This document contains a series of electrical schedule drawings for the U.S. Department of Veterans Affairs (VA) located in Vancouver, WA. The drawings are part of a design-build project and include detailed electrical panel and switchboard schedules for multiple buildings (Buildings 11, 13, 14, and 15). Each schedule provides comprehensive information about electrical systems, including voltage, bus ratings, main circuit breakers, circuit descriptions, load types, and spare circuit capacity. The documents are technical electrical engineering drawings prepared by a consulting discipline for the Office of Construction and Facilities Management, showing existing and revised electrical infrastructure configurations across different building locations.
The electrical schedules cover various panel types such as Motor Control Centers (MCCs), switchboards, and panelboards, with detailed breakdowns of circuit configurations, load types, and electrical demand factors. Each drawing includes specific technical details like voltage (208/120 Wye), amperage ratings, short circuit interruption (AIC) ratings, and circuit-level information including descriptions for lighting, receptacles, mechanical equipment, and spare circuits. The drawings are part of a comprehensive electrical system documentation set for a VA facility renovation or upgrade project, providing precise technical specifications for electrical infrastructure across multiple buildings.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FROM TO QTY SIZE (QTY) & SIZE GROUND
SIZE
013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -
013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -
013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -
013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1
013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -
NOTES
BLDG 013 - CONDUIT AND WIRE SCHEDULE
CONDUIT
TAG SERVICE
ROUTING CONDUIT CONDUCTORS
NOTE(S):
1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.
FROM TO QTY SIZE (QTY) & SIZE GROUND
SIZE
013-P-01 SITE LIGHTING CONTACTOR PANELBOARD "PMP-4/1" SITE LIGHTING CONTACTOR 1 1" (2) 10 AWG (1) 10 AWG - 013-P-02 SURGE PROTECTION DEVICE PANELBOARD "MDS-4" SURGE PROTECTION DEVICE 1 1" (4) 6 AWG (1) 10 AWG -
13-C-01 PHOTOCELL SITE LIGHTING CONTACTOR PHOTOCELL 1 1" (2) 12 AWG (1) 12 AWG
013-G-01 WATER PIPE BOND MAIN FIRE RISER WATER PIPE BONDING BUSBAR 1 - - 2 AWG -
013-G-02 SERVICE EQUIPMENT BOND BONDING BUSBAR PANEL "MDS-4" 1 - - 2 AWG -
013-G-03 GROUNDING ARRAY GROUND ROD GROUND ROD 1 - - 3/0 AWG 1
013-G-04 AIR TERMINAL BOND ESE AIR TERMINAL GROUND ROD 1 - - 2 AWG -
NOTES
BLDG 013 - CONDUIT AND WIRE SCHEDULE
CONDUIT
TAG SERVICE
ROUTING CONDUIT CONDUCTORS
NOTE(S):
1. GROUNDING ELECTRODE SYSTEM BONDING CONDUCTORS SHALL BE ROUTED IN CONDUIT WHERE EXPOSED AND SHALL BE BARE WHEN UNDERGROUND.
Location: BLDG 14, RM 112 Volts: 208/120 Wye A.I.C Rating: 22k Supply From: "DP-7/1" Phases: 3 Bus Rating: 225A
Mounting: Surface Wires 4 Main Circuit Breaker: 200A Enclosure: Type 1
CKT Trip Poles Poles Trip 1 20 A 1 0 0 1 20 A 2 3 20 A 1 0 0 1 20 A 4 5 20 A 1 0 0 2 15A 6 7 20 A 1 0 0 '' '' 8 9 20 A 1 0 0 2 20 A 10
11 20 A 2 0 0 " " 12 13 " " 0 0 2 20 A 14 15 20 A 1 0 0 " " 16 17 20 A 1 0 0 1 20 A 18 19 20 A 1 0 0 1 20 A 20 21 20 A 1 0 0 1 20 A 22 23 20 A 1 0 0 1 20 A 24 25 20 A 1 0 0 1 20 A 26 27 20 A 1 0 0 2 20 A 28 29 20 A 1 0 0 " " 30 31 20 A 1 0 0 2 30 A 32 33 20 A 1 0 0 " " 34 35 20 A 1 0 0 1 20 A 36 37 20 A 1 0 0 1 20 A 38 39 20 A 1 0 0 2 30 A 40 41 20 A 1 0 0 " " 42 43 20 A 1 0 0 1 20 A 44 45 20 A 1 0 0 1 20 A 46 47 20 A 1 0 0 1 20 A 48 49 20 A 1 0 100 3 30 A 50 51 20 A 1 0 100 " " 52 53 20 A 1 0 100 " " 54
SPARE SURGE PROTECTION DEVICE
SPARE "
SPARE "
SPARE SPARE
SPARE SPARE
SPARE SPARE
RECEPT RM 108 CONDENSATE PUMP
LIGHTS MEZZAINE RTU HEAT
GYM EXHAUST FANS (OFF) "
LIGHTS UPPER LEVEL SPARE
RECEPT UPPER LEVEL "
RECEPT LOWER LEVEL RM 108 AC / RECEPT
SCOREBOARD LOCKER AREA EXHAUST FANS
LIGHTS MAIN LEVEL EAST WALL HEATER SOUTH STORAGE
LIGHTS MAIN LEVEL NORTH "
EXIT LIGHTS HEAT DOWNSTAIRS WEST (OFF)
GYM RECEPT HEAT DOWNSTAIRS EAST
GYM RECEPT FIRE ALARM PANEL
" GYM LIGHTS
EXHAUST FAN - MECHANICAL RM "
RECEPT MEACHNICAL RM HEAT UPSTAIRS
WALL HEATER NORTH STORAGE RM "
CIRCUIT DESCRIPTION
WATER COOLER - WATER HEATER GYM LIGHTS
GYM CEILING FANS STORAGE RM LIGHTS AND NORTH RECEPT
EXTERIOR LIGHTS - STAIR LIGHTS HEATER ENTRY WAY
PANELBOARD: 14-D6A (REPLACEMENT)
VA PER PHASE
CIRCUIT DESCRIPTION A B C
MECHANICAL RM LIGHTS ''
PUMP - MECHANICAL RM RECEPT GYM LIGHTS