Attachment J11 - PIMC 2021 Fire Alarm Testing Report.pdf

PDF 2 MB Posted

Attached to
PIMC Maintenance & Improvements (M&I) Renovations
Solicitation number
75H701-23-R-00001
Issued by

About this file

This solicitation notice is for a construction project to complete maintenance and improvement renovations at the Phoenix Indian Medical Center in Phoenix, Arizona. The scope of work includes asbestos abatement, replacement of flooring, countertops, and furniture, mechanical HVAC work, painting, roof replacement, and fire system upgrades. The period of performance is 300 calendar days from notice to proceed. The contract value is estimated between $1 million to $5 million and will be a firm fixed price contract awarded using lowest price technically acceptable criteria. A site visit is scheduled as detailed in the solicitation. The Department of Health and Human Services Indian Health Service is the contracting agency.

View the file

Other files

File Type Posted
B04 Pre-Proposal Inquiries (23R00001) (85-87).pdf PDF
B05 75H70123R00001 Amendment A000008.pdf PDF
B05 75H70123R00001 Amendment A000007.pdf PDF
Attachment J17 - WD AZ20230031 2023.01.06.pdf PDF
B05 75H70123R00001 Amendment A000006.pdf PDF
B04 Pre-Proposal Inquiries (23R00001) (1-84).pdf PDF
Attachment J01 R2 - SOW - PIMC MI Renovations (CHANGES IN RED) 2022.12.05.pdf PDF
Attachment J01 R2 - SOW - PIMC MI Renovations FINAL 2022.12.05.pdf PDF
B05 75H70123R00001 Amendment A000005.pdf PDF
Attachment J12 R1 - Micro Lab Renovation Schematics.pdf PDF
Attachment J01 R1 - SOW - PIMC MI Renovations (changes in red) 2022.11.28.docx DOCX document
Attachment J02 R1 - PIMC Campus Map.pdf PDF
B04 Pre-Proposal Inquiries (23R00001) 1-29.pdf PDF
Attachment J04 R1 - Behavioral Health Schematics.pdf PDF
Attachment J03 R1 - 3rd Floor Nurse Station Replacement.pdf PDF
B05 75H70123R00001 Amendment A000004.pdf PDF
Attachment J06 R1 - Main Tower Maintenance Areas.pdf PDF
Attachment J26 - Asbestos Abatement Specification.pdf PDF
Attachment J01 R1 - SOW - PIMC MI Renovations FINAL 2022.11.28.pdf PDF
Attachment J24 - Hospital Exterior Painting.pdf PDF
Attachment J25 - Buildings 5 and 6 Asbestos Survey.pdf PDF
Attachment J10 R1 - Fire Sprinkler Replacement and Testing.pdf PDF
Attachment J05 R1 - Outpatient Floor Plans.pdf PDF
B05 75H70123R00001 Amendment A000003.pdf PDF
B05 75H70123R00001 Amendment A000002.pdf PDF
B04 Pre-Proposal Inquiries (23R00001).pdf PDF
Attachment J19 - Self Performed Calculation Sheet (Amend A00002).pdf PDF
B03 Site Visit Agenda and Sign-in (23R00001).pdf PDF
B05 75H70123R00001 Amendment A000001.pdf PDF
Attachment J17 - WD AZ20220031 Mod 8 2022.10.28.pdf PDF
B01 RFP 75H701-23-R-00001.pdf PDF
Attachment J04 - Behavioral Health Schematics.pdf PDF
Attachment J03 - 3rd Floor Nurse Station Replacement.pdf PDF
Attachment J19 - Self Performed Calculation Sheet (Construction).docx DOCX document
Attachment J12 - Micro Lab Renovation Schematics.pdf PDF
Attachment J17 - WD AZ20220031 Mod 7 2022.10.07.pdf PDF
Attachment J06 - Main Tower Maintenance Areas.pdf PDF
Attachment J09 - ED Waiting Room Ventilation.pdf PDF
Attachment J23 - Financial Institution Reference Sheet.docx DOCX document
Attachment J08 - CSR Schematics.pdf PDF
Attachment J21 - Past Performance Questionnaire.docx DOCX document
Attachment J10 - Fire Sprinkler Replacement and Testing.pdf PDF
Attachment J20 - Company Specialized Experience Form.docx DOCX document
Attachment J01 - SOW - PIMC MI Renovations 2022.10.25.pdf PDF
Attachment J15 - ICRA Permit.pdf PDF
Attachment J22 - Key Personnel Resume Form.docx DOCX document
Attachment J14 - Phoenix Solid Waste Access and Enclosure Standard Details.pdf PDF
Attachment J07 - PIMC Asbestos Survey Feb 2003.pdf PDF
Attachment J13 - Trash Enclosure Location.pdf PDF
Attachment J18 - 2022 Exemption Letter for a Qualifying Hospital.pdf PDF
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System

Inspection Certificate

For

Phoenix Indian Medical

4212 N 16th S

Phoenix, AZ 85253

Inspection Date

Apr 14, 2021

Tested to NFPA 72 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

IT IS THE RESPONSIBILITY OF THE PROPERTY OWNER OR

DESIGNATED REPRESENTATIVE THAT REQUESTED THIS

INSPECTION TO REVIEW REPORTS AND CORRECT ANY

DEFICIENCIES NOTED.

Building: Phoenix Indian Medical Company: Western States Fire Protection

Contact: Warren Yonnie Contact: Luciano lopez

Title: N/A Title: Inspector

Attachment J11 - PIMC 2021 Fire Alarm Testing Report

Western States Fire Protection 1 04/20/2021

Executive Summary Generated by: BuildingReports.com

Building Information

Building: Phoenix Indian Medical Contact: Warren Yonnie

Address: 4212 N 16th S Phone: 928-551-3562

Address: Fax:

City/State/Zip: Phoenix, AZ 85253 Mobile:

Country: United States of America Email: warren.yonnie@ihs.gov

Inspection Performed By

Company: Western States Fire Protection Inspector: Luciano lopez

Address: 4346 East Elwood St. Phone: 480.259.7984

Address: Suite 100 Fax:

City/State/Zip: Phoenix, Arizona 85040 Mobile:

Country: United States of America Email: luciano.lopez@wsfp.us

System Control Unit Manufacturer: Notifier Inspection Date: 03/20/2021 IDC Style:

Model Number: NFS-3030D Install Date: 03/20/2015 SLC Style:

Software Version: Version Date: 03/20/2015 NAC Style:

