Q997, SOF NSWG-2 Combat Service Support Facilities 1626397 JEB Little Creek-Fort Story, Virginia Beach, Virginia

PART SIX - ATTACHMENTS - Page 1

PART SIX – ATTACHMENTS

A. Q997 FF&E SUMMARY

B. 28 31 76.00 22 INTERIOR COMBINATION EMERGENCY COMMUNICATIONS SYSTEMS

C. HYDRANT FLOW TEST RESULTS

D. Q997 GEOTECHNICAL REPORT - (UNDER SEPARATE COVER)

E. A/V SYSTEM REQUIREMENTS SHEETS

F. NSW COASTAL CAMPUS ADP LIGHTING

G. PKG 3 P334 LOGSU IFC DRAWINGS BOAT STORAGE- (ELECTRONICALLY ONLY)

H. CRANE INFORMATION FORM FOR OVER HEAD ELECTRIC TRAVELING CRANE(S)

I. HAZARDOUS MATERIALS REPORT

J. A BOVEGROUND STORAGE TANK (AST) CLOSURE REPORT FORM

K. TOPGOGRAPHIC SURVEY

L. PERMIT RECORD OF DECISION (PROD)

M. UTILITY CONNECTION PERMIT APPLICATION AND INSTRUCTIONS

N. LOW IMPACT DEVELOPMENT (LID)

O. LOGSU SOCOM Little Creek-Armory Gear and Supply Rev1 Dwgs_01-27-20

P. Q997 FINAL DRAWINGS

[THIS PAGE INTENTIONALLY LEFT BLANK]

Attachment A

Q997 FF&E SUMMARY

!*.//01()(

234567 :39;<5=> ?45@ A>

BC5

A> 3@6

DEEFGHIFJKGI

L���

MN

O P

QRS

ITEM #427

0�����

1������������������� ��������������2�������&�����������������!�������������"��������

�������������������������3�����!

4567897:;8<=>?

����� @ABCCDEFGF

������0�H� *�I�$��"�I

�����J�����K����� ,�"*,I

L������0���� �"�I�M�

�������N���� O"POI

0������N�

����� �"QI

1��������0���� �"�I�M�

�����J�����R���� SM,���

��������0���� "�Q%I�M�

R����R���� %���

N� ���������#����T�� �S"�I

N�

������U�������������L�� SS"PI

��#�� ,,�-�M������

VWX

���������� 0�12 34�35) 6 32� 7�()�3�8

�"#���$%&% �+�, ����%&%�"/ ����/+9 :;<=>?@ABB C

DEF�G6EH�IJ�KLLEMG�N�GIO��DG

P� /�P�+�,�-../ �� �����Q�

RSTUVSW�X�YVZ[T[\]Z

H�1�5�� �G� ̂32�

_ �̀-aa�b� c/. /�� b�

+,���d eb �

���������f�� ,�g /̀ d b/��

-aa�b� �����#b� h-i� j ,�

I�5���k1 l�-�#�l � /+,�� /g�a ��-.����� mnopqors�tuvwxyzonp�m{|}}~������mqxy�{zqxx�mzn�q���z�ysq�{zo�q�

+,-.�/0/0123 � ���45$

67�89&:''

;<==�>?�@A�BCDEFDGH�IDJ>

*��5� �� 4

KHF�BBLM0/NOLP+�JHFF>�QF>CE�RFS=DSG�RTCUF�DSV?TW?TC>FJ

X�����������Y�����>?

QCUF���������Y�����>HC>�C�J>CS=CT=�R?Z�RTCUF�VCS[>�=?\

()������������������QCZDQ̂ Q�VCWCVD>A�R?Z�CS=�WCS�RTCUF\

_?̂�VCS�VECQW�>HF�QC>FTDCE�̀D>H�>HF��

�������a�J?�>HC>�R?>H HCS=J�CTF�bTFF�b?T�W?JD>D?SDSG�>HF�JHFF>�QF>CE\ X�����������Y����EF>�bECSGFJ CS=�bECWJ�HCSG�=?̀ S�̀HDEF�J>DEE�CEE?̀ DSG�A?̂�>?�GF>�VE?JF�>?

>HF�RFS=�EDSF\

��c����Y����� ��HFEWJ�A?̂�QCUF�TFWFC>CREF�WCT>J�b?T WT?=̂V>D?S�T̂SJ�̀D>H?̂>�=DbbDV̂E>A\ +DQWEF�Y�����������c��������EF>J�A?̂�̀?TU�?S�dCTD?̂J GĈGFJ�?b�JHFF>�QF>CE\ ��������������CJJDJ>J�DS�EDb>DSG�>HF�CWT?Sa�JCdDSG Fbb?T>�b?T�>HF�?WFTC>?T\

���������������������Y�����������̀DEE�ECJ>�>HT?̂GH�AFCTJ

b?T�WT?=̂V>DdF�̂JF\ BCDEFDGH�V?dFTJ�>HDJ�JHFF>�QF>CE�bDSGFT�RTCUF�̀D>H�C�(%����

������X��������CJ�̀FEE�CJ������������������������

���Y�

�e�@CUDSG�QCSA�JDfFJ�CS=�JHCWFJ�?b�>CSUJa

WCSJa�R?ZFJa�CS=�Q̂ VH�Q?TF\ gh@i�j�kilik+mBIi�Omnoik�Bk<,i�BBLM0/NOLP+ p����� ��q�(%98'%)&r%(9(s

