ATTACHMENT - VOLUME 12A_Power Updated 07.25.13-2.pdf

PDF 1 MB Posted

Attached to
Y1DZ--PROJECT 675-23-100, Bid-Build (BB) Renovate Lake Nona Building 2 for Emergency Department and Observation Unit
Solicitation number
36C24825R0025-0001
Issued by

About this file

This is an electrical power plan drawing for Level 1, Area E, Zone 2 of a new VA Medical Center hospital project in Orlando, Florida. The drawing shows the detailed electrical layout including receptacles, junction boxes, conduits, and other electrical components for various clinical spaces including waiting rooms, corridors, examination rooms, offices, and other medical facilities.

The drawing provides specific installation requirements through 35 detailed notes covering items such as conduit routing to branch racks, device mounting heights, connections to automatic doors, security systems, and medical equipment. Key spaces shown include VRE offices, interview rooms, corridors, reception areas, and testing rooms. The drawing is part of bid alternate #1 and includes revisions through December 2012 (CPR 366). The plan indicates the building is fully sprinklered and was prepared by RLF architectural firm under VA project number 673-950.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

J

J

J

J

J

J

J J

J

M

J

J

J

J

J J

J

J J J

J

J

J

PP

PP

PP

PP

PP

PP

EE

J J

JJ

JJ

JJ

JJ

JJ

JJ

J

G

G

G

G

G

G

GG

G

G

G

G

G

G

G

G

H1E2LS1- 1,3

H1E2LC1- 2,4

H1E2LN1-

7,9,11

H1E2LN1- 4,6

H1E2LC1-

20,22

H1E2LC1- 15

H1E2LN1- 12

H1E2LN1-

15,17

H1E2LN1-

18,20

H1E2LN1-

21,23

H1E2LN1- 28

H1E2LN1-

24,26

H1E2LN2- 1,3

H1E2LN2- 2

H1E2LN2- 4

H1E2LN2- 5

H1E2LC1- 17

H1E2LN2- 6

H1E2LC3- 4

H1E2LN3- 2,4

H1E2LN3- 5,7

G

H1E2LN3- 12

H1E2LN3-

14,16

H1E2LN3-

13,15

G

H1E2LN3-

18,20

H1E2LN3-

17,19,21

H1E2LN3- 22

H1E2LN3-

24,26

H1E2LN3-

23,25

H1E2LN3-

28,30

H1E2LN4- 2,4

H1E2LN4- 5,7

H1E2LN4- 1,3

H1E2LN4- 6

H1E2LN4-

10,12

H1E2LC3- 1

H1E2LN4- 8

H1E3LN1- 1,3

H1E2LN4- 9

H1E2LN4- 14

H1E2LN4-

11,16

H1E2LN4- 13

H1E1LC2- 25

H1E1LN2-

16,14

H1E1LN2- 13

H1E2LC1- 5

H1E2LN2-

14,16

VRE OFFICE

1C908

H -E

P 1.

1F E

3- A

H -E

P 1.

1F E

2- A

H -E

P 1.

1F E

2- A

H -E

P 1.

1F E

H1E2LN1- 13

TV

TV

12H1E2LN2- 8

H1E2LN2- 10

H1E2LN3- 32

EX

EX

EX

H1E3LN1- 35

EX

EX

EX

G

G

8 8

G G

WAITING

1C102

CORRIDOR

1CC01

RECEPTION

1C101

HEARING RM

1C202

CLOSET

1C104

CLOSET

1C106

HAC

1C108

TESTING RM

1C110

INTERVIEW

1C203

JOB LAB

1C403

CUBICLES

1C606

CORRIDOR

1CC04

MAIL ROOM

1C112a

CORRIDOR

1CC02

INTERVIEW

1C201

VRE OFFICE

1C401

CORRIDOR

1CC06

VRE OFFICE

1C904

VRE OFFICE

1C902

VRE

SUPERVISOR

1C901

CORRIDOR

1CC09

ALCOVE

1CC09c

VRE OFFICE

1C903

VRE OFFICE

1C907

H1E2LN4- 18

H1E2LN1- 10

H1E2LN1- 14

H1D5LE3- 10

H1D5LE3- 9

EWC

H1E2LN1- 25

H1E2LS1- 11

H1E2LS1- 12

H1E2LS1- 13

7.1

2.2

C.2

A.2

D.2

B.2

C.1

A.1

D.1

B.1

1.2

8.1

A

B

2.0

7.3

30.2

A.05

32.2

A.04

2.8

1.4

32333435

A7

A7

6.7

7.7

B.3

A.01

35.4 31.7

D.3

A.02

32.8

A.03

33.8

A.07

0' - 4 1/2"

