This document provides details for a federal solicitation seeking construction services for an emergency department expansion project at the Cleveland VA Medical Center. The solicitation will be issued as an Invitation for Bid for a firm-fixed-price construction contract valued between $10-20 million to design and build a 27,000 square foot two-story addition and renovate approximately 10,000 square feet of an existing emergency department. The project scope includes integrating a psychiatric emergency department and specialty care clinics, upgrading mechanical, electrical and plumbing systems, and constructing exterior site improvements. The solicitation is designated as a total Service-Disabled Veteran-Owned Small Business set-aside and will be issued by the Department of Veterans Affairs on or around February 26, 2021, with a period of performance of approximately 695 calendar days from notice to proceed. Questions regarding the solicitation must be submitted in writing by the specified date.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTIONABBREVIATION SYMBOL
US
SAN
UST
DS
ODS
PD
DCW
DHW
RDHW
TDHW
MA
N
O
MV
F.P.S.C.
H.B.
F.D.
A.F.D.
R.D.
A.D.
PLUMBING SYMBOL LEGEND
US SANITARY SEWER BELOW FLOOR OR GRADE
EUS EXISTING SANITARY SEWER BELOW FLOOR OR GRADE
SAN SANITARY SEWER ABOVE FLOOR
SANITARY VENT
IW INDIRECT WASTE (ABOVE OR BELOW FLOOR)
UST STORM SEWER BELOW FLOOR OR GRADE
DS DOWNSPOUT ABOVE FLOOR (WITHIN BUILDING SPACE)
OSD OVERFLOW DOWNSPOUT ABOVE FLOOR (WITHIN BUILDING SPACE)
PD PUMP DISCHARGE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
RDHW RECIRCULATED DOMESTIC HOT WATER
TDHW TEMPERED DOMESTIC HOT WATER
MA MEDICAL COMPRESSED AIR
NITROGEN
O OXYGEN
MV MEDICAL VACUUM
SHOCK STOP IN HORIZONTAL
GATE VALVE
GAS COCK
GLOBE VALVE
BALL VALVE
BALANCE VALVE (SEE SPECIFICATIONS)
CHECK VALVE (SWING)
PUMP DISCHARGE SILENT LIFT CHECK VALVE
BUTTERFLY VALVE
CONCENTRIC REDUCER/INCREASER
STRAINER WITH BLOWDOWN
UNION
FLANGED UNION
EXPANSION JOINT
PIPE ANCHOR
PIPE GUIDE
PIPE SLEEVE (SEE SPECIFICATIONS FOR ADDIT. REQUIREMENTS)
VIBRATION CONNECTION (SEE SPECIFICATIONS)
BFP DOUBLE CHECK BACKFLOW PREVENTER
RPBP REDUCED PRESSURE BACKFLOW PREVENTER WITH AIR GAP DEVICE AND DRAIN
COMPANION FLANGE
C.O. CLEANOUT
FW/FCO FLUSH WITH FLOOR CLEANOUT
FW/WCO FLUSH WITH WALL CLEANOUT
F.P.S.C. FROSTPROOF SILL COCK / WALL HYDRANT
FAUCET OR HOSE BIBB
F.D. SANITARY FLOOR DRAIN
A.F.D. ACID FLOOR DRAIN
R.D. ROOF DRAIN
A.D. AREA DRAIN (STORM)
D.S. D.S. DOWNSPOUT
R.L. R.L. RAIN LEADER
PRESSURE GAUGE WITH GAUGE COCK (WATER)
PRESSURE GAUGE WITH BALL VALVE (WATER)
P__-__ PLUMBING FIXTURE (SEE SCHEDULE)
PE__-__ PLUMBING EQUIPMENT (SEE SCHEDULE)
E.C. E.C. ELECTRICAL CONTRACTOR
F.P.C. F.P.C. FIRE PROTECTION CONTRACTOR
G.C. G.C. GENERAL CONTRACTOR
H.C. H.C. HVAC CONTRACTOR
P.C. P.C. PLUMBING CONTRACTOR
A.D. A.D. ACCESS DOOR
A.F.F. A.F.F. ABOVE FINISHED FLOOR
F.F.E. F.F.E. FINISHED FLOOR ELEVATION
MFR. MFR. MANUFACTURER
N.O. N.O. NORMALLY OPEN
N.C. N.C. NORMALLY OPEN
TYP. TYP. TYPICAL
INDICATES TIE INTO EXISTING
INDICATES REMOVE TO POINT FOR RECONNECTION
INDICATES REMOVE TO POINT AND CAP
PLUMBING DEMOLITION GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL DEMOLITION DRAWINGS IN ADDITION TO ANY
ADDITIONAL DEMOLITION DRAWING NOTES ON THE INDIVIDUAL DEMOLITION DRAWING.
2. WALLS SHOWN IN DASHED ARE BEING REMOVED. WALLS SHOWN TO BE REMOVED MAY
CONTAIN PLUMBING PIPING TO FIXTURES THAT ARE TO REMAIN. THIS PIPING IS TO BE
PROTECTED DURING WORK.
3. DARK, DASHED LINES INDICATE PIPING AND EQUIPMENT TO BE REMOVED.
4. UNLESS NOTED OTHERWISE, ALL PIPING TO BE DEMOLISHED SHALL BE REMOVED BACK TO THE
MAIN AND CAPPED.
5. CAP ALL REMAINING PIPING WITH SIMILAR MATERIALS. PIPE ENDS INDICATED TO BE CAPPED
ARE NOT TO BE CRIMPED. ALL DCW, DHW, & RDHW PIPING SHOWN TO BE REMOVED AND NOT
INDICATED TO BE EXTENDED WITH NEW WORK, THE CAPPED ENDS ARE TO BE INSULATED WITH
MATERIALS SPECIFIED FOR NEW WORK.
6. NEW INSULATION IS TO BE INSTALLED ON ANY EXPOSED SECTIONS OF PIPING THAT WAS
PREVIOUSLY INSULATED PRIOR TO THE START OF DEMOLITION WORK. THIS INCLUDES CAPPED
ENDS OF PIPING.
7. PROVIDE HANGERS TO SUPPORT ANY REMAINING PIPING OR EQUIPMENT.
8. REMOVE ALL HANGERS AND SUPPORTS FOR PIPING AND EQUIPMENT BEING DEMOLISHED.
9. OWNER SHALL HAVE SALVAGE RIGHTS TO ANY EQUIPMENT OR MATERIALS BEING REMOVED.
ANY EQUIPMENT OR MATERIALS REFUSED BY THE OWNER SHALL BE REMOVED FROM THE SITE.
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
10. SEE SPECIFICATIONS FOR ALL CUTTING AND PATCHING REQUIREMENTS REQUIRED UNDER
DEMOLITION AND ALSO INDICATED ON DRAWINGS.
11. THIS CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF
CONSTRUCTION.
12. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION AND
ELEVATION OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO COMMENCING WORK. THE
PLUMBING CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES WHICH OCCURS BY HIS FAILURE
TO LOCATE OR PRESERVE THE UNDERGROUND CONDITIONS.
