Attachment 11-648-20-116 Drawings 212-223.pdf

PDF 13 MB Posted

Attached to
Z2DA--CON 648-20-116 Correct Electrical FCA Deficiencies Bldgs. /Site (Vancouver)
Solicitation number
36C26026R0040
Issued by

About this file

This document contains a series of electrical schedule drawings for the U.S. Department of Veterans Affairs (VA) located in Vancouver, WA. The drawings are part of a design-build project and include detailed electrical panel and switchboard schedules for multiple buildings (Buildings 11, 13, 14, and 15). Each schedule provides comprehensive information about electrical systems, including voltage, bus ratings, main circuit breakers, circuit descriptions, load types, and spare circuit capacity. The documents are technical electrical engineering drawings prepared by a consulting discipline for the Office of Construction and Facilities Management, showing existing and revised electrical infrastructure configurations across different building locations.

The electrical schedules cover various panel types such as Motor Control Centers (MCCs), switchboards, and panelboards, with detailed breakdowns of circuit configurations, load types, and electrical demand factors. Each drawing includes specific technical details like voltage (208/120 Wye), amperage ratings, short circuit interruption (AIC) ratings, and circuit-level information including descriptions for lighting, receptacles, mechanical equipment, and spare circuits. The drawings are part of a comprehensive electrical system documentation set for a VA facility renovation or upgrade project, providing precise technical specifications for electrical infrastructure across multiple buildings.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FROM TO QTY SIZE (QTY) & SIZE GROUND

SIZE

013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -

013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -

013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -

013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1

013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -

NOTES

BLDG 013 - CONDUIT AND WIRE SCHEDULE

CONDUIT

TAG SERVICE

ROUTING CONDUIT CONDUCTORS

NOTE(S):

1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.

FROM TO QTY SIZE (QTY) & SIZE GROUND

SIZE

013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -

13-C-01 PHOTOCELL SITE LIGHTING CONTACTOR PHOTOCELL 1 1" (2) 12 AWG (1) 12 AWG

013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -

013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -

013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1

013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -

NOTES

BLDG 013 - CONDUIT AND WIRE SCHEDULE

CONDUIT

TAG SERVICE

ROUTING CONDUIT CONDUCTORS

NOTE(S):

1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.

Location: BLDG 14, RM 112 Volts: 208/120 Wye A.I.C Rating: 22k Supply From: "DP-7/1" Phases: 3 Bus Rating: 225A

Mounting: Surface Wires 4 Main Circuit Breaker: 200A Enclosure: Type 1

CKT Trip Poles Poles Trip 1 20 A 1 0 0 1 20 A 2 3 20 A 1 0 0 1 20 A 4 5 20 A 1 0 0 2 15A 6 7 20 A 1 0 0 '' '' 8 9 20 A 1 0 0 2 20 A 10

11 20 A 2 0 0 " " 12 13 " " 0 0 2 20 A 14 15 20 A 1 0 0 " " 16 17 20 A 1 0 0 1 20 A 18 19 20 A 1 0 0 1 20 A 20 21 20 A 1 0 0 1 20 A 22 23 20 A 1 0 0 1 20 A 24 25 20 A 1 0 0 1 20 A 26 27 20 A 1 0 0 2 20 A 28 29 20 A 1 0 0 " " 30 31 20 A 1 0 0 2 30 A 32 33 20 A 1 0 0 " " 34 35 20 A 1 0 0 1 20 A 36 37 20 A 1 0 0 1 20 A 38 39 20 A 1 0 0 2 30 A 40 41 20 A 1 0 0 " " 42 43 20 A 1 0 0 1 20 A 44 45 20 A 1 0 0 1 20 A 46 47 20 A 1 0 0 1 20 A 48 49 20 A 1 0 100 3 30 A 50 51 20 A 1 0 100 " " 52 53 20 A 1 0 100 " " 54

SPARE SURGE PROTECTION DEVICE

SPARE "

SPARE "

SPARE SPARE

SPARE SPARE

SPARE SPARE

RECEPT RM 108 CONDENSATE PUMP

LIGHTS MEZZAINE RTU HEAT

GYM EXHAUST FANS (OFF) "

LIGHTS UPPER LEVEL SPARE

RECEPT UPPER LEVEL "

RECEPT LOWER LEVEL RM 108 AC / RECEPT

SCOREBOARD LOCKER AREA EXHAUST FANS

LIGHTS MAIN LEVEL EAST WALL HEATER SOUTH STORAGE

LIGHTS MAIN LEVEL NORTH "

EXIT LIGHTS HEAT DOWNSTAIRS WEST (OFF)

GYM RECEPT HEAT DOWNSTAIRS EAST

GYM RECEPT FIRE ALARM PANEL

" GYM LIGHTS

EXHAUST FAN - MECHANICAL RM "

RECEPT MEACHNICAL RM HEAT UPSTAIRS

WALL HEATER NORTH STORAGE RM "

CIRCUIT DESCRIPTION

WATER COOLER - WATER HEATER GYM LIGHTS

GYM CEILING FANS STORAGE RM LIGHTS AND NORTH RECEPT

EXTERIOR LIGHTS - STAIR LIGHTS HEATER ENTRY WAY

PANELBOARD: 14-D6A (REPLACEMENT)

VA PER PHASE

CIRCUIT DESCRIPTION A B C

MECHANICAL RM LIGHTS ''

PUMP - MECHANICAL RM RECEPT GYM LIGHTS