FIRE ALARM / MNS / RELEASING SYSTEM LEGEND GENERAL NOTES:AUDIBLE DESIGN CRITERIA:
ABBREVIATIONS:
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AWG AMERICAN WIRE GAGE
CD CANDELA
CFM CUBIC FEET PER MINUTE
CIS COMMON INTELLIGIBILITY SCALE
CO CARBON MONOXIDE
DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER
DB DECIBEL
DBA DECIBEL A-WEIGHTED
DDC DIRECT DIGITAL CONTROL
EMCS ENERGY MONITORING AND CONTROL SYSTEM
FA FIRE ALARM
FDC FIRE DEPARTMENT CONNECTION
FM FM GLOBAL
FX FIRE SUPPRESSION
HZ HERTZ
IAW IN ACCORDANCE WITH
IDC INITIATING DEVICE CIRCUIT
MNS MASS NOTIFICATION SYSTEM
NAC NOTIFICATION APPLIANCE CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NC NORMALLY CLOSED
NO NORMALLY OPEN
RTS REMOTE TEST SWITCH
SLC SIGNALING LINE CIRCUIT
TYP TYPICAL
UL UNDERWRITERS LABORATORY
WP WEATHER PROOF (NEMA 250, TYPE 3R)
P = PHOTOELECTRIC
S = SUPPLY
S P
PHOTOELECTRIC SMOKE DETECTOR
S S
IN-DUCT PHOTOELECTRIC SMOKE DETECTOR
REMOTE INDICATOR
WF WATER FLOW DETECTOR / SWITCH (PROVIDED BY DIVISION 21)
F MANUAL FIRE ALARM PULL STATION
LOC LOCAL OPERATIONS CONSOLE
FAA FIRE ALARM ANNUNCIATOR
VS VALVE SUPERVISORY SWITCH (PROVIDED BY DIVISION 21)
SS
SURGE SUPPRESSOR
(TRANSIENT VOLTAGE SURGE SUPPRESSOR)
DH DOOR HOLD (PROVIDED BY DIVISION 08)
AMP AMPLIFIER
S SPEAKER
SPEAKER / STROBE COMBINATION
STROBE
WALL MOUNT STROBE
AOM ADDRESSABLE OUTPUT CONTROL MODULE
AIM ADDRESSABLE INPUT MONITOR MODULE
CO
CARBON MONOXIDE DETECTOR
RL NON-ADDRESSABLE OUTPUT RELAY
IM ISOLATION MODULE
BATT SECONDARY POWER SUPPLY (BATTERY)
GROUND
VISIBLE DESIGN CRITERIA:
FACU/ACU
COMBINATION FIRE ALARM CONTROL UNIT
AND AUTONOMOUS CONTROL UNIT
RTS
REMOTE TEST STATION
ST SHUNT TRIP BREAKER (BY DIVISION 26)
ESR ELEVATOR SYSTEM RECALL PANEL (BY DIVISION 14)
R = RED
NAC
NOTIFICATION CIRCUIT POWER BOOSTER,
EXTENDER PANEL
1. PROVIDE AUDIBLE NOTIFICATION APPLIANCES AS INDICATED TO
ACCOMPLISH THE FOLLOWING DESIGN CRITERIA WITH ALL DOORS, FIRE
SHUTTERS, AND WINDOWS CLOSED. WHERE THIS DESIGN CRITERIA IS
NOT ACCOMPLISHED DURING COMMISSIONING, PROVIDE ADDITIONAL
DEVICES TO MEET THE MINIMUM DESIGN CRITERIA WITHOUT EXCEEDING
THE LIMITATIONS OF THE FACU, NAC, OR AMP. (INCLUSIVE OF PRESCRIBED
SAFETY FACTORS).
2. PROVIDE A QUANTITY OF SPEAKERS IN EACH ROOM/AREA TO ACHIEVE THE
REQUIRED SOUND POWER AND INTELLIGIBILITY OUTLINED IN THESE
CONTRACT DOCUMENTS. NOTE: DEPENDING ON THE QUALITY OF SPEAKER
USED, SEVERAL SPEAKERS TAPPED AT A LOWER SETTING MAY BE
REQUIRED TO ACHIEVE THE PRESCRIPTIVE CIS SCORE.
3. PROVIDE A MINIMUM SOUND POWER OF 70 DBA AND 15 DBA OVER THE
AVERAGE AMBIENT SOUND LEVEL AT THE MOST REMOTE LOCATION WITHIN
THE ROOM/AREA MEASURED AT 5 FT AFF. MEASURE THE SOUND POWER
OFF THE TEMPORAL THREE TONE PATTERN. THE FOLLOWING CRITERIA
WILL BE USED FOR REVIEW AND APPROVAL OF SHOP DRAWINGS.
A. REDUCE THE SOUND POWER BY 6 DB EACH TIME THE DISTANCE
BETWEEN THE APPLIANCE AND THE LISTENER IS DOUBLED.
STARTING DISTANCE IS PER MANUFACTURER'S DATASHEET,
TYPICALLY 10 FT.
B. REDUCE THE SOUND POWER IN ACCORDANCE WITH THE
MANUFACTURER'S DATASHEET FOR SOUND POWER DISTRIBUTION
NOT PERPENDICULAR TO THE FACE OF THE APPLIANCE. REFER TO
MANUFACTURER'S TYPICAL SOUND OUTPUT DISTRIBUTION DIAGRAM.
C. IN LIEU OF THE MANUFACTURER'S PUBLISHED DB LOSS, ASSUME A
MINIMUM 15 DB LOSS THROUGH A STANDARD CLOSED DOOR.
4. PROVIDE EXTERIOR SPEAKERS MEETING A MINIMUM SOUND POWER OF 70
DBA AND 15 DBA OVER THE AVERAGE AMBIENT SOUND LEVEL, AND A CIS OF
0.8 WITHIN THE AREA INDICATED MEASURED AT 5 FT ABOVE GRADE.
MEASURE THE SOUND POWER OFF THE TEMPORAL THREE TONE PATTERN.
THE AVERAGE AMBIENT SOUND LEVEL IS THE ROOT MEAN SQUARE, A-
WEIGHTED, SOUND PRESSURE LEVEL MEASURED OVER THE DURATION THE
BUILDING IS NORMALLY OCCUPIED.
5. MEET THE FOLLOWING INTELLIGIBILITY CRITERIA:
A. ACHIEVE A CIS SCORE OF 0.8 IN EACH ROOM MEASURED AT 5 FT AFF.
B. A LESSER CIS IS PERMITTED IN AREAS OF THE BUILDING WITH
EXCESSIVE SOUND REFLECTIONS, SUCH AS ROOMS WITH HARD
SURFACES (METAL, TILE, OR CONCRETE), WHERE THE OCCUPANT
CAN WALK NO MORE THAN 33 FT TO A LOCATION THAT ACHIEVES THE
MINIMUM CIS. THIS AREA MUST BE READILY ACCESSIBLE, WITHOUT
REQUIRING THE OCCUPANT TO WALK THROUGH A SECURED
DOOR/AREA OR EXIT THE BUILDING.
C. A LESSER CIS IS PERMITTED IN A NORMALLY UNOCCUPIED ROOM OF
THE BUILDING, WHERE THE OCCUPANT CAN WALK NO MORE THAN 50
FT TO A LOCATION THAT ACHIEVES THE MINIMUM CIS. THIS AREA
MUST BE READILY ACCESSIBLE, WITHOUT REQUIRING THE OCCUPANT
TO WALK THROUGH A SECURED DOOR/AREA OR EXIT THE BUILDING.
NORMALLY UNOCCUPIED ROOMS ARE CONSIDERED TO BE STORAGE
ROOMS < 100 SF, MECHANICAL / ELECTRICAL ROOMS,
COMMUNICATION CLOSETS, AND FIRE PROTECTION ROOMS.
1. PROVIDE VISIBLE NOTIFICATION APPLIANCES AS REQUIRED TO ACHIEVE
THE COVERAGE INDICATED.
2. SPACE STROBES IN ACCORDANCE WITH THE CRITERIA OUTLINED IN NFPA
72, UNLESS OTHERWISE NOTED.
1. PROVIDE AN ADDRESSABLE COMBINED FIRE ALARM / MASS
NOTIFICATION SYSTEM. INCLUDE CAPABILITY TO USE FIRE ALARM
SPEAKERS FOR PA ANNOUNCEMENTS AS INDICATED.
2. COORDINATE ALL REQUIRED SYSTEMS TO THE SATISFACTION OF THE
ENGINEER AND AUTHORITY HAVING JURISDICTION. ANY DEFICIENCIES,
INCONSISTENCIES, OR POORLY COORDINATED INSTALLATIONS SHALL BE
CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST.
