Attachment_S_-_Drawings_-_Chiller_-_067196-12_Bid-Permit_Specs_Combined.pdf

PDF 19 MB Posted

Attached to
Chiller Replacement, Glen Burnie, MVA
Solicitation number
BPM047469
Issued by
Anne Arundel County, Maryland

About this file

This is a set of mechanical and electrical drawings for a chiller renovation project at the Maryland Department of Transportation Motor Vehicle Administration Building A in Glen Burnie, MD (Contract No. V-MUL-19010-AE-A). The project involves replacing two of three existing water-cooled chillers and associated mechanical/electrical systems in the building's penthouse mechanical room. The scope includes installation of new chillers CH-1 and CH-2 (250 tons each), piping modifications, refrigerant monitoring system upgrades, new chemical treatment systems, and lighting upgrades. The drawings detail demolition and new work for chilled water piping, condenser water piping, electrical power, and lighting systems.

The drawings specify detailed technical requirements including chiller capacities (250 tons each, using R-134A refrigerant), flow rates (599 GPM chilled water, 753 GPM condenser water), electrical requirements (460V/3-phase power, 253 MCA per chiller), and control system integration with the existing building automation system (Schneider Electric Eco-Struxture 2.0). The drawings include demolition plans, new work plans, piping diagrams, electrical one-line diagrams, and lighting layouts. Special considerations are given to maintaining existing services during construction, with requirements that power interruptions occur only outside of business hours (5:00 PM to 6:00 AM Monday-Friday and 1:30 PM to 6:00 AM Saturday-Monday) with prior written approval.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10200 GRAND CENTRAL AVE, SUITE 310

OWINGS MILLS, MD 21117

L o c a l F ile

/1

/2

:1

:5

P

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L

/0

-1

A

C e n tr a l_

R

.r v t

C e n tr a l F ile B

IM

A c e n tr a l_

R .r v t

P ro je c t N u m b e r:

-1

PROJECT NUMBER: 067196-12

MARYLAND DEPARTMENT OF TRANSPORTATION

MOTOR VEHICLE ADMINISTARTION

6601 RITCHIE HIGHWAY NE, GLEN BURNIE, MD 21062

BID/PERMIT SUBMISSION

GLEN BURNIE BUILDING A

CHILLER RENOVATION

AUGUST 11, 2023

VICINITY MAP LOCATION MAP

SCALE: NTS SCALE: NTS

DRAWING INDEX

GENERAL

G001 COVER SHEET

G002 GENERAL NOTES

MECHANICAL

M001 LEGEND, GENERAL NOTES & ABBREVIATIONS

MD101 DEMOLITION FLOOR PLANS

MD301 PIPING RISER DIAGRAM – DEMOLITION

M101 NEW WORK FLOOR PLAN

M301 PIPING RISER DIAGRAM

M501 DETAILS

M601 SCHEDULES

M801 CONTROLS

ELECTRICAL

E001 GENERAL NOTES, SYMBOL LIST AND ABBREVIATIONS

E101 PARTIAL PENTHOUSE PLANS AND DIAGRAMS

E201 PENTHOUSE LIGHTING PLAN - DEMOLITION

E202 PENTHOUSE LIGHTING PLAN - NEW WORK

E601 DIAGRAM, LIGHTING AND PANEL SCHEDULES

CONTRACT NO. V-MUL-19010-AE-A

S

TA

T E

O F MARYLAN

D

A

R C H I T ECT

JA

M E S E . FICKES

N o . 1 9412

SCVTO

B

O N

Æ V

I K V B T A T U S T V Æ

C O

R O

N A

S T

I

NOS

1 6 3 2

1. UNOBSTRUCTED ACCESS TO EXISTING EMERGENCY EXISTS SHALL BE MAINTAINED AT ALL TIMES.

2. ALL DEBRIS AND UNUSED MATERIAL RESULTING FROM DEMOLITION SHALL BE DISPOSED OF OFF SITE IN COMPLIANCE WITH

ALL LOCAL, STATE, AND FEDERAL AUTHORITIES.

3. REMOVE EXISTING PARTITIONS, EQUIPMENT, & DEVICES AS INDICATED.

4. REMOVAL OF EXISTING HVAC & PLUMBING FIXTURES & SAFING TO BE BY APPROPRIATE TRADES.

5. COORDINATE LOCATION OF ALL NEW FLOOR & WALL PENETRATIONS WITH OWNER PRIOR TO CUTTING OR CORING.

COORDINATE LOCATION WITH CONSTRUCTION DRAWINGS. SEAL ALL PENETRATIONS.

6. ALL CONTRACTORS ARE TO REPORT ALL UNEXPECTED, UNCOVERED EXISTING CONDITIONS WHICH IMPACT LAYOUT OF NEW

WORK IMMEDIATELY TO ARCHITECT.

7. FOR EXTENT & SCOPE OF PLUMBING, MECHANICAL & ELECTRICAL REMOVALS, SEE INDIVIDUAL TRADE DRAWINGS.

8. SAW CUT ALL NEW OPENINGS IN EXISTING CONSTRUCTION. DO NOT HAMMER & CHISEL. CARE MUST BE TAKEN NOT TO DAMAGE EXISTING CONSTRUCTION. COORDINATE TIME OF LOUD/HEAVY NOISE CONSTRUCTION WITH OWNER TO LIMIT

DISTURBANCE.

9. ALL ELECTRICAL CIRCUITS, DEVICES, WIRING & LIGHTING TO BE REMOVED ARE TO BE DISCONNECTED AT SOURCE PANEL, WIRE REMOVED FROM CIRCUIT BREAKER, PRIOR TO DEMOLITION TAKING PLACE.

10. PROVIDE PORTABLE LIGHTING DURING DEMOLITION & CONSTRUCTION AS REQUIRED.

11. PROVIDE DUMPSTERS AND OTHER DEMOLITION EQUIPMENT AS REQUIRED.

12. REMOVE EXISTING WORK AS REQUIRED TO ACCOMMODATE NEW WORK, INCLUDING EXISTING WALL & FLOOR FINISHES IN

SPACES SCHEDULED TO BE REFINISHED.

13. PROVIDE APPROPRIATE FULL HEIGHT PROTECTION/TEMPORARY PARTITIONS PRIOR TO COMMENCING DEMOLITION. PLACED

IN LOCATIONS APPROVED BY OWNER.

14. ALL BUILDING ACCESS AND REMOVAL OF MATERIALS MUST BE APPROVED BY OWNER.

15. REMOVE EXISTING ELECTRICAL & PLUMBING FIXTURES AND DEVICES AS INDICATED ON DRAWINGS OR AS REQUIRED AND

ASSOCIATED WITH OTHER ITEMS OF DEMOLITION.

16. CONTRACTOR SHALL DETERMINE CONSTRUCTION OF EXISTING CONDITIONS CONCEALED BY GYPSUM BOARD OR OTHER MATERIALS. MATERIALS INDICATED ON DRAWINGS IS FROM BEST INFORMATION AVAILABLE. DIFFERING CONDITIONS SHALL

NOT FORM THE BASIS OF A CHANGE ORDER TO THE CONTRACT.

17. NOT ALL DEMOLITION IS INDICATED ON THE DEMOLITION PLAN DRAWING. DEMOLITION REQUIRED TO INSTALL NEW WORK THAT CAN BE RESONABLY INFERRED TO BE REQUIRED TO INSTALL THE NEW WORK SHALL BE PERFORMED WITHOUT

ADDITIONAL COST TO THE OWNER.

1. ALL WORK TO CONFORM TO REQUIREMENTS OF THE GOVERNING BUILDING CODE, OSHA AND ALL OTHER APPLICABLE CODES, RULES, REGULATIONS, ORDINANCES, ETC. IN THEIR LATEST EDITION. CONFORM ALL WORK TO REQUIREMENTS OF

ALL AUTHORITIES HAVING JURISDICTION.

2. ALL WORK THAT IS IMPLIED OR REASONABLY INFERRED BY THE DRAWINGS IS THE RESPONSIBILITY OF THE CONTRACTOR.

THE INCLUSION OF ANY AND ALL WORK BY MENTION, NOTATION, DETAIL, ITEMIZATION OR IMPLICATION, HOWEVER BRIEF, MEANS THAT THE CONTRACTOR TO PROVIDE AND INSTALL SAME AT NO ADDITIONAL COST OR BURDEN TO THE OWNER. ALL WORK PERFORMED TO INCLUDE ALL APPURTENANCES AND APPARATUS NORMALLY DEEMED TO BE PART OF A COMPLETE PACKAGE WITHIN THE DEFINITIONS OF ORDINARY INDUSTRY STANDARDS. ALL TRADES ARE RESPONSIBLE FOR REVIEWING THE ENTIRE SET OF DRAWINGS THEREBY NOTING AND INCLUDING THEIR WORK AS APPLICABLE. THE INTENT OF THE DRAWING SET IS TO RESULT IN A COMPLETE AND FINISHED PROJECT IN ALL REGARDS AT THE CONCLUSION OF THE WORK.

INCLUDE ALL WORK, WHETHER SHOWN OR NOT, AS MAY BE NECESSARY TO ACCOMPLISH THE INTENDED RESULT.

3. APPLY AND PAY FOR ALL PERMITS, INSPECTIONS, APPROVALS, ETC. ARRANGE AND COORDINATE ALL REQUIRED

INSPECTIONS AND SECURE ALL NECESSARY APPROVALS OF THE WORK.