13. IF DURING CONSTRUCTION OPERATIONS, THE PLUMBING CONTRACTOR ENCOUNTERS
UTILITIES OTHER THAN THOSE LOCATIONS SHOWN IN THE PLANS, HE SHALL IMMEDIATELY
NOTIFY THE ENGINEER AND TAKE THE NECESSARY STEPS TO PROTECT THE FACILITY AND
ASSURE THE CONTINUANCE OF SERVICE.
14. AN ATTEMPT HAS BEEN MADE TO SHOW ALL ITEMS TO BE REMOVED AND/OR RELOCATED.
FIELD VERIFY EXISTING CONDITIONS INCLUDING LOCATIONS AND INVERTS AND REMOVE OR
RELOCATE ALL PLUMBING PIPING THAT INTERFERES WITH NEW CONSTRUCTION PRIOR TO START
OF WORK.
15. ANY DISRUPTION OF ANY EXISTING SERVICE THAT SERVES THE BUILDING SHALL BE
COORDINATED WITH THE OWNER PRIOR TO DISRUPTION. WORK ASSOCIATED WITH THIS
SERVICE SHALL BE PERFORMED AT A TIME REQUESTED BY OWNER WHICH COULD BE
PERFORMED OFF STANDARD WORKING HOURS AT NO ADDITIONAL COST TO OWNER FOR TIME OF
WORK. COST TO BE INCLUDED UNDER BASE BID FOR PROJECT.
16. ALL CONTRACTORS SHALL COORDINATE THEIR WORK WITH OTHER CONTRACTORS AND WITH
THE OWNER. THIS INCLUDES ALL SHUTDOWNS AND DRAINING REQUIRED. THIS CONTRACTOR TO
COORDINATE PLUMBING SYSTEM SHUTDOWNS WITH THE OWNER AT LEAST 24 HOURS PRIOR TO
THE BEGINNING OF THE SHUTDOWN.
17. THE PLUMBING CONTRACTOR IS TO MINIMIZE THE AMOUNT OF CEILING, CHASE, AND WALL
REMOVAL FOR THE REMOVAL AND REPLACEMENT OF SANITARY, VENT, DCW, AND DHW LINES
SERVING THE PLUMBING FIXTURES. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR
PATCHING THE CEILING, CHASE, AND WALLS TO MATCH EXISTING CONDITIONS. REMOVAL OF
SANITARY AND WATER PIPING IS TO BE COORDINATED WITH THE NEW WORK PLANS AND THE
OWNER TO MINIMIZE DISTURBANCE.
18. WHERE PLUMBING PIPING HAS BEEN REMOVED AND/OR CAPPED, THE PLUMBING
CONTRACTOR IS TO PATCH FLOOR/WALL TO MATCH EXISTING CONDITIONS.
19. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING OF EXISTING
WALLS, CEILINGS, AND FLOORS THAT REQUIRES PLUMBING WORK AND IS OUTSIDE THIS
PROJECT. PATCHING IS TO MATCH EXISTING CONSTRUCTION AND FINISH.
20. REMOVAL AND REINSTALLATION OF CEILINGS NOT INDICATED TO BE REMOVED AND
REINSTALLED ON THE ARCHITECTURAL DRAWINGS TO BE PERFORMED BY THIS CONTRACTOR
FOR DEMOLITION OR INSTALLATION OF NEW PIPING OR EQUIPMENT OUTSIDE THE PROJECT
AREA. REMOVAL OF PLUMBING PIPING IN CEILING SPACE IS TO BE COORDINATED WITH THE NEW
WORK PLAN TO MINIMIZE DISTURBANCE TO ADJACENT SPACES.
21. P.C. TO REROUTE/RECONNECT ALL ACTIVE VENT PIPE REMOVED DURING CONSTRUCTION DUE TO DEMOLITION OF INTERIOR WALLS. VENT PIPING SHALL BE ROUTED IN NEW FURRED COLUMN
SPACE OR NEW WALL STUD SPACE AS REQUIRED.
22. THE PLUMBING CONTRACTOR SHALL REMOVE PLUMBING PIPING IN WALLS TO BE REMOVED
AND RE-PIPE ALL ITEMS OUTSIDE THE DEMOLITION LIMITS AND RESTORE TO ORIGINAL WORKING
CONDITION.
23. WHERE EXISTING PIPING IS MAINTAINED AT WALLS SHOWN TO BE DEMOLISHED,
CONTRACTOR TO REMOVE ABANDONED SLEEVES ASSEMBLIES AND ANY ASSOCIATED
FIRESTOPPING MATERIALS ON PIPING. PIPING INSULATION WITHIN AND AROUND THE SLEEVE
ASSEMBLY IS TO BE REMOVED AND REPLACED WITH SIMILAR INSULATION MATERIALS, MATCHING
EXISTING.
PLUMBING NEW WORK GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL PLUMBING DRAWINGS IN ADDITION TO ANY
ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.
2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.
4. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION AND
ELEVATION OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO COMMENCING WORK. THE
PLUMBING CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES WHICH OCCURS BY HIS FAILURE
TO LOCATE OR PRESERVE THE UNDERGROUND CONDITIONS.
5. IF DURING CONSTRUCTION OPERATIONS, THE PLUMBING CONTRACTOR ENCOUNTERS
UTILITIES OTHER THAN THOSE LOCATIONS SHOWN IN THE PLANS, HE SHALL IMMEDIATELY
NOTIFY THE ENGINEER AND TAKE THE NECESSARY STEPS TO PROTECT THE FACILITY AND
ASSURE THE CONTINUANCE OF SERVICE.
6. COORDINATE WITH GENERAL TRADES WORK, HVAC WORK, FIRE PROTECTION WORK,
ELECTRICAL WORK AND OTHER WORK.
7. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED
STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL
REQUIREMENTS.
8. THE PLUMBING DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW
EXACT LOCATION OF EQUIPMENT AND PIPING UNLESS DIMENSIONS ARE GIVEN OR OTHERWISE
IMPLIED FOR CLEARANCES, ETC. PIPING AND PLUMBING EQUIPMENT ARE TO BE INSTALLED
ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN MIND ACTUAL
BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK. CONTRACTORS
IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND OTHER RELATED
WORK NECESSARY TO PROVIDE MINOR OFFSETS IN PLUMBING WORK AS REQUIRED TO AVOID
CONFLICT WITH OTHER WORK ON THIS PROJECT OR AS REQUIRED IN ORDER TO OBTAIN
MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.
9. THE PLUMBING CONTRACTOR IS TO COORDINATE ALL PIPING WITH OTHER TRADES PRIOR TO
ROUTING PIPING AND SHALL MAKE OFFSETS AND ADJUST PIPE ROUTING AS REQUIRED TO
HANDLE CONFLICTS IN FIELD. THE PLUMBING CONTRACTOR SHALL ALSO BE REQUIRED TO
OFFSET VERTICAL SANITARY AND VENT LINES AROUND STRUCTURAL MEMBERS AS REQUIRED
AND SHALL INCLUDE IN THEIR BASE BID THE ASSOCIATED COST FOR ADDITIONAL FITTINGS,
PIPING, AND MAN HOURS TO ACCOMMODATE CONFLICTS.
