Text version
List of Work Orders
| Work Order | Description | Work Type | Work Sub-Type | Status | Location Description | Asset | Asset Tag | Equipment ID | Target Start | Is dynamic | Dynamic Job Plan applied | Site | Location | ||||||||||||||||
| 18-33194759 | QA The touch screen on Chiller #2 is not working. | WR | QACALL | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 8/29/18 3:43 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 18-33194947 | QA The touch screen on Chiller #1 is not working. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 8/29/18 3:45 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-40417921 | Chillers still not working right they keep turning off on no condenser water flow pumps not ramping up have to run in hand please report | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 2/19/19 3:19 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-40417930 | BOILER # 2 NOT TAKING B A S COMMAND AS PER SCHNIDER TECH CONTRACTOR IT'S AN ENTERNAL PROBLEM DOES SEND COMMAND BUT STAYS IN STANDBY | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 2/15/19 9:15 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-40417951 | 24 HOUR CONVENT BUBBLE ROOM TO HOT 1ST FLOOR | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 2/15/19 9:10 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-40758848 | QA GSA ADRIAN MINJAREZ CONVENT started sweeped leaves clean over flow for generator pan | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 3/5/19 3:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-40758860 | QA GSA ADRIAN MINJAREZ QA cooling tower maint looking for nearest water hose connection | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 3/5/19 3:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-40902870 | C-2 Visit visit scheduled for tomorrow at 2P, C-2 will be visiting the Laredo Port of Entry. Request to clean outside area Convent there are some beer cans and some trash at Gateway to the Americas Bridge between the fence and the GOV parking by the flag poles. | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 3/12/19 3:47 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-40902999 | REQUEST TO CHECK DOOR AT CONVENT INTAKE PROCESSING ROOM BASEMENT | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 3/12/19 4:53 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-41862132 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/15/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-41877816 | REQUEST TO CHECK FOR RATS IN CONVENT AGRICULTURE BRIDGE 1 1ST FLOOR | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 3/20/19 3:27 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-41878102 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 3/18/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-41878131 | FOLLOW UP ON TX0116CV CONVENT COOLING TOWER / NOISY BEARINGS (NON-WARRANTED PARTS OF COOLING TOWER) | WR | SERVCALL | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 3/20/19 5:24 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-41905477 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/20/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-41959370 | tour and chemical check went to pick up truck for tour BPHQ was told ociel going after talking to mr roasales | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 3/21/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-41990768 | TX0116CV. Check holding cells negative pressure. | WR | QACALL | CLOSE | TX0116CV-USBS CONVENT | 3/22/19 3:36 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-41992594 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/22/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42023378 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/22/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42030380 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/25/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42048686 | Central Office Master Fire Alarm Panel Data Request: Follow the two tasks in the Planning Tab. | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/1/19 8:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42055164 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/26/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42095088 | CONVENT COOLING TOWER / NOISY BEARINGS /the cooling tower motor shaft bearings are making much more noise that before. | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 971345 | TX0116C09B001 | TX0116CV-CTR-C09B-1 | 3/29/19 3:55 PM | NO | 07 | 89357 | |||||||||||||||||
| 19-42190175 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 3/28/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42240855 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/3/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42240871 | wait for gateway glass and escort him to 2nd floor exit glass door came to repair checked it but well need more repair then they were told by construction | CM | CORRECT | CLOSE | TX0116CV-Floor 02 | 4/3/19 11:30 AM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-42241836 | Water faucet Convent the ladies room upstairs at Gateway to the Americas Bridge. it needs another battery because it is not turning on. | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/4/19 5:48 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42280595 | REQUEST TO CHECK WATER FOUNTAINS AT BRIDGE 1 CONVENT FOR REPLACEMENT OF FILTERS | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 4/9/19 3:44 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-42290385 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 4/4/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-42290588 | QA ADRIAN MINJARES GSA installed 2 electrical covers behind tower CONVENT | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 4/5/19 12:00 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-42290609 | escort sprinkler construction let them in to boiler rm at convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/5/19 4:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42290641 | replaced belt eru#1 broke off b-42 SECOND FLOOR MECHANICAL ROOM CONVENT | CM | CORRECT | CLOSE | TX0116CV-Floor 02-Mechanical Equipment Room | 4/5/19 4:30 PM | NO | 07 | 89363 | ||||||||||||||||||||
| 19-42361555 | 24 HOUR LIGHTS BASEMENT ROOM 021 WATER LEAK COMING OUT CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 4/11/19 7:38 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-42635496 | MAIN FLOOR DRAIN CLOGGED CONVENT BASEMENT AREA | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 4/15/19 12:03 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-42636624 | 24 HOUR BASEMENT LEAK ROOM 021 AT CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 4/11/19 7:38 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-42636750 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/12/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42636782 | worked on 1st floor cell 133 toilet not flushing had trouble removeing secure screws to remove cover | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 4/12/19 11:00 AM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-42636794 | installed condensate pan tablets on all ahus on convent | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Mechanical Equipment Room | 4/12/19 2:00 PM | NO | 07 | 89359 | ||||||||||||||||||||