4. BECOME FAMILIAR WITH THE PROJECT THROUGH INSPECTION OF THE SITE AND REVIEW OF THE DRAWINGS SO AS TO THOROUGHLY UNDERSTAND THE NATURE AND REQUIREMENTS OF THE WORK. ANY AND ALL DISCREPANCIES OR OMISSIONS TO BE REPORTED TO THE OWNER PRIOR TO THE COMMENCEMENT OF ANY WORK AFFECTED BY SUCH DISCREPANCY OR OMISSION. ENSURE THAT DISCREPANCIES OR OMISSIONS ARE REPORTED AND CLARIFICATION OBTAINED PRIOR TO WORK BEING PERFORMED. ANY AND ALL WORK PROCEEDING OTHERWISE AND THEN FOUND TO BE INCORRECT OR INCONSISTENT WITH THE INTENDED RESULT WILL BE REMOVED, REPLACED AND/OR CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST OR BURDEN TO THE OWNER. VERIFY ALL DIMENSIONS AND LOCATIONS IN THE FIELD. COORDINATE ALL WORK WITH CONDITIONS ENCOUNTERED IN THE FIELD AND MAKE ALL NECESSARY ADJUSTMENTS ACCORDINGLY.

5. CONTRACTOR IS RESPONSIBLE FOR FINAL FIT, FINISH, APPEARANCE AND PERFORMANCE OF ALL WORK.

6. VERIFY ALL DIMENSIONS AND CONDITIONS AT THE WORK SITE PRIOR TO THE COMMENCEMENT OF WORK.

7. VERIFY EXISTING CONDITIONS AFFECTING THE WORK PRIOR TO BIDDING AND ALL ASPECTS OF THE WORK PRIOR TO

COMMENCEMENT.

8. APPLY, INSTALL OR UTILIZE ALL MATERIALS IN ACCORDANCE WITH MANUFACTURER’S PRINTED LITERATURE.

9. ALL WORK TO BE PERFORMED IN A FIRST-CLASS WORKMANLIKE MANNER, MATCHING AND ALIGNING ALL SURFACES SO AS TO AFFORD A NEAT FINISHED APPEARANCE. CLEAN ALL SURFACES FREE OF SOIL, DIRT, REFUSE AND DEBRIS RESULTANT FROM THE WORK. ALL ADJACENT SURFACES TO BE LEFT AS THEY APPEARED PRIOR TO COMMENCEMENT OF THE WORK. PROVIDE ADEQUATE PROTECTION OF ALL ADJACENT AND EXISTING SURFACES TO REMAIN SUFFICIENT TO ENSURE AGAINST DAMAGE DURING CONSTRUCTION OPERATIONS. AT CONCLUSION OF THE WORK, ALL FINISHED EXPOSED SURFACES INCLUDING GLASS, ALUMINUM AND FINISHED HARDWARE TO BE THOROUGHLY CLEANED TO THE SATISFACTION OF THE OWNER.

10. ALL WORK TO BE PROPERLY AND ADEQUATELY PROTECTED FROM DAMAGE AT ALL TIMES REGARDLESS OF THE STAGE OF COMPLETION. TAKE RESPONSIBILITY FOR SAFETY AT ALL TIMES, IN ALL PLACES AND UNDER ALL CONDITIONS AFFECTING OR AFFECTED BY THE WORK. ADHERE TO ALL ACCEPTED SAFETY PRACTICES AND PROVIDE ALL FENCES, BARRICADES, GUARDRAILS, PARTITIONS, ETC. AS MAY BE NECESSARY IN ORDER TO PROTECT LIFE AND PROPERTY FROM INJURY OR DAMAGE AND AS MAY BE REQUIRED BY ANY AND ALL AUTHORITIES HAVING JURISDICTION. REPAIR ANY AND ALL DAMAGE TO THE PREMISES ARISING FROM OR ASSOCIATED WITH WORK SITE OPERATIONS AND/OR ACTIVITIES CONNECTED TO THE

WORK.

11. LEAVE ALL CHASES, HOLES, OPENINGS, ETC. PLUMB LEVEL, TRUE AND OF A PROPER SIZE OR CUT SAME INTO EXISTING WORK AS MAY BE NECESSARY FOR PROPER INSTALLATION OF WORK. CONSULT, CONFER AND OTHERWISE COORDINATE WITH ANY AND ALL OTHER CONTRACTORS AND CONCERNED PARTIES REGARDING PROPER LOCATION, SIZE, PLACEMENT, ALIGNMENT AND ORIENTATION OF SAME. IN CASE OF ANY FAILURE TO LEAVE OR CUT SUCH OPENINGS OR OTHERWISE LEAVE SUCH ACCOMMODATIONS IN PROPER PLACE, CUT THEM AFTERWARDS AT OWN EXPENSE. NO EXCESSIVE CUTTING WILL BE PERMITTED NOR ANY STRUCTURAL MEMBERS TO BE CUT WITHOUT THE CONSENT OF THE ARCHITECT.

12. ALL EQUIPMENT TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. ALL LABOR, EQUIPMENT

AND MATERIAL TO BE GUARANTEED AS PER PROJECT SPECIFICATIONS.

13. COMPLY WITH ALL OWNER SAFETY TRAINING REQUIREMENTS AND SITE PROCEDURES, AND COORDINATE THE FOREGOING

WITH OWNER'S DESIGNATED REPRESENTATIVES.

14. PERFORM ALL WORK WITHOUT INTERFERING WITH OWNER'S NORMAL OPERATIONS.

15. PROJECT DOCUMENTS ARE INTENDED TO BE COMPLEMENTARY. ITEMS INDICATED IN ONE PLACE OR ANOTHER AMONG THE

DOCUMENTS ARE INTENDED AS THOUGH SHOWN IN ALL PLACES.

16. COORDINATE ALL NEW WORK WITH ALL EXISTING CONDITIONS. EXISTING ELEMENTS AFFECTING THE WORK REQUIRE SUCH

COORDINATION WHETHER OR NOT THEY ARE INDICATED IN THE DOCUMENTS.

17. DO NOT SCALE DRAWINGS FOR CONSTRUCTION PURPOSES.

18. ALL WORK IS GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION.

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:1

:5

P

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L

/0

-1

A

C e n tr a l_

R

.r v t

G002

GENERAL NOTES,

SYMBOLS, LEGENDS &

ABBREVIATIONS

08/11/23

JEFMDMD

067196

G L E

N B

U R

N

IE

B U

IL

D

IN

G

A C

H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

GENERAL

SHEET 2 OF 15

C e n tr a l F ile B

IM

A c e n tr a l_

R .r v t

P ro je c t N u m b e r:

GENERAL DEMOLITION NOTES GENERAL NOTES

REVISIONS

NO. DATE DESCRIPTION

19412

04-11-2024

S

TA

T E

O F MARYLAN

D

A

R C H I T ECT

JA

M E S E . FICKES

N o . 1 9412

SCVTO

B

O N

Æ V

I K V B T A T U S T V Æ

C O

R O

N A

S T

I

NOS

1 6 3 2

NEW WORK LINEWEIGHT

EXISTING WORK LINEWEIGHT

FUTURE WORK LINEWEIGHT

DEMOLITION WORK LINEWEIGHT

POINT OF CONNECTION

TERMINATION POINT OF DEMOLITION

SHEET NOTE REFERENCE

REVISION REFERENCE

M301

INDICATES PLAN/DETAIL NUMBER

PLAN/DETAIL TITLE

SCALE (AS REQUIRED)

INDICATES PLAN/DETAIL NUMBER

INDICATES DRAWING ON WHICH

DRAWING SECTION APPEARS

VAV/AIR VALVE TAG

8"

VAV-1

DESIGNATION

DUCT INLET/PIPE SIZE

CFM/GPM

EQUIPMENT TAGE-1

VIEW TITLE

SCALE:

NORTH ARROW

DIFFUSER, REGISTER, OR GRILLE

DESIGNATION AND AIRFLOW TAG(S)150

8"

CD-1

TYPE

CFM

CD-1

CD-1-150

NECK

POINT OF FUTURE CONNECTION

AREA OF DEMOLITION

SYMBOL DESCRIPTION

PIPING TURNING DOWN

PIPE BRANCH TOP TAKEOFF

CAP

PIPE RISER UP/DOWN

PIPING TURNING UP

PIPE BRANCH BOTTOM TAKEOFF

TEE DOWN

FLOW DIRECTION

R/D

PIPE SLOPE RISE/DROP

CONCENTRIC REDUCER/INCREASER

ECCENTRIC REDUCER/INCREASER (FOB)

UNION

, PIPE CONTINUATION

PIPE ANCHOR

PIPE GUIDE

FLEXIBLE PIPE CONNECTOR

STEAM TRAP

EXPANSION LOOP (WxH)

DIFFERENTIAL PRESSURE TRANSDUCER

TEMPERATURE SENSOR

PRESSURE SENSOR

FLOW SWITCH

FLOW METER

PUMP

H W

EXPANSION JOINT

EJ

VALVE IN VERTICAL PIPE

BLIND FLANGE

VENTURI FLOW METER

T

P

DP

FS

FM

DESCRIPTION

STRAINER WITH DRAIN VALVE AND CAP

GEN. SHUTOFF VALVE (BALL, GATE, BUTTERFLY)

GATE VALVE

CHECK VALVE

BALL VALVE

BUTTERFLY VALVE

GAS COCK

STRAINER

PRESSURE REDUCING VALVE

CALIBRATED BALANCING VALVE

CONTROL VALVE, TWO-WAY (ELECTRIC)

CONTROL VALVE, THREE-WAY (ELECTRIC)

THREE-WAY MANUAL VALVE

SOLENOID VALVE

RELIEF/SAFETY VALVE

SYMBOL

s

GLOBE VALVE

OUTSIDE STEM & YOKE VALVE

PRESSURE GAUGE WITH COCK

THERMOMETER

PRESSURE/TEMPERATURE TEST PORT

AQUASTAT

NORMALLY CLOSED PORT (NC)

CONTROL VALVE, TWO-WAY (PNEUMATIC)

CONTROL VALVE, THREE-WAY (PNEUMATIC)

