This document provides details for a federal solicitation seeking construction services for an Emergency Department expansion project. The Department of Veterans Affairs intends to award a firm-fixed-price contract for design-build services including general construction, alterations, electrical work, mechanical work and other items to create a 27,000 square foot addition and 10,000 square foot renovation at the Cleveland VAMC. Work will integrate a Psychiatric Emergency Department, Specialty Care Clinics and support spaces. The project also involves site work such as a new entrance drive, parking lot, and security features. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and issued on February 26, 2021 via invitation for bid. The period of performance is approximately 695 calendar days from notice to proceed. All questions must be submitted in writing by the specified date.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
C
C
H
G
F
E.1
E
515049 49.4
STEEL GRATING,
OPEN TO SHAFT
BELOW - SEE
SECTIONS THRU
SHAFT AS TAGGED
ALUM. COPING ATOP CMU
KNEE WALL, SEE SECTION ROOF CONSTRUCTION:
EPDM ROOFING SYSTEM OVER
MIN. R-30 RIGID INSULATION,
TAPERED 1/4" PER FOOT TO DRAIN,
5/8" DENS-GLASS PROTECTION
BOARD + VAPOR BARRIER, CAST-
IN-PLACE CONC. ROOF DECK
AS-200
AS-2001
AS-200
E.9
D.9
D.7
D.6
54A 54.7
E'
E' D'
D'
G.5
H
IG
H P
O
IN
T
H
IG
H P
O
IN
T
HIGH POINT
EXISTING
LIMESTONE PANEL
WALL TO REMAIN
AS-201
AS-202
AS-202
AS-203
PORTION OF
EXISTING LIMESTONE
PANEL WALL TO BE
FULLY DEMOLISHED
EXISTING LOWER
ROOF BELOW
S
LO
P E
D O
W N
1/4" P E
R F
T . T
Y P
.S
LO
P
E D
O W
N
1/4" P E
R F
T . T
Y P
S
LO
P E
D O
W N
1/4" P E
R F
T . T
Y P
SLOPE DOWN
1/4" PER FT. TYP.
SLOPE DOWN
1/4" PER FT. TYP.
SLOPE DOWN
1/4" PER FT. TYP.
SLOPE DOWN
1/4" PER FT. TYP.
SLOPE DOWN
1/4" PER FT. TYP.
COLUMN ENCLOSURE
BELOW SHOWN
DASHED
SLOPE DOWN
1/4" PER FT. TYP.
ROOF
DRAIN
ROOF
DRAIN
ROOF
DRAIN
ROOF
DRAIN
METAL TRIM BAND BELOW,
SEE ELEVATIONS. JOINTS
TO ALIGN W/FRONT
ELEVATION
S
LO
P E
S T
R U
C T
U R
E
D O
W N
AS-200 4
CANOPY ROOF
CONSTRUCTION: EPDM
ROOFING SYSTEM OVER 5/8"
DENS-GLASS PROTECTION
BOARD ON METAL DECK
INTERALLY ILLUMINATED, RED
"EMERGENCY" SIGNAGE LETTERING,
TOP-MOUNTED TO CANOPY PARAPET
WALL, SEE ELEVATION
EXISTING CONC.
PEDESTAL PAVER
ROOF
/2
ROOF
DRAIN
ROOF DRAIN
14'-8" 27'-0" 27'-0" 27'-0"
50.1
AS-202
AS-201
AS-201
AS-201
AS-201
AS-201
S
LO
P E
S T
R U
C T
U
W N
1/ 4"
P E
R F
T . T
Y P
80.000°
S
LO
P E
S T
R U
C T
U
W N
49.5
AS-201
AS-201
SIM.
27'-0" 1'-11" 21'-0"
TAPERED
INSULATION
TAPERED
INSULATION
AS-203
AS-203
51.05
AS-203
DASHED LINE
INDICATES
VESTIBULE
WALL BELOW
PAINTED STEEL CANOPY
HANGER RODS ATTACHED
TO COLUMNS ON INTERIOR,
SEE STRUCT. PAINT COLOR
SHALL MATCH CANOPY
METAL PANELS
ALUMINUM COPING
ON PARAPET WALL,
TYP.
ALUMINUM COPING
ON PARAPET WALL,
TYP.
ALUMINUM COPING
ON PARAPET WALL,
TYP.
AS-204
EXISTING BRICK ON CMU
PARAPET WALL IN THIS AREA TO
BE DEMO'D FROM TOP OF EX.
ROOF DECK. NEW ROOFING
MEMBRANE SYSTEM SHALL
OVERLAP ON TOP OF EXISTING
MEMBRANE, BELOW NEW ALUM.
COPING ASSEMBLY - SEE
SECTION DETAIL
NEW LOCATION FOR
AC-50 CONDENSING
UNIT, SEE MECH.
PORTION OF EXISTING
LIMESTONE PIER TO REMAIN
ABOVE NEW ROOF. BOTTOM
TO BE CUT/MODIFIED TO
ACCEPT NEW ROOFING,
REFER TO ENLARGED
SECTION DETAIL
REFER TO ENLARGED SECTION
DETAIL 7/AS-402 FOR
CUTTING/RESUPPORTING OF
LIMESTONE ABOVE NEW ROOF,
TYP. ENTIRE LENGTH OF NEW
ADDITION
REFER TO ENLARGED SECTION
DETAILN 8/AS-402 FOR
CUTTING/RESUPPORTING OF
BRICK ABOVE NEW ROOF, TYP.
ENTIRE LENGTH OF NEW
ADDITION
12" W X 8" H METAL THRU-WALL
SCUPPER. PROVIDE ROOFING
SYSTEM ON INTERIOR
PERIMETER OF SCUPPER
OPENING AND SEAL TO ALL
EXTERIOR MATERIALS TO
PROVIDE WEATHERTIGHT
CONDITION. SEE EXTERIOR
ELEVATIONS FOR LOCATION
INTENT
ALUM. COPING
ATOP BRICK WALL
BELOW, SEE
SECTION
AS-402
TYP.
DETAIL
AS-402
TYP.
DETAIL
AS-402
ALUM. COPING
ATOP NEW
EXERIOR WALL
12" W X 8" H METAL THRU-WALL
SCUPPER. PROVIDE ROOFING
SYSTEM ON INTERIOR PERIMETER
OF SCUPPER OPENING AND SEAL
TO ALL EXTERIOR MATERIALS TO
PROVIDE WEATHERTIGHT
CONDITION. SEE EXTERIOR
ELEVATIONS FOR LOCATION
INTENT
12" W X 8" H METAL THRU-WALL
SCUPPER. PROVIDE ROOFING
SYSTEM ON INTERIOR PERIMETER
OF SCUPPER OPENING AND SEAL
TO ALL EXTERIOR MATERIALS TO
PROVIDE WEATHERTIGHT
CONDITION. SEE EXTERIOR
ELEVATIONS FOR LOCATION
INTENT
PORTION OF EXISTING LIMESTONE PIER TO
REMAIN ABOVE NEW ROOF. BOTTOM TO BE
CUT/MODIFIED TO ACCEPT NEW ROOFING,
REFER TO ENLARGED SECTION DETAIL
PEDESTAL-MOUNTED
ROOFTOP SECURITY
CAMERA. SEE ELEC. DWGS.
PEDESTAL-
MOUNTED
ROOFTOP
SECURITY
CAMERA. SEE
ELEC. DWGS.
3S4
3AC267 3AC266 3AC265 3AC264 3AC263 3AC262
3AC261 3AC259
3AC260
3AC231 3AC234 3AC236 3AC237 3AC238 3AC240
3AC241
3AC232 3AC233 3AC235 3AC239
3AC218 3AC219 3AC220 3AC221 3AC222 3AC223
3AC258
3AC267
3AC256
3AC255
3AC254
3AC217
3AC257
3AC230
'-0
AS-200
12" W X 16" H +/- METAL THRU-
WALL SCUPPER. PROVIDE
ROOFING SYSTEM ON INTERIOR
PERIMETER OF SCUPPER
OPENING AND SEAL TO ALL
EXTERIOR MATERIALS TO
PROVIDE WEATHERTIGHT
CONDITION. SEE EXTERIOR
ELEVATIONS FOR LOCATION
INTENT
IN
S
U
LA
T
V
S T
IB
U
LE
R
O O
F U
N
IN
S U
LA
T
A N
O P
Y R
O O
F
CONSTRUCT STUD WALL
W/SHEATHING AT EXPOSED END
OF LIMESTONE PANEL. RUN ROOF
MEMBRANE UP ENTIRE FACE.
FULLY SEAL
SECURELY ANCHOR
END OF GUARDRAIL
TO REAR OF
LIMESTONE
10'-0" MIN. VIF
NEW FREE-STANDING, NON-PENETRATING
GUARDRAIL SYSTEM. BASIS OF DESIGN:
KATTSAFE GW34 SERIES (OR EQUAL) @ 42"
MIN. ABOVE THE HIGHEST POINT OF THE
ROOF - VERIFY HEIGHT IN FIELD.
GUARDRAILS SHALL BE IN COMPLIANCE
WITH OSHA 1926.02 & OSHA 1910.23. GC
SHALL SUBMIT DOCUMENTATION INDICATED
COMPLIANCE WITH SAME
12" W X 16" H +/- METAL THRU-
WALL SCUPPER. PROVIDE
ROOFING SYSTEM ON INTERIOR
PERIMETER OF SCUPPER
OPENING AND SEAL TO ALL
EXTERIOR MATERIALS TO
PROVIDE WEATHERTIGHT
CONDITION. SEE EXTERIOR
ELEVATIONS FOR LOCATION
INTENT
ROOF LOW
PT. @ D.7
LINE
OPEN TO
BELOW
NEW FREE-STANDING, NON-PENETRATING
GUARDRAIL SYSTEM. BASIS OF DESIGN:
KATTSAFE GW34 SERIES (OR EQUAL) @ 42" MIN.
ABOVE THE HIGHEST POINT OF THE ROOF -
VERIFY HEIGHT IN FIELD. GUARDRAILS SHALL BE
IN COMPLIANCE WITH OSHA 1926.02 & OSHA
1910.23. GC SHALL SUBMIT DOCUMENTATION
INDICATED COMPLIANCE WITH SAME. VERIFY
FINAL LOCATION IN FIELD W/CONDENSING UNIT
18'-0"
AS-204
SECURELY ANCHOR
END OF GUARDRAIL
TO EXTERIOR WALL
'-0
GENERAL NOTES:
CONSIDER ALL AREAS OWNER-OCCUPIED UNLESS NOTED OTHERWISE.