Location: Ground Fire Alarm Control Room Current Protection: Breaker

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time

Western States Fire Protection 2 04/20/2021

Inspection Summary

Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty %

Sound Test 10 2.21% 10 100.00% 10 100.00% 0 0%

Control 51 11.28% 51 100.00% 42 82.35% 9 17.65%

Initiating 391 86.50% 391 100.00% 391 100.00% 0 0%

Totals 452 100% 452 100.00% 443 98.01% 9 1.99%

Certification

Company: Western States Fire Protection Building: Phoenix Indian Medical

Inspector: Luciano lopez Contact: Warren Yonnie

Signed: Mar 20, 2021 3:12:35 PM Signed:

Western States Fire Protection 3 04/20/2021

Discrepancy Report Generated by: BuildingReports.com

Building: Phoenix Indian Medical Control Panel: 3 - Fire-Lite

MS-9050UD

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12

More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf

Pull Station Notifier NBG-12LX 10/03/2011 16

More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf

ScanID Location Problem Address Reference

Control

Battery

62607986 Dental Clinic Southeast Riser Room Failed Test 3 NFPA72 Table

14.4.3.2 (9a)(1)

62607987 Dental Clinic Southeast Riser Room Failed Test 3 NFPA72 Table

14.4.3.2 (9a)(1)

Code References NFPA72 Table

14.4.3.2 (9a)(1)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations

Western States Fire Protection 4 04/20/2021

Building: Phoenix Indian Medical Control Panel: 4

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12

More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf

Pull Station Notifier NBG-12LX 10/03/2011 16

More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf

ScanID Location Problem Address Reference

Control

Battery

62607977 Dental Clinic Annex Southeast Electrical

Room

Failed Test 4 NFPA72 Table

14.4.3.2 (9a)(1)

62607978 Dental Clinic Annex Southeast Electrical

Room

Failed Test 4 NFPA72 Table

14.4.3.2 (9a)(1)

Code References NFPA72 Table

14.4.3.2 (9a)(1)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment

Western States Fire Protection 5 04/20/2021

Building: Phoenix Indian Medical Control Panel: 5 - Edwards 2412

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12

More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf

Pull Station Notifier NBG-12LX 10/03/2011 16

More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf

ScanID Location Problem Address Reference

Control

Battery

62607981 Behavioral Health Bldg 5 By Room C-2 Failed Test 5 NFPA72 Table

14.4.3.2 (9a)(1)

62607982 Behavioral Health Bldg 5 By Room C-2 Failed Test 5 NFPA72 Table

14.4.3.2 (9a)(1)

Code References NFPA72 Table

14.4.3.2 (9a)(1)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment

Western States Fire Protection 6 04/20/2021

Control Panel: 8 - Fire-Lite

MS-5024UD

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12

More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf

Pull Station Notifier NBG-12LX 10/03/2011 16

More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf

ScanID Location Problem Address Reference

Control

Control Panel

40PIF-82144 Pathology Services Office By East Exit Damaged/Worn 8 NFPA72 14.2.2.2.2

Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.

Western States Fire Protection 7 04/20/2021

Control Panel: 9 - Faraday

MPC-1000

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12

More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf

Pull Station Notifier NBG-12LX 10/03/2011 16

More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf

ScanID Location Problem Address Reference

Control

Battery

62607966 Warehouse Northeast Failed Test 9 NFPA72 Table

14.4.3.2 (9a)(1)

62607967 Warehouse Northeast Failed Test 9 NFPA72 Table

14.4.3.2 (9a)(1)

Code References NFPA72 Table

14.4.3.2 (9a)(1)

Batteries shall be replaced in accordance with the recommendations of the alarm equipment

Western States Fire Protection 8 04/20/2021

Proposed Solutions Report

Building: Phoenix Indian Medical Control Panel: 3 - Fire-Lite MS-9050UD

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Control

Battery

62607986 Dental Clinic Southeast Riser Room Replace Battery

T/M

62607987 Dental Clinic Southeast Riser Room Replace Battery

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

62607977 Dental Clinic Annex Southeast Electrical

Room

Replace Battery

62607978 Dental Clinic Annex Southeast Electrical

Room

Replace Battery

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

62607981 Behavioral Health Bldg 5 By Room C-2 Replace Battery

62607982 Behavioral Health Bldg 5 By Room C-2 Replace Battery

Building: Phoenix Indian Medical Control Panel: 8 - Fire-Lite MS-5024UD

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

Western States Fire Protection 9 04/20/2021

Control Panel

40PIF-82144 Pathology Services Office By East Exit Investigate MS-5024UD T/M

Building: Phoenix Indian Medical Control Panel: 9 - Faraday MPC-1000

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a

62607966 Warehouse Northeast Replace Battery

62607967 Warehouse Northeast Replace Battery

PO #: (none) T/M

Western States Fire Protection 10 04/20/2021

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note Women’s Clinic Reports Back To Main Fire Panel And The Disables For The Main Building Are The Same.

Dental Annex Reports To The Panel In The Basement Of Building 1. You need To Disable N01L01M034 For

The NACS At Dental Annex.

PEDS And The Chiller Plants AV’s Are Disabled From The Main Panel.

Did Not Set Off AV’s At Main Hospital Per Customer.

Recommend Adding FACP Sign To All Building Doors Where The Panel Is Located.

Building: Phoenix Indian Medical Control Panel: n/a

ScanID Note Device Type Location Comment

0003 2 Sound Test Dental Clinic Annex Passed

Reports Back To Building 1 Panel In Basement. Need To Disable Booster N01L01M034 When Testing.

0009 3 Sound Test PEDS Passed

Building Reports Back To Main Panel. Need To Enable Main Panel To Test AV’s.

Western States Fire Protection 11 04/20/2021

Control Panel: 1 - Notifier

NFS-3030D

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Initiating 40PIF-82796 4 Duct Detector 1st Hallway Near Pharmacy Passed

Reports as alarm

40PIF-82797 5 Duct Detector 1st Hallway Near Pharmacy Passed

Reports as alarm

40PIF-82805 6 Duct Detector 1st Hallway X-Ray Files Passed

Reports as alarm

Western States Fire Protection 12 04/20/2021

Building: Phoenix Indian Medical Control Panel: 2 - FCI 7200

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Initiating 40PIF-82625 7 Pull Station Specialty Services Waiting Area Passed

Recommend Replacing Per Manufacturer.