AUTOMATIC AIR VENT (EXTEND TO DRAIN)

MANUAL AIR VENT

AAV

MAV

FUSOMATIC GATE VALVE

F

SYMBOL

DOUBLE LINE DESCRIPTION

DUCTWORK, SIZE AS INDICATED

DUCTWORK, WITH SOUNDLINING

VANED ELBOW

SUPPLY DUCT TURNING UP AND DOWN

RETURN DUCT TURNING UP AND DOWN

EXHAUST/RELIEF DUCT TURNING UP AND DOWN

DUCT RISE/DROP IN AIRFLOW DIRECTION

DUCT TRANSITION, SQUARE TO SQUARE

DUCT TRANSITION, SQUARE TO ROUND

DUCT CAPPED

45 DEGREE TAP

CONICAL TAP

SPUN-IN RUNOUT FITTING W/ FLEX. & VD

FLEXIBLE DUCT

MANUAL VOLUME DAMPER

FIRE DAMPER

SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER

BACKDRAFT DAMPER

MOTORIZED DAMPER

RETURN, EXHAUST GRILLE OR REGISTER

SUPPLY AIR DIFFUSER, 4-WAY BLOW

UNDERCUT DOOR

DOOR LOUVER

THERMOSTAT, MASTER THERMOSTAT

TEMPERATURE SENSOR

SUPPLY AIR DIFFUSER, 3-WAY BLOW

SUPPLY AIR DIFFUSER, 2-WAY BLOW

SUPPLY AIR DIFFUSER, 1-WAY BLOW

FLEXIBLE CONNECTION

HUMIDISTAT

HUMIDITY SENSOR

DUCT SMOKE DETECTOR

CARBON MONOXIDE SENSOR

STATIC PRESSURE SENSOR

UC

DL

12x12

DUCT ACCESS DOORAD

AD

AIR FLOW MEASURING STATION

DUCT CONTINUATION

SUPPLY AIR FLOW DIRECTION

OUTSIDE AIR FLOW DIRECTION

RETURN/EXHAUST AIR FLOW DIRECTION

OA

FREEZESTAT

MANUAL TIMER SWITCH

SWITCH OR TOGGLE SWITCH

HAND/OFF/AUTO SWITCH

UN-VANED ELBOW

VANED TEE

UN-VANED TEE

BAROMETRIC DAMPER

LINEAR SLOT DIFFUSER

GAS CONCENTRATION MONITOR

RADIUS ELBOW

HOA

TM

S

AFMS

SP

CO

D

HS

FZ

H

TS

TT

SF

R/D

20x12

20x12

F

BD

MD

BDD

S

SAFETY SWITCH/PUSH BUTTONPB

1. NOT ALL ABBREVIATIONS, LINE TYPES, OR SYMBOLS MAY APPEAR ON THESE

CONTRACT DOCUMENTS.

2. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC AND ARE INTENDED TO

INDICATE CAPACITY, SIZE, APPROXIMATE LOCATION AND GENERAL ARRANGEMENT.

WHILE THE DRAWINGS ARE GENERALLY TO SCALE AND ARE AS ACCURATE AS THE

SCALE WILL PERMIT, DIMENSIONS SHALL BE CONFIRMED IN THE FIELD.

3. THE CONTRACTOR SHALL COMPLY WITH THE LAWS, ORDINANCES, RULES AND

REGULATIONS OF LOCAL AND STATE GOVERNMENTAL AUTHORITIES; OF THE

NATIONAL FIRE PROTECTION ASSOCIATION AS INTERPRETED BY THE ENFORCING

AUTHORITY HAVING JURISDICTION; AND OF PUBLIC UTILITIES HAVING CONNECTION

WITH ANY OF THE SYSTEMS HEREIN SPECIFIED.

4. INSTALL EQUIPMENT IN A SERVICEABLE MANNER WITHOUT DISRUPTION TO

ADJACENT SERVICES OR DAMAGING INSULATION. THIS INCLUDES, BUT IS NOT

LIMITED TO: PROVIDE VALVE OPERATOR EXTENSIONS TO EXTEND THRU THE

INSULATION AND HANDLES TO SWING TOWARD THE OPERATOR FOR ISOLATION.

5. PROVIDE ALL NEW AND REUSED WALL PENETRATIONS WITH A SLEEVE/CONDUIT

FOR SERVICES PENETRATING IT. THIS INCLUDES, BUT IS NOT LIMITED

TO: DUCTWORK, PIPING, POWER, AND CONTROL WIRING.

6. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS

REQUIRED BY ANY OF THE FOREGOING AUTHORITIES, AND PAY FOR ALL OTHER

COSTS IN CONNECTION WITH THE WORK. CERTIFICATES SHALL BE IN DUPLICATE

AND SHALL BE DELIVERED TO THE OWNER.

7. THE SITE, LOCATION, AND ROUTING OF SYSTEMS INDICATED TO HAVE NEW

CONNECTIONS MADE TO THEM ARE SHOWN AS ACCURATELY AS FIELD CONDITIONS

PERMIT. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY EXAMINE THE

CONTRACT DRAWINGS. ALL EXISTING CONDITIONS SHALL BE EXAMINED AND THEIR

EXACT LOCATIONS VERIFIED. THE CONTRACTOR SHALL REPORT TO THE ENGINEER

ANY CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED EQUIPMENT A

PROBLEM. NO CONSIDERATION OR ALLOWANCE WILL BE GRANTED FOR FAILURE

TO INVESTIGATE CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTUAL

REQUIREMENTS.

8. THE CONTRACTOR SHALL INSTALL AND CONNECT EQUIPMENT AND MATERIALS IN

ACCORDANCE WITH THE BEST ENGINEERING PRACTICE AND, UNLESS OTHERWISE

SHOWN OR SPECIFIED, FOLLOW THE MANUFACTURER'S PRINTED INSTALLATION

REQUIREMENTS AND RECOMMENDATIONS, AND FURNISH AND INSTALL REQUIRED

AUXILIARY ITEMS TO PROVIDE A COMPLETE INSTALLATION.

9. THE CONTRACTOR SHALL REPAIR WALLS, CEILING, FLOORS, ETC., THAT ARE

REQUIRED TO BE PENETRATED, OR OTHERWISE DISTURBED. THE REPAIRS SHALL

BE WITH MATERIALS AND FINISHES TO MATCH EXISTING. FIRE WALL PENETRATIONS

SHALL BE SEALED WITH SUITABLE MATERIALS TO PRESERVE FIRE WALL INTEGRITY.

10. THE CONTRACTOR SHALL REMOVE EQUIPMENT NOT INDICATED TO BE REUSED TO

A DESIGNATED LOCATION AT THE PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN

ASSEMBLED FOR THE OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL

EQUIPMENT NOT TO BE RETAINED BY THE OWNER SHALL BE REMOVED FROM THE

SITE BY THE CONTRACTOR.

11. COORDINATE WITH OTHER TRADES TO AVOID INTERFERENCE AMONG

MECHANICAL, ELECTRICAL, ARCHITECTURAL AND STRUCTURAL, PLUMBING, ETC.

PROVIDE NECESSARY OFFSETS IN PIPING, DUCTWORK AND FITTINGS ETC.,

REQUIRED TO PROPERLY INSTALL WORK WITHOUT INTERFERENCES.

12. BUILDING SYSTEMS SHALL REMAIN IN SERVICE UNLESS INDICATED OTHERWISE.

OUTAGES OR INTERRUPTIONS SHALL BE KEPT TO A MINIMUM DURATION. NOTIFY

THE OWNER 48 HOURS IN ADVANCE OF ANY OUTAGE OR INTERRUPTION. IF

TEMPORARY CONNECTIONS ARE NECESSARY TO ASSURE THIS CONTINUITY OF

SERVICES, THEY SHALL BE FURNISHED BY THE CONTRACTOR WITHOUT ADDITIONAL

CHARGE TO THE OWNER AND SHALL BE REMOVED WHEN NO LONGER NEEDED.

13. THE CONTRACTOR SHALL ARRANGE AND EXECUTE HIS WORK SUCH THAT ANY

CONNECTIONS, BOTH TEMPORARY OR PERMANENT, TO, OR REARRANGEMENT OF,

PRESENT EQUIPMENT, PIPING, ETC., SHALL BE MADE IN SUCH A MANNER AS TO

ASSURE FULL RESUMPTION OF SERVICE AT THE TIME DESIGNATED BY THE OWNER.

14. THE CONTRACTOR SHALL LOCATE EQUIPMENT WHICH MUST BE SERVICED,

OPERATED OR MAINTAINED IN FULLY ACCESSIBLE POSITIONS. FURNISH ACCESS

DOORS AS REQUIRED FOR BETTER ACCESSIBILITY. MINOR DEVIATIONS FROM

DRAWINGS MAY BE MADE TO ALLOW FOR ACCESSIBILITY, BUT CHANGES OF

MAGNITUDE WHICH INVOLVE EXTRA COSTS SHALL NOT BE MADE WITHOUT

WRITTEN APPROVAL.

15. ALL DIMENSIONS FOR EXISTING PIPING AND DUCTWORK SHALL BE VERIFIED IN THE

FIELD BY THE CONTRACTOR PRIOR TO CONSTRUCTION, WHERE NEW WORK

CONNECTIONS ARE INDICATED. NEW DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR

DIMENSIONS.

16. OPENINGS REMAINING IN EXISTING PIPING/DUCTWORK AS A RESULT OF

DEMOLITION SHALL BE SEALED WITH AN AIRTIGHT/WATERTIGHT SHEET METAL CAP.

WHERE EXISTING SYSTEMS ARE INSULATED, WORK SHALL INCLUDE REPAIR AND

REPLACEMENT OF INSULATION EITHER DAMAGED OR REMOVED AS A RESULT OF

DEMOLITION.

