Attachment 5 - Drawings 4 of 4 - Dublin GA - EHRM.pdf
PDF 21 MB Posted
- Attached to
- Z2DZ--EHRM Infrastructure Upgrades Dublin, GA Project 557-22-700 Federal contract opportunity
- Solicitation number
- 36C77625B0013
About this file
This document is an architectural and engineering drawing set (Volume 4 of 4) for Electrical and Technology Infrastructure Upgrades at the Carl Vinson VA Medical Center in Dublin, Georgia, with project number 557-22-700. The comprehensive set includes detailed electrical and technology plans for 26 different buildings, covering telecom rooms, technology infrastructure, power systems, and fiber optic backbone routing. Key technical elements include installing new telecommunications rooms with standardized configurations, upgrading electrical panels, implementing new fiber optic cabling infrastructure, installing cable trays, adding power distribution units, and modernizing technology infrastructure across multiple campus buildings.
The drawings specify detailed technical requirements such as installing 18-24" wide cable trays at 9' above finished floor, mounting fire-rated backboards, implementing secondary bonding busbars, installing new patch panels, and providing dedicated power circuits for telecommunications equipment. Each building's telecom room will receive similar standardized upgrades, including new racks, power connections, fire/smoke sleeve assemblies, and infrastructure to support modern technology systems. The project involves extensive work across the VA Medical Center campus, with a focus on upgrading electrical and technology infrastructure to improve communications and technology capabilities.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
7' -0
5'-0"
VAN
ACCESSIBLE
LOADING AREA
SF
SF
EA
SE
MEN
T A
PP
RO
XIM
AT
EL
Y S
HO
WN
' E
XIS
TIN
G W
AT
ER
LI
NE
EA
SE
MEN
T
2.5" PLASTIC WITNESS POST
1/2" REBAR FOUND IN
CONCRETE MONUMENT
CONCRETE NAIL FOUND
Bldg 5 Gen
Bldg 4 Gen
Water Tower Gen
Bldg 8 Gen
Circuit 2 Gen
OBSERVATION MONITORING WELL
UP
UP
DEANE + STROLLO, LLC718 Virginia DriveOrlando, FL. 32803T: (407) 423-5355 F: (407) 422-5994
H
IL
LC
R
ES
T
PK
W
Y.
BE
LL
EV
UE
R D.
INDUSTRIAL BLVD.
INDUSTRIAL BLVD.
H
IL
LC
R
ES
T
PK
W
Y.
FAIRVIEW PARK HOSPITAL
FA
IR
VI
EW
P
AR
K
DR
IV
E
Bldg 27 Gen
F
F
F
F
F F
F
F
FF
F
F
SIGN
NE
FF
PL
AC
E
NE
FF
P
LA
CE
BE
LL
EV
UE
AV
EN
UE
AL
EX
AN
DE
R D
RIV
E
JO
HNSO
N ST
REE
T
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
METAL BLDGS.BLDG. 31
BLDG. 46
BLDG. 36
BLDG. 24
BLDG. 43
BLDG. 32
BLDG. 39
GAZEBO
BLDG. 68
BLDG. 67
BLDG. 21
LAKE LEISURE
AC
AC
PARKING
PARKING
BLDG. 34
BLDG. 35
STEPS
RAMP
PATIO
R
AM
P 1:
S
LO
PE
R
AM
P 1:
S
LO
PE
R
AM
P 1:
S
LO
PE
LA
N
D
IN
G
VAN VAN VAN VAN
RAMP
CONCRETE DITCH
CONCRETE
CONCRETE
CONCRETE
SLAB
SLAB
NEW PARKING
CTCT
AC
AC
AC
AC
OBSERVATION MONITORING WELL
BLDG. 17
BLDG.
BLDG. 47
BLDG. 41
BLDG
BLDG. 63
BLDG. 81
BLDG. 82
BLDG. 27
BLDG.
BLDG. 71BLDG. 28
BLDG. 66
CO
OL
IN
G
TO
W
ER
BLDG. 69
BLDG. 30
WATER TANK
BLDG. 5
BLDG. 3 BLDG. 1
BLDG. 9
BLDG. 13
BLDG. 11
BLDG. 2
BLDG. 40
BLDG. 4
BLDG. 6
BLDG. 8
BLDG. 10
BLDG. 12
BLDG. 85
BLDG. 14
BLDG. 86
BLDG. 25
BLDG. 26
BLDG. 29
BLDG. 15
BLDG. 19
GAZEBO
SUBSTATION
BLDG. 44
BLDG. 62
BLDG. 84
BLDG.