ALL WALLS ARE DRAWN AND DIMENSIONED TO A 5" NOMINAL WIDTH TYPICAL UNLESS OTHERWISE NOTED.
ALL DIMENSIONS ARE CLEAR DIMENSIONS FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD.
ALL SUB-CONTRACTORS (I.E. FIRE PROTECTION, HVAC, FIRE ALARM, ELECTRICAL, ETC.) TO DESIGN AND INSTALL SYSTEM PER OWNER REQUIREMENTS AND IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL APPLICABLE CODES.
PATCH AND REPAIR ALL EXISTING AREAS TO REMAIN AS REQUIRED TO MATCH EXISTING CONDITIONS.
WHERE NEW UTILITIES ARE TO BE INSTALLED IN EXISTING PARTITIONS, ALL SUB-CONTRACTORS SHALL REMOVE EXISTING DRYWALL AS REQUIRED FOR INSTALLATION OF SAME AND PATCH AND REPAIR WITH NEW
TO MATCH EXISTING CONDITIONS UPON COMPLETION OF UTILITY INSTALLATION.
ALL DAMAGE TO EXISTING AREAS OCCURING AS A RESULT OF CONSTRUCTION SHALL BE REPAIRED AS REQUIRED BY THE CONTRACTOR. CONTRACTOR SHALL PROTECT ALL EXISTING WALL, CEILING, AND FLOOR FINISHES IN EACH AREA. ANY SURFACES DAMAGED BY CONTRACTOR SHALL BE REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
ALL NEW PENETRATIONS IN FIRE-RATED ASSEMBLIES TO MAINTAIN FIRE RATING OF ASSEMBLY AS
REQUIRED.
NEW AND EXISTING FURNITURE SHOWN FOR REFERENCE ONLY. THE OWNER SHALL REMOVE, PRIOR TO CONSTRUCTION, ALL ITEMS THAT THE OWNER DESIRES TO SALVAGE. ALL REMAINING ITEMS INDICATED TO BE DEMOLISHED SHALL BE REMOVED BY THE CONTRACTOR AND LEGALLY DISPOSED OF IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL ITEMS TO REMAIN IN SPACE SHALL BE PROTECTED THROUGHOUT BY THE CONTRACTOR THROUGHOUT CONSTRUCTION. NEW FURNITURE TO BE FURNISHED AND INSTALLED
BY THE OWNER UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL PROVIDE DUST-REMOVAL WALK-OFF MATS (TACKY MAT) AT ALL CONSTRUCTION ENTRY
POINTS.
CONTRACTOR SHALL PROVIDE HEPA FILTERED NEGATIVE AIR MACHINE(S) TO MAINTAIN NEGATIVE PRESSURE IN WORK AREAS ENSURING NO DUST OR FUMES WILL BE TRANSFERRED TO OCCUPIED AREAS.
PROVIDE VISUAL PRESSURE MONITORING DEVICE AT DUST-PROOF BARRICADE TO CONFIRM PRESSURE.
DUST MONITORING SHALL BE BY OWNER. SEE SPECIFICATION 01 00 00 "GENERAL REQUIREMENTS"
ATTACHMENT AND 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS.
ALL DEMOLITION WORK BEING DONE OUTSIDE TEMPORARY PARTITIONS IS TO BE APPROPRIATELY SEALED OFF TO PREVENT THE TRANSMISSION OF DUST AND DEBRIS. WORK SHALL BE DONE TO MINIMIZE DISRUPTION TO VISITORS, PATIENTS, AND STAFF. COORDINATE LOCATION OF BARRIERS WITH OWNER.
THE HOSPITAL'S SMOKE AND FIRE SUPPRESSION SYSTEM SHALL REMAIN IN OPERATION WITHIN THE
PROJECT AREA DURING THE ENTIRE CONSTRUCTION PHASE.
FIELD VERIFY LOCATION OF ALL EXISTING CONDITIONS. NOTIFY COR OF ANY DISCREPANCIES.
WHERE NEW DOORS ARE INDICATED IN EXISTING WALL ASSEMBLIES, CUT OPENINGS IN EXISTING WALL.
REFER TO DOOR SCHEDULE FOR DIMENSIONS. PREPARE OPENINGS FOR NEW DOOR, INCLUSIVE OF THE ADDITION OF JAMB AND HEAD STUD REINFORCEMENT (I.E. DOUBLE STUDS, HEADERS) AND PATCH ADJACENT
WALLS TO MATCH EXISTING.
ALL FLOOR, WALL, CEILING, AND MISC. FIRE-RESISTIVE ASSEMBLIES AND CONSTRUCTION SHALL BE OF THE FIRE RATING CALLED FOR ON THE DRAWINGS AND/OR AS REQUIRED BY CODE. ALL EXISTING FIRE-RESISTIVE ASSEMBLIES SHALL BE MAINTAINED AND THE RATING NOT COMPROMISED. FIRE RATED ASSEMBLIES AND CONSTRUCTION INCLUDING ALL FIRESTOPPING, FIRE RATED DOORS, AND MISC. FIRE RESISTIVE REQUIREMENTS SHALL BE LEFT UNCONCEALED AS REQUIRED FOR INSPECTION BY THE BUILDING OFFICIAL.
DEBRIS REMOVAL SHALL NOT INTERFERE WITH OWNER'S OPERATIONS AND SHALL OCCUR DURING OFF HOURS AS DETERMINED BY THE COR. SEE ALSO SPECIFICATION SECTION 01 35 26 "SAFETY REQUIREMENTS" FOR ADDITIONAL REQUIREMENTS REGARDING THE HAULING OF DEBRIS FROM THE PROJECT AREA.
ALL NOISE-GENERATING OPERATIONS SHALL BE SCHEDULED SO AS NOT TO IMPEDE OWNER'S OPERATIONS AS DETERMINED BY THE COR. ALL WORK IN PUBLIC CORRIDORS SHALL BE PERFORMED OFF-HOURS UNLESS
OTHERWISE APPROVED BY THE COR.
EXISTING FLOOR SLABS ARE 2 HR FIRE RATED. FOR ALL NEW CORE DRILLS/UTILITY PENETRATIONS, GC SHALL UTILIZE GROUND PENETRATING RADAR TO X-RAY EXISTING FLOOR SLAB AT PROPOSED, NEW PENETRATION LOCATION TO ENSURE THAT FLOOR SLAB REBAR STRUCTURE WILL NOT BE COMPROMISED, AND GC SHALL NOTIFY COR AND A/E TEAM OF ANY ISSUES DISCOVERED IN FIELD. GC SHALL PROVIDE NEW 2 HR RATED THRU-SLAB FIRESTOP ASSEMBLIES AT ALL PENETRATIONS. FOR EXISTING THRU-SLAB UTILITIES THAT ARE REMOVED AS A PART OF DEMOLITION SCOPE, GC SHALL PATCH CONCRETE SLAB FULLY WITH NEW CONCRETE TO MATCH EXISTING OR APPROVED 2 HR RATED INFILL FIRESTOP ASSEMBLY WHEN APPROVED
BY THE COR.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
SYMBOL LEGEND:
INDICATES EXISTING DOOR
INDICATES NEW DOOR
EXISTING WALLS TO REMAIN
NEW WALLS
WALLS TO BE REMOVED FULL HEIGHT U.N.O.
DASHED LINES INDICATE ITEMS TO BE DEMOLISHED
HATCHED AREA OUTSIDE OF PROJECT SCOPE.
ACCESS INTO CEILING SPACES MAY OCCUR, REFER
TO MEP DWGS.
FIRE-RATED PLASTIC SHEETING/METAL STUD WALL TEMPORARY PARTITION WALL W/3'-0" X 7'-0"
SCWD DOOR FOR CONTRACTOR ACCESS ONLY. WALL AND DOOR TO BE REMOVED UPON
COMPLETION OF WORK U.N.O. PATCH/REPAIR EXISTING CONDITIONS AS REQUIRED UPON
REMOVAL OF ALL TEMPORARY CONSTRUCTION. REFER TO TEMPORARY CONSTRUCTION BARRIER
DETAIL ON SHEET AS-601. SCHEDULE NOTE: CONSTRUCTION OF TEMPORARY BARRIERS SHALL BE
PERFORMED AFTER NORMAL BUSINESS HOURS UNLESS OTHERWISE APPROVED BY THE COR.
TEMPORARY ZIP WALL PROTECTION TO BE PROVIDED AROUND CONSTRUCTION AREA PER VA
SAFETY STANDARDS. INSTALLATION OF ZIP WALL MAY NEED TO OCCUR AFTER RELOCATION OF
CASEWORK/FURNITURE. GC TO COORDINATE SEQUENCING OF INSTALL WITH COR
GENERAL CONSTRUCTION PARTITION NOTE: WHERE TEMP. CONST. PARTITIONS CONFLICT
W/EX. LIGHTS/DIFFUSER/MEP ITEM LOCATIONS (INDICATED ON CEILING DEMOLITION PLANS), GC
SHALL COORD. W/COR TO EITHER TEMPORARILY REMOVE SUCH ITEMS, OR ADJUST LOCATION
OF CONST. PARTITION ACCORDINGLY TO ALLOW ITEMS TO REMAIN IN PLACE
REFER TO SHEET AS-600 FOR WINDOW TYPES#
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
BID ISSUE SUBMISSION
C U s e rs
\d a v e
\D o c u m e n ts
\E x p a n d E m e rg e n c y D e p t_
R d a k a p la n
.r v t
/1
/2
:4
:3
P
M
AS-3.1
THIRD FLOOR/NEW ADDITION ROOF PLAN -
PHASE I
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJK DAK
SCALE: 1/8" = 1'-0"
THIRD FLOOR/NEW ADDITION ROOF PLAN - PHASE I
NORTH
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20
90% CD's SUBMISSION 5.13.20
100% CD's SUBMISSION 6.26.20
FINAL CD's SUBMISSION 9.11.20
BID ISSUE SUBMISSION 2.9.21
ADDENDUM 2 4.16.21
SECOND FLOOR
679' - 5 3/8"
49.4
AS-202
AS-202
50.1
14'-10"
1'-0"
1'-8"
CANOPY T.O.S. LOW
681' - 5"
.0
+/- 2'-5"
49.5
8"
METAL PANELS, SEE
ELEVATIONS
METAL PANELS
CONT. DRIP EDGE
ALUM. COPING, FINISH TO
MATCH METAL PANELS
METAL PANEL
SYSTEM OVER AIR+
WEATHER RES.
