This solicitation notice is for a construction project to complete maintenance and improvement renovations at the Phoenix Indian Medical Center in Phoenix, Arizona. The scope of work includes asbestos abatement, replacement of flooring, countertops, and furniture, mechanical HVAC work, painting, roof replacement, and fire system upgrades. The period of performance is 300 calendar days from notice to proceed. The contract value is estimated between $1 million to $5 million and will be a firm fixed price contract awarded using lowest price technically acceptable criteria. A site visit is scheduled as detailed in the solicitation. The Department of Health and Human Services Indian Health Service is the contracting agency.
View the file
Other files
Show 40 more
Latest 50 of 53 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Alarm and Life Safety System
Inspection Certificate
For
Phoenix Indian Medical
4212 N 16th S
Phoenix, AZ 85253
Inspection Date
Apr 14, 2021
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
IT IS THE RESPONSIBILITY OF THE PROPERTY OWNER OR
DESIGNATED REPRESENTATIVE THAT REQUESTED THIS
INSPECTION TO REVIEW REPORTS AND CORRECT ANY
DEFICIENCIES NOTED.
Building: Phoenix Indian Medical Company: Western States Fire Protection
Contact: Warren Yonnie Contact: Luciano lopez
Title: N/A Title: Inspector
Attachment J11 - PIMC 2021 Fire Alarm Testing Report
Western States Fire Protection 1 04/20/2021
Executive Summary Generated by: BuildingReports.com
Building Information
Building: Phoenix Indian Medical Contact: Warren Yonnie
Address: 4212 N 16th S Phone: 928-551-3562
Address: Fax:
City/State/Zip: Phoenix, AZ 85253 Mobile:
Country: United States of America Email: warren.yonnie@ihs.gov
Inspection Performed By
Company: Western States Fire Protection Inspector: Luciano lopez
Address: 4346 East Elwood St. Phone: 480.259.7984
Address: Suite 100 Fax:
City/State/Zip: Phoenix, Arizona 85040 Mobile:
Country: United States of America Email: luciano.lopez@wsfp.us
System Control Unit Manufacturer: Notifier Inspection Date: 03/20/2021 IDC Style:
Model Number: NFS-3030D Install Date: 03/20/2015 SLC Style:
Software Version: Version Date: 03/20/2015 NAC Style:
Location: Ground Fire Alarm Control Room Current Protection: Breaker
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time
Western States Fire Protection 2 04/20/2021
Inspection Summary
Category Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Sound Test 10 2.21% 10 100.00% 10 100.00% 0 0%
Control 51 11.28% 51 100.00% 42 82.35% 9 17.65%
Initiating 391 86.50% 391 100.00% 391 100.00% 0 0%
Totals 452 100% 452 100.00% 443 98.01% 9 1.99%
Certification
Company: Western States Fire Protection Building: Phoenix Indian Medical
Inspector: Luciano lopez Contact: Warren Yonnie
Signed: Mar 20, 2021 3:12:35 PM Signed:
Western States Fire Protection 3 04/20/2021
Discrepancy Report Generated by: BuildingReports.com
Building: Phoenix Indian Medical Control Panel: 3 - Fire-Lite
MS-9050UD
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12
More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf
Pull Station Notifier NBG-12LX 10/03/2011 16
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
ScanID Location Problem Address Reference
Control
Battery
62607986 Dental Clinic Southeast Riser Room Failed Test 3 NFPA72 Table
14.4.3.2 (9a)(1)
62607987 Dental Clinic Southeast Riser Room Failed Test 3 NFPA72 Table
14.4.3.2 (9a)(1)
Code References NFPA72 Table
14.4.3.2 (9a)(1)
Batteries shall be replaced in accordance with the recommendations of the alarm equipment manufacturer or when the recharged battery voltage or current falls below the manufacturer's recommendations
Western States Fire Protection 4 04/20/2021
Building: Phoenix Indian Medical Control Panel: 4
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12
More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf
Pull Station Notifier NBG-12LX 10/03/2011 16
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
ScanID Location Problem Address Reference
Control
Battery
62607977 Dental Clinic Annex Southeast Electrical
Room
Failed Test 4 NFPA72 Table
14.4.3.2 (9a)(1)
62607978 Dental Clinic Annex Southeast Electrical
Room
Failed Test 4 NFPA72 Table
14.4.3.2 (9a)(1)
Code References NFPA72 Table
14.4.3.2 (9a)(1)
Batteries shall be replaced in accordance with the recommendations of the alarm equipment
Western States Fire Protection 5 04/20/2021
Building: Phoenix Indian Medical Control Panel: 5 - Edwards 2412
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12
More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf
Pull Station Notifier NBG-12LX 10/03/2011 16
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
ScanID Location Problem Address Reference
Control
Battery
62607981 Behavioral Health Bldg 5 By Room C-2 Failed Test 5 NFPA72 Table
14.4.3.2 (9a)(1)
62607982 Behavioral Health Bldg 5 By Room C-2 Failed Test 5 NFPA72 Table
14.4.3.2 (9a)(1)
Code References NFPA72 Table
14.4.3.2 (9a)(1)
Batteries shall be replaced in accordance with the recommendations of the alarm equipment
Western States Fire Protection 6 04/20/2021
Control Panel: 8 - Fire-Lite
MS-5024UD
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12
More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf
Pull Station Notifier NBG-12LX 10/03/2011 16
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
