMING DOMESTIC WATER SERVICE DIAGRAM

Scale: N.T.S.

PIPE SLEEVE THRU EXTERIOR WALL OR FOUNDATION

WALL (BELOW GRADE) DETAIL

Dwg of

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

P-601

PLUMBING SCHEDULES

JTWX 84 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

HWH-5 MECH. SHED 1302A

EXISTING BUILDING

DOMESTIC HOT

WATER

LARGE VOLUME

ELECTRIC

50 [ 190 ] 176 [ 670 ] 100 [ 690 ] 6 30 5 3 208

DESIGN BASIS: AO SMITH MODEL

DEV-52-30

HWH-4 MECH. ROOM 115

EXISTING ADMIN.

BUILDING

DOMESTIC HOT

WATER

LARGE VOLUME

ELECTRIC

80 [ 300 ] 176 [ 670 ] 100 [ 690 ] 6 30 5 3 208

DESIGN BASIS: AO SMITH MODEL

DEV-80-30

HWH-3 MECH. ROOM H07

HONOR GUARD

BUILDING

DOMESTIC HOT

WATER

SMALL VOLUME

ELECTRIC

20 [ 76 ] 11.6 [ 44 ] 100 [ 690 ] 1 2 2 1 120

DESIGN BASIS: RHEEM MODEL

XE20P06PU20U0

HWH-2 HAC ROOM 121

NEW PUBLIC

RESTROOM

BUILDING

DOMESTIC HOT

WATER

SMALL VOLUME

ELECTRIC

20 [ 76 ] 11.6 [ 44 ] 100 [ 690 ] 1 2 2 1 120

CEILING HUNG;

DESIGN BASIS: RHEEM MODEL

XE20P06PU20U0

HWH-1 MECH. ROOM 107

NEW ADMIN.

BUILDING

DOMESTIC HOT

WATER

SMALL VOLUME

ELECTRIC

20 [ 76 ] 11.6 [ 44 ] 100 [ 690 ] 1 2 2 1 120

DESIGN BASIS: RHEEM MODEL

XE20P06PU20U0

GAL [L] GAL/HR [L/HR] PSIG [kPa] TOTAL kW kW PER

ELEMENT

PHASE VOLT

MARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM AND/OR

SERVICE

TYPE

STORAGE CAPACITY

RECOVERY @ 70 °F [21°C]

RISE

RELIEF VALVE SETTING

NO OF

ELEMENTS

ELECTIRCAL INPUT

REMARKS

ELECTRIC WATER HEATER SCHEDULE

ET-5

MECH. SHED

1302A

POTABLE THERMAL

EXPANSION TANK

40 [ 4 ] 140 [ 60 ] 40 [ 280 ] 80 [ 550 ] 100 [ 690 ] 8.5 [ 32 ] 5.9 [ 22 ] .75 [ 19 ] DESIGN BASIS: WATTS MODEL PLT-20

ET-4 MECH. ROOM 115

POTABLE THERMAL

EXPANSION TANK

40 [ 4 ] 140 [ 60 ] 40 [ 280 ] 80 [ 550 ] 100 [ 690 ] 8.5 [ 32 ] 5.9 [ 22 ] .75 [ 19 ] DESIGN BASIS: WATTS MODEL PLT-20

ET-3 MECH. ROOM H07

POTABLE THERMAL

EXPANSION TANK

40 [ 4 ] 140 [ 60 ] 40 [ 280 ] 80 [ 550 ] 100 [ 690 ] 2.1 [ 8 ] 1.3 [ 5 ] .75 [ 19 ] DESIGN BASIS: WATTS MODEL PLT-5

ET-2 HAC ROOM 121

POTABLE THERMAL

EXPANSION TANK

40 [ 4 ] 140 [ 60 ] 40 [ 280 ] 80 [ 550 ] 100 [ 690 ] 2.1 [ 8 ] 1.3 [ 5 ] .75 [ 19 ] DESIGN BASIS: WATTS MODEL PLT-5

ET-1 MECH. ROOM 107

POTABLE THERMAL

EXPANSION TANK

40 [ 4 ] 140 [ 60 ] 40 [ 280 ] 80 [ 550 ] 100 [ 690 ] 2.1 [ 8 ] 1.3 [ 5 ] .75 [ 19 ] DESIGN BASIS: WATTS MODEL PLT-5

°F [°C] °F [°C] PSIG [kPa] PSIG [kPa] PSIG [kPa] GAL [L] GAL [L] IN [mm]