/ �**��4�5��� ��pt������pt4��

ITEM #428

*+,�-.-�/0-12*

3��� 4����� $$56789:5;<

?<<@ 89 ?A7

A'6B

$�#
C��� 7

D 8E6F

<�G�� 8H =����I A

858JAKI

L

AKI

EKI

9K

M�N�� O� ���

P��� � Q97���

67K

�&&��
;�������
?3>

��@ 9R%AR%6A

S ���T�>� N��

���UVWXYU�

+XWZW�U�UWY

��U\]

VWX

̀WXa -YVWXb��UWY

Attachment B

28 31 76.00 22 INTERIOR COMBINATION

EMERGENCY COMMUNICATIONS

SYSTEMS REGIONAL SPECIFICATION

EXAMPLE

SECTION 28 31 76.00 22

INTERIOR COMBINATION EMERGENCY COMMUNICATIONS SYSTEMS

04/16

PART 1 GENERAL

1.1 RELATED SECTIONS

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein. In addition, refer to the following sections for related work and coordination:

[Section 21 12 00 STANDPIPE SYSTEMS] [Section 21 13 13.00 20 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION] [Section 21 13 16.00 20 DRY-PIPE FIRE SPRINKLER SYSTEMS] [Section 21 21 00 FIRE EXTINGUISHING SPRINKLER SYSTEMS (RESIDENTIAL)] [Section 21 30 00 FIRE PUMPS] [Section 14 21 00.00 20 ELECTRIC TRACTION ELEVATORS] [Section 14 24 00 HYDRAULIC ELEVATORS] [Section 23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST

SYSTEMS]

[Section 08 71 00 DOOR HARDWARE] [Section 07 84 00 FIRESTOPPING for additional work related to firestopping.] [Section 21 23 00.00 20 WET CHEMICAL FIRE EXTINGUISHING for KITCHEN

CABINET]

[Section 21 13 19.00 20 [DELUGE][PREACTION] FIRE SPRINKLER SYSTEMS] [Section 21 13 20.00 20 FOAM FIRE EXTINGUISHING FOR AIRCRAFT HANGARS] [Section 21 13 21.00 20 FOAM FIRE EXTINGUISHING FOR FUEL TANK

PROTECTION]

[Section 21 13 22.00 20 FOAM FIRE EXTINGUISHING FOR HAZ/FLAM MATERIAL

FACILITY]

[Section 21 21 01.00 20 CARBON DIOXIDE FIRE EXTINGUISHING (HIGH

PRESSURE)]

[Section 21 21 02.00 20 CARBON DIOXIDE FIRE EXTINGUISHING (LOW

PRESSURE)]

1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ACOUSTICAL SOCIETY OF AMERICA (ASA)

ASA S3.2 (2009; R 2014) Method for Measuring the Intelligibility of Speech Over Communication Systems (ASA 85)

FM GLOBAL (FM)

FM APP GUIDE (updated on-line) Approval Guide

SECTION 28 31 76.00 22 Page 1 http://www.approvalguide.com/

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits

IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)

IEC 60268-16 (2003; ED 4.0) Sound System Equipment - Part 16: Objective Rating Of Speech Intelligibility By Speech Transmission Index

INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)

ISO 7240-16 (2007) Fire Detection And Alarm Systems — Part 16: Sound System Control And Indicating Equipment

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 101 (2015; ERTA 2015) Life Safety Code

NFPA 170 (2015) Standard for Fire Safety and Emergency Symbols

NFPA 241 (2013; Errata 2015) Standard for Safeguarding Construction,Alteration, and Demolition Operations

NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code

NFPA 72 (2016) National Fire Alarm and Signaling Code

NFPA 90A (2015) Standard for the Installation of Air Conditioning and Ventilating Systems

NFPA 720 (2015) Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

47 CFR 15 Radio Frequency Devices

47 CFR 90 Private Land Mobile Radio Services

SECTION 28 31 76.00 22 Page 2

UNDERWRITERS LABORATORIES (UL)

UL 1480 (2003; Reprint Oct 2012) Standard for Speakers for Fire Alarm, Emergency, and Commercial and Professional Use

UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired

UL 2017 (2008; Reprint May 2011) General-Purpose Signaling Devices and Systems

UL 228 (2006; Reprint Nov 2008) Door Closers-Holders, With or Without Integral Smoke Detectors

UL 268 (2009) Smoke Detectors for Fire Alarm Systems

UL 268A (2008; Reprint Oct 2014) Smoke Detectors for Duct Application

UL 464 (2009; Reprint Apr 2012) Standard for Audible Signal Appliances

UL 521 (1999; Reprint Apr 2015) Heat Detectors for Fire Protective Signaling Systems

UL 864 (2014) Standard for Control Units and Accessories for Fire Alarm Systems

UL Electrical Constructn (2015) Electrical Construction Equipment Directory

UL Fire Prot Dir (2015) Fire Protection Equipment Directory

1.3 DEFINITIONS

Wherever indicated in this specification or on the contract drawings, the equipment, devices, and functions shall be defined as follows:

a. COMBINATION EMERGENCY COMMUNICATIONS SYSTEM: NFPA 72 terminology describing a combination fire alarm and mass notification system where the building mass notification system is integrated with the building fire alarm control unit to form one combined system that performs both functions.

b. COMBINATION EMERGENCY COMMUNICATIONS SYSTEM PANELS (CECP):

Combination Emergency Communications System Panel may consist of separate autonomous control unit and fire alarm control unit supplied from the same or different manufacturers, or a single panel supplied by one manufacturer. Where the term "COMBINATION EMERGENCY COMMUNICATIONS SYSTEM PANEL" or "CECP" is utilized the intent is NOT to limit the designer to one manufacturer or a single enclosure.

