Attachment D- CCFEC-Bid-Docs-Drwgs-04-Struc.pdf
PDF 987 KB Posted
- Solicitation number
- S-C01010-00007195
- Issued by
- Clackamas County, Canyonville City, Oregon
About this file
This document is a set of structural design plans and specifications for the Clackamas County Fairgrounds Multiuse Building project. The project is being undertaken by Clackamas County, Oregon, and the City of Oregon City. The plans include details for the foundation, floor slabs, walls, columns, and other structural elements of the new multi-purpose building. Key details include specifications for concrete, reinforcing steel, masonry, and metal building systems. The plans provide loading information, including live loads, snow loads, and seismic and wind loads. The bid for this project is due on July 13, 2023, and the plans indicate this is a bid set, suggesting the project is out for competitive bid.
The plans include standard construction details and requirements, such as submittal procedures, special inspections, and earthwork specifications. Pricing information is not included, but the plans provide a basis for bidders to estimate the construction costs. The project appears to be funded by Clackamas County and/or the City of Oregon City, but specific funding sources are not mentioned. The plans do not indicate any set-asides or preferences, and there is no information provided about any incumbent contractors.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:0
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S001
GENERAL NOTES
AND SHEET
INDEX
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
STRUCTURAL SHEET INDEX
SHEET NUMBER SHEET NAME
S001 GENERAL NOTES AND SHEET INDEX
S002 SPECIAL INSPECTIONS, SYMBOLS AND ABBREVIATIONS
S010 LOADING PLANS
S011 LOADING PLANS
S201A FOUNDATION PLAN - WEST
S201B FOUNDATION PLAN - EAST
S300 TYPICAL CONCRETE DETAILS
S301 FOUNDATION SECTIONS
GRAND TOTAL: 8
DESIGN CRITERIA
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
OSSC 2022
IBC 2021
ASCE 7-16
ACI 318-19
AISC 360-16
AISI S100
AWS D1.1, D1.3 AND D1.8
TMS 402/602-16
2. RISK CATEGORY III
3. GENERAL COLLATERAL LOAD 10 PSF
OTHER SUPERIMPOSED LOADS ARE LISTED ON PLANS. VERIFY LOADS WITH MEP PLANS.
4. LIVE LOADS: SEE S010, S011 FOR LOADING PLANS
5. SNOW:
GROUND SNOW 10 PSF
SNOW EXPOSURE FACTOR 0.9
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.1
FLAT-ROOF SNOW 7 PSF
BALANCED SNOW LOAD 11 PSF
OSSC MIN SNOW LOAD 27 PSF
SEE S011 FOR SNOW DRIFT PLAN
6. SEISMIC:
SEISMIC DESIGN CATEGORY D
IMPORTANCE FACTOR 1.25
SOIL CLASS D
SS 0.791 g
S1 0.367 g
SDS 0.624 g
SD1 0.475 g
TL 16 s
TS 0.761 s
SEISMIC FORCE RESISTING SYSTEM TBD – BY PEMB ENG
R TBD – BY PEMB ENG
Cd TBD – BY PEMB ENG
Ω0 TBD – BY PEMB ENG
ρ TBD – BY PEMB ENG
ANALYSIS PROCEDURE TBD – BY PEMB ENG
DESIGN BASE SHEAR, STRENGTH
LEVEL
TBD – BY PEMB ENG NOTE: FOLLOW PROVISIONS
OF ASCE 7-16 11.4.8 EXCEPTION 2.
7. WIND:
BASIC WIND SPEED V ULT = 103 MPH
EXPOSURE CLASS C
INTERNAL PRESSURE COEFF, GCpi ± 0.18
BASE SHEAR, STRENGTH LEVEL TBD – BY PEMB ENG
GENERAL
1. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. STRUCTURAL SUBSTITUTIONS MAY BE ALLOWED WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. SUPPLIER SHALL PROVIDE SEALED DESIGN CALCULATIONS OR
SUITABLE PRODUCT LITERATURE FOR THE COMPONENTS.
4. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF
NEW WORK.
6. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
7. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
9. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
10. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
11. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
12. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
13. NO HOLES, NOTCHES, BLOCK-OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
14. PENETRATIONS SHALL BE CAST-IN-PLACE AND SHALL NOT BE PERMITTED EXCEPT AS
SHOWN IN THE STRUCTURAL DRAWINGS.
15. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, CONTRACTOR SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH CONDITIONS IN FIELD, TEMPORARY
CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE PROPOSAL
SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK.
SUBMITTALS
1. SUBMITTALS ARE:
a. CONCRETE MIX DESIGNS
b. MATERIAL PRODUCT DATA FOR STRUCTURAL MATERIALS
c. CONCRETE AND MASONRY REINFORCING
d. STEEL FABRICATION AND MISCELLANEOUS METALS
2. SUBMITTALS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
3. SUBMITTALS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DOES NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
4. FOR ADDITIONAL INFORMATION ON REQUIRED SUBMITTALS, SEE INDIVIDUAL MATERIAL
SECTIONS.
DEFERRED SUBMITTALS DELEGATED DESIGN
1. DEFERRED SUBMITTALS PER OSSC SECTION 107.3.4.1 SHALL BE SUBMITTED TO THE
BUILDING OFFICIAL AND THE DESIGN PROFESSIONALS AND REVIEWED PRIOR TO
INSTALLATION.
2. DEFERRED SUBMITTALS ARE:
a. PRE-ENGINEERED METAL BUILDING
b. CURTAIN WALL AND STOREFRONT SYSTEMS
c. STAIRS, ACCESS LADDERS, HANDRAILS, GUARDRAILS, AND GRATING
d. SEISMIC AND/OR GRAVITY SUPPORT AND ANCHORAGE FOR MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION EQUIPMENT AND SYSTEMS
3. ALL DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE QUALIFIED
PROFESSIONAL ENGINEER, REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED,
RESPONSIBLE FOR THE PREPARATION OF THESE DOCUMENTS.
EARTHWORK
1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT DATED JUNE 30, 2022 BY
LANDSLIDE TECHNOLOGY. REPORT IS ON FILE WITH THE ARCHITECT.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
FOOTINGS 2500 PSF
3300 PSF (SEISMIC OR WIND)
FROST DEPTH 1 FT (HEATED)
EQUIVALENT FLUID PRESSURE
AT REST PRESSURE 60 PSF/FT, DRAINED
PASSIVE PRESSURE 350 PSF/FT OF DEPTH
COEFFICIENT OF FRICTION 0.35
3. ALL EXCAVATIONS SHALL BE PROPERLY AND SAFELY BACKFILLED. DO NOT PLACE
BACKFILL BEHIND RETAINING/BASEMENT WALLS BEFORE CONCRETE HAS ATTAINED
SPECIFIED COMPRESSIVE STRENGTH. CONTRACTOR SHALL BRACE OR PROTECT ALL
WALLS BELOW GRADE FROM LATERAL LOADS UNTIL SUPPORTING FLOORS ARE
COMPLETELY IN PLACE AND HAVE ATTAINED 7-DAY STRENGTH MINIMUM. BACKFILLING IS
NOT PERMITTED FOR FOUNDATION WALLS UNTIL SUPPORTED SLAB TOP AND BOTTOM IS
IN PLACE OR THE WALL IS ADEQUATELY BRACED TO RESIST LATERAL LOADS.
CONTRACTOR SHALL PROVIDE FOR DESIGN, PERMITS, AND INSTALLATION OR SHORING
AND/OR SHEETING.
4. CONTRACTOR SHALL PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE
WATER, GROUND WATER OR SEEPAGE. FREE GROUND WATER WAS NOT ENCOUNTERED
IN THE BORINGS. DETAILS OF GROUND WATER INFORMATION CAN BE OBTAINED FROM
THE ABOVE-MENTIONED GEOTECHNICAL REPORT. IF GROUND WATER SHOULD OCCUR
DURING EXCAVATION, SPECIAL PROCEDURES SHALL BE IMPLEMENTED AS
RECOMMENDED BY THE GEOTECHNICAL ENGINEER.