MIN MAXMARK LOCATION TYPE

SYSTEM TEMPERATURE RANGE

INITIAL PRESSURE IN TANK

MAX OPERATING

PRESSURE

RELIEF VALVE PSIG [kPA] MIN TANK VOLUME MIN ACCEPT VOLUME PIPE SIZE TO TANK

REMARKS

DOMESTIC WATER THERMAL EXPANSION TANK SCHEDULE

P-801 WALL HYDRANT NA #VALUE! NA #VALUE! .75 [ 19 ] NA #VALUE! NA 5 YES NO

P-701 SHOWER 2 [ 50 ] 2 [ 50 ] .5 [ 13 ] .5 [ 13 ] 2 2 YES NO

P-528 SINK SERVICE LUNCHROOM 2 [ 50 ] 2 [ 50 ] 0.5 [ 13 ] 0.5 [ 13 ] 3 2 YES NO

P-502 MOP SINK, FLOOR MOUNTED 3 [ 75 ] 2 [ 50 ] .75 [ 19 ] .75 [ 19 ] 2 3 YES NO

P-420 LAVATORY, COUNTER TOP 1.5 [ 38 ] 1.5 [ 38 ] .5 [ 13 ] .5 [ 13 ] 1 2 NO NO

P-413 LAVATORY, COUNTER TOP 1.5 [ 38 ] 1.5 [ 38 ] .5 [ 13 ] .5 [ 13 ] 1 2 YES NO

P-401 LAVATORY, WALL HUNG 1.5 [ 38 ] 1.5 [ 38 ] 0.5 [ 13 ] 0.5 [ 13 ] 1 2 YES NO

P-201 URINAL WALL HUNG 2 [ 50 ] 1.5 [ 38 ] .75 [ 19 ] NA #VALUE! 2 5 N/A NO

P-107 WATER CLOSET, WALL HUNG, 4 [ 100 ] 2 [ 50 ] 1 [ 25 ] NA #VALUE! 4 10 N/A NO

P-103 WATER CLOSET, WALL HUNG, 4 [ 100 ] 2 [ 50 ] 1 [ 25 ] NA #VALUE! 4 10 N/A NO

IN [mm] IN [mm] IN [mm] IN [mm]

MARK DESCRIPTION

WASTE PIPE VENT PIPE COLD WATER HOT WATER WASTE

FIXTURE

UNITS

WATER

FIXTURE

UNITS

HANDLES

ELECTRIC

SENSOR

REMARKS

PLUMBING FIXTURE SCHEDULE

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR-COOLED CONDENSER

ACCH AIR-COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACU AIR CONDITIONING UNIT

ACD AUTOMATIC CONTROL DAMPER,

MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER,TWO

POSITION

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND

REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT

EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BUFFER TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHWP CHILLED WATER PUMP

CHW CHILLER WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CLEAN OUT

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CHWCC CHILLED WATER COOLING COIL

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

D-4 ECONOMIZER OUTDOOR AIR

DAMPER

dB DECIBELS Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE

ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

ECC ENGINEERING CONTROL CENTER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE

EX EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

FF FINAL FILTER

FM FLOW METER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HHW HEATING HOT WATER

HHWC HEATING HOT WATER COIL

HHWP HEATING HOT WATER PUMP

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM

CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

Hz HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IV INLET VANES

kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

L LITER

L/s LITERS PER SECOND

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LH LATENT HEAT

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPS LOW PRESSURE SUPPLY (STEAM)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL

PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER, SI UNIT

M/s METERS PER SECOND (OR

METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING

VALUE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM

CONDENSATE)