HOWEVER; whether installed as combined or separate panels or provided by one or separate manufacturers, the panels shall be integrated in their controls and performance to meet the requirements of this section and NFPA 72.

SECTION 28 31 76.00 22 Page 3

c. AUTONOMOUS CONTROL UNIT (ACU): The primary control unit for the building mass notification system portion of the CECP. ACU may be physically separate from, or a integral part, of the FACU.

d. FIRE ALARM CONTROL UNIT (FACU): Fire alarm system component portion of the CECP, provided with primary and secondary power sources, which receives signals from initiating devices or other fire alarm control units, and processes these signals to determine part or all of the required fire alarm system output function(s). FACU may be separate from or a portion of the ACU. Where more than one fire alarm control unit is installed in the building, one panel shall be designated as the Master Fire Alarm Control Unit.

e. SUPPLEMENTARY FIRE ALARM CONTROL PANELS: When necessary multiple interconnected fire alarm control units may be utilized to create a networked system consisting of a master fire alarm control unit and one or more supplementary fire alarm control panels capable of peer to peer communications. Networked panels shall be UL Listed as compatible. Interconnecting separate manufacturers' fire alarm panels or fire alarms panels not capable of peer-to-peer communications is prohibited. The term "supplementary fire alarm control panel" does not refer to releasing service fire alarm panels.

f. LOCAL OPERATING CONSOLE (LOC): Equipment used by authorized personnel and emergency responders to make live voice building-wide mass notification system messages

g. SUPPLEMENTARY NOTIFICATION APPLIANCE CIRCUIT(SNAC)and AUXILIARY POWER SUPPLY PANELS: A panel separate from the "combination emergency communications system panel"(s), usually located remote from the main panel(s). SNAC's are utilized to power visual notification appliance circuits and auxiliary power supplies provide supplementary power to devices or functions requiring power in addition to that available from the SLC.

h. MONITOR MODULE: Term utilized to describe a Signaling Line Circuit Interface as defined by NFPA 72.

i. CONTROL MODULE AND RELAY MODULE: Terms utilized to describe an "Emergency Control Function Interface" as defined in NFPA 72.

j. TERMINAL CABINET: A steel cabinet with locking, hinge-mounted door that terminal strips are securely mounted inside. Utilizing tape or glue is not an acceptable means of mounting terminal strips.

k. TEXTUAL AUDIBLE APPLIANCES: Term utilized by NFPA 72 to describe speaker appliances. The term "textual audible appliance" is utilized because the term "speaker" might also refer to a person who is speaking.

1.4 SYSTEM DESCRIPTION

1.4.1 Scope

This work includes completion of design and [providing a new, complete,] [and] [modifying the existing] combination emergency communications system as described herein and on the contract drawings for [building name].

Fire Alarm Control Unit portion shall be an analog/addressable system.

SECTION 28 31 76.00 22 Page 4

Include in the system all necessary wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically indicated or described. Provide system[s] complete and ready for operation.

[Equipment and devices shall be compatible and operable with existing building [fire alarm] [combination fire alarm and mass notification system]. Equipment shall not impair reliability or operational functions of the existing system. The existing building system panel is [Make, Model & Manufacturer]]

[Equipment and devices shall be compatible and operable with the existing fire alarm reporting system and shall not impair reliability or operational functions of the existing system. Existing fire alarm reporting system is a "[100mA Gamewell loop][radio transmitters][DACT][dedicated [copper][fiber] phone pair]" system and utilizes [digital electronic telegraphic fire alarm][Monaco][King-Fisher (KFCi)][Digitize][AES Intellinet] transmitters.]

[Equipment and devices shall be compatible and operable with existing installation-wide mass notification system and shall not impair reliability or operational functions of the existing system. The installation-wide mass notification system utilizes [Cooper/Madahcom][Federal Signal][King-Fisher (KFCi)][Whelen][ATI][HyperLink][Genesis][Altelicon][StreamLine]tranceivers.]

a. Provide equipment, materials, inspection, and testing in strict accordance with the required and advisory provisions of NFPA 72, ISO 7240-16, and IEC 60268-16 except as modified herein. [The system layouts on the contract drawings show the intent of coverage and are shown in suggested locations. Final quantity, system layout, and coordination are the responsibility of the Contractor.][ A single fire alarm control unit is indicated with terminal cabinets at each floor, at each riser location.]

[b. [Where remote supplementary fire alarm control units, supplementary notification appliance circuit panels, or supplementary power supply panels are needed, they shall be provided at the locations indicated. Contact the NAVFAC [MIDLANT][ ] Fire Protection Engineer if locations for remote panels have not been indicated.] [Each remote fire alarm control unit shall be powered from a wiring riser specifically for that use. Where remote fire control units are provided, equipment for notification appliances may be located in the remote fire alarm control units.]]

1.4.2 Technical Data and Computer Software

Computer software and technical data relating to computer software that are specifically identified in this project, and may be defined/required in other specifications, shall be delivered in accordance with the CONTRACT CLAUSES. Data to be submitted shall include complete system, equipment, and software descriptions. Descriptions shall show how the equipment will operate as a system to meet the performance requirements of the contract. The data package shall also include the following listed.