10. SEE ARCHITECTURAL PLANS FOR EXACT LOCATION AND ELEVATION OF PLUMBING FIXTURES.
11.ALL COLD WATER AND HOT WATER PIPING TO INDIVIDUAL SINKS AND INDIVIDUAL LAVATORIES
TO BE 1/2", UNLESS OTHERWISE INDICATED.
12. ALL COLD WATER AND HOT WATER PIPING SERVING 3 OR LESS SINKS OR LAVS ARE TO BE 3/4"
UNLESS NOTED OTHERWISE.
13. FINAL COLD WATER PIPING CONNECTIONS TO WATER CLOSETS TO BE 1-1/4".
14. UNLESS OTHERWISE NOTED SEE PLUMBING FIXTURE SCHEDULE FOR FIXTURE DRAIN, VENT, DCW AND DHW PIPE SIZES.
15. P.C. TO FURNISH WALL FLANGES AROUND ALL PIPING EXPOSED BELOW CEILING AND
CASEWORK.
16. P.C. TO COORDINATE ALL SHOWER UNITS WITH G.C. TO ENSURE PROPER INSTALLATION,
ROUGH-IN, AND CLEARANCE REQUIREMENTS PRIOR TO ORDERING AND INSTALLATION.
COORDINATE ANY CHANGE IN SIZE OR CONFIGURATION WITH ARCHITECT.
17. P.C. TO COORDINATE ALL COUNTERTOP SINKS WITH CASEWORK TO ENSURE PROPER
INSTALLATION AND CLEARANCE REQUIREMENTS PRIOR TO ORDERING AND INSTALLATION.
COORDINATE ANY CHANGE IN SIZE OR CONFIGURATION WITH PROJECT ENGINEER AND
ARCHITECT.
18. SEE PLUMBING ISOMETRICS FOR SANITARY PIPE SIZES NOT INDICATED ON FLOOR PLANS.
19. UNLESS OTHERWISE INDICATED, ALL PIPING TO RUN GENERALLY BELOW DUCTWORK FOR
ACCESS TO VALVING. DO NOT OBSTRUCT EQUIPMENT OR ACCESS DOORS.
20. SEE ARCHITECTURAL DRAWINGS FOR FINAL PLACEMENT AND ELEVATION OF MEDICAL GAS
OUTLETS.
21. WITH REGARDS TO MEDICAL GAS MAINTENANCE SERVICE VALVES, PROVIDE A PLASTIC
COATED CABLE AND KEY LOCK ASSEMBLY TO LOCK VALVES OPEN. THE HANDLE OF EACH VALVE
SHALL BE DRILLED TO PERMIT PASSING THE CABLE THRU THE VALVE HANDLE. ALL LOCKS SHALL
BE KEYED THE SAME. TURN KEYS OVER TO OWNER. EACH VALVE SHALL BE LABELED IN
REGARDS TO AREA SERVED AND MEDICAL GAS WITHIN PIPE.
22. THE PLUMBING CONTRACTOR IS TO INSTALL HOUSEKEEPING PADS FOR ALL PLUMBING
EQUIPMENT UNITS.
23. SEE PROJECT SPECIFICATIONS FOR CUTTING AND PATCHING RESPONSIBILITIES.
24. FINAL FLOOR DRAIN ELEVATIONS ARE TO BE SET BY THE PLUMBING CONTRACTOR.
COORDINATE EXACT POSITIONING OF FLOOR DRAINS WITH HVAC CONTRACTOR TO SERVE HVAC
EQUIPMENT AS INTENDED, AND TO AVOID TRIPPING HAZARDS WITH ABOVE FLOOR DRAIN PIPING.
25. PLUMBING FIXTURE NUMBERS ARE SHOWN ON WASTE PLANS AND REFERS TO PLUMBING
FIXTURE SCHEDULE.
26. ACCESS PANELS ARE TO BE FURNISHED AND INSTALLED BY THE PLUMBING CONTRACTOR.
THE PLUMBING CONTRACTOR IS TO COORDINATE LOCATION AND INSTALLATION OF VALVES,
SHOCK STOPS, AND CLEANOUTS ABOVE ACCESS PANEL WITH G.C. AND ARCHITECTURAL
DRAWINGS TO MINIMZE SIZE OF PANELS.
27. DRAIN VALVES WITH HOSE ADAPTORS ARE TO BE INSTALLED AT THE BASE OF ALL DCW, DHW, AND RDHW RISERS.
28. EQUIPMENT CONNECTION ARRANGEMENTS, FLANGES, UNIONS, VALVING, ETC. ARE NOT
TYPICALLY SHOWN ON PLAN VIEWS. REFER TO DETAILS AND FLOW DIAGRAMS FOR
REQUIREMENTS. INSTALL ALL VALVES AND OTHER ITEMS REQUIRING OR FACILITATING
MAINTENANCE IN ACCESSIBLE LOCATIONS, AND SO AS TO NOT OBSTRUCT MAINTENANCE ON
EQUIPMENT SERVED.
29. SEAL ALL PIPING PENETRATIONS THROUGH NON-RATED FLOORS TO PREVENT PASSAGE OF
SMOKE.
BUILDING DRAIN CLEANOUT DETAIL
N.T.S.
"Y" BRANCH
FINISHED GRADE
ADJUSTABLE HOUSING
6" C.I. ENCASED IN IN CONCRETE
6" THICK ON EACH SIDE OF PIPE
6" C.I.
P.C. TO COORDINATE WITH ROOM FINISH SCHEDULE
AND PLUMBING FIXTURE SCHEDULE, PROVIDE
CARPET MARKERS WHERE APPLICABLE.
COORDINATE LOCATIONS WITH CARPET INSTALLER.
P.C. TO FURNISH COVER LIDS TO MATCH TYPE OF
FLOOR FINISH.
M A
X
IN-LINE CENTRIFUGAL PUMP. SUPPORT
INDEPENDENTLY FROM PIPING. SEE
PLANS AND SCHEDULE FOR
ADDITIONAL INFORMATION.
UNION (TYP.)
BALL VALVE (TYP.)
PRESSURE GAUGE WITH
GAUGE COCK (TYP.)
BALANCE VALVE (TYP.)
TEMPERATURE GAUGE
WITH BALL VALVE (TYP.)
NOTE:
1. ALL PIPING AND PUMPS TO BE SUPPORTED WITH 2"x2"x1/4"
GALVANIZED ANGLE FRAMING MOUNTED TO FLOOR OR WALL.
2. SUPPORT PIPING AND PUMPS INDEPENDENTLY FROM ANGLE
IRON WALL BRACKETS.
RECIRCULATED HOT WATER PUMP DETAIL
N.T.S.
VENT PIPE CURB DETAIL
N.T.S.
STORM COLLAR CLAMP
TO PIPE
SILICONE CAULK
ROOF LINE
ROOF INSULATION
ROOFING, MEMBRANE, RUN
UP UNDER COVER (BY G.C.)
PIPE - SEE PLANS FOR QUANTITY
SIZES, ARRANGEMENT, AND
CONTINUATION
ANCHOR TO EXISTING ROOF
DECK AS REQUIRED
"PATE" TYPE PCA-5
CURB ASSEMBLY
OR APPROVED
EQUAL
GALVANIZED STEEL COVER
SECURE TO CURB
STAINLESS STEEL CLAMP
VENT TERMINATION HEIGHT IN
ACCORDANCE WITH LOCAL
JURISDICTION.