5. WHERE THERE IS NOT SUFFICIENT SPACE FOR SLOPED EMBANKMENTS, SHORING WILL BE
REQUIRED. SEE THE GEOTECHNICAL REPORT FOR INFORMATION REGARDING THE DESIGN
AND INSTALLATION OF THE SHORING. SHORING THAT IS NOT PART OF THE PERMANENT
BUILDING SUPPORT IS THE CONTRACTOR’S RESPONSIBILITY AND OUTSIDE THIS PERMIT.
6. CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING
STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS,
WALLS, SLABS, UTILITIES, ETC.
7. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK
OPERATIONS FOR FILL MATERIAL OR BURIED STRUCTURES SUCH AS CESSPOOLS,
CISTERNS AND FOUNDATIONS. IF ANY SUCH MATERIAL OR STRUCTURES ARE FOUND,
ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY. ALL ABANDONED FOUNDATIONS,
UTILITIES AND OTHER STRUCTURES THAT INTERFERE WITH NEW CONSTRUCTION SHALL
BE REMOVED.
8. ALL FOOTINGS AND SLABS ON GRADE SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL
OR CONTROLLED COMPACTED FILL, REMOVING ANY EXISTING FILL, ORGANIC MATERIAL,
OR UNSUITABLE SOILS, AS RECOMMENDED BY THE GEOTECHNICAL REPORT. EXPOSED
NATURAL SOIL SHALL BE PROOF ROLLED BELOW SLABS ON GRADE.
9. ALL REQUIRED BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING AREA
SHALL BE MECHANICALLY COMPACTED IN 12” LAYERS TO 95% MAXIMUM DRY DENSITY PER
ASTM D1557 AND TO THE APPROVAL OF THE INSPECTION AGENCY.
10. THE MOISTURE CONTENT OF ONSITE CLAYEY SOILS AT THE TIME OF COMPACTION SHALL
BE BETWEEN 2-3% ABOVE OPTIMUM MOISTURE CONTENT.
11. ANY REQUIRED IMPORT FILL SOIL SHALL HAVE A LOW POTENTIAL FOR EXPANSION AND
SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO IMPORTING.
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE
AMERICAN CONCRETE INSTITUTE “ACI DETAILING MANUAL” (SP-066) EXCEPT AS
OTHERWISE SHOWN, NOTED OR SPECIFIED.
2. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR 40 60 80 Fy = 40 60 80 KSI
DEFORMED EPOXY-COATED BARS ASTM A775 Fy = 60 KSI
DEFORMED GALVANIZED-COATED
BARS
ASTM A767 Fy = 60 KSI
DEFORMED BAR ANCHORS ASTM A1064 Fy = 70 KSI
WELDABLE BARS, DEFORMED ASTM A706, GR 60 Fy = 60 KSI
3. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE OUTERMOST
REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3”
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2”
#5 BARS OR SMALLER 1 1/2”
NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
SLABS, JOIST AND WALLS WITH #14 AND #18 BARS 1 1/2”
SLABS, JOISTS AND WALLS WITH #11 BARS OR SMALLER 3/4”
4. WELDING OF REINFORCING BARS TO BE IN ACCORDANCE WITH AWS D1.4.
5. DEFORMED BAR ANCHORS (DBA) SHALL BE AUTOMATICALLY END WELDED WITH SUITABLE
WELDING EQUIPMENT IN THE SHOP OR IN THE FIELD. WELDING SHALL BE IN ACCORDANCE
WITH THE MANUFACTURER.
6. SUPPORTS FOR REINFORCEMENT SHALL HAVE CLASS 2 PROTECTION AS DEFINED IN THE
CRSI MANUAL OF STANDARD PRACTICE, UNLESS OTHERWISE NOTED.
7. SUPPORTS FOR COATED REINFORCEMENT SHALL HAVE CLASS 1 PROTECTION AS
DEFINED IN THE CRSI MANUAL OF STANDARD PRACTICE, UNLESS OTHERWISE NOTED.
8. CONTINUOUS HORIZONTAL REINFORCING SHALL BE LAPPED AT MIDSPAN FOR TOP BARS
AND DIRECTLY OVER SUPPORTS FOR BOTTOM BARS. AT DISCONTINUOUS ENDS, THE TOP
STEEL SHALL BE BENT DOWN 12 BAR DIAMETERS OR 12” MINIMUM, WHICHEVER IS
GREATER.
9. WHERE REINFORCEMENT LENGTH IS SPECIFIED, NO SPLICES ARE PERMITTED WITHIN THE
SPECIFIED LENGTH WITHOUT APPROVAL BY THE STRUCTURAL ENGINEER.
10. DOWELS BETWEEN FOOTINGS AND WALLS OR COLUMNS SHALL BE THE SAME GRADE,
SIZE AND SPACING OR NUMBER AS THE VERTICAL REINFORCING, RESPECTIVELY, UNLESS
OTHERWISE NOTED. PROVIDE FOUNDATION DOWELS TO MATCH SIZE AND SPACING OF
WALL OR COLUMN REINFORCEMENT. EXTEND DOWELS A LAP SPLICE LENGTH INTO WALL
OR COLUMN AND TERMINATE WITH STANDARD HOOK AT BOTTOM OF FOOTING, UNLESS
OTHERWISE NOTED.
11. REINFORCING IN WALL FOOTINGS AND GRADE BEAMS BETWEEN COLUMNS SHALL BE
DEVELOPED (Ld) INTO COLUMN FOOTINGS.
12. CUTTING OF REINFORCING WHICH CONFLICTS WITH EMBEDDED OBJECTS OR SLEEVES IS
NOT ACCEPTABLE.
13. REINFORCING BARS SHALL BE BENT COLD, AND NO METHOD OF FABRICATION SHALL BE
USED WHICH WOULD BE INJURIOUS TO THE MATERIAL. HEATING OF BARS FOR BENDING IS
NOT PERMITTED.
14. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED
ON THE DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
15. USE TEMPLATES TO SET ALL EMBEDDED ANCHOR BOLTS, LEVELING PLATES, AND DOWEL
BARS AS REQUIRED OR INDICATED ON THE DRAWINGS.
16. SUBMIT SHOP DRAWINGS FOR FABRICATION AND PLACEMENT OF REINFORCING STEEL.
INCLUDE SCHEDULES AND DIAGRAMS OF BENT BARS AND SHOW ARRANGEMENT OF
REINFORCEMENT, INCLUDING CONCRETE COVER. STRUCTURAL ENGINEER’S REVIEW WILL
BE FOR COMPLIANCE WITH DESIGN REQUIREMENTS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING DIMENSIONS AND QUANTITIES.
17. ALL CONCRETE NOT OTHERWISE SPECIFIED SHALL BE REINFORCED TO THE MINIMUM
REQUIREMENT OF ACI 318.
18. REINFORCE ALL ARCHITECTURAL CONCRETE TOPPING SLABS WITH 6x6-W1.4xW1.4 WWR
UNLESS OTHERWISE NOTED.
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE CORRESPONDING EDITION OF THE
AMERICAN CONCRETE INSTITUTE PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI
308.1, ACI 318 AND SP-066, UNLESS OTHERWISE NOTED.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER REDUCING ADMIXTURE ASTM C494
3. CONCRETE STRENGTHS SHALL CONFORM TO:
INTENDED USE STRENGTH (PSI) EXPOSURE
CLASS
FOUNDATIONS 4000 N/A
SLAB ON GRADE 4000 N/A
NORMAL-WEIGHT 28-DAY STRENGTH UNLESS OTHERWISE NOTED.
4. THE MODULUS OF ELASTICITY OF ALL CONCRETE SHALL EXCEED 57,000 SQRT(f’c) FOR NORMAL-WEIGHT CONCRETE OR wc1.5 33 SQRT(f’c).
