This document contains an Infection Control Risk Assessment (ICRA) permit and details of a federal construction contract opportunity. The ICRA permit outlines four classes of construction risk and guidelines for infection control during renovation work at Phoenix Indian Medical Center. The solicitation seeks proposals for a firm fixed price construction contract valued between $1,000,000 to $5,000,000. The scope of work includes asbestos abatement, flooring replacement, mechanical and HVAC improvements, painting, roof replacement, and fire system work at Phoenix Indian Medical Center. Offerors must register in SAM and the period of performance is 300 calendar days from notice to proceed. The solicitation will use LPTA evaluation and be procured as an RFP by the Department of Health and Human Services Indian Health Service.

View the file

Other files

File Type Posted
B04 Pre-Proposal Inquiries (23R00001) (85-87).pdf PDF
B05 75H70123R00001 Amendment A000008.pdf PDF
B05 75H70123R00001 Amendment A000007.pdf PDF
Attachment J17 - WD AZ20230031 2023.01.06.pdf PDF
B05 75H70123R00001 Amendment A000006.pdf PDF
B04 Pre-Proposal Inquiries (23R00001) (1-84).pdf PDF
Attachment J01 R2 - SOW - PIMC MI Renovations (CHANGES IN RED) 2022.12.05.pdf PDF
Attachment J01 R2 - SOW - PIMC MI Renovations FINAL 2022.12.05.pdf PDF
B05 75H70123R00001 Amendment A000005.pdf PDF
Attachment J12 R1 - Micro Lab Renovation Schematics.pdf PDF
Attachment J01 R1 - SOW - PIMC MI Renovations (changes in red) 2022.11.28.docx DOCX document
Attachment J02 R1 - PIMC Campus Map.pdf PDF
B04 Pre-Proposal Inquiries (23R00001) 1-29.pdf PDF
Attachment J04 R1 - Behavioral Health Schematics.pdf PDF
Attachment J03 R1 - 3rd Floor Nurse Station Replacement.pdf PDF
B05 75H70123R00001 Amendment A000004.pdf PDF
Attachment J06 R1 - Main Tower Maintenance Areas.pdf PDF
Attachment J26 - Asbestos Abatement Specification.pdf PDF
Attachment J01 R1 - SOW - PIMC MI Renovations FINAL 2022.11.28.pdf PDF
Attachment J24 - Hospital Exterior Painting.pdf PDF
Attachment J25 - Buildings 5 and 6 Asbestos Survey.pdf PDF
Attachment J10 R1 - Fire Sprinkler Replacement and Testing.pdf PDF
Attachment J05 R1 - Outpatient Floor Plans.pdf PDF
B05 75H70123R00001 Amendment A000003.pdf PDF
B05 75H70123R00001 Amendment A000002.pdf PDF
B04 Pre-Proposal Inquiries (23R00001).pdf PDF
Attachment J19 - Self Performed Calculation Sheet (Amend A00002).pdf PDF
B03 Site Visit Agenda and Sign-in (23R00001).pdf PDF
B05 75H70123R00001 Amendment A000001.pdf PDF
Attachment J17 - WD AZ20220031 Mod 8 2022.10.28.pdf PDF
B01 RFP 75H701-23-R-00001.pdf PDF
Attachment J04 - Behavioral Health Schematics.pdf PDF
Attachment J03 - 3rd Floor Nurse Station Replacement.pdf PDF
Attachment J19 - Self Performed Calculation Sheet (Construction).docx DOCX document
Attachment J12 - Micro Lab Renovation Schematics.pdf PDF
Attachment J17 - WD AZ20220031 Mod 7 2022.10.07.pdf PDF
Attachment J06 - Main Tower Maintenance Areas.pdf PDF
Attachment J09 - ED Waiting Room Ventilation.pdf PDF
Attachment J23 - Financial Institution Reference Sheet.docx DOCX document
Attachment J08 - CSR Schematics.pdf PDF
Attachment J21 - Past Performance Questionnaire.docx DOCX document
Attachment J10 - Fire Sprinkler Replacement and Testing.pdf PDF
Attachment J20 - Company Specialized Experience Form.docx DOCX document
Attachment J01 - SOW - PIMC MI Renovations 2022.10.25.pdf PDF
Attachment J22 - Key Personnel Resume Form.docx DOCX document
Attachment J14 - Phoenix Solid Waste Access and Enclosure Standard Details.pdf PDF
Attachment J07 - PIMC Asbestos Survey Feb 2003.pdf PDF
Attachment J13 - Trash Enclosure Location.pdf PDF
Attachment J18 - 2022 Exemption Letter for a Qualifying Hospital.pdf PDF
Attachment J11 - PIMC 2021 Fire Alarm Testing Report.pdf PDF
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 | P a g e

Infection Control Risk Assessment Permit

Work Location/Description:

Start Date End Date:

Project Manager Name / Phone Number :

TYPE A:

TYPE B:

TYPE C:

TYPE D:

Low Risk

Medium Risk

High Risk

Highest Risk

Identify Any Adjacent High Risk Areas:

Above Below Front Behind Lateral NA

CLASS 1 1 Minimize raising dust from construction operations 2 Immediately replace any ceiling tile displaced for visual inspection.

1 Minor demolition for remodeling.

CLASS II 1 Minimize raising dust by water misting work surfaces to control dust while cutting.