17. PIPING SCOPE REQUIREMENTS: HORIZONTAL DRAINAGE PIPING SHALL BE

INSTALLED IN UNIFORM ALIGNMENT AT UNIFORM SLOPES. THE MINIMUM SLOPE OF

HORIZONTAL DRAINAGE PIPE SHALL BE IN ACCORDANCE WITH THE FOLLOWING:

SIZE (INCHES) MINIMUM SLOPE (INCHES PER FOOT)

2-1/2 OR LESS 1/4

3 TO 6 1/8

8 OR LARGER 1/16

1. EXISTING HANGERS SHALL BE MODIFIED TO FACILITATE NEW

ABOVE CEILING WORK.

2. EQUIPMENT NOT BEING REUSED SHALL BE REMOVED IN ITS

ENTIRETY AS REQUIRED TO FACILITATE NEW WORK.

2/20/2023

LINES & REFERENCE SYMBOLS

PIPING

MECH VALVESDUCTWORK

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:2

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

M001

LEGEND, GENERAL

NOTES, &

ABBREVIATIONS

08/11/23

PWHJMJJMJ

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 3 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

GENERAL NOTES

GENERAL DEMOLITION NOTES

ABBREVIATIONS

HWS HOT WATER SUPPLY

HX HEAT EXCHANGER

HZ HERTZ (CYCLES PER SECOND)

ID INSIDE DIAMETER

IN WG INCHES OF WATER GAUGE

IN, “ INCH, INCHES

INFO INFORMATION

INT INTERIOR

INV EL INVERT ELEVATION

ISOL ISOLATION

kAIC KILO AMPERE INTERRUPTING CAPACITY

KW KILOWATTS

L LENGTH, LONG

LAV LAVATORY

LBS POUNDS

LDR LEADER

LP LIQUID PROPANE

LPCR LOW PRESSURE CONDENSATE RETURN

LPS LOW PRESSURE STEAM

LRA LOAD RATED AMPS

LWT LEAVING WATER TEMPERATURE

M METER

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH THOUSAND BRITISH THERMAL UNITS

PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MPS MEDIUM PRESSURE STEAM

MTD MOUNTED

MUW MAKE UP WATER

N NITROGEN

N/A NOT APPLICABLE

NC NORMALLY CLOSED, NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPENED

No NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OA OUTSIDE AIR

OC ON CENTER

OS&Y OUTSIDE STEM AND YOKE VALVE

P PUMP

PC PUMPED CONDENSATE

PD PRESSURE DROP

PG PRESSURE GAUGE

PLBG PLUMBING

PNEU PNEUMATIC

POS POSITION

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PS PRESSURE SWITCH

PSC PUMPED STEAM CONDENSATE RETURN

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PVC POLYVINYL CHLORIDE

(RL) RELOCATED POSITION

R RISE

RA RETURN AIR

RD ROOF DRAIN, REFRIGERANT

DISCHARGE

REF REFRIGERANT

REQ'D REQUIRED

RF RETURN FAN

RL REFRIGERANT LIQUID

RLA RATED LOAD AMPS

RM ROOM

RPM REVOLUTIONS PER MINUTE

RPZ REDUCED PRESSURE BFP

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

S SWITCH

S/S START/STOP

SA SUPPLY AIR

SAN SANITARY

SC STEAM CONDENSATE RETURN

SCCR SHORT CIRCUIT CURRENT RATING

SF SUPPLY FAN, SQUARE FEET

SK SINK

SP STATIC PRESSURE

SPEC SPECIFICATION

SPR SPRINKLER

SQ SQUARE

SQ FT SQUARE FOOT, SQUARE FEET

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STM STEAM

TEMP TEMPERATURE, TEMPORARY

TP TEST PORT, TRAP PRIMER

TW TEPID WATER

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UV UNIT VENTILATOR

V VOLTS, VENT

VD VOLUME DAMPER

VEL VELOCITY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VIB VIBRATION

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W WIDTH, WIDE

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WG WATER GAUGE

WMS WIRE MESH SCREEN

WPD WATER PRESSURE DROP

WT WEIGHT

ZN ZONE

AAV AUTOMATIC AIR VENT

ABV ABOVE

AD AREA DRAIN, ACCESS DOOR, AIR

DRYER

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUST, ADJUSTABLE

AF ANTI-FREEZE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATELY

ARCH ARCHITECTURAL

AS AIR SEPARATOR

AST ABOVEGROUND STORAGE TANK

ATV ATMOSPHERIC VENT

AVG AVERAGE

BA BREATHABLE AIR

BAS BUILDING AUTOMATION SYSTEM

BFP BACKFLOW PREVENTER

BLDG BUILDING

BLW BELOW

BMS BUILDING MANAGEMENT SYSTEM

BOD BASIS OF DESIGN

BOT BOTTOM

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNITS PER HOUR

C COMMON

CA COMPRESSED AIR

CD CONDENSATE DRAIN

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CI CAST IRON

CL CENTER LINE

CLNG CEILING

CNG COMPRESSED NATURAL GAS

CO CLEANOUT, CARBON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CONT'D CONTINUED

CPVC CHLORINATED POLYVINYL CHLORIDE

CUH CABINET UNT HEATER

CV CLEANING VACUUM, CHECK VALVE

CW COLD WATER

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

Cx COMMISSIONING

CxA COMMISSIONING AUTHORITY

(D) DEMOLISH, REMOVE

D DRAIN, DEPTH

DB DECIBELS

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROL

DEG, ° DEGREES

DEH DEHUMIDIFIER

DEPT DEPARTMENT

DESG DESIGNATION

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DI DEIONIZED WATER

DIA, Ø DIAMETER

DIFF DIFFERENTIAL, DIFFERENCE

DISC DISCONNECT

DN DOWN

DWG DRAWING

(E) EXISTING TO REMAIN

(ER) EXISTING RELOCATED

EA EACH

EA EXHAUST AIR

EDB ENTERING DRY BULB

EF EXHAUST FAN

EFF EFFICIENCY

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EQ EQUAL

ET EXPANSION TANK

EWB ENTERING WET BULB

EXT EXTERIOR

(F) FUTURE

FCO FLOOR CLEANOUT

FD FLOOR DRAIN, FIRE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FF FINISHED FLOOR

FG FUEL GAS

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLR FLOOR

FM FLOW METER

FO FUEL OIL

FOF FUEL OIL FILL

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOW SWITCH

FT HD FEET OF HEAD

FT, ‘ FOOT, FEET

FZ FREEZE, FREEZSTAT

°F DEGREES FAHRENHEIT

G GAS

GA GAUGE

GAL GALLON, GALLONS

GALV GALVANIZED

GEN GENERATOR

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GUH NATURAL GAS UNIT HEATER

H HEIGHT

H2O WATER

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

HORIZ HORIZONTAL

HP HORSEPOWER

HPS HIGH PRESSURE STEAM

HTG HEATING

HUH HYDRONIC UNIT HEATER

HWR HOT WATER RETURN

REVISIONS

NO. DATE DESCRIPTION

SHEET DEMOLITION NOTES

1. REMOVE AND DISPOSE OF CHILLER, STARTER, WIRING, CONDUIT,

JUNCTION AND PULL BOXES, DISCONNECT, SENSORS, AND

CONTROLS. REMOVAL SHALL INCLUDE REFRIGERANT

EVACUATION BY A CERTIFIED COMPANY. RECOVERED

REFRIGERANT SHALL BE DISPOSED PER LOCAL AND STATE

REGULATIONS.

2. DISCONNECT EXISTING REFRIGERANT VENT/RELIEF PIPING AND

DEMOLISH TO POINT SHOWN, AND CAP AND SEAL PIPING.

3. DISCONNECT AND REMOVE EXISTING REFRIGERANT MONITORING

PANEL.

4. EXISTING CHILLER, CH-3, IS EXISTING TO REMAIN.

5. PROVIDE PRE-DEMOLITION WATER FLOW AND HEAD PRESSURE

MEASUREMENT OF HYDRONIC CHILLED WATER PUMPS. SEND

REPORT TO ENGINEER.

6. PROVIDE PRE-DEMOLITION WATER FLOW AND HEAD PRESSURE

MEASUREMENT OF HYDRONIC CONDENSER WATER PUMPS. SEND

REPORT TO ENGINEER.

7. REMOVE EXISTING PNEUMATIC CONTROL VALVES FROM CHILLED

WATER PIPING AND CONDENSER WATER PIPING. FIELD VERIFY

PNEUMATIC PIPE ROUTING SERVING PNEUMATIC CONTROL

VALVES AND PERMANENTLY CAP ASSOCIATED PNEUMATIC LINES

BACK TO MAIN.

8. DURING REMOVAL OF CHILLERS, THE WEIGHT OF THE CHILLERS

SHALL NOT BE PUT ON THE ROOF. CONTRACTOR SHALL SUBMIT A

CRANE LIFT SAFETY PLAN.

9. REMOVE SECTION OF PIPE FOR INSTALLATION OF AIR

SEPARATOR.

K

K

L

L

M

M

N

N

O

O

(E)CT-1

(E)CH-3

(E)CWP-2

(E)CWP-1

(E)CHWP-4(E)CHWP-2(E)CHWP-1(E)CHWP-3(E)CHWP-5

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)8" Ø CWR

(E)8" Ø CWR

(E)8" Ø CWS

(E)8" Ø CWS

(E)8" Ø CWR

(E)8" Ø CWS

(E)8" Ø CWS

(E)6" Ø CHWS

(E)8" Ø CHWS

(E)6" Ø CHWS

(E)8" Ø CHWR

(E)6" Ø CHWS

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWS

(D)ET-1

(D)CSF

(E)8" Ø CHWS

(E)2" Ø DCW

(E)2" Ø DCW

(E)1 1/2" Ø DCW

(E)8" Ø CHWR

(E)1 1/2" Ø DCW

TO (E)ET

(E)6" Ø CHWS

(E)6" Ø CHWR

DN TO (E)AHU-3

CHW COIL

(E)4" Ø CHWS

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)8" Ø CWR

(E)8" Ø CWS

(E)2" Ø DCW

DN TO (E)CH-2

(E)MCC

(E)7'-0"x7'-0"RELIEF AIR LOUVER W/MOD(E)14'-0"x10'-0" INTAKE

AIR LOUVER SERVING

(E)AHU-3

(E)2" REFRIG. VENT(E)2" REFRIG.