40PIF-82627 8 Pull Station Specialty Services North Exit Passed

Recommend Replacing Per Manufacturer.

Western States Fire Protection 13 04/20/2021

Control Panel: 6 - Notifier

NFS-3030D

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Control 62607974 9 Control Panel NIH Bldg 1 West Basement Passed

Dental Annex And Building 1 Report To This Panel. Disable N01L01M034 For Dental Annex. Pull Nacs For

Building 1.

Western States Fire Protection 14 04/20/2021

Control Panel: 7 - Fire-Lite

SFP-1024

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Initiating 40PIF-82579 10 Pull Station PCMC Center Corridor Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82578 11 Pull Station PCMC West Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82580 12 Pull Station PCMC East Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82584 13 Pull Station PCMC North Exit To Registration Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82581 14 Pull Station PCMC Northside East Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82582 15 Pull Station PCMC Northside Northwest Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

Western States Fire Protection 15 04/20/2021

MS-5024UD

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Control 40PIF-82144 16 Control Panel Pathology Services Office By East Exit Damaged/Worn

Terminal To Transformer Is Defective. Panel Losses Power Intermittently. See Pictures

Initiating 40PIF-82558 17 Pull Station Pathology Services Office East Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

40PIF-82559 18 Pull Station Pathology Services West Exit Passed

Recommend Replacing Pull Station Per Manufacturer.

Western States Fire Protection 16 04/20/2021

Inspection & Testing

NFS-3030D

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed

Control

Annunciator 1st East Main Entrance Office Inspected 6:19:05 AM 03/20/2021

Annunciator NIH Bldg 1 North Exit Inspected 8:20:29 AM 04/13/2021

Battery 1st South Electrical Closet Near Elevators Inspected 6:13:44 AM 03/20/2021

Battery 1st South Electrical Closet Near Elevators Inspected 6:14:38 AM 03/20/2021

Battery 2nd South Electrical Closet Near Elevators Inspected 6:27:27 AM 03/20/2021

Battery 2nd South Electrical Closet Near Elevators New 6:35:33 AM 03/20/2021

Battery Ground Fire Alarm Control Room Inspected 5:59:31 AM 03/20/2021

Battery Ground Fire Alarm Control Room Inspected 6:00:32 AM 03/20/2021

Battery PEDS North Riser Room Inspected 8:16:03 AM 04/14/2021

Battery PEDS North Riser Room Inspected 8:16:44 AM 04/14/2021

Control Panel Ground Fire Alarm Control Room Inspected 6:01:18 AM 03/20/2021

Power Supply 1st South Electrical Closet Near Elevators Inspected 6:11:28 AM 03/20/2021

Power Supply 2nd South Electrical Closet Near Elevators Inspected 6:27:00 AM 03/20/2021

Power Supply PEDS North Riser Room Inspected 8:15:05 AM 04/14/2021

Initiating

Duct Detector 1st Hallway Near Pharmacy Tested 7:43:48 AM 03/20/2021

Duct Detector 1st Hallway Near Pharmacy Tested 7:57:56 AM 03/20/2021

Duct Detector 1st Hallway X-Ray Files Tested 7:58:32 AM 03/20/2021

Duct Detector 1st Hallway X-Ray Files Tested 8:01:39 AM 03/20/2021

Duct Detector 4th Room 4-35 Back Corner Of Room Tested 8:28:00 AM 03/20/2021

Duct Detector 5th Office 5-28 Tested 8:43:22 AM 03/20/2021

Duct Detector 5th Room 5-27 Tested 8:36:38 AM 03/20/2021

Duct Detector Roof East Tested 9:19:41 AM 03/20/2021

Duct Detector Ground AHU/Riser Room Tested 7:27:18 AM 03/20/2021

Duct Detector Ground AHU/Riser Room Tested 7:27:23 AM 03/20/2021

Duct Detector Ground Kitchen AHU 10 Tested 7:31:02 AM 03/20/2021

Duct Detector Women’s Clinic West Corridor Tested 10:09:43 AM 04/13/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:03:43 PM 03/20/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:05:24 PM 03/20/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:05:48 PM 03/20/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:06:14 PM 03/20/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:06:36 PM 03/20/2021

Heat Detector Penthouse Elevator Control Room Inspected 1:06:52 PM 03/20/2021

Heat Detector Chiller Northwest Mezzanine Inspected 8:49:41 AM 04/14/2021

Western States Fire Protection 17 04/20/2021

Heat Detector Chiller Southeast Mezzanine Inspected 8:46:15 AM 04/14/2021

Heat Detector Chiller Southwest Mezzanine Inspected 8:48:50 AM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:48:26 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:49:43 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:49:54 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:03 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:12 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:21 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:31 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:40 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:48 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:50:58 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:51:08 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:51:19 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:51:30 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:51:39 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:51:48 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:00 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:09 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:17 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:25 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:33 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:50 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:52:59 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:53:07 PM 04/14/2021