5. DRYPACK OR GROUT SHALL HAVE A MINIMUM 28-DAY STRENGTH OF 7000 PSI.
6. SLAB-ON-GRADE CONSTRUCTION: LOCATE SAW-CUT CONTROL JOINTS ALONG COLUMN
LINES WITH INTERMEDIATE JOINTS SPACED PER THE TABLE BELOW, UNLESS OTHERWISE
NOTED. SLAB PANELS SHALL HAVE A MAXIMUM LENGTH TO WIDTH RATIO OF 1.5:1.
PROVIDE ADDITIONAL CONTROL JOINTS AT ALL RE-ENTRANT CORNERS. REFERENCE
ARCHITECTURAL FOR ADDITIONAL CONTROL JOINT INFORMATION.
THICKNESS (IN) MAXIMUM JOINT SPACING EACH WAY (FT)
4 12
5 13
6 15
8 18
10 20
12 22
7. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ENSURE PROPER
DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, AND EDGES
OF WALLS/FOUNDATIONS PRIOR TO PLACING CONCRETE.
8. UNLESS OTHERWISE NOTED, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS
OR COLUMNS.
9. CONSTRUCTION JOINTS SHALL BE CLEANED BEFORE POUR. LOCATION TO BE APPROVED
BY THE STRUCTURAL ENGINEER. SUBMIT LOCATION PLAN OF ALL PROPOSED JOINTS NOT
INDICATED ON DRAWINGS FOR APPROVAL PRIOR TO BEGINNING WORK.
10. PRIOR TO PLACING CONCRETE, THE CONTRACTOR SHALL ENSURE ALL REINFORCING AND
EMBEDMENTS, INCLUDING COLUMN ANCHOR BOLTS, ARE PROPERLY LOCATED AND
SECURELY TIED IN PLACE.
11. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH
CONCRETE BEFORE PLACING. SECURE SLEEVES TO PREVENT MOVEMENT DURING
PLACING OPERATIONS. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS.
12. CONFIRM WITH ARCHITECT THAT MATERIALS TO BE EMBEDDED ARE SUITABLE FOR
EMBEDMENT IN CONCRETE.
13. CONDUIT, PIPES, AND SLEEVES EMBEDDED IN CONCRETE SHALL CONFORM TO
REQUIREMENTS OF ACI 318, SECTIONS 20.7 AND 26.8.
14. NO ALUMINUM SHALL BE ALLOWED IN THE CONCRETE WORK UNLESS COATED TO
PREVENT ALUMINUM-CONCRETE REACTION.
15. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED WITH A 3/4
INCH CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
16. INTERNALLY VIBRATE ALL CAST-IN-PLACE CONCRETE EXCEPT SLABS-ON-GRADE WHICH
NEED ONLY BE VIBRATED AROUND UNDER FLOOR DUCTS AND OTHER EMBEDDED ITEMS.
VIBRATE TOPS OF COLUMNS.
17. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
18. IF CONCRETE IS PLACED BY PUMPING, SUPPORT SHALL BE PROVIDED FOR THE HOSE. THE
HOSE SHALL NOT BE ALLOWED TO RIDE ON THE REINFORCING AND OTHER EMBEDDED
ITEMS.
19. CONCRETE SLABS SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 7 DAYS.
FORMS FOR CONCRETE WALLS SHALL BE LEFT IN PLACE FOR 7 DAYS OR MAY BE
STRIPPED AFTER 3 DAYS AND COATED WITH AN APPROVED CURING COMPOUND.
20. NO LOADS SHALL BE PLACED ON STRUCTURAL CONCRETE SLABS WITHIN 7 DAYS AFTER
CONCRETE IS PLACED. AFTER CONCRETE IS PLACED, IN NO CASE SHALL THE
SUPERIMPOSED CONSTRUCTION LOADS BE GREATER THAN SPECIFIED DESIGN LIVE
LOADS, UNLESS THE WORK IS SHORED.
21. NOTIFY THE ARCHITECT/STRUCTURAL ENGINEER 48 HOURS MINIMUM PRIOR TO ALL
POURS.
22. CONTRACTOR SHALL SURVEY ALL CONCRETE WORK WITHIN 48 HOURS OF PLACING
CONCRETE TO ENSURE PLACEMENT IS IN ACCORDANCE WITH PROJECT REQUIREMENTS.
23. THE DESIGN AND ENGINEERING OF FORMWORK, SHORING AND RESHORING, AS WELL AS
THEIR CONSTRUCTION, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. FORMS
SHALL BE DESIGNED TO HAVE SUFFICIENT STRENGTH TO SAFELY WITHSTAND THE LOADS
RESULTING FROM PLACEMENT AND VIBRATION OF THE CONCRETE AND SHALL ALSO BE
DESIGNED FOR SUFFICIENT RIGIDITY TO MAINTAIN SPECIFIED TOLERANCES. CONTRACTOR
SHALL SUBMIT DETAILED FORMWORK SHOP DRAWINGS TO THE ARCHITECT TO BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN CONCEPT ONLY.
24. CORING OF CONCRETE IS NOT PERMITTED UNLESS APPROVED BY THE STRUCTURAL
ENGINEER.
25. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING FREE
WATER, FROST, ICE OR SNOW.
26. DURING WINTER CONSTRUCTION, ALL FOOTINGS SHALL BE PROTECTED FROM FROST
PENETRATION UNTIL THE BUILDING IS ENCLOSED AND TEMPORARY HEAT IS PROVIDED.
27. GENERAL CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR SIZE, LOCATION AND HEIGHT
OF MECHANICAL EQUIPMENT PADS ON CONCRETE SLAB ON STEEL DECK AND SLAB-ON-
GRADE.
28. THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND
REVIEWED BY THE TESTING AGENCY. RESPONSIBILITY FOR OBTAINING THE REQUIRED
DESIGN STRENGTH IS THE CONTRACTOR’S. SUBMIT TEST DATA ON EACH PROPOSED MIX
FOR REVIEW IN ACCORDANCE WITH THE APPLICABLE CODE. MIX DESIGNS SUBMITTED
WITHOUT THE REQUIRED TEST DATA WILL BE RETURNED WITHOUT REVIEW.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY AND
CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY AND
CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE STRUCTURAL
ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH MANUFACTURER’S WRITTEN
INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
a. EXPANSION ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
GROUTED
MASONRY
HILTI KB3 (ESR-1385) DEWALT POWER STUD+ SD1 (ESR-2966)
SIMPSON WEDGE-ALL (ESR-1396)
CRACKED
CONCRETE
HILTI KBTZ (ESR-1917) DEWALT POWER STUD+ SD2 (ESR-2502) RED
HEAD TRUBOLT+ (ESR-2427) SIMPSON STRONG
BOLT 2 (ESR-3037)
b. THREADED SCREW ANCHORS
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
GROUTED
MASONRY
HILTI KWIK HUS-EZ
(ESR-3056)
DEWALT WEDGE-BOLT+ (ESR-1678) SIMPSON
TITEN HD (ESR-1056)
CRACKED
CONCRETE
HILTI KWIK HUS-EZ
(ESR-3027)
DEWALT POWER SCREW-BOLT+ (ESR-3889)
SIMPSON TITEN HD (ESR-2713)
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR ASTM A193
GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO COMPONENT
STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW MASONRY, A SCREEN TUBE
SHALL BE PROVIDED.
ANCHORED
INTO
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HOLLOW
MASONRY
HILTI HIT-HY 270
(ESR-4143)
DEWALT AC 100+ GOLD (ESR-3200) SIMPSON
SET-XP (ESR-0265)
GROUTED
MASONRY
HILTI HIT-HY 270
(ESR-4143)
DEWALT AC 100+ GOLD (ESR-3200) RED HEAD A7
ACRYLIC (ESR-3951) SIMPSON SET-XP (ESR-0265)
CONCRETE HILTI HIT-HY 200
(ESR-3187)
DEWALT AC 200+ (ESR-4027) SIMPSON SET-3G
(ESR-4057)
4. CRACKED CONCRETE REPRESENTS ALL CONCRETE FOR PROJECTS LOCATED IN SEISMIC
DESIGN CATEGORY C OR HIGHER, TENSILE ZONES SUCH AS BOTTOMS OF BEAMS AND
SLABS, OR WHERE NOTED ON THE DRAWINGS.