BARRIER & EXTERIOR
GRADE SHEATHING
ON 6" METAL STUDS
@ 16" O.C.
TWO (2) LAYERS 3/4" FRTW
PLYWOOD, SLOPED
TOWARDS ROOF
ROOF MEMBRANE ON
FRTW PLYWOOD
SHEATHING, CONT. TO
FRONT EDGE OF COPING
ROOF DRAIN, ROUTE LEADER
TO COLUMN (BEYOND).
PROVIDE HEAT TRACE. SEE
PLUMBING DWGS.
2'-8"
ALUMINUM
COMPOSITE METAL
PANEL SYSTEM
OVER AIR +
WEATHER BARRIER,
5/8" EXT. GRADE
SHEATHING, 6" MTL.
STUD FRAMING @
16" O.C., SEE
REFLECTED CEILING
PLAN FOR COLOR,
JOINTS, AND
RECESSED LINEAR
LIGHTING
LOCATIONS
2 HR RATED EDGE-OF-SLAB FIRESTOP
ASSEMBLY, TYP. ENTIRE PERIMETER.
PER UL DESIGN CW-S-1013. SEE
ENLARGED SECTION DETAIL FOR
ADDT'L. DETAILS
/4
/1
/1
STUD CLIPS TYP., SEE
STRUCT. DWGS.
AS-403
AS-403
NEW CURTAIN SYSTEM IN
EX. LIMESTONE WALL
OPENING BEYOND
EXISTING LIMESTONE CLAD
PANEL WALL BEYOND
BONDBREAKER, TYP.
ALUM. CURTAIN WALL
SYSTEM, TYP.
QUARTZ WINDOW SILL,
TYP.
AS-402
SEE SECTION 1
FOR TYP. WALL
NOTES
1'-3"
ALL CANOPY STEEL FRAMING
AND METAL ROOF DECK
SHALL RECEIVE 90 MIN.
FIREPROOF SPRAY
ASSEMBLY PER UL DES P719.
REFER TO UL ASSEMBLY FOR
REQUIRED THICKNESS
1'-7"
1'-7"
SLOPED TOP OF ROOF,
SEE ROOF PLAN
6" H CONC. CURB BASE, SEE
ELEVATIONS
METAL PANELS, SEE
ELEVATIONS
6" H CONC. CURB BASE, SEE
ELEVATIONS
F
E.1
T/ADDITION ROOF
691' - 0 3/4"
E.9
D.7
Main Entry Vestibule
1A208
5/8" GWB ON 1-5/8" MTL.
FURRING WITH 1-1/2"
RIGID INSUL. IN BETWEEN
NEW 8" CMU ON
EXISTING BEAM, SEE
STRUCT. DWGS.
EX. FLOOR SLAB TO REMAIN,
SEE STRUCT. DWGS. FOR
CONNECTIONS TO NEW SLAB
EX. CONC. BEAM AND
FLOOR SLAB
EX. LIMESTONE
TO REMAIN
FROST SLAB,
SEE STRUCT.
DWGS.
NEW AUTOMATIC
SLIDING DOOR SYSTEM
EXISTING SLAB
AND GRADE
BEAMS TO
REMAIN
ROOF MEMBRANE
OVER INSULATION,
VAPOR BARRIER,
PROTECTION BD.,
METAL DECK
FLASHING
METAL PANEL
EX. CONC. BEAM
EX. WALL W/
LIMESTONE FINISH TO
REMAIN
EX. LIMESTONE
COPING
AS-403
AS-403
ALUM. CURTAIN
WALL SYSTEM
GYP. BD. SOFFIT ON 3-5/8"
MTL. STUDS @ 16" O.C.
EX. LIMESTONE PANELING TO
BE CUT AND RESUPPORTED
TO PERMIT NEW ROOF SLAB
CONSTRUCTION, SEE
ENLARGED DETAIL
EX. LIMESTONE CLAD WALL
ASSEMBLY TO REMAIN.
PORTIONS OF PANELING TO BE
REMOVED/RESUPPORTED - SEE
ENLARGED SECTION DETAILS
SEE STRUCT.
DWGS. FOR BEAM
BEARING DETAIL
V
IF
E
X
O P
G
EXISTING HEADER
OF OPENING TO
REMAIN
Lobby/Waiting
X1A211
Waiting Room
2AC200A
NEW ROOF SLAB DOWELED
INTO EX. SLAB & BEAM, SEE
STRUCT.
EX. COPING & BRICK
ON CMU WALL @ EX.
ROOF PARAPET TO BE
DEMO'D AS SHOWN
(SEE ROOF PLAN
LINE OF EXISTING
EXTERIOR WALL
BEYOND
NEW
STOREFRONT
ENTRY DOOR,
SEE SCHED.
BOX STUD
HEADER
EX. CLGS.
TO REMAIN
INFILL W/GYP.
BD. AS REQ'D.
@ JT. TO EX.
CLG.Lobby
2A191
NEW SLAB-ON-
GRADE WITH
RECESSED
PEDESTRIAN
MAT
ALL CANOPY STEEL FRAMING AND METAL
ROOF DECK SHALL RECEIVE 90 MIN.
FIREPROOF SPRAY ASSEMBLY PER UL
DES P719. REFER TO UL ASSEMBLY FOR
REQUIRED THICKNESS
INSULATED EXTERIOR
WALL ASSEMBLY SHALL
EXTEND TO UNDERSIDE
OF DECK AS SHOWN.
FULLY SEAL AROUND
STEEL BEAM
PENETRATION THRU WALL
AS-204
VESTIBULE FLOOR
SLAB: CONC. SLAB-ON-
GRADE OVER VAPOR
BARRIER, 2" R-10 RIGID
INSULATION, EXTENDED
MIN. 2'-0" INTO
INTERIOR OF BUILDING
STUD HEADER,
SEE STRUCT.
CAULK,
FLASHING
CANOPY
ROOF
VESTIBULE
ROOF
FIBER CANT
STRIP @ ROOF
TRANSITION
7 5/8"
FRTW WD. PLATE
INFILL, SEE
ENLARGED DETAIL
LAP
ROOFING
SYSTEMS
BELOW NEW
COPING
SEE ROOF
PLAN FOR
LOW POINT &
DRAIN
LOCATION
AS-403
FIRST FLOOR
667' - 0"
BASEMENT LEVEL
653' - 3"
SECOND FLOOR
679' - 5 3/8"
EX. THIRD FLOOR
691' - 2 3/4"
T/ADDITION ROOF
691' - 0 3/4"
D'
CANOPY T.O.S. HIGH
683' - 6"
2'-0" 18'-3"
CANOPY T.O.S. MID
682' - 8 1/2"
1'-4"
11 1/2"
CONT. DRIP EDGE
CONT. STEEL ANGLE,
SEE STRUCT.
ALUM. COPING, FINISH
TO MATCH METAL
PANELS
METAL PANEL SYSTEM
OVER AIR+ WEATHER
RES. BARRIER &
EXTERIOR GRADE
SHEATHING ON 6"
METAL STUDS @ 16"
O.C.
FRTW NAILER
ALUMINUM COMPOSITE
METAL PANEL SYSTEM
OVER AIR + WEATHER
BARRIER, 5/8" EXT. GRADE
SHEATHING, 6" MTL. STUD
FRAMING @ 16" O.C., SEE
REFLECTED CEILING PLAN
FOR JOINT AND RECESSED
LINEAR LIGHTING
LOCATIONS
5/8" GWB SOFFIT ON
METAL STUD
FRAMING
SUSPENDED CEILING
SYSTEM
DRYWALL TO ACOUSTICAL
TRANSITION MOLDING WITH
SHADOW REVEAL,
ARMSTRONG 7902 OR EQ.
SEE SECTION 5, SHEET
AS-201 FOR TYP.
BASEMENT &
WATERPROOFING NOTES
TYPICAL BRICK WALL
CONSTRUCTION
SEE SECTION 5, SHEET AS-201
ALUMINUM STOREFRONT WINDOWS
TYP. SEE WINDOW TYPES FOR
GLAZING
/2
2 HR RATED EDGE-OF-SLAB FIRESTOP
ASSEMBLY, TYP. ENTIRE PERIMETER. PER UL
DESIGN CW-S-1013. SEE ENLARGED SECTION
DETAIL FOR ADDT'L. DETAILS
METAL PANEL RETURN @
TOP, SLOPE 1/4" PER FOOT
FOR DRAINAGE
STUD CLIPS TYP., SEE
STRUCT. DWGS.
AS-403
AS-403
AS-402
1'-4"
EPDM ROOF MEMBRANE
OVER 5/8" FRTW PLYWOOD,
STEEL ROOF DECKING,
SLOPED STEEL STRUCTURE,
1/4" PER FOOT
SLOPE DN. 1/4" PER FOOT
AS-402
NOTE: DIMENSION VARIES ON
ELEVATION, SEE EXTERIOR
ELEVATIONS FOR PUNCHED
OPENING WINDOW HEIGHTS
AND SHEET AS-600 FOR
WINDOW DIMENSIONS
QUARTZ WINDOW
SILL, TYP.
CONT. ALUM. COPING OVER
FRTW WOOD PLATE, TYP.
ROOF CONSTRUCTION:
EPDM ROOFING SYSTEM
OVER MIN. R-30 RIGID
INSULATION, TAPERED 1/4"
PER FOOT TO DRAIN, 5/8"
DENS-GLASS PROTECTION
BOARD + VAPOR BARRIER,
CAST-IN-PLACE CONC. ROOF
DECK
TYPICAL BRICK WALL CONSTRUCTION: FACEBRICK
OVER 2-3/4" AIRSPACE, CONTINUOUS R-7.5 RIGID
INSULATION BOARD, AIR + WEATHER BARRIER, GYP.
SHEATHING, 6" MTL. STUDS @ 16" O.C. W/R-19 BATT
INSUL. IN BETWEEN, 5/8" GYPSUM BOARD FINISH ON
INTERIOR. PROVIDE VAPOR BARRIER ON WARM SIDE
OF BATT INSULATION. VAPOR BARRIER SHALL HAVE
FLAME SPREAD INDEX MAX. OF 25 AND SMOKE
DEVELOPED INDEX MAX OF 450.
BRICK TIES SHALL BE PROVIDED
@ 16" O.C. VERTICALLY, TYP.
BRICK WEEPS SHALL BE
PROVIDED @ 24" O.C. MIN.
HORIZONTALLY @ ALL FLASHING
AND SHELF ANGLE LOCATIONS
ALL CANOPY STEEL FRAMING
AND METAL ROOF DECK
SHALL RECEIVE 90 MIN.