3. THE FIRE ALARM DRAWINGS ARE SCHEMATIC IN NATURE AND SHOW A
MINIMAL QUANTITY OF DEVICES. DETERMINE THE FINAL QUANTITY AND
LOCATION OF ALL DEVICES IN ACCORDANCE WITH THE SPECIFICATIONS,
CONTRACT DRAWINGS, AND MANUFACTURER'S WRITTEN
RECOMMENDATIONS TO BE COMPLIANT WITH ALL APPLICABLE CODES
AND STANDARDS. PROVIDE ADDITIONAL DEVICES WHEN REQUIRED FOR
A FULLY FUNCTIONING FIRE ALARM SYSTEM AND MASS NOTIFICATION AS
REQUIRED BY NFPA 72, UFC 3-600-01 AND UFC 4-021-01.
4. CONCEAL ALL CONDUITS IN WALLS OR ABOVE CEILINGS UNLESS
OTHERWISE INDICATED. EXCEPTION: CONDUIT IS ALLOWED TO BE
SURFACE MOUNTED ON WALLS AND CEILINGS IN UNFINISHED AREAS
(SUCH AS MECHANICAL ROOM, ELECTRICAL ROOM, FIRE PROTECTION
ROOM). WHERE A CONDUIT SUPPLIES A DEVICE NOT MOUNTED DIRECTLY
ON THE WALL OR CEILING, ROUTE THE CONDUIT AS A SINGLE PENDENT
DROP TO EACH DEVICE FROM THE CEILING SURFACE ABOVE. DO NOT
TRAPEZE CONDUIT ACROSS AN OPEN SPACE.
5. ALL EXPOSED FIRE ALARM JUNCTION BOXES, COVERS AND CONDUITS IN
UNFINISHED AREAS ARE TO BE PROVIDED PRE-FINISHED RED FROM THE
FACTORY. PAINT EXPOSED CONDUIT AND JUNCTION BOXES IN FINISHED
AREAS TO MATCH ADJACENT SURFACES. FOR FINISHED AREAS WITH
EXPOSED CONDUIT AND BOXES TO MATCH ADJACENT SURFACES, LABEL
INSIDE COVER OF JUNCTION BOXES "FIRE ALARM", AND INSTALL 3/4"
WIDE RED BANDS ON CONDUIT EVERY 20FT AND ON BOTH SIDES OF
WALL PENETRATIONS PER UFC 3-600-01.
6. PROVIDE CONDUIT IN ACCORDANCE WITH THE REQUIREMENTS OF THE
ELECTRICAL SPECIFICATIONS, UNLESS OTHERWISE NOTED. SUPPORT
CONDUIT IN ACCORDANCE WITH THE NEC SUCH AS MAXIMUM 10 FT
SUPPORT INTERVALS AND 3 FT FROM A TERMINATION. TENSION ONLY
HANGERS ARE NOT PERMITTED SUCH AS BATWINGS. FLEXIBLE CONDUIT
IS ONLY PERMITTED WHEN CONNECTING TO THE FOLLOWING DEVICES
AND APPLIANCES: DEVICES LOCATED ON FIRE SUPPRESSION
EQUIPMENT SUCH AS FLOW/PRESSURE SWITCHES AND TAMPER
SWITCHES, DEVICES AND APPLIANCES LOCATED IN REMOVABLE CEILING
TILES, OR DUCT DETECTORS.
7. PROVIDE CONDUCTOR SIZING NOT LESS THAN 18 AWG FOR SLC.
PROVIDE CONDUCTOR SIZING NOT LESS THAN 16 AWG FOR NAC AND
IDC. PER UFC 3-600-01 CONSISTENTLY COLOR COORDINATE ALL
CONDUCTORS THROUGH THE SYSTEM IN RELATION TO DEVICES THEY
FEED SUCH AS SLC - BLACK/RED, STROBE - YELLOW/BLUE. PROVIDE
ADDRESSABLE SLC CIRCUITS WITH SHIELDED CONDUCTORS, WHERE
THE SHIELDING IS GROUNDED AT ONE END. PROVIDE ALL CIRCUITS WITH
LABELING AT THE POINT OF TERMINATION SUCH AS SLC 1, NAC 8, IDC 4.
8. RUN CONDUCTORS FROM DEVICE TO DEVICE WITHOUT SPLICES. WIRE
NUTS ARE PROHIBITED. UTILIZE TERMINAL STRIPS WHERE
CONDUCTORS CANNOT BE DIRECTLY TERMINATED AT THE DEVICE SUCH
AS PIGTAILS OFF A HEAT DETECTOR.
9. DO NOT USE FIRE ALARM EQUIPMENT PANELS AS RACEWAY FOR
ROUTING POWER WIRING OR LOW VOLTAGE WIRING. ONLY ROUTE
WIRING TERMINATING WITHIN THE PANEL INTO THE PANEL. PROVIDE 1/4
INCH SEPARATION BETWEEN POWER-LIMITED FIRE ALARM CIRCUITS AND
POWER CIRCUITS.
10. MOUNTING DEVICES IN THE FACU, INCLUDING ANY SUBPANELS SUCH AS
ACU, AMP AND NAC, WHICH ARE NOT UL LISTED OR FM APPROVED AS
PART OF THE UNIT IS PROHIBITED.
11. PROVIDE SURGE SUPPRESSORS TO PROTECT ALL POWER SUPPLY
CIRCUITS TO THE FACU, INCLUDING ANY SUBPANELS SUCH AS ACU, AMP,
NAC, AND ALL FIRE ALARM CIRCUITS LEAVING OR ENTERING THE
BUILDING. DEVICES AND APPLIANCES MOUNTED DIRECTLY ON THE
EXTERIOR OF THE BUILDING SUCH AS WALL MOUNTED EXTERIOR
SPEAKERS DO NOT REQUIRE SUPPRESSORS WHEN LIGHTNING
PROTECTION IS PROVIDED. MOUNT SURGE SUPPRESSORS IN A
SEPARATE ENCLOSURE, UNLESS IT IS UL LISTED OR FM APPROVED AND
INSTALLED IN THE CONTROL UNIT BY THE FACTORY.
12. INSTALL FIRE ALARM BATTERIES IN THE ENCLOSURE OF THE
DEVICE/UNIT IT SUPPORTS SUCH AS FACU ENCLOSURE OR IN AN
INDEPENDENT DEDICATED ENCLOSURE.
WC WET CHEMICAL SYSTEM
HORN / STROBE COMBINATION
WC WET CHEMICAL SYSTEM REMOTE PULL STATION (WC)
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o n e
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:5
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA001
FIRE ALARM
NOTES, LEGEND
AND
ABBREVIATIONS
18-0060
02-25-2021
C. QUINN
C. CARRAS
Revisions
ID Date Description
11/17/2020 02/25/2021
PROVIDE CEILING MOUNTED SPEAKERS AND CLEAR STROBES
AS REQUIRED TO ACHIEVE DESIGN CRITERIA.
PROVIDE CEILING MOUNTED SPEAKERS AS REQUIRED
TO ACHIEVE DESIGN CRITERIA.
NOTIFICATION APPLIANCES ARE NOT REQUIRED .
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS, AS
REQUIRED TO ACHIEVE DESIGN CRITERIA.
FIRE ALARM HATCH LEGEND
NO HATCH
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS AND
STROBES TO ACHEIVE THE DESIGN CRITERIA.
F
S P
F
S P
F
F
F
F
CO
LOC
LOC
F
F
S P
A
B
C
E
F
G
H
L
N
P
Q
7.6 8.6 9.2 9.8 10.6 10.8 11.6
6.7
7.7
8.7 9.7
10.5
11 12
CORR
RECEIVING
ELEV EQUIP
CST STORAGE
STAIR
CONF
C S
T L
O G
A
D M
IN
A
MECH
ELEC
GROUNDS &
MAINTENANCE
FLAMMABLE
STORAGE
IT
CST READY
BAYS
CUST
TOILET
TOILET
OFFICE
36A
CST SURVEY
CST COMMO
OFFICE
29A
CST MED
SUPPORT
OFFICE
28A
CST MED STOR
36B
IT
ELEC
CST
OPERATIONS
OFFICE
29B
OFFICE
28B
CST COMMAND
OFFICE
28C
MECH
TRAINING AID
STORAGE
29C
PLUMBING
CHASE
30E
CORRIDOR
7B CORR
STAIR
F
F
F
AMP
NAC
AMP NAC
S P
VS
VSWF
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F'
'D'
'B'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:5
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA101-1A
FIRE ALARM AND
MNS PLAN -
LOWER LEVEL -
OVERALL
18-0060
02-25-2021
C. QUINN
C. CARRAS
NOTES:
REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WALL MOUNTED NOTIFICATION DEVICES ARE PERMITTED IN UNFINISHED
AREAS WITH CONGESTED CEILINGS SUCH AS A MECHANICAL ROOM.
REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING
PLANS.
1/16" = 1'-0"
FIRE ALARM AND MNS PLAN - LOWER LEVEL - OVERALL
1.
2.
3.
SCALE IN FEET
0 8' 16' 32'
KEYED NOTES
1 PROVIDE RECESSED PANEL.
2 REFER TO FIRE SUPPRESSION DRAWINGS FOR QUANTITY AND /
OR LOCATIONS OF DEVICE(S).
3 MANUAL PULL STATION AND EXTERIOR SPEAKER
REQUIREMENTS ARE NOT REQUIRED AS PART OF OPTION 1.
REFER TO FA901-1F.
Revisions
ID Date Description
11/17/202002/25/2021
F
S P
FAA
F
CO
F
CO
LOC
LOC
WC
F
N A
C A
M P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
C
E
F
G
H
J
K
L
M
N
N.5
P
Q
R
2.6 3.6 4.8 5.4 7.6 8.6 9.8 10.6 10.8 11.6
3.5
4 5
5.1
5.9
6.7
7.7
8.7 9.7
10.5
11 12
ASSEMBLY
CLASSROOM/
LECTURE
FAMILY
READINESS
RECRUITING
LEARNING
CENTER
DISPLAY
101A
L A
C T
A T
IO
N
LOCKERS
CLASSROOM
BREAK /
VENDING
CLASSROOM
TRAINING
VEST
MECH / WATER
SERVICE
ANTE
105A
ANTE
105B
PHYSICAL
FITNESS
MEN
110WOMEN
ISSUING
BEVERAGES
158B
MEDICAL
TABLE / CHAIR
STORAGE
104A
KITCHEN
SERVING
158A
LOBBY / MAIN
HALL
CORR
CORR
ELEC
IT
VAULT
153A
ARMORER
ISSUING
ISSUING
152.1
WOMEN
LOCKERS
108A
MEN LOCKERS
110A
MECH
ELEC
CUST
IT
PANTRY /
OFFICE
160D
CUST
160C
TOILET
160B
SCULLERY
160A
CORR
157B
CORR
157A
CORR
CORR
101C
ALCOVE
101B
ALCOVE
101D
MEN SHOWERS
110BWOMEN
SHOWERS
108B
TOILET
CONF
OFFICE
OFFICE
WORK RM
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CONF
OFFICE
OFFICE
MECH
WORK RM
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PLUMBING
CHASE
109C
PLUMBING
CHASE
111C
ISSUING
157E
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORR
101E
ELEV LOBBY /
STAIR
101F
HEATED
STORAGE
VS
WP
DHDH
DH
DH
DH
DH
DH
3 3
DH
DH
WC
DH
WF
PROVIDE CEILING MOUNTED SPEAKERS AND CLEAR STROBES
AS REQUIRED TO ACHIEVE DESIGN CRITERIA.
PROVIDE CEILING MOUNTED SPEAKERS AS REQUIRED
TO ACHIEVE DESIGN CRITERIA.
NOTIFICATION APPLIANCES ARE NOT REQUIRED .
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS, AS
REQUIRED TO ACHIEVE DESIGN CRITERIA.
FIRE ALARM HATCH LEGEND
NO HATCH
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS AND
STROBES TO ACHEIVE THE DESIGN CRITERIA.
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F''E'
'C' 'D'
'B' 'A'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA101-2A
FIRE ALARM AND
MNS PLAN - MAIN
LEVEL - AREA A,
B, C & D
18-0060
02-25-2021
C. QUINN
C. CARRAS
1/16" = 1'-0"
FIRE ALARM AND MNS PLAN - MAIN LEVEL - AREA A, B, C & D
SCALE IN FEET
0 8' 16' 32'
NOTES:
REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WALL MOUNTED NOTIFICATION DEVICES ARE PERMITTED IN UNFINISHED
AREAS WITH CONGESTED CEILINGS SUCH AS A MECHANICAL ROOM AND
HIGH-CEILING AREAS SUCH AS MAIN HALL AND ASSEMBLY.
REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING
PLANS.
1.
2.
3.
1 / FA101 - 2E
KEYED NOTES
1 EXTERIOR WP HORN STROBE OVER FDC.
2 PROVIDE RECESSED PANEL.
3 PROVIDE OUTPUT MODULE AND 24V POWER FOR MAGNETIC DOOR
HOLD OPEN DEVICES. REFER TO ARCHITECTURE DRAWING A-601
FOR DOOR HARDWARE INFORMATION.
4 PROVIDE 4" OCTOGONAL BOX FOR THE MANUAL PULL STATION
WHERE SHOWN ON THE PLANS AT 48" AFF. THE BOX SHALL HAVE
THE DEVICE MOUNTING SCREWS AT THE 2 AND 8 O'CLOCK
POSITIONS, AND 1/2" DIAMETER CONDUIT STUBBED STRAIGHT UP
TO 6" ABOVE THE FINISHED CEILING. NO BENDS OR ELBOWS ARE
PERMITTED IN THIS CONDUIT.
5 REFER TO FIRE SUPPRESSION DRAWINGS FOR QUANTITIES AND
LOCATIONS.
Revisions
ID Date Description
P
N A
C
A M
P
F A
B
C
2.6 3.6 4.8 5.4 7.6 8.6 9.2 9.8 10.6 10.8 11.6
LOCKERS
ELEC
157D
IT
157C
CONF
MECH
HEATED
STORAGE
CORR
OPEN OFFICE
F FF
F A
C U
A C
U
L O
C
PROVIDE CEILING MOUNTED SPEAKERS AND CLEAR STROBES
AS REQUIRED TO ACHIEVE DESIGN CRITERIA.
PROVIDE CEILING MOUNTED SPEAKERS AS REQUIRED
TO ACHIEVE DESIGN CRITERIA.
NOTIFICATION APPLIANCES ARE NOT REQUIRED .
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS, AS
REQUIRED TO ACHIEVE DESIGN CRITERIA.
FIRE ALARM HATCH LEGEND
NO HATCH
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS AND
STROBES TO ACHEIVE THE DESIGN CRITERIA.
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F''E'
'C' 'D'
'B' 'A'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA101-2E
FIRE ALARM AND
MNS PLAN - MAIN
LEVEL - AREA E &
F
18-0060
02-25-2021
C. QUINN
C. CARRAS
1/16" = 1'-0"
FIRE ALARM AND MNS PLAN - MAIN LEVEL - AREA E & F
NOTES:
REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WALL MOUNTED NOTIFICATION DEVICES ARE PERMITTED IN UNFINISHED
AREAS WITH CONGESTED CEILINGS SUCH AS A PUMP ROOM OR
MECHANICAL ROOM.
REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING
PLANS.
1.
2.
3.
SCALE IN FEET
0 8' 16' 32'
1 / FA101 - 2A
KEYED NOTES
1 PROVIDE RECESSED PANEL.
Revisions
5 FT (MIN)
12 INCHES
(MAX)FOR CEILING HEIGHTS LESS
THAN 96 INCHES THE VISIBLE
LENS MOUNTING HEIGHT
SHALL BE WITHIN 6 INCHES
OF THE CEILING
TO EXIT DOOR
5 FT (MAX)
INCHES
MAX
SYNCHRONIZE TWO
OR MORE
APPLIANCES IN ANY
FIELD OF VIEW
I
N C
H E
S
WALL MOUNTED
SMOKE DETECTOR
CEILING MOUNTED
SMOKE DETECTOR
SUPPLY OR
RETURN
DIFFUSER
CEILING
FINISHED FLOOR
WALL
MOUNTED
VISIBLE
APPLIANCE
MINIMUM 12 INCHES
FROM LIGHT SWITCH
(TYPICAL FOR FOAM
APPLIANCES)
PULL STATIONS SHALL NOT BE
LOCATED BEHIND DOOR SWINGS.
MAXIMUM DISTANCE BETWEEN SPEAKERS
SHALL NOT EXCEED 30 FEET,
UNLESS OTHERWISE NOTED.
DO NOT EXCEED A DISTANCE
OF 20 FEET, UNLESS
OTHERWISE NOTED.
60 INCHES
TO TOP
BATT BATT
NAC
NAC
AMP
AMP
BATT
FACU/
ACU
ROUTE CONDUIT TO ACHIEVE
SEPARATION OF POWER-
LIMITED FIRE ALARM CIRCUITS
AND POWER CIRCUITS
IN
S
T A
L L N
O G
R E
A T
E R
T
H A
N
I
N C
H E
S A
F F
DACT
F
FAA LOC
SS SS
CEILING MOUNTED
VISIBLE APPLIANCE
AUDIBLE
ONLY
WALL
MOUNTED
APPLIANCE
5 FT (MIN)
CARBON MONOXIDE
DETECTOR
WALL MOUNTED MAGNETIC
DOOR HOLDER. REFER TO ARCHITECTURAL
DRAWINGS FOR LOCATIONS.