METAL BUILDING SYSTEMS
1. FOUNDATION DESIGN IS BASED ON PRESUMED REACTIONS FROM THE METAL BUILDING
FRAMING ABOVE. ACTUAL REACTIONS SUPPLIED BY THE SELECTED METAL BUILDING
MANUFACTURER MAY DIFFER FROM PRESUMED REACTIONS. BASED ON ACTUAL
REACTIONS SUPPLIED, MODIFICATIONS TO THE FOUNDATION PLAN MAY BE REQUIRED.
GENERAL CONTRACTOR SHALL INCLUDE IN THEIR BID AN ADD AND DEDUCT PRICE PER
CUBIC YARD OF CONCRETE WORK INSTALLED IN CASE SUCH CHANGES ARE REQUIRED.
2. METAL BUILDING MANUFACTURER SHALL ENGAGE A QUALIFIED PROFESSIONAL
ENGINEER, REGISTERED IN THE STATE WHERE THE PROJECT IS LOCATED, TO DESIGN THE
METAL BUILDING AND TO SUBMIT SEALED DRAWINGS AND STRUCTURAL CALCULATIONS.
3. FOUNDATION DESIGN IS BASED ON THE METAL BUILDING COLUMNS HAVING PINNED
BASES AND TRANSFERRING NO MOMENTS TO THE FOUNDATIONS.
4. [ENGR NOTE: COORDINATE THIS NOTE WITH THE DESIGN CRITERIA SECTION FOR
POSSIBLE DUPLICATION.] ALL EXTERNAL LATERAL LOAD RESISTANCE AND STABILITY OF
THE METAL BUILDING IN THE COMPLETED STRUCTURE IS PROVIDED BY (TBD BY METAL
BUILDING MANUFACTURE). THE VERTICAL LATERAL MEMBERS CARRY THE APPLIED
LATERAL LOADS TO THE BUILDING FOUNDATION. THE HORIZONTAL DIAPHRAGM AT THE
ROOF IS PROVIDED BY (TBD BY METAL BUILDING MANUFACTURE) AND DISTRIBUTES THE
LATERAL WIND AND SEISMIC FORCES HORIZONTALLY TO THE VERTICAL LATERAL
MEMBERS. ALL LATERAL RESISTING MEMBERS ARE BY THE METAL BUILDING
MANUFACTURER.
5. METAL BUILDING MANUFACTURER IS SOLELY RESPONSIBLE FOR THE DESIGN AND
MANUFACTURE OF THE METAL BUILDING. THE BUILDING MUST BE DESIGNED TO MEET THE
LOADING INDICATED ON THE DRAWINGS AND THE DESIGN CRITERIA NOTES.
6. METAL BUILDING MANUFACTURER IS TO COORDINATE WITH ARCHITECTURAL DRAWINGS
FOR WINDOW AND DOOR OPENINGS WHEN DESIGNING THE LATERAL SYSTEM.
MASONRY
1. CMU CONSTRUCTION SHALL BE PERFORMED IN ACCORDANCE WITH TMS 402/602
“BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES”.
2. MINIMUM 28-DAY COMPRESSIVE STRENGTHS FOR CMU CONSTRUCTION SHALL BE:
DESIGN ASSEMBLY STRENGTH, f’m 2000 PSI
INDIVIDUAL CONCRETE MASONRY UNITS 2800 PSI
GROUT 2000 PSI
3. CMU MATERIALS SHALL CONFORM TO THE FOLLOWING STANDARDS:
CONCRETE MASONRY UNITS ASTM C90, NORMAL WEIGHT
MORTAR [ENGR NOTE: CHOOSE ONE] ASTM C270,
TYPE S
GROUT ASTM C476
JOINT REINFORCING ASTM A82
4. ALL LOAD BEARING CMU WALLS TO HAVE FULL MORTAR BED, HEAD, AND COLLAR JOINTS.
5. GROUT SOLID ALL JAMBS FULL HEIGHT IN LOAD BEARING CMU WALLS TO UNDERSIDE OF
LINTEL PLUS ONE CELL BEYOND BEARING LENGTH.
6. PROVIDE MINIMUM 1 INCH GROUT BETWEEN MAIN REINFORCING AND/OR BOLTS AND CMU
UNIT FACE. VERTICAL REINFORCEMENT SHALL BE CENTERED IN WALL, UNLESS
OTHERWISE NOTED. VERTICAL REINFORCING BARS SHALL SECURELY BE HELD IN
POSITION BY WIRE TIES OR OTHER APPROVED MEANS TO ENSURE DESIGN LOCATION AND
LAP. PLACE BARS AND LAP PRIOR TO GROUTING.
7. HORIZONTAL BOND BEAM AND VERTICAL REINFORCING SHALL BE CONTINUOUS UNLESS
OTHERWISE NOTED.
8. CELLS SHALL BE IN VERTICAL ALIGNMENT. DOWELS IN FOOTINGS SHALL BE SET TO ALIGN
WITH VERTICAL REINFORCING STEEL.
9. ALL CELLS CONTAINING REINFORCING SHALL BE FILLED SOLID WITH GROUT.
10. LIFTS OF GROUT SHALL BE KEYED 1 1/2 INCHES INTO THE PREVIOUS COURSE BELOW.
11. HORIZONTAL BAR REINFORCEMENT SHALL BE FULLY EMBEDDED IN GROUT IN AN
UNINTERRUPTED POUR.
12. EXCEPT FOR WALL PILASTERS, VERTICAL REINFORCEMENT SHALL BE FIELD CUT FOR 4’-0”
LIFTS AND LAP SPLICED PER LAP LENGTH SCHEDULE.
13. COORDINATE ANY UNIDENTIFIED PIPE OR DUCT PASSING THROUGH STRUCTURAL CMU
WALLS WITH TYPICAL DETAILS, UNLESS OTHERWISE NOTED.
14. SEE ARCHITECTURAL DRAWINGS FOR SURFACE AND HEIGHT OF UNITS, LAYING PATTERN,
AND JOINT TYPE. ALL BLOCK SHALL BE LAID IN RUNNING BOND, UNLESS OTHERWISE
NOTED.
15. PROVIDE HORIZONTAL TIES WHERE CMU ABUTS CONCRETE.
STRUCTURAL SYMBOL LIST
GENERAL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
TOP OF STRUCTURAL FRAMING ABOVE
ELEVATION (+0'-0")
(+16'-3")
TOP OF STRUCTURAL FOUNDATION
BELOW ELEVATION (+0'-0")
(-2'-0")
-1" SLAB DEPRESSION
S STEP IN FOOTING
FOUNDATION SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
N/A
N/A
RAMP DOWN
RAMP UP
SLAB CURB WALL
SLAB DROP
SLAB FOLD
SLAB THICKNESS CHANGE
SLAB/BEAM
SLOPING SLAB DROP
CONCRETE SYMBOLS:
DESCRIPTION DETAIL REFERENCESYMBOL
N/ARAMP (DIRECTION)RAMP UP
STEEL SYMBOLS:
SYMBOL DESCRIPTION DETAIL REFERENCE
RIGID FRAME COLUMN BY OTHERS
SEE ARCH
DIAGONAL BRACE BY OTHERS SEE ARCH
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
S300
SIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE KEY:
NEW WORK
(DARK SOLID LINE/LINE WEIGHT WILL VARY)
NEW WORK BELOW OR BEYOND VIEW
(DARK DASH LINE)
EXISTING TO BE REMOVED
(DARK DASH LINE)
EXISTING WORK TO REMAIN
(HALFTONED SOLID LINE/LINE WEIGHT WILL VARY)
NON STRUCTURAL
(HALFTONED LIGHT SOLID LINE)
GRID OR CENTERLINE
MATERIAL LEGEND:
CONCRETE - CAST-IN-PLACE
CONCRETE - EXISTING
EARTH
GRAVEL OR GRANULAR FILL
GROUT OR DRYPACK OR SAND
MASONRY
METAL / COLD-FORM STUD
PRECAST CONCRETE
STEEL
COLUMN DESIGNATION
BASE PLATE MARK
SF#(+X'-X")
P# (+X'-X")
FOOTING MARK (TOP ELEVATION)
PIER MARK (TOP ELEVATION)
N O R
HT
W XxX
BP
X
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:0
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S002
SPECIAL
INSPECTIONS,
SYMBOLS AND
ABBREVIATIONS
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
STRUCTURAL ABBREVIATION KEY
ABBR: DESCRIPTION: ABBR: DESCRIPTION:
KSF
KSI
L
LBS
LL
LLH
LLV
LONG.