FIREPROOF SPRAY
ASSEMBLY PER UL DES P719.
REFER TO UL ASSEMBLY FOR
REQUIRED THICKNESS
1'-3"
1'-7"
METAL PANELS OVER 2" MTL. FURRING ZEE-
CHANNELS @ 24" O.C. W/CONT. R-7.5
INSULATION BOARD, AIR + WEATHER BARRIER,
GYP. SHEATHING, 6" STUDS @ 16" O.C. W/R-19
BATT INSUL. IN BETWEEN, VAPOR BARRIER ON
WARM SIDE OF INSULATION
METAL PANEL PIER
BEYOND. JOINTS TO
ALIGN WITH FRONT
ELEVATION
TAPERED INSULATION,
SLOPED MIN. 1/4" PER
FT. TO DRAIN, SEE ROOF
PLAN
/4
/1
PTD. COVER PLATE @
CONNECTION, SEE STRUCT.
GALV. STEEL HANGER ROD,
SEE ROOF PLAN FOR
DETAILS. PAINT TO MATCH
RED METAL PANELS. SEE
STRUCT. DWGS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
BID ISSUE SUBMISSION
C U s e rs
\d a v e
\D o c u m e n ts
\E x p a n d E m e rg e n c y D e p t_
R d a k a p la n
.r v t
/1
/2
:1
:1
P
M
AS-202
WALL SECTIONS EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJK DAK
WALL SECTION
SCALE: 1/2" = 1'-0"AS-202
SECTION THROUGH ENTRY CANOPY
WALL SECTION
SCALE: 1/2" = 1'-0"AS-202
SECTION THROUGH MAIN LOBBY
WALL SECTION
SCALE: 1/2" = 1'-0"AS-202
SECTION THROUGH SOUTH CANOPY
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20
90% CD's SUBMISSION 5.13.20
100% CD's SUBMISSION 6.26.20
FINAL CD's SUBMISSION 9.11.20
FIRST FLOOR
667' - 0"
SECOND FLOOR
679' - 5 3/8"
5049.4
T/ADDITION ROOF
691' - 0 3/4"
50.1
Police/Security
1AC281
Lobby
1A211
Lobby/Waiting
1AC225
Waiting Room
2AC200A
SOLID GRAY AREAS
INDICATES EXISTING
BUILDING
REFER TO STRUCT.
DWGS. FOR DOWELING
DETAILS @
NEW/EXISTING SLAB
TRANSITIONS
EXISTING CONC. BEAM
SUSPENDED CEILING TILE
SOLID GRAY AREAS
INDICATES EXISTING
BUILDING
NEW CONCRETE FLOOR
SLAB. SEE STRUCT. DWGS.
FOR DOWELING
REQUIREMENTS
NOTE: TOP OF EX. SLAB MAY
HAVE SLOPE DOWN IN THIS
LOCATION (FORMER SPALLING
FROM EXTERIOR EXPOSURE,
DRAINAGE SLOPE, ETC). GC
SHALL PROVIDE LIGHTWEIGHT
CONC. TOPPING AS REQ'D. TO
ENSURE FLUSH TRANSITION
FROM NEW/EXISTING SLABS
ALUM. COPING ON ANCHOR CHAIR,
FRTW WD. PLATE, COLOR TO MATCH
METAL PANELS
NOTE: DESIGN INTENT IS TO MATCH TOP
OF METAL COPING WITH TOP OF EX.
LIMESTONE COPING. VERIFY FINAL
HEIGHTS IN FIELD
EXISTING BRICK EXTERIOR
WALL BEYOND TO REMAIN
EXISTING ROOF DRAIN, INSULATION,
AND MEMBRANE TO REMAIN
AS-306
NEW STOREFRONT ENTRY
DOOR, SEE SCHEDULE
SUSPENDED
CEILING TILE,
TYP.
GYP. BD.
SOFFIT ON
3-5/8" MTL.
STUDS, TYP.
11"
MIN. 2" THK. MINERAL WOOL
INSULATION HELD IN PLACE
W/1-1/2" SQ. PERIMETER ANGLES
SECURED TO CURTAIN WALL
FRAME. REFER TO UL ASSEMBLY
CW-D-2008 FOR DETAILS
2 HR RATED EDGE-OF-SLAB
FIRESTOPPING ASSEMBLY, TYP. @
ALL CURTAIN WALL/FLOOR SLAB
LOCATIONS PER UL DESK CW-D-2008
METAL PANELS OVER 2" MTL. FURRING
ZEE-CHANNELS @ 24" O.C. W/CONT.
R-7.5 INSULATION BOARD, AIR +
WEATHER BARRIER, GYP. SHEATHING,
6" STUDS @ 16" O.C. W/R-19 BATT INSUL.
IN BETWEEN, VAPOR BARRIER ON
WARM SIDE OF INSULATION
AS-202
SEE STRUCT. DWGS. FOR
SLAB SHORING AND
DOWELING DETAILS AT
NEW/EXISTING CONST.
JOINT
A B
O V
E R
O O
F
M
IN
M
IN
MIN.
1'-0"
PROVIDE NEW METAL
FLASHING @ BASE OF
NEW EXTERIOR WALL.
RUN FLASHING BEHIND
METAL PANELS AND
LAP OVER TOP OF EX.
ROOFING SYSTEM MIN.
1'-0". FULL SEAL @ LAP
JOINT
8"
V
IF
ROOF CONSTRUCTION: EPDM
ROOFING SYSTEM OVER MIN. R-30
RIGID INSULATION, TAPERED 1/4" PER
FOOT TO DRAIN, 5/8" DENS-GLASS
PROTECTION BOARD + VAPOR
BARRIER, CAST-IN-PLACE CONC.
ROOF DECK
/2
NEW FREE-STANDING, NON-PENETRATING
GUARDRAIL SYSTEM. BASIS OF DESIGN:
KATTSAFE GW34 SERIES (OR EQUAL) @ 42"
MIN. ABOVE THE HIGHEST POINT OF THE
ROOF - VERIFY HEIGHT IN FIELD.
GUARDRAILS SHALL BE IN COMPLIANCE
WITH OSHA 1926.02 & OSHA 1910.23. GC
SHALL SUBMIT DOCUMENTATION INDICATED
COMPLIANCE WITH SAME. VERIFY FINAL
LOCATION IN FIELD W/CONDENSING UNIT
POLICE/SECURITY
DESK, SEE SECTION
DETAIL
FIRST FLOOR
667' - 0"
BASEMENT LEVEL
653' - 3"
SECOND FLOOR
679' - 5 3/8"
EX. THIRD FLOOR
691' - 2 3/4"
T/ADDITION ROOF
691' - 0 3/4"
54.7
/4
/1
/1
/8
"1'-7"
10"
1'-7"
C.I.P. CONC. BEAM -
SEE STRUCT.
PROVIDE THRU-WALL
FLASHING @ FLOOR LEVEL,
TYP.
C.I.P. CONCRETE WALL W/WATERPROOFING
SYSTEM OVER ENTIRE FACE RUNNING FROM
BOTTOM OF FOOTER TO TOP OF 1ST FLOOR
SLAB (TYP.) PROVIDE CONTINUOUS R-7.5
RIGID XPS INSULATION BOARD FROM TOP OF
FOOTER TO T/1ST FLOOR SLAB AS SHOWN.
REFER TO STRUCT. DWGS. FOR WALL
REINFORCEMENT AND GRAVEL BACKFILL
REQUIREMENTS, TYP.
BASIS-OF-DESIGN WATERPROOFING SYSTEM:
SOPREMA COLPHENE LM BARR. APPROVED
EQUAL PERMITTED, SUBJECT TO
REVIEW/APPROVAL BY VA AND A/E. SYSTEM IS
COMPOSED OF THE FOLLOWING COMPONENTS,
STARTING FROM FACE OF CONC. WALL:
• LIQUID-APPLIED COLPHENE LM BARR
ELASTOMERIC WATERPROOFING
MEMBRANE
• COLPHENE BARR FLASHING
• SELF-ADHERED COLPHENE BSW
PROTECTOR LAYER
• RIGID R-7.5 EXTRUDED POLYSTYRENE
INSULATION (XPS)
• SOPRANATURE DRAINAGE MAT
CONTINUOUS STAINLESS STEEL THRU-
WALL FLASHING, TYP. ABOVE GRADE
SOLID GROUT AIRSPACE
FROM BOTTOM OF
FLASHING TO T/CONC.
WALL, TYP.
TYPICAL BRICK WALL CONSTRUCTION:
FACEBRICK OVER 2-3/4" AIRSPACE, CONTINUOUS
R-7.5 RIGID INSULATION BOARD, AIR + WEATHER
BARRIER, GYP. SHEATHING, 6" MTL. STUDS @ 16"
O.C. W/R-19 BATT INSUL. IN BETWEEN, 5/8"
GYPSUM BOARD FINISH ON INTERIOR. BRICK
WEEPS SHALL BE PROVIDED @ 24" O.C. MIN.
HORIZONTALLY @ ALL FLASHING AND SHELF
ANGLE LOCATIONS. PROVIDE VAPOR BARRIER
ON WARM SIDE OF BATT INSULATION. VAPOR
BARRIER SHALL HAVE FLAME SPREAD INDEX
MAX. OF 25 AND SMOKE DEVELOPED INDEX MAX
OF 450.
BRICK TIES SHALL BE PROVIDED @ 16" O.C.
VERTICALLY, TYP. BRICK WEEPS SHALL BE
PROVIDED @ 24" O.C. MIN. HORIZONTALLY
@ ALL FLASHING AND SHELF ANGLE
LOCATIONS
CONT. GALV. STEEL
ANGLE - SEE STRUCT.
2 HR EDGE OF SLAB FIRESTOP
ASSEMBLY PER UL DES CW-
S-1013
METAL PANELS OVER 2" MTL.
FURRING ZEE-CHANNELS @ 24" O.C.
W/CONT. R-7.5 INSULATION BOARD,
AIR + WEATHER BARRIER, GYP.
SHEATHING, 6" STUDS @ 16" O.C.
W/R-19 BATT INSUL. IN BETWEEN,
VAPOR BARRIER ON WARM SIDE OF
INSULATION
CONT. ALUM. COPING OVER
FRTW WOOD PLATE, TYP.
METAL STUD CLIPS, SEE
STRUCT. TYP.
ROOF CONSTRUCTION: EPDM
ROOFING SYSTEM OVER MIN.