CLEVIS HANGER PIPE SUPPORT
N.T.S.
NOTE:
REFER TO HANGER SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
PIPE ℄
TYPICAL FOR
UN-INSULATED PIPE
TYPICAL FOR
INSULATED PIPE
STRUCTURAL FRAMING
NOTE: SUPPLY ADDITIONAL
SUPPORT STEEL AS
REQUIRED
BEAM CLAMP
HEX NUTS (4 REQUIRED)
THREADED ROD (SEE
SPECIFICATIONS FOR DIAMETER)
ADJUSTABLE CLEVIS HANGER
PIPE WITH INSULATION AND
JACKET (AS APPLICABLE).
SEE SPECIFICATIONS FOR
REQUIREMENTS.
180 DEG. INSULATION PROTECTION
SHIELD, 14 GA., GALVANIZED BY 18"
LONG FOR PIPING 8" AND OVER.
SEE SPECIFICATIONS FOR 6" AND
UNDER.
SUPPORT BLOCK (SEE
SPECIFICATIONS)
TYPICAL ROOF DRAIN DETAIL
N.T.S.
SEE DRAWINGS FOR SIZES
UNDERDECK CLAMP
P.C. TO INSTALL ALL
NECESSARY SUPPORT
BRACING PLATE AROUND
OPENING AS REQUIRED
TO INSTALL ROOF DRAIN.
FLASHING AND COUNTER FLASHING
BY ROOFING CONTRACTOR. P.C. TO
COORDINATE AND SECURE ROOFING
MEMBRANE TO ROOF DRAIN.
ROOF MEMBRANE
INSULATION
CONCRETE DECK
INSULATE ALL VERTICAL AND
HORIZONTAL SECTIONS OF
DOWNSPOUT, SEE
DOWNSPOUT DETAIL
WALL SECTION
FLOOR SECTION
FURNISH AND INSTALL
FIRESTOP MATERIALS IN
ACCORDANCE WITH
APPROPRIATE U.L. SYSTEMS
TO MAINTAIN FIRE RESISTANCE
RATING
PIPE SLEEVE
DAMMING MATERIAL
(PER U.L. TESTED
SYSTEM DESIGN)
FLOOR SLAB; SEE
ARCHITECTURAL DRAWINGS
FOR FLOOR CONSTRUCTION
AND FIRE RATING
PIPE INSULATION
(WHERE SPECIFIED)
PENETRATING COMPONENT
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE WITH
APPROPRIATE U.L. SYSTEMS TO
MAINTAIN FIRE RESISTANCE RATING
PIPE SLEEVE (SLEEVE TO
EXTEND 2" ABOVE FLOOR
IN MECHANICAL EQUIPMENT
ROOMS.)
SEAL JOINT BETWEEN SLEEVE
AND FLOOR SLAB WITH MIN. 1/2"
BEAD FIRESTOP CAULK
SEE ARCHITECTURAL
DRAWINGS FOR WALL
CONSTRUCTION AND FIRE
RATING
PENETRATING COMPONENT
PIPE INSULATION
(WHERE SPECIFIED)
NOTES:
1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN
TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.
2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND
UL CERTIFIED OR FM CERTIFIED PERSONNEL.
7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL
APPLICATIONS.
8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING
APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.
THROUGH FIRE-RATED CONSTRUCTIONS
N.T.S.
FIRESTOPPING DETAIL FOR PENETRATIONS
NOTE:
1. PROVIDE FLUSHING TAPS, DISINFECTION, AND TESTING FOR EACH DOMESTIC WATER SYSTEM: DOMESTIC COLD WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RETURN.
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED TO COMPLETE DISINFECTION AND TESTING PER THE PROCEDURE LISTED BELOW THIS WILL INCLUDE BUT NOT BE LIMITED TOO THE FOLLOWING; BACKFLOW PREVENTER, TEMPORARY PUMPS, CONNECTION/DRAIN HOSES, CHLORINE, BARRELS AND TESTING EQUIPMENT.
SEQUENCE OF OPERATIONS:
1. DOMESTIC WATER PIPE SHALL BE FLUSHED AND DISINFECTED PRIOR TO CONNECTING TO HOSPITAL POTABLE WATER SYSTEMS, AND BEFORE ACCEPTANCE BY THE VA. CONTRACTOR SHALL SCHEDULE TEST WITH VA AND DOCUMENT DISINFECTION WITH A WITNESSED REPORT. A. INSTALL ISOLATION VALVES AND INJECTION TEES ON THE HOT, COLD AND HOT WATER RETURN LINES SO ALL FIXTURES INSTALLED IN THE SCOPE OF THE PROJECT CAN BE DISINFECTED (SHOCK CHLORINATED). INSURE ISOLATION VALVES ARE INSTALLED TO PROHIBIT DISINFECTION CHEMICALS FROM ENTERING BACK
INTO THE MEDICAL CENTER DOMESTIC WATER LINES.
A. REMOVE ALL LAMINAR FLOW DEVICES AND OR SCREENS AND COMPLETELY FLUSH ALL FIXTURES AT FULL VOLUME FOR
10 MINUTES. SOURCE WATER SHALL HAVE A BACKFLOW PROTECTION DEVICE.
B. DISINFECTION SHALL BE ACCOMPLISHED THRU SHOCK CHLORINATION WITH ONE OF FOLLOWING TWO METHODS:
1. FILL PIPING SYSTEM WITH A WATER/CHLORINE MIXTURE LEVEL OF AT LEAST 50 PPM FREE CHLORINE FOR A MINIMUM OF 24 HOURS. ALL FIXTURES SHOULD HAVE 50 PPM AT THE TAP. (STRONG SMELL OF CHLORINE AT THE FAUCET).
2. FILL PIPING SYSTEM WITH A WATER/CHLORINE MIXTURE LEVEL OF AT LEAST 200 PPM FREE CHLORINE FOR A MINIMUM OF 3 HOURS AND A MAXIMUM OF 4 HOURS. ALL FIXTURES SHOULD HAVE 200 PPM AT THE TAP. (STRONG SMELL OF
CHLORINE AT THE FAUCET).
D. AFTER DISINFECTION ALL FIXTURES MUST BE FLUSHED AND TESTED TO INSURE SAFE POTABLE WATER LEVELS ARE
AVAILABLE. NO MORE THAN 3 PPM FREE CHLORINE.
E. TWO TEST SAMPLES SHALL BE TAKEN 24 HOURS APART FROM EACH OF THE FOLLOWING LOCATIONS; BEGINNING OF MAIN, END OF MAIN, AND EACH BRANCH. WATER SHALL BE TESTED FOR FREE CHLORINE (LESS THAN 3 PPM) AND COLIFORM
ORGANISMS (NONE PRESENT).
F. SUBMIT REPORT WHICH DOCUMENTS ABOVE TEST AND PROCEDURE. RESULT SHALL BE WITNESSED AND SIGNED OFF BY
VA REPRESENTATIVE.