VENT

(E)EMERGENCY

EXHAUST FAN

(D)CH-2

(E)18"x12" OA DUCT

(D)CH-1

A P

P R

O X

. 4

'-0 " T

O E

D G

E O

F R

O O

F

MD101

(E)EYE

WASH

(E)6" Ø CHWR

(E)6" Ø CHWR (D)6"⌀

(E)6" Ø CHWS

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)4" Ø CHWR

(E)4" Ø CHWR

(E)4" Ø CHWS

(E)4" Ø CHWS

(D

-1

/2

(D)4"⌀, (ABANDONED)

(D)4"⌀

(D)6"⌀

(D)4"⌀

(D)6"⌀

(D)6"⌀

1. SEE SHEET M001 FOR GENERAL NOTES, LEGENDS AND

ABBREVIATIONS.

GENERAL NOTES

M

(D)BACKFLOW

PREVENTOR (D)PRESSURE

REDUCING VALVE

(D)CHEMICAL

SHOT FEEDER

(D)EXPANSION TANK

(D)1-1/2" ⌀ TO CHILLED

WATER LOOP

(E)3/4" ⌀ TO CHILLED

WATER LOOP

(E)1 1/2" Ø DCW

(E)1 1/2" Ø DCW

(E)1 1/2" Ø DCW

(E)2" Ø CHWR (E)1 1/2" Ø DCW

2/20/2023

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:4

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

MD101

DEMOLITION FLOOR

PLANS

08/11/23

PWHJMJJMJ

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 4 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

SCALE: 1/4" = 1'-0"

CHILLER PENTHOUSE PIPING FLOOR PLAN - DEMOLITION

SCALE: 1/4" = 1'-0"

CHILLED WATER MAKEUP WATER PIPING SECTION

(E)8" CWS

(E)8" CWS

(E )6

C

W S

(E )6

C

W S

(E)CT-1

(E)8" CHWS

(E)8" CHWR

(E )6

"C W

R

MEZZANINE

MEZZANINE

EXTERIOR

(E) 8" CWR

(E)6"CWS/R TO

(E)CH-3

CONDENSER WATER FLOW DIAGRAM

CHILLED WATER FLOW DIAGRAM

(E)1-1/2" DCW

(E)1-1/2" MAKE-

UP WATER

(E)DRAIN AND

OVERFLOW TO

(E)ROOF DRAIN

(TYP.)

(E) 8" CWR BYPASS

(E) 8" CWR

(E) 8" CWR

(E) 6"

(E) 6"

(E)8" CWR

(E )6

"C W

R

(E)8" CWS

EXISTING CONCRETE PAD, TYP.

(D) BYPASS CONTROL VALVE

(E)

CHWP-5 (E)

CHWP-3

(E)

CHWP-1

(E)

CHWP-2

(E)

CHWP-4

(E)4" CHWR TO (E)AHU-4, BASEMENT

(E)6" CHWR TO (E)AHU-2, MEZZANINE

(E)6" CHWR

TO (E)AHU-1,

MEZZANINE

(E)6" CHWR TO (E)AHU-3, MEZZANINE

(STANDBY)

(E)6" CHWS

TO AHU-1

(E)6" CHWS

TO (E)AHU-3,

MEZZANINE

(E)4" CHWS TO AHU-4,

BASEMENT

(E)6" CHWS

TO (E)AH-3

(E )6

C

W S

(E )6

"C W

R

(D)6" CWS/R TO

(D)CH-1

(E)6" CHWR

(E)6" CHWR

(E)6" CHWR

(E)4" CHWR

(E)8" CHWR

(E)6" CHWR

(E)6" CHWS/R (E)6" CHWS/R (E)6" CHWS/R (E)6" CHWS/R (E)6" CHWS/R

(E)INCOMING

DOMESTIC COLD

WATER SUPPLY

(E)1-1/2" DCW TO

CHILLED WATER LOOP

CHILLED WATER MAKEUP CONNECTION DIAGRAM

(D)BACKFLOW

PREVENTOR

(D)PRESSURE

REDUCING VALVE

(E)8" CHWS

(E)4" CHWS

(E)6" CHWR

(E)2" CHWR

(D) EXPANSION

TANK

REMOVE EXISTING

PNEUMATIC VALVE

(D)

CH-2

(D )C

W S

(D )C

W R

(E)

CH-3

(E )C

W S

(E )C

W R

REMOVE EXISTING

PNEUMATIC CONTROL VALVE

REMOVE EXISTING PNEUMATIC

CONTROL VALVE

(D)6"CWS/R TO

(E)CH-2

(D)

CH-1

(E )C

W S

(E )C

W R

EXISTING CONCRETE PAD

TO REMAIN, TYP.

MEZZANINE

(D)1-1/4" AIR

GAP & DRAIN

(E)3/4" TO

EXPANSION TANK

(E)BYPASS

2/20/2023

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:4

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

MD301

PIPING RISER DIAGRAM -

DEMOLITION

08/11/23

PWHAPTAPT

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 5 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

SCALE: NTS

CHILLED WATER AND CONDENSER WATER PIPING SCHEMATIC- DEMOLITION

SHEET KEYNOTES

1. PROVIDE NEW CHILLER, CORRESPONDING VIBRATION

ISOLATION, ANCHOR, AND SUPPORT. REFER TO MECHANICAL

DETAILS. CONNECT NEW CHILLER INTO EXISTING BUILDING

AUTOMATIC SYSTEM.

2. PROVIDE REFRIGERANT VENT/RELIEF PIPING FROM CHILLER (AS

PER CHILLER MANUFACTURER) AND ASHRAE STANDARD 15.

CONNECT NEW REFRIGERANT RELIEF PIPING FROM CHILLER TO

EXISTING REFRIGERANT RELIEF MAIN.

3. PROVIDE NEW EXPANSION TANK ON NEW 3'-6" L x1'-6" W x4" H

CONCRETE EQUIPMENT PAD. REFER TO MECHANICAL DETAILS.

4. PROVIDE NEW AIR SEPARATOR AND RECONNECT TO EXISTING

PIPING. EXTEND 1-1/2" COLD WATER MAKE-UP TO AIR

SEPARATOR. REFER TO MECHANICAL DETAILS.

5. PROVIDE NEW REFRIGERANT SENSOR AT EACH NEW CHILLER

AND AT EXISTING CHILLER. PROVIDE NEW REFRIGERANT

MONITORING SYSTEM.

6. PROVIDE NEW REFRIGERANT MONITORING CONTROL PANEL

AND SYSTEM. BASIS OF DESIGN: HALOGUARD IR. CONNECT TO

EXISTING EMERGENCY EXHAUST FAN CONTROLS AND NEW

REFRIGERANT MONITOR SENSORS TO NEW MONITORING

CONTROL PANEL.

7. PROVIDE CHEMICAL BYPASS FEEDER AND ASSOCIATED PIPING

AND VALVES. EXTEND 3/4" PIPING AND CONNECT TO EXISTING

PIPING. REFER TO MECHANICAL PIPING.

8. PROVIDE NEW CHILLED WATER PIPING FROM POINT SHOWN.

PROVIDE SHUTOFF VALVE(S) IN VERTICAL CHWS/R PIPING.

PROVIDE NEW PRESSURE GAUGES AND THERMOSTATS. REFER

TO MECHANICAL DETAILS. PROVIDE INSULATION FOR CHILLED

WATER SUPPLY AND RETURN PIPING AND VALVES.

9. PROVIDE NEW CONDENSER WATER PIPING FROM POINT

SHOWN. PROVIDE SHUTOFF VALVE(S) IN VERTICAL CHWS/R

PIPING. PROVIDE NEW PRESSURE GAUGES AND THERMOSTATS.

REFER TO MECHANICAL DETAILS.

10. MAINTAIN MINIMUM 3'-6" CLEARANCE IN FRONT OF EXISTING

MCC FOR CHILLER, CH-1 EQUIPMENT AND PIPING.

11. DURING INSTALLATION OF CHILLERS, THE WEIGHT OF THE

CHILLERS CANNOT BE SET ON THE ROOF (AREA OUTSIDE THE

MECHANICAL ROOM). SUBMIT CRANE LIFT SAFETY PLAN.

12. PROVIDE NEW ISOLATION VALVE WITH ELECTRIC ACTUATION AT

EXISTING CHILLER, (E)CH-2. CONNECTION TO EXISTING

CONTROL SYSTEM.

13. NEW 6'-0" x 4'-0" X 1/2" STEEL PLATE CRIBBING SHALL BE

INSTALLED CENTERED UNDER SUPPORT FEET OF NEW CHILLER

TO BE INSTALLED.