Bldg 2 Gen
FUEL
TANK
MRI
BLDG.29
ANNEX
New Water Tower Location
Bldg.10
New Chiller Plant
BLDG. 87
BLACKWOOD DRIVE
EX
IS
TIN
G
JO
HN
SO
N
ST
RE
ET
JOHNSON STREET
ALEXANDER DRIVE
BLACKWOOD DRIVE
TROJAKOWSKI AVENUE
EVANS AVENUE
TROJAKOWSKI AVENUE
EVANS AVENUE
CROWLEY AVENUE
CROWLEY AVENUE
VETERANS PARKWAY US HWY 80
VETERANS PARKWAY US HWY 80 VETERANS PARKWAY US HWY 80
JOHNSON STREET
BLACKWOOD DRIVE
AL
EX
AN
DE
R D
RIV
E
JOHNSON STREET
THOMAS LANE
THOMAS LANE
NORTHWEST DRIVE
JOHNSON STREET
EVANS AVENUE
TROJAKOWSKI AVENUE
NEW JO
HNSON STREET WEST
SHADED BUILDINGS REPRESENT
PROJECT SCOPE
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
PROJECT SITE MAP PROJECT LOCATION MAP
/6
/2
9:
:5
PM
C :\U se rs
\a pu lle n\
D oc um en ts \M
S_
-1
-V A
D ub lin E
H R
M _G
EN
_R
_a pu lle nV D
XT
7.
rv t
GE-001
COVER
1 1DSC
EHRM INFRASTRUCTURE
UPGRADES
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027 NOVEMBER 8, 2024
100% BID DOCUMENTS
557-22-70022-192
VARIOUS
EHRM INFRASTRUCTURE UPGRADES
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027
VA PROJECT #: 557-22-700
KTK
NORTH
NORTH
DRAWING LIST - VOLUME 4 OF 4
SHEET NUMBER SHEET NAME DWG OF DWG
GENERAL
GE-001 COVER 1 1
ELECTRICAL
00.ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 91
00.ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 91
00.ET501 TYPICAL TELECOM ROOM DETAILS 3 91
00.ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 91
00.ET503 ELECTRICAL AND TECHNOLOGY DETAILS 5 91
00.ET504 TECHNOLOGY DETAILS 6 91
00.ET505 CHANNEL RACK POWER AND TE DETAILS 7 91
00.ET506 TR RACK DETAILS 8 91
00.ET507 SITE TECHNOLOGY DETAILS 9 91
00.TS101 SITE FIBER BACKBONE ROUTING PLAN 10 91
00.TS102 SITE FIBER BACKBONE ROUTING DIAGRAM 11 91
00.T-601 TECHNOLOGY RISERS 12 91
01.ET411 BUILDING 1, LEVEL A, TELECOM ROOM 101-1 PLANS 13 91
01.ET421 BUILDING 1, LEVEL B, TELECOM ROOM 207-1 PLANS 14 91
01.ET601 BUILDING 1, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 15 91
02.ET401 BUILDING 2, LEVEL C, TELECOM ROOM BM123B-2 PLANS 16 91
02.ET411 BUILDING 2, LEVEL A, TELECOM ROOM 104-2 PLANS 17 91
02.ET421 BUILDING 2, LEVEL B, TELECOM ROOM 209A-2 PLANS 18 91
02.ET601 BUILDING 2, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 19 91
03.ET401 BUILDING 3, LEVEL C, TELECOM ROOM BM101A-3 PLANS 20 91
03.ET412 BUILDING 3, LEVEL A, CONFERENCE ROOM 112A-3 PLANS 21 91
03.ET421 BUILDING 3, LEVEL B, TELECOM ROOM 219-3 PLANS 22 91
03.ET601 BUILDING 3, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 23 91
04.ET401 BUILDING 4, LEVEL C, TELECOM ROOM BM105-4 PLANS 24 91
04.ET411 BUILDING 4, LEVEL A, TELECOM ROOM 118-4 PLANS 25 91
04.ET421 BUILDING 4, LEVEL B, TELECOM ROOM 202-4 PLANS 26 91
04.ET601 BUILDING 4, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 27 91
05.ET411 BUILDING 5, LEVEL A, TELECOM ROOM C137-5 PLANS 28 91
05.ET601 BUILDING 5, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 29 91
06.ET411 BUILDING 6, LEVEL A, TELECOM ROOM 103-6 PLANS 30 91
06.ET421 BUILDING 6, LEVEL B, TELECOM ROOM 226-6 PLANS 31 91
06.ET601 BUILDING 6, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 32 91
08.ET411 BUILDING 8, LEVEL A, TELECOM ROOM 172C-8 PLANS 33 91
08.ET421 BUILDING 8, LEVEL B, TELECOM ROOM 213-8 PLANS 34 91
08.ET601 BUILDING 8, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 35 91
09.ET421 BUILDING 9, LEVEL B, TELECOM 210A-9 PLANS 36 91
09.ET601 BUILDING 9, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 37 91
10.ET401 BUILDING 10, LEVEL C, TELECOM ROOM BM107A-10 PLANS 38 91
10.ET411 BUILDING 10, LEVEL A, TELECOM ROOM 130-10 PLANS 39 91
10.ET421 BUILDING 10, LEVEL B, TELECOM ROOM 205-10 PLANS 40 91
10.ET601 BUILDING 10, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 41 91
11.ET401 BUILDING 11, LEVEL C, TELECOM ROOM BM101A-11 PLANS 42 91
11.ET411 BUILDING 11, LEVEL A, TELECOM ROOM 125-11 PLANS 43 91
