Attachment J - Cass Tech HS Inspection Report.pdf
PDF 3 MB Posted
- Solicitation number
- RFP DET 270000000151 2
- Issued by
- Wayne County, Detroit City, Michigan
About this file
This inspection report documents a visual assessment of the roof systems at Detroit Public Schools' Cass Technical High School, conducted on April 24, 2026. The inspection evaluated existing roof conditions installed in 2003/2004 across multiple roof areas (A-Y) to determine remaining surface life. Roof Areas A-S consist of granule surface modified bitumen membrane that was coated in 2021 with rubberized asphalt; Roof Areas T-W contain the original granule surface modified bitumen membrane; and Roof Areas X and Y feature a metal panel standing seam system. The inspection revealed all roof cores were wet with signs of moisture present. The project encompasses approximately 85,000 square feet of roof area across the school building located at 2501 2nd Ave, Detroit, MI 48201, with varying heights ranging from 12 feet to 95 feet and drainage systems consisting of roof drains and eaves.
The inspection recommendations include complete removal of existing roof systems in Areas A-W down to the structural steel deck and installation of an R-30 insulation system with a fully-adhered 60-mil EPDM membrane, eligible for a 20-year warranty. Roof Areas X and Y require no action at this time. The estimated construction cost for full replacement is $2,482,000.00. The inspection identified several issues requiring remediation, including membrane blisters, active leaks, open flashing, vegetation growth on roof surfaces, and deteriorated ladder systems. The report notes that the remaining life assessment assumes no maintenance is performed on the existing systems, with all roof areas requiring replacement within the near term based on their age and current condition.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Detroit Public Schools – Cass Technical Hich School
2501 2nd Ave.
Detroit, MI 48201
June 10, 2026
Detroit Public Schools – Cass Technical Hich School
Table of Contents
Executive Summary Page 3
Roof Plan Page 4
Roof Area Descriptions Page 5
Roof Area Photos Page 14
EXECUTIVE SUMMARY
On April 24, 2026 a visual inspection of the existing roof system was performed. The purpose of this inspection was to determine the estimated surface life left of the existing roof system. All roof were installed in 2003/2004. Roof Areas A-S existing systems consisted of a granule surface modified bitumen roof membrane which was coated in 2021 with a rubberized asphalt coating. Roof
Areas T, U, V & W existing system consisted of the original granule surface modified bitumen roof membrane. Roof Areas X & Y consisted of an existing metal panel standing seam roof system.
Note: All cores that were taking were wet and shoed signs of moisture.
Observations & Recommendations:
Roof Areas A-W: Remove existing roof systems system down to the structural steel deck. Install a
R-30 Insulation system with a fully-adhered 60-mil EPDM membrane. This system is eligible for a
20 year warranty.
Roof Areas X & W: No action required at this time
Estimated Construction Costs:
Full replacement with a R-30 Insulation System with a fully-adhered 60-mil EPDM: $2,482,00.00
ROOF PLAN:
Note: Remaining life of existing roof systems is based on the estimated age of the roofs, visual inspection and assuming no maintenance being performed.
ROOF AREA DESCRIPTIONS:
Roof Area ID: A
Size: 11,007 sf.
Year Installed: 2003/2004
Height: 95 ft
Structural Slope: None
Drainage: Roof Drains
Roof Area ID: B
Size: 1,800 sf.
Year Installed: 2003/2004
Height: 75 ft
Roof Area ID: C
Size: 18,360 sf.
Year Installed: 2003/2004
Height: 75 ft
Roof Area ID: D
Size: 915 sf.
Year Installed: 2003/2004
Height: 75 ft
Drainage: Eave
Roof Area ID: E
Size: 465 sf.
Year Installed: 2003/2004
Height: 77 ft
Roof Area ID: F
Year Installed: 2003/2004
Height: 77 ft
Roof Area ID: G
Size: 435 sf.
Year Installed: 2003/2004
Height: 85 ft
Drainage: Roof Drain
Roof Area ID: H
Size: 2,399 sf.
Year Installed: 2003/2004
Height: 55 ft
Roof Area ID: I
Size: 8,649 sf.
Year Installed: 2003/2004
Height: 45 ft
Roof Area ID: J
Size: 1,620 sf.
Year Installed: 2003/2004
Height: 45 ft
Roof Area ID: K
Size: 338 sf.
Year Installed: 2003/2004
Height: 60 ft
Roof Area ID: L
Size: 492 sf.
Year Installed: 2003/2004
Height: 53 ft
Roof Area ID: M
Size: 3,960 sf.
Year Installed: 2003/2004
Height: 70 ft
Roof Area ID: N
Size: 4,758 sf.
Year Installed: 2003/2004
Height: 35 ft
Roof Area ID: O
Size: 338 sf.
Year Installed: 2003/2004
Height: 53 ft
Roof Area ID: P
Size: 370 sf.
Year Installed: 2003/2004
Height: 40 ft
Roof Area ID: Q
Year Installed: 2003/2004
Height: 40 ft
Roof Area ID: R
Size: 937 sf.
Year Installed: 2003/2004
Height: 40 ft
Roof Area ID: S
Size: 2,534 sf.
Year Installed: 2003/2004
Height: 40 ft
Roof Area ID: T
Size: 1,185 sf.
Year Installed: 2003/2004
Height: 12 ft
Structural Slope: 1/8-inch
Roof Area ID: U
Size: 1,197 sf.
Year Installed: 2003/2004
Height: 12 ft
Roof Area ID: V
Size: 2,534 sf.
Year Installed: 2003/2004
Height: 15 ft
Roof Area ID: W
Size: 1,240 sf.
Year Installed: 2003/2004
Height: 15 ft
Roof Area ID: Y
Size: 15,500 sf.
Year Installed: 2003/2004
Height: 50 ft
Structural Slope: 8:12
Roof Area ID: X
Size: 9000 sf.
Year Installed: 2003/2004
Height: 90 ft
Structural Slope: 8:12
ROOF AREA PHOTOS:
Membrane blisters Membrane blisters
Active leak Open flashing
Overview
Existing wall ladder – Needs to be replaced
Open flashing Overview
Vegetation growing on roof
Existing repairs made to drain sump/membrane blisters
File details come from the government source that posted it. Updated .