MPS MEDIUM PRESSURE SUPPLY (STEAM)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OR OPERATING ROOM

OSA OUTSIDE SUPPLY AIR

(CONDITIONED)

P PUMP

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PHC PREHEAT COIL

PHCP PREHEAT COIL PUMP

PPM PARTS PER MILLION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH –

ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

R/E RETURN OR EXHAUST

RA RETURN AIR

RAT RETURN AIR TEMPERATURE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND

DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSR SOLID SEPARATOR

ST STEAM TRAP

SV STEAM SAFETY VALVE

SVS STEAM VENT SILENCER

T & PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL

OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE)

RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WATTS

Wb WET-BULB (TEMPERATURE)

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

XT EXPANSION TANK

YR YEAR

MECHANICAL ABBREVIATIONS

CO2 CARBON DIOXIDE SENSOR

HUMIDISTAT OR HUMIDITY SENSOR

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

ROUND FLEX DUCT

LINEAR SLOT DIFFUSER

BALANCING DAMPER

FIRE DAMPER

SMOKE DAMPER

D

R INCLINED RISE, IN

DIRECTION OF AIRFLOW

INCLINED DROP, IN DIRECTION

OF AIRFLOW

CONNECT NEW DUCT

TO EXISTING

LIMIT OF DEMOLITION

VANED ELBOW (PROVIDE ALL

SQUARE OR RECTANGULAR

ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

STANDARD RADIUS ELBOW

(LONG RADIUS)

10x8 NEW DUCT (INSIDE

DIMENSIONS: WIDTH X DEPTH)

EXISTING DUCT TO REMAIN

EXISTING DUCT TO BE

DEMOLISHED

DUCT TRANSITION

END MOUNTED OR SIDEWALL GRILLE

SUPPLY

RETURN45°

45°

DN

DN

UP

UP

DNUP

STANDARD BRANCH SUPPLY OR

RETURN, NO SPLITTER (45° TAP)

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

S-60

S-15

CR-15

CHWS

CHWR

HIGH PRESSURE STEAM

PIPING (60 PSI)

LOW PRESSURE STEAM PIPING

(15 PSI AND BELOW)

LOW PRESSURE STEAM

CONDENSATE RETURN

CHILLED WATER SUPPLY PIPING

CHILLED WATER RETURN PIPING

PIPE UP

PIPE DOWN

BOTTOM CONNECTION

TOP CONNECTION

CAPPED OR PLUGGED PIPE

GLOBE VALVE

GATE VALVE

BALL VALVE

STEAM SAFETY VALVE

PRESSURE REGULATING VALVE

WYE STRAINER VALVE

BALANCING VALVE

MODULATING TWO-WAY CONTROL

VALVE

STEAM TRAP

D CONDENSATE DRAIN LINE

CR-60 HIGH PRESSURE STEAM

CONDENSATE RETURN

HWS

HWR

HEATING HOT WATER SUPPLY

PIPING

HEATING HOT WATER RETURN PIPING

RLS REFRIGERANT LINE SET (LIQUID

AND SUCTION)

CONNECT TO EXISTING PIPE

LIMIT OF DEMOLITION

INLINE CENTRIFUGAL PUMP

STEAM PRESSURE REDUCING

VALVE

DRAIN VALVE

TEST PLUG

SUPPLY

TERMINAL UNIT SUPPLY

DUCT BRANCH (CONICAL

TAP)

CHECK VALVE

FIRE / SMOKE DAMPER

VANED ELBOW (SHORT RADIUS) S-30

CR-30

MEDIUM PRESSURE STEAM

PIPING (16 PSI AND 59 PSI)

MEDIUM PRESSURE STEAM

CONDENSATE RETURN

THERMOSTAT OR TEMPERATURE SENSOR

TWO POSITION CONTROL VALVE

MODULATING THREE-WAY

CONTROL VALVE

T

H

F

SD

FS

MECHANICAL LEGEND

MOTORIZED DAMPER

1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.

2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.

3. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.

4. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE REQUIRED.

5. EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.

6. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).