WALL MOUNTED MAGNETIC
DOOR HOLDER. REFER TO ARCHITECTURAL
DRAWINGS FOR LOCATIONS.
FACU / ACU
FIRE ALARM
DEVICES
LOWER LEVER
MAIN LEVEL
IM IM
FIRE ALARM
DEVICES
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA501
FIRE ALARM
DETAILS
18-0060
02-25-2021
C. QUINN
C. CARRAS
NTS
TYPICAL MOUNTING DETAIL
NTS
CLASS B ISOLATION MODULE MOUNTING
Revisions
ID Date Description
FACU / ACU
NOTES:
KEYED NOTES:
S P
VS WF
F
BATT
SS
120 VAC
S
SS
NAC
BATT
SS
120 VAC
AMP
S
WP
2 2
CO
AOM
AOMS
S
RTS
RL
24 V FROM
VFD/STARTER
TO ENABLE
INPUT ON
VFD/STARTER
POWER CIRCUIT
VISIBLE NOTIFICATION APPLIANCE CIRCUIT (CLASS B)
AUDIBLE NOTIFICATION APPLIANCE CIRCUIT (CLASS B)
SIGNALING LINE CIRCUIT (CLASS B)
AIM
AIMAIMAIM
120 VAC 1 BATT
CIRCUIT LEGEND:
SYNCHRONIZATION
CIRCUIT TO NEXT NAC
PANEL
WP
INITIATING DEVICE CIRCUITS
WF 11
ST
AOM
RL
AIM
-120 VAC
RL
AIM
TO
PROTECTED
DEVICE
ESR
+120 VAC
FAA
LOC
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS, AND SYMBOLS.
2. THE FIRE ALARM RISER SHOWS THE INTENT OF THE
FIRE ALARM INFRASTRUCTURE. NOT ALL DEVICES
ARE SHOWN. CONTRACTOR SHALL PROVIDE THE
QUANTITY OF DEVICES AS REQUIRED TO COMPLY
WITH NFPA 72, UFC 3-600-01,UFC 4-021-01 AND
CONTRACT DOCUMENTS.
3. EACH FLOW AND TAMPER SWITCH SHALL REPORT
BACK TO THE FIRE ALARM CONTROL PANEL WITH A
SEPARATE ADDRESS. GROUPED SWITCHES ON ONE
ADDRESS ARE NOT ACCEPTABLE.
RED, LOCKABLE BREAKER LABELED "FIRE ALARM"
PROVIDED BY DIVISION 26. SEE ELECTRICAL PLANS
FOR ADDITIONAL INFORMATION.
QUANTITY AND LOCATION BY CONTRACTOR'S
DESIGN TO MEET DESIGN CRITERIA.
REFER TO FIRE SUPPRESSION DRAWINGS FOR
QUANTITY AND / OR LOCATIONS OF DEVICE(S).
REFER TO FIRE ALARM PLANS FOR QUANTITY AND /
OR LOCATIONS OF DEVICE(S).
PROVIDE ADDRESSABLE INPUT AND/OR OUTPUT
MODULE(S) AS REQUIRED TO ACHIEVE THE
FUNCTIONALITY INDICATED IN THE FIRE ALARM
MATRIX.
PROVIDE ADDITIONAL BOOSTER PANELS AS
REQUIRED PER CONTRACTOR'S DESIGN. WHERE
ADDITIONAL BOOSTER PANELS ARE REQUIRED,
LOCATE AS INDICATED ON PLAN.
PROVIDE ADDITIONAL AMPLIFIERS AS REQUIRED PER
CONTRACTOR'S DESIGN. WHERE ADDITIONAL
AMPLIFIERS ARE REQUIRED, LOCATE AS INDICATED
ON PLAN.
PROVIDE SUPPLY AND RETURN DUCT SMOKE
DETECTORS FOR DIRECT SHUT DOWN FOR THE
FOLLOWING UNITS: AHU-101, AHU-102, AHU-201,
AHU-203, AHU-204, AHU-205, AHU-206, AHU-207,
AUH-208, MAU-101, MAU-102, ERU-202, SHUTDOWN
THROUGH THE EMCS/DDC IS NOT PERMITTED.
REFERENCE MECHANICAL DRAWINGS FOR EXACT
LOCATION.
EXTERIOR WP HORN STROBE OVER FDC.
EXTERIOR WP FIRE ALARM / MASS NOTIFICATION
SPEAKERS.
24 VDC TO FACU OR NAC PANEL.
RELAY TO MONITOR INTEGRITY OF POWER SUPPLY.
RELAY TO ENABLE 120 VAC TO SHUNT TRIP
BREAKER.
ELEVATOR SHUNT TRIP BREAKER (BY DIVISION 26).
REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS.
PROVIDE INDICATING LIGHT AND SIGN NEAR HVAC
UNIT MODULE ON SMOKE DETECTION WHERE
INDICATING LIGHT ON THE SMOKE DETECTOR IS NOT
VISIBLE FROM FLOOR.
DESTRATIFICATION FAN SHUNT TRIP
(BY DIVISION 26). REFER TO ELECTRICAL DRAWINGS
FOR LOCATIONS.
PUBLIC ADDRESS PAGING INPUT. REFER TO T-403
FOR VOIP DEVICE AND ASSOCIATED ANALOG INPUT.
EXTERIOR WEATHER PROOF SPEAKER/STROBE
PROVIDED FOR ROOF TERRACE NOTIIFICATION.
EGRESS LIGHTING TO ACTIVATE UPON ACTIVATION
OF FIRE ALARM. REFER TO LIGHTING CONTROLS
MATRIX ON ELECTRICAL DRAWING E-711 FOR
REQUIRED LOCATIONS.
WF 11
STRL
AIM
-120 VAC
RL
AIM
TO
DESTRATIFICATION
FAN CONTROL
+120 VAC
LOWER LEVEL
UPPER LEVEL
MAIN LEVEL
MAIN LEVEL
S P
F
BATT
SS
120 VAC
S
NAC
BATT
SS
120 VAC
AMP
S WP
2 2
CO
AOM
AOMS
S/R
RTS
RL
24 V FROM
VFD/STARTER
TO ENABLE
INPUT ON
VFD/STARTER
AIM
AIM
15 11
SYNCHRONIZATION
CIRCUIT TO NEXT NAC
PANEL
PA 17DACT
AOM
EGRESS LIGHTING
SYSTEM
AIM
WC
AOM
DH
5 11
WP
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA601
FIRE ALARM
ONE-LINE
DIAGRAM
18-0060
02-25-2021
C. QUINN
C. CARRAS
Revisions
FIRE ALARM CONTROL UNIT (FACU) FUNCTIONAL MATRIX
ANNUNCIATION AT
LOCAL PANEL
NOTIFICATION AUXILIARY
FUNCTION
A U
D
IO
-V
IS
IB
L E
F
IR
E A
L A
M
IN
D
IC
A T
IO
N
B Y
D E
V
IC
E
A U
D
IO
-V
IS
IB
L E
T R
O U
B L E
I N
D
IC
A T
IO
N
B
Y D
E V
IC
E
A U
D
IO
-V
IS
IB
L E
S U
P E
R V
IS
O
IC
A T
IO
N
B Y
D E
V
IC
E
M A
N U
A L P
U L L S
T A
T
IO
N A
L A
R M
S
IG
N A
L
O
C E
N T
R A
L S
T A
T
IO
C
M M
O N
T R
O U
B L E
S
IG
N A
L
C
N T
R A
L S
T A
T
IO
N
C O
M M
O N
S U
P E
R V
IS
O
R Y
S
IG
N
C E
N T
R A
L S
T A
T
IO
N
S H
U T
-D O
W N
A S
S O
C
IA
T E
D
IR
N D
L
IN
G E
Q U
IP
M
E N
T
E L E
V A
T O
R R
E C
A L L T
O P
R
IM
A
C A
L L F
L O
O R
E L E
V A
T O
R R
E C
A L L T
O S
E C
O N
D A
C
A L L F
L O
O R
IN
IT
IA
T
E E
L E
V A
T O
R S
H U
N T
T
IP
ALARM SIGNALS
MANUAL FIRE ALARM STATIONS
SMOKE DETECTOR OVER FACU, AMPS AND NAC PANELS
FLOW SWITCHES - WET-PIPE SYSTEM
SMOKE DETECTION - ELEVATOR MAIN FLOOR LOBBY
SMOKE DETECTION - ELEVATOR LOWER LEVEL
SMOKE DETECTION - ELEVATOR EQUIPMENT ROOM
AC POWER FAILURE
LOW BATTERY
OPEN CIRCUIT FAULT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
TROUBLE SIGNALS
COMPONENT COMMON TROUBLE
SUPERVISORY SIGNALS
COMPONENT COMMON SUPERVISORY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
F
IR
E A
L A
R M
/M N
S V
IS
IB
T
IF
IC
A T
IO
N
M A
S S
N O
T
IF
IC
A
T
IO
N O
V E
R R
ID
E
S
IG
N
F
IR
E S
Y S
T E
M C
O N
T R
O L P
A N
E L
M A
S S
N O
T
IF
IC
A
T
IO
N A
N N
O U
N C
E M
E N
T
F
IR
E A
L A
R M
A U
D
IB
L E
N O
T
IF
IC
A
T
IO
N
S
IL
E N
C E
G E
N E
R A
L F
IR
E
A L A
N
O U
N C
E M
E N
T
X
X
X
X
X
X
KITCHEN HOOD SUPPRESSION X
X
X
X
X
X
X
D
IS
A B
L E
P U
B L
IC
A D
D R
E S
S S
Y S
T E
M
X
X
X
X
X
X