3' - 0"

H1E2LC3-

3,10

H1E2LN2- 22

H1E2LN2- 23

H1E2LN2- 24

7' - 9 1/2"

5' - 1"

14' - 3"

7' - 4"

17' - 6"

8' - 2 1/2"

3' - 11 1/2"

12' - 1"

9' - 7"

10' - 0"

3' - 8"

0' - 6 1/2"

+66"

OC OC

OC

OC

+66"

+48"

+48"

+48"

+48"

OC

OC

+66"

TV

OC

OC

OC

OC

H1E2LN4- 20

H1E2LN3-

8,10

H1E2LN3-

11,9

B

B

H1E2LS1- 10

H1E2LS1- 9

H-DVC

H-H-FACU

B

B

B

B

B

B B

17 19,21

H1E2LN1- 8

EWC

H1E2LN1- 16

H1E2LN1- 1

H1E2LS1- 8

H-FAAP

H-FCU-1.17

ST-H-FCU-1.17

+48"

+48"

H1E2LN1- 22

H1E2LN3- 31

G

G G

OC

H1E2LN2- 20

H1E2LN2-

13,11

H1E1LC2- 40

H1E1LN1-

19,21

H1E2LN4- 17

H1E2LC1- 26

H1E2LC1- 24

H1E2LC3- 6

H1E2LN1- 29

G +48"

OC

11 8

AUTOMATIC

DOOR

AUTOMATIC

DOOR

H1E2LN1- 19

H1E2LC1- 6,8

H1E2LC1-

12,14

H1E2LS1- 6

H1E2LC1- 1,3

H1E2LN2-26

H1E2LN2-27,29

P

H1E2LS1-14

H-EP4.007

25 27

H1E2LS2-1

H1E2LS2-3

H1E2LC1-

30,32

30 30

H1E2LC1- 7,9

TV

H1E2LN2-

18,15

33 H1E2LS1-17

N2 N1 E2 E1

N2 N1 E2 E1

N1N2

E2 E1

H1E2LC1- 29

H1E1LN2- 50

H 1E

3L N

1-

TR

PUBLIC TLT

MALE

1B603

PUBLIC TLT

FEMALE

1B601

HAC

1B604

ELEC

1C102aADMISSIONS

CHECK IN

1B204

PROCEDURE

CHECK IN

1B205

ADMISSIONS

CHECK IN

1B202

PROCEDURE

CHECK IN

1B203

PHONE

1A501

ED TLT

FEMALE

1A504

ED TLT MALE

1A502

ELEC

1B201aVENDING

1A121a

WAITING

1A121

TRIAGE

1A718

TRIAGE

1A119

ISOLATION

1A721ANTE RM

1A719

ISOLATION

1A717

OFFICE

1A801

OFFICE

1A803

PATIENT TLT

1A115

PHYSICIAN

1F507

CONSULT

1A124

PHYSICIAN

1F505

PHYSICIAN

1F503

FIRE

COMMAND

1B505

EQ. ALCOVE

1AC08a

GYN EXAM/

TREAT

1A122

PATIENT TLT

1A714

EXAM/TREAT

1A715

COMM

1B201b

MAS WORKRM

1B201

SECURITY

SCREENING

1B403c

CORRIDOR

1BC06

PHONE

1B602

KIOSK

CHECK-IN

1BC04a

CORRIDOR

1BC02

VESTIBULE

1B303

CORRIDOR

1BC03

CORRIDOR

1AC08

CORRIDOR

1AC05

LOBBY

1B403

ELEVATOR

1BE04

ELEVATOR

1BE02

EQ. ALCOVE

1AC08b

ELEC

1C102a

ELEC

1C102a

ELEC

1C102a

ELEC

1C102a

ELEVATOR

1BE03

HOLDING

1B303b

WAITING

1B403d

ESCORT

SERVICES

1B701

OFFICE OF

DECEDENT

AFFAIRS

1B703

CORRIDOR

1BC07

CORRIDOR

1BC05

ELEVATOR

LOBBY

1B405

CORRIDOR

1BC04

RECEPTION

1B403a

ARMORY

WORKRM

1B303c

WAITING

1B403b

WHEEL CHAIR

STOR

1B401a

VESTIBULE

1B401

MECH

1B401b

OPERATIONS

1B303a

VESTIBULE

1B301

CORRIDOR

1AC07

CORRIDOR

1AC01

ELEVATOR

1BE01

EXTERIOR

ARCADE

1A198 EXTERIOR

ARCADE

1C198

VESTIBULE

1BCO1a

WAITING

1A121

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.