Failure to fully comply with the following stipulations shall result in the removal and replacement of the combination emergency communications

SECTION 28 31 76.00 22 Page 5 system at no cost to the Government. Requests for extension of time for any delay to the completion of the project due to the removal, redesign, resubmittal process, and replacement of the original system will not be considered. Liquidated damages shall apply and will be assessed in accordance with the contract clauses.

a. Identification of programmable portions of system equipment and capabilities.

b. Description of system revision and expansion capabilities and methods of implementation detailing both equipment and software requirements.

c. Provision of operational software data on all modes of programmable portions of the combination emergency communications system.

d. Description of Fire Alarm Control Unit equipment operation.

e. Description of auxiliary and remote equipment operations.

f. Library of application software.

g. Operation and maintenance manuals.

1.4.3 Keys

Keys and locks for equipment, panels and devices shall be identical.

Provide the Contracting Officer with no less than six (6) keys of each type required. Direct requests for keys from all Government personnel to the Contracting Officer. Under no circumstances shall the contractor provide any keys to the building occupants. If any portion of building is occupied during construction or occupants begin moving into the building prior to project completion, the fire alarm contractor shall remove and secure all keys to the combination emergency communications system. [All keys and locks shall be mastered to a single key as required by the AHJ.] [Keys shall be CAT [60][_____].]

1.5 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for the Prime Contractor Quality Control approval. The NAVFAC [MIDLANT] [ ] Fire Protection Engineer shall review and approve all submittals requiring Government approval.

[[Provide electronic submittals.] [If permitted by the Contracting Officer, provide electronic submittals.] File format of electronic submittal materials shall be portable document format. No other electronic formats shall be accepted. Catalog data shall be first generation scans or manufacturer's originals. Shop drawings shall be plotted to scale. Scale all line weights. Submittals consisting of illegible pdf's shall be returned disapproved without review. One hard copy review set of the entire package, including full scale shop drawings, shall accompany each submittal for use by the NAVFAC [MIDLANT] [ ] Fire Protection Engineer. The single hard copy review set shall be retained by the Government reviewer. The Government reviewer shall digitally stamp, sign and lock the electronic submittal package prior to returning the electronic copy to the Contracting Officer.]

SECTION 28 31 76.00 22 Page 6

Submit the following in accordance with Section 01 33 00 SUBMITTAL

PROCEDURES:

SD-01 Preconstruction Submittals

Within 36 days of contract award but no less than 14 days prior to commencing any work on site, the Prime Contractor shall submit the following for review and approval:

Qualifications for Fire Alarm System Subcontractor; G

On Staff Fire Alarm System Designer(s); G

Supervising Fire Alarm Technician; G

Installing Technicians; G

Testing Personnel; G

Contractor SD-02,SD-03 & SD-05 submittals received prior to the review and approval of the Qualifications of the Fire Alarm Subcontractor shall be returned Disapproved Without Review. All resultant delays shall be the sole responsibility of the Prime Contractor.

Contract requirements for the Fire Alarm Contractor to have NICET Certified Fire Alarm Technicians on staff are NOT negotiable. The Prime Contractor's Quality Control Manager shall not endorse nor submit the qualifications for the fire alarm system subcontractor if fire alarm contractor does not have the required NICET Technicians on staff. All resultant delays shall be the sole responsibility of the Prime Contractor.

SD-02 Shop Drawings

Include Annotated catalog data, in table format on the drawings, showing manufacturer's name, model, voltage, and catalog numbers for equipment and components. Submitted shop drawings shall not be smaller than ANSI D (22 in x 34 in).

Wiring Diagrams; G

Provide point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that are supervised or controlled by the system. Diagrams shall show connections from field devices to the CECP and remote fire alarm control units, initiating circuits, switches, relays and terminals. Point-to-point wiring diagrams shall be job specific. Point-to-point wiring diagrams shall not indicate connections or circuits not being utilized.

Provide complete riser diagrams indicating the wiring sequence of devices and their connections to the control equipment.

Include a color-code schedule for the wiring. Include floor plans showing the locations of devices, appliances, and equipment.

System Layout; G

SECTION 28 31 76.00 22 Page 7

Plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, conduit sizes, wire counts, wire color-coding, circuit identification in each conduit, and circuit layouts for all floors. Drawings shall comply with the requirements of NFPA 170, and NFPA 72. Indicate candela rating of each visual notification appliance. Indicate the wattage of each speaker. Clearly identify the locations of isolation modules. Indicate the addresses of all devices, modules, relays, etc.

System Operation; G

A complete list of device addresses, [and] corresponding messages.

Provide a complete description of the system operation in matrix format.

Notification Appliances; G

Provide data on each circuit to indicate that there is at least [25][50] percent spare capacity on each notification appliance circuit, a [25][50] percent spare capacity for each supplementary notification appliance circuit panel and auxiliary power supply panel, and [25][50] percent spare capacity for each signaling line circuit. Annotate data for each circuit on the drawings.

Amplifiers; G

Provide data to indicate the amplifiers have sufficient capacity to simultaneously drive all notification speakers at the wattage setting required to meet intelligibility requirements while maintaining a minimum [25][50] percent spare capacity. Annotate data for each circuit on the drawings. Contractor shall be responsible for additional and/or larger amplifiers if adjustments during testing to meet intelligibility requirements reduces the spare capacities to less than [25][50] percent.

As-Built Drawings

Provide four sets of detailed as-built drawings. Furnish four sets of CD or DVD discs containing software backup with CAD-based drawings in latest version of AutoCAD *.dwg format of as-built drawings and schematics. Discs shall also include as-built drawings plotted to scale in *.pdf format along with *.pdf copies of the manufacturer's data, and calculations. The drawings shall include complete wiring diagrams showing point-to-point connections between devices and equipment, both factory and field wired. Include a riser diagram and drawings showing the as-built location of devices and equipment. The drawings shall show the system as installed, including deviations from both the contract drawings and the approved shop drawings. These drawings shall be submitted within 14 days after the final acceptance test of the system. At least one copy of the as-built (red-lined) drawings shall be provided at the time of, or prior to, the final acceptance test.