| 19-42636800 | spot check chiller and tower good running convent | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 4/12/19 5:00 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-42708712 | WATER LEAK 1ST FLOOR CELL BLOCK 171 CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/16/19 1:04 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42710447 | QA TX0116CV: Outside wall lights have spider webs accumulation. located facing inspection canopy. Need cleaning. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 4/16/19 2:28 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-42710462 | QA TX0116CV: AQI recycling containers and area behind containers need to be cleaned. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 4/16/19 2:31 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-42710470 | QA TX0116CV: Outside wall and wall lights have spider webs accumulation. North side wall facing canopy. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 4/16/19 2:33 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-42710481 | QA TX0116CV: North most side wall have dirt and bird feces accumualtion. located facing inspection canopy and TABC booth. Need cleaning. | GSAI | NORMAL | CLOSE | TX0116CV-USBS CONVENT | 4/16/19 2:34 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42710487 | QA TX0116CV: Entrance wall area by Primary booths need to be cleaned. Dirt and smudges on wall. | GSAI | NORMAL | CLOSE | TX0116CV-USBS CONVENT | 4/16/19 2:36 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42723226 | tour and chemical check/added salt bags to softner | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/15/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42810861 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/16/19 11:30 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42810955 | escort elevator tech and gsa inspector convent elevator inspection | WR | QACALL | CLOSE | TX0116CV-USBS CONVENT | 4/16/19 2:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42812387 | REQUEST TO CHECK SALLY PORT ENTRANCE DOOR HARDWEAR NOT LOCKING PROPERLY | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/18/19 10:03 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-42813950 | 24 HOUR CONVENT WATER LEAK IN BASEMENT COMING FROM CLEAN OUT BY BASEMENT DETAINEES AREA | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 4/13/19 7:30 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-42813959 | 24 HOUR SEWER DRAIN BACKING UP BASEMENT | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 4/15/19 10:45 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-42817124 | checked 2nd floor as per frankie got called last night supper hot chiller and ahu on walked thrue felt cool | CM | CORRECT | CLOSE | TX0116CV-Floor 02 | 4/18/19 11:00 AM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-42817159 | spot check boiler and chiller on CONVENT/tour and chemical check | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 4/18/19 9:00 AM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-43206229 | tour and chemical check convent bridge | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/19/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43213052 | escort camero took pictures of sally port door top and bottom doors, and 2nd floor glass doorby chiller room escort mr quintania and joe garza and construction first floor toilets open toilet access doors to check for leaks they thought they were leaking and going down to basement | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 4/19/19 11:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-43214613 | trouble shoot sidewalk light by canopy got run over last night looked for tripped breaker found none turned out to be city problem as per gabe walk thrue looking for burned lights found none convent | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/19/19 2:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43216161 | spot check chiller was on convent | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 4/19/19 5:30 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-43300958 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/22/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43300967 | 24 HOUR CELL 171 HOT WATER IS COMING OUT NOT STOPPING | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 4/20/19 3:45 AM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-43307406 | 24 HOUR A/C HOT 2ND FLOOR CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 4/17/19 11:00 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-43307412 | 24 HOUR A/C FEELS HOT CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 4/20/19 7:30 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-43311154 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/23/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43315917 | adjusted timers for outside lightes canopy and pole convent | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 4/25/19 2:00 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-43315931 | dust and sweep chiller room dust and sweep boiler room | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 4/25/19 3:00 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-43315940 | unclogged toilet basement womens gym | CM | CORRECT | CLOSE | TX0116CV-SubBasement | 4/25/19 11:00 AM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-43316116 | INSTALL NEW CUSTODISAL DISPENSERS IN CUSTODIAL ROOM BUILDING6, AND CONVENT BRIDGE | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 4/25/19 10:30 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-43329544 | 24 HOUR CONVENT CELL 171 HOT WATER IS COMING OUT NOT STOPPING | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/20/19 3:45 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43377062 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 4/26/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-43377756 | basement hall way lites are off traced breaker and turned on | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/26/19 10:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43425656 | CONVENT BRIDGE CONTROL ROOM 112 TEMPERATURE VERY HOT | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 4/30/19 3:47 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43432179 | tour and chemical check COMNVENT | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 4/29/19 10:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43501506 | tour and chemical check checked and monitored chillers/ check for any leaks storm | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 5/1/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43501522 | oiled door squicking basement going to gym CONVENT | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 5/1/19 2:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43543083 | MISC escort elevator tech convent need to order part he advised gabe vargas | WR | UTILMISC | CLOSE | TX0116CV-USBS CONVENT | 5/3/19 3:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43572505 | convent Water Faucet The water faucet in the ladies 2nd floor is not working needs batteries | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 5/8/19 2:53 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-43576312 | Raw sewage leak--Convent it has been reported that there is a raw sewage leak in/around the stair well leading to the commander at Convent Border station | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 5/9/19 4:08 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43576465 | replaced battery 2nd floor womens toilet sink repair door stopper comand center added epoxy cement glue left to dry for tomarrow | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 5/8/19 3:00 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-43610057 | REQUEST TO CHECK 1ST FLOOR ROOM 021 FOR WATER LEAK | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 5/13/19 2:46 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-43677546 | QA GSA VERONICA ARCHULETA / CONVENT BRIDGE REQUEST TO CLEAN ALL LIGHT LENS FITURES THROUGHT BUILIDNG , 1ST, 2ND. BASEMENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 5/14/19 4:00 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-43765902 | CONVENT 1ST FLOOR MAIN LOBBY TO WARM - TURN ON CHILLER #1 TO HELP #2 COOL DOWN SPACE TEMP | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 5/14/19 5:00 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44409600 | escort fire alarm sprinkler tecks did annual convent | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 5/15/19 3:30 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44409609 | tour and chemical check turned off canopy lights and adjust timer building 6 | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 5/15/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44410290 | REQUEST TO CHECK A/C THROUGH OUT BUBBLE ROOM /PEDESTRAIN WALKWAY 1ST FLOOR CONVENT BRIDGE TOO HOT THROUGH OUT BUILIDNG | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 5/20/19 2:32 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44416038 | start replaceing bearings and shaft tower#1 convent | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 5/20/19 10:30 AM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-44416411 | tour and chemical check CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 5/17/19 9:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-44416750 | request to check fire panel/ checked fire panel did reset need to put out service call CONVENTmight be phone lines/ fire panel/ checked fire panel not transmitting to monitoring center | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 5/17/19 11:00 AM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-44416765 | womens toilet 2nd floor going down slow unclogged convent | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 5/17/19 12:00 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44416825 | QA TX0116CV: The screen on cooling tower cistern tanks has debris accumulation. Debris need to be removed. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/21/19 4:11 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44416829 | QA TX0116CV: Hallway light ceiling lens has bug accumulation by Amistad plaza exit door. | GSAI | NORMAL | CLOSE | TX0116CV-USBS CONVENT | 5/21/19 4:12 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-44416837 | QA TX0116CV: Outside drain by pedestrian exit ramp needs to be clear of debris. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/21/19 4:14 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44416841 | QA TX0116CV: Holding cell wall needs paint touch up. Room 170 | GSAI | NORMAL | CLOSE | TX0116CV-USBS CONVENT | 5/21/19 4:15 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-44416846 | QA TX0116CV: Sallyport roof drain needs to be clear of debris. | GSAI | NORMAL | CLOSE | TX0116CV-Roof | 5/21/19 4:17 PM | NO | 07 | 63032 | ||||||||||||||||||||
| 19-44444498 | turn chiller#2 on and monitor they wont turn off | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 5/20/19 10:00 AM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-44494483 | CHECK MINISPLIT UNIT ROOM 206 AT BRIDGE 1 CONVENT FOR NOT WORKING PROPERLY/ under warranty | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 5/22/19 4:30 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-44532894 | REQUEST TO CHECK BOOTH # 4 CONVENT BRIDGE VERY HOT AC NOT WORKING PROPERLY REPORTED BY SUPERVISOR CBP VASQUEZ | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 5/24/19 4:04 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44532909 | REQUEST TO CHECK CONVENT BUILDING TOO HOT REPORTED BY CBP SUPERVISOR VASQUEZ AND WATCH COMANDER JUAN HERNANDEZ | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 5/24/19 4:11 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44634146 | QA GSA VERONICA ARCHULETA / CONVENT BRIDGE /Floor outside of lobby was cleaned. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 5/29/19 10:37 AM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44634240 | QA GSA VERONICA ARCHULETA / CONVENT BRIDGE / floor at commander center was cleaned under floor mat and all edges . | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 5/29/19 10:39 AM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44634310 | QA GSA VERONICA ARCHULETA / CONVENT BRIDGE / cobwebs around windows frames. - cobwebs on columns was removed . - cobwebs on doors frame was removed. OUTSIDE CANOPY AND THROUGH OUT BUILIDNG | GSAI | NORMAL | CLOSE | TX0116CV-Entire Building | 5/29/19 10:41 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44643483 | tour and chemical check convent | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 5/28/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44662559 | REQUEST TO CHECK CONVENT EXIT DOORS AIR CURTAINS BEING ON OFF POSITION | WR | QACALL | CLOSE | TX0116CV-Floor 01 | 5/30/19 5:10 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44705023 | URGENT BASEMENT OVERFLOW AT CONVENT BRIDGE COMING FROM SEWER | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 5/31/19 4:33 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-44769345 | replaced flush button, sloan valve on cell toilet convent 1st floor | CM | CORRECT | CLOSE | TX0116CV-Floor 01 | 6/3/19 12:00 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44769358 | unclogged sink 2nd floor mens restroom convent reported by diana | CM | CORRECT | CLOSE | TX0116CV-Floor 02 | 6/3/19 4:30 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-44785725 | POWER OUT AT CONVENT BRIDGE 1 BASEMENT AREA PROCESSING NO POWER | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 6/4/19 2:53 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-44789950 | REQUEST TO CHECK CONVENT BRIDGE LANE #4 FOR LEAK COMING FROM A/C | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 6/5/19 9:27 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44794173 | REQUEST TO INSTALL MISSING CHILDREN CABINET AT CONVENT BRIDGE 1 | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 6/5/19 12:06 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44794979 | REQUEST TO CHECK WATER FAUCET AT CONVENT 2ND FLOOR LADIES RESTROOM AND MEN RESTROOM | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 6/5/19 3:52 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-44804047 | NO POWER BASEMENT AREA CONVENT | WR | SERVCALL | CLOSE | TX0116CV-Basement | 6/6/19 1:00 PM | NO | 07 | 63026 | ||||||||||||||||||||