ScanID Location Problem Address Reference
Control
Control Panel
40PIF-82144 Pathology Services Office By East Exit Damaged/Worn 8 NFPA72 14.2.2.2.2
Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Western States Fire Protection 7 04/20/2021
Control Panel: 9 - Faraday
MPC-1000
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty
Items listed for Recall or Replacement/Upgrade Pull Station Fire-Lite BG-10 04/01/2013 12
More Information: https://www.cityfire.com/assets/PDFs/hfs-bg-10-series-letter-april-2013.pdf
Pull Station Notifier NBG-12LX 10/03/2011 16
More Information: http://image.exct.net/lib/feef1078766c0d/d/1/SSD%20Pullstation%20Bulletin.pdf
ScanID Location Problem Address Reference
Control
Battery
62607966 Warehouse Northeast Failed Test 9 NFPA72 Table
14.4.3.2 (9a)(1)
62607967 Warehouse Northeast Failed Test 9 NFPA72 Table
14.4.3.2 (9a)(1)
Code References NFPA72 Table
14.4.3.2 (9a)(1)
Batteries shall be replaced in accordance with the recommendations of the alarm equipment
Western States Fire Protection 8 04/20/2021
Proposed Solutions Report
Building: Phoenix Indian Medical Control Panel: 3 - Fire-Lite MS-9050UD
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Control
Battery
62607986 Dental Clinic Southeast Riser Room Replace Battery
T/M
62607987 Dental Clinic Southeast Riser Room Replace Battery
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
62607977 Dental Clinic Annex Southeast Electrical
Room
Replace Battery
62607978 Dental Clinic Annex Southeast Electrical
Room
Replace Battery
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
62607981 Behavioral Health Bldg 5 By Room C-2 Replace Battery
62607982 Behavioral Health Bldg 5 By Room C-2 Replace Battery
Building: Phoenix Indian Medical Control Panel: 8 - Fire-Lite MS-5024UD
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
Western States Fire Protection 9 04/20/2021
Control Panel
40PIF-82144 Pathology Services Office By East Exit Investigate MS-5024UD T/M
Building: Phoenix Indian Medical Control Panel: 9 - Faraday MPC-1000
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a
62607966 Warehouse Northeast Replace Battery
62607967 Warehouse Northeast Replace Battery
PO #: (none) T/M
Western States Fire Protection 10 04/20/2021
Notes & Recommendations
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note Women’s Clinic Reports Back To Main Fire Panel And The Disables For The Main Building Are The Same.
Dental Annex Reports To The Panel In The Basement Of Building 1. You need To Disable N01L01M034 For
The NACS At Dental Annex.
PEDS And The Chiller Plants AV’s Are Disabled From The Main Panel.
Did Not Set Off AV’s At Main Hospital Per Customer.
Recommend Adding FACP Sign To All Building Doors Where The Panel Is Located.
Building: Phoenix Indian Medical Control Panel: n/a
ScanID Note Device Type Location Comment
0003 2 Sound Test Dental Clinic Annex Passed
Reports Back To Building 1 Panel In Basement. Need To Disable Booster N01L01M034 When Testing.
0009 3 Sound Test PEDS Passed
Building Reports Back To Main Panel. Need To Enable Main Panel To Test AV’s.
Western States Fire Protection 11 04/20/2021
Control Panel: 1 - Notifier
NFS-3030D
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 40PIF-82796 4 Duct Detector 1st Hallway Near Pharmacy Passed
Reports as alarm
40PIF-82797 5 Duct Detector 1st Hallway Near Pharmacy Passed
Reports as alarm
40PIF-82805 6 Duct Detector 1st Hallway X-Ray Files Passed
Reports as alarm
Western States Fire Protection 12 04/20/2021
Building: Phoenix Indian Medical Control Panel: 2 - FCI 7200
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 40PIF-82625 7 Pull Station Specialty Services Waiting Area Passed
Recommend Replacing Per Manufacturer.
40PIF-82627 8 Pull Station Specialty Services North Exit Passed
Recommend Replacing Per Manufacturer.
Western States Fire Protection 13 04/20/2021
Control Panel: 6 - Notifier
NFS-3030D
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Control 62607974 9 Control Panel NIH Bldg 1 West Basement Passed
Dental Annex And Building 1 Report To This Panel. Disable N01L01M034 For Dental Annex. Pull Nacs For
Building 1.
Western States Fire Protection 14 04/20/2021
Control Panel: 7 - Fire-Lite
SFP-1024
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 40PIF-82579 10 Pull Station PCMC Center Corridor Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82578 11 Pull Station PCMC West Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82580 12 Pull Station PCMC East Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82584 13 Pull Station PCMC North Exit To Registration Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82581 14 Pull Station PCMC Northside East Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82582 15 Pull Station PCMC Northside Northwest Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
Western States Fire Protection 15 04/20/2021
MS-5024UD
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Control 40PIF-82144 16 Control Panel Pathology Services Office By East Exit Damaged/Worn
Terminal To Transformer Is Defective. Panel Losses Power Intermittently. See Pictures
Initiating 40PIF-82558 17 Pull Station Pathology Services Office East Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
40PIF-82559 18 Pull Station Pathology Services West Exit Passed
Recommend Replacing Pull Station Per Manufacturer.