CONSULTANTS: ARCHITECT/ENGINEERS:

OFFICE OF

FACILITIES

MANAGEMENT

on e ei gh th in ch o ne fo ot

B

A

C

D

E

F th re e in ch es o ne fo ot

6"

6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot

6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

A NEW HOSPITAL FOR

VAMC ORLANDO, FLORIDA

Orlando, Florida

673-950Professional Seals:

EB / RLF of04 JUNE, 2010

BUILDING IS FULLY SPRINKLERED

01 AND 02

HOSPITAL / CLINIC

H-EP1.1FE2-A

LEVEL 1, AREA E, ZONE 2

POWER PLAN BID ALTERNATE NO. 1

SIN 3849

N

1/8" = 1'-0" GRAPHIC SCALE

4' 8' 24'16'

A1

C2

KEY PLAN

C1

D3

D4

E2

A2 A3

B1 B2

AREA E, ZONE 2

D2

D5 D6

E1 E3

D1

D7

CLINIC

HOSPITAL

P-W P-E

A4

E4

W

NOTES:

GENERAL NOTES

1. ALL HOMERUNS SHALL BE ROUTED FROM THE DEVICE OR FIXTURE

INDICATED UP TO THE BRANCH CONDUIT RACK LOCATED IN THE "S4"

ZONE OF INTERSTITIAL SPACE. EXTEND CONDUIT ALONG THE RACK IN

THE "S4" ZONE AND THEN TRANSITION UP THE MAIN DISTRIBUTION

WIREWAYS TO THE PANELBOARD LOCATED IN THE ELECTRICAL ROOM.

SEE H-EP-5.504 FOR DETAIL REFERENCE.

2. COORDINATE THE LOCATION AND MOUNTING HEIGHT OF ALL

DEVICES WITH ARCHITECTURAL AND INTERIOR ELEVATION.

3. PROVIDE 1" CONDUIT FOR DATA ROUTE FROM FLOOR BOX AS

SHOWN. TURN UP CONDUITS IN NEAREST WALL AND STUB UP TO

ABOVE CEILING.

No. Description Date

8 CPR 132 10/17/2011

9 CPR 169 10/31/2011

10 CPR 177 11/16/2011

11 CPR 211 01/06/2012

12 CPR 230 02/23/2012

13 CPR 278 05/04/2012

14 CPR 312 07/27/2012

15 CPR 366 12/20/2012

4. WHERE DEVICES ARE INDICATED "OC" TO BE MOUNTED ABOVE A

COUNTERTOP,MOUNT DEVICE SUCH THAT BOTTOM OF

COVERPLATE IS (2") ABOVE TOP OF BACK SPLASH. IF THERE IS NO

BACK SPLASH, MOUNT DEVICE (2") ABOVE FINISHED COUNTER TOP

SURFACE TO BOTTOM OF DEVICE COVERPLATE.

23 CONNECTION TO WON FIRE DOOR. PROVIDE

CONDUIT, JUNCTION BOXES AND WIRING PER

MANUFACTURER REQUIREMENTS.

24 PROVIDE BACKBOX, CONDUIT AND WIRE TO KEYED

CONTROL STATION PER MANUFACTURER

REQUIREMENTS. MOUNT AT +60"AFF.

25 PROVIDE BACKBOX, CONDUIT AND WIRE TO SINGLE

DOOR DISPLAY PER MANUFACTURER

REQUIREMENTS. MOUNT AT +60"AFF.

26 PROVIDE BACKBOX, CONDUIT AND WIRE TO

OBSTRUCTION DETECTOR PER MANUFACTURER

REQUIREMENTS. MOUNT AT +60"AFF.

27 3/4" CONDUIT FOR LOW VOLTAGE WIRING.

28 CONNECTION TO AUTODOOR OPERATOR. PROVIDE

CONDUIT, JUNCTION BOXES AND WIRING PER

MANUFACTURER REQUIREMENTS.

29 CONNECTION TO POWER STRIP IN SECURITY

EQUIPMENT CABINET. PROVIDE ALL CONDUCTORS,

CONDUIT, FLEXIBLE CONDUIT, JUNCTION BOXES,

CONNECTORS, FITTING, ETC. REQUIRED FOR

PROPER CONNECTION.