| 19-44821596 | QA TX0116CV - Interviewing room #146 has two water stained ceiling tiles. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 6/10/19 5:16 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44821607 | QA TX0116CV. Front of building by Zaragoza street. There is an opening by or next rain gutter. It is a potential water penetration into the building It needs to be closed. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 6/10/19 5:23 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44821618 | QA TX0116CV. Ground lights by flag pole, light poles, and building wall night lights are on during the day. Photo cells or timers need to be checked. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 6/10/19 5:32 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44821871 | QA Misc. TX0116CV. Request miscellaneous services to paint yellow caution sign on first floor stairways. It has to be painted across and read from the top and about 12 inches wide. Safety yellow with black letters painted across at the center. Please ask technician to call me for details. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 6/10/19 5:37 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44821877 | QA TX0116CV. The basement stairways need to be swept and remove dust accumulation. | GSAI | NORMAL | CLOSE | TX0116CV-Basement | 6/10/19 5:41 PM | NO | 07 | 63026 | ||||||||||||||||||||
| 19-44899963 | QA CEILING LAMP MISSING AT ENYTRANCE HALLWAY BY AMISTAD PLAZA ENTRANCE | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 6/11/19 12:48 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44903905 | tour and chemical check added 13 bags of salt to softner at convent bridge | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 6/7/19 9:00 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44905621 | QA Adrains qc glued 2 pocket holders in generator | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 6/7/19 11:30 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44922257 | tour and chemical check/ swept chiller room | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 6/10/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-44922358 | BEGIN WITH REMOVAL OF OLD TOILET AND PAPER TOILET/ DESPENSER AND NEW DISPENSER INSTALLED | CM | CORRECT | CLOSE | TX0116CV-Floor 01 | 6/11/19 8:00 AM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44922958 | Convent CBP is requesting to have the door handle repaired in room 152./door handle to Rm 152, Convent Bridge I/1st floor, requires repair as the handle came apart at both sides. This is a main door to IPT processing and has high usage. | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 6/12/19 3:22 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44924470 | QA VERONICA ARCHULETA PED WALKWAY / CONVENT GROUNDS Heavy accumulation of debis, trash and leaves in planted areas. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924492 | QA VERONICA ARCHULETA CONVENT PED WALKWAY /Ensure contractor removes temporary irrigation (white piping)? Exposed and lifted drip lines. Irrigation | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924507 | QA VERONICA ARCHULETA / PED WALKWAY / CONVENT Plants & Hard Surfaces Visible dead shrubs along planted areas. WARRANTY? Heavy accumulation of soil on paved areas. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924518 | QA VERONICA ARCHULETA CONVENT/ PED WALKWAY / Exterior Light Fixtures | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924560 | ADMIN BLDG / Holding Cells & Interview Area Floors free of dirt, trash or debris however appear chipped by entrance doors. NOTE: Ensure O&M manuels are received for maintenance | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 5/14/19 2:30 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44924637 | QA VERONICA ARCHULETA CONVENT ADMIN BLDG / Holding Cells & Interview Area Floors free of dirt, trash or debris however appear chipped by entrance doors. NOTE: Ensure O&M manuels are received for maintenance. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 5/14/19 2:30 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44924666 | QA VERONICA ARCHULETA CONVENT ADMIN / Command Center - floors Floors under desks heavily scuffed and no finish | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 5/14/19 2:30 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-44924675 | QA VERONICA ARCHULETA CONVENT SECONDARY INSPECTION / CanopyLight accumulation of dust & cobwebs on canopy. Ensure semi-annual cleaning of canopies is scheduled and completed. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924689 | QA VERONICA ARCHULETA CONVENT PRIMARY INSPECTION / Booths - floorsFloors dusty, stained and grime buildup. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924693 | QA VERONICA ARCHULETA CONVENT PRIMARY INSPECTION / Booths - surfacesStainless steel counter stained and spotted | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924699 | QA VERONICA ARCHULETA CONVENT PED Walkway / Public Entrance -Floors dusty, stained & grimy. X -Gum accumulation on sidewalks. X -Canopy fixtures light layer of dust. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924711 | QA VERONICA ARCHULETA CONVENT ADMIN BLDG / Sally Port-Light fixtures Heavy accumulation of dust and cobwebs. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 5/14/19 2:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-44924744 | QA VERONICA ARCHULETA CONVENT Supplies/Material should not be leaning or X touching water heater & piping. NOTE: Recommend removal of microwave. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 02 | 5/14/19 2:30 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-45569743 | unclogged ladies sink 1st floor restroom behind command center | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 6/12/19 12:00 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-45569760 | replaced prefilters ahu#1-1 as per mr vargas no air flow in building replaced prefilterseru#-6 as per mr vargas no air flow in building | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 6/12/19 2:00 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-45579782 | Request to check Smardt chiller to check cavity temperatures on the Smardt chillers at Convent? The cavity temperatures are to low on the compressors. | WR | QACALL | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 6/18/19 2:04 PM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-45579946 | REQUEST TO CHECK THE PEDESTRAIN WALKWAY A/C NOT WORKING CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 6/18/19 2:38 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-45579963 | Convent early tour | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 6/17/19 11:30 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-45632134 | Urgent AC Outage / LAN Room / Convent Bridge / Laredo The mini-split a/c unit in the OIT Security LAN room #206 at Convent Bridge is still not functional. The room is reaching high temperatures | WR | SERVCALL | CLOSE | TX0116CV-USBS CONVENT | 6/19/19 4:05 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-45632197 | Convent escort Mechanical Service Team start working on chiller #2 PM | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 6/18/19 10:30 AM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-45766159 | Convent tour | CM | CORRECT | CLOSE | TX0116CV-USBS CONVENT | 6/21/19 3:00 PM | NO | 07 | 60500 | ||||||||||||||||||||
| 19-45856152 | QC OMI Basement, door from sally port, not closing | need to adjust door | OMI | INITIAL | CLOSE | TX0116CV-Basement | 6/27/19 11:13 AM | NO | 07 | 63026 | |||||||||||||||||||
| 19-45856159 | QC OMI 2nd floor, break rm, return filter dirty | need to replace filter | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:14 AM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45856168 | QC OMI 2nd floor, break rm, lamp lenses dirty | need to clean lamp lenses | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:16 AM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45856182 | QC OMI 2nd floor,admin,all lamp lenses dirty | need to clean lamp lenses | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:17 AM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45856186 | QC OMI 2nd floor, admin, return filters dirty | need to replace return air filters | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:19 AM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45856189 | QC OMI 2nd floor, cubicle area, return filters dirty | need to replace return filters | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:21 AM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45856203 | QC OMI 2nd floor, hallway exit, northside, lamp lenses dirty | X | need to clean lamp lenses | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 11:23 AM | NO | 07 | 63030 | ||||||||||||||||||
| 19-45856212 | QC OMI Canopy area, inspection tables, bottoms dirty and scracthed | X | need to clean and re-paint | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 6/27/19 11:24 AM | NO | 07 | 89357 | ||||||||||||||||||
| 19-45856244 | QC OMI Boiler rm, eye wash , missing signature, water came out dirty | X | needs signature and exercize unit | OMI | INITIAL | CLOSE | TX0116CV-Basement | 6/27/19 11:26 AM | NO | 07 | 63026 | ||||||||||||||||||
| 19-45856270 | QC OMI Boiler Rm, Boiler # 1, checked releif valve | X | relief valve working fine | OMI | INITIAL | CLOSE | TX0116CV-Basement-Boiler Mechanical Room | 6/27/19 11:31 AM | NO | 07 | 89356 | ||||||||||||||||||
| 19-45856280 | QC OMI | Boiler Rm, Boiler # 2, checked releif valve | X | Relief Valve working fine | OMI | INITIAL | CLOSE | TX0116CV-Basement-Boiler Mechanical Room | 6/27/19 11:33 AM | NO | 07 | 89356 | |||||||||||||||||
| 19-45856285 | QC OMI | Argriculture Rm, lamp lenses dirty | NEED CLEANING | X | Need to clean lenses | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:34 AM | NO | 07 | 63029 | ||||||||||||||||
| 19-45856298 | QC OMI 13 | Cu-5 outside Agriculture, is dirty | X | Unit needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:37 AM | NO | 07 | 63029 | |||||||||||||||||
| 19-45856309 | QC OMI CU-3 outside of Agriculture RM. Is dirty | X | Unit needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:38 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-45856323 | QC OMI Gutter outside of Agriculture, canopy area very dirty | X | Gutter needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 6/27/19 11:41 AM | NO | 07 | 89357 | ||||||||||||||||||
| 19-45856328 | QC OMI Westside entrance door to pedestrian area, not closing | X | Door needs to be adjusted | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:42 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-45856348 | QC OMI | Pedestrian area, return dirty | X | Need to clean return | I | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:44 AM | NO | 07 | 63029 | ||||||||||||||||
| 19-45856362 | QC OMI Pedestrian area, Fire extinguisher, not signed | X | Need to check extinguisher and sign card | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 6/27/19 11:46 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-45856383 | QC OMI Door from pedestrian area to elevator, paint chipped | X | Need to paint door | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 11:48 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-45856392 | QC OMI Gutter drain outside of sally port very dirty | X | Neeed to clean gutter drain | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 6/27/19 11:49 AM | NO | 07 | 89357 | ||||||||||||||||||
| 19-45860001 | tour and chemical check | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 6/25/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-45860066 | replace 2 ballast canopy convent helped alfaro replace 1 ballast canopy convent | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 6/26/19 11:00 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-45862547 | QC OMI CUSTODIAL COBWEBS ON CEILING ( SALLY PORT AREA ) | X | COBWEBS NEEDS TO BE REMOVED | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 6/27/19 5:49 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-45862555 | QC OMI CUSTODIAL DEBRIS AND DIRTY ON ELEVATOR'S TRASHOLD | X | TRASHOLD NEEDS TO BE CLEANED | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 6/27/19 5:52 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-45862559 | QC OMI CUSTODIAL COBWEBS ON WINDOWS FRAME ( BREAK ROOM ) | X | WINDOWS NEDDS TO BE CLEANED ) | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 6/27/19 5:53 PM | NO | 07 | 63029 | ||||||||||||||||||
| 19-45862562 | QC OMI CUSTODIAL COBWEBS ON WINDOWS ( OUT SIDE AREA ) | X | WINDOWS NEED TO BE FREE OF COBWEBS | OMI | INITIAL | CLOSE | TX0116CV-USBS CONVENT | 6/27/19 5:55 PM | NO | 07 | 60500 | ||||||||||||||||||
| 19-45862569 | QC OMI CUSTODIAL DUST ON TOP OF PARTITION WALLS ( SECOND FLOOR ADMINISTRATION AREA ) | X | PARTITION WALLS NEED WIPE DOWN | OMI | INITIAL | CLOSE | TX0116CV-USBS CONVENT | 6/27/19 5:57 PM | NO | 07 | 60500 | ||||||||||||||||||