K L M N O

(E)CT-1

(E)CH-3

(E)CWP-2

(E)CWP-1

(E)CHWP-4(E)CHWP-2(E)CHWP-1(E)CHWP-3(E)CHWP-5

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)4" Ø CHWR

(E)6" Ø CHWR(E

)6

Ø

C H

W R

(E )6

Ø

C H

W R

(E )6

Ø

C H

W R

(E)8" Ø CWR

(E)8" Ø CWR

(E)8" Ø CWS

(E)8" Ø CWS

(E)8" Ø CWR

(E)8" Ø CWS

(E)8" Ø CWS

(E)6" Ø CHWS

(E)6" Ø CHWR

(E)8" Ø CHWS

(E)6" Ø CHWS

(E)8" Ø CHWR

(E)6" Ø CHWS

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWS

(E)1 1/2" Ø DCW

(E)8" Ø CHWS

(E)2" Ø DCW

(E)2" Ø DCW

(E)1 1/2" Ø DCW

(E)8" Ø CHWR

(E)1 1/2" Ø DCW

TO (E)ET

(E)6" Ø CHWS

(E)6" Ø CHWR

(E)6" CHWS/R

DN TO(E)CH-2

(E)4" Ø CHWR

(E)6" Ø CHWR

(E)6" Ø CHWR

(E)8" Ø CWR

(E)8" Ø CWS

(E)2" Ø DCW

CSF-1

1CH-2

CH-1

ET-CHW

(E)7'-0"x7'-0" RELIEF

AIR LOUVER W/ MOD

(E)MCC

DN TO (E)AHU-3

CHW COIL

CSF-2

AS-1

AS-3

AS-4 AS-2

(E)2" REFRIG. RELIEF VENT(E)2" REFRIG.

RELIEF VENT

(E)EMERGENCY

EXHAUST FAN

M101

4" Ø

6" Ø

6" Ø

M101

(E)18"x12 OA DUCT

(E)6" Ø CHWS

(E)4" Ø CHWS

(E)EYE WASH

(E)2" Ø CHWR

(E)2" REFRIG.

RELIEF VENT

/2

Ø

1 1/2" Ø DCW

V-CH-3CH

V-CH-3C

V-CH-2CH

V-CH-2C

V-CH-1CH V-CH-1C

(E) BACKFLOW PREVENTOR,

COOLING TOWER MAKE-UP WATER

M101

/2

Ø

(E)4" Ø CHWS

1 1/2" Ø DCW

6" Ø

4" Ø

1. SEE SHEET M001 FOR GENERAL NOTES, LEGENDS AND

ABBREVIATIONS.

GENERAL NOTES

K L

(E)6" Ø CHWR

(E)6" Ø CHWS (E)6" Ø CWR

(E)6" Ø CWS

HIGH-PERFORMANCE

BUTTERFLY VALVE

(E)EMERGENCY

EXHAUST

FAN

V-CH-3CH

V-CH-3C

2"⌀ REFRIGERANT VENT

M

N

6" Ø CHWS

6" Ø CHWR

(E)6" Ø CWS

(E)6" Ø CWR

(E)8" Ø CWS

(E)8" Ø CWR

(E)8" Ø CHWR

(E)6" Ø CHWS

V-CH-1CH

V-CH-1C

2"⌀ REFRIGERANT VENT

M

EXISTING FLOOR

DRAIN

BFP-1

PRV-1ET-CHW

CSF-1

1 1/2" Ø

TO AIR SEPARATORS

(E)EYE WASH

1 1/2" Ø

FROM EXPANSION TANK

(E)1 1/2" Ø DCW (E)1 1/2" Ø DCW

1 1/2" Ø

BACKFLOW

PREVENTOR DRAIN

(E)3/4" TO CHILLED

WATER LOOP

(E)1-1/2" CAPPED

(E)1 1/2" Ø DCW

2/20/2023

4' 8'0'

SCALE: 1/4" = 1'-0"

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:3

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

M101

NEW WORK FLOOR PLAN

08/11/23

PWHJMJJMJ

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 6 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

SCALE: 1/4" = 1'-0"

CHILLER PENTHOUSE PIPING FLOOR PLAN - NEW WORK

SCALE: 1/4" = 1'-0"

CH-3 PIPING SECTION

SCALE: 1/4" = 1'-0"

CH-1 PIPING SECTION

GENERAL STRUCTURAL NOTE NEW CHILLER SUPPORTS:

NEW CHILLERS SHALL HAVE VIBRATION DAMPENING MECHANISMS

WITHIN THE MACHINERY TO PREVENT VIBRATIONS FROM EXTENDING

INTO THE BUILDING STRUCTURE.

SCALE: 1/4" = 1'-0"

CHILLED WATER MAKEUP SECTION

(E)8" CWS

(E )6

C

W S

C W

S

EXISTING COOLING TOWER

(E)8" CHWS

(E)8" CHWR

(E )6

"C W

R

MEZZANINE

MEZZANINE

EXTERIOR

(E) 8" CWR

(E)6"CWS/R TO

(E)CH-3

6" CWS/R TO

CONDENSER WATER FLOW DIAGRAM

CHILLED WATER FLOW DIAGRAM

(E)1-1/2" DCW

(E)1-1/2" MAKE-UP

WATER

(E)DRAIN AND

OVERFLOW TO

(E)ROOF DRAIN

(TYP.)

NOT ALL VALVES ARE SHOWN. REFER TO

"M501 - MECHANICAL DETAILS" AND SPECIFICATIONS.

(E) 8" CWR BYPASS

(E) 8" CWR

(E) 8" CWR

(E) 6"

(E) 6"

(E)8" CWR

"C

W R

(E)8" CWS

EXISTING CONCRETE

PAD, TYP.

(D) BYPASS CONTROL VALVE

(E)

CHWP-5 (E)

CHWP-3

(E)

CHWP-1

(E)

CHWP-2

(E)

CHWP-4

(E)4" CHWR TO (E)AHU-4, IN BASEMENT

(E)6" CHWR TO (E)AHU-2, MEZZANINE

(E)6" CHWR TO (E)AHU-1,

MEZZANINE

(E)6" CHWR TO (E)AHU-3, MEZZANINE

(STANDBY)

(E)6" CHWS

TO AHU-1

(E)6" CHWS

TO (E)AHU-3,

MEZZANINE

(E)4" CHWS

TO (E)AHU-4,

BASEMENT

(E)6" CHWS

TO (E)AH-3

C W

S

"C

W R

6" CWS/R TO

AS-4

ET-1

CSF-2

AS-2

AS-3

(E)4" CHWR

(E)6" CHWR

(E)6" CHWR

(E)6" CHWR

4"

6"

6"

6"

(E)6" CHWR

417 GPM 417 GPM 389 GPM 417 GPM417 GPM

(E)2" CHWR

NEW ISOLATION VALVE WITH

ELECTRIC ACTUATION, CONNECT TO

EXISTING CONTROL SYSTEM, TYP.

CH-2

C W

S

C W

R

250 TONS

CONDENSER WATER: 753 GPM

CHILLED WATER: 599 GPM

6"

EXISTING

CH-3

(E )C

W S(E

)C W

R

250 TONS

(E)6"CHWS

6"

CH-1

C W

S

C W

R

EXISTING

CONCRETE PAD,

TYP.

250 TONS

(STANDBY)

6"

(E)6"CHWR

3/4"

(E)6"CHWRV-CH-2CH

V-CH-3CH

V-CH-1CH

V-CH-2C

V-CH-3C

V-CH-1C

(E)INCOMING

DOMESTIC COLD

WATER SUPPLY

(E)1-1/2" DCW TO

CHILLED WATER LOOP

CHILLED WATER MAKEUP CONNECTION DIAGRAM

BFP-1

PRV-1

1-1/4" AIR GAP & DRAIN TO

NEAREST EXISTING FLOOR DRAIN

(E)3/4" TO

EXPANSION TANK

(E)BYPASS

CH-2 CH-1

AS-1

CONDENSER WATER: 753 GPM

CHILLED WATER: 599 GPM

CONDENSER WATER: 753 GPM

CHILLED WATER: 599 GPM

SEE "CHILLER PIPING"

DETAIL

SEE "CHILLER PIPING"

DETAIL

2/20/2023

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:3

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

M301

PIPING RISER DIAGRAM

08/11/23

PWHAPTAPT

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 7 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

SCALE: NTS

CHILLED WATER & CONDENSER WATER PIPING SCHEMATIC- NEW WORK

F

TEMPERATURE GAUGE (TYP)

PRESSURE GAUGE (TYP)

DRAIN VALVE

(TYP)

EXISTING HOUSEKEEPING PAD.

MODIFY TO ACCOMMODATE NEW CHILLER.

NEOPRENE WAFFLE VIBRATION ISOLATION PADS.

PER RECOMMENDATION OF CHILLER

MANUFACTURER (TYP)

SEE NOTE 9

CHILLER

VICTAULIC

COUPLING

(TYP)

EVAPORATOR

CONDENSER

SEE NOTE 9

FLOW SWITCH (TYP)

FROM CONDENSER WATER PUMP,

SEE NOTE 10

TO COOLING TOWER,

SEE NOTE 10

TO SYSTEM,

SEE NOTE 10

FROM CHILLED WATER PUMP,

SEE NOTE 10

HIGH PERFORMANCE

BUTTERFLY VALVE

(TYP)

2" REFRIGERANT

VENT PIPING, SEE

NOTE 11

FLOOR

C W

S

C W

R

NOTES:

1. THIS DETAIL IS A GENERAL SCHEMATIC TO SHOW THE CHILLER PIPING, VALVES, GAUGES, ETC. REFER TO FLOOR PLANS FOR ACTUAL

CONNECTIONS, ORIENTATION, AND LAYOUT.

2. REPLACE CHILLED WATER AND CONDENSER WATER SUPPLY AND RETURN PIPE, VALVES, & FITTINGS AS SHOWN ON THE FLOOR PLAN.

GROOVED PIPE AND VICTAULIC COUPLINGS SHALL BE USED.

3. CONNECT CHILLER REFRIGERANT RELIEF VALVES TO NEW REFRIGERANT PURGE PIPE. PROVIDE A PIPING FLEXIBLE CONNECTION CLOSE TO

THE CHILLER. PROVIDE A TEE IN THE DISCHARGE PIPING NEAR THE CHILLER WITH A DRAIN VALVE, NIPPLE AND CAP IN THE BOTTOM OF THE

TEE.