IN-DUCT SMOKE DETECTORS XX X X
XMASS NOTIFICATION INPUT (LOCAL) XX X X X
GENERAL VALVE SUPERVISORY X X
IN
IT
IA
T
E D
E S
T R
A T
IF
IC
A T
IO
N
F
U N
T T
R
IP
X
IN
IT
IA
T
E F
L A
S H
IN
G
R E
D H
A T
S
IG
N
L E
V A
T O
R
IN
IT
IA
T
E S
O L
ID
S T
A T
E R
E D
H
IG
N A
L I
N E
L E
V A
T O
R
X
X
X S
M O
K E
D E
T E
C T
IO
N
A L A
R M
S
IG
N
C E
N T
R A
L S
T A
T
IO
N
X
X
X
X
F
IR
E S
U P
P R
E S
S
IO
N A
C T
IV
A
T
IO
N A
L A
N
A L T
O C
E N
T R
A L S
T A
T
IO
N
C A
R B
O N
M O
N O
X
ID
E A
L A
R M
S
IG
N A
L T
O C
E N
T R
A L S
T A
T
IO
N
X
XCARBON MONOXIDE DETECTORS X
XXX
P U
B L
IC
A D
D R
E S
S A
N N
O U
N C
E M
E N
T O
V
F
IR
E A
L A
R M
M
N S
S P
E A
K E
R S
PUBLIC ADDRESS PAGING VIA VOIP PHONE SYSTEM X
X
R E
L E
A S
E H
O L D
-O P
E N
D E
V
IC
E
O R
S
C A
R B
O N
M O
N
IX
ID
E
A N
N O
U N
C E
M E
N T
X
FLOW SWITCHES - ELEVATOR EQUIPMENT ROOM X
SMOKE DETECTORS - FIRE DOOR HOLD - OPEN XX X X X X
X X
X
X
A C
T
IV
A T
E E
M E
R G
E N
C Y
E G
R E
H T
IN
G
X
X
X
X
X
X
X
X
MASS NOTIFICATION MESSAGES SHALL BE A FEMALE
VOICE AND STATE THE FOLLOWING. MASS NOTIFICATION MESSAGES ARE
LISTED IN ORDER OF PRIORITY. COORDINATE FINAL MESSAGES WITH BASE.
1. (TEMPORAL THREE ALERT TONE)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. A FIRE EMERGENCY HAS OCCURRED; PLEASE LEAVE THE
BUILDING BY THE NEAREST EXIT DO NOT USE THE ELEVATORS."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
2. (TEMPORAL FOUR ALERT TONE)
<TWO ROUNDS>
"MAY I HAVE YOU ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. CARBON MONOXIDE HAS BEEN DETECTED IN THE BUILDING.
PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT."
<PAUSE 2 SECONDS> REPEAT MESSAGE
3. (A HORN IS PLAYED FOR 4 SECONDS)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. A BOMB THREAT HAS BEEN REPORTED IN THE BUILDING.
PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT DO NOT USE THE
ELEVATORS."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
4. (A HORN IS PLAYED FOR 4 SECONDS)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. AN INTRUDER OR HOSTILE PERSON HAS BEEN REPORTED IN
THE BUILDING. PLEASE SEEK A DESIGNATED SAFE LOCATION
IMMEDIATELY."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
5. (A HORN IS PLAYED FOR 4 SECONDS)
<TWO ROUNDS>
"MAY I HAVE YOU ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. PLEASE SEEK A DESIGNATED SAFE LOCATION IMMEDIATELY"
<PAUSE 2 SECONDS> REPEAT MESSAGE
6. (A HORN IS PLAYED FOR 4 SECONDS)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
7. (A HORN IS PLAYED FOR 8 SECONDS)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. A WEATHER EMERGENCY HAS BEEN REPORTED IN THE
AREA. PLEASE SEEK A DESIGNATED SAFE LOCATION IMMEDIATELY;
DO NOT USE THE ELEVATORS."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
8. (A HORN IS PLAYED FOR 4 SECONDS)
<ONE ROUND>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION
PLEASE. THE EMERGENCY HAS BEEN RESOLVED; RETURN TO
NORMAL OPERATIONS."
<PAUSE 2 SECONDS> REPEAT MESSAGE
9. (A HORN IS PLAYED FOR 8 SECONDS)
<ONE ROUND>
"TEST, TEST, TEST, THIS IS AN EMERGENCY NOTIFICATION AUDIO
SYSTEM TEST; YOU MAY CONTINUE NORMAL OPERATIONS, TEST,
TEST, TEST."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
10. SPARE - NO MESSAGE
MASS NOTIFICATION MESSAGES
NOTES:
REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1.
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA602
FIRE ALARM
MATRIX
18-0060
02-25-2021
C QUINN
C. CARRAS
Revisions
PROVIDE CEILING MOUNTED SPEAKERS AND CLEAR STROBES
AS REQUIRED TO ACHIEVE DESIGN CRITERIA.
PROVIDE CEILING MOUNTED SPEAKERS AS REQUIRED
TO ACHIEVE DESIGN CRITERIA.
NOTIFICATION APPLIANCES ARE NOT REQUIRED .
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS, AS
REQUIRED TO ACHIEVE DESIGN CRITERIA.
FIRE ALARM HATCH LEGEND
NO HATCH
PROVIDE WEATHERPROOF WALL MOUNTED SPEAKERS AND
STROBES TO ACHEIVE THE DESIGN CRITERIA.
F
F
A
B
C
E
D.9
C.5
B.1
11.6
F
F
GPTB BAY
Office
Office
Corridor 7C
F
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F'
'D'
'B'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FA901-1F
FIRE ALARM AND
MNS PLAN -
LOWER LEVEL -
AREA F - OPTION
18-0060
02-25-2021
C. QUINN
C. CARRAS
NOTES:
REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WALL MOUNTED NOTIFICATION DEVICES ARE PERMITTED IN UNFINISHED
AREAS WITH CONGESTED CEILINGS SUCH AS A PUMP ROOM OR
MECHANICAL ROOM.
REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING
PLANS.
1.
2.
3.
0 4' 8' 16'1/8" = 1'-0"
FIRE ALARM AND MNS PLAN - LOWER LEVEL - OPTION 1
Revisions
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AS AUTOMATIC SPRINKLER
FP FIRE PROTECTION
FM FIRE MAIN
(M) MECHANICALLY SUPERVISED
NC NORMALLY CLOSED
NO NORMALLY OPEN
RCP REFLECTED CEILING PLAN
RN RISER NIPPLE
(S) ELECTRICALLY SUPERVISED
SQ FT SQUARE FOOT
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
PRESSURE RELIEF VALVE
OUTSIDE SCREW AND YOKE
VALVE (OS&Y)
VALVE
DOUBLE CHECK BACKFLOW
PREVENTER
INDICATING BUTTERFLY VALVE
FLOW TEST HEADER
CHECK VALVE
PIPE CAP
AUTOMATIC DRAIN VALVE
FIRE DEPARTMENT
CONNECTION
PRESSURE GAUGE
SIGHT GLASS
FLOW SWITCH
FIRE SUPPRESSION LEGEND
FIRE SUPPRESSION ABBREVIATIONS
FIRE SUPPRESSION DESIGN CRITERIA
FIRE SUPPRESSION GENERAL NOTES
DRAIN PIPING
PIPING SYMBOLS / LINE DESIGNATION
THRUST BLOCK
AUTOMATIC AIR RELEASE
VALVE
RISER LOCATION
HAZARD CLASSIFICATION
NOTE 1: PROVIDE 200 ºF RATED SPRINKLERS IN MECHANICAL, ELECTRICAL, VEHICLE MAINTENANCE BAY AND COMMUNICATION ROOMS.