CONNECTION POINT TO EXISTING
DOMESTIC COLD WATER SYSTEM WITHIN 2 PIPE
DIAMETERS MAIN BRANCH TO NEW
PLUMBING FIXTURES
EXISTING DOMESTIC
WATER SYSTEM
ISOLATION VALVE
WITHIN 2 PIPE
DIAMETERS
3/4" BALL VALVE WITH MALE
HOSE THREADS AND CAP
DOMESTIC WATER DISINFECTING/FLUSHING PROCEDURE
N.T.S.
3" SUMP VENT, SEE FLOOR
PLAN FOR CONTINUATION
WIRING BY E.C.
CONTROL PANEL FURNISHED
AND INSTALLED BY P.C.
COORDINATE WIRING TO
BAS WITH T.C.C. SEE
SPECIFICATIONS.
HIGH LEVEL ALARM
INDICATOR
CONTROL WIRING ACCESS
CONDUIT
SUMP PUMP ACCESS
AND REMOVAL COVER
MOUNT CONTROL PANEL
ON NEAREST WALL
PLAN VIEW
ELEVATION
4" THICK CONCRETE PAD
36" x 60" DEEP
POLYETHYLENE
BASIN
FLOOR
BASIN LID
3" SUMP VENT
CLEANOUT
BALL VALVE
PUMP DISCHARGE
CHECK VALVE
UNION
PUMP ACCESS COVER
PUMP OFF
PUMP #1 ON
PUMP #2 ON
HIGH LEVEL ALARM
UNION
PUMP DISCHARGE
PUMP PULL ROD/CABLE
ASSEMBLY
DUPLEX SUMP PUMP DETAIL
N.T.S.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
6:
P M
P-001
PLUMBING GENERAL NOTES, SCHEDULES,
DETAILS, AND SYMBOL LEGEND
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
NOTES:
PLUMBING FIXTURE CONNECTION SCHEDULE
MARK NO. FIXTURE DRAINAGE WATER
REMARKSW.P. V.P. CW HW
FD-D FLOOR DRAIN
FD-E FLOOR DRAIN
FD-H AREA DRAIN
P-103 WATER CLOSET
WALL HUNG
4" 2" 1-1/2" - P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-418 LAVATORY
WALL HUNG
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-420 LAVATORY
COUNTERTOP
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-422 LAVATORY
COUNTERTOP
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-502 MOP SINK 3" 1-1/2" 1/2" 1/2"
P-505 CLINIC SERVICE SINK 4" 2" 1/2" 1/2"
P-510 STAINLESS STEEL
WALL HUNG SINK
1-1/2" 1-1/2" 1/2" 1/2" OPERATED WITH FOOT PEDAL
P-529 STAINLESS STEEL
UNDERMOUNT SINK
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-531 STAINLESS STEEL
DROP-IN SINK
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-532 SINK INTEGRAL TO
COUNTERTOP
1-1/2" 1-1/2" 1/2" 1/2" P.C. TO PROVIDE ALL OF THE REQUIRED TRANSFORMERS FOR
INSTALLATION AND WIRING BY E.C.
P-608 ELECTRIC WATER
COOLER WITH BOTTLE
FILLER
1-1/2" 1-1/2" 1/2" -
P-701 SHOWER 2" 1-1/2" 1/2" 1/2" G.C. TO INSTALL TILED SHOWER WALLS, FLOORS, AND CEILING.
P-708 WALL MOUNTED
EYEWASH STATION
1-1/2" 1-1/2" 1/2" 1/2" EYEWASH WITH STAINLESS STEEL BOWL FOR WALL MOUNTING.
P-801 FROST PROOF WALL
HYDRANT
- - 3/4" -
P-804 HOSE BIBB - - 3/4" -
P-910 WATER CLOSET
LIGATURE RESISTANT
4" 2" 1-1/2" -
P-936 LAVATORY INTEGRAL TO
COUNTER
WITH LIGATURE
RESISTANT FAUCET
1-1/2" 1-1/2" 1/2" 1/2"
NOTES:
MEDICAL GAS EQUIPMENT SCHEDULE
NO. DESCRIPTION MAKE MODEL REMARKS
ME-1 ZONE VALVE BOX BEACON/MEDAES
(OR APPROVED EQUAL)
- ZONE VALVE BOX WITH FULL PORT VALVES, COPPER TUBE EXTENSIONS, STACKABLE DESIGN FOR (4)
VALVES (MV, O, CO2, AND MA, SEE PLANS FOR SIZES), WITH GAUGES, REMOVABLE COVER PANEL WITH PULL RING, SERVICE WINDOW DISPLAY AND GAUGE DISPLAY. 18 GAUGE STEEL BOX CONSTRUCTION WITH FACTORY FABRICATED FRAMES. VALVES TO BE INDEXED FOR GAS SERVICE AND BE UL AND
N.F.P.A. 99 COMPLIANT.
ME-2 AREA ALARM PANEL BEACON/MEDAES
(OR APPROVED EQUAL)
TOTAL ALERT
INFINITY
AREA ALARM PANEL WITH (4) MEDICAL GAS MODULES, LED DISPLAY WITH PRESSURE STATUS
INDICATORS, TEST BUTTON, NORMAL/ABNORMAL INDICATING LIGHTS, 120/1/60 VOLTAGE
REQUIREMENTS. AUDIO ALARM WITH ALARM SILENCE BUTTON.
ME-3 MEDICAL GAS WALL
OUTLETS
BEACON/MEDAES
(OR APPROVED EQUAL)
SERIES B PIN INDEX
KEY STYLE
MODULAR QUICK-CONNECT OUTLET STATION (CONFIRM OUTLET TYPE WITH OWNER PRIOR TO
PURCHASE), SAFETY-KEYED, COLOR-CODED. PROVIDE BOTTLE SLIDES WITH ALL VACUUM OUTLETS.
COORDINATE QUANTITY AND LOCATIONS OF BOTTLE SLIDES WITH ARCHITECT/OWNER. SEE FLOOR
PLANS FOR GAS SERVICE REQUIRED AND LOCATIONS. SEE ARCHITECTURAL PLANS FOR FINAL
LOCATION.
NOTES:
PLUMBING EQUIPMENT SCHEDULE
MARK. NO. DESCRIPTION MAKE/MODEL/SIZE REMARKS
PE-1 DUPLEX FOUNDATION
SUMP PUMPS AND BASIN
"CRANE/BARNES"
MODEL SE1044L
OR APPROVED EQUAL
(2) PUMPS RATED FOR 43 GPM AT TDH. 1 HP, 208V/3 PHASE. PROVIDE 36" DIA. x 60" DEEP POLYETHYLENE BASIN. PROVIDE WITH NEMA 1 DUPLEX CONTROL PANEL. CONTROL PANEL TO INCLUDE HOA SWITCH FOR EACH PUMP, ALARM AUXILIARY DRY CONTACT, AND (4) LEVEL FLOAT SWITCHES WITH 20' CORDS. PROVIDE PUMPS WITH 25' CORDS.