Western States Fire Protection 16 04/20/2021
Inspection & Testing
NFS-3030D
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed
Control
Annunciator 1st East Main Entrance Office Inspected 6:19:05 AM 03/20/2021
Annunciator NIH Bldg 1 North Exit Inspected 8:20:29 AM 04/13/2021
Battery 1st South Electrical Closet Near Elevators Inspected 6:13:44 AM 03/20/2021
Battery 1st South Electrical Closet Near Elevators Inspected 6:14:38 AM 03/20/2021
Battery 2nd South Electrical Closet Near Elevators Inspected 6:27:27 AM 03/20/2021
Battery 2nd South Electrical Closet Near Elevators New 6:35:33 AM 03/20/2021
Battery Ground Fire Alarm Control Room Inspected 5:59:31 AM 03/20/2021
Battery Ground Fire Alarm Control Room Inspected 6:00:32 AM 03/20/2021
Battery PEDS North Riser Room Inspected 8:16:03 AM 04/14/2021
Battery PEDS North Riser Room Inspected 8:16:44 AM 04/14/2021
Control Panel Ground Fire Alarm Control Room Inspected 6:01:18 AM 03/20/2021
Power Supply 1st South Electrical Closet Near Elevators Inspected 6:11:28 AM 03/20/2021
Power Supply 2nd South Electrical Closet Near Elevators Inspected 6:27:00 AM 03/20/2021
Power Supply PEDS North Riser Room Inspected 8:15:05 AM 04/14/2021
Initiating
Duct Detector 1st Hallway Near Pharmacy Tested 7:43:48 AM 03/20/2021
Duct Detector 1st Hallway Near Pharmacy Tested 7:57:56 AM 03/20/2021
Duct Detector 1st Hallway X-Ray Files Tested 7:58:32 AM 03/20/2021
Duct Detector 1st Hallway X-Ray Files Tested 8:01:39 AM 03/20/2021
Duct Detector 4th Room 4-35 Back Corner Of Room Tested 8:28:00 AM 03/20/2021
Duct Detector 5th Office 5-28 Tested 8:43:22 AM 03/20/2021
Duct Detector 5th Room 5-27 Tested 8:36:38 AM 03/20/2021
Duct Detector Roof East Tested 9:19:41 AM 03/20/2021
Duct Detector Ground AHU/Riser Room Tested 7:27:18 AM 03/20/2021
Duct Detector Ground AHU/Riser Room Tested 7:27:23 AM 03/20/2021
Duct Detector Ground Kitchen AHU 10 Tested 7:31:02 AM 03/20/2021
Duct Detector Women’s Clinic West Corridor Tested 10:09:43 AM 04/13/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:03:43 PM 03/20/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:05:24 PM 03/20/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:05:48 PM 03/20/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:06:14 PM 03/20/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:06:36 PM 03/20/2021
Heat Detector Penthouse Elevator Control Room Inspected 1:06:52 PM 03/20/2021
Heat Detector Chiller Northwest Mezzanine Inspected 8:49:41 AM 04/14/2021
Western States Fire Protection 17 04/20/2021
Heat Detector Chiller Southeast Mezzanine Inspected 8:46:15 AM 04/14/2021
Heat Detector Chiller Southwest Mezzanine Inspected 8:48:50 AM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:48:26 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:49:43 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:49:54 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:03 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:12 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:21 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:31 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:40 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:48 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:50:58 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:51:08 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:51:19 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:51:30 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:51:39 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:51:48 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:00 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:09 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:17 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:25 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:33 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:50 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:52:59 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:53:07 PM 04/14/2021
Heat Detector Warehouse High Heat Inspected 12:53:16 PM 04/14/2021
Pull Station 1st East Central Hall By PEDS Tested 8:22:24 AM 03/20/2021
Pull Station 1st East Main Lobby Information Tested 8:14:55 AM 03/20/2021
Pull Station 1st East Main Lobby Tested 8:15:55 AM 03/20/2021
Pull Station 1st North Exit By Security Tested 7:57:15 AM 03/20/2021
Pull Station 1st Northwest Lab Exit Tested 7:37:04 AM 03/20/2021
Pull Station 1st Southeast By Conference Room Tested 8:16:52 AM 03/20/2021
Pull Station 1st Southwest OR Minor OP Exit Tested 7:29:57 AM 03/20/2021
Pull Station 1st West OR Exit Tested 7:32:19 AM 03/20/2021
Pull Station 1st Central Hall By Pharmacy Tested 8:03:29 AM 03/20/2021
Pull Station 1st Exit By ER Lobby Tested 8:28:35 AM 03/20/2021
Pull Station 2nd North Hall ICU BY 2-29 Tested 8:45:09 AM 03/20/2021
Pull Station 2nd South Hall ICU BY 2-42 Tested 9:04:29 AM 03/20/2021
Pull Station 2nd Southeast Hall By Stairs Tested 9:09:29 AM 03/20/2021
Pull Station 2nd Southwest ICU By Stairs Tested 9:00:24 AM 03/20/2021
Pull Station 2nd Hall By Stairs Tested 8:40:51 AM 03/20/2021
Pull Station 3rd North Hall Near Stairwell A Tested 11:04:07 AM 03/20/2021
Pull Station 3rd Southeast Hall Near Stairwell B Tested 10:51:39 AM 03/20/2021
Pull Station 3rd Southwest Hall Near Stairs Tested 10:43:48 AM 03/20/2021
Pull Station 4th North Hall Near Stair A Tested 11:45:04 AM 03/20/2021
Pull Station 4th Northwest Nurses Station Tested 11:12:28 AM 03/20/2021
Pull Station 4th South Hall Near Stair B Tested 11:26:19 AM 03/20/2021