Heat Detector Warehouse High Heat Inspected 12:53:16 PM 04/14/2021

Pull Station 1st East Central Hall By PEDS Tested 8:22:24 AM 03/20/2021

Pull Station 1st East Main Lobby Information Tested 8:14:55 AM 03/20/2021

Pull Station 1st East Main Lobby Tested 8:15:55 AM 03/20/2021

Pull Station 1st North Exit By Security Tested 7:57:15 AM 03/20/2021

Pull Station 1st Northwest Lab Exit Tested 7:37:04 AM 03/20/2021

Pull Station 1st Southeast By Conference Room Tested 8:16:52 AM 03/20/2021

Pull Station 1st Southwest OR Minor OP Exit Tested 7:29:57 AM 03/20/2021

Pull Station 1st West OR Exit Tested 7:32:19 AM 03/20/2021

Pull Station 1st Central Hall By Pharmacy Tested 8:03:29 AM 03/20/2021

Pull Station 1st Exit By ER Lobby Tested 8:28:35 AM 03/20/2021

Pull Station 2nd North Hall ICU BY 2-29 Tested 8:45:09 AM 03/20/2021

Pull Station 2nd South Hall ICU BY 2-42 Tested 9:04:29 AM 03/20/2021

Pull Station 2nd Southeast Hall By Stairs Tested 9:09:29 AM 03/20/2021

Pull Station 2nd Southwest ICU By Stairs Tested 9:00:24 AM 03/20/2021

Pull Station 2nd Hall By Stairs Tested 8:40:51 AM 03/20/2021

Pull Station 3rd North Hall Near Stairwell A Tested 11:04:07 AM 03/20/2021

Pull Station 3rd Southeast Hall Near Stairwell B Tested 10:51:39 AM 03/20/2021

Pull Station 3rd Southwest Hall Near Stairs Tested 10:43:48 AM 03/20/2021

Pull Station 4th North Hall Near Stair A Tested 11:45:04 AM 03/20/2021

Pull Station 4th Northwest Nurses Station Tested 11:12:28 AM 03/20/2021

Pull Station 4th South Hall Near Stair B Tested 11:26:19 AM 03/20/2021

Western States Fire Protection 18 04/20/2021

Pull Station 4th Southwest Hall Near Stair C Tested 11:14:14 AM 03/20/2021

Pull Station 5th North Hall Near Stair A Tested 12:33:21 PM 03/20/2021

Pull Station 5th South Hall Near Stair B Tested 12:13:51 PM 03/20/2021

Pull Station 5th Southwest Hall Near Stairwell Tested 11:57:51 AM 03/20/2021

Pull Station Chiller East Exit By Electrical Panel Tested 8:26:39 AM 04/14/2021

Pull Station Chiller West Exit Roll Up Door Tested 8:24:38 AM 04/14/2021

Pull Station Dental Clinic Annex Northeast Exit Tested 6:53:28 AM 04/13/2021

Pull Station Ground East Hall By Stairs Tested 6:35:42 AM 03/20/2021

Pull Station Ground Northeast Admin Area Exit Tested 6:23:25 AM 03/20/2021

Pull Station Ground Northwest Warehouse Exit Tested 6:01:10 AM 03/20/2021

Pull Station Ground Southeast Exit By Comm Room Tested 6:38:25 AM 03/20/2021

Pull Station Ground Southwest Exit By Food Storage Tested 7:15:57 AM 03/20/2021

Pull Station Ground West Admin Area Exit Tested 6:22:14 AM 03/20/2021

Pull Station Ground West Engineering Exit Tested 5:45:46 AM 03/20/2021

Pull Station Ground West Exit By Copy Room Tested 6:56:23 AM 03/20/2021

Pull Station Ground West Kitchen Exit Tested 6:50:41 AM 03/20/2021

Pull Station Ground Service Elevator Lobby Tested 6:54:04 AM 03/20/2021

Pull Station NIH Bldg 1 East Office Exit Tested 8:27:14 AM 04/13/2021

Pull Station NIH Bldg 1 North Exit Tested 8:19:35 AM 04/13/2021

Pull Station NIH Bldg 1 Northeast Exit Tested 8:24:24 AM 04/13/2021

Pull Station NIH Bldg 1 Northeast Office Exit Tested 8:26:26 AM 04/13/2021

Pull Station NIH Bldg 1 Northwest Exit By Lab 1 Tested 8:09:43 AM 04/13/2021

Pull Station NIH Bldg 1 Northwest Lab 1 Exit Tested 8:07:41 AM 04/13/2021

Pull Station NIH Bldg 1 South Corridor Exit Tested 8:22:49 AM 04/13/2021

Pull Station NIH Bldg 1 South Exit Tested 8:21:16 AM 04/13/2021

Pull Station NIH Bldg 1 Southeast Exit Tested 8:25:29 AM 04/13/2021

Pull Station NIH Bldg 1 West Basement Tested 8:36:31 AM 04/13/2021

Pull Station NIH Bldg 1 West Exit Tested 8:17:20 AM 04/13/2021

Pull Station PEDS North Riser Room Tested 8:13:18 AM 04/14/2021

Pull Station PEDS Northwest Exit Tested 7:53:36 AM 04/14/2021

Pull Station PEDS Southeast Exit Tested 8:01:16 AM 04/14/2021

Pull Station PEDS Southwest Exit Tested 8:02:19 AM 04/14/2021

Pull Station PEDS Main Entrance Tested 7:46:47 AM 04/14/2021

Pull Station Warehouse Northeast Exit Tested 9:10:57 AM 04/14/2021

Pull Station Warehouse Northwest Exit Tested 9:28:42 AM 04/14/2021

Pull Station Warehouse South Exit Tested 9:29:45 AM 04/14/2021

Pull Station Warehouse Southeast Exit Tested 9:26:33 AM 04/14/2021

Pull Station Women’s Clinic North Corridor Tested 9:58:51 AM 04/13/2021

Pull Station Women’s Clinic Southeast Exit Tested 10:00:15 AM 04/13/2021

Pull Station Women’s Clinic Southwest Exit Tested 9:54:35 AM 04/13/2021

Smoke Detector 1st East Pharmacy Waiting Inspected 8:19:58 AM 03/20/2021

Smoke Detector 1st North Essential Hall Inspected 8:01:23 AM 03/20/2021

Smoke Detector 1st North Hall By ER Entry Inspected 8:00:09 AM 03/20/2021

Smoke Detector 1st North Lab Waiting Area Inspected 7:49:55 AM 03/20/2021

Smoke Detector 1st North Special Lab Inspected 7:41:58 AM 03/20/2021

Smoke Detector 1st Northwest General Lab Inspected 7:38:31 AM 03/20/2021

Smoke Detector 1st Northwest General Lab Inspected 7:39:40 AM 03/20/2021