| 19-45862573 | QC OMI CUSTODIAL SCRATCH ON WALL ( SECOND FLOOR PERMISSION AREA ) | WALLS NEED TO BE FREE OF SCRATCHES | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 5:58 PM | NO | 07 | 63030 | |||||||||||||||||||
| 19-45862578 | QC OMI CUSTODIALDUST AND INSECTS ON COUNTER ( PERMISSION ARA 2 FLOOR ) | X | COUNTER NEEDS TO BE CLEANED | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 6:00 PM | NO | 07 | 63030 | ||||||||||||||||||
| 19-45862581 | QC OMI CUSTODIAL STAINS ON DOOR KICK PLATE ( MEN RESTROOM SECOND FLOOR) | X | DOOR KICK PLATE NEEDS TO BE CLEANED | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 6/27/19 6:02 PM | NO | 07 | 63030 | ||||||||||||||||||
| 19-45862583 | QC OMI CUSTODIAL COBWEBS ON WINDOWS ( COMANDER CENTER AREA ) | X | WINDOWS NEEDS TO BE FREE OF COBWEBS | OMI | INITIAL | CLOSE | TX0116CV-USBS CONVENT | 6/27/19 6:04 PM | NO | 07 | 60500 | ||||||||||||||||||
| 19-45862588 | QC OMI CUSTODIAL STAINS ON CABINETS ( AQI ROOM ) | X | STAINLEES STEEL NEEDS WIPE DOWN | OMI | INITIAL | CLOSE | TX0116CV-USBS CONVENT | 6/27/19 6:05 PM | NO | 07 | 60500 | ||||||||||||||||||
| 19-45907025 | Convent verify unit parts needed to repair ac on second floor land room already send quote to Mr Jerome he needs to review and sign special order form to place the order. | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 6/27/19 3:00 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-46050817 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/1/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46053631 | QA TX0116CV: Outside lights by Amistad Plaza are on during the day | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 7/1/19 2:20 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-46053637 | QA TX0116CV: Outside lights by inspection area are on. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 7/2/19 2:22 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-46053647 | QA TX0116CV: Open PVC pipe on floor by AQI collection bins. It needs to be covered to keep debris and water out of the pipe. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 7/1/19 2:24 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-46053662 | QA TX0116CV: Entrance surface area to pedestrian processing area needs to be cleaned. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 7/1/19 2:26 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-46192313 | tour and chemical check | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/5/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46207039 | BOILER advised gabe boilers lost bas command and also booth#4 reported under warrenty not working | CM | CORRECT | CLOSE | TX0116CV-Basement-Boiler Mechanical Room | 7/5/19 12:30 PM | NO | 07 | 89356 | ||||||||||||||||||||
| 19-46207076 | replaced battery sink 2nd floor womens toilet replaced battery sink 1st floor mens restroom alfredo reported basement womens | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/5/19 4:30 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46209346 | turned boiler #2 on as per gabe for condensation | CM | CORRECT | CLOSE | TX0116CV-Basement-Boiler Mechanical Room | 7/9/19 10:00 AM | NO | 07 | 89356 | ||||||||||||||||||||
| 19-46210492 | spot check sinks done yesterday working fine CONVENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/9/19 12:30 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46214669 | tour and chemical check turn on boiler for a while | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/10/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46887592 | tour and chemical check CONVENT | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/11/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-46888140 | convent bridge booth #4 not cooling found burned motor proceded to remove motor and belt | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/12/19 11:00 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47009704 | QC OMI MECHANICAL Eye wash station adjacent to command center is dirty | X | Need to clean and exercise accordingly | OMI | INITIAL | CLOSE | TX0116CV-Basement | 7/18/19 12:01 PM | NO | 07 | 63026 | ||||||||||||||||||
| 19-47009722 | QC OMI LANDSCAPE Branches too low on the pedestrian walk way | X | Need to trim tree branches | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:05 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009736 | QC OMI MECHANICAL Curb line adjacent to pedestrian walkway is dirty | X | Need to sweep curb line | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:09 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009743 | QC OMI LANDSCAPE Weeds found in flower bed | X | Need to weed out bed | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:11 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009754 | QC OMI MECHANICALGutter on southwest side pedestrian walkway is dirty | X | Need to clean out gutters | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:13 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009760 | QC OMI MECHANICAL Lane 5, bike lane, lamp is dirty | X | Need to clean lamp | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:15 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009769 | QC OMI MECHANICAL Booth # 2 , outside top panel found open | X | Need to close and secure panel | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:16 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009776 | QC OMI MECHANICAL Booth # 1, Condensation drip found & panel dirty | X | Need to resolve the condensation problem | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:18 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009809 | QC OMI MECHANICAL TABC booth, has dirty lamp lense | X | Need to clean lamp lense | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:24 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47009827 | QC OMI MECHANICAL Hall way next to command center, lamp lenses is dirty | X | Need to clean lamp lenses | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/18/19 12:28 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47010928 | escort jake chemical check | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 971345 | TX0116C09B001 | TX0116CV-CTR-C09B-1 | 7/17/19 5:00 PM | NO | 07 | 89357 | |||||||||||||||||