Western States Fire Protection 18 04/20/2021
Pull Station 4th Southwest Hall Near Stair C Tested 11:14:14 AM 03/20/2021
Pull Station 5th North Hall Near Stair A Tested 12:33:21 PM 03/20/2021
Pull Station 5th South Hall Near Stair B Tested 12:13:51 PM 03/20/2021
Pull Station 5th Southwest Hall Near Stairwell Tested 11:57:51 AM 03/20/2021
Pull Station Chiller East Exit By Electrical Panel Tested 8:26:39 AM 04/14/2021
Pull Station Chiller West Exit Roll Up Door Tested 8:24:38 AM 04/14/2021
Pull Station Dental Clinic Annex Northeast Exit Tested 6:53:28 AM 04/13/2021
Pull Station Ground East Hall By Stairs Tested 6:35:42 AM 03/20/2021
Pull Station Ground Northeast Admin Area Exit Tested 6:23:25 AM 03/20/2021
Pull Station Ground Northwest Warehouse Exit Tested 6:01:10 AM 03/20/2021
Pull Station Ground Southeast Exit By Comm Room Tested 6:38:25 AM 03/20/2021
Pull Station Ground Southwest Exit By Food Storage Tested 7:15:57 AM 03/20/2021
Pull Station Ground West Admin Area Exit Tested 6:22:14 AM 03/20/2021
Pull Station Ground West Engineering Exit Tested 5:45:46 AM 03/20/2021
Pull Station Ground West Exit By Copy Room Tested 6:56:23 AM 03/20/2021
Pull Station Ground West Kitchen Exit Tested 6:50:41 AM 03/20/2021
Pull Station Ground Service Elevator Lobby Tested 6:54:04 AM 03/20/2021
Pull Station NIH Bldg 1 East Office Exit Tested 8:27:14 AM 04/13/2021
Pull Station NIH Bldg 1 North Exit Tested 8:19:35 AM 04/13/2021
Pull Station NIH Bldg 1 Northeast Exit Tested 8:24:24 AM 04/13/2021
Pull Station NIH Bldg 1 Northeast Office Exit Tested 8:26:26 AM 04/13/2021
Pull Station NIH Bldg 1 Northwest Exit By Lab 1 Tested 8:09:43 AM 04/13/2021
Pull Station NIH Bldg 1 Northwest Lab 1 Exit Tested 8:07:41 AM 04/13/2021
Pull Station NIH Bldg 1 South Corridor Exit Tested 8:22:49 AM 04/13/2021
Pull Station NIH Bldg 1 South Exit Tested 8:21:16 AM 04/13/2021
Pull Station NIH Bldg 1 Southeast Exit Tested 8:25:29 AM 04/13/2021
Pull Station NIH Bldg 1 West Basement Tested 8:36:31 AM 04/13/2021
Pull Station NIH Bldg 1 West Exit Tested 8:17:20 AM 04/13/2021
Pull Station PEDS North Riser Room Tested 8:13:18 AM 04/14/2021
Pull Station PEDS Northwest Exit Tested 7:53:36 AM 04/14/2021
Pull Station PEDS Southeast Exit Tested 8:01:16 AM 04/14/2021
Pull Station PEDS Southwest Exit Tested 8:02:19 AM 04/14/2021
Pull Station PEDS Main Entrance Tested 7:46:47 AM 04/14/2021
Pull Station Warehouse Northeast Exit Tested 9:10:57 AM 04/14/2021
Pull Station Warehouse Northwest Exit Tested 9:28:42 AM 04/14/2021
Pull Station Warehouse South Exit Tested 9:29:45 AM 04/14/2021
Pull Station Warehouse Southeast Exit Tested 9:26:33 AM 04/14/2021
Pull Station Women’s Clinic North Corridor Tested 9:58:51 AM 04/13/2021
Pull Station Women’s Clinic Southeast Exit Tested 10:00:15 AM 04/13/2021
Pull Station Women’s Clinic Southwest Exit Tested 9:54:35 AM 04/13/2021
Smoke Detector 1st East Pharmacy Waiting Inspected 8:19:58 AM 03/20/2021
Smoke Detector 1st North Essential Hall Inspected 8:01:23 AM 03/20/2021
Smoke Detector 1st North Hall By ER Entry Inspected 8:00:09 AM 03/20/2021
Smoke Detector 1st North Lab Waiting Area Inspected 7:49:55 AM 03/20/2021
Smoke Detector 1st North Special Lab Inspected 7:41:58 AM 03/20/2021
Smoke Detector 1st Northwest General Lab Inspected 7:38:31 AM 03/20/2021
Smoke Detector 1st Northwest General Lab Inspected 7:39:40 AM 03/20/2021
Western States Fire Protection 19 04/20/2021
Smoke Detector 1st Northwest Radiology Hall Inspected 7:46:30 AM 03/20/2021
Smoke Detector 1st West Special Lab Inspected 7:44:26 AM 03/20/2021
Smoke Detector 1st Central Electrical Room M-119 Inspected 8:10:10 AM 03/20/2021
Smoke Detector 1st Elevator Lobby Inspected 2:18:54 PM 03/20/2021
Smoke Detector 1st Entry To Lab Department Inspected 7:48:59 AM 03/20/2021
Smoke Detector 1st ER Lobby Inspected 8:26:39 AM 03/20/2021
Smoke Detector 1st Hall At Recovery Entry Inspected 8:04:56 AM 03/20/2021
Smoke Detector 1st Hall By Elevators Inspected 8:07:45 AM 03/20/2021
Smoke Detector 1st Hall By Pharmacy Inspected 8:02:23 AM 03/20/2021
Smoke Detector 1st Medical Records Window Inspected 8:25:23 AM 03/20/2021
Smoke Detector 1st Pharmacy Window Inspected 8:21:03 AM 03/20/2021
Smoke Detector 1st Service Elevator Lobby Inspected 2:18:42 PM 03/20/2021
Smoke Detector 2nd East Central Hall By 2-24 Inspected 9:10:37 AM 03/20/2021
Smoke Detector 2nd North By Nurse Station Inspected 8:42:23 AM 03/20/2021
Smoke Detector 2nd North By Staff 2-28 Inspected 8:43:06 AM 03/20/2021
Smoke Detector 2nd Northeast By Room 2-14 Inspected 8:34:55 AM 03/20/2021
Smoke Detector 2nd Northeast By Room 2-15 Inspected 8:37:04 AM 03/20/2021
Smoke Detector 2nd Northeast By Room 2-17 Inspected 8:37:57 AM 03/20/2021
Smoke Detector 2nd Northeast By Room 2-18 Inspected 8:38:37 AM 03/20/2021
Smoke Detector 2nd Northeast By Room 2-19 Inspected 8:40:03 AM 03/20/2021
Smoke Detector 2nd South By Nurse Station Inspected 9:07:22 AM 03/20/2021
Smoke Detector 2nd South Hall By Staff Room Inspected 9:05:44 AM 03/20/2021
Smoke Detector 2nd Southeast Hall By 2-33 Inspected 9:08:25 AM 03/20/2021
Smoke Detector 2nd Southwest ICU By Room 1 Inspected 9:02:46 AM 03/20/2021
Smoke Detector 2nd Southwest ICU By Room 2 Inspected 8:58:17 AM 03/20/2021
Smoke Detector 2nd Southwest ICU By Room 2-42 Inspected 9:03:30 AM 03/20/2021
Smoke Detector 2nd Southwest ICU By Stairs Inspected 8:56:56 AM 03/20/2021
Smoke Detector 2nd Elevator Lobby Inspected 2:18:27 PM 03/20/2021
Smoke Detector 2nd Hall By Office 2-11 Inspected 9:19:39 AM 03/20/2021