Western States Fire Protection 19 04/20/2021

Smoke Detector 1st Northwest Radiology Hall Inspected 7:46:30 AM 03/20/2021

Smoke Detector 1st West Special Lab Inspected 7:44:26 AM 03/20/2021

Smoke Detector 1st Central Electrical Room M-119 Inspected 8:10:10 AM 03/20/2021

Smoke Detector 1st Elevator Lobby Inspected 2:18:54 PM 03/20/2021

Smoke Detector 1st Entry To Lab Department Inspected 7:48:59 AM 03/20/2021

Smoke Detector 1st ER Lobby Inspected 8:26:39 AM 03/20/2021

Smoke Detector 1st Hall At Recovery Entry Inspected 8:04:56 AM 03/20/2021

Smoke Detector 1st Hall By Elevators Inspected 8:07:45 AM 03/20/2021

Smoke Detector 1st Hall By Pharmacy Inspected 8:02:23 AM 03/20/2021

Smoke Detector 1st Medical Records Window Inspected 8:25:23 AM 03/20/2021

Smoke Detector 1st Pharmacy Window Inspected 8:21:03 AM 03/20/2021

Smoke Detector 1st Service Elevator Lobby Inspected 2:18:42 PM 03/20/2021

Smoke Detector 2nd East Central Hall By 2-24 Inspected 9:10:37 AM 03/20/2021

Smoke Detector 2nd North By Nurse Station Inspected 8:42:23 AM 03/20/2021

Smoke Detector 2nd North By Staff 2-28 Inspected 8:43:06 AM 03/20/2021

Smoke Detector 2nd Northeast By Room 2-14 Inspected 8:34:55 AM 03/20/2021

Smoke Detector 2nd Northeast By Room 2-15 Inspected 8:37:04 AM 03/20/2021

Smoke Detector 2nd Northeast By Room 2-17 Inspected 8:37:57 AM 03/20/2021

Smoke Detector 2nd Northeast By Room 2-18 Inspected 8:38:37 AM 03/20/2021

Smoke Detector 2nd Northeast By Room 2-19 Inspected 8:40:03 AM 03/20/2021

Smoke Detector 2nd South By Nurse Station Inspected 9:07:22 AM 03/20/2021

Smoke Detector 2nd South Hall By Staff Room Inspected 9:05:44 AM 03/20/2021

Smoke Detector 2nd Southeast Hall By 2-33 Inspected 9:08:25 AM 03/20/2021

Smoke Detector 2nd Southwest ICU By Room 1 Inspected 9:02:46 AM 03/20/2021

Smoke Detector 2nd Southwest ICU By Room 2 Inspected 8:58:17 AM 03/20/2021

Smoke Detector 2nd Southwest ICU By Room 2-42 Inspected 9:03:30 AM 03/20/2021

Smoke Detector 2nd Southwest ICU By Stairs Inspected 8:56:56 AM 03/20/2021

Smoke Detector 2nd Elevator Lobby Inspected 2:18:27 PM 03/20/2021

Smoke Detector 2nd Hall By Office 2-11 Inspected 9:19:39 AM 03/20/2021

Smoke Detector 2nd Hall By Office 2-27 Inspected 9:12:46 AM 03/20/2021

Smoke Detector 2nd ICU By Patient Room 10 Inspected 8:46:40 AM 03/20/2021

Smoke Detector 2nd ICU By Patient Room 11 Inspected 8:44:01 AM 03/20/2021

Smoke Detector 2nd ICU By Patient Room 7 Inspected 8:48:53 AM 03/20/2021

Smoke Detector 2nd ICU By Patient Room 9 Inspected 8:47:16 AM 03/20/2021

Smoke Detector 2nd Service Elevator Lobby Inspected 2:18:15 PM 03/20/2021

Smoke Detector 3rd North Hall Near Nurses Station Tested 11:03:06 AM 03/20/2021

Smoke Detector 3rd North Hall Near Room 3-17 Tested 11:01:37 AM 03/20/2021

Smoke Detector 3rd Northeast Hall Near Room 3-11 Tested 10:59:22 AM 03/20/2021

Smoke Detector 3rd Northeast Hall Near Room 3-15 Tested 11:00:13 AM 03/20/2021

Smoke Detector 3rd Northwest Hall Near Room 3-50 Tested 10:45:02 AM 03/20/2021

Smoke Detector 3rd Northwest Hall Near Room 3-52 Tested 10:45:42 AM 03/20/2021

Smoke Detector 3rd Northwest Hall Near Room 3-54 Tested 10:46:18 AM 03/20/2021

Smoke Detector 3rd South Hall Near 3-26 Tested 10:52:40 AM 03/20/2021

Smoke Detector 3rd South Hall Near Nurses Station Tested 10:49:41 AM 03/20/2021

Smoke Detector 3rd South Hall Near Stairwell B Tested 10:52:28 AM 03/20/2021

Smoke Detector 3rd Southeast Hall Near Room 3-7 Tested 10:56:43 AM 03/20/2021

Smoke Detector 3rd Southeast Hall Near Room 3-9 Tested 10:58:01 AM 03/20/2021

Western States Fire Protection 20 04/20/2021

Smoke Detector 3rd Southwest Hall Near Room 3-52 Tested 10:44:24 AM 03/20/2021

Smoke Detector 3rd Southwest Hall Near Room 3-59 Tested 10:43:53 AM 03/20/2021

Smoke Detector 3rd West Central Electrical Room Tested 10:48:35 AM 03/20/2021

Smoke Detector 3rd West Hall Near Room 3-57 Tested 10:47:05 AM 03/20/2021

Smoke Detector 3rd Electrical Closet Near Elevator Tested 11:08:09 AM 03/20/2021

Smoke Detector 3rd Elevator Lobby Inspected 2:17:53 PM 03/20/2021

Smoke Detector 3rd Service Elevator Lobby Inspected 2:18:04 PM 03/20/2021

Smoke Detector 4th East Hall Near Room 4-11 Tested 11:30:50 AM 03/20/2021

Smoke Detector 4th North Hall Near Room 4-17 Tested 11:44:31 AM 03/20/2021

Smoke Detector 4th North Hall Near Room 4-19 Tested 11:09:21 AM 03/20/2021

Smoke Detector 4th Northeast Hall Near Room 4-12 Tested 11:34:55 AM 03/20/2021

Smoke Detector 4th Northeast Hall Near Room 4-15 Tested 11:36:24 AM 03/20/2021

Smoke Detector 4th Northeast Hall Near Room 4-24 Tested 11:39:28 AM 03/20/2021

Smoke Detector 4th Northwest Hall Near Room 4-36 Tested 11:11:05 AM 03/20/2021

Smoke Detector 4th Northwest Hall Near Room 4-39 Tested 11:13:15 AM 03/20/2021

Smoke Detector 4th South Hall Near Delivery Room Tested 11:17:41 AM 03/20/2021

Smoke Detector 4th South Hall Near Room 4-33 Tested 11:19:02 AM 03/20/2021