| 19-47013959 | REQUEST TO CHECK FOUL SEWER SMELL IN BASEMENT AT CONVENT BRIDGE | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 7/19/19 11:15 AM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-47014075 | QC OMI CUATODIAL stains on side walk by basement entrance | X | side walk needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 7/19/19 11:44 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47014079 | QC OMI MECHANICAL hole on floor under floor mat ( comander center room ) | X | floor tile needs to be changed | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 7/19/19 11:45 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47014088 | QC OMI CUSTODIAL cobwebs on columns (secondary inspection area ) | X | columns need dusting | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 11:47 AM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014095 | QC OMI CUSTODIAL shoes stains on wall ( out side comander center ) | X | walls need to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 11:49 AM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014126 | QC OMI CUSTODIAL dust and cobwebs on sink ( secondary inspection area ) | X | sinck needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 7/19/19 12:02 PM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47014135 | QC OMI CUSTODIAL dust , cobwebs and stains on all inspection booths | X | booths needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 7/19/19 12:04 PM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47014139 | QC OMI CUSTODIAL debris and dirty on ground ( secondary inspection area ) | X | ground needs pressure wash | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 12:05 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014144 | QC OMI CUSTODIAL dust and stains on tables ( secondary inspection area ) | X | tables need wipe down | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 12:08 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014150 | QC OMI CUSTODIAL cobwebs and dust on wall ( TABC booth ) | X | booth needs dusting | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 12:10 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014162 | QC OMI CUSTODAIL smock stains on column ( dameg by X-Ray truck ) | X | stains need to be removed | OMI | INITIAL | CLOSE | TX0116CV-Exterior-Outside | 7/19/19 12:11 PM | NO | 07 | 89357 | ||||||||||||||||||
| 19-47014873 | 24 HOUR NO LIGHTS ON SECONDARY INSPECTION | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/5/19 10:00 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47014917 | 24 HOUR LIGHTS NOT ON AT SECONDARY AREA | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/12/19 10:34 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47084131 | QA Request to trim the overgrown tree branches on the buildings in front of the Kennel building | WR | QACALL | CLOSE | TX0116CV-Exterior-Outside | 7/23/19 3:17 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47084632 | QA Request to repair lights in four parking light poles. | WR | QACALL | CLOSE | TX0116CV-Exterior-Outside | 7/23/19 3:22 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47088497 | checked cells in convent with suppervisor salinas discharge | temp at 65 degrees in cells sent email report | WR | SERVCALL | CLOSE | TX0116CV-Basement-Boiler Mechanical Room | 7/22/19 10:30 AM | NO | 07 | 89356 | |||||||||||||||||||
| 19-47089473 | tour convent | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/23/19 4:04 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47091185 | SIMPLEX CALLED IN NO TEST SIGNAL RECEIVED RECENTLY TO MONITORING SYATEM, PLEASE CHECK THE SENSOR INVOLVE. | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 7/23/19 4:29 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47146900 | 24 HOUR HOLDING CELLS ARE HOT REACHING 85F | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 7/21/19 10:30 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47150506 | REQUEST TO CHECK SECURE DOOR FOR NOT WORKING PROPERLY CONVENT BRIDGE BASEMENT EASTERN HALLWAY | WR | SERVCALL | CLOSE | TX0116CV-SubBasement | 7/25/19 3:23 PM | NO | 07 | 63033 | ||||||||||||||||||||
| 19-47150958 | 24 HOUR CONVENT GAS SMELL SHOP AREA | WR | SERVCALL | CLOSE | TX0116CV-Entire Building | 7/24/19 11:00 PM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47150968 | CBP has submitted a request to repair the HVAC at Primary Booth #4. The unit is not working and a temporary portable unit has been in use. | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/25/19 5:55 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47216575 | CBP is requesting to check the lights by the perimeter fence near Convent bridge where the temporary buildings are being set up. | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/30/19 10:53 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47282193 | replaced flag us | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 7/26/19 4:00 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47307221 | convent tour | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/29/19 10:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47328956 | REQUEST TO CHECK SINK NO FLOW 1ST FLOOR MALE RESTROOM AT CONVENT BRIDGE INFRONT OF ADMINSTRATIVE OFFICE | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 7/31/19 12:20 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-47333742 | 24 HOUR BOOTH #4 A/C NOT WORKING CONVENT | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 7/26/19 9:00 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47415919 | Convent early tour | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 7/31/19 11:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47429504 | URGENT CONVENT BRIDGE BASEMENT AREA SEWAGE BACKING UP | WR | SERVCALL | CLOSE | TX0116CV-Basement | 8/2/19 2:15 PM | NO | 07 | 63026 | ||||||||||||||||||||
| 19-47499712 | Convent escort Johnson Controls for annual PM fire pannel testing BPHQ escort Johnson Controls for annual PM fire panel testing | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 8/6/19 9:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47499752 | CHECK GENERATOR CONVENT BRIDGE 1 NEED TO REPLACE BATTERRIES | CM | CORRECT | CLOSE | TX0116CV-Exterior-Outside | 8/7/19 12:00 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47499803 | 24 HOUR CONVENT BRIDGE FANS UNDER CANOPY NOT WORKING | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 8/3/19 11:00 AM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47499819 | 24 HOUR CBP OFFICER REQUEST TO CHECK SECOND FLOOR WOMENS RESTROOM SINK NOT WORKING | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 8/4/19 1:00 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-47543005 | CONVENT found generator on low batterry fault, check baterries where dry will need to replace both baterries -advise Mr Rosales | CM | CORRECT | CLOSE | TX0116CV-Floor 02-Mechanical Equipment Room | 8/7/19 12:00 PM | NO | 07 | 89363 | ||||||||||||||||||||
| 19-47543022 | Convent basement area trip breaker caused by CBP portable cooler - reset breaker | WR | SERVCALL | CLOSE | TX0116CV-Basement | 8/7/19 11:00 AM | NO | 07 | 63026 | ||||||||||||||||||||
| 19-47552153 | CONVENT 2ND WOMENS RESTROOM SINK NEEDS BATTERY | WR | SERVCALL | CLOSE | TX0116CV-Floor 02 | 8/9/19 6:06 PM | NO | 07 | 63030 | ||||||||||||||||||||
| 19-47561033 | REQUEST TO CHECK A/C NOT WORKING AT CONVENT KENNELS BUILIDNG | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 8/12/19 12:29 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47561493 | AC Unit outage at Vehicle Primary Lane 2 at the Convent Bridge I | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 8/12/19 2:42 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47614202 | Convent early tour | CM | CORRECT | CLOSE | TX0116CV-Entire Building | 8/12/19 11:00 AM | NO | 07 | 63027 | ||||||||||||||||||||
