ATTACHMENT - VOLUME 9A_Plumbing Updated 07.11.13-3.pdf
PDF 892 KB Posted
- Solicitation number
- 36C24825R0025-0001
About this file
This is a plumbing plan drawing for Level 1 Area E2 showing an alternate design (#2) for a VA hospital/clinic facility. The drawing, at a scale of 1/8" = 1'-0", details plumbing layouts including roof drainage systems, sanitary lines, vent pipes, and water supply lines throughout various hospital spaces including VRE offices, exam rooms, treatment areas, corridors, and public facilities.
The plan indicates specific plumbing specifications including 15" secondary roof drainage systems servicing 44,751 SF and 38,320 SF areas, 8" sanitary lines handling up to 632 fixture units, and various water supply lines ranging from 3/4" to 2" in diameter. The drawing contains multiple room labels and numbers, plumbing fixture designations (P-series numbers), and detailed annotations for mounting heights and connections. The document shows revisions through CPR 323 dated 08/16/12 and is part of construction documents for what appears to be the Orlando VA Medical Center project.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
15" SECONDARY
ROOF DRIANAGE.
24" ABOVE
FINISHED GRADE
(44751 SF)
15" SECONDARY
ROOF DRIANAGE.
24" ABOVE
FINISHED GRADE
(38320 SF)
P-101
4" VENT UP
6" SAN UP &
DN (182 FU)
8" SAN UP &
DN (624 FU)
4" VENT
UP & DN
4" VENT UP & DN
8" SAN UP &
DN (632 FU)
15" SRW UP (38320 SF)
15" RW UP &
DN (44751 SF)
P-560B
P-117
TYP
P-401
P-560B
P-401
P-401
P-401
P-528E
P-528E
P-120
P-404
P-201
P-404
P-404
P-404
P-502
P-609
FLOOR C.O.
P-101
P-102
P-102 P-102
P-101
P-102
P-102
FLOOR C.O.
P-201
P-102
P-202P-609
P-502
2" W UP & DN
2" W UP
& DN
H -P
L
.1 F
E
-A
H -P
L
.1 F
E
-A
H -P
L
.1 F
E
-A
H -P
L
.1 F
E
-A
VRE OFFICE
1C903
VRE SUPERVISOR
1C901
VRE OFFICE
1C902 VRE OFFICE
1C904
JOB LAB
1C403
VRE OFFICE
1C401
CORRIDOR
1CC01
TESTING RM
1C110
HAC
1C108
CLOSET
1C106
CLOSET
1C104
RECEPTION
1C101
CORRIDOR
1CC04
INTERVIEW
1C203
CORRIDOR
1CC02
INTERVIEW
1C201
HEARING RM
1C202
WAITING
1C102
1 1/2" V UP & DN
LOBBY
1B403
WAITING
1B403d
EQ. ALCOVE
1AC07b
VESTIBULE
1B301
OFFICE
1A803
OFFICE
1A801
EXAM/TREAT
1A715
GYN EXAM/
TREAT
1A122
PATIENT TLT
1A115
PATIENT TLT
1A714
EXAM/TREAT
1A109d
PHYSICIAN
1F505
PHYSICIAN
1F507
ANTE RM
1A719
ISOLATION
1A721
ISOLATION
1A717
ADMISSIONS
CHECK IN
1B204
ADMISSIONS
CHECK IN
1B202
PROCEDURE
CHECK IN
1B203
ED TLT MALE
1A502
ED TLT FEMALE
1A504
HAC
1B604
PUBLIC TLT
FEMALE
1B601
CORRIDOR
1BC02
PHONE
1A501
CORRIDOR
1AC05
PROCEDURE
CHECK IN
1B205
CORRIDOR
1AC08
TRIAGE
1A119
TRIAGE
1A718
PHYSICIAN
1F503
GYN EXAM/
TREAT
1A120
CONSULT
1A124
CORRIDOR-1
1BC04-1
CORRIDOR
1FC05
Space
2C558
SECURITY
SCREENING
1B403c
FIRE COMMAND
1B505
OPERATIONS
1B303a
CORRIDOR
1BC03
VESTIBULE
1B303
HOLDING
1B303b
CORRIDOR
1FC07
MAS WORKRM
1B201
COMM
1B201b
KIOSK CHECK-IN
1BC04aELEC
1B201a
VENDING
1A121a
ARMORY
WORKRM
1B303c
WAITING
1A121
ESCORT
SERVICES
1B701
CORRIDOR
1BC07
CORRIDOR
1BC06
ELEVATOR
LOBBY
1B405
OFFICE OF
DECEDENT
AFFAIRS
1B703
WAITING
1B403b
15" RW UP &
DN. (38320 SF)
FLOOR C.O.