NOTE 2: UPRIGHT SPRINKLER FINISH TO BE BRASS.
NOTE 3: DRY SIDEWALL SPRINKLERS SHALL BE BRASS, 200ºF, ORDINARY HAZARD
NOTE 4: PROVIDE GUARD FOR SPRINKLER IN ELEVATOR MACHINE ROOM AND ELEVATOR PIT.
NO HATCH
MARK
WET
SYSTEM
TYPE
WET
REMOTE
AREA
SQ FT
HOSE
DEMAND
GPM
TEMP
RATING (ºF)
TYPE
(CEILINGS)
ORDINARY
ORDINARY
QUICK RESPONSE
CONCEALED
QUICK RESPONSE
UPRIGHT
NOTES
1, 2, 3, 4
0.10
DENSITY
GPM/SF
0.20
MAXIMUM AREA
PER HEAD
SQ FT
LIGHT HAZARD
ORDINARY HAZARD
ADDITIONAL CODE
REFERENCE
SPRINKLER CHARACTERISTICS
K-FACTOR FINISH
5.6 OR 8.0
8.0
WHITE
FIRE SUPPRESSION SYSTEM
WET SYSTEM
ELBOW UP OR DOWN
TEE UP OR DOWN
SYSTEM PIPING
1. SERVE THE FIRE SUPPRESSION SYSTEM FROM THE
EXISTING DOMESTIC SYSTEM. PERFORM A HYDRANT
FLOW TEST, AND INCORPORATE THIS TEST INTO THE
HYDRAULIC CALCULATIONS. HYDRANT FLOW TESTING
SHALL BE IN ACCORDANCE WITH NFPA 291, AND THE
RESULTS OF THE TESTING SHALL BE SUBMITTED AS
INDICATED IN NFPA 291 FIGURE 4.11.2.
FOR INFORMATION ONLY: FLOW TEST 1
DATE 01/13/2021
STATIC 96 PSI
RESIDUAL 80 PSI
FLOW 1277 GPM
FLOW HYDRANT LOCATION: NORTH AT DEAD END.
GAUGE HYDRANT LOCATION: 770 FT NORTH OF
CAPEHART ROAD ON 25TH ST.
2. INCLUDE A 10% OR 5 PSI SAFETY FACTOR IN THE
HYDRAULIC CALCULATIONS, WHICHEVER IS GREATER.
3. THE FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED
AND INSTALLED BY A LICENSED / CERTIFIED COMPANY
WHERE EMPLOYEES ARE LICENSED / CERTIFIED TO
INSTALL FIRE PROTECTION EQUIPMENT IN THE STATE OF
NEBRASKA.
4. ALL COMPONENTS AND ASSEMBLIES USED IN THIS FIRE
PROTECTION SYSTEM MUST BE SPECIFICALLY UL LISTED
OR FM APPROVED FOR THEIR INTENDED USE.
5. USE SCHEDULE 40 BLACK STEEL FIRE WATER PIPING ON
THIS PROJECT. PROVIDE PIPING MATERIAL SUITABLE
FOR USE IN POTABLE WATER SYSTEMS IN COMPLIANCE
WITH THE INTERNATIONAL PLUMBING CODE AND LOCAL
JURISDICTION PRIOR TO THE BACKFLOW PREVENTER.
1. PROVIDE ALL NECESSARY COMPONENTS FOR A WET-PIPE
SYSTEM IN THE READINESS CENTER. AT A MINIMUM
PROVIDE COMPONENTS AS INDICATED ON THESE
DRAWINGS. PROVIDE ADDITIONAL COMPONENTS AND
MODIFICATIONS AS REQUIRED TO PROVIDE A FULLY
FUNCTIONING FIRE SUPPRESSION SYSTEM.
2. THE FIRE SUPPRESSION SYSTEM SHALL BE SUPPLIED
FROM THE NEW DEDICATED INCOMING FIRE MAIN. REFER
TO CIVIL DRAWINGS.
3. COORDINATE ALL REQUIRED SYSTEMS TO THE
SATISFACTION OF THE ENGINEER AND AUTHORITY
HAVING JURISDICTION. CORRECT ANY DEFICIENCIES,
INCONSISTENCIES, OR POORLY COORDINATED
INSTALLATIONS AT NO ADDITIONAL COST.
4. FINAL DESIGN REQUIREMENTS (DEVICE QUANTITY, SIZE,
AND LOCATIONS) ARE THE SOLE RESPONSIBILITY OF THE
FIRE SUPPRESSION CONTRACTOR. DRAWINGS INDICATE
MINIMUM REQUIREMENTS; VERIFY AND COORDINATE
FINAL DESIGN REQUIREMENTS WITH THESE
CONSTRUCTION DOCUMENTS, SPECIFICATIONS,
REFERENCE DOCUMENTS, APPLICABLE CODES, AND
FACILITY USER REQUIREMENTS.
5. ALL DRAIN PENETRATIONS THROUGH EXTERIOR WALL
SHALL BE NO GREATER THAN 2'-0" ABOVE FINISHED
GRADE.
6. INSTALL FIRE PROTECTION PIPE HANGERS PER THE
FOLLOWING LIMITATIONS:
A. THE SINGLE POINT DEAD LOAD APPLIED TO ANY
STRUCTURAL MEMBER SHALL NOT EXCEED 300 LBS.
PROVIDE TRAPEZE HANGERS TO DISTRIBUTE THE
LOAD BETWEEN STRUCTURAL MEMBERS WHERE A
SINGLE HANGER EXCEEDS THE LIMITATIONS.
B. SIX INCH DIAMETER PIPE ROUTED PERPENDICULAR
TO JOISTS SHALL BE SUPPORTED AT A JOIST PANEL
POINTS.
C. SIX INCH DIAMETER PIPE ROUTED PERPENDICULAR
TO JOISTS SHALL BE SUPPORTED ON ALTERNATE
JOISTS.
7. ALL VALVES INCLUDING CONTROL AND TRIM VALVES
SHALL BE WITHIN 6'-0" AFF.
TYPE
(EXPOSED)
QUICK RESPONSE
UPRIGHT
QUICK RESPONSE
CONCEALED
SPRINKLER SYSTEM BOUNDARY
1, 2
WHITE
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX001
FIRE
SUPPRESSION
NOTES, LEGEND
AND
ABBREVIATIONS
18-0060
02-25-2021
C. QUINN
C. CARRAS
Revisions
HAZARD
CLASSIFICATION
HAZARD SCHEDULE
LIGHT HAZARD CEILING
HEIGHT
NO HATCH
MARK
ORDINARY HAZARD
SPRINKLER FEED
MAIN FROM ABOVE2
A
B
C
E
F
G
H
L
N
P
K.5
J.9
H.9
G.5
F.3
D.9
C.5
B.1
9.2 9.8 10.6 10.8 11.6
8.7 9.7
10.5
11 12
CORR
RECEIVING
ELEV EQUIP
CST STORAGE
STAIR
CONF
CST LOG / ADMIN
08A
MECH
ELEC
GROUNDS &
MAINTENANCE
FLAMMABLE
STORAGE
IT
CST READY
BAYS
CUST
TOILET
TOILET
OFFICE
36A
CST SURVEY
CST COMMO
OFFICE
29A
CST MED
SUPPORT
OFFICE
28A
CST MED STOR
36B
IT
ELEC
CST
OPERATIONS
OFFICE
29B
OFFICE
28B
CST COMMAND
OFFICE
28C
MECH
TRAINING AID
STORAGE
29C
PLUMBING
CHASE
30E
CORRIDOR
7B
CORR
STAIR
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F'
'D'
'B'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX101-1A
FIRE
SUPPRESSION
PLAN - LOWER
LEVEL - OVERALL
18-0060
02-25-2021
C. QUINN
C. CARRAS
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
MINIMUM NUMBER OF LOW POINT DRAINS INDICATED
ON DRAWINGS. PROVIDE ADDITIONAL LOW POINT
DRAINS AS REQUIRED BY NFPA-13.
PROVIDE AIR VENTS AT HIGH POINT OF EACH
SPRINKLER SYSTEM. PROVIDE DRAINS TO DISCHARGE
TO EXTERIOR.
COORDINATE SPRINKLER LOCATIONS WITH REFLECTED
CEILING PLANS. REFER TO ARCHITECTURAL DRAWINGS
FOR REFLECTED CEILING PLANS.
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK
OBSTRUCTIONS IN ROOMS NOT PROVIDED WITH A
CEILING IN ACCORDANCE WITH NFPA-13
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS
FOR DUCTWORK LOCATIONS.