7. INSTALL EQUIPMENT AS INDICATED, ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS, AND REPLACEMENT.

8. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.

9. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF ALL OTHER TRADES.

10. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH ALL CONTRACTORS PRIOR TO INSTALLATION.

11. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.

12. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.

13. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND

PIPING IN THE FIELD.

14. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.

15. NOTIFY COR REGARDING DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS OR DIMENSIONS BEFORE PERFORMING WORK. FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE CONTRACTOR'S ACCEPTANCE OF EXISTING CONDITIONS AS FIT FOR THE PROPER EXECUTION OF THE WORK.

16. SEE ARCHITECTURAL DRAWINGS FOR FINAL LOCATION OF CEILING INSTALLED EQUIPMENT.

17. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE AND AS CLOSE AS POSSIBLE TO BUILDING WALLS, CEILING AND FLOOR AND ROOF STRUCTURE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.

18. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.

19. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.

20. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.

21. MAKE A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH COR.

22. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS.

23. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE

NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.

24. INSTALL PIPING FREE OF SAGS AND BENDS.

25. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.

26. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL CLOSETS/ROOMS.

27. PREPARE DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY THE GOVERNMENT.

A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.

B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, ALL DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, CEILING GRID AND HEIGHT, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER AND OTHER CEILING MOUNT DEVICES OR EQUIPMENT THAT PROTRUDE INTO THE CEILING CAVITY.

C. IF THERE ARE OUTSTANDING ISSUES THAT CANNOT BE RESOLVED, CONSULT WITH COR FOR GUIDANCE AND MAKE CORRECTIONS IN ACCORDANCE WITH DIRECTIONS GIVEN.

D. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.

28. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK LACKING

COORDINATION AT NO ADDITIONAL COST

MECHANICAL GENERAL NOTES

1. VERIFY EXISTING CONDITIONS PRIOR TO BEGINNING WORK. NOTIFY COR REGARDING CONFLICTS BEFORE PROCEEDING WITH WORK.

2. REMOVED ITEMS REMAIN PROPERTY OF GOVERNMENT UNTIL COR DETERMINES THAT THEY ARE NOT REQUIRED. REMOVE FROM SITE ITEMS NOT BEING RETAINED BY

GOVERNMENT OR REINSTALLED AS PART OF THIS WORK.

3. DO NOT DISTURB ITEMS NOT INDICATED FOR DEMOLITION.

4. VERIFY SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION. RELOCATE, REMOVE AND ADJUST MECHANICAL AND ELECTRICAL ITEMS AS NECESSARY TO

COORDINATE WITH NEW WORK.

5. AFTER DEMOLITION IS COMPLETE, PATCH AND REPAIR FINISHES TO MATCH EXISTING ADJACENT CONDITIONS.

6. COORDINATE DEMOLITION WITH COR. SUBMIT SHUTDOWN PLAN AND SCHEDULE TO COR FOR REVIEW AND APPROVAL.

7. PROTECT EXISTING UTILITIES TO REMAIN FROM DAMAGE DURING DEMOLITION. REPAIR UTILITIES AND SERVICES DAMAGED AT NO ADDITIONAL COST.

8. TEMPORARILY MOVE OR TAKE EQUIPMENT OUT OF SERVICE AS NECESSARY TO COMPLETE WORK.

9. SAWCUT OR CORE DRILL CONCRETE FLOOR AS REQUIRED FOR DEMOLITION WORK INDICATED. COORDINATE WITH NEW MECHANICAL WORK AND WORK OF OTHER TRADES.