Smoke Detector 2nd Hall By Office 2-27 Inspected 9:12:46 AM 03/20/2021
Smoke Detector 2nd ICU By Patient Room 10 Inspected 8:46:40 AM 03/20/2021
Smoke Detector 2nd ICU By Patient Room 11 Inspected 8:44:01 AM 03/20/2021
Smoke Detector 2nd ICU By Patient Room 7 Inspected 8:48:53 AM 03/20/2021
Smoke Detector 2nd ICU By Patient Room 9 Inspected 8:47:16 AM 03/20/2021
Smoke Detector 2nd Service Elevator Lobby Inspected 2:18:15 PM 03/20/2021
Smoke Detector 3rd North Hall Near Nurses Station Tested 11:03:06 AM 03/20/2021
Smoke Detector 3rd North Hall Near Room 3-17 Tested 11:01:37 AM 03/20/2021
Smoke Detector 3rd Northeast Hall Near Room 3-11 Tested 10:59:22 AM 03/20/2021
Smoke Detector 3rd Northeast Hall Near Room 3-15 Tested 11:00:13 AM 03/20/2021
Smoke Detector 3rd Northwest Hall Near Room 3-50 Tested 10:45:02 AM 03/20/2021
Smoke Detector 3rd Northwest Hall Near Room 3-52 Tested 10:45:42 AM 03/20/2021
Smoke Detector 3rd Northwest Hall Near Room 3-54 Tested 10:46:18 AM 03/20/2021
Smoke Detector 3rd South Hall Near 3-26 Tested 10:52:40 AM 03/20/2021
Smoke Detector 3rd South Hall Near Nurses Station Tested 10:49:41 AM 03/20/2021
Smoke Detector 3rd South Hall Near Stairwell B Tested 10:52:28 AM 03/20/2021
Smoke Detector 3rd Southeast Hall Near Room 3-7 Tested 10:56:43 AM 03/20/2021
Smoke Detector 3rd Southeast Hall Near Room 3-9 Tested 10:58:01 AM 03/20/2021
Western States Fire Protection 20 04/20/2021
Smoke Detector 3rd Southwest Hall Near Room 3-52 Tested 10:44:24 AM 03/20/2021
Smoke Detector 3rd Southwest Hall Near Room 3-59 Tested 10:43:53 AM 03/20/2021
Smoke Detector 3rd West Central Electrical Room Tested 10:48:35 AM 03/20/2021
Smoke Detector 3rd West Hall Near Room 3-57 Tested 10:47:05 AM 03/20/2021
Smoke Detector 3rd Electrical Closet Near Elevator Tested 11:08:09 AM 03/20/2021
Smoke Detector 3rd Elevator Lobby Inspected 2:17:53 PM 03/20/2021
Smoke Detector 3rd Service Elevator Lobby Inspected 2:18:04 PM 03/20/2021
Smoke Detector 4th East Hall Near Room 4-11 Tested 11:30:50 AM 03/20/2021
Smoke Detector 4th North Hall Near Room 4-17 Tested 11:44:31 AM 03/20/2021
Smoke Detector 4th North Hall Near Room 4-19 Tested 11:09:21 AM 03/20/2021
Smoke Detector 4th Northeast Hall Near Room 4-12 Tested 11:34:55 AM 03/20/2021
Smoke Detector 4th Northeast Hall Near Room 4-15 Tested 11:36:24 AM 03/20/2021
Smoke Detector 4th Northeast Hall Near Room 4-24 Tested 11:39:28 AM 03/20/2021
Smoke Detector 4th Northwest Hall Near Room 4-36 Tested 11:11:05 AM 03/20/2021
Smoke Detector 4th Northwest Hall Near Room 4-39 Tested 11:13:15 AM 03/20/2021
Smoke Detector 4th South Hall Near Delivery Room Tested 11:17:41 AM 03/20/2021
Smoke Detector 4th South Hall Near Room 4-33 Tested 11:19:02 AM 03/20/2021
Smoke Detector 4th South Hall Near Room 402 Tested 11:22:10 AM 03/20/2021
Smoke Detector 4th South Hall Near Room 405 Tested 11:23:08 AM 03/20/2021
Smoke Detector 4th South Hall Near Stairwell B Tested 11:26:41 AM 03/20/2021
Smoke Detector 4th South Hall Near Stairwell B Tested 11:29:45 AM 03/20/2021
Smoke Detector 4th Southeast Hall Near Stair 4-8 Tested 11:29:55 AM 03/20/2021
Smoke Detector 4th Southwest Hall Near Room 4-48 Tested 11:15:50 AM 03/20/2021
Smoke Detector 4th West Hall Near Room 4-45 Tested 11:15:41 AM 03/20/2021
Smoke Detector 4th Elevator Lobby Inspected 2:17:33 PM 03/20/2021
Smoke Detector 4th Service Elevator Lobby Inspected 2:17:44 PM 03/20/2021
Smoke Detector 5th East Hall Near Room 5-8 Tested 12:20:23 PM 03/20/2021
Smoke Detector 5th East Hall Near Stairwell-A Tested 12:34:39 PM 03/20/2021
Smoke Detector 5th East Nurses Station Tested 12:28:15 PM 03/20/2021
Smoke Detector 5th North Hall Near Room 5-32 Tested 12:35:04 PM 03/20/2021
Smoke Detector 5th North Hall Near Room 5-45 Tested 12:05:46 PM 03/20/2021
Smoke Detector 5th Northeast Hall Near Room 5-10 Tested 12:25:21 PM 03/20/2021
Smoke Detector 5th Northeast Hall Near Room 5-10 Tested 12:27:18 PM 03/20/2021
Smoke Detector 5th Northeast Hall Near Room 5-35 Tested 11:48:36 AM 03/20/2021
Smoke Detector 5th Northwest Hall Near Room 5-29 Tested 11:51:12 AM 03/20/2021
Smoke Detector 5th Northwest Hall Near Room 5-36 Tested 11:50:02 AM 03/20/2021
Smoke Detector 5th Northwest Hall Near Room 5-38 Tested 11:52:27 AM 03/20/2021
Smoke Detector 5th Southeast Hall Near Room 5-23 Tested 12:16:05 PM 03/20/2021
Smoke Detector 5th Southeast Hall Near Room 5-48 Tested 12:08:13 PM 03/20/2021
Smoke Detector 5th Southeast Hall Near Room 5-5 Tested 12:17:33 PM 03/20/2021
Smoke Detector 5th Southwest Hall Near Room 5-40 Tested 12:00:28 PM 03/20/2021
Smoke Detector 5th Southwest Hall Near Room 5-40 Tested 12:07:13 PM 03/20/2021
Smoke Detector 5th West Hall Near Room 5-39 Tested 12:00:21 PM 03/20/2021
Smoke Detector 5th Electrical Room Near Room 5-26 Tested 12:10:04 PM 03/20/2021
Smoke Detector 5th Elevator Lobby Inspected 1:44:48 PM 03/20/2021
Smoke Detector 5th Hall Near Room 5-2 Tested 12:15:54 PM 03/20/2021
Smoke Detector 5th Service Elevator Lobby Inspected 1:45:13 PM 03/20/2021
Western States Fire Protection 21 04/20/2021
Smoke Detector Penthouse Elevator Control Room Inspected 1:38:03 PM 03/20/2021
Smoke Detector Penthouse Elevator Control Room Inspected 1:38:21 PM 03/20/2021
Smoke Detector Penthouse Inspected 12:40:09 PM 03/20/2021
Smoke Detector Chiller Northeast Mezzanine Inspected 8:44:54 AM 04/14/2021
Smoke Detector Chiller Paint Shop/Tool Storage Inspected 2:15:15 PM 04/14/2021
Smoke Detector Ground East Admin Billing Office Inspected 6:25:11 AM 03/20/2021