R-30 RIGID INSULATION,
TAPERED 1/4" PER FOOT TO
DRAIN, 5/8" DENS-GLASS
PROTECTION BOARD + VAPOR
BARRIER, CAST-IN-PLACE CONC.
ROOF DECK
2 HR RATED EDGE-OF-SLAB FIRESTOP
ASSEMBLY, TYP. ENTIRE PERIMETER. PER
UL DESIGN CW-S-1013.
8"
C.I.P. CONC. BEAM -
SEE STRUCT.
CAULK JT., TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
BID ISSUE SUBMISSION
C U s e rs
\d a v e
\D o c u m e n ts
\E x p a n d E m e rg e n c y D e p t_
R d a k a p la n
.r v t
/1
/2
:5
:0
P
M
AS-204
WALL SECTIONS EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJK DAK
WALL SECTION
SCALE: 1/2" = 1'-0"AS-204
THRU NEW/EXISTING ENTRY LOBBY
WALL SECTION
SCALE: 1/2" = 1'-0"AS-204
SECTION @ NE BRICK/METAL PANEL TRANSITION
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20
90% CD's SUBMISSION 5.13.20
100% CD's SUBMISSION 6.26.20
FINAL CD's SUBMISSION 9.11.20
SECOND FLOOR
679' - 5 3/8"
50.1
CANOPY T.O.S. HIGH
683' - 6"
CANOPY T.O.S. LOW
681' - 5"
CANOPY T.O.S. MID
682' - 8 1/2"
/4
QUARTZ WINDOW
SILL, TYP.
CAULK, TYP.
ALUMINUM CURTAIN
WALL
(2) 2 X 4 FRTW WD.
PLATE
TWO-PIECE MTL. REGLET
COUNTER FLASHING
1'-3"
/2
/2
/8
R-7.5 RIGID INSULATLION AND
AIR/WEATHER BARRIER
SHALL BE PROVIDED @ FACE
AND UNDERSIDE OF CONC.
BEAM AS SHOWN. SUCH
SYSTEMS SHALL BE
CONTINUOUS WITH STUD
WALL SYSTEM ASSEMBLY.
FULLY LAP AND SEAM
1/2"
CAULK JT.
EXTEND ROOF MEMBRANE
SYSTEM INTO OPENING AND
UP ENTIRE VERT. FACE OF
RIGID INSULATION
SEE ROOF PLAN FOR
LOCATIONS OF TAPERED
INSULATION
GENERAL NOTE FOR
ALL CURTAIN WALL
LOCATIONS: PROVIDE
WATERPROOFING PER
MANUF. INSTRUCTIONS,
TYP.
CONT .MTL. SILL PAN (BY
C.W. SUPPLIER) FLASHING,
CAULK, TYP.
49.4 49.5
METAL PANELS
ALUM. COPING, FINISH TO
MATCH METAL PANELS
METAL PANEL SYSTEM
OVER AIR+ WEATHER RES.
BARRIER & EXTERIOR
GRADE SHEATHING ON 6"
METAL STUDS @ 16" O.C.
TWO (2) LAYERS 3/4" FRTW
PLYWOOD, SLOPED
TOWARDS ROOF
ROOF MEMBRANE ON
FRTW PLYWOOD
SHEATHING, CONT. TO
FRONT EDGE OF COPING
1'-8"
CAULK,
TYP.
MITERED CORNER
M
IN
/8
1/2"
1'-0"
CAULK @ SEAM,
TYP.
STEEL ANGLES W/STUD
CLIPS, TYP. @ TOP AND
BOTTOM OF BEAM, SEE
STRUCT.
NOTE: SECTION DETAILS ARE
TAKEN @ UNINSULATED
PORTION OF CANOPY. ROOF
MEMBRANE SYSTEM SHOWN
OVER PITCHED SHEATHING.
REFER TO ROOF PLAN AND
WALL SECTIONS FOR AREA OF
CANOPY THAT IS FULLY
INSULATED (ENTRY
VESTIBULE)
2'-10 1/2"
ANCHOR CHAIR NAILED
TO PLYWD., TYP.
CAULK @ SEAM,
TYP.
SECOND FLOOR
679' - 5 3/8"
CANOPY T.O.S. HIGH
683' - 6"
CANOPY T.O.S. LOW
681' - 5"
CANOPY T.O.S. MID
682' - 8 1/2"
5/8" GWB ON 1-5/8" MTL.
FURRING @ 16" O.C.
8" CMU ON EXISTING
BEAM, SEE STRUCT.
DWGS.
EX. FLOOR SLAB, SEE
STRUCT. DWGS.
EX. CONC. BEAM
EX. LIMESTONE
TO REMAIN
NEW AUTOMATIC
SLIDING DOOR SYSTEM
TWO-PIECE MTL. REGLET
COUNTER FLASHING
ALUMINUM CURTAIN WALL
QUARTZ WINDOW
SILL
EX. LIMESTONE SILL
CAP TO BE REMOVED
11 1/2"
SEE STRUCT. DWGS.
FOR BEAM BEARING
4' -0
CAULK INTERIOR &
EXTERIOR
NEW PTD GYP. BD.
OVER EX. FRAMING
RUN ROOF MEMBRANE UP
VERTICAL FACE OF 3" RIGID
INSULATION AND INTO NEW
CURTAIN WALL OPENING
PAINTED GYP. BD .
INTERIOR
CONT .MTL. SILL PAN (BY
C.W. SUPPLIER) FLASHING,
CAULK, TYP.
GENERAL NOTE FOR
ALL CURTAIN WALL
LOCATIONS: PROVIDE
WATERPROOFING PER
MANUF. INSTRUCTIONS,
TYP.
T/ADDITION ROOF
691' - 0 3/4"
D'
5/8" GWB ON METAL
STUD FRAMING
SUSPENDED CEILING
SYSTEM
DRYWALL TO ACOUSTICAL
TRANSITION MOLDING WITH
SHADOW REVEAL,
ARMSTRONG 7902 OR EQ.
METAL PANEL RETURN @
TOP, SLOPE 1/4" PER FOOT
FOR DRAINAGE
STUD CLIPS, TYP.
CAULK, TYP.
CAULK, TYP.
MITER CORNER
1'-4"
8"
1'-7"
2 HR RATED EDGE-OF-SLAB
FIRESTOP ASSEMBLY, TYP.
ENTIRE PERIMETER. PER UL
DESIGN CW-S-1013
FLASHING, TYP.
STUD CLIPS @
UNDERSIDE OF
BEAM, TYP. SEE
STRUCT.
CAULK @ SEAM, TYP.
CONT. ALUM. COPING OVER
FRTW WD. PLATE, TYP.
FRTW WD. BLOCKING
AS REQ'D. @
CURTAIN WALL HEAD
HEAVY DASHED
LINES INDICATE
STEEL TUBE
CONNECTION @
ROOF SLAB EDGE.
SEE STRUCT.
10" X 14" GALV. STEEL PLATE FOR
CANOPY HANGER ROD ATTACHMENT TO
BUILDING. SEE STRUCT. DWGS. PLATE
SHALL BE PAINTED TO MATCH
SURROUNDING METAL PANELS AND BE
FULLY SEALED AT PERIMETER BETWEEN
METAL PANELS
ANCHOR CHAIR, NAILED TO
TOP PLATE, TYP.
GENERAL NOTE FOR
ALL CURTAIN WALL
LOCATIONS: PROVIDE
WATERPROOFING PER
MANUF. INSTRUCTIONS,
TYP.
SECOND FLOOR
679' - 5 3/8"
CANOPY T.O.S. HIGH
683' - 6"
CANOPY T.O.S. MID
682' - 8 1/2"
1'-4"
/8
ALUMINUM STOREFRONT
SYSTEM
FLASHING, CAULK JT., TYP.
GYP. BD. RETURN
6" STUD HEADER, TYP.
CONC. FLOOR
SLAB, TYP.
MTL. FLASHING,
SEALANT, TYP. @
SILL
BRICK RETURN @
JAMBS
GALV. STEEL SHELF
ANGLE - SEE
STRUCT. DWGS. THRU-WALL WEEPS,
MIN. 24" O.C., TYP.
CAULK, TYP.
QUARTZ WINDOW
SILL, TYP.
CAULK, TYP.
ALUMINUM CURTAIN
WALL
2 X 6 FRTW WD.
PLATE
/4
(2) 2 X 4 FRTW WD.
PLATE
CONT. MTL. FLASHING
TWO-PIECE CONT. MTL.
REGLET COUNTER FLASHING
SEALANT / CAULK, TYP.
1'-3"
CIP CONC. BEAM
CAULK, TYP.
METAL FURRING INFILL
(OR FRTW BLOCKING) @
FACE OF CONC. BEAM AS
REQ'D.
/2
R-7.5 RIGID INSULATLION AND
AIR/WEATHER BARRIER
SHALL BE PROVIDED @ FACE
AND UNDERSIDE OF CONC.
BEAM AS SHOWN. SUCH
SYSTEMS SHALL BE
CONTINUOUS WITH STUD
WALL SYSTEM ASSEMBLY.
FULLY LAP AND SEAM
ROOF MEMBRANE
SYSTEM SHALL EXTEND
INTO OPENING AND RUN
UP VERTICAL FACE OF
INSULATION
BENT PLATE, SEE
STRUCT. DWGS.
ALL CANOPY STEEL
FRAMING AND METAL ROOF
DECK SHALL RECEIVE 90
MIN. FIREPROOF SPRAY
ASSEMBLY PER UL DES
P719. REFER TO UL
ASSEMBLY FOR REQUIRED
THICKNESS
STEEL DECK ANGLE
W/CLIPS TO STUDS, SEE
STRUCT.
E.1
T/ADDITION ROOF
691' - 0 3/4"
EX. CONC. BEAM
EX. LIMESTONE PANEL
WALL TO REMAIN
CONT. FIBER CANT @
HIGH POINT, TYP.
NEW STEEL SHELF
ANGLE BOLTED TO EX.
CMU BACK UP WALL -
SEE STRUCT.
RUN NEW ROOF MEMBRANE UP
FACE OF ANGLE, FULLY SEAL
ALONG ENTIRE LENGTH. WHERE
SHELF SUPPORT ANGLES DO
NOT OCCUR, GC SHALL PROVIDE
TERM. BAR @ TOP OF ROOF
MEMBRANE
HEAVY DASHED LINES
INDICATE EXISTING
LIMESTONE PANEL TO BE
REMOVED. REMOVE EX.