P-806
MOUNT 1'-6" O.C. ABOVE
ASSOCIATED LEVEL.
P-806
MOUNT 1'-6" O.C. ABOVE
ASSOCIATED LEVEL.
3/4" CW UP
3/4" CW
UP
FLOOR C.O.
CW UP HW & CW UP
PUBLIC TLT MALE
1B600
H-PL1.1FE2-A
H-PL1.1FD5-A
H-PL1.1FE2-A
H-PL1.1FD5-A
H -P
L
.1 F
E
-A
H -P
L
.1 F
E
H -P
L
.1 F
E
-A
H -P
L
.1 F
E
'-6
'-6
7.1
2.2
C.2
A.2
D.2
B.2
C.1
A.1
D.1
B.1
1.2
8.1
A
C
B
2.0
7.3
A.05
34.5
34.2 32.4
32.2
A.04 2.8
1.4
32333435 A7
7.7
34.4
A.01
35.4 31.7
D.3
32.8
A.03
32.5
33.8
A.07
FD-C FD-C
FD-C
FD-C
6" RW UP
TO RD-16" SRW UP
TO RD-2
(2,112 SQ. FT.)
P-560B
8" SECONDARY
ROOF
DRIANAGE. 24"
ABOVE FINISHED
GRADE
(10203 SF)
8" RW UP & DN
8" SRW UP
(10203 SF)
WALL
C.O.
6" RW & SRW UP
(3,917 SQ. FT.))
R W
LOBBY
1B403
WAITING
1B403d
WAITING
1B403b
34.5 34.2 32.4 32.2
A.04
A734.4
A.02
32.8
A.03
33.8
S R
W 6" SECONDARY
ROOF
DRIANAGE. 24"
ABOVE FINISHED
GRADE
(4,112 SQ. FT.)
6" RW DN
(4,112 SQ. FT.)
6" RW UP
TO RD-1
(2,164 SQ. FT.)
6" SRW UP
TO RD-2
(2,112 SQ. FT.)
6" RW UP
TO RD-1
6" SRW UP
TO RD-2
6"
6"
6" 6"
6"
6"
WALL
C.O.
6" SRW UP
TO RD-2
(1,958 SQ. FT.)
6" RW UP
UP TO RD-1
(1,958 SQ. FT.)
6"
CO
6"
8"
N
1/8" = 1'-0" GRAPHIC SCALE
4' 8' 24'16'
A1
C2
KEY PLAN
C1
D3
D4
E2
A2 A3
B1 B2
AREA E, ZONE 2
D2
D5 D6
E1 E3
D1
1/8" = 1'-0"
Level 1 Area E2 - Plumbing - Alternate #2
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
04 JUNE, 2010
Professional Seals:
EB / RLF
NOTES:
SHEET NOTES:
01 AND 02
4322Dwg. ofGO/PPG
ZONE 2 PLUMBING PLAN
BID ALTERNATE NO. 2
HOSPITAL/CLINIC LEVEL 1, AREA E,
H-PL1.1FE2-A
1/8" = 1'-0"
Partial Plan - Level 1 - Plumbing
1 1/2" CW FROM TRAP PRIMER DN TO FD-C.
2. 2" VENT FROM BELOW.
3. CONNECT 2" VENT TO 4" VENT IN PIPE CHASE.
No. Description Date
1 CPR 078 05-12-11
2 CPR 130 08/25/11
3 CPR 160 10/14/11
4 CPR 222 02/27/12
5 CPR 323 08/16/12
File details come from the government source that posted it. Updated .