30 TERMINATE CONDUITS AT SECURITY SYSTEM

EQUIPMENT CABINET. COORDINATE EXACT

TERMINATION LOCATION IN FIELD, BASED ON

EQUIPMENT MANUFACTURER REQUIREMENTS.

31 PROVIDE 1" EMPTY CONDUIT ROUTED TO NEAREST

SECURITY SYSTEM CABLE TRAY IN INTERSTITIAL

SPACE.

32 PROVIDE 1" EMPTY CONDUIT ROUTED TO LADDER

RACK IN COMMUNICATIONS ROOM 1B201b.

33 CONNECTION TO AIR PRESSURIZATION MONITORING

PANEL. PROVIDE ALL CONDUCTORS, CONDUIT,

FLEXIBLE CONDUIT, JUNCTION BOXES,

CONNECTORS, FITTINGS, ETC. REQUIRED FOR

PROPER CONNECTION.

34 CONNECTION TO PTZ CCTV CAMERA. PROVIDE ALL

CONDUCTORS, CONDUIT, FLEXIBLE CONDUIT,

JUNCTION BOXES, CONNECTORS, FITTINGS, ETC.

REQUIRED FOR PROPER CONNECTION.

35 PROVIDE RECEPTACLE WALL PLATE WITH TAMPER

PROOF SCREWS AND BEVELED EDGES.

1 MOUNT THIS RECEPTACLE FLUSH IN CEILING,

WITHIN 24" OF PATIENT LIFT TRACK. COORDINATE

EXACT LOCATION WITH PATIENT LIFT SYSTEM

MANUFACTURER. TYPICAL FOR ALL

CEILING-MOUNTED RECEPTACLES IN

EXAM/TREATMENT ROOMS.

2 PROVIDE CEILING MOUNTED JUNCTION BOX FOR

EXAM LIGHTS. TYPICAL FOR EACH EXAM ROOM.

COORDINATE WITH RCP FOR ACTUAL LOCATION.

3 REFER TO H-AI2 SERIES DRAWINGS FOR DEVICE

LOCATIONS ON HEADWALL FOR THIS ROOM.

4 NOT USED.

5 NOT USED.

6 NOT USED

7 PROVIDE JUNCTION BOX FOR POWER CONNECTION

TO THE FIRE ALARM ANNUCIATOR PANEL. FOR

LOCATION COORDINATE AT SITE.

8 PROVIDE GFI RECEPTACLES IN ELEVATOR PIT AND

CONNECT TO THE SAME CIRCUIT THAT SERVE THE

ELEVATOR PIT LIGHT AHEAD OF THE LIGHT SWITCH.

FOR EXACT LOCATION COORDINATE AT SITE WITH

ELEVATOR PIT DRAWING.

10 EXTEND THE WIRE FROM THIS RECEPTACLE TO THE

FIXTURE AS SHOWN ON THE LIGHTING PLAN

H-EL1.1FE2. CONNECT TO THE 120V, SINGLE PHASE

CIRCUITS SHOWN ON THIS DRAWING.

12 LOCATION FOR STUB UP CONDUITS FOR POWER,

DATA, VOICE AND TASK LIGHT FOR POWER

CONNECTIONS TO RECEPTION DESK. FOR DETAILS

COORDINATE WITH INTERIOR/MILWORK DETAILS.

13 NOT USED

14 NOT USED

15 REFER TO MOTOR STARTER SCHEDULE ON SHEET

H-EP7.000 FOR FEEDER INFORMATION.

16 SEE SHEET H-EP1.1FE3-A FOR CONTINUATION.

17 SEE SHEET H-EP1.1FE1 FOR CONTINUATION.

18 PROVIDE JUNCTION BOX FOR THE SIGNAGE. REFER

TO ARCHITECTURAL DRAWING FOR EXACT

LOCATION.

19 PROVIDE MULTI ASSEMBLY OUTLETS WITH ONE

OUTLET EVERY 1 FEET. MOUNT AT +4'-0" AFF.

20 CONNECTION TO CLEAN AGENT CONTROL PANEL

21 TO MANUAL MOTOR RATED SWITCH SERVIING

EXHAUST FAN H-EF-45 ON SHEET H-EP1.1NE.

22 SWITCH WITH RED LED PILOT LIGHT. LIGHT SHALL

ILLUMINATE WHEN SWITCH IS IN THE "ON" POSITION.

PROVIDE ENGRAVED LAMINATED NAMEPLATE WITH

RED FACE AND WHITE 1/4" HIGH LETTERING

INDICATING "FIRE EXTINGUISHING EXHAUST FAN

CONTROL".

File details come from the government source that posted it. Updated .