Smoke Detector Ground East Business Office Inspected 6:30:14 AM 03/20/2021
Smoke Detector Ground East Electrical Room Inspected 6:27:23 AM 03/20/2021
Smoke Detector Ground East Engineering Prep Room Inspected 6:31:59 AM 03/20/2021
Smoke Detector Ground East Hall By Business Office Inspected 6:28:39 AM 03/20/2021
Smoke Detector Ground East Hall By Telephone Room Inspected 6:34:51 AM 03/20/2021
Smoke Detector Ground East Telephone Room Inspected 6:33:21 AM 03/20/2021
Smoke Detector Ground North Warehouse Area Inspected 6:06:52 AM 03/20/2021
Smoke Detector Ground Northeast Central Admin Area Open
Office
Inspected 6:15:07 AM 03/20/2021
Smoke Detector Ground Northeast Central Admin Area Open
Office
Inspected 6:16:08 AM 03/20/2021
Smoke Detector Ground Northwest Central Admin Area Open
Office
Inspected 6:14:21 AM 03/20/2021
Smoke Detector Ground Northwest Central Admin Area Inspected 6:13:01 AM 03/20/2021
Smoke Detector Ground South Dirty Linen Storage Inspected 7:11:30 AM 03/20/2021
Smoke Detector Ground Southeast Central Admin Area Open
Office
Inspected 6:19:01 AM 03/20/2021
Smoke Detector Ground Southeast Central Admin Area Open
Office
Inspected 6:20:59 AM 03/20/2021
Smoke Detector Ground Southwest Central Admin Area Open
Office
Inspected 6:16:52 AM 03/20/2021
Smoke Detector Ground Southwest Central Admin Area Open
Office
Inspected 6:20:11 AM 03/20/2021
Smoke Detector Ground Southwest Hall By Mail Room Inspected 6:57:25 AM 03/20/2021
Smoke Detector Ground West Business Office Inspected 6:29:27 AM 03/20/2021
Smoke Detector Ground West Kitchen Inspected 6:47:34 AM 03/20/2021
Smoke Detector Ground West Non Sterile Storage Inspected 7:25:56 AM 03/20/2021
Smoke Detector Ground West Warehouse Area Inspected 6:02:54 AM 03/20/2021
Smoke Detector Ground Central Electrical Closet Inspected 7:06:17 AM 03/20/2021
Smoke Detector Ground Clean Linen Storage Inspected 7:24:13 AM 03/20/2021
Smoke Detector Ground Elevator Lobby Inspected 2:22:15 PM 03/20/2021
Smoke Detector Ground Engineering Bio Med Office Inspected 5:59:37 AM 03/20/2021
Smoke Detector Ground Engineering Locksmith Office Inspected 5:57:46 AM 03/20/2021
Smoke Detector Ground Engineering Office Inspected 5:55:20 AM 03/20/2021
Smoke Detector Ground Engineering Office Inspected 5:56:33 AM 03/20/2021
Smoke Detector Ground FACP Room Inspected 5:45:11 AM 03/20/2021
Smoke Detector Ground Housekeeping Inspected 7:02:25 AM 03/20/2021
Smoke Detector Ground Housekeeping Admin Office Inspected 7:01:12 AM 03/20/2021
Smoke Detector Ground Kitchen Food Storage Inspected 6:49:25 AM 03/20/2021
Smoke Detector Ground Kitchen By Hood Inspected 6:46:37 AM 03/20/2021
Smoke Detector Ground Service Elevator Lobby Inspected 2:21:28 PM 03/20/2021
Western States Fire Protection 22 04/20/2021
Smoke Detector NIH Bldg 1 East Exit Inspected 8:49:43 AM 04/13/2021
Smoke Detector NIH Bldg 1 Southwest Room 405 Inspected 8:59:34 AM 04/13/2021
Smoke Detector NIH Bldg 1 Electrical/Telco Room Inspected 8:43:09 AM 04/13/2021
Smoke Detector NIH Bldg 1 Lab 03 Freezer Storage Inspected 8:39:45 AM 04/13/2021
Smoke Detector NIH Bldg 1 Lab 03 Freezer Storage Inspected 8:41:27 AM 04/13/2021
Smoke Detector NIH Bldg 1 Lab Room 202 Inspected 8:42:10 AM 04/13/2021
Smoke Detector NIH Bldg 1 Storage Room 701 Inspected 8:46:34 AM 04/13/2021
Smoke Detector PEDS North Riser Room Inspected 8:10:30 AM 04/14/2021
Smoke Detector PEDS Southeast Corridor By Staff Lounge Inspected 8:00:01 AM 04/14/2021
Smoke Detector PEDS Southeast Office Open Area Inspected 7:59:23 AM 04/14/2021
Smoke Detector PEDS Southwest Office Open Area Inspected 7:58:12 AM 04/14/2021
Smoke Detector PEDS Corridor By Data Room 038 Inspected 7:52:03 AM 04/14/2021
Smoke Detector PEDS Corridor By Directors Office Inspected 8:04:48 AM 04/14/2021
Smoke Detector PEDS Corridor By Exam Room 4 Inspected 7:54:44 AM 04/14/2021
Smoke Detector PEDS Corridor By Exam Room 6 Inspected 8:02:57 AM 04/14/2021
Smoke Detector PEDS Corridor By Housekeeping 027 Inspected 7:51:17 AM 04/14/2021
Smoke Detector PEDS Corridor By Restrooms Inspected 7:55:46 AM 04/14/2021
Smoke Detector PEDS Corridor Women’s By Exam Room 2 Inspected 8:06:14 AM 04/14/2021
Smoke Detector PEDS Waiting Area Inspected 7:48:42 AM 04/14/2021
Smoke Detector PEDS Waiting Area Inspected 8:08:41 AM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:39:21 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:41:11 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:41:23 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:41:36 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:41:50 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:42:01 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:42:12 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:42:22 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:42:32 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:42:42 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:43:03 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:43:13 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:43:25 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:43:34 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:43:58 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:44:07 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:44:18 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:44:29 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:44:37 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:44:47 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:03 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:14 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:25 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:36 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:46 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:45:56 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:46:05 PM 04/14/2021