| 19-47716559 | Cnvent escort Mechanical Service Team work on chiller 1 deficiencies found when performing PM. | CM | CORRECT | CLOSE | TX0116CV-Floor 01-Chiller Mechanical Room | 8/14/19 10:30 AM | NO | 07 | 89358 | ||||||||||||||||||||
| 19-47716640 | BS1 K9 David De Leon request to check AC not working- system working properly, | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 8/14/19 4:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47752077 | Convent CBP request to check air compressor located on green room - check power OK, this is agency equiptment | WR | SERVCALL | CLOSE | TX0116CV-Exterior-Outside | 8/15/19 5:30 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47857454 | QA TX0116CV: Inspection canopy posts, lights, and mesh screen has spider web accumulation. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 8/19/19 3:46 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47857460 | QA TX0116CV: Outside canopy by Amistad Plaza has spider web build up. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 8/19/19 3:48 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47857467 | QA TX0116CV: Inspection canopy posts, lights, and mesh screen has spider web accumulation. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 8/19/19 3:49 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47857475 | QA TX0116CV: Amistad Plaza bushes. Branches need to be trimmed to access door to power disconnect area. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 8/19/19 3:51 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47857483 | QA TX0116CV: Water stained ceiling tile in front of room 206 | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 8/19/19 3:52 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-47857488 | QA TX0116CV: Grounds by primary booths has flying debris accumulation. | GSAI | NORMAL | CLOSE | TX0116CV-Basement | 8/19/19 3:54 PM | NO | 07 | 63026 | ||||||||||||||||||||
| 19-47860679 | QA TX0116CV: Entrance area by room 201 has spider webs. | GSAI | NORMAL | CLOSE | TX0116CV-Floor 01 | 8/19/19 4:27 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-47864399 | QA TX0116CV: Pedestrian entrance concrete walkway ramp surface area has stains build up and needs to be cleaned. | GSAI | NORMAL | CLOSE | TX0116CV-Exterior-Outside | 8/19/19 4:36 PM | NO | 07 | 89357 | ||||||||||||||||||||
| 19-47885216 | CONVENT BRIDGE 1ST FLOOR COMMAND CENTER TOO HOT REQUEST TO CHECK A/C | WR | SERVCALL | CLOSE | TX0116CV-Floor 01 | 8/19/19 5:27 PM | NO | 07 | 63029 | ||||||||||||||||||||
| 19-47969501 | QC OMI MECHANICAL CONVENT Staircase frame from basement paint is chipped and not presentable | X | Need to paint metal frame & metal steps | OMI | INITIAL | CLOSE | TX0116CV-Basement | 8/20/19 5:35 PM | NO | 07 | 63026 | ||||||||||||||||||
| 19-47969503 | QC OMI MECHANICAL CONVENT Lamps in hallway in fronmt of elevator 1, are dirty | X | Need to clean the lenses on these lamps | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 8/20/19 5:37 PM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47969507 | QC OMI MECHANICAL CONVENT Mini-split in staircase landing, filter is dirty | X | Need to clean filter & unit | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:39 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969509 | QC OMI MECHANICAL CONVENT Special unit area, hot air coming out of vent | X | Need to re-direct hot air away from common area | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:40 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969513 | QC OMI MECHANICAL CONVENT PM Fire extinguisher located at north exist, no signature | X | Need to inspect and sign on tag | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:42 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969515 | QC OMI MECHANICAL CONVENT Water line installed above ground, eyesoar | X | Warranty Item, Inform GSA | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:43 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969520 | QC OMI MECHANICAL CONVENT Concrete rubble found in bed adjacent to pedestrian walk way | X | Warranty item, Inform GSA | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:45 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969522 | QC OMI MECHANICAL CONVENT PM Fire extinguisher next to 116, no signature | X | Need to inspect and sign on tag | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:46 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969523 | QC OMI MECHANICAL CONVENT Room next to bubble rm, lamps extremely dirty | X | Need to clean the lamp lenses | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 5:48 PM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47969525 | QC OMI MECHANICAL CONVENT Mini-split located second floor of staircase, dirty filter | X | Need to clean filter & unit | OMI | INITIAL | CLOSE | TX0116CV-Floor 02 | 8/20/19 5:50 PM | NO | 07 | 63030 | ||||||||||||||||||
| 19-47979629 | OMI QC CUSTODIAL CONVENT Dirty and stains on elevator's threshold | X | needs to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/21/19 11:00 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47979893 | OMI QC CUSTODIAL CONVENT Emergency stairs going to the basement has gum | X | gums need to removed | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:02 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47980165 | OMI QC CUSTODIAL CONVENT Cobwebs on ceiling light ( first floor by elevator | X | cobwebs need to be removed | OMI | INITIAL | CLOSE | TX0116CV-Floor 01 | 8/20/19 11:03 AM | NO | 07 | 63029 | ||||||||||||||||||
| 19-47980556 | OMI QC CUSTODIAL CONVENT Dust on windows frame going to the secon floor | X | window frame needs to be free of dust | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:05 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47980977 | OMI QC CUSTODIAL CONVENT Men and women restroom floors are dirty | X | floors need to be scrubbed | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:08 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47981412 | OMI QC CUSTODIAL CONVENT Dirty under floor mat ( North exit area ) | X | Flor needs to be sweeped and mopping | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:10 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47981921 | OMI QC CUSTODIAL CONVENT dust on windows frame ( permission area secon floor ) | X | frame needs to be free of dust | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:12 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47982985 | OMI QC CUSTODIAL CONVENT stains on water fountain ( secon floor rest area ) | X | water fountains need to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:18 AM | NO | 07 | 63027 | ||||||||||||||||||
| 19-47983359 | OMI QC CUSTODIAL CONVENT Cobwebs on windows ( pedestrian walkway next to posada hotel ) | X | windows need to be cleaned | OMI | INITIAL | CLOSE | TX0116CV-Entire Building | 8/20/19 11:20 AM | NO | 07 | 63027 |