SD-03 Product Data

SECTION 28 31 76.00 22 Page 8

Provide UL or FM listing cards for equipment provided. Include annotated catalog data, in table format, showing manufacturer's name, model, voltage and catalog numbers for all equipment and components.

Technical Data And Computer Software; G

Fire alarm control unit (FACU); G Autonomous control unit (ACU); G Combination emergency communications system panel (CECP); G Local operating consoles (LOC); G [Supplementary fire alarm control units; G] Amplifiers; G Digitalized voice generators; G [Supplementary notification appliance circuit panel; G] [Auxiliary power supply panel; G] [Remote annunciator; G] [Graphic annunciator; G] [Installation-wide mass notification system transceiver; G] [Solid state telegraph transmitter ; G] [Fire alarm radio transceiver; G] [Digital alarm communicator transmitter (DACT); G] Batteries; G Battery chargers; G Wiring and cable; G Surge protection; G Ceiling bridges for ceiling mounted appliances; G

Back boxes and conduit; G Terminal cabinets/assemblies; G Notification appliances; G [LED Text Displays; G] [LED text display control panels; G] [Scrolling LED Text Displays; G] [Scrolling LED text display control panels; G] Addressable monitor module; G Addressable control/relay module; G Isolation module; G Manual stations; G Smoke detectors; G [Duct mounted smoke detectors; G] [Heat detector; G] [Carbon monoxide detector; G] [Smoke detector sounder bases; G] [Waterflow switches; G] [Tamper switches; G] [High/low air supervisory switches ; G] [Room low temperature supervisory switch; G] [Electromagnetic door holders; G] [Environmental enclosures or guards; G]

Manufacturer's installation and maintenance manuals; G Provide one copy of the most recent Manufacturer's installation and maintenance manuals for each piece of equipment being installed. This data is necessary for use by NAVFAC [MIDLANT] [ ] Fire Protection Engineering when reviewing the contractor's submittal. Manual may be submitted in *.pdf format and submitted directly to NAVFAC [MIDLANT] [ ] Fire Protection Engineering.

SECTION 28 31 76.00 22 Page 9

SD-05 Design Data

System Operation; G

Provide a complete description of the system operation, in matrix format, on the shop drawings.

Battery power; G

a. Verify battery capacity exceeds supervisory and alarm power requirements.

1). Substantiate the battery calculations for alarm, alert, and supervisory power requirements. Ampere-hour requirements for each system component and each panel component, and the battery-recharging period, shall be included.

2). Provide complete battery calculations for both the alarm, alert, and supervisory power requirements. Ampere-hour requirements for each system component shall be submitted with the calculations.

b. For battery calculations, use the following assumptions: Assume a starting voltage of 24 VDC for starting the calculations to size the batteries. Calculate the required Ampere-hour for the specified standby time, and then calculate the required Ampere-hour for the specified alarm time. Calculate the nominal battery voltage after operation on batteries for the specified time period.

Voltage Drop Calculations; G

Provide voltage drop calculations to indicate sufficient voltage is available for proper operation of the system and all components, at the minimum rated voltage of the system operating on batteries.

Utilize the lump sum method for voltage drop calculations. Assume the entire appliance load is at the end of the circuit (lump sum). Utilize 16 VDC as the operating voltage of the appliances and 21.6 VDC as the voltage at the circuit terminals.

Spare Capacity Calculations; G

Provide calculations verifying the contract stipulated [25][50] spare capacity is provided for each notification appliance circuit, FACU/ACU, SNAC panel, and auxiliary power supply panel.

Also provide a calculation indicating a [25][50] percent spare capacity is maintained for each SLC.

SD-06 Test Reports

Field Quality Control Testing Procedures; G Smoke detector testing procedures; G [Carbon monoxide detector testing procedures; G] [Heat detector testing procedures; G] [Room low temperature supervisory switch testing procedures; G]

SECTION 28 31 76.00 22 Page 10

SD-07 Certificates

Installer

SD-09 Manufacturer's Field Reports

Combination emergency communications system panel (CECP)

Provide reports on preliminary tests, include printer information. Include the NFPA 72 Record of Completion and NFPA 72 Inspection and Testing Form, with the appropriate test reports.

printer generated data shall consist of a unique identifier for each device, combination emergency communications system panel, initiating device and notification appliance, with an indication of test results, and signature of the factory-trained technician of the control panel manufacturer and equipment installer.

SD-10 Operation and Maintenance Data

Operation and Maintenance (O&M) Instructions; G

Provide [one][four] copies of the Operation and Maintenance Instructions, indexed and in booklet form. The Operation and Maintenance Instructions shall be a single volume or in separate volumes, and may be submitted as a Technical Data Package.

Manuals shall be approved prior to training.

Original and backup copies of all software delivered for this contract on each type of CD/DVD media utilized.

[[Provide Operation and Maintenance (O&M) Instructions in electonic format.] [If permitted by the Contracting Officer, provide Operation and Maintenance (O&M) Instructions in electonic format.] File format of electronic submittal materials shall be portable document format. No other electronic formats shall be accepted.]

Instruction of Government Employees

The installers training history for the employees involved with this contract.

1.6 QUALITY ASSURANCE

Equipment and devices shall be compatible and operable with existing installation-wide fire alarm reporting and mass notification systems and shall not impair reliability or operational functions of existing system.