MECHANICAL DEMOLITION GENERAL NOTES

EXISTING

NEW WORK KEYNOTE

DEMOLITION KEYNOTE

NEW BOLD TEXT INDICATES NEW ITEM

ITALICIZED TEXT INDICATES EXISTING ITEM

DIFFUSER TAG

DETAIL OR SECTION MARK

SHOWN ON DRAWING

DETAIL MODULE NUMBER

CONNECT TO EXISTING

LIMIT OF DEMOLITION

EQUIPMENT TAG

ANNOTATION SYMBOLS

##-VAV-#

SD-## ###

Dwg of

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

M-001

MECHANICAL GENERAL INFORMATION

ADWX 85 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

14x610x6 x

17x8 20x9 x x

26x7

18x18 x x9 x9 x6 x4 x412 x6 x4 x6

A B D

E

G

F1

LUNCH ROOM112

PARTS /TOOLS

MECHANICAL

ROOM

ENCLOSED

MAINTENANCE

BAYS

MAINT. BAY

8x5

8x814ø

8x8

8x8

8x5

6x6

28x12

20x14

H

L

MEN'S

ROOM

WOMEN'S

ROOM

FAMILY

VESTIBULE

HAC

OFFICE

FOREMAN

SUPERINTENDENT

OFFICE

SECRETARY

RECEPTION

OPERATIONS

CENTER

LOBBY

VESTIBULE

103A

MEN'S

TOILET

HAC

CORRIDOR

WOMEN'S

TOILET

WOMEN'S

LOCKER ROOM &

TOILET

F

K

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

MD101

FIRST FLOOR MECHANICAL

DEMOLITION PLAN

ADWX 86 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

Scale: 1/8" = 1'-0"

FIRST FLOOR MECHANICAL DEMOLITION PLAN

NORTH

0 4 8 16

1 EXISTING TO REMAIN.

2 DEMOLISH EXISTING GRILLES AND ASSOCIATED

DUCTWORK .

3 DEMOLISH EXISTING EXHAUST GRILLES AND

ASSOCIATED DUCTWORK.

4 DEMOLISH EXISTING ERV UNIT AND

ASSOCIATED DUCTWORK AND GRILLES.

5 DEMOLISH EXISTING BLOWER COIL UNIT AND

ASSOCIATED REFRIGERANT PIPING,

DUCTWORK AND GRILLES.

6 DEMOLISH EXISTING LOUVER. REPAIR THE

WALL OPENING PER ARCHITECTURAL SPEC.

7 EXISTING LOUVER TO REMAIN.

8 DEMOLISH EXISTING AHU.

9 DEMOLISH EXISTING BOILER AND ASSOCIATED

PUMP AND PIPING.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

A B D

EXT CONDENSING UNIT

EXT EXHAUST FAN

H

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

MD102

ROOF MECHANICAL DEMOLITION

PLAN

ADWX 87 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

NORTH

0 4 8 16

1 EXISTING CONDENSING UNIT TO REMAIN.

2 DEMOLISH EXISTING CONDENSING UNIT AND

ASSOCIATED REFRIGERANT PIPING.

3 DEMOLISH EXISTING EXHAUST FAN AND

ASSOCIATED DUCTWORK.

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

Scale: 1/8" = 1'-0"

ROOF MECHANICAL DEMOLITION PLAN

AHU-1

1 1/4" RS

1/2" RL

1 1/4" RS

1/2" RL

1" D

EF-2

EF-1

EF-3

200SD-1

200RG-1

200SD-1

200RG-1

260SD-1

140SD-1

-RG-1

90RG-1

260SD-1

140SD-1

140SD-1

420RG-1

140RG-1

260SD-1

120SD-1

100RG-2

-RG-1

140SD-1

200SD-1

200RG-1

85SD-1

60SD-1

50RG-2

100RG-2

260SD-1

140SD-1

660RG-1

140SD-1

100SD-1

520RG-1

260SD-1

14x4314x43 30x16 x

28x14 ø

6ø x

12x1016x14

10x8 ø

8ø ø

6ø ø

6ø

16x10 14x8

28x16 x x

14x8 x ø

8ø

8ø

12x8 ø

8ø ø ø

20x12

6ø x

12x10

8ø ø

12x10

8ø ø ø ø

140RG-1

ACCU-1

EH-2

EH-2

EH-1

EH-1

EH-2

ø

T

50RG-2

ø

140SD-1

100SD-1

100RG-1

-RG-2

-RG-2

-RG-2

ERV-1

EH-2

6ø x

8ø ø ø ø

10x8

NORMALLY CLOSED

MOTORIZED DAMPER

NORMALLY CLOSED

MOTORIZED DAMPER

SF-1

CC-1

HC-1

AF-1

14x10 ø ø ø

TR-CU-01

TR-AC-01

3/4" RS

1/2" RL

T

3/4" RS

1/2" RL

x

14x8

14x8

14x10 x

6ø

8ø

8ø

8ø

8ø

6ø

14x8

MEN'S

WOMEN'S

HAC

CORRIDOR

MECH./ ELEC.