4. ALL PIPING SHALL BE CONFIGURED TO MINIMIZE INTERFERENCE WITH THE SERVICE AND MAINTENANCE OF THE CHILLER.

5. PROVIDE AND INSTALL TEMPERATURE AND PRESSURE GAUGES WITH SNUBBERS.

6. FURNISH AND INSTALL FLOW SWITCHES AS INDICATED ON PLANS UNLESS PROVIDED ON THE CHILLER BY THE MANUFACTURER.

7. FURNISH AND INSTALL SENSORS FOR ALL DATA POINTS NOT INCLUDED BY THE CHILLER MANUFACTURER.

8. UTILIZE SUFFICIENT VICTAULIC PIPE COUPLINGS TO ALLOW REMOVAL OF PIPE AND ACCESSORIES TO PERMIT EVAPORATOR AND CONDENSER

TUBE REMOVAL. ALL OTHER PIPE SHALL BE WELDED.

9. MAINTAIN APPROPRIATE CLEARANCES PER MANUFACTURER'S RECOMMENDATION ON PIPING TO ACCOMMODATE ALL VALVES, FLEX

CONNECTIONS, AND PIPE FITTINGS. PERFORM ADDITIONAL PIPE CUTTING IF REQUIRED.

10. REFER TO SPECIFIC CHILLER PLANT DRAWINGS FOR EXACT PIPE SIZES.

11. SIZE AND INSTALL REFRIGERANT VENT PIPING AT CHILLER PER MANUFACTURER'S REQUIREMENTS.

FLEXIBLE CONNECTION

(TYP)

STRAINER

NOTE 11NOTE 11

2"

NOTE 11

F

C H

W S

C H

W R

(E)2"

STRAINER

CONTROL VALVE

CONTROL VALVE

C F

SFUNNEL FILL

WITH CAP

CHEMICAL TANK

WITH HIGH-

TEMP FILTER

BALANCING

COCK

PUMP

SUCTION

0-200

PSIG

1/2" TEST SAMPLE

OUTLET WITH CAPUNION

TYP.

C F

R

PUMP

DISCHARGE

/4

/4

DRAIN VALVE

WITH CAP

SUPPORT LEGSCONCRETE PAD

NOTES:

1. SEE SCHEDULE/SPECIFICATIONS FOR

CAPACITY AND ACCESSORIES

2. REFER TO FLOOR PLANS FOR LOCATION

BALL VALVE

CHECK VALVE

GAUGE WITH COCK

PROVIDE BASE PLATES AND

ANCHOR TO CONCRETE PAD

PRESSURE

GAUGE

E X

P A

N S

IO

N

T A

N K

PRESSURIZED

EXPANSION TANK

(BLADDER TYPE)

PRE-CHARGING

AIR CONNECTION

LOCK VALVE OPEN AND

REMOVE HANDLE

TO CHWR, SEE FLOOR

PLANS FOR SIZING

UNION

DRAIN VALVE

WITH 3/4" NPT HOSE

CONNECTION

CONCRETE EQUIPMENT PAD,

SEE FLOOR PLANS FOR SIZING,

SEE "EQUIPMENT CONCRETE PAD DETAIL" ON S001

AIR VENT

SHIELD LENGTH

4" OR

SMALLER

8"-24"

5"-6"

PIPE DIA.

12"

24"

18"

PIPE SHIELD DIMENSIONS

GALVANIZED PROTECTION

SHIELD-18 GA.,LENGTH PER

TABLE WHEN PIPING IS

INSULATED

NYLON INSERT

LOCKNUTS (TYPICAL)

GALVANIZED STEEL ALL THREADED ROD

PIPE

PIPE INSULATION

RIGID INSULATION

INSERT, EXTEND 2"

BEYOND SHIELD

NYLON INSERT

LOCKNUTS (TYPICAL)

AIR SEPARATOR

AUTOMATIC AIR VENT

1-1/2" MAKE-UP WATER

GATE VALVE

HIGH PERFORMANCE

BUTTERFLY VALVE, TYP

CHILLED WATER

RETURN

CHWR TO EXPANSION TANK, SEE

FLOOR PLANS FOR SIZING

LOCKING NUT

(TYP)

STAND (TYP)

BOLT PIPE ROLLER

TO CHANNEL (TYP)

SUPPORT NUT

(TYP)

6" STEEL CHANNEL

MAX SPACING 2'-0" OC

INSULATION

(NOT VAPOR BARRIER)

UNINSULATED PIPE

PIPE

VIBRATION ISOLATOR, TYPICAL

(WHERE APPLICABLE REFER TO

SPECIFICATIONS)

HANGER ROD

(TYP)

PIPE SADDLE, MIN

12" LENGTH

ROLLER (TYP)

WELD

PIPE SHIELD TO

PREVENT PIPE WEAR,

STRAPPED TO PIPE

1-1/2" MAKE-UP WATER

CONNECTION TO

HVAC EQUIPMENT

BACKFLOW PREVENTER INSTALLED 12" TO

60" ABOVE FINISHED FLOOR. (WATTS909LF)

CONNECT NEW CW CONNECTION TO

EXISTING CW PIPING

WATER REGULATING VALVE

(WATTS MODEL LF2235) SET

FOR 35 PSI

ROUTE TO NEAREST FLOOR

DRAIN, END 2" ABOVE FOR AIR

GAP

PROVIDE FUNNEL DRAIN

FITTING

2/20/2023

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:3

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

M501

DETAILS

08/11/23

PWHAPTJMJ

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 8 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

SCALE: NTS

CHILLER PIPING

SCALE: NTS

BY-PASS CHEMICAL SHOT FEEDER

SCALE: NTS

VERTICAL EXPANSION TANK PIPING

SCALE: NTS

CLEVIS PIPE HANGER

SCALE: NTS

AIR SEPARATOR

SCALE: NTS

LARGER DIAMETER PIPING ROLLER HANGER

SCALE: NTS

MAKE-UP WATER CONNECTION

CONTROL VALVE SCHEDULE

MARK CHILLER SERVED PIPE SERVED SIZE (IN.) MODULATION POWER

V-CH-1CH CH-1 CHILLED WATER 6" OPEN / CLOSE NOTE 1

CONDENSER WATERV-CH-1C

V-CH-2CH

V-CH-2C

V-CH-3CH

V-CH-3C

CH-1

CH-2

CH-2

CH-3

CH-3

CHILLED WATER

CONDENSER WATER

CHILLED WATER

CONDENSER WATER

6"

6"

6"

6"

6"

OPEN / CLOSE

OPEN / CLOSE

OPEN / CLOSE

OPEN / CLOSE

OPEN / CLOSE

NOTE 1

NOTE 1

NOTE 1

NOTE 1

NOTE 1

1. FURNISH 120V OR 24 VDC POWER TO CONTROL THE ACTUATOR. CONTROL VENDOR TO SELECT POWER AND

PROVIDE WIRING AND CONDUIT TO POWER AND CONTROL THE VALVE.

2/20/2023

1 2 3 4 5 6

A

B

C

D

E

PROJECT NUMBER:

DESIGNED: MODELED: CHECKED:

DATE:

DRAWING TITLE:

DRAWING NO.:

1 2 3 4 5 6

Gannett Fleming, Inc.

10200 Grand Central Ave.

Suite 310 Owings Mills • MD • 21117 t 410 • 907 • 2710

L o c a l F ile www.gannettfleming.com

PROFESSIONAL CERTIFICATION.

I HEREBY CERTIFY THAT THESE

DOCUMENTS WERE PREPARED

OR APPROVED BY ME, AND

THAT I AM A DULY LICENSED

PROFESSIONAL ARCHITECT OR

ENGINEER UNDER THE LAWS OF

THE STATE OF MARYLAND,

LICENSE NO.

EXPIRATION DATE:

/1

/2

:3

:3

A

M

A u to d e s k D o c s /0

-M D

O T

M

V A

V

M

U L /0

.1

M

V A

-G B

-C h ill e r_ M

E P

R

.r v t

M601

SCHEDULES

08/11/23

PWHAPTJMJ

067196.12

G L E

N B

U R

N

IE

B U

IL

D

IN

G

'A

C H

IL

L E

R R

E N

O V

A T

IO

N

M A

R Y

L A

N D

D E

P A

R T

M E

N T

O F

T R

A N

S P

O R

T A

T

IO

N M

O T

O R

V E

H

IC

L E

A D

M

IN

IS

T

A R

T

IO

N

R

IT

C H

IE

H

IG

H

W A

Y N

E G

L E

N B

U R

N

IE

M

D

BID/PERMIT SUBMISSION

MECHANICAL

SHEET 9 OF 15

C e n tr a l F ile B

IM

M c e n tr a l_

R .r v t

P ro je c t N u m b e r:

.1

27702

06/14/2024

WATER COOLED CHILLER SCHEDULE

MARK

CAPACITY

(TONS)

REFRIGERANT

TYPE

FLUID

TYPE

EVAPORATOR CONDENSER COMPRESSORS/CIRCUITS ELECTRICAL DATA

NPLV

(KW/TON)

SPL RATING

OPERATING

WEIGHT

(LBS)

BASIS OF DESIGN

REMARKS

EWT

(°F)

LWT

(°F)

FLOW

RATE

(GPM)

WPD

(FT WG)

FOULING

FACTOR EWT (°F)

LWT

(°F)

FLOW

RATE

(GPM)

WPD

(FT WG)

FOULING

FACTOR QTY TYPE

KW

(EA) V Ø FLA MCA MOCP

SPL

(dB)

SPL

DISTANCE MANUFACTURER MODEL

(E)CH-3 250 R-123 WATER 54 44 600.0 0.0 85 95 0.0 CENTRIFUGAL 0 460 3 0.0 0.0 0.0 0 0 0 EXISTING TO REMAIN

CH-1 250 R-134A WATER 54 44 599.0 17.2 0.00010 85 95 753.4 14.6 0.000250 1 SCREW 141 460 3 213.0 253.0 450.0 0.3707 84 3'-0" 15366 CARRIER 23RVA4A4NPJR350

CH-2 250 R-134A WATER 54 44 599.0 17.2 0.00010 85 95 753.4 14.6 0.000250 1 SCREW 141 460 3 213.0 253.0 450.0 0.3707 84 3'-0" 15366 CARRIER 23RVA4A4NPJR350

EXISTING COOLING TOWER SCHEDULE (REFERENCE ONLY)

MARK

TOTAL

COOLING

CAPACITY

(TONS) FAN QTY

FAN

HP

EWT

(°F)

LWT

(°F)

FLOW

RATE

(GPM)

WPD

(FT WG)

AMBIENT

TEMP WB

(°F)

ELECTRICAL DATA

APPROX.

