Attachment 1 CLIN Schedule.pdf
PDF 71 KB Posted
- Attached to
- Fort Novosel, AL Tank Inspection
- Solicitation number
- PANNWD-25-P-0000-003355
About this file
This is a Contract Line Item Number (CLIN) schedule detailing five specific tank inspection and maintenance services to be performed at Fort Novosel, AL.
The work includes: (1) API Out-of-Service Internal Tank Inspection for Facility 25647 Tank 2, involving transfer of 3,000 gallons of F-24 fuel, cleaning, wiper seal replacement, and UT Survey; (2) Wiper Seal Replacement for the same tank; (3) STI Inspection with strapping charts for Facility 901, involving 1,500 gallons of Mogas fuel transfer and tank strapping to 1/16th inch precision; (4) STI Inspection with strapping charts for Facility 900, involving 1,500 gallons of Diesel fuel transfer; and (5) STI Inspection with strapping charts for Facility 908, involving similar diesel fuel transfer and inspection requirements. All items are firm-fixed-price (FFP) and require kick-off meetings, disposal of up to 100 gallons of fuel/sludge per tank, manway seal replacements, and both draft and final reports.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 1 Job API Out-of-Service Internal Tank Inspection Service – Facility 25647 Tank 2
FFP
All work to conduct Kick-Off Meeting, providing temporary storage, transferring and returning up to 3,000 gallons of F-24 fuel, disposing of fuel/sludge or residual product up to 100 gallons, setting floating pan legs to maintenance level, cleaning the tank, replacing the wiper seal, conducting a UT Survey, returning floating pan legs to operational level, and providing an aboveground storage tank AST Internal Inspection on FAC 25647 Tank 2 and complete DRAFT and FINAL reports.
FOB: Fort Novosel. AL
PSC CD: XXXX
NET AMT
0002 1 Tank Wiper Seal Replacement Facility 25647 Tank 2
FFP
All work to replace wiper seal and pan penetration seals accordance with the PWS.
0003 1 Job STI Inspection with Strapping Charts Tank Inspection Service – Facility 901
FFP
All work to conduct Kick-Off Meeting, temporary storage, transferring and returning up to 1,500 gallons of Mogas fuel, disposing of fuel/sludge or residual product up to 100 gallons, cleaning the tank, tank strapping, providing strapping chart to 1\16th of an inch, replacing manway seal, and providing an aboveground storage tank (STI) Inspection, and complete DRAFT and FINAL reports.
0004 1 Job STI Inspection with Strapping Charts Tank Inspection Service – Facility 900
FFP
All work to conduct Kick-Off Meeting, transferring and returning up to 1,500 gallons of Diesel fuel from one tank to the other in between inspections, disposing of fuel/sludge or residual product up to 100 gallons per tank, cleaning the tank, tank strapping, providing strapping chart to 1\16th of an inch, replacing manway seal, and providing an aboveground storage tank (STI) Inspection and complete DRAFT and FINAL reports.
0005 1 Job STI Inspection with Strapping Charts Tank Inspection Service – Facility 908
FFP
All work to conduct Kick-Off Meeting, transferring and returning up to 1,500 gallons of Diesel fuel from one tank to the other in between inspections, disposing of fuel/sludge or residual product up to 100 gallons per tank, cleaning the tank, tank strapping, providing strapping chart to 1\16th of an inch, replacing manway seal, and providing an aboveground storage tank (STI) Inspection and complete DRAFT and FINAL reports.