1.
1/16" = 1'-0"
FIRE SUPPRESSION PLAN - LOWER LEVEL - OVERALL
SCALE IN FEET
0 8' 16' 32'
KEYED NOTES:
INSTALL SPINKLERS UNDER OVERHEAD DOORS PER
NFPA 13
PROVIDE SPRINKLERS IN ELEVATOR PIT PER DETAIL 3
ON SHEET FX601
PROVIDE SPRINKLER CONTROL VALVE PER DETAIL 4
ON SHEET FX601
SPRINKLER PIPE ROUTING IN CORRIDOR SHALL AVOID
ONE-FOOT CLEARANCE ABOVE CABLE TRAY.
2.
3.
4.
5.
Revisions
11/17/2020 02/25/2021
WC
SYSTEM 2
SYSTEM 1
SYSTEM 3
C
E
F
G
H
J
K
L
M
N
N.5
P
Q
R
K.5
J.9
H.9
G.5
F.3
D.9
C.5
2.6 3.6 4.8 5.4 7.6 8.6 9.8 10.6 10.8 11.6
1 2 3
3.5
4 5
5.1
5.9
6.7
7.7
8.7 9.7
10.5
11 12
ASSEMBLY
CLASSROOM/
LECTURE
FAMILY
READINESS
RECRUITING
LEARNING
CENTER
DISPLAY
101A
LACTATION
LOCKERS
CLASSROOM
BREAK /
VENDING
CLASSROOM
TRAINING
VEST
MECH / WATER
SERVICE
ANTE
105A
ANTE
105B
PHYSICAL
FITNESS
MEN
WOMEN
ISSUING
BEVERAGES
158B
MEDICAL
TABLE / CHAIR
STORAGE
104A
KITCHEN
160 SERVING
158A
LOBBY / MAIN
HALL
CORR
CORR
ELEC
IT
VAULT
153A
ARMORER
ISSUING
ISSUING
152.1
WOMEN
LOCKERS
108A
MEN LOCKERS
110A
MECH
ELEC
CUST
IT
PANTRY /
OFFICE
160D
CUST
160C
TOILET
160B
SCULLERY
160A
CORR
157B
CORR
157A
CORR
CORR
101CALCOVE
101B
ALCOVE
101D
LIFT EQUIP
105C
MEN SHOWERS
110B
WOMEN
SHOWERS
108B
TOILET
CONF
OFFICE
OFFICE
WORK RM
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CONF
OFFICE
OFFICE
MECH
WORK RM
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PLUMBING
CHASE
109C
PLUMBING
CHASE
111C
PLUMBING
CHASE
30D
ISSUING
157E
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORR
101E
ELEV LOBBY /
STAIR
101F
HEATED
STORAGE
FX601
ELEV: 94' 2"
HEATED
STORAGE
HAZARD
CLASSIFICATION
HAZARD SCHEDULE
LIGHT HAZARD CEILING
HEIGHT
NO HATCH
MARK
ORDINARY HAZARD
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F''E'
'C' 'D'
'B' 'A'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX101-2A
FIRE
SUPPRESSION
PLAN - MAIN
LEVEL - AREA A,
B, C & D
18-0060
02-25-2021
C. QUINN
C. CARRAS
1/16" = 1'-0"
FIRE SUPPRESSION PLAN - MAIN LEVEL - AREA A, B, C & D
KEYED NOTES:
FIRE PROTECTION RISER DOWN TO LOWER LEVEL
ROUTE FEED MAINS FOR STAIRWELL RISERS ABOVE
CEILING IN CORRIDOR.
PROVIDE SPRINKLER COVERAGE IN THE MAIN HALL
IN ACCORDANCE WITH NFPA 13 TABLE 9.2.7.1.
WET CHEMICAL SUPPRESSION SYSTEM FOR
COOKING APPLIANCES PROVIDED BY KITCHEN HOOD
SUBCONTRACTOR.
PROVIDE LOW POINT DRAIN. PROVIDE CAPPED
DRAIN CONNECTION LOCATED IN MECHANICAL ROOM
107.
PROVIDE LOW POINT DRAIN DISCHARGE TO MOP
SINK LOCATED IN CUSTODIAN CLOSET.
REDUCE PIPE SIZE TO 4" PRIOR TO ENTERING
COLUMN ENCLOSURE. ENLARGE PIPE SIZE AFTER
EXITING COLUMN ENCLOSURE AS REQUIRED TO
MEET HYDRAULIC REQUIREMENTS. COORDINATE
REQUIRED OPENING IN PRECAST WALL PANEL FOR
PIPE EXITING COLUMN ENCLOSURE FOR
INSTALLATION OF FITTINGS AND COUPLINGS.
REFER TO CIVIL PLANS FOR CONTINUATION.
SCALE IN FEET
0 8' 16' 32'
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
MINIMUM NUMBER OF LOW POINT DRAINS INDICATED
ON DRAWINGS. PROVIDE ADDITIONAL LOW POINT
DRAINS AS REQUIRED BY NFPA-13.
PROVIDE AIR VENTS AT HIGH POINT OF EACH
SPRINKLER SYSTEM. PROVIDE DRAINS TO DISCHARGE
TO EXTERIOR.
REFER TO ARCHITECTURE DRAWINGS FOR REFLECTED
CEILINGS. COORDINATE ALL SPRINKLER LOCATIONS
WITH CEILING AND OBSTRUCTIONS
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK
OBSTRUCTIONS IN ROOMS NOT PROVIDED WITH A
CEILING IN ACCORDANCE WITH NFPA-13
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS
FOR DUCTWORK LOCATIONS.
VARIATION IN ROUTING OF FEED MAINS SHALL BE
APPROVED BY THE ARCHITECT.
1.
2.
3.
4.
5.
6.
1 / FX101 - 2E
Revisions
HAZARD
CLASSIFICATION
HAZARD SCHEDULE
LIGHT HAZARD CEILING
HEIGHT
NO HATCH
MARK
ORDINARY HAZARD
A
B
C
B.1
2.6 3.6 4.8 5.4 7.6 8.6 9.2 9.8 10.6 10.8 11.6
ELEC
157D
IT
157C
LOCKERS
CORR
MECH
OPEN OFFICE
HEATED
STORAGE
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F''E'
'C' 'D'
'B' 'A'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX101-2E
FIRE
SUPPRESSION
PLAN - MAIN
LEVEL - AREA E &
F
18-0060
02-25-2021
C. QUINN
C. CARRAS
1/16" = 1'-0"
FIRE SUPPRESSION PLAN - MAIN LEVEL - AREA E & F
SCALE IN FEET
0 8' 16' 32'
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
COORDINATE SPRINKLER LOCATIONS WITH REFLECTED
CEILING PLANS. REFER TO ARCHITECTURAL DRAWINGS
FOR REFLECTED CEILING PLANS.
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK
OBSTRUCTIONS IN ROOMS NOT PROVIDED WITH A
CEILING IN ACCORDANCE WITH NFPA-13
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS
FOR DUCTWORK LOCATIONS.
VARIATION IN ROUTING OF FEED MAINS SHALL BE
APPROVED BY THE ARCHITECT.
REFER TO ARCHITECTURE DRAWINGS FOR REFLECTED
CEILINGS. COORDINATE ALL SPRINKLER LOCATIONS
WITH CEILING AND OBSTRUCTIONS.
1.
KEYED NOTES:
PROVIDE DRY SIDEWALL SPRINKLERS TO PROTECT
AREA UNDER DOCK CANOPY.
1 / FX101 - 2A
2.
3.
4.
5.
Revisions
SYSTEM
2 LOWER
LEVEL
27,327 SQ FT
A
B
C
E
F
G
H
L
N
P
Q
K.5
J.9
H.9
G.5
F.3
D.9
C.5
B.1
7.6 8.6 9.2 9.8 10.6 10.8 11.6
6.7
7.7
8.7 9.7
10.5
11 12
(INCLUDING OPTION 1)
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F'
'D'
'B'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX111-1A
SPRINKLER
BOUNDARIES -
LOWER LEVEL -
OVERALL
18-0060
02-25-2021
C. QUINN
C. CARRAS
1/16" = 1'-0"
LOWER LEVEL - OVERALL
SCALE IN FEET
0 8' 16' 32'
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
COORDINATE SPRINKLER LOCATIONS WITH REFLECTED
CEILING PLANS. REFER TO ARCHITECTURAL DRAWINGS
FOR REFLECTED CEILING PLANS.
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK
OBSTRUCTIONS IN ROOMS NOT PROVIDED WITH A
CEILING IN ACCORDANCE WITH NFPA-13
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS
FOR DUCTWORK LOCATIONS.
VARIATION IN ROUTING OF FEED MAINS SHALL BE
APPROVED BY THE ARCHITECT.