The installation-wide fire reporting system utilizes [100mA Gamewell loop][Monaco radio transmitters][King-Ffisher (KFCi) radio transmitter][Digitize radio transmitter][AES Intellinet radio transmitter][DACT][dedicated [copper][fiber] phone pair]. The installation-wide mass notification system utilizes [Cooper/Madahcom][Federal Signal][King-Fisher (KFCi)][Whelen][ATI][HyperLink][Genesis][Altelicon][StreamLine]tranceivers.

a. In NFPA publications referred to herein, consider advisory provisions to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; interpret reference to "authority having jurisdiction" and/or AHJ to mean the Naval

SECTION 28 31 76.00 22 Page 11

Facilities Engineering Command, [MIDLANT] [ ], Fire Protection Engineer.

b. The recommended practices stated in the manufacturer's literature or documentation shall be considered as mandatory requirements.

c. Devices and equipment for fire alarm service shall be listed by UL Fire Prot Dir or approved by FM APP GUIDE.

1.6.1 Qualifications

1.6.1.1 Qualifications for Fire Alarm System Subcontractor

The Prime Contractor shall be responsible for obtaining the services of a qualified fire alarm system subcontractor for the design and installation of the combination emergency communications system. The firm designated by the Prime Contractor as their qualified fire alarm system subcontractor:

a. Shall have been in existence a minimum of four years prior to contract award.

b. Shall provide proof of previous experience installing a system of equal or greater complexity, utilizing the same equipment to be provided under this contract.

c. Shall provide proof of adequate qualified staffing to meet all of the following requirements:

1.6.1.1.1 On-Staff Fire Alarm System Designer(s)

A qualified fire alarm contractor shall have at least one on staff NICET Level IV SET, (Senior Engineering Technician) fire alarm technician. This technician shall also have proof of factory certified training for the design of the systems utilizing the equipment being installed. The NICET Level IV technician(s) shall be the lead technician responsible for the contractor's design of the combination emergency communications system, including, but not limited to, the selection and design of necessary equipment, battery, power and circuit calculations, provision of the required manufacturers data and the creation and completion of the shop drawings. The submittal materials (drawings, calculations & manufacturer's data) shall bear the stamp and signature of the NICET Level IV technician. RFI's pertaining to the combination emergency communications system shall be reviewed and signed by the NICET Level IV technician prior to submission to the Contracting Officer.

A NICET Level III, ET (Engineering Technician) fire alarm technician may be utilized to create the shop drawings, calculations and submittal material provided the Level III technician is directly supervised by the NICET Level IV technician. The NICET Level IV technician remains responsible for the system design and submittal materials. Both technicians' signatures and stamps shall be included on the submittal material.

1.6.1.1.2 Supervising Fire Alarm Technician

A NICET Level II, AET (Associate Engineering Technician) fire alarm technician with a minimum of 8 years experience shall supervise the installation of the combination emergency communications system. The fire alarm technicians supervising the installation of equipment shall also be

SECTION 28 31 76.00 22 Page 12 factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the approved shop drawings.

Supervising technician shall be a direct employee of the firm designated by the Prime Contractor as their qualified fire alarm system subcontractor.

1.6.1.1.3 Installing Technicians

The installing Contractor shall provide fire alarm technicians with a minimum of four years of experience utilized to assist in the installation and termination devices, appliances, cabinets and panels. The fire alarm technicians installing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the approved shop drawings. Technicians with minimum NICET Level I or II Certification are preferred. Installing technicians shall be direct employees of the firm designated by the Prime Contractor as their qualified fire alarm system subcontractor.

1.6.1.1.4 Testing Personnel

The installing Contractor shall provide Fire Alarm Technicians with a minimum of eight years of experience utilized to test and certify the installation of the combination emergency communications system devices, appliances, cabinets and panels. The fire alarm technicians testing the equipment shall be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the approved shop drawings. Testing personnel shall be direct employees of the firm designated by the Prime Contractor as their qualified fire alarm system subcontractor.

1.6.2 Regulatory Requirements

1.6.2.1 Requirements for Fire Protection Service

Equipment and material shall be Listed by UL and listed in UL Fire Prot Dir, UL Electrical Constructn or Approved by FM and listed in FM APP GUIDE.

Where the terms "listed" or "approved" appear in this specification, they shall mean listed in UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described shall not be interpreted as waiving this requirement. All listings or approval by testing laboratories shall be from an existing ANSI or UL published standard.

1.7 DELIVERY, STORAGE, AND HANDLING

Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

1.8 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS

The combination emergency communications system Operation and Maintenance Instructions shall include:

a. "Manufacturer Data Package [5][_____]" as specified in Section 01 78 23 OPERATION AND MAINTENANCE DATA. Provide an electronic copy of the OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS

b. Manufacturer's installation and maintenance manuals outlining step-by-step procedures required for system startup, operation, and shutdown. The manual shall include the manufacturer's name, model

SECTION 28 31 76.00 22 Page 13 number, service manual, parts list, and complete description of equipment and their basic operating features.

c. Maintenance manual listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. The manuals shall include conduit layout, equipment layout and simplified wiring, and control diagrams of the system as installed.

d. The manuals shall include complete procedures for system revision and expansion, detailing both equipment and software requirements.

e. Software delivered for this project shall be provided, on CD or DVD discs.

f. Printouts of configuration settings for all devices.

g. Routine maintenance checklist. The routine maintenance checklist shall be arranged in columnar format. The first column shall list all installed devices, the second column shall state the maintenance activity or state no maintenance required, the third column shall state the frequency of the maintenance activity, and the fourth column for additional comments or reference.