2 Seal unused doors with duct tape.

3 Block off and seal air vents with plastic or impervious material.

4 Wipe surfaces with cleaner/disinfectant.

5 Isolate HVAC system in areas where work is being performed

1 Contain construction waste prior to transport in tightly covered containers.

2 Wet mop and/or vacuum with HEPA-filtered vacuum prior to leaving area.

3 Remove critical barrier(s) carefully to minimize spread of dirt/debris.

4 Use hospital-approved disinfectant 5 Place dust mat at entrance and exit of work area.

7 Restore HVAC when work completed.

CLASS III 1 Infection control permit prior to construction.

2 Isolate HVAC system in area of work to prevent contamination of the duct system.

3 Complete all critical barriers or implement control cube or other method prior to work.

4 Maintain negative air pressure within work environment with HEPA-equipment.

5 Do not remove barriers from site until completed project is checked by infection Control.

6 Environmental Services thoroughly cleans.

1 Vacuum work with HEPA-filtered vacuum.

2 Wet mop with hospital approved cleaner/disinfectant.

3 Remove barrier materials carefully to minimize spread of dirt/debris.

4 Contain construction waste prior to transport in tightly covered containers.

5 Cover transport receptacles or carts.

6 Tape coverings.

7 When complete, restore HVAC system where work was performed.

CLASS IV 1 Obtain Infection Control permit prior to start of construction.

2 Isolate HVAC system in work area to prevent contamination of duct system.

3 Complete all critical barriers or use control cube method prior to start of construction.

4 Maintain negative air pressure within work site – utilizing HEPA-equipped air filtration units.

5 Seal holes, pipes, conduits, and punctures.

6 Construct anteroom and require all personnel to pass through this room so they can be vacuumed off using a HEPA vacuum cleaner before leaving work site, or wear protective paper coveralls (bunny suit) that is removed each time leaving the work site.

7 Require all personnel entering work site to wear shoe covers.

1 Do not remove barriers from work site until project is checked by Infection Control; and is thoroughly cleaned by environmental services.

2 Vacuum work area with HEPA-filtered vacuums.

3 Wet mop with hospital–approved disinfectant.

4 Remove barrier(s) carefully to minimize spread of dirt/debris associated with construction.

5 Contain construction waste prior to transport in tightly covered containers.

6 Cover transport receptacles or cart.

7 Tape coverings.

8 At completion, restore HVAC system where work was performed.

Permit Requested By Signature / Date Infection Control Signature / Date

Attachment J15. ICRA Permit PH22PH01H6, PIMC M&I Renovations

2 | P a g e

Class Determination

RISK GROUP TYPE A TYPE B TYPE C TYPE D

LOW Risk Class 1 Class II Class II Class III/IV

MEDIUM Risk Class 1 Class II Class III Class IV

HIGH Risk Class 1 Class II Class III/IV Class IV

HIGHEST Risk Class II Class III/IV Class III/IV Class IV

Risk Groups

Low Risk

Office areas, Maintenance, Housekeeping, Storage Areas, Stairwells, Storage buildings, Warehouse, Library, Meeting Rooms, Staff Lounges, Empty Patient Rooms

Medium Risk Clinical areas, Physical Therapy, Radiology, Dental, Behavioral Health, Same Day Surgery, Outpatient Services, Cafeteria, Snack Bar

High Risk Emergency Room, Laboratories, Pharmacy, Occupied Patient Rooms, Inpatient Departments, Food Preparation Areas, Nursery, PACU, Above Ceiling Work in Open Interstitial Space within 100 Linear Feet of Group III/IV, Labor and Delivery, Medication Rooms.

Highest Risk Sterile Areas, Segregated Compound Area (IV Room), Containment Segregated Compounding Area (Chemo), Airborne Isolation, Positive Pressure Rooms, Sterile Supply, Operating Rooms, C-Section Operating Rooms, Endoscopy, Intensive Care, Oncology Infusion.

Project Type

TYPE A Inspection and non-invasive activities

• Removal of ceiling tiles for visual inspection only ( limited to one tile per 50 square feet)

• Painting, not sanding

• Wallcovering, electrical trim work, minor plumbing, and activities that do not general dust or require cutting of walls or access to ceiling other than for visual inspection

TYPE B Small-scale, short duration activities that create minimal dust

• Installation of telephone and computer cabling

• Access to chase spaces

• Cutting of walls or ceiling where dust migration can be controlled

TYPE C Work that generates moderate to high level of dust or requires demolition or removal of any fixed building components or assemblies

• Sanding of walls for painting or wall coverings

• Removal of floor covering, ceiling tiles, and case work

• New wall construction

• Minor duct work or electrical work above ceiling

• Major cabling activities

• Activities that cannot be completed in a single work shift

TYPE D Major demolition and construction projects

• Activities that require consecutive work shifts

• Required heavy demolition or removal of a complete cabling system

• New Construction

Blank Page

Work LocationDescription:
Start Date:
End Date:
Project Manager Name Phone Number Row1: Brandon Groh, 602-364-5063
fill_4:
Check Box1: Off
Check Box2: Off
Check Box3: Off
Check Box4: Off
Check Box5: Off
Check Box6: Off
Check Box7: Off
Check Box8: Off
Check Box9: Off
Check Box10: Off
Check Box11: Off
Check Box12: Off
Check Box13: Off
Check Box14: Off

File details come from the government source that posted it. Updated .