STAFF TOILET

HAC

STAFF TOILET

LUNCH ROOM

STORAGE

CONFERENCE

ROOM

TR

RECORDS

STORAGE

LOBBY

OFFICE

DIRECTOR'S

OFFICE

WORK STATIONS

OPERATIONS

CORRIDOR

CORRIDOR

RECEPTION

STORAGE

CORRIDOR

101A

GRAVE LOCATOR

RM.

OFFICE

2.5

A0

A.8

C.9

D.5

C

H9

A.1

2.92.72.32.11.1

MOUNT UNIT A

MINIMUM OF 8'

ABOVE FINISHED

GROUND

BOLT UNIT TO FRAME (TYP.)

UNISTRUT FRAME

REFRIGERANT

LIQUID AND SUCTION

LINES TO BUILDING

EXTERIOR W

ALL

NOTES:

1. COORDINATE ON SITE TO PROVIDE REQUIRED

CLEARANCES PER EQUIPMENT

MANUFACTURER'S INSTALLATION

INSTRUCTIONS.

2. COVER ALL EXPOSED COILS WITH WIRE

SCREEN GUARD.

CONDENSING UNIT

WATER STOP AND

ANCHOR COLLAR

EXTERIOR WALL

GROUT

WALL SLEEVE

STAINLESS STEEL

NUT AND BOLT

CARRIER PIPE

PRESSURE PLATE

CLOSURE

RUBBER LINK

SECTION

GROUT

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

MH101

ADMINISTRATION BLDG HVAC PLAN

JTWX 88 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

N O

R T

H0 4 8 16

Scale: 1/4" = 1'-0"

FIRST FLOOR HVAC PLAN - ADMINISTRATION BUILDING

1 1" DOOR UNDERCUT.

2 EXHAUST WEATHER HOOD WITH BIRD SCREEN

AND BACKDRAFT DAMPER.

3 INTERLOCK EXHAUST FAN WITH ROOM

LIGHTING

4 6"X6" TRANSFER ELBOW WITH ACOUSTIC

INSULATION.

5 48"X42" INTAKE LOUVER.

6 48"X42" EXHAUST LOUVER.

7 PROVIDE NEW AIR HANDLING UNIT IN

MECHANICAL ROOM AND OUTDOOR ACCU ON 6"

THICK CONCRETE HOUSEKEEPING PAD.

8 PROVIDE NEW THERMOSTAT AND CONNECT TO

AHU-1.

9 20"X18" INTAKE LOUVER.

10 20"X18" EXHAUST LOUVER.

Scale: N.T.S.

CONDENSING UNIT INSTALLATION DETAIL

Scale: N.T.S.

PIPE SLEEVE THRU EXTERIOR WALL DETAIL

F S

NOT PART OF SCOPE

NOT PART OF SCOPE

NOT PART OF SCOPE

TOILET/ SHOWER

TOILET/ SHOWER

ENCLOSED

MAINTENANCE

BAYS

MECHANICAL

ROOM

WOMEN'S LOCKER

ROOM & TOILET

LUNCH ROOM

PARTS /TOOLS

MAINTENANCE BAY 114

MAINT. BAY

SHOP

VEST.