ANGLE ATTACHMENT
SEE STRUCT. DWGS. FOR
DOWELING INTO EX. BEAM
7 5/8"
GC SHALL RESUPPORT EX.
LIMESTONE PORTIONS TO
REMAIN AS REQ'D, AND DEVELOP
DETAILS FOR SAME WITH STONE
SUPPLIER/ENGINEERNOTE: INSULATED STUD
WALL W/SHEATHING,
AIR/WEATHER BARRIER TO
BE PROVIDED OVER HEAD
OF OPENING AS SHOWN.
MTL. STUD HEADER
SEE STRUCT. DWGS.
FOR CONC.
THICKENING OF EX.
BEAM
EX. THIRD FLOOR
691' - 2 3/4"
F
T/ADDITION ROOF
691' - 0 3/4"
TWO (2) FRTW WD. TOP
PLATES, ANCHORED TO
TOP OF EX. CMU
TWO (2) COURSES OF
EXISTING CMU BACKUP
WALL TO REMAIN FROM
DEMO
NEW ROOFING
SYSTEM ON
ADDITION
NEW EPDM ROOF
MEMBRANE SHALL LAP
OVER EXISTING ROOF
MEMBRANE BELOW NEW
ALUM. COPING
EX.CONCRETE
PEDESTAL SYSTEM
OVER PVC ROOFING
MEMBRANE TO
REMAIN.
TEMPORARILY
REMOVE PAVERS AS
REQUIRED TO
ACHIEVE ROOFING
SYSTEM LAP AS
SHOWN, REPLACE
UPON COMPLETION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
AT
E
I
T C
J.
O
O
FO
H
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
BID ISSUE SUBMISSION
C U s e rs
\d a v e
\D o c u m e n ts
\E x p a n d E m e rg e n c y D e p t_
R d a k a p la n
.r v t
/1
/2
:2
:4
P
M
AS-403
ENLARGED SECTION DETAILS EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJK DAK
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH ENTRY CANOPY AT SECOND FLOOR SLAB
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH ENTRY CANOPY AT EXTERIOR
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH MAIN LOBBY AT EXISTING BEAM
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH SOUTH CANOPY AT TENSION CABLE BRACKET
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH BOTTOM OF SOUTH CANOPY
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
SECTION THROUGH MAIN LOBBY PARAPET
SECTION DETAIL
SCALE: 1 1/2" = 1'-0"AS-403
NEW/EXISTING ROOF CONNECTION
Revisions: Date:
SCHEM. DESIGN SUBMISSION 10.21.19
DESIGN DEV. SUBMISSION 12.9.19
65% CD's SUBMISSION 1.28.20
90% CD's SUBMISSION 5.13.20
100% CD's SUBMISSION 6.26.20
FINAL CD's SUBMISSION 9.11.20
@ COL.
SIM
@ COL.
@ COL.
@ COL.
TYP
GRADE BEAM NOTES:
1. BOTTOM REINFORCEMENT TO LAP AT CENTERLINE OF SUPPORTS AND
TOP REINFORCEMENT TO LAP AT MIDDLE THIRD OF GRADE BEAM SPAN.
2. LAP SPLICES, SEE GENERAL NOTES.
3. TOP REINFORCEMENT TO EXTEND TO ENDS OF DISCONTINUOUS GRADE
BEAMS AND HOOK 1'-0" MINIMUM.
4. PROVIDE CORNER BARS TOP AND BOTTOM TO MATCH SIZE AND QUALITY
OF GRADE BEAM REINFORCEMENT.
5. LOCATE CONSTRUCTION JOINTS IN MIDDLE THIRD OF SPAN.
6. DENOTES SEE SECTION FOR BAR REINFORCING LOCATION.
GRADE BEAM SCHEDULE
MARK
SIZE REINFORCING
STIRRUPS
WIDTH x DEPTH BOTTOM TOP
GB36x36-1 36"x36" (8) - #6 (8) - #6 #4 @ 12"O.C.
GB36x42-1 36"x42" (8) - #8 (8) - #8 #4 @ 12"O.C.
GB60x36-1 60"x36" (8) - #6 (11) - #10 (2) - #4 @ 2"O.C. &
(2) #4 @ 15"O.C. FOR REMAINDER
GB48x36-1 48"x36" (5) - #6 (9) - #8 (2) - #4 @ 6"O.C.
GB68x38/50 68"x38"/50" (10) - #6 (14) - #10 (2) - #4 @ 2"O.C. CANT'L ENDS
#4 @ 15" O.C. CENTER SPAN
REMARKS
SEE SECT. 4 ON
SHEET S-5.2
GB36x42-2 36"x42" (10) - #8 (10) - #8 #4 @ 10"O.C.
GB48x42-2 48"x42" (10) - #8 (10) - #8 #4 @ 10"O.C.
GB68x42-1 68"x42" (16) - #6 (16) - #6 (2) - #4 @ 18"O.C.
GB24x36-1 24"x36" (5) - #7 #4 @ 16"O.C.
GB16x39-1 16"x39" (4) - #7 #4 @ 16"O.C.
(5) - #7
(4) - #7
GB60x36/42 60"x36"/42" (10) - #6 (14) - #10 (2) - #4 @ 2"O.C. CANT'L ENDS
#4 @ 15" O.C. CENTER SPAN
TYPICAL DRILLED PIER DETAIL
VERT. REINFORCING
SEE SCHEDULE
TIE REINFORCING
SEE SCHEDULE
TEMPORARY STEEL CASING
REQUIRED FULL DEPTH OF
DRILLED PIER. REFER TO
GEOTECHNICAL REPORT
SEE GENERAL NOTES
BAR CLEARANCE
DOUBLE PERIMETER DRAIN AND UNDERSLAB DRAINAGE
SYSTEM. 4"Ø PERF. SCH.40 PVC AT 12'-0" O.C. EA. WAY,
WRAPPED IN GEO-FABRIC AND PLACED IN A 12"x18"
TRENCH BACK FILLED WITH STONE BELOW THE BOTTOM
OF 6" SUB-BASE STONE. DRAIN PIPE SHALL BE SLOPED,
COORDINATE SLOPE W/ PLUMBING. SEE PLUMBING
DRAWING SHEET P-0.2-1
SAWCUT CONTROL JOINTS
TYP. SEE TYP. DETAIL ON
SHEET S-5.0 (TYP.)
FOR BIDDING PURPOSES, CONTRACTOR SHALL
INCLUDE A SEPARATE LINE ITEM FOR SHEET
PILING REQUIREMENTS ON 4-SIDES OF THE
BUILDING AND DEWATERING OPERATIONS, TO
ADDRESS A POTENTIAL HIGH WATER TABLE
ABOVE THE BASEMENT SLAB ELEVATION.
BIDDERS MUST REVIEW THE GEOTECHNICAL
REPORT PROVIDED IN THE SPECIFICATIONS AND
PLAN FOR SHEET PILING AND DEWATERING
OPERATIONS BASED ON CONDITIONS
IDENTIFIED WITHIN.
G
F F
E.1
5352515049 49.4
F.4
51.05
E'
E'
D'
D'
D.6
E.9 E.9
G.5
D.7
D.9
E
54A
'-8
'-0
'-1
1" 9'
-7
'-6
/2
2' -4
"2 '-6
1'-11" 21'-0"
27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 22'-11"
4'-8" 22'-4"14'-8" 2"
'-9
2' -6
'-8
/2
'-1
/2
'-6
/8
'-2
/8
(E) 36"Ø 650'-3" - 621'-0"
(E) 48"Ø 650'-3" - 621'-0"
(E ) 4
8"Ø
0'-
3"
- 62
1'- 0" (E
) 5 4"Ø
0'-
3"
- 62
1'- 0"
(E ) 3
6"Ø
8'-
0"
- 62
1'- 0" (E
) 5 4"Ø
8'-
0"
- 62
1'- 0" (E) 36"Ø
646'-6" - 621'-0"
(E) 60"Ø 646'-6" - 621'-0"
(E) 54"Ø 646'-6" - 621'-0"
(E) 54"Ø 646'-6" - 621'-0"
(E ) 3
6"Ø
0'-
3"
- 62
1'- 0"
(E) 36"Ø 663'-4" - 622'-0"
(E) 36"Ø 663'-4" - 622'-0"
(E ) 3
6"Ø
8'-
0"
1'-
0"
(E) 36"Ø 663'-4" - 622'-0"
EXISTING
CONCRETE SHEAR
WALL TO REMAIN
(E) 6"± SLAB ON GRADE
6x6-W2.9xW2.9 W.W.F
(T/SLAB EL. = 649.5' USGS)
(E) 1'-2"± CONC WALL
TO REMAIN BELOW
(E) 1'-2"± CONC WALL
TO REMAIN BELOW
(E) 16"± HYDRAULIC SLAB
(T/SLAB EL. = 647.33' USGS)
(E) 5"± SLAB ON GRADE
6x6-W1.4xW1.4 W.W.F
(T/SLAB EL. = 653.25' USGS)
CONTRACTOR TO PROVIDE TEMPORARY RETENTION
SYSTEM AS REQUIRED TO AVOID UNDERMINING THE
EXISTING FOUNDATION / SLABS TO REMAIN.
TEMPORARY RETENTION SYSTEM SHALL NOT
INTERFERE WITH NEW OR EXISTING CONSTRUCTION.
AFTER NEW CONSTRUCTION IS COMPLETE,
CONTRACTOR SHALL CUT AND REMOVE THE
TEMPORARY RETENTION SYSTEM TO -8'-0" BELOW
GRADE, REMAINDER CAN REMAIN IN PLACE.
8" NON-LOAD BEARING CMU
WALL. SEE SECTIN FOR ADD'L.
INFO.
54.7
54.7
GB36x36-1
G B x4
2-
GB48x36
G B x3
6/ 42G
B x3 6/
GB36x36-1
DP3.5
DP3.5
DP4.5
DP4.0
DP4.5
DP4.5
DP5.0
DP5.0
DP4.5
DP2.5
DP5.0
DP4.5DP4.0
DP4.0
DP4.0
DP3.5
DP4.5
DP3.5
DP2.5
DP2.5
DP3.5
DP4.0
DP5.5
DP5.5
3'-0" 9'-6"
DP5.0
(-4 '-1
0")
(-4 '-1
0")
(-4 '-1
0")
(-4'-4")
(-4'-4")
(-1 '-4
(-4 '-1
0")
(-4 '-1
0")
(-4'-10")
(-4'-4")
(-5 '-8
(-4'-10")
(-4 '-4
(-4'-4")
(-4'-4")
(-4'-10")
(-4'-10")
(-4 '-1
0")
(-4 '-1
0")
(-4 '-1
0")
DP5.0
(-2 '-8
S-5.2
S-5.2
S-5.2
S-5.2
S-5.2
S-5.2
S-5.2
S-5.2
S-5.2
GB36x42-1
CL OF
DRILLED PIER
CL OF
DRILLED PIER
10.00° 28'-9"
'-1
0"
'-6
'-5
(E) 36"Ø 663'-4" -
622'-0"
49.5
4"
(-4 '-4
4' -0
C.J.