LSH
LSV
LT WT
MAX
MECH
MANUF
MIN
NIC
NTS
OC
OH
OPNG
OSB
PEMB
PCF
PJP
PL
PLF
PSF
PSI
PT
R
REINF
REQD
RTU
SAD
SCHED
SFRS
SIM
SL
S.M.S.
SP
SPECS
SQ
STIFF
STL
SYM
T&B T.O.
TC
TEMP
tf
THK
TRANS
TYP
UON
VERT
VIF
W/
WP
WT
WWR
(E) A.B.
ARCH
B.O.
bf
BF
BM
B.N.
BOTT
BTWN
CFSF
CGS
CJP
CLR
CL
CMU
COL
CONC
CONN
CONST
CONT
COORD
DIA
DL
DET
DWG
DWL
EA
EF
EFF
EL
ELEC
EMBED
E.N.
EOD
EOS
EQ
EQUIP
ETC
EW
EXP
EXT
f 'c
FDN
F.N.
FT
FTG
Fy
GA
GALV
GLB
GT
HORIZ
HSA
HSB
JT
K, KIP
NUMBER OR POUNDS
AT
DEGREE
DIAMETER
EXISTING
ANCHOR BOLT
ARCHITECT, -URE, -URAL
BOTTOM OF
BEAM FLANGE WIDTH
BRACE FRAME
BEAM
BOUNDARY NAILING
BOTTOM
BETWEEN
COLD FORM STEEL FRAMING
CENTER OF GRAVITY OF THE TENDON
COMPLETE JOINT PENETRATION WELD
CLEAR
CENTERLINE
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATION
DIAMETER
DEAD LOAD
DETAIL
DRAWING
DOWEL
EACH
EACH FACE
EFFECTIVE
ELEVATION
ELECTRICAL
EMBEDMENT
EDGE NAILING
EDGE OF DECK
EDGE OF SLAB
EQUAL
EQUIPMENT
ETCETERA
EACH WAY
EXPANSION
EXTERIOR
CONCRETE COMPRESSIVE STRENGTH
FOUNDATION
FIELD NAILING
FOOT
FOOTING
YIELD STRESS
GAGE OR GAUGE
GALVANIZED
GLULAM BEAM
GIRDER TRUSS
HORIZONTAL
HEADED STUD ANCHOR
HIGH STRENGTH BOLT
JOINT
KILOPOUND (1,000 POUNDS)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH
POUNDS
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LONG SIDE HORIZONTAL
LONG SIDE VERTICAL
LIGHTWEIGHT
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OPPOSITE HAND
OPENING
ORIENTED STRAND BOARD
PRE-ENGINEERED METAL BUILDING
POUNDS PER CUBIC FOOT
PARTIAL JOINT PENETRATION WELD
PLATE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST-TENSION, -ED, -ING
RADIUS
REINFORCING, -MENT, -ED
REQUIRED
ROOF TOP UNIT
SEE ARCHITECTURAL DRAWINGS
SCHEDULE
SEISMIC FORCE-RESISTING SYSTEM
SIMILAR
SNOW LOAD
SHEET METAL SCREW
SPACE(S)
SPECIFICATION(S)
SQUARE
STIFFENER
STEEL
SYMMETRICAL
TOP AND BOTTOM
TOP OF
PRE-TENSIONED BOLT
TEMPERATURE
BEAM FLANGE THICKNESS
THICK
TRANSVERSE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
VERIFY IN FIELD
WITH
WORK POINT
WEIGHT
WELDED WIRE REINFORCING
TESTING, INSPECTIONS, AND OBSERVATIONS
1. THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF THE CONSTRUCTION. SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS “SPECIAL INSPECTIONS” AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE.
2. SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION
REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
a. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
b. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION PROGRAM.
c. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
d. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS.
4. SPECIAL INSPECTIONS AND TESTS ARE REQUIRED FOR MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL MANUFACTURER’S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN CHAPTER 17 OF THE IBC OR IN STANDARDS REFERENCED BY
THE IBC. THESE ITEMS INCLUDE:
a. POST-INSTALLED ANCHORS - INSPECTION
5. THE FOLLOWING WORK SHALL BE INSPECTED BY THE SPECIAL INSPECTOR UNLESS SPECIFICALLY WAIVED BY THE BUILDING OFFICIAL.
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
CONCRETE CONSTRUCTION
1. INSPECT REINFORCEMENT AND VERIFY PLACEMENT X ACI 318: CH 20,
25.2, 25.3, 26.2.1-26.6.3
1908.4
2. MATERIAL IDENTIFICATION OF REINFORCING (TYPE/GRADE) X AISC 341: TABLE
J9.1
3. REINFORCING STEEL HAS NOT BEEN REBENT IN THE FIELD X AISC 341: TABLE
J9.1
4. REINFORCING STEEL HAS BEEN TIED AND SUPPORTED AS REQUIRED X AISC 341: TABLE
J9.1
5. REINFORCING STEEL CLEARANCES HAVE BEEN PROVIDED X AISC 341: TABLE
J9.1
6. REINFORCING BAR WELDING:
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706 X AWS D1.4
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16”; AND X ACI 318: 26.6.4
c. INSPECTS ALL OTHER WELDS X
7. INSPECT ANCHORS CAST IN CONCRETE X ACI 318: 17.8.2
8. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS:
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
X ACI 318: 17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a X ACI 318: 17.8.2
9. VERIFY USE OF REQUIRED DESIGN MIX X ACI 318: CH 19,
26.4.2, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
10. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF
THE CONCRETE
X ASTM C172, ASTM
C31, ACI 318: 26.5,
26.12
1907.10
11. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES
X ACI 318: 26.5 1908.6, 1908.7,
1908.8
12. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED
X ACI 318: 26.11.2(b)
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
SOILS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE
THE DESIGN BEARING CAPACITY
X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL
X
3. PERFORM CLASSIFICATIONS AND TESTING OF COMPACTED FILL MATERIAL X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL
X
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT
SITE HAS BEEN PREPARED PROPERLY
X
1 2 3 4 5 6 7 8 9 10 11 12
A
B
C
LL1
LL2
1 2 3 4 5 6 7 8 9 10 11 12
A
B
C
M1
LIVE LOADING LEGEND:
100 PSF LIVE LOAD
125 PSF STORAGE LOAD
LL1
LL2
MEZZANINE LOADING LEGEND:
40 PSF LIVE LOAD
SEE MECH PLAN FOR
UNITS AND LOADS
ASSUMED CONSTRUCTION: POST AND
BEAM, WITH CONCRETE FILLED METAL
DECK
M1
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:1
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S010
LOADING PLANS
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
1/16" = 1'-0"
LEVEL 1 LOADING PLAN
1/16" = 1'-0"
MEZZANINE LOADING PLAN