PE-2 INLINE RECIRCULATING
HOT WATER PUMP
"TACO"
MODEL 112
OR APPROVED EQUAL
INLINE PUMP CAPACITY TO BE 20 GPM WITH 16 FEET OF HEAD. MOTOR RPM OF 3450, 1/3 HP MOTOR, 120 VOLT/1 PHASE, AND 1" PUMP CONNECTIONS. E.C. TO PROVIDE MOTOR STARTER AND DISCONNECT SWITCH. SEE SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FINAL SUBMISSION 9.11.20
BID ISSUE SUBMISSION 2.9.21
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1" RDHW
2" DHW
3" DCW
1" R
D H
W 2"
R D
H W
3" D
C W
3/4" MA
UST UST
UST
U
ST
U
ST
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP TO FIRST FLOOR.
2. REMOVE SECTION OF EXISTING FOOTER DRAINAGE PIPING. COORDINATE EXTENT OF
REMOVAL WITH NEW WORK PLAN.
3. REMOVE EXISTING STORM PIPING BACK TO MAIN AND CAP.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-0-1
BASEMENT LEVEL PHASE I PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
BASEMENT LEVEL PHASE I PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FE
C
FEC
FE
C
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1" RDHW
2" DHW
3" DCW
1" R
D H
W 2"
R D
H W
3" D
C W
2" SAN
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP TO FIRST FLOOR.
2. REMOVE 2" SAN BACK TO POINT INDICATED AND CAP.
3. REMOVE EXISTING 4" SAN BACK TO POINTS INDICATED FOR RECONNECTION UNDER NEW
WORK.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-0-2
BASEMENT LEVEL PHASE II PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
BASEMENT LEVEL PHASE II PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FEC
FE
C
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1" RDHW
2" DHW
3" DCW
1" R
D H
W 2"
R D
H W
3" D
C W
4" S
AN
2 3 3 4
4" S
AN
4"
S
AN
4" SAN
4" S
AN
4"
S
AN
2" SAN 2" SAN
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP TO FIRST FLOOR.
2. REMOVE EXISTING 2" SAN BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW WORK.
3. REMOVE EXISTING 2" SAN BACK TO POINT INDICATED AND CAP.
4. REMOVE EXISTING 4" SAN BACK TO POINT INDICATED AND CAP.
5. REMOVE EXISTING 3" SAN BACK TO POINT INDICATED AND CAP.
6. REMOVE EXISTING 4" SAN BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW WORK.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-0-3
BASEMENT LEVEL PHASE III PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
BASEMENT LEVEL PHASE III PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
M F
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1/ 2"
1" 2"
1" 1/2"
2"
1/2" RDHW
1" DHW
2" DCW
3/ 4"
O
1/ 2"
M V
1/ 2"
M A
1/2" 2"
3/4"
1/ 2"
R D
H W
3/ 4"
D H
W 3/
4" D
C W
1/2" MA
1 1/2" MV
3/4" O
3/4" 1 1/2"
1/2"
2"1 1/
4" 1/
2"
1/2" MA
1 1/2" MV
3/4" O
1/ 2"
M A
1" M
V 1/
2" O
1/2" RDHW
3/4" DHW
1 1/2" DCW
3/ 4"
3/ 4"
1/ 2"
1/ 2"
M A
1/
4" M
V 1/
2" O
1/2" 1 1/4"
1/2"
1/
4" 1/
2"
1/ 2"
3/ 4"
3/ 4"
1/ 2"
1/2" RDHW
1 1/4" DHW
2" DCW
2" D
C W
1/
4" D
H W
1/2" MA
1 1/4" MV
1/2" O
1/2" O
3/4" MV
1/2" MA
1/2" 3/4"
1/2"
1/ 2"
1/ 2"
3/ 4"
3/ 4"
1/
2"
1/2" 1/2"
1/2"
1/ 2"
M A
1/
2" M
V 3/
4" O
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP AND DOWN.
2. EXISTING 3/4" O, 1-1/2" MV AND 1/2" MA LINES DOWN IN WALL TO EXISTING ZONE VALVE BOX
AND BACK UP TO CEILING SPACE.
3. REMOVE EXISTING STORM PIPING FROM SALLYPORT ROOF DRAIN BACK TO MAIN AND CAP.
4. REMOVE EXISTING STORM PIPING FROM ROOF DRAIN BACK TO MAIN AND CAP.
5. REMOVE EXISTING 1/2" MA PIPING FROM POINT INDICATED BACK TO EXISTING MEDICAL GAS RISERS LOCATED AT NORTH SIDE OF COLUMN (L,50) ADJACENT TO MEN'S TOILET ROOM 1-M52
FOR TIE-IN UNDER NEW WORK.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-1-1
FIRST FLOOR LEVEL PHASE I PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
FIRST FLOOR LEVEL PHASE I PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FE
C
FEC
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
3 3 4
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP AND DOWN.
2. EXISTING 3/4" O, 1-1/2" MV AND 1/2" MA LINES DOWN IN WALL TO EXISTING ZONE VALVE BOX
AND BACK UP TO CEILING SPACE.
3. REMOVE EXISTING PLUMBING FIXTURE ALONG WITH ALL ASSOCIATED DOMESTIC WATER,
SANITARY AND VENT PIPING, AND VALVING TO POINTS INDICATED AND CAP.
4. REMOVE EXISTING MEDICAL GAS OUTLETS AND MEDICAL GAS PIPING BACK TO POINTS
INDICATED AND CAP.
5. REMOVE EXISTING DCW PIPING BACK TO POINT INDICATED FOR TIE-IN UNDER NEW WORK.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-1-2
FIRST FLOOR LEVEL PHASE II PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
FIRST FLOOR LEVEL PHASE II PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
R
EF
FE
C
FE
C
FEC
FEC
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1/2" MA
1 1/2" MV
3/4" O
1/2" MA
1 1/2" MV
3/4" O
2" DCW
2" SAN2"
4" S
AN
4"
4" S
AN
4"
S
AN
4" SAN
4"
1/ 2"
M A
1/
4" M
V 1/
2" O
1/ 2"
M A
1" M
V 1/
2" O
1/ 2"
M A
3/ 4"
M V
1/ 2"
O
1/2" RDHW
3/4" DHW
1 1/2" DCW
1/2" O
1/2" MA
3/4" MV
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP AND DOWN.
2. REMOVE EXISTING ZONE VALVE BOX FOR RELOCATION UNDER NEW WORK. REMOVE EXISTING
3/4" O, 1-1/2" MV AND 1/2" MA LINES BACK TO POINTS INDICATED FOR RECONNECTION UNDER NEW
WORK.
3. REMOVE EXISTING PLUMBING FIXTURE ALONG WITH ALL ASSOCIATED DOMESTIC WATER,
SANITARY AND VENT PIPING, AND VALVING TO POINTS INDICATED AND CAP.
4. REMOVE EXISTING MEDICAL GAS OUTLETS AND MEDICAL GAS PIPING BACK TO POINTS
INDICATED FOR TIE-IN UNDER NEW WORK.
5. REMOVE EXISTING 1-1/4" MV, 1/2" O, AND 1/2" MA PIPING BACK TO POINTS INDICATED FOR TIE-
IN UNDER NEW WORK.
6. REMOVE EXISTING 1" DHW PIPING BACK TO POINT INDICATED FOR TIE-IN UNDER NEW WORK.
7. REMOVE EXISTING 1/2" RDHW PIPING BACK TO POINT INDICATED FOR TIE-IN UNDER NEW
WORK.