1.9 WARRANTY PERIOD REPAIR SERVICE, MAINTENANCE AND ADJUSTMENTS

During guarantee period, the service technician shall be on-site within 24 hours after notification. All repairs shall be completed within 24 hours of arrival on-site. During the guarantee period, the installing fire alarm contractor is responsible for conducting all required testing and maintenance in accordance with the requirements and recommended practices of NFPA 72 and the system manufacturer. Installing fire alarm contractor is NOT responsible for any damage resulting from abuse, misuse or neglect of equipment by the end user

1.10 EXTRA MATERIALS

1.10.1 Repair Service/Replacement Parts

Repair services and replacement parts for the system shall be available for a period of ten years after the date of final acceptance of this work by the Contracting Officer.

1.10.2 Interchangeable Parts

Spare parts furnished shall be directly interchangeable with the corresponding components of the installed system. Spare parts shall be suitably packaged and identified by nameplate, tagging, or stamping.

Spare parts shall be delivered to the Contracting Officer at the time of the final acceptance testing.

1.10.3 Spare Parts

Furnish the following spare parts and accessories:

a. [Four][_____] fuses for each fused circuit

b. [Two][_____] smoke detectors

[c. [Two][_____] thermal detectors]

SECTION 28 31 76.00 22 Page 14

[d. [Two][_____] carbon monoxide detectors]

e. [Two][_____] addressable control modules

f. [Two][_____] addressable interface modules

1.10.4 Special Tools

Software, connecting cables and proprietary equipment, necessary for the maintenance, testing, and reprogramming of the equipment shall be furnished to the Contracting Officer.

PART 2 PRODUCTS

2.1 MATERIALS AND EQUIPMENT

2.1.1 Manufacturer

Components shall be of current design and shall be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a combination emergency communications system, complete, conforming to NFPA 72, except as otherwise or additionally specified herein.

2.1.2 Standard Products

Provide materials, equipment, and devices that are UL Listed or FM Approved for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials. Material and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least [two][_____] years prior to bid opening.

2.1.3 Nameplates

Major components of equipment shall have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:

a. CECP (includes component panels)

b. Automatic transmitters (for both the installation-wide fire alarm reporting system and installation-wide mass notification systems)

Furnish nameplates to obtain approval by the Contracting Officer before installation. Obtain approval by the Contracting Officer for installation locations. Nameplates shall be etched metal or plastic, permanently attached by screws to panels or adjacent walls.

2.2 GENERAL PRODUCT REQUIREMENT

All combination emergency communications system equipment shall be listed for use under the applicable reference standards.

SECTION 28 31 76.00 22 Page 15

2.3 FIRE ALARM CONTROL UNIT(FACU) AND AUTONOMOUS CONTROL UNIT(ACU)

Provide a complete control panel fully enclosed in a lockable steel enclosure as specified herein. At the designer's discretion, the FACU and ACU may be housed in separate panels that contain independent power supplies and batteries or the ACU may be housed in the same panel with the FACU as a combination emergency communications system panel (CECP).

Operations required for testing or for normal care and maintenance of the systems shall be performed from the front of the FACU enclosure. If more than a single unit is required at a location to form a complete control panel, the unit enclosures shall match exactly.

a. Each control unit shall provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit shall be suitable for operation on a 120 Volt, 60 Hertz, normal building power supply. Provide each panel with supervisory functions for power failure, internal component placement, and operation.

b. Visual indication of alarm, supervisory, or trouble initiation on the fire alarm control unit shall be by liquid crystal display or similar means with a minimum of 80 characters, that at least 32 are field changeable. The ACU shall have the capability of temporarily deactivating the fire alarm messages while delivering voice messages.

Provide conductor integrity monitoring for strobe, display, temporary deactivation of fire alarm audible notification appliances and speaker wiring.

c. Provide secure operator console with a microphone for delivering live voice messages. Provide adequate discrete outputs to temporarily deactivate fire alarm audible notification, and initiate/synchronize strobes. Provide a complete set of self-diagnostics for controller and appliance network. Provide local diagnostic information display and local diagnostic information and system event log file.

2.3.1 Cabinet

Install control panel components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of panels as well as field wiring. The enclosure shall be identified by an engraved laminated phenolic resin nameplate. Lettering on the nameplate shall say "Fire Alarm and Mass Notification Control Panel" and shall not be less than one inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches.

The cabinet shall be provided in a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and surface mounting provisions.

2.3.2 Control Modules

Provide power and control modules to perform all functions of the FACU.

Provide audible signals to indicate any alarm, supervisory, or trouble condition. The alarm signals shall be different from the trouble signal.

Connect circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for identification. Locate diodes and relays, if any, on screw terminals in the FACU. Circuits operating at 24 VDC shall not operate at less than 21.6 Volts. Circuits operating at any

SECTION 28 31 76.00 22 Page 16 other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage.

2.3.3 Silencing Switches

a. Alarm Silencing Switch: Provide an alarm silencing switch at the FACU that shall silence the audible signal but not affect the visual alarm indicator. This switch shall be overridden upon activation of a subsequent alarm.

b. Supervisory/Trouble Silencing Switch: Provide supervisory and trouble silencing switch that shall silence the audible trouble and supervisory signal, but not affect the visual indicator. This switch shall be overridden upon activation of a subsequent alarm, supervision, or trouble condition. Audible trouble indication must resound automatically every 24 hours after the silencing feature has been operated.

2.3.4 Non-Interfering

Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Circuits shall be manually reset by switch from the FACU after the initiating device or devices have been restored to normal.