C.J.
4' -0
C.J.
4' -0
C .J.
6'-0"
C .J.
C.J.
C.J.
4' -0
5'
-1
5/ 8"
6'-0"
PILE CAP DETPH TO
MATCH GRADE BEAM
DEPTH, TYP. SEE
SECTIONS.
NEW MECH. EQUIPMENT ON
CONCRETE HOUSEKEEPING PAD
(TYP). SEE TYPICAL EQUIPMENT
PAD DETAIL ON SHEET S-5.0. SEE
MECH. & ARCH. DRAWINGS FOR
EXTENT (TYP).
F.D.
F.D.
50.1
(-4'-10")
12" MIN.14" MIN.
M
IN
"M
IN
EXISTING
DRILLED PIER
TO REMAIN
R E
TA
IN
IN
G
W A L
L 1'
-2 " C
O N
C
4' -0
2'
-1
WALL
1'-2" CONC.
DRILLED PIER
10 3/4" CL OF
WALL
1'-2" CONC.
5"
WALL
1'-2" CONC.
1'-7"
W
ALL
1'-2" C O
N C
W
ALL
1'-2" C O
N C
5"
1'-7"
8"
10'-5"
W
ALL
2'-10" C O
N C
1'-0"
W
ALL
1'-10" C O
N C
WALL
1'-2" CONC. 5"
1'-7"
WALL
2'-2" CONC.
W
AL
L 1'
-2 " C
O N
C
WALL
1'-2" CONC.
WALL
1'-2" CONC
SEE ARCH FOR
SEGEMENT RADIUS
C .J.
S-5.2
(E ) 3
6"Ø
8'-
0"
1'-
0"
(E ) 3
6"Ø
8'-
0"
2'-
0"
1'-2"
(E ) 3
6"Ø
3'-
0"
2'-
0"
(E ) 3
6"Ø
3'-
0"
2'-
0"
(-4'-10")
(-4'-10")
GB36x36-1GB36x36-11
2'-10"
11"
S-5.2
S-5.2 A
S-5.1
S-5.1
WALL
1'-6" CONC.
W
ALL
1'-6" C O
N C
CL OF GB68x42
= CL OF COL.
NEW FLOOR SLAB INFILL FOR
NEW UNDERGROUND PLUMBING.
SEE SECTION 1 ON SHEET S-5.0.
SEE ARCH & PLUMBING DRAWINGS
FOR EXTENTS.
NEW 6" SAN. LINE TO
CONNECT TO (E) LINE
G.C. TO COORD. W/
MECH. CONTRACTOR
G B x3
6/
S-5.0
F.S.
6' -8
CL OF
DRILLED PIER
GB36x42-1
G B x4
2-
G B x4
2-
G B x4
2-
50" DEEP GB5'-0"
GB68x38/50
GB60x36/42
THICKEN BOT. OF
GRADE BEAM
THICKEN BOT. OF
GRADE BEAM
GB36x42-2
GB36x42-1
GB36x42-1
G B x4
2-
G B x4
2-
G B x4
2-
S-5.1
5'-0" 42" DEEP GB
(-4 '-4
CL OF
DRILLED PIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
ADDENDUM 2
C :\R ev it
Lo ca ls \2
9-
_S tru ct _R
_n m ay be rry jo ne s.
rv t 4/
/2
3:
:1
PM
S-1.0
FOUNDATION PLAN EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 TBA TBA
NOTES:
• FLOOR CONSTRUCTION: 6" CONCRETE SLAB ON GRADE WITH#4 BARS @ 16" O.C EA. WAY (CENTERED IN SLAB). PROVIDE 15 MIL VAPOR BARRIER AND 6" AASHTO #57 OR EQUIVALENT LAYER OF GRANULAR FILL BELOW SLAB
(UNO). PROVIDE UNDER SLAB DRAINAGE COORD. WITH MECH. DRAWINGS AND SEE SECTIONS.
• TOP OF SLAB ELEVATION = "BASEMENT LEVEL", SEE ELEVATION LEGEND. CONTRACTOR TO VERIFY FINAL FLOOR ELEVATION MATCHED THE EXISTING UPPER BASEMENT ADJACENT BUILDING FLOOR ELEVATION. NOTIFY E.O.R. AND
ARCH. OF RECORD OF ANY DISCRAPANCIES.
• TOP OF INTERIOR DRILLED PIER ELEVATION = SEE PLAN REFERENCED FROM "BASEMENT LEVEL", SEE ELEVATION
LEGEND.
• TOP OF EXTERIOR DRILLED PIER ELEVATION = SEE PLAN REFERENCED FROM "BASEMENT LEVEL", SEE ELEVATION
LEGEND.
• TOP OF INTERIOR AND EXTERIOR GRADE BEAM ELEVATION = (-1'-4") UNO.
• CONTINUOUS GRADE BEAMS ARE MARKED THUS: GBX.XxX.X-X
(TOP OF GB EL.)
• PROVIDE (2) #4x3'-0" LONG AT ALL REENTRANT CORNERS.
• SEE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT AND FINISH OF SLAB ON GRADE AND
ANY FLOOR DEPRESSIONS, UNDERFLOOR CONDUITS, DRAINS, ETC.
• SEE SHEET S-0.1, S-0.2, & S-03 FOR GENERAL NOTES.
• SEE SHEET S-5.0 FOR TYPICAL DETAILS.
• DPX.X DENOTES DRILLED CONCRETE PIER. SEE DRILLED PIER SCHEDULE ON THIS SHEET.
• GBX.XxX.X-X DENOTES GRADE BEAM. SEE GRADE BEAM SCHEDULE ON THIS SHEET.
• FOUNDATIONS ADJACENT TO EXISTING STRUCTURES SHALL BEAR ON UNDISTURBED SOIL AT THE SAME ELEVATION
OF THE EXISTING FOOTINGS.
• (E) DENOTES EXISTING CONSTRUCTION.
• DENOTES DOWEL NEW CONC. WALL INTO EXISTING CONC. WALL WITH #5 DOWELS @ 6" O.C. PROVIDE CONT.
SWELLING WATER STOP OR EQUAL BETWEEN NEW AND EXISTING CONC. WALLS. PROVIDE SIKA SWELL S-2 POLYURETHANE , EXTRUDABLE SWELLING WATER STOP OR EQUAL (CONTRACTOR SHALL SUBMIT PRODUCT DATA).
• DENOTES SUMP PIT, SEE PLUMBING DRAWINGS SHEET P-0.2-1.
• DENOTES AIR HANDLER UNIT (AHU) SUMP PIT. SEE DETAIL ON SHEET S-5.0. G.C. TO COORDINATE EXTENT
WITH MECH. CONTRACTOR.
• DENOTES EXISTING DRILL PIER TO BE REMOVED 3'-0" BELOW BOTTOM OF NEW GRADE BEAM ELEVATION.
• DENOTES NEW DOOR OPENING THRU EXISTING 14" THICK CONCRETE BASEMENT WALL. SEE PLAN ON SHEET
S-2.0 FOR ADDITIONAL REQUIREMENTS.
• DENOTES EXISTING DRILLED PIER TO REMAIN AND NEW CONCRETE WALLS TO BE PLACED AROUND DRILLED PIER AS SHOWN ON PLAN. DURING EXCAVATION EARTH SURROUNDING EXISTING DRILLED PIER SHALL BE REMOVED IN 3'-0" MAX. LIFTS. IF EARTH REMOVAL EXCEEDS THE 3'-0" MAX., THE EXISTING DRILLED PIER SHALL BE TEMPORARY
BRACED. BRACING SHALL BE SUPPLIED BY A SHORING CONTRACTORS ENGINEER.
• C.J. DENOTES VERTICAL CONSTRUCTION JOINT WITHIN BASEMENT WALL. SEE TYPICAL DETAIL ON SHEET S-5.0.
N SCALE: 1/8" = 1'-0"
FOUNDATION PLAN
DRILLED PIER SCHEDULE 50,000psf END BRG. (25 TONS)
MARK
SHAFT
SIZE Ø
VERTICAL REINFORCING
HORIZONTAL TIES
QUANTITY &
SIZE ALLOWABLE LOADS (Kips)
DP2.5 30"
DP3.5 42" (7) #9 481 #3 @ 18" O.C.
DP4.0 48" (9) #10 628 #4 @ 18" O.C.
DP4.5 54" (9) #10 795 #4 @ 18" O.C.
DP5.0 60" (9) #11 982 #4 @ 18" O.C.
DP5.5 66" (11) #11 1188 #4 @ 18" O.C.
ELEVATION LEGEND
LEVEL DESIGNATION ELEVATION (UNO)
Project Datum
ROOF (FUTURE THIRD FLOOR) 691' - 0 3/4"
TOP OF STEEL @ CANOPY 683' - 6"
SECOND FLOOR 679' - 5 3/8"
FIRST FLOOR 667' - 0" ●
BASEMENT LEVEL 653' - 3"
NOTES:
• ELEVATIONS ON PLAN MAY VARY FROM ELEVATIONS SHOWN IN
THE ELEVATION LEGEND. SEE PLAN FOR SPECIFIC ELEVATION
VARIATIONS.
• ● DENOTES THE LEVEL THAT IS THE PROJECT DATUM.
DRILLED PIER NOTES:
• SEE TYPICAL DRILLED PIER DETAIL ON THIS SHEET.
• FOR DRILLED PIER TESTING, SEE SPECIFICATIONS.
CONTRACTOR TO REMOVE EXISTING
CONCRETE FOUNDATIONS, FOUNDATION
WALLS, ETC. AS INDICATED WITHIN THE
ARCHITECTURAL DEMO PLANS.
Revisions: Date:
DESIGN DEV. SUBMISSION 12.9.19
SCHEM. DESIGN SUBMISSION 10.21.19
65% CD's SUBMISSION 1.28.20 90% CD's SUBMISSION 5.13.20 100% CD's SUBMISSION 6.26.20 FINAL CD's SUBMISSION 9.11.20
FE
FEC
FE
C
T H
X-H
PS
X-H
PC
Ex.
