FROM TO QTY SIZE (QTY) & SIZE GROUND

SIZE

018-P-01 PANELBOARD "18-2B1 SECT 1/2" SWITCHBOARD "18-2SDS2" PANELBOARD "18-2B1 SECT 1/2" 1 4" (4) 600 kcmil 3 AWG - 018-P-02 PANELBOARD "18-2A1 SECT 1/2" SWITCHBOARD "18-2SDS1" PANELBOARD "18-2A1 SECT 1/2" 2 2" (4) 3/0 AWG 3 AWG - 018-P-03 PANELBOARD "18-2A2 SECT 1/2" SWITCHBOARD "18-2SDS1" PANELBOARD "18-2A2 SECT 1/2" 2 EXIST. (4) 3/0 AWG 3 AWG 2

018-G-01 SERVICE EQUIPMENT BOND PANEL "4MDS" GROUND ROD 1 - - 3/0 AWG 1

018-G-02 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -

018-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1

NOTE(S):

1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.

2. EXISTING RACEWAY SHALL BE REUSED.

BLDG 18 GROUNDING - CONDUIT AND WIRE SCHEDULE

CONDUIT

TAG SERVICE

ROUTING CONDUIT CONDUCTORS

NOTES