Smoke Detector 4th South Hall Near Room 402 Tested 11:22:10 AM 03/20/2021

Smoke Detector 4th South Hall Near Room 405 Tested 11:23:08 AM 03/20/2021

Smoke Detector 4th South Hall Near Stairwell B Tested 11:26:41 AM 03/20/2021

Smoke Detector 4th South Hall Near Stairwell B Tested 11:29:45 AM 03/20/2021

Smoke Detector 4th Southeast Hall Near Stair 4-8 Tested 11:29:55 AM 03/20/2021

Smoke Detector 4th Southwest Hall Near Room 4-48 Tested 11:15:50 AM 03/20/2021

Smoke Detector 4th West Hall Near Room 4-45 Tested 11:15:41 AM 03/20/2021

Smoke Detector 4th Elevator Lobby Inspected 2:17:33 PM 03/20/2021

Smoke Detector 4th Service Elevator Lobby Inspected 2:17:44 PM 03/20/2021

Smoke Detector 5th East Hall Near Room 5-8 Tested 12:20:23 PM 03/20/2021

Smoke Detector 5th East Hall Near Stairwell-A Tested 12:34:39 PM 03/20/2021

Smoke Detector 5th East Nurses Station Tested 12:28:15 PM 03/20/2021

Smoke Detector 5th North Hall Near Room 5-32 Tested 12:35:04 PM 03/20/2021

Smoke Detector 5th North Hall Near Room 5-45 Tested 12:05:46 PM 03/20/2021

Smoke Detector 5th Northeast Hall Near Room 5-10 Tested 12:25:21 PM 03/20/2021

Smoke Detector 5th Northeast Hall Near Room 5-10 Tested 12:27:18 PM 03/20/2021

Smoke Detector 5th Northeast Hall Near Room 5-35 Tested 11:48:36 AM 03/20/2021

Smoke Detector 5th Northwest Hall Near Room 5-29 Tested 11:51:12 AM 03/20/2021

Smoke Detector 5th Northwest Hall Near Room 5-36 Tested 11:50:02 AM 03/20/2021

Smoke Detector 5th Northwest Hall Near Room 5-38 Tested 11:52:27 AM 03/20/2021

Smoke Detector 5th Southeast Hall Near Room 5-23 Tested 12:16:05 PM 03/20/2021

Smoke Detector 5th Southeast Hall Near Room 5-48 Tested 12:08:13 PM 03/20/2021

Smoke Detector 5th Southeast Hall Near Room 5-5 Tested 12:17:33 PM 03/20/2021

Smoke Detector 5th Southwest Hall Near Room 5-40 Tested 12:00:28 PM 03/20/2021

Smoke Detector 5th Southwest Hall Near Room 5-40 Tested 12:07:13 PM 03/20/2021

Smoke Detector 5th West Hall Near Room 5-39 Tested 12:00:21 PM 03/20/2021

Smoke Detector 5th Electrical Room Near Room 5-26 Tested 12:10:04 PM 03/20/2021

Smoke Detector 5th Elevator Lobby Inspected 1:44:48 PM 03/20/2021

Smoke Detector 5th Hall Near Room 5-2 Tested 12:15:54 PM 03/20/2021

Smoke Detector 5th Service Elevator Lobby Inspected 1:45:13 PM 03/20/2021

Western States Fire Protection 21 04/20/2021

Smoke Detector Penthouse Elevator Control Room Inspected 1:38:03 PM 03/20/2021

Smoke Detector Penthouse Elevator Control Room Inspected 1:38:21 PM 03/20/2021

Smoke Detector Penthouse Inspected 12:40:09 PM 03/20/2021

Smoke Detector Chiller Northeast Mezzanine Inspected 8:44:54 AM 04/14/2021

Smoke Detector Chiller Paint Shop/Tool Storage Inspected 2:15:15 PM 04/14/2021

Smoke Detector Ground East Admin Billing Office Inspected 6:25:11 AM 03/20/2021

Smoke Detector Ground East Business Office Inspected 6:30:14 AM 03/20/2021

Smoke Detector Ground East Electrical Room Inspected 6:27:23 AM 03/20/2021

Smoke Detector Ground East Engineering Prep Room Inspected 6:31:59 AM 03/20/2021

Smoke Detector Ground East Hall By Business Office Inspected 6:28:39 AM 03/20/2021

Smoke Detector Ground East Hall By Telephone Room Inspected 6:34:51 AM 03/20/2021

Smoke Detector Ground East Telephone Room Inspected 6:33:21 AM 03/20/2021

Smoke Detector Ground North Warehouse Area Inspected 6:06:52 AM 03/20/2021

Smoke Detector Ground Northeast Central Admin Area Open

Office

Inspected 6:15:07 AM 03/20/2021

Smoke Detector Ground Northeast Central Admin Area Open

Office

Inspected 6:16:08 AM 03/20/2021

Smoke Detector Ground Northwest Central Admin Area Open

Office

Inspected 6:14:21 AM 03/20/2021

Smoke Detector Ground Northwest Central Admin Area Inspected 6:13:01 AM 03/20/2021

Smoke Detector Ground South Dirty Linen Storage Inspected 7:11:30 AM 03/20/2021

Smoke Detector Ground Southeast Central Admin Area Open

Office

Inspected 6:19:01 AM 03/20/2021

Smoke Detector Ground Southeast Central Admin Area Open

Office

Inspected 6:20:59 AM 03/20/2021

Smoke Detector Ground Southwest Central Admin Area Open

Office

Inspected 6:16:52 AM 03/20/2021

Smoke Detector Ground Southwest Central Admin Area Open

Office

Inspected 6:20:11 AM 03/20/2021

Smoke Detector Ground Southwest Hall By Mail Room Inspected 6:57:25 AM 03/20/2021

Smoke Detector Ground West Business Office Inspected 6:29:27 AM 03/20/2021

Smoke Detector Ground West Kitchen Inspected 6:47:34 AM 03/20/2021

Smoke Detector Ground West Non Sterile Storage Inspected 7:25:56 AM 03/20/2021

Smoke Detector Ground West Warehouse Area Inspected 6:02:54 AM 03/20/2021

Smoke Detector Ground Central Electrical Closet Inspected 7:06:17 AM 03/20/2021

Smoke Detector Ground Clean Linen Storage Inspected 7:24:13 AM 03/20/2021

Smoke Detector Ground Elevator Lobby Inspected 2:22:15 PM 03/20/2021

Smoke Detector Ground Engineering Bio Med Office Inspected 5:59:37 AM 03/20/2021

Smoke Detector Ground Engineering Locksmith Office Inspected 5:57:46 AM 03/20/2021