1 2 3 4 5 6 7 8 9 10 11 12
B
C
S3
S3
S3
S3S3
S3
S1 S2 S2
1 2 3 4 5 6 7 8 9 10 11 12
A
B
C
R2
R1
R3
ROOF LOADING LEGEND:
25 PSF UNBALANCED SNOW LOAD 1
2 PSF UNBALANCED SNOW LOAD 1
5 PSF SOLAR ALLOWANCE (SEE ARCH)
7 PSF UNBALANCED SNOW LOAD 1
NOTES:
1. MIN BALANCED SNOW LOADING: 27 PSF ENTIRE ROOF
2. MIRROR UNBALANCED SNOW LOAD (R1, R2, R3) AROUND
GRIDLINE B FOR, UNBALANCED SNOW LOAD 2
3. ROOF LIVE LOAD: 20 PSF
R1
R2
R3
BOTTOM OF STEEL LOADING LEGEND:
25 PLF LIGHTING/AUDIO LOADING
130 PLF MOVING PARTITION LOAD
(16' PARTITION HEIGHT)
ALLOWABLE 1/8" DIFFERENTIAL
DEFLECTION OVER 12' SPAN
DEMISING WALL ABOVE FRAME 8 PSF
INDUSTRIAL FAN SEE MECH FOR WEIGHT
AND VERIFY LOCATION, ADDITIONAL FRAMING
MAY BE REQUIRED
S1
S2
S3
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:1
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S011
LOADING PLANS
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
1/16" = 1'-0"
BOTTOM OF STEEL FRAME LOADING PLAN
1/16" = 1'-0"
ROOF LOADING LOAD PLAN
1 2 3 4 5 6
B
C
30'-0" 30'-0" 30'-0" 30'-0" 30'-0"
5" CONCRETE SOG
W/ #4 @ 16" OC EW
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF10.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF6.0
(-1'-0")
SF6.0
(-1'-0") SF8.0
(-1'-0")
SF8.0
(-1'-0") SF10.0
(-1'-0")
SF8.0
(-1'-0")
S301
S301
S301
S301
S301
SF4.0
(-1'-0")
SF4.0
(-1'-0")
X-BRACING X-BRACING X-BRACING
X-BRACING
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
7'-0"
UNO
4'-0" TYP
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
C F
.0
C F
.0
C F
.0
C F
.0
C F
.0
C F
.0
C F
.0
S301
SF4.0
(-1'-0")
SF4.0
(-1'-0")
S301
2'-0"
S301
TYP
4 4
SIM
TYP
S301
PEMB MANF VERIFY END WALL
COLUMN QUANITY AND SPACING
IS SUFFICIENT FOR ECONOMIC DESIGN
GENERAL FOUNDATION SHEET NOTES:
1. SEE SHEET S001 FOR GENERAL NOTES
SEE SHEET S002 FOR SYMBOLS/ABBREVIATIONS
SEE SHEET S300 FOR TYPICAL CONCRETE DETAILS
2. TOP OF SLAB ON GRADE = 0'-0" UNO
3. TOP OF EXTERIOR FOOTINGS SHALL BE A MINIMUM
OF 1'-0" BELOW ADJACENT GRADE. CONTRACTOR
SHALL REVIEW EXTERIOR GRADES AND TOP OF
FOOTING ELEVATIONS PRIOR TO FOOTING POUR
4. SAD FOR DIMENSION, ELEVATIONS, SLOPES, CURBS,
STEPS AND PADS
5. CONTRACTOR VERIFY ALL DIMENSIONS WITH ARCH
DRAWINGS
6. SEE ARCHITECTURAL DRAWINGS FOR NON-
STRUCTURAL WALLS.
KEYNOTES:
1. RIGID FRAME COLUMN BY OTHERS, TYP UNO
2. METAL GIRT WALL WITH CMU VENEER, BY OTHERS.
3. TRENCH DRAIN, SEE
4. (6) #5 (10 #5 AT SIM) CONT BARS CENTERED IN
THICKENED SLAB BARS TO BE CONTINUOUS
THROUGH SLAB JOINTS TYP AT ALL FRAMES.
SEE
5. MEZZANINE FRAME COLUMN BY OTHERS, TYP UNO
6. END WALL WIND COLUMN (HSS OR WF), BY OTHERS.
SEE APART OF MEZZANINE FRAMING
WHERE OCCURS
7. HAIRPIN CENTERED IN SLAB, SEE DETAIL
8. COLUMN FOR PARTITION STORAGE BY OTHERS
9. COLUMN FOR STAIR FRAMING BY OTHERS
10. RIGID FRAME COLUMN FOR MOVINGPARTITION WALL,
NO ROOF LOADING.
11. CONTROL JOINT LAYOUT SEE ARCH.
3/S301
6/S301
1/S301
5/S301
4/S300
CONTINUOUS FOOTING SCHEDULE
CF2.0
MARK
2'-0"
WIDTH
1'-0"
THICKNESS
(3) # 6 BOTTOM
LONG REIN
REINFORCING
TRANS REIN
#6 @ 18" OC BOTTOM
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:1
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S201A
FOUNDATION
PLAN - WEST
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
N O R
HT
1/8" = 1'-0"
FOUNDATION PLAN - WEST
SPREAD FOOTING SCHEDULE
MARK LENGTH WIDTH THICKNESS
REINFORCING
LONG DIRECTION SHORT DIRECTION
SF4.0 4'-0" 4'-0" 1'-0" (4) #6 BOTTOM (4) #6 BOTTOM
SF6.0 6'-0" 6'-0" 1'-6" (6) #6 BOTTOM (6) #6 BOTTOM
SF8.0 8'-0" 8'-0" 1'-6" (8) #6 BOTTOM (8) #6 BOTTOM
SF10.0 8'-0" 11'-0" 1'-6" (11) #6 BOTTOM (8) #6 BOTTOM
6 7 8 9 10 11 12
B
C
30'-0" 30'-0" 30'-0" 22'-0" 22'-0" 22'-0"
5" CONCRETE SOG
W/ #4 @ 16" OC EW
SF10.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF6.0
(-1'-0")
SF6.0
(-1'-0")SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
SF10.0
(-1'-0")
SF8.0
(-1'-0")
SF8.0
(-1'-0")
S301
S301
S301
S301
S301
SF4.0
(-7")
SF4.0
(-7")
SF4.0
(-7")
SF4.0
(-7")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")5
7'-0"
UNO
4'-0" TYP
X-BRACING X-BRACING X-BRACINGX-BRACING
X-BRACING X-BRACINGX-BRACINGX-BRACING
SF4.0
(-1'-0")
SF4.0
(-1'-0")
/8
/8
SF4.0
(-7")
SF4.0
(-7")
SF4.0
(-7")
SF4.0
(-7")
7"
S301
TYP
UNO
TYP
UNO
S301
TYP
UNO
S301
TYP
UNO
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
CF2.0
(-1'-0")
C F
.0
C F
.0
C F
.0
C F
.0
C F
.0
C F
.0
S301
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
SF4.0
(-1'-0")
5 9
S301
2'-0"
S301
SIM
4 4
C F
.0
PEMB MANF VERIFY END WALL
COLUMN QUANITY AND SPACING
IS SUFFICIENT FOR ECONOMIC DESIGN
PEMB MANF VERIFY END WALL
COLUMN QUANITY AND SPACING
IS SUFFICIENT FOR ECONOMIC DESIGN
GENERAL FOUNDATION SHEET NOTES:
1. SEE SHEET S001 FOR GENERAL NOTES
SEE SHEET S002 FOR SYMBOLS/ABBREVIATIONS
SEE SHEET S300 FOR TYPICAL CONCRETE DETAILS
2. TOP OF SLAB ON GRADE = 0'-0" UNO
3. TOP OF EXTERIOR FOOTINGS SHALL BE A MINIMUM
OF 1'-0" BELOW ADJACENT GRADE. CONTRACTOR
SHALL REVIEW EXTERIOR GRADES AND TOP OF
FOOTING ELEVATIONS PRIOR TO FOOTING POUR
4. SAD FOR DIMENSION, ELEVATIONS, SLOPES, CURBS,
STEPS AND PADS
5. CONTRACTOR VERIFY ALL DIMENSIONS WITH ARCH
DRAWINGS
6. SEE ARCHITECTURAL DRAWINGS FOR NON-
STRUCTURAL WALLS.
KEYNOTES:
1. RIGID FRAME COLUMN BY OTHERS, TYP UNO
2. METAL GIRT WALL WITH CMU VENEER, BY OTHERS.
3. TRENCH DRAIN, SEE
4. (6) #5 (10 #5 AT SIM) CONT BARS CENTERED IN
THICKENED SLAB BARS TO BE CONTINUOUS
THROUGH SLAB JOINTS TYP AT ALL FRAMES.