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

REMARKSV Ø FLA MCA MOCP SCCR MANUFACTURER MODEL

(E)CT-1 625 2 0 95 85 °F 1500 0.0 95 460 3 0.0 0.0 0.0 0 kA - - EXISTING TO REMAIN

EXPANSION TANK SCHEDULE

MARK

TOTAL VOLUME

(GAL)

ACCEPTANCE

VOLUME (GAL)

FILL

PRESSURE

(PSI)

DIAMETER

(IN)

HEIGHT

(IN) LOCATION

APPROX. MAX.

OPERATING WEIGHT

(LBS)

BASIS OF DESIGN

REMARKSMANUFACTURER MODEL

ET-CHW 34 19 12 20" 38 PENTHOUSE 200 TACO CBX130-125

EXISTING PUMP SCHEDULE (REFERENCE ONLY)

MARK TYPE SERVICE

FLOW

(GPM)

HEAD

(FT WG)

FLUID

TEMP (°F) FLUID TYPE

MOTOR

HP RPM

ELECTRICAL

DATA

OPERATING

WEIGHT

(LBS)

BASIS OF DESIGN

REMARKSV Ø MANUFACTURER MODEL

(E)CHWP-1 CENTRIFUGAL (E)AHU-1 417 45 54 CHILLED WATER 7.5 1750 460 3 - - - 1

(E)CHWP-2 CENTRIFUGAL (E)AHU-2 389 45 54 CHILLED WATER 7.5 1750 460 3 - - - 1

(E)CHWP-3 CENTRIFUGAL (E)AHU-3 417 45 54 CHILLED WATER 7.5 1750 460 3 - - - 1

(E)CHWP-4 CENTRIFUGAL (E)AHU-5 417 45 54 CHILLED WATER 7.5 1750 460 3 - - - 1

(E)CHWP-5 CENTRIFUGAL STANDBY 417 45 54 CHILLED WATER 7.5 1750 460 3 - - - 1

(E)CWP-1 CENTRIFUGAL (E)CT-1 1500 50 95 CONDENSING WATER 30 1770 460 3 - - - 1

(E)CWP-2 CENTRIFUGAL (E)CT-1 1500 50 95 CONDENSING WATER 30 1770 460 3 - - - 1

AIR SEPARATOR SCHEDULE

MARK

MAX

FLOW

(GPM)

CONNECTION

SIZE (IN) STRAINER

MAX WPD

(FT/H20)

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

REMARKSMANUFACTURER MODEL

AS-1 700 6" STAINLESS STEEL MESH (1/4" x 3/4") 0.8 580 BELL AND GOSSETT R-6F 1

AS-2 700 6" STAINLESS STEEL MESH (1/4" x 3/4") 0.8 580 BELL AND GOSSETT R-6F 1

AS-3 700 6" STAINLESS STEEL MESH (1/4" x 3/4") 0.8 580 BELL AND GOSSETT R-6F 1

AS-4 300 4" STAINLESS STEEL MESH (1/4" x 3/4") 0.8 280 BELL AND GOSSETT R-4F 1

CHEMICAL SHOT FEEDER SCHEDULE

MARK

TANK

VOL.

(GAL)

MAX

PRESSURE

(PSI)

MAX TEMP.

(F)

APPROX.

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

REMARKSMANUFACTURER MODEL

CSF-1 10.0 300 200 120 NEPTUNE DBF-10HP

CSF-2 10.0 300 200 120 NEPTUNE DBF-10HP

PLUMBING BACKFLOW PREVENTER SCHEDULE

MARK SERVICE

FLOW

(GPM)

SIZE

(IN)

VELOCITY

(FPS)

MAX PD

(PSI) TYPE

APPROX.

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

REMARKSMANUFACTURER MODEL

BFP-1 CHILLED WATER LOOP 30 1 1/4" 6 15.00 REDUCED PRESSURE ZONE ASSEMBLY 16 WATTS LF909 1, 2

1. REDUCED PRESSURE ZONE ASSEMBLY INCLUDES TWO (2) INLINE INDEPENDENT CHECK VALVES WITH AN INTERMEDIATE RELIEF VALVE AND SHALL COMPLY WITH NSF 61 AND ASSE 1013.

2. PROVIDE MANUFACTURER'S AIR GAP DEVICE.

1. PROVIDE MANUFACTURER'S AUTOMATIC AIR VENT ACCESSORY.

PRESSURE REDUCING VALVE SCHEDULE

MARK SERVICE

FLOW

(GPM)

SIZE

(IN)

VELOCITY

(FPS)

MAX PD

(PSI) TYPE

APPROX.

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

REMARKS

MANUFACTU

RER MODEL

PRV-1 CHILLED WATER LOOP 30 1 1/2" 3 5.00 PRESSURE REDUCING VALVE 14 WATTS LF2235

1. EXISTING TO REMAIN, BALANCE TO INDICATED FLOW RATE.

EXISTING

CH-3

CH-2

CH-1

CONTROL

PANEL

CONTROL

PANEL

CONTROL

PANEL

V-CH-3CH

V-CH-1CH

CHWS

CHWR

CHWS

CHWS

CHWR

CHWR

CWS

CWS

CWS

CWR

CWR

CWR

(E)CHWP-5

(E)CHWP-3

(E)CHWP-1

(E)CHWP-2

(E)CHWP-4

CHWR

CHWR

CHWR

CHWR

V-CH-1C

V-CH-3C

CHWS

(E)CWP-2

(E)CWP-1

(E)COOLING

TOWER

FSFM T

T

FSFM

T

T

FM T

T

V-CH-2CH

V-CH-2C

FS

FS

FS

FS

MOTOR VEHICLE ADMINISTRATION EMCS SEQUENCES OF OPERATION

FOR THE HEADQUARTERS BUILDING – CHILLER REPLACEMENT

1. The MVA Headquarters building in Glen Burnie MD has an existing building automation system (BAS). The existing BAS is Schneider Electric Eco-Struxture 2.0 Installed in 2019. This project is to replace two of three existing water cooled chillers. Existing pumping systems to remain as is. The existing control systems will be modified as required to provide new control functions. Control functions not affected by these upgrades do not need to be modified.

2. New controls will be the latest version of Schneider Electric Eco-Struxture compatible with the existing system. Contact for current control contractor is:

John Beahm, Sales Operation Manager, Control Sources LLC. Cell: 410.365.6009

Fax: 410.574.6300 Email: jbeahm@controlsources.biz

1. Chilled Water Plant Operating Modes

a. The EMCS shall enable the chilled water plant when the outside air dry-bulb temperature is above 48°F (ADJ) for 30 minutes

(ADJ), and there is a request for cooling.

b. A request for cooling shall be initiated in each AHU when the CHW Valve is 100% open (ADJ) for ten minutes (ADJ), and the discharge air is 2°F (ADJ) above set point for ten minutes (ADJ).

c. A request for cooling shall be cleared when the CHW Valve is 0% open (ADJ) for ten (ADJ) minutes or when the AHU is de-energized.

d. The EMCS shall disable the chilled water plant when the outside air dry-bulb temperature is below 45°F (ADJ) for 60 minutes

(ADJ), or there are no requests for cooling for 60 minutes (ADJ).

e. The OWS shall include provisions to override automatic operation and manually enable or disable chilled water plant operating modes based on a single graphic command.

2. Chiller Lead / Lag Designation Modes

a. The EMCS shall use lead / lag chiller designations to equalize runtime during staging. Chillers shall not be started and stopped for the sole purpose of maintaining equalized runtime.

b. If a chiller failure is detected, that chiller will be removed from the staging sequence until the failure is manually reset at the OWS.

c. The facility operator shall have the provisions to make one or more chillers unavailable to staging sequence for purposes of performing routine maintenance.

d. The OWS graphics shall clearly indicate the calculated staging sequence, as well as any chillers that are either unavailable or need to be reset.

3. Chilled Water Supply Temperature Set Point Modes

a. Chilled water temperature set point shall be reset as follows:

Outdoor Air Temperature Dry-Bulb Chilled Water Set Point

50°F (ADJ) 49°F (ADJ)

85°F (ADJ) 44°F (ADJ)

b. All chillers shall operate at the same chilled water temperature set point, and all chilled water temperatures listed are leaving or supply water temperatures.

4. Chiller Control Modes

a. The EMCS shall enable and disable chillers as required by the chiller staging sequence.

b. The EMCS shall be connected to each respective chiller interface and monitor all chiller operating parameters which are currently connected to the DDC systems in the Headquarters Building. All points will be displayed on the OWS graphics.

c. All factory-furnished interlocks, time delays, and load controls included with the chiller control panel to maintain the integrity of the chiller shall remain intact.

d. The EMCS shall monitor and confirm chiller status through the local chiller controller.

e. If a chiller failure is detected, the EMCS shall initiate an alarm at the OWS,…