CORRIDOR

EF-7

A B D

EH-4

EH-5

MEN'S LOCKER

ROOM

EH-3

AHU-3

-RG-2

-RG-2

-RG-2

-RG-2

-RG-1

-RG-1

100RG-2

100RG-2

T

T

T

14x8 x x x

8ø

8ø ø

150SD-1

150SD-1

130SD-1

BALANCE

TO 450 CFM

BALANCE

TO 150 CFM

BALANCE

TO 310 CFM

BALANCE

TO 495 CFM

8ø

180SD-1

EF-8

x

20x14

28x12

20x14

20x14

RL

RS

H

L

K

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans Affairs

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Drawing Title

Approved: Project Director

Phase

Building Number Integrity Federal Services

(304) 725-8456

F ile

P at h:

L

P

R O

JE

C

T S

E

N G

\2

P

R O

JE

C

T S

\2 2-

3-

IF

S

-N C

A -D

A Y

T

M E

T E

R Y

R E

N O

V -O

H \R

V T

\C O

N T

E N

T \T

IT

LE

B

LO

C K

S \8

C

M

_G

-T T

LB

E

M P

T Y

.D W

G

Apogee Consulting Group

(919) 858-7420

Foresite Group

(770) 368-1399

The LA Group

(518) 587-8100

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9

VA FORM 08 - 6231

321 4 5 6 7 8 9 10

CLIN 001

MH102

EXIST. ADMINISTRATION BLDG. HVAC

PLAN

JTWX 89 186JULY 28, 2023

BID DOCUMENTS

22-023

BID DOCUMENTS

DAYTON NATIONAL CEMETERY

PIC/ADMIN BLDG, REPLACE COMMITTAL

SHELTER B, AND ROAD REPAIRS

N

AREA OF WORK

SCOPE OUTLINE

KEY PLAN

SCALE: NO SCALE

1 12"X8" TRANSFER ELBOW.

2 6"X6" TRANSFER ELBOW.

3 14"X8" TRANSFER ELBOW.

4 EXHAUST WEATHER HOOD WITH BIRD SCREEN

AND BACKDRAFT DAMPER.

5 INTERLOCK WITH WITH AHU-3.

6 1" DOOR UNDERCUT.

7 30"X40" EXHAUST LOUVER.

8 30"X40" INTAKE LOUVER.

9 AHU-3 TO EXISTING CONDENSING UNIT ON

ROOF.

NORTH

0 4 8 16

Scale: 1/4" = 1'-0"

FIRST FLOOR HVAC PLAN - EXISTING ADMIN

F

EA

H1 H2

H3

H4

H5

H6

ACCU-2

EF-5

EF-6

EF-4

245SD-1

245SD-1

230SD-1

130SD-1

110SD-1

130RG-1

655RG-1

60RG-2

210SD-1

210RG-1

195RG-1 110RG-1

245SD-1

x

20x8 x x x ø

10ø

8ø1 x

8ø x

8ø x x x

1 1/4" RS

1/2" RL

6x6

12ø

EH-2

80RG-2

-RG-2

-RG-2

x

6x6 x

140RG-2

180SD-1

EH-2

EH-2

EH-2

-RG-2

-RG-2

18x14

MH103

x8

NORMALLY CLOSED

MOTORIZED DAMPER

H1.1 H1.9

H3.1

H7

H7.9

H8

EA

OA16x16

16x16 x

18x14

AHU-2

SF-2

CC-2

HC-2

AF-2

14x18

MIXING BOX

NORMALLY

CLOSED

MOTORIZED

DAMPER

FIRST FLOOR

0"

ROOF LEVEL

12' - 0"

TRUSS BEARING HT

10' - 8"

H2

FIRST FLOOR

0"

ROOF LEVEL

12' - 0"

TRUSS BEARING HT

10' - 8"

H2 H1.9

# KEY NOTES:

Dwg of

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREAS S S S

ACG Project Number

GORDON - The LA Group Joint Venture, LLC

The LA Group 40 Long Alley Saratoga Springs, NY 12866

(518) 587-8100

INTEGRITY FEDERAL SERVICES

148 S. Queen Street, Suite 201 Martinsburg, WV 25401

(304) 725-8456

Location

Issue Date

Project Number

Drawing Number

Project Title

Checked Drawn

MONTGOMERY COUNTY, OHIO

810CM3030Office of Design and Construction

Service

U.S. Department of Veterans…