8. REMOVE EXISTING MEDICAL GAS ALARM PANEL FOR RELOCATION UNDER NEW WORK.
REMOVE EXISTING 1/2" O, 1/2" MV AND 1/2" MA LINES BACK TO POINTS INDICATED FOR
RECONNECTION UNDER NEW WORK.
9. REMOVE EXISTING MEDICAL GAS VALVE AND PIPING ALONG WITH OTHER MISCELLANEOUS
PIPING LOCATED IN BUILT-OUT CHASE BACK TO MAINS AND CAP.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-1-3
FIRST FLOOR LEVEL PHASE III PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
FIRST FLOOR LEVEL PHASE III PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1/ 2"
M A
1/
4" M
V 3/
4" O
3/4" O
1/2" MA
1 1/4" MV
3/ 4"
3/ 4"
1/ 2"
3/4" DHW
3/4" DCW
1/2" O
1" MV
1/2" MA
1/ 2"
R D
H W
1/
4" D
H W
2" D
C W
1" 1 1/2"
1/2" RDHW
1" DHW
1 1/2" DCW
1/
2" D
C W
1" D
H W
1/ 2"
R D
H W
1 1/2" DCW
1" DHW 1"
1 1/2"
3/4" 1 1/2"
1" DHW
1 1/2" DCW
3/ 4"
1/
4" 1/
2"
CODED NOTES
1. EXISTING 2-1/2" DCW, 2" DHW AND 3/4" RDHW RISERS UP FROM FIRST FLOOR.
2. EXISTING 1-1/4" MV, 3/4" MA AND 1/2" O LINES DOWN TO EXISTING ZONE VALVE BOX AND BACK
UP TO CEILING SPACE.
3. REMOVE EXISTING ROOF DRAIN AND ASSOCIATED STORM PIPING.
4. EXISTING ROOF DRAIN TO REMAIN.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
9:
P M
P-D-2-1
SECOND FLOOR LEVEL PHASE I PLUMBING
DEMOLITION PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
SECOND FLOOR LEVEL PHASE I PLUMBING DEMOLITION PLAN
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FEC
FE
C
X-H
PS
X-H
PC
Ex.
HWS
/R
STA
CKE
D
ON
WAL
L.
TIE
NEW
P.C
. IN
TO
EXIS
TING
8"
(PR
OST
HET
CSSTO
RAG
EC2
(80
C1 (330
STO
RAG
E
(RE
H.
MED
. S
VC)
X-1
X-1
CRA
WL
SPA
CE
"x
14"x 12"
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
1" RDHW
2" DHW
3" DCW
1" R
D H
W 2"
R D
H W
3" D
C W
1" R
D H
W 2"
D H
W
1/ 2"
D C
W
PE-2
BAC285
BAC284
BAC281 BAC282
BAC280
BAC274
BAC283
BAC253
BAC250B
BAC254 BAC255
BAC252
BAC251
BAC250
BAC256
BAC328
BA109C
BS3
BA109
BAC329
BAC330
BAC275
BAC260B
BAC272
BAC270C
BAC270B
BAC270A
BAC269
BAC260A
BAC271
BAC273
BAC260
BAC261
BAC260C
BAC262
BAC298A
BA150A
BAC264
BAC268
BAC265
BAC266
BA150B
BA148 BA149 BAC241
BS4
BA152
BA151
BA153
BA150C
BA152A
BAC241A
BA153A
DECONTAMINATION
STORAGE TANK
P-804
1" D
C W
1" DCW
1" D
C W
CODED NOTES
1. EXISTING 3" DCW, 2" DHW AND 1" RDHW RISERS UP TO FIRST FLOOR.
2. INSTALL NEW 2-1/2" DCW, 2" DHW AND 1" RDHW RISERS UP TO FIRST FLOOR.
3. TIE NEW 2-1/2" DCW, 2" DHW AND 1" RDHW LINES INTO EXISTING 3" DCW, 2" DHW AND 1" RDHW
PIPING AND EXTEND TO NEW ADDITION.
4. INSTALL NEW DOMESTIC HOT WATER RECIRCULATION PUMP IN BASEMENT CEILING SPACE.
SEE DETAIL FOR ADDITIONAL REQUIREMENTS.
5. INSTALL 3/4" DCW LINE DOWN ALONG WALL AND EXTEND TO HOSE BIBB. COORDINATE FINAL
ELEVATION WITH ARCHITECTURAL PLANS.
6. INSTALL 1" DCW WITH AN ASSE 1013 REDUCED PRESSURE BACKLOW PREVENTER FOR
HEATING WATER SYSTEM MAKEUP. COORDINATE EXACT LOCATION WITH H.C. H.C. SHALL
EXTEND FROM ROUGH-IN POINT FOR FINAL CONNECTION TO HEATING WATER SYSTEM.
PLAN NOTES
A. THIS DRAWING WAS DESIGNED TO PLOT AS 30" X 42" PLOT. IF PLOT DOES NOT MATCH THE
DESIGNED SIZE, THE GRAPHICAL SCALE SHALL BE USED.
B. SEE SHEET P-001 FOR PLUMBING SYMBOL LEGEND, PLUMBING GENERAL NOTES, AND
PLUMBING DETAILS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\a m ca le es e\
D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ am ca le es e.
rv t
2/ 9/
:0
6:
P M
P-0.1-1
BASEMENT LEVEL PHASE I PLUMBING PIPING
IMPROVEMENT PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS DMR2.9.21
N 1/8" = 1'-0"
BASEMENT LEVEL PHASE I PLUMBING PIPING IMPROVEMENT PLAN
ROOM LEGEND
Number Name
BA109 Mechanical Room BA109C Office BA148 Electrical BA149 TeleComm
BA150A Corridor BA150B Corridor BA150C Corridor BA151 Main Electrical Room BA152 Pharmacy Drug Cache
BA152A Secure Storage BA153 Mechanical Room
BA153A Relief Areawell
BAC241 HVAC
BAC241A Outside Air Enclosure BAC250 Waiting
BAC250B Passage BAC251 Triage BAC252 Exam BAC253 Exam BAC254 Exam BAC255 Exam BAC256 Records BAC260 Reception/ Waiting
BAC260A Passage BAC260B Passage BAC260C Passage BAC261 Regulatory/ Fiscal Office BAC262 2 Person Office BAC264 Storage BAC265 4 Person Office BAC266 IT Work Offices BAC268 Copy/ Work Passage BAC269 2 Person Office
BAC270A Break Area/ Pantry BAC270B Collaboration Area BAC270C Open Student Offices BAC271 Director Office BAC272 Office BAC273 Office BAC274 2 Person Office BAC275 2 Person Office BAC280 Anti-Coagulation Clinic Open Office BAC281 Office BAC282 Copy File/Work BAC283 Break Room BAC284 Corridor BAC285 Storage, File Room
BAC298A Closet BAC328 Corridor BAC329 Womens BAC330 Mens
BS3 Stair 3 BS4 Stair 4
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20
FEC
FE
C
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
4" US 4" US
4" US
4" US
2" S
AN
4" S
AN
4"
2 1/2" SAN
2" SAN
4" 3" SAN
4" U
S
2" SAN
3"
4" US
DECONTAMINATION
STORAGE TANK
FW/FCO
C.O.