SEE
5. MEZZANINE FRAME COLUMN BY OTHERS, TYP UNO
6. END WALL WIND COLUMN (HSS OR WF), BY OTHERS.
SEE APART OF MEZZANINE FRAMING
WHERE OCCURS
7. HAIRPIN CENTERED IN SLAB, SEE DETAIL
8. COLUMN FOR PARTITION STORAGE BY OTHERS
9. COLUMN FOR STAIR FRAMING BY OTHERS
10. RIGID FRAME COLUMN FOR MOVINGPARTITION WALL,
NO ROOF LOADING.
11. CONTROL JOINT LAYOUT SEE ARCH.
3/S301
6/S301
1/S301
5/S301
4/S300
CONTINUOUS FOOTING SCHEDULE
CF2.0
MARK
2'-0"
WIDTH
1'-0"
THICKNESS
(3) # 6 BOTTOM
LONG REIN
REINFORCING
TRANS REIN
#6 @ 18" OC BOTTOM
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:1
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S201B
FOUNDATION
PLAN - EAST
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
N O R
HT
1/8" = 1'-0"
FOUNDATION PLAN - EAST
SPREAD FOOTING SCHEDULE
MARK LENGTH WIDTH THICKNESS
REINFORCING
LONG DIRECTION SHORT DIRECTION
SF4.0 4'-0" 4'-0" 1'-0" (4) #6 BOTTOM (4) #6 BOTTOM
SF6.0 6'-0" 6'-0" 1'-6" (6) #6 BOTTOM (6) #6 BOTTOM
SF8.0 8'-0" 8'-0" 1'-6" (8) #6 BOTTOM (8) #6 BOTTOM
SF10.0 8'-0" 11'-0" 1'-6" (11) #6 BOTTOM (8) #6 BOTTOM
135°
BEND
NOTE:
1. ALL HOOKS, BENDS AND LAPS SHALL BE AS INDICATED UNLESS
SPECIFICALLY NOTED ON DETAIL. FOR LIGHTWEIGHT CONCRETE,
MULTIPLY VALUE FROM THE GENERAL NOTES TABLE BY 1.18.
CAP STIRRUP135° BEND
LAP SPLICE
180° BEND
WIRE REINFORCING
TOGETHER, TYP
'D' = BAR BEND DIAMETER
6d FOR #3 THRU #8 8d FOR #9, #10, AND #11
90°
BEND
MAX SLOPE
ALTERNATE CAP DIRECTION IF
SLAB OCCURS BOTH SIDES OF
BEAM OR LOCATE 90° BEND
TYP ON SLAB SIDE WHERE
SLAB OCCURS ONLY ONE SIDE.
IF NO SLAB OCCURS EITHER
SIDE PROVIDE 135° BEND EACH
SIDE. CAP STIRRUPS MAY BE
USED IN BEAMS UNO.
2 1/2" MIN
4d
' D
' D
GENERAL NOTES
LAP SPLICE PER
OFFSET 90° BEND
M
IN
d
4d
'd' BAR DIAMETER
4" M
IN
6d
'd' BAR DIAMETER
'd' BAR DIAMETER
SEMI-RIGID SEALANT
SEE SPECS
SAWCUT JOINT WITHIN
24 HOURS OF CONCRETE
PLACEMENT
SLAB ON GRADE
SEE PLAN
NOTES:
1. SEE CAST-IN-PLACE CONCRETE GENERAL NOTES
CONCERNING LOCATION OF JOINTS.
S E
E P
L A
N
T H
IC
K
N E
S S t)
1/4" t/
M
IN
IM
U
M
FIRST POUR SUBSEQUENT POUR
2" x 4" CONT SHAPED KEY OR "BURKE", "KEYED KOLD JOINT" OR EQUIVALENT
LOCATED AT CONTRACTOR'S OPTION
REINFORCING
SEE PLAN
TYP
1'-6"
TYP
6"
S E
E P
L A
N
T H
IC
K
N E
S S
CRUSHED ROCK
SLAB ON GRADE - SEE PLAN
REINFORCING - SEE PLAN
NOTES:
1. COMPACT ALL FILL MATERIAL TO 98% OF THE MAXIMUM DRY DENSITY PER ASTM D1557.
2. VAPOR RETARDER TO MEET ASTM E1745, CLASS A AND BE NOT LESS THAN 15 MILS THICK.
3. SEE GEOTECH REPORT FOR SOG CRUSHED ROCK REQUIREMENTS
/3 t)
S E
E P
L A
N T
H
IC
K N
E S
S t)
REINFORCING
SEE PLAN
NOTE:
1. CONTRACTOR OPTION TO PROVIDE CONSTRUCTION JOINT AT STEP.
#4 @ 12" OC
#4 CONT
1'-2"
1'-0" 6"
S E
E P
L A
N
T H
IC
K
N E
S S
F O
R D
E P
R E
S S
IO
N
S E
E P
L A
N A
N D
A R
C H
IT
E
C T
U R
A L
#5 @ 18" OC
#5 @ 12" OC CONT IN CURB
#5 CONT IN SLAB
SLAB ON GRADE - SEE PLAN
SEE
ARCH
S E
E P
L A
N
T H
IC
K
N E
S S
M
A X
STEEL STRINGER
BY STAIR
SUPPLIER
SLAB ON GRADE
SEE PLAN
CONNECTION TO
SLAB BY STAIR
SUPPLIER
2'-0"
(3) #5 BARS,
MID DEPTH
EL (SEE PLAN)
T.O. SLAB
ADD TIES, TYP
SECOND POURFIRST POUR
JOINT SHALL BE WITHIN
MIDDLE 1/3 OF SPAN
ALL REINFORCING
SHALL CONTINUE
UNINTERRUPTED
1#6 EW FOR MEMBERS UP TO 7" WIDE
2#6 EW FOR MEMBERS 8" TO 20" WIDE
4#6 EW FOR MEMBERS 20" TO 40" WIDE
6#6 EW FOR MEMBERS WIDER THAN 40"
TYP
1'-0"
B E
A M
D E
P T
H
"D
3" 3" 3" 3"
INTENTIONALLY
ROUGHEN
FOOTING (LEVEL,
SLOPED OR STEPPED)
PIPE
PIPE
FINISH GRADE
COMPACTED BACKFILL
TAMPED SAND
PIPE
NO EXCAVATION
BELOW THIS LINE
ALL SLEEVES TO BE
1" CLEAR ALL
AROUND PIPE
WALL
NOTES:
1. PIPE DIAMETER SHALL NOT EXCEED 8".
2. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ALL
LOCATIONS, ELEVATIONS, ETC. OF SITE UTILITIES.
3. DETAIL REQUIRED AT ALL UTILITIES HAVING A PLAN
WIDTH UP TO 1'-0". FOR WIDTHS GREATER THAN 1'-0",
SEE PLAN FOR REQUIRED DETAIL.
4. PIPE IS NOT ALLOWED UNDER SPREAD FOOTINGS.
PLACE CONTROLLED LOW STRENGTH
CONCRETE FILL AROUND SLEEVE PRIOR
TO THE FOUNDATION POUR OR POUR
WITH THE FOOTING USING THE FOOTING
MIX. MAKE SAME WIDTH AS FOOTING AND
FULL WIDTH OF PIPE TRENCH (2'-0" MIN)
M
IN
1'-0" MIN
1'-6" MIN
4" MIN
H E
R E
N O
P
IP
E S
4" MIN
A
SECTION A
CASE 1
152"122"94" 108" 137"65"54"33" 43"
91" 101"81"72"63"43"36"29"22"
63"17" 22" 28" 33" 55"49" 78"70" 117"33"25" 42" 50" 94"73" 83" 105"
(SEE NOTES BELOW) (NORMAL WEIGHT CONCRETE)
C L A
S S
B T
E N
S
IO
N S
P L
IC
E f'c P
S I
#9
81"
105"
91"
70"19" 25"
22"
24"
29"
32"
28" 37"
31" 37"
36"
40"
43"
48"
62"54"
72"
80"
63"
70"
47" 56" 93"81"
BAR SIZE
GRADE 60
#4#3 #6#5 #8#7
101"
113"
87"79"
91"
102"
131"118"
#11#10
151"
195"
170"
131"
43"
37"
48"
28"
32"
36"
47" 56"
54"
60"
64"
72"
56"42" 70" 84"
121"
136"
105"81" 93"
94"
106"
107"
121"
118"
153"
136"
157"122" 139" 177"
BOUNDARY, COLUMN AND BEAM
REINFORCING SPLICE DETAIL
SPLICE DETAIL
WALL OR SLAB REINFORCING
B
A
COLUMN
REINFORCING BAR SPLICE AND STRAIGHT
DEVELOPMENT LENGTHS SCHEDULE
*1 1/2" OR WIRED IN CONTACT
NOTES:
1. TABULATED VALUES ARE BASED ON ACI 318-05 CHAPTER 12, GRADE 60
REINFORCING BARS AND NORMAL WEIGHT CONCRETE.
2. CASES 1 AND 2, WHICH DEPEND ON THE TYPE OF STRUCTURAL ELEMENT,
CONCRETE COVER, AND THE CENTER-TO-CENTER SPACING OF THE BARS,
ARE DEFINED AS:
BEAMS AND CASE 1: CONCRETE COVER > 1.0 db AND CTR-CTR SPACING COLUMNS: > 2.0 db AND WITH STIRRUPS OR TIES THROUGHOUT
Ld NOT LESS THAN THE CODE MINIMUM.
CASE 2: CONCRETE COVER < 1.0 db AND CTR-CTR SPACING < 2.0 db.
ALL OTHER CASE 1: CONCRETE COVER > 1.0 db AND CTR-CTR SPACING ELEMENTS: > 3.0 db.
CASE 2: CONCRETE COVER < 1.0 db AND CTR-CTR SPACING
< 3.0 db.
3. LAP SPLICES OF DEFORMED BARS AND DEFORMED WIRE IN TENSION
SHALL BE CLASS B SPLICES EXCEPT THAT CLASS A SPLICES ARE ALLOWED
WHEN ONE-HALF OR LESS OF THE TOTAL REINFORCEMENT IS SPLICED WITHIN
THE REQUIRED LAP LENGTH.
4. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE TABULATED VALUES
BY 1.3.
5. FOR EPOXY-COATED BARS, MULTIPLY THE TABULATED VALUES BY ONE OF
THE FOLLOWING FACTORS:
CONCRETE COVER AND SPACING TOP BARS OTHER BARS
COVER < 3.0 db OR CTR-CTR SPACING < 7.0 db 1.50 1.50 COVER > 3.0 db OR CTR-CTR SPACING > 7.0 db 1.20 1.20
6. db = NOMINAL DIAMETER OF A BAR.
7. TOP BARS ARE HORIZONTAL REINFORCING WITH MORE THAN 12" OF CONCRETE
CAST BELOW THE BAR.
8. OTHER BARS ARE ALL VERTICAL REINFORCING, ALL HORIZONTAL WALL REINFORCING, AND
HORIZONTAL REINFORCING WITH LESS THAN 12" OF CONCRETE BELOW BAR.
9. SMALLER BAR LAP LENGTH MAY BE USED WHEN SPLICING DIFFERENT SIZE BARS.
10. LAP SPLICES ARE NOT PERMITTED IF MECHANICAL SPLICES ARE SHOWN.
11. NON-CONTACT LAP SPLICED BARS SHALL NOT BE SPACED TRANSVERSELY FUTHER
APART THAN ONE -FIFTH OF THE REQUIRED LAP SPLICE LENGTH NOR 6 INCHES.
12. LAP TOP BARS AT MIDSPAN AND BOTTOM BARS AT SUPPORTS UNLESS OTHERWISE
SHOWN.
13. BUNDLED BAR SPLICES:
A. INDIVIDUAL BAR SPLICES WITHIN THE BUNDLE SHALL NOT OVERLAP EACH
OTHER.
B. INCREASE LAP LENGTH 20% AT THREE BARS. INCREASE LAP LENGTH
33% AT FOUR BARS.
FACE OF SUPPORT
COLUMN OR WALL
REINFORCING
BAR
BOTTOM REINF
1 MAX
TOP REINF
1 MAX
EXTEND BAR STRAIGHT UNO
PROVIDE STANDARD HOOK
WHERE NECESSARY
REINFORCING BAR SPLICE AND STRAIGHT
DEVELOPMENT LENGTHS SCHEDULE
"Ld"
"L"
12" MIN
12d OR
"Ld"
12" MIN
12d OR d 1
/2
M
IN
"Ld"
C L A
S S
B T
E N
S
IO
N S
P L
IC
E
TOP
TOP
TOP
OTHER
OTHER
OTHER
f'c P
S I
#9
BAR SIZE
GRADE 60
#4#3 #6#5 #8#7 #11#10
TOP
TOP
TOP
OTHER
OTHER
OTHER
CASE 2
(SEE NOTES BELOW) (NORMAL WEIGHT CONCRETE)
BEAM
139"111"86" 98" 125"59"49"30" 40"
083" 93"74"66"58"40"33"26"20"
57"15" 20" 25" 30" 51"44" 71"64" 107"30"23" 38" 46" 85"66" 76" 96"
0 TOP
OTHER
TOP
OTHER
REF. SCALE IN INCHES
0 1 2
IMEG CORP. RESERVES PROPRIETARY
RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN
THEREON. SAID DRAWING AND/OR DATA
ARE THE EXCLUSIVE PROPERTY OF IMEG
CORP. AND SHALL NOT BE USED OR
REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN
APPROVAL AND PARTICIPATION OF IMEG
CORP. ©2023 IMEG CORP.
1022 SW SALMON STREET
SUITE 300
PORTLAND, OR 97205
P: 503.274.1843 F: 503.273.5696 www.imegcorp.com
PROJECT #22004849.00
PROJECT NUMBER:
SHEET TITLE:
DRAWN BY:
CONSULTANT:
SHEET:
PRELIMINARY
NOT FOR
CONSTRUCTION
Suite 300 503.221.2077
Portland OR 97209 www.lrsarchitects.com
A R C H I T E C T S 720 NW Davis 503.221.1121
PROJECT #22004849.00
/1
/2
:4
:1
P
M A u to d e s k D o c s
/2
.0
L R
S -C
C F
M u lt i- P u rp o s e
/S
.0
L
R S
-C C
F M u lt i-
P u rp o s e
C
.r v t
FSG
S300
TYPICAL
CONCRETE
DETAILS
BID SET
CLACKAMAS
COUNTY
FAIRGROUNDS
MULTI-PURPOSE
BUILDING
694 NE 4TH AVENUE
CANBY, OR 97013
222033
05.05.2023
NO SCALE
TYPICAL REINFORCING DETAILS
NO SCALE
TYPICAL CONTROL JOINT
NO SCALE
TYPICAL CONSTRUCTION JOINT
NO SCALE
TYPICAL SLAB SECTION
2 NO SCALE
TYPICAL SLAB DEPRESSION
NO SCALE
TYPICAL CURB DETAIL
6 NO SCALE
THICKENED SLAB
AT STAIR STRINGER
3/4" = 1'-0"
CONCRETE GRADE BEAM AND
FOOTING CONSTR JOINT
3/4" = 1'-0"
TYPICAL PIPE TRENCH DETAIL
103/4" = 1'-0"
REINFORCING BAR SPLICE SCHEDULE AND NOTES (GRADE 60)
EL (REF PLAN)
T.O. FTG
EL (REF PLAN)
T.O. SOG
C L R
S E
E S
C H
E D
EXTERIOR CONC
OR GRADE
SEE ARCH
FACE OF
CMU VENEER
FOOTING REIN
SEE SCHEDULE
(2) #4 CONT.
AT SLAB EDGE
SECTION AT GIRT WALL
GRID
EL (REF PLAN)
T.O. FTG
EL (REF PLAN)
T.O. SOG
EXTERIOR CONC OR
GRADE
SEE ARCH
SECTION AT…