2.3.5 Voice Notification System

The Voice Notification System shall comply with the requirements of NFPA 72 for Emergency Voice/Alarm Communications System requirements ISO 7240-16, IEC 60268-16, except as specified herein.

Tones and voice messages shall repeat until the control panel is reset or silenced. A live voice message shall override the automatic audible output through use of a microphone input at the control panel.

a. The system shall be a [single][dual] channel voice notification system incorporating user selectability of a minimum 8 distinct sounds for tone signaling, and the incorporation of a voice module for delivery of prerecorded messages.

b. The digitalized voice message shall consist of a non-volatile (EPROM) microprocessor based input to the amplifiers. The microprocessor shall actively interrogate circuitry, field wiring, and digital coding necessary for the immediate and accurate rebroadcasting of the stored voice data into the appropriate amplifier input. Loss of operating power, supervisory power, or any other malfunction that could render the digitalized voice module inoperative shall automatically cause the three tone temporal signal to take over all functions assigned to the failed unit.

c. When using the microphone, live messages shall be broadcast through all speakers. The system shall be capable of operating all speakers at the same time. [The Voice Notification System shall support Public Address (PA) paging for the facility.]

d. The Mass Notification functions shall override the manual or automatic fire alarm notification [or Public Address (PA)] functions.

The system shall have the capability of utilizing a remote microphone station with redundant controls of the notification system control

SECTION 28 31 76.00 22 Page 17 panel. A hand held microphone shall be provided and, upon activation, shall take priority over any tone signal, recorded message or PA microphone operation in progress, while maintaining the strobe Notification Appliance Circuits activation.

Where the Combined Emergency Communications System consists of separate autonomous control and fire alarm control units, a Class X pathway shall be provided as the means for activating the strobe appliances.

The activation of the strobe circuits shall follow the operation of the speaker notification appliance circuits.

Audio output shall be selectable for line level (600 ohms), 25 or 70.7 volt output.

The audio amplifier outputs shall be not greater than 100 watts RMS output.

The strobe notification appliance circuits shall provide at least 2 amps of 24 VDC power to operate strobes and have the ability to synchronize all strobes.

All outputs and operational modules shall be fully supervised with on-board diagnostics and trouble reporting circuits.

Form "C" contacts shall be provided for system alarm and trouble conditions.

Circuits shall be provided for operation of auxiliary appliances during trouble conditions.

During a Mass Notification event the panel shall not generate nor cause any trouble alarms to be generated with the fire alarm portion of the combination emergency communications system.

Mass Notification functions shall take precedence over all other function performed by the Voice Notification System.

Messages shall be recorded professionally utilizing standard industry methods and be recorded utilizing a professional female voice. Message and tone volumes shall both be at the same decibel level. Messages recorded from the system microphone shall not be accepted. Messages shall be the following:

1) FIRE ALARM MESSAGE: Three Tone Temporal Pattern (0.5 sec on, 0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on, 1.5 second off.) The alarm signal shall be a square wave. The wave shall have a fundamental frequency of 520 Hz ± 10 percent followed by:

"May I have your attention, please. May I have your attention, please. A fire has been reported in the building. Please leave the building by the nearest exit [or exit stair]. [Do not attempt to utilize the elevator[s]]" Provide a [2][_____] second pause.

Repeat the tones and message.

[2) CARBON MONOXIDE ALARM MESSAGE: Four Tone Temporal (0.5 sec on,

0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on,, 1.5 second off.) The alarm signal shall

SECTION 28 31 76.00 22 Page 18 be a square wave. The wave shall have a fundamental frequency of 520 Hz ± 10 percent followed by:

"May I have your attention please. May I have your attention please. [Dangerous concentrations] [High levels] of carbon monoxide have been detected in the building. Please leave the building by the nearest exit [or exit stair]." Provide [2][_____] second pause. Repeat the tones and message.]

[3) HANGAR BAY PRE-DISCHARGE ALARM: [Three Pulse Temporal Pattern (0.5 sec on, 0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on 1.5 second off) The alarm signal shall be a square wave. The wave shall have a fundamental frequency of 520 Hz ± 10 percent followed by:]

"May I have your attention, please. May I have your attention, please. An open flame has been detected in the hangar bay. Foam system discharge is [imminent] [about to occur]. Please leave the building by the nearest exit [or exit stair]. [Do not attempt to utilize the elevator[s]]" Provide a [2][_____] second pause.

Repeat the tones and message.]

[4) COMPUTER ROOM PRE-DISCHARGE ALARM: [Three Pulse Temporal Pattern (0.5 sec on, 0.5 second off, 0.5 second on, 0.5 second off, 0.5 second on 1.5 second off) The alarm signal shall be a square wave. The wave shall have a fundamental frequency of 520 Hz ± 10 percent followed by:]

"May I have your attention, please. May I have your attention, please. A fire has been detected inside Server Room [room number ]. Gaseous suppression system discharge is [imminent] [about to occur]. Please leave the building by the nearest exit [or exit stair]. [Do not attempt to utilize the elevator[s]]" Provide a [2][_____] second pause. Repeat the tones and message.]

[5) BLANK]

[6) BLANK]

[7) BLANK]

[8) BLANK]

a. Auxiliary Input Module shall be designed to be an outboard expansion module to either expand the number of optional remote microphone stations, or allow a telephone interface.

[b. Remote Microphone station (PA) shall incorporate a Push-To-Talk (PTT) microphone, and controls to allow Public Address paging in the facility. The Public Address paging function shall not override any alarm or notification functions. The microphone shall be [desktop][handheld][______] style.]

2.3.6 Memory

Provide each control unit with non-volatile…