Smoke Detector Ground Engineering Office Inspected 5:55:20 AM 03/20/2021

Smoke Detector Ground Engineering Office Inspected 5:56:33 AM 03/20/2021

Smoke Detector Ground FACP Room Inspected 5:45:11 AM 03/20/2021

Smoke Detector Ground Housekeeping Inspected 7:02:25 AM 03/20/2021

Smoke Detector Ground Housekeeping Admin Office Inspected 7:01:12 AM 03/20/2021

Smoke Detector Ground Kitchen Food Storage Inspected 6:49:25 AM 03/20/2021

Smoke Detector Ground Kitchen By Hood Inspected 6:46:37 AM 03/20/2021

Smoke Detector Ground Service Elevator Lobby Inspected 2:21:28 PM 03/20/2021

Western States Fire Protection 22 04/20/2021

Smoke Detector NIH Bldg 1 East Exit Inspected 8:49:43 AM 04/13/2021

Smoke Detector NIH Bldg 1 Southwest Room 405 Inspected 8:59:34 AM 04/13/2021

Smoke Detector NIH Bldg 1 Electrical/Telco Room Inspected 8:43:09 AM 04/13/2021

Smoke Detector NIH Bldg 1 Lab 03 Freezer Storage Inspected 8:39:45 AM 04/13/2021

Smoke Detector NIH Bldg 1 Lab 03 Freezer Storage Inspected 8:41:27 AM 04/13/2021

Smoke Detector NIH Bldg 1 Lab Room 202 Inspected 8:42:10 AM 04/13/2021

Smoke Detector NIH Bldg 1 Storage Room 701 Inspected 8:46:34 AM 04/13/2021

Smoke Detector PEDS North Riser Room Inspected 8:10:30 AM 04/14/2021

Smoke Detector PEDS Southeast Corridor By Staff Lounge Inspected 8:00:01 AM 04/14/2021

Smoke Detector PEDS Southeast Office Open Area Inspected 7:59:23 AM 04/14/2021

Smoke Detector PEDS Southwest Office Open Area Inspected 7:58:12 AM 04/14/2021

Smoke Detector PEDS Corridor By Data Room 038 Inspected 7:52:03 AM 04/14/2021

Smoke Detector PEDS Corridor By Directors Office Inspected 8:04:48 AM 04/14/2021

Smoke Detector PEDS Corridor By Exam Room 4 Inspected 7:54:44 AM 04/14/2021

Smoke Detector PEDS Corridor By Exam Room 6 Inspected 8:02:57 AM 04/14/2021

Smoke Detector PEDS Corridor By Housekeeping 027 Inspected 7:51:17 AM 04/14/2021

Smoke Detector PEDS Corridor By Restrooms Inspected 7:55:46 AM 04/14/2021

Smoke Detector PEDS Corridor Women’s By Exam Room 2 Inspected 8:06:14 AM 04/14/2021

Smoke Detector PEDS Waiting Area Inspected 7:48:42 AM 04/14/2021

Smoke Detector PEDS Waiting Area Inspected 8:08:41 AM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:39:21 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:41:11 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:41:23 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:41:36 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:41:50 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:42:01 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:42:12 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:42:22 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:42:32 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:42:42 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:43:03 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:43:13 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:43:25 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:43:34 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:43:58 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:44:07 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:44:18 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:44:29 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:44:37 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:44:47 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:03 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:14 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:25 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:36 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:46 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:45:56 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:46:05 PM 04/14/2021

Western States Fire Protection 23 04/20/2021

Smoke Detector Warehouse High Smoke Inspected 12:46:13 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:46:22 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:46:32 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:46:45 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:47:12 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:47:48 PM 04/14/2021

Smoke Detector Warehouse High Smoke Inspected 12:47:58 PM 04/14/2021

Smoke Detector Women’s Clinic Center Corridor Inspected 10:07:52 AM 04/13/2021

Smoke Detector Women’s Clinic East Corridor Inspected 10:01:50 AM 04/13/2021

Smoke Detector Women’s Clinic East Corridor Inspected 10:04:15 AM 04/13/2021

Smoke Detector Women’s Clinic North Corridor Inspected 10:05:52 AM 04/13/2021

Smoke Detector Women’s Clinic West Corridor Inspected 10:06:29 AM 04/13/2021

Smoke Detector Women’s Clinic West Corridor Inspected 10:07:10 AM 04/13/2021

Western States Fire Protection 24 04/20/2021

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Battery Specialty Services By Receptionist Desk Inspected 10:43:26 AM 04/12/2021

Battery Specialty Services By Receptionist Desk Inspected 10:43:34 AM 04/12/2021

Control Panel Specialty Services By Receptionist Desk Inspected 9:14:16 AM 04/12/2021

Initiating

Duct Detector Specialty Services Corridor By Exam Room #1 Tested 10:49:36 AM 04/12/2021

Duct Detector Specialty Services Corridor By Nurse Station Tested 10:44:55 AM 04/12/2021

Duct Detector Specialty Services Waiting Area Tested 10:51:27 AM 04/12/2021

Pull Station Specialty Services North Exit Tested 11:04:11 AM 04/12/2021

Pull Station Specialty Services Northeast Exit Tested 11:01:00 AM 04/12/2021

Pull Station Specialty Services Northwest Exit Tested 11:02:33 AM 04/12/2021

Pull Station Specialty Services Waiting Area Tested 10:58:02 AM 04/12/2021

Smoke Detector Specialty Services By Receptionist Desk Inspected 9:20:46 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exam Room #1 Inspected 9:39:37 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exam Room #4 Inspected 9:40:45 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exit To Waiting

Area

Inspected 9:45:18 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Pharmacy Window Inspected 9:41:14 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exam Room #3 Inspected 9:55:21 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exam Room #6 Inspected 9:49:51 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Exam Room #8 Inspected 9:48:51 AM 04/12/2021

Smoke Detector Specialty Services Corridor By North Exit Inspected 9:53:27 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Nurse Station Inspected 9:21:08 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #116 Inspected 9:50:45 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #122 Inspected 9:51:43 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #123 Inspected 9:52:37 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #133 Inspected 9:56:13 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #141 Inspected 9:22:16 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office #150

Surgery Department

Inspected 9:37:00 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office 101 Inspected 9:46:20 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Office 105 Inspected 9:47:52 AM 04/12/2021

Smoke Detector Specialty Services Corridor By Women’s

Restroom

Inspected 9:59:10 AM 04/12/2021

Smoke Detector Specialty Services Patient Waiting Area Inspected 9:42:44 AM 04/12/2021

Smoke Detector Specialty Services Patient Waiting Area Inspected 9:43:40 AM 04/12/2021

Western States Fire Protection 25 04/20/2021

MS-9050UD

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Annunciator Dental Clinic Main Entrance Inspected 11:56:39 AM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:10:44 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:11:12 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:11:19 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:11:24 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:14:48 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:15:02 PM 04/12/2021