11.ET421 BUILDING 11, LEVEL B, TELECOM ROOM 235-11 PLANS 44 91
11.ET601 BUILDING 11, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 45 91
12.ET401 BUILDING 12, LEVEL C, TELECOM ROOM BM103A-12 PLANS 46 91
12.ET411 BUILDING 12, LEVEL A, TELECOM ROOM 117A-12 PLANS 47 91
12.ET421 BUILDING 12, LEVEL B, TELECOM ROOM 232A-12 PLANS 48 91
12.ET601 BUILDING 12, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 49 91
13.ET411 BUILDING 13, LEVEL A, TELECOM ROOM 104-13 PLANS 50 91
13.ET421 BUILDING 13, LEVEL B, TELECOM ROOM 224-13 PLANS 51 91
13.ET601 BUILDING 13, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 52 91
14.ET401 BUILDING 14, LEVEL C, TELECOM ROOM BM104A-14 PLANS 53 91
14.ET411 BUILDING 14, LEVEL A, TELECOM ROOM 101A-14 PLANS 54 91
14.ET421 BUILDING 14, LEVEL B, TELECOM ROOM 232-14 PLANS 55 91
14.ET601 BUILDING 14, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 56 91
15.ET411 BUILDING 15, LEVEL A, TELECOM ROOM 107-15 PLANS 57 91
15.ET421 BUILDING 15, LEVEL B, TELECOM ROOM 230-15 PLANS 58 91
15.ET601 BUILDING 15, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 59 91
16.ET401 BUILDING 16, LEVEL C, TELECOM ROOM B11A-16 PLANS 60 91
16.ET421 BUILDING 16, LEVEL B, TELECOM ROOM 216-16 PLANS 61 91
16.ET601 BUILDING 16, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 62 91
17.ET411 BUILDING 17, LEVEL A, TELECOM ROOM 111-17 PLANS 63 91
17.ET421 BUILDING 17, LEVEL B, TELECOM ROOM 205-17 PLANS 64 91
17.ET601 BUILDING 17, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 65 91
19.ET411 BUILDING 19, LEVEL A, TELECOM ROOM 117-19 PLANS 66 91
19.ET421 BUILDING 19, LEVEL B, TELECOM ROOM 216A-19 PLANS 67 91
19.ET601 BUILDING 19, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 68 91
25.ET411 BUILDING 25, LEVEL A, TELECOM ROOM 101A-25 PLANS 69 91
25.ET601 BUILDING 25, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 70 91
26.ET401 BUILDING 26, LEVEL C, TELECOM ENCLOSURE BM108B-26 PLANS 71 91
26.ET411 BUILDING 26, LEVEL A, TELECOM ROOM 106-26 PLANS 72 91
26.ET601 BUILDING 26, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 73 91
27.ET411 BUILDING 27, LEVEL A, TELECOM ROOM 107-27 PLANS 74 91
27.ET601 BUILDING 27, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 75 91
28.ET411 BUILDING 28, LEVEL A, TELECOM ROOM 108-28 PLANS 76 91
28.ET601 BUILDING 28, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 77 91
29.ET411 BUILDING 29, LEVEL A, TELECOM ENCLOSURE 113A-29 PLANS 78 91
29.ET601 BUILDING 29, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 79 91
30.ET411 BUILDING 30, LEVEL A, TELECOM ENCLOSURE 104-30 PLANS 80 91
30.ET601 BUILDING 30, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 81 91
40.ET412 BUILDING 40, LEVEL A, COMPUTER ROOM 106 TECHNOLOGY PLANS 82 91
85.ET411 BUILDING 85, LEVEL A, TELECOM ROOM 121-85 PLANS 83 91
85.ET601 BUILDING 85, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 84 91
86.ET411 BUILDING 86, LEVEL A, TELECOM ROOM 106-86 PLANS 85 91
86.ET601 BUILDING 86, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 86 91
87.ET411 BUILDING 87, LEVEL A, TELECOM ROOM 120-87 PLANS 87 91
87.ET412 BUILDING 87, LEVEL A, TELECOM ROOM 169-87 PLANS 88 91
87.ET601 BUILDING 87, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 89 91
89.ET411 BUILDING 89, LEVEL A, TELECOM ROOM 1215-89 PLANS 90 91
89.ET601 BUILDING 89, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 91 91
VOLUME 4 OF 4
Docusign Envelope ID: B71C0D48-D83D-418C-8E57-61AA26C33206
11/8/202411/8/2024
S SS
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA
TYPE
EQUIPMENT CONNECTIONAS
NOTED
E
AS
SPECIFIED
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED7'-0"
CENTER
4' LINEAR - WALL MOUNTED7'-0"
CENTER
WALL SCONCE6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
UPS UNINTERUPTABLE POWER
SUPPLY
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PDU