REFER TO ARCHITECTURE DRAWINGS FOR REFLECTED
CEILINGS. COORDINATE ALL SPRINKLER LOCATIONS
WITH CEILING AND OBSTRUCTIONS
SPRINKLER SYSTEM BOUNDARY INCLUDES FLOOR
AREA OF ALL ABI'S.
1.
2.
3.
4.
5.
6.
KEYED NOTES
1 PROVIDED AS PART OF OPTION 1. REFER TO
FX901-1F.
Revisions
ID Date Description
SYSTEM
1 MAIN
LEVEL
SYSTEM 3
MAIN LEVEL,
SOUTH
WING
43,000 SQ FT
32,000 SQ FT
A
B
C
E
F
G
H
J
K
L
M
N
N.5
P
Q
R
K.5
J.9
H.9
G.5
F.3
D.9
C.5
B.1
2.6 3.6 4.8 5.4 7.6 8.6 9.2 9.8 10.610.8 11.6
1 2 3
3.5
4 5
5.1
5.9
6.7
7.7
8.7 9.7
10.5
11 12
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F''E'
'C' 'D'
'B' 'A'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX111-2A
SPRINKLER
BOUNDARIES -
MAIN LEVEL -
OVERALL
18-0060
02-25-2021
C. QUINN
C. CARRAS
1" = 20'-0"
MAIN LEVEL - OVERALL
SCALE IN FEET
0 20' 40'10'
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
COORDINATE SPRINKLER LOCATIONS WITH REFLECTED
CEILING PLANS. REFER TO ARCHITECTURAL DRAWINGS
FOR REFLECTED CEILING PLANS.
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK
OBSTRUCTIONS IN ROOMS NOT PROVIDED WITH A
CEILING IN ACCORDANCE WITH NFPA-13
REQUIREMENTS. REFER TO MECHANICAL DRAWINGS
FOR DUCTWORK LOCATIONS.
VARIATION IN ROUTING OF FEED MAINS SHALL BE
APPROVED BY THE ARCHITECT.
REFER TO ARCHITECTURE DRAWINGS FOR REFLECTED
CEILINGS. COORDINATE ALL SPRINKLER LOCATIONS
WITH CEILING AND OBSTRUCTIONS.
SPRINKLER SYSTEM BOUNDARY INCLUDES FLOOR
AREA OF ALL ABI'S.
1.
2.
3.
4.
5.
6.
Revisions
FROM HEADER
DRAIN TO
EXTERIOR
TO WET
SYSTEM
AUTOMATIC AIR
VENT LOCATED AT
HIGH POINT IN
SYSTEM.
INSPECTOR'S
TEST
MAIN DRAIN
PRESSURE
RELIEF
VALVE
(SET AT
175 PSI)
FROM SPRINKLER SYSTEM (S)
ELEV. MACHINE ROOM
TO RISER MAIN DRAIN
OR OTHER EXTERIOR
LOCATION
INSPECTORS TEST VALVE
TO SPRINKLER
LOWER LEVEL
FROM LOWER LEVEL
SPRINKLER LINE
M
A X
SIDEWALL SPRINKLER
S
(S)
T O
W E
T S
Y S
T E
M
(S)
(S)
AUXILIARY DRAIN VALVESPLASH BLOCK FLANGED CONNECTION
MAIN DRAIN
EXTERIOR WALL 1
FX601
BY DIVISION 21
T O
W E
T S
Y S
T E
M
(S)
T O
W E
T S
Y S
T E
M
(S)
(S
N C
FX601
FX601
BY DIVISION 33
2.6
Exterior Wall
FDC
TEST
HEADER
DOUBLE CHECK BACKFLOW
PREVENTER
BUTTERFLY
VALVE
TO WET SYSTEM 3 TO WET SYSTEM 2
TO WET SYSTEM 1
BUTTERFLY VALVE INSTALLED
IN VERTICAL (TYP.)
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:0
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX601
FIRE
SUPPRESSION
RISER, DETAILS,
AND ENLARGED
PLANS
18-0060
02-25-2021
C. QUINN
C. CARRAS
NTS
WET RISER DETAIL
NTS
ELEVATOR MACHINE ROOM SECTION DETAIL
NTS
ELEVATOR PIT SPRINKLER DETAIL
NTS
WET RISER ROOM DETAIL
1/2" = 1'-0"
MECH/WATER SERVICE - ROOM 156 PLAN
0 1' 2' 4'
Revisions
A
B
C
E
F
F.3
D.9
C.5
B.1
11.6
GPTB BAY
Office
Office
Corridor 7C
Hall
HAZARD
CLASSIFICATION
HAZARD SCHEDULE
LIGHT HAZARD CEILING
HEIGHT
NO HATCH
MARK
ORDINARY HAZARD
SHEET NUMBER
SHEET TITLE
CLIENT INFORMATION
PROJECT INFORMATION
JOB #
ISSUE DATE
Checked by Drawn by
Davis Design All Rights Reserved
E a s t
M a in
S u it e
V e rm ill io n S
D
P h o n e
-6
-1
V e rm il li o n
N S tr e e t, S u it e
L in c o ln N
E
P h o
-4
-9
F a x
-4
-9
L in c o ln L in c o ln
N th
S tr e e t, S u it e
O m a h a
N E
-4
-3
W a rd
P a rk w a y
K a n s a s C it y
M O
-3
-9
'F'
'D'
'B'
C
R e v it
P ro je c t s \1
F
C e n tr a l_ c ca rr a s b u rn s m c d
.c o m .r v t
/2
/2
:2
:1
A
M
Nebraska Army National Guard
BELLEVUE
READINESS
CENTER
S. 25th and Capehart Rd., Bellevue, NE
FX901-1F
FIRE
SUPPRESSION
PLAN - LOWER
LEVEL - AREA F -
OPTION 1
18-0060
02-25-2021
C. QUINN
C. CARRAS
NOTES:
REFER TO FX001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
MINIMUM NUMBER OF LOW POINT DRAINS INDICATED ON DRAWINGS.
PROVIDE ADDITIONAL LOW POINT DRAINS AS REQUIRED BY NFPA-13.
PROVIDE AIR VENTS AT HIGH POINT OF EACH SPRINKLER SYSTEM.
PROVIDE DRAINS TO DISCHARGE TO EXTERIOR.
COORDINATE SPRINKLER LOCATIONS WITH REFLECTED CEILING PLANS.
REFER TO ARCHITECTURAL DRAWINGS FOR REFLECTED CEILING
PLANS.
COORDINATE SPRINKLER LOCATIONS WITH DUCTWORK OBSTRUCTIONS
IN ROOMS NOT PROVIDED WITH A CEILING IN ACCORDANCE WITH
NFPA-13 REQUIREMENTS. REFER TO MECHANICAL DRAWINGS FOR
DUCTWORK LOCATIONS.
KEYED NOTES:
INSTALL SPRINKLERS UNDER OVERHEAD DOORS PER NFPA 13.1
1.
2.
3.
4.
5.
1/8" = 1'-0"
FIRE SUPPRESSION PLAN - LOWER LEVEL - OPTION 1
0 4' 8' 16'
Revisions
| FIRE PROTECTION |
| FA001 - FIRE ALARM NOTES, LEGEND AND ABBREVIATIONS |
| FA101-1A - FIRE ALARM AND MNS PLAN - LOWER LEVEL - OVERALL |
| FA101-2A - FIRE ALARM AND MNS PLAN - MAIN LEVEL - AREA A, B, C & D |
| FA101-2E - FIRE ALARM AND MNS PLAN - MAIN LEVEL - AREA E & F |
| FA501 - FIRE ALARM DETAILS |
| FA601 - FIRE ALARM ONE-LINE DIAGRAM |
| FA602 - FIRE ALARM MATRIX |
| FA901-1F - FIRE ALARM AND MNS PLAN - LOWER LEVEL - AREA F - OPTION 1 |
| FX001 - FIRE SUPPRESSION NOTES, LEGEND AND ABBREVIATIONS |
| FX101-1A - FIRE SUPPRESSION PLAN - LOWER LEVEL - OVERALL |
| FX101-2A - FIRE SUPPRESSION PLAN - MAIN LEVEL - AREA A, B, C & D |
| FX101-2E - FIRE SUPPRESSION PLAN - MAIN LEVEL - AREA E & F |
| FX111-1A - SPRINKLER BOUNDARIES - LOWER LEVEL - OVERALL |
| FX111-2A - SPRINKLER BOUNDARIES - MAIN LEVEL - OVERALL |
| FX601 - FIRE SUPPRESSION RISER, DETAILS, AND ENLARGED PLANS |
| FX901-1F - FIRE SUPPRESSION PLAN - LOWER LEVEL - AREA F - OPTION 1 |