Control Panel Dental Clinic Southeast Riser Room Inspected 12:01:19 PM 04/12/2021

Power Supply Dental Clinic Southeast Riser Room Inspected 12:11:45 PM 04/12/2021

Power Supply Dental Clinic Southeast Riser Room Inspected 12:13:04 PM 04/12/2021

Voice Evacuation Dental Clinic Southeast Riser Room Inspected 12:13:38 PM 04/12/2021

Initiating

Pull Station Dental Clinic Northeast Exit Tested 11:58:30 AM 04/12/2021

Pull Station Dental Clinic Southeast Exit Tested 11:53:02 AM 04/12/2021

Pull Station Dental Clinic Southeast Riser Room Tested 11:59:43 AM 04/12/2021

Pull Station Dental Clinic Main Entrance Tested 11:57:40 AM 04/12/2021

Smoke Detector Dental Clinic Southeast Riser Room Inspected 12:03:54 PM 04/12/2021

Failed/Other

Control

Battery Dental Clinic Southeast Riser Room Inspected 12:07:49 PM 04/12/2021

Battery Dental Clinic Southeast Riser Room Inspected 12:08:02 PM 04/12/2021

Western States Fire Protection 26 04/20/2021

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Power Supply Dental Clinic Annex Southeast Electrical Room Inspected 7:21:47 AM 04/13/2021

Initiating

Pull Station Dental Clinic Annex Waiting Area Tested 7:10:16 AM 04/13/2021

Smoke Detector Dental Clinic Annex Southeast Electrical Room Inspected 7:18:49 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Housekeeping

Inspected 6:58:44 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Multipurpose

Room 130

Inspected 7:15:36 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Panoramic 128 Inspected 6:59:22 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Room 107 Inspected 7:14:03 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Room 125 Inspected 7:03:52 AM 04/13/2021

Smoke Detector Dental Clinic Annex Corridor By Soiled Utility

Inspected 7:01:56 AM 04/13/2021

Smoke Detector Dental Clinic Annex Storage Room 112 Inspected 7:16:38 AM 04/13/2021

Smoke Detector Dental Clinic Annex Waiting Area Inspected 7:07:19 AM 04/13/2021

Smoke Detector Dental Clinic Annex Waiting Area By Restrooms Inspected 7:12:12 AM 04/13/2021

Control

Battery Dental Clinic Annex Southeast Electrical Room Inspected 7:23:38 AM 04/13/2021

Battery Dental Clinic Annex Southeast Electrical Room Inspected 7:23:55 AM 04/13/2021

Western States Fire Protection 27 04/20/2021

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Control Panel Behavioral Health Bldg 5 By Room C-2 Inspected 2:09:10 PM 04/12/2021

Initiating

Duct Detector Behavioral Health Bldg 5 Corridor By Room

B-16

Tested 2:15:09 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Southeast Exit Tested 2:33:45 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 West Exit Tested 2:30:29 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Breakroom Tested 2:32:31 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Breakroom Office A-3 Tested 2:33:02 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Corridor By Room B-7 Tested 2:31:02 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Corridor By Room B-9 Tested 2:25:21 PM 04/12/2021

Pull Station Behavioral Health Bldg 5 Waiting Area Tested 2:31:34 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Breakroom Office A-3 Inspected 2:19:52 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Breakroom Inspected 2:18:42 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By FACP Inspected 1:56:51 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room

B-10

Inspected 2:13:44 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room

B-15

Inspected 2:14:35 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room B-7 Inspected 2:12:17 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room B-8 Inspected 2:10:29 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room

C-10

Inspected 2:21:30 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Corridor By Room C-6 Inspected 2:17:15 PM 04/12/2021

Smoke Detector Behavioral Health Bldg 5 Waiting Area Inspected 2:23:56 PM 04/12/2021

Control

Battery Behavioral Health Bldg 5 By Room C-2 Inspected 2:36:48 PM 04/12/2021

Battery Behavioral Health Bldg 5 By Room C-2 Inspected 2:37:00 PM 04/12/2021

Western States Fire Protection 28 04/20/2021

Control Panel: 6 - Notifier

NFS-3030D

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Battery NIH Bldg 1 West Basement Inspected 9:07:41 AM 04/13/2021

Battery NIH Bldg 1 West Basement Inspected 9:08:00 AM 04/13/2021

Control Panel NIH Bldg 1 West Basement Inspected 9:04:47 AM 04/13/2021

Western States Fire Protection 29 04/20/2021

Building: Phoenix Indian Medical Control Panel: 7 - Fire-Lite SFP-1024

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Battery PCMC Reception Area Inspected 11:54:19 AM 04/13/2021

Battery PCMC Reception Area Inspected 11:54:33 AM 04/13/2021

Control Panel PCMC Reception Area Inspected 11:50:01 AM 04/13/2021

Initiating

Pull Station PCMC East Exit Tested 12:04:57 PM 04/13/2021

Pull Station PCMC North Exit To Registration Tested 12:15:40 PM 04/13/2021

Pull Station PCMC Northside East Exit Tested 12:18:15 PM 04/13/2021

Pull Station PCMC Northside Northwest Exit Tested 12:20:26 PM 04/13/2021

Pull Station PCMC Northside Nurse Office Station Tested 12:21:26 PM 04/13/2021

Pull Station PCMC Southwest Pharmacy Exit Tested 12:09:52 PM 04/13/2021

Pull Station PCMC Center Corridor Exit Tested 12:02:24 PM 04/13/2021

Pull Station PCMC West Exit Tested 12:02:12 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Exam Room 11 Inspected 12:26:26 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Restroom Inspected 12:33:09 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 17 Inspected 12:32:18 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 19 Inspected 12:31:45 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 24 Inspected 12:31:07 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 28 Inspected 12:30:35 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 30 Inspected 12:30:00 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Room 50 Inspected 12:28:22 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Talking Room Inspected 12:27:01 PM 04/13/2021

Smoke Detector PCMC Northside Corridor By Team Room Silver

A

Inspected 12:29:28 PM 04/13/2021

Smoke Detector PCMC Northside Exit To Registration Inspected 12:25:32 PM 04/13/2021

Western States Fire Protection 30 04/20/2021

MS-5024UD

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which

Control

Battery Pathology Services Office By East Exit Inspected 1:08:30 PM 04/13/2021

Battery Pathology Services Office By East Exit Inspected 1:09:04 PM 04/13/2021

Initiating

Pull…