Western States Fire Protection 23 04/20/2021
Smoke Detector Warehouse High Smoke Inspected 12:46:13 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:46:22 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:46:32 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:46:45 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:47:12 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:47:48 PM 04/14/2021
Smoke Detector Warehouse High Smoke Inspected 12:47:58 PM 04/14/2021
Smoke Detector Women’s Clinic Center Corridor Inspected 10:07:52 AM 04/13/2021
Smoke Detector Women’s Clinic East Corridor Inspected 10:01:50 AM 04/13/2021
Smoke Detector Women’s Clinic East Corridor Inspected 10:04:15 AM 04/13/2021
Smoke Detector Women’s Clinic North Corridor Inspected 10:05:52 AM 04/13/2021
Smoke Detector Women’s Clinic West Corridor Inspected 10:06:29 AM 04/13/2021
Smoke Detector Women’s Clinic West Corridor Inspected 10:07:10 AM 04/13/2021
Western States Fire Protection 24 04/20/2021
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Battery Specialty Services By Receptionist Desk Inspected 10:43:26 AM 04/12/2021
Battery Specialty Services By Receptionist Desk Inspected 10:43:34 AM 04/12/2021
Control Panel Specialty Services By Receptionist Desk Inspected 9:14:16 AM 04/12/2021
Initiating
Duct Detector Specialty Services Corridor By Exam Room #1 Tested 10:49:36 AM 04/12/2021
Duct Detector Specialty Services Corridor By Nurse Station Tested 10:44:55 AM 04/12/2021
Duct Detector Specialty Services Waiting Area Tested 10:51:27 AM 04/12/2021
Pull Station Specialty Services North Exit Tested 11:04:11 AM 04/12/2021
Pull Station Specialty Services Northeast Exit Tested 11:01:00 AM 04/12/2021
Pull Station Specialty Services Northwest Exit Tested 11:02:33 AM 04/12/2021
Pull Station Specialty Services Waiting Area Tested 10:58:02 AM 04/12/2021
Smoke Detector Specialty Services By Receptionist Desk Inspected 9:20:46 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exam Room #1 Inspected 9:39:37 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exam Room #4 Inspected 9:40:45 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exit To Waiting
Area
Inspected 9:45:18 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Pharmacy Window Inspected 9:41:14 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exam Room #3 Inspected 9:55:21 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exam Room #6 Inspected 9:49:51 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Exam Room #8 Inspected 9:48:51 AM 04/12/2021
Smoke Detector Specialty Services Corridor By North Exit Inspected 9:53:27 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Nurse Station Inspected 9:21:08 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #116 Inspected 9:50:45 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #122 Inspected 9:51:43 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #123 Inspected 9:52:37 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #133 Inspected 9:56:13 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #141 Inspected 9:22:16 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office #150
Surgery Department
Inspected 9:37:00 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office 101 Inspected 9:46:20 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Office 105 Inspected 9:47:52 AM 04/12/2021
Smoke Detector Specialty Services Corridor By Women’s
Restroom
Inspected 9:59:10 AM 04/12/2021
Smoke Detector Specialty Services Patient Waiting Area Inspected 9:42:44 AM 04/12/2021
Smoke Detector Specialty Services Patient Waiting Area Inspected 9:43:40 AM 04/12/2021
Western States Fire Protection 25 04/20/2021
MS-9050UD
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Annunciator Dental Clinic Main Entrance Inspected 11:56:39 AM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:10:44 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:11:12 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:11:19 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:11:24 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:14:48 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:15:02 PM 04/12/2021
Control Panel Dental Clinic Southeast Riser Room Inspected 12:01:19 PM 04/12/2021
Power Supply Dental Clinic Southeast Riser Room Inspected 12:11:45 PM 04/12/2021
Power Supply Dental Clinic Southeast Riser Room Inspected 12:13:04 PM 04/12/2021
Voice Evacuation Dental Clinic Southeast Riser Room Inspected 12:13:38 PM 04/12/2021
Initiating
Pull Station Dental Clinic Northeast Exit Tested 11:58:30 AM 04/12/2021
Pull Station Dental Clinic Southeast Exit Tested 11:53:02 AM 04/12/2021
Pull Station Dental Clinic Southeast Riser Room Tested 11:59:43 AM 04/12/2021
Pull Station Dental Clinic Main Entrance Tested 11:57:40 AM 04/12/2021
Smoke Detector Dental Clinic Southeast Riser Room Inspected 12:03:54 PM 04/12/2021
Failed/Other
Control
Battery Dental Clinic Southeast Riser Room Inspected 12:07:49 PM 04/12/2021
Battery Dental Clinic Southeast Riser Room Inspected 12:08:02 PM 04/12/2021
Western States Fire Protection 26 04/20/2021