HWS
/R
STA
CKE
D
ON
WAL
L.
TIE
NEW
P.C
. IN
TO
EXIS
TING
8"
(PR
OST
HET
CSSTO
RAG
EC2
(80
C1 (330
STO
RAG
E
(RE
H.
MED
. S
VC)
X-1
X-1
CRA
WL
SPA
CE
"x
14"x 12"
50 50.3 51 52 53 54 55
E
E.1
F
G
H
H1
J
HWP-1
HWP-2
VFD-HWP-1
VFD-HWP-2
HX-2 HX-1 EXT-1
6" CWS
6" CWR
3" SVD
3" HWR
3" HWS
CP-1
2" C
PD
6" HPS
AS-1
3" H
W S3"
H W
R
3" S
VD
3" LPS10
" L
P S
4" L
P S
4" LPS
4" C
W S
4" C
W R
3/ 4"
H W
R
3/ 4"
H W
S
3.2
1/
2" L
PC
2"
L
PS
1/
2" C
W R
1/
2" C
W S
2" L
PC
3" L
P S
2 1/2" LPS
1 1/2" LPS
3" LPC
FM
FM
AC-48
AC-49
2" L
P S
BAC285
BAC284
BAC281 BAC282
BAC280
BAC274
BAC283
BAC253
BAC250B
BAC254 BAC255
BAC252
BAC251
BAC250
BAC256
BAC328
BA109C
BS3
BA109
BAC329
BAC330
BAC275
BAC260B
BAC272
BAC270C
BAC270B
BAC270A
BAC269
BAC260A
BAC271
BAC273
BAC260
BAC261
BAC260C
BAC262
BAC298A
BA150A
BAC264
BAC268
BAC265
BAC266
BA150B
BA148 BA149 BAC241
BS4
BA152
BA151
BA153
BA150C
BA152A
BAC241A
BA153A
1-H-AC-48
2" V
CODED NOTES
1. END SUCTION PUMP, SEE DETAIL (TYP.). MOUNT ON 4" EQUIPMENT PAD PROVIDED BY M.C.
PER DETAILS.
2. VARIABLE FREQUENCY DRIVE, MOUNT TO WALL USINGG STAINLESS STEEL UNI-STRUT AND
HARDWARE (TYP.).
3. STEAM TO HOT WATER HEAT EXCHANGER, SEE DETAIL (TYP.). MOUNT ON 4" EQUIPMENT PAD
PROVIDED BY M.C. PER DETAILS.
4. CONDENSATE PUMP/RECEIVER, SEE DETAIL (TYP.).
5. STEAM PRESSURE REDUCING STATION TO BE RACKED ON WALL. SEE "STEAM PRESSURE
REDUCING STATION DETAIL". OUTLET PRESSURE SHALL BE 15 PSI.
6. ROUTE SAFETY VENT PIPING TO STEAM PRESSURE REDUCING STATION.
7. HEATING WATER EXPANSION TANK. MOUNT ON 4" EQUIPMENT PAD PROVIDED BY M.C. PER
DETAILS.
8. MINIMUM 10 GALLON VERTICAL FLASH TANK. EXTEND 3/4" HPC FROM PRV STATION TO FLASH TANK INLET. ROUTE 2" FLASH STEAM FOR TIE IN TO LPS MAIN. PROVIDE CHECK VALVE IN PIPING
PRIOR TO TIE-IN.
9. INSTALL MECHANICAL SLEEVE SEAL AT WALL PENETRATION (TYP. FOR 4).
10. AIR AND DIRT SEPARATOR.
11. 6" CWS/CWR, 6" HPS, AND 2" CPD TO BE ROUTED BELOW GRADE TO EXISTING SUB-BASEMENT FOR TIE IN TO EXISTING UTILITY MAINS. BURIED PIPING SHALL BE FACTORY FABRICATED DOUBLE
WALL PIPING. COORDINATE INVERT OF PIPING TO AVOID EXISTING GRADE BEAMS. ALL WALL
PENETRATIONS SHALL BE PROVIDED WITH MECHANCIAL SLEEVE SEALS.
12. ROUTE 2-1/2” LPS TO VIFB HEATING COIL. PROVIDE CONNECTIONS, TRAPS, VALVES, ETC. PER
DETAIL.
13. ROUTE 1-1/2” LPS TO STEAM HUMIDIFIER. PROVIDE CONNECTIONS, TRAPS, VALVES, ETC. PER
DETAIL. EXTEND DRAIN PIPING TO NEAREST FLOOR DRAIN.
14. INSTALL NEW PUMPING TRAP T-2 IN 24"X36"X18" DEEP PIT. PIT BY OTHERS. 3"X36" LONG RECEIVER SHALL BE MOUNTED ON FLOOR LEVEL. EXTEND HEATING COIL AND HUMIDIFER DRAIN TO RECEIVER INLETS. ROUTE 2” MPC FROM PUMP TO EXISTING MAIN INLET HEADER AT FLASH TANK IN EXISTING BUILDING MECHANICAL ROOM. EXTEND MPS FROM MAIN TO PUMP TRAP INLET.
INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS..
15. ROUTE 4” CWS/CWR TO CHILLED WATER COIL. PROVIDE CONNECTIONS, TRAPS, VALVES, ETC.
PER DETAIL.
16. ROUTE 3” HWS/HWR AND 3" SVD PIPING UP WITHIN SHAFT TO FLOOR ABOVE.
17. ROUTE 2-1/2” CWS/CWR TO CHILLED WATER COIL. PROVIDE CONNECTIONS, TRAPS, VALVES, ETC. PER DETAIL.
18. ROUTE 2” LPS TO VIFB HEATING COIL. PROVIDE CONNECTIONS, TRAPS, VALVES, ETC. PER
DETAIL.
19. INSTALL NEW PUMPING TRAP T-2 IN 24"X36"X18" DEEP PIT. PIT BY OTHERS. 3"X36" LONG RECEIVER SHALL BE MOUNTED ON FLOOR LEVEL. EXTEND HEATING COIL AND HUMIDIFER DRAIN TO RECEIVER INLETS. ROUTE 1-1/2” MPC FROM PUMP TO EXISTING MAIN INLET HEADER AT FLASH TANK IN EXISTING BUILDING MECHANICAL ROOM. EXTEND MPS FROM MAIN TO PUMP TRAP INLET.
INSTALL PER MANUFACTURER INSTALLATION INSTRUCTIONS.
20. INSTALL NEW VAV BOX. EXTEND ¾” HWS/HWR TO VAV BOX. PROVIDE VALVES, CONNECTIONS
ETC. PER DETAIL.
21. NEW CHILLED WATER FLOW METER. TIE OUTPUTS IN TO EXISTING BAS. REFER TO
TEMPERATURE CONTROL DRAWINGS FOR MORE DETAILED INFORMATION.
22. NEW RS/RL PIPING DOWN FROM ABOVE. TIE IN TO EXISTING RS/RL PIPING SERVING AC-50.
COORDINATE ALL REQUIRED SHUTDOWNS AND REWORK OF PIPING AS REQUIRED TO MINIMAZE
SHUTDOWN OF AC-50 AS MUCH AS POSSIBLE.
23. SEE SHEET H-B.2-1 FOR CONTINUATION.
24. PLUMBING DECONTAMINATION TANK. SHOWN FOR COORDINATION PURPOSES ONLY. REFER
TO PLUBMING DRAWINGS FOR ADDITIONAL INFORMATION.
PLAN NOTES
A. SEE SHEET H-001 FOR GENERAL NOTES AND SYMBOL LEGEND.
B. SEE SHEETS H-002 THROUGH H-004 FOR HVAC DETAILS.
C. SEE SHEETS H-005 THROUGH H-007 FOR TEMPERATURE CONTROLS.
D. SEE SHEETS H-008 AND H-009 FOR HVAC SCHEDULES.
E. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING CONSTRUCTION. COORDINATE EXACT
HEIGHT AND MOUNTING OF DUCTWORK AND PIPING TO AVOID CONFLICTS WITH OTHER UTILITIES
AND CEILINGS.
F. ALL DUCTWORK AND PIPING SHOWN THIS SHEET IS LOCATED IN CEILING SPACE UNLESS
NOTED OTHERWISE.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
HIO
P R O F E
SS IO N
AL EN
G
IN
E E R
REG IST E R
ED
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: NICK CARROZZA
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
1468 WEST 9TH STREET #400
CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
CIVIL/MECH./ELEC./PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
LANDSCAPE ARCHITECTURE:
JAMES S. MCKNIGHT
P.O. BOX 14158
CLEVELAND, OH 44114
P. 216.952.2408
HAZARDOUS MATERIALS
ASSESSMENT:
STEPHEN J. SEBESTA &
ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
BID ISSUE SUBMISSION
C :\U se rs
\S Pa vl ik
\D oc um en ts \1
_M
EP
_C
EN
TR
AL
F
IL
E_ sp av lik sb m ce
.c om
.rv t
4/
/2
8:
:4
AM
H-0.2-1
BASEMENT LEVEL PHASE I HVAC PIPING
IMPROVEMENT PLAN
EMERGENCY DEPARTMENT
EXPANSION
10701 EAST BLVD. CLEVELAND, OHIO
541-370
2.9.21 CJS SRP2.9.21
N 1/8" = 1'-0"
BASEMENT LEVEL PHASE I HVAC PIPING IMPROVEMENT PLAN
ROOM LEGEND
Number Name
BA109 Mechanical Room BA109C Office BA148 Electrical BA149 TeleComm
BA150A Corridor BA150B Corridor BA150C Corridor BA151 Main Electrical Room BA152 Pharmacy Drug Cache
BA152A Secure Storage BA153 Mechanical Room
BA153A Relief Areawell
BAC241 HVAC
BAC241A Outside Air Enclosure BAC250 Waiting
BAC250B Passage BAC251 Triage BAC252 Exam BAC253 Exam BAC254 Exam BAC255 Exam BAC256 Records BAC260 Reception/ Waiting
BAC260A Passage BAC260B Passage BAC260C Passage BAC261 Regulatory/ Fiscal Office BAC262 2 Person Office BAC264 Storage BAC265 4 Person Office BAC266 IT Work Offices BAC268 Copy/ Work Passage BAC269 2 Person Office
BAC270A Break Area/ Pantry BAC270B Collaboration Area BAC270C Open Student Offices BAC271 Director Office BAC272 Office BAC273 Office BAC274 2 Person Office BAC275 2 Person Office BAC280…