C.O.
C.O.
C.O.
FW/FCO
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
C.O.
8" U
ST
UST
U
ST
UST
UST
U
ST
UST
U
ST
4" DT
4" DT
4" DT
4" DT
4" DT
4" DT
FINISHED FLOOR
= 653.25
PE-14" DS
4" SAN
C.O.
C.O.
C.O.
4" DS
4" SAN
4" SAN
4" DS
FW/FCO
4" SAN
2"
2" S
AN
2"
S
AN
8" D
S
4" DS
4" D
S
6" DS C.O.
C.O.
C.O.
C.O.
C.O.
6" DS
6" D
S
FW/FCO
4" U
S
3" IW
2" DS
C.O.
3"
3" SAN
3" S
AN
C.O.
2" S
AN
4" S
AN
2" SAN
4"
2" 4"
C.O.
C.O.
FD-E
FD-E
FD-E
FD-E
C.O.
3" S
AN
UST
4" U
S 4"
U S
4" US
BAC285
BAC284
BAC281 BAC282
BAC280
BAC274
BAC283
BAC253
BAC250B
BAC254 BAC255
BAC252
BAC251
BAC250
BAC256
BAC328
BA109C
BS3
BA109
BAC329
BAC330
BAC275
BAC260B
BAC272
BAC270C
BAC270B
BAC270A
BAC269
BAC260A
BAC271
BAC273
BAC260
BAC261
BAC260C
BAC262
BAC298A
BA150A
BAC264
BAC268
BAC265
BAC266
BA150B
BA148 BA149 BAC241
BS4
BA152
BA151
BA153
BA150C
BA152A
BAC241A
BA153A
C.O.
4"
4" S
AN
2"
FD-E
4" U
S
4" US
FD-H
4" U
S 4"
U S
FD-H
4" D
S
4" INVERT = 651.25
4" INVERT = 650.2
4" INVERT = 649.8
4" INVERT = 651.0
FD-E
FD-E
CODED NOTES
1. INSTALL 8" STORM PIPE THROUGH WALL AT INVERT = 652.0. EXTEND 8" STORM PIPE TO TIE INTO CLEANOUT AS SHOWN ON CIVIL DRAWING GS-3. SEE CIVIL DRAWINGS FOR CONTINUATION.
2. TIE NEW 4" US INTO EXISTING 4" US AND EXTEND TO NEW ADDITION.
3. INSTALL 1-1/2" SAN UP TO SINK(S) ON FLOOR ABOVE. EXTEND 1-1/2" VENT UP IN WALL TO
CEILING SPACE.
4. INSTALL 4" SAN AND 3" VENT STACKS UP IN WALL ON FLOOR ABOVE.
5. INSTALL 4" STORM STACK UP TO ROOF DRAIN.
6. INSTALL 4" SAN UP TO SHOWER ON FLOOR ABOVE.
7. INSTALL 4" SAN DOWN TO DECONTAMINATION STORAGE TANK.
8. INSTALL 2" VENT UP IN WALL ON FLOOR ABOVE TO CEILING SPACE.
9. INSTALL 4" SAN AND 3" VENT STACKS UP IN CHASE ON FLOOR ABOVE.
10. INSTALL 4" US TO THIS POINT FOR FUTURE CONNECTION AND EXTENSION UNDER PHASE II.
11. ROUTE NEW FOOTER DRAINAGE PIPING AROUND NEW ADDITION AND RECONNECT INTO
EXISTING SYSTEM. EXISTING BUILDING DRAWINGS INDICATE THE LOW POINT OF SLOPED
FOOTER DRAINAGE PIPING TO BE NEAR COLUMN (E1,53). THE INTENT IS FOR THE NEW FOOTER
DRAINAGE PIPING TO BE SLOPED @ A MINIMUM OF 0.5% TOWARD THE NEW LOW POINT NEAR
COLUMN (D',53) AND TIE INTO EXISTING FOOTER DRAINAGE PIPING. SURVEY EXISTING INVERTS TO MAINTAIN POSITIVE SLOPE. FIELD VERIFY PRIOR TO CONSTRUCTION. FIELD VERIFY SIZE OF
PIPING.
12. INSTALL 4" PERFORATED DRAIN TILE UNDER SLAB. REFER TO STRUCTURAL DRAWINGS FOR
UNDERSLAB DRAINAGE SYSTEM INFORMATION.
13. INSTALL SUMP PUMP AND BASIN. INSTALL 2" PUMP DISCHARGE UP ALONG WALL TO CEILING
SPACE. REFER TO DETAIL FOR ADDITIONAL INFORMATION. COORDINATE ELECTRICAL
REQUIREMENTS WITH E.C.
14. PROVIDE OPENING IN SUMP CROCK FOR EXTENSION OF UNDERSLAB DRAINAGE SYSTEM.
REFER TO STRUCTURAL DRAWINGS FOR UNDERSLAB DRAINAGE SYSTEM INFORMATION.
15. INSTALL 4" SAN AND 3" VENT STACKS UP ALONG COLUMN TO BASEMENT CEILING SPACE.
16. INSTALL 8" STORM STACK DOWN ALONG WALL TO BELOW SLAB.
17. TIE NEW FOOTER DRAINAGE PIPING INTO EXISTING AT APPROXIMATELY THIS LOCATION AND AT AN APPROXIMATE EXISTING INV. = 644.5. SURVEY EXISTING INVERTS TO MAINTAIN POSITIVE
SLOPE. FIELD VERIFY PRIOR TO CONSTRUCTION. FIELD VERIFY SIZE OF PIPING.
18. INSTALL 2-1/2" VENT UP ALONG WALL TO CEILING SPACE AND EXTEND TO VENT STACK.
19. INSTALL 3" SAN UP TO FLOOR DRAIN IN MAIN ENTRY VESTIBULE ON FLOOR ABOVE.
20. INSTALL 4" SAN UP TO CLINIC SINK ON FLOOR ABOVE.
21. INSTALL 4" SAN UP TO W.C. ON FLOOR ABOVE.
22. INSTALL 1-1/2" SAN UP TO LAV ON FLOOR ABOVE.
23. INSTALL 3" SAN UP TO FLOOR DRAIN ON FLOOR ABOVE.
24. INSTALL 500 GALLON VERTICAL POLYETHYLENE DECONTAMINATION STORAGE TANK IN
SECONDARY CONTAINMENT TANK. PROVIDE WITH HIGH LEVEL FLOAT SENSOR AND ALARM
PANEL. ALARM PANEL SHALL BE INSTALLED ON WALL IN BASEMENT NEAR DECONTANIMATION
TANK AND BE TIED INTO BUILDING AUTOMATION SYSTEM. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. SEE DETAIL (THIS SHEET).
25. INSTALL 4" STORM STACK UP TO ROOF DRAIN ON CANOPY.
26. INSTALL 4" STORM STACK UP IN CHASE TO ROOF DRAIN ON CANOPY.
27. TIE 4" STORM PIPING INTO 8" STORM LATERAL AT…