These documents are electrical one-line diagrams for a U.S. Department of Veterans Affairs (VA) construction project located in Vancouver, Washington. The diagrams detail the existing and revised electrical distribution systems for multiple buildings, showing the interconnections between various electrical equipment such as transformers, switchboards, panel boards, and circuit breakers. The drawings include detailed technical specifications for electrical components, with size and magnetic properties noted for different equipment like Square D breakers, Cutler Hammer devices, and busway systems. The electrical system appears to serve multiple building functions including lighting, power distribution, elevators, HVAC systems, and emergency backup power, with voltage levels ranging from low to medium voltage configurations. The diagrams are part of a design-build project for a VA facilities improvement initiative, prepared by an architectural and engineering consulting team.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(013EP101)

7 MV TRANSFORMER SHALL HAVE THE FOLLOWING

CHARACTERISTICS:

- PRIMARY SELECTIVITY AND DISCONNECT.

- PRIMARY FUSES PER MANUFACTURER.

- PROVIDE GROUND ROD AND GROUNDING CONDUCTOR

BONDING WITHIN XFMR FOOTPRINT PER NEC.

3 MV TRANSFORMER SHALL HAVE THE FOLLOWING

CHARACTERISTICS:

- PRIMARY SELECTIVITY AND DISCONNECT.

- PRIMARY FUSES PER MANUFACTURER.

- PROVIDE GROUND ROD AND GROUNDING CONDUCTOR

BONDING WITHIN XFMR FOOTPRINT PER NEC.

012-P-01

DPMSPD

90A 3P

SPD

60A 3P

WEATHERPROOF SOUND

PROVIDE GENERATOR AS INDICATED TO REPLACE EXISTING

GENERATOR SERVING BUILDINGS 01 AND 11. ALL

ASSOCIATED POWER FEEDERS AND CONTROLS SHALL BE

REPLACED AS REQUIRED. REFERENCE ONE-LINE DIAGRAM

ON SHEET 001ED603 AND ENLARGED PLAN ON SHEET

001EP401d FOR ADDITIONAL INFORMATION. REFERENCE

SPECIFICATION 26 32 13 ENGINE GENERATORS FOR

ADDITIONAL INFORMATION.

DPM 02-PMP-09(DP9A/1) 3

02-

DPM

SPD

60A 3P

CONTINUE FROM PMT-02 SEC

SHEET EP602

3 7 5 012-P-01

(013EP101)