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Power Supply Dental Clinic Annex Southeast Electrical Room Inspected 7:21:47 AM 04/13/2021
Initiating
Pull Station Dental Clinic Annex Waiting Area Tested 7:10:16 AM 04/13/2021
Smoke Detector Dental Clinic Annex Southeast Electrical Room Inspected 7:18:49 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Housekeeping
Inspected 6:58:44 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Multipurpose
Room 130
Inspected 7:15:36 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Panoramic 128 Inspected 6:59:22 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Room 107 Inspected 7:14:03 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Room 125 Inspected 7:03:52 AM 04/13/2021
Smoke Detector Dental Clinic Annex Corridor By Soiled Utility
Inspected 7:01:56 AM 04/13/2021
Smoke Detector Dental Clinic Annex Storage Room 112 Inspected 7:16:38 AM 04/13/2021
Smoke Detector Dental Clinic Annex Waiting Area Inspected 7:07:19 AM 04/13/2021
Smoke Detector Dental Clinic Annex Waiting Area By Restrooms Inspected 7:12:12 AM 04/13/2021
Control
Battery Dental Clinic Annex Southeast Electrical Room Inspected 7:23:38 AM 04/13/2021
Battery Dental Clinic Annex Southeast Electrical Room Inspected 7:23:55 AM 04/13/2021
Western States Fire Protection 27 04/20/2021
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Control Panel Behavioral Health Bldg 5 By Room C-2 Inspected 2:09:10 PM 04/12/2021
Initiating
Duct Detector Behavioral Health Bldg 5 Corridor By Room
B-16
Tested 2:15:09 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Southeast Exit Tested 2:33:45 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 West Exit Tested 2:30:29 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Breakroom Tested 2:32:31 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Breakroom Office A-3 Tested 2:33:02 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Corridor By Room B-7 Tested 2:31:02 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Corridor By Room B-9 Tested 2:25:21 PM 04/12/2021
Pull Station Behavioral Health Bldg 5 Waiting Area Tested 2:31:34 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Breakroom Office A-3 Inspected 2:19:52 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Breakroom Inspected 2:18:42 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By FACP Inspected 1:56:51 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room
B-10
Inspected 2:13:44 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room
B-15
Inspected 2:14:35 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room B-7 Inspected 2:12:17 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room B-8 Inspected 2:10:29 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room
C-10
Inspected 2:21:30 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Corridor By Room C-6 Inspected 2:17:15 PM 04/12/2021
Smoke Detector Behavioral Health Bldg 5 Waiting Area Inspected 2:23:56 PM 04/12/2021
Control
Battery Behavioral Health Bldg 5 By Room C-2 Inspected 2:36:48 PM 04/12/2021
Battery Behavioral Health Bldg 5 By Room C-2 Inspected 2:37:00 PM 04/12/2021
Western States Fire Protection 28 04/20/2021
Control Panel: 6 - Notifier
NFS-3030D
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Battery NIH Bldg 1 West Basement Inspected 9:07:41 AM 04/13/2021
Battery NIH Bldg 1 West Basement Inspected 9:08:00 AM 04/13/2021
Control Panel NIH Bldg 1 West Basement Inspected 9:04:47 AM 04/13/2021
Western States Fire Protection 29 04/20/2021
Building: Phoenix Indian Medical Control Panel: 7 - Fire-Lite SFP-1024
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Battery PCMC Reception Area Inspected 11:54:19 AM 04/13/2021
Battery PCMC Reception Area Inspected 11:54:33 AM 04/13/2021
Control Panel PCMC Reception Area Inspected 11:50:01 AM 04/13/2021
Initiating
Pull Station PCMC East Exit Tested 12:04:57 PM 04/13/2021
Pull Station PCMC North Exit To Registration Tested 12:15:40 PM 04/13/2021
Pull Station PCMC Northside East Exit Tested 12:18:15 PM 04/13/2021
Pull Station PCMC Northside Northwest Exit Tested 12:20:26 PM 04/13/2021
Pull Station PCMC Northside Nurse Office Station Tested 12:21:26 PM 04/13/2021
Pull Station PCMC Southwest Pharmacy Exit Tested 12:09:52 PM 04/13/2021
Pull Station PCMC Center Corridor Exit Tested 12:02:24 PM 04/13/2021
Pull Station PCMC West Exit Tested 12:02:12 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Exam Room 11 Inspected 12:26:26 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Restroom Inspected 12:33:09 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 17 Inspected 12:32:18 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 19 Inspected 12:31:45 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 24 Inspected 12:31:07 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 28 Inspected 12:30:35 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 30 Inspected 12:30:00 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Room 50 Inspected 12:28:22 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Talking Room Inspected 12:27:01 PM 04/13/2021
Smoke Detector PCMC Northside Corridor By Team Room Silver
A
Inspected 12:29:28 PM 04/13/2021
Smoke Detector PCMC Northside Exit To Registration Inspected 12:25:32 PM 04/13/2021
Western States Fire Protection 30 04/20/2021
MS-5024UD
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Battery Pathology Services Office By East Exit Inspected 1:08:30 PM 04/13/2021
Battery Pathology Services Office By East Exit Inspected 1:09:04 PM 04/13/2021
Initiating
Pull…