This is an attachment document detailing tank inspection requirements at Fort Novosel, Alabama, containing specifications for four storage tanks that require inspection services. The document outlines technical specifications for three 12,000-gallon tanks (900, 901, and 908) requiring STI inspections and one larger tank (25647 Tank 2) requiring API 653 Internal inspection.

The specifications include tank dimensions, fuel types (diesel and Mogas), and specific requirements for each tank. The three 12,000-gallon tanks are 8 feet in diameter and 25'4" in length, each with one 24-inch manway, requiring certified strapping charts and manway seal replacement. Tank 25647 is significantly larger with a design capacity of 108,000 gallons (max fill 106,871), measures 27'0" in diameter and 28'2" in height, requires ultrasonic testing, and has two 36-inch manways requiring wiper seal replacement. The total volume of fuel that needs to be transferred and/or disposed of during the inspections is 7,900 gallons.

View the file

Other files

File Type Posted
Response to contractor questions.pdf PDF
Attachment J4 - DIESEL TANK 908 (NOW D-2) INSPECTION_10 MAY 2016.pdf PDF
Attachment F - SP-POL-CMP-INSPECT-FY25- NVL API Internal Inspection Template.docx DOCX document
Attachment C - SP-POL-CMP-INSPECT-FY25-NVL Tank Data Sheet.pdf PDF
Service Contract Act WD 2015-4631 dated 23Dec24.pdf PDF
Attachment 1 CLIN Schedule.pdf PDF
Attachment G - SP-POL-CMP-INSPECT-FY25-NVL Return To Service Letter.docx DOCX document
Diesel Tank Side View.pdf PDF
Installation Questions - (PO 26) SP-POL-CMP-INSPECT-FY25-NVL.pdf PDF
Attachment J1 - API 653_Molinelli Tank 2_18 Feb 2015.pdf PDF
MOGAS Tank Front View.pdf PDF
Attachment J3 - MOGAS TANK 901 (NOW M-1) INSPECTION_10 MAY 2016.pdf PDF
Tank 1_25649_Tank 2_25647_Molinelli.pdf PDF
MOGAS Tank Side View.pdf PDF
Combined Synopsis Solicitation.pdf PDF
Attachment J2 - DIESEL TANK 900 (NOW D-1) INSPECTION_10 MAY 2016.pdf PDF
Attachment H - SP-POL-CMP-INSPECT-FY25-NVL STI External Inspection Template.docx DOCX document
Attachment A - SP-POL-CMP-INSPECT-FY25-NVL General Installation Security Requirements.pdf PDF
Attachment E - SP-POL-CMP-INSPECT-FY25- NVL Inspection Telecon Briefing Template.docx DOCX document
Attachment 2 PerformanceWork Statement.pdf PDF
Attachment D - SP-POL-CMP-INSPECT-FY25-NVL.xlsx XLSX spreadsheet
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SITE CODE INSTALLATION STATE / COUNTRY INSPECTION TYPE FACILITY NUMBER LOCAL ID # FUEL TYPE TANK CAPACITY (GA) TANK DIAMETER (FT) TANK LENGTH / HEIGHT (FT) UT (Yes/No)

ROUNDNESS SURVEY

Req. (Yes/No)

CERTIFIED STRAPPING

CHART Req. (Yes/No)

REPLACE IFR SEAL (Yes/No)

Gallons Remaining will need to be stored/transferred/d isposed of

# Manways & Sizes

NVL Fort Novosel Alabama/ USA STI 900 Diesel 12,000 8' 25' - 4" No No Yes Manway seal will be replaced as part of the STI Inspection

One 24 inch manway

NVL Fort Novosel Alabama/ USA STI 901 Mogas 12,000 8' 25' - 4" No No Yes Manway seal will be replaced as part of the STI Inspection

One 24 inch manway

NVL Fort Novosel Alabama/ USA STI 908 Diesel 12,000 8' 25' - 4" No No Yes Manway seal will be replaced as part of the STI Inspection

One 24 inch manway

NVL Fort Novosel Alabama/ USA

API 653

Internal

25647 Tank 2 F-24 Design Cap: 108,000 Max Fill Cap: 106,871

27'-0" 28'-2" Yes No No Replace Wiper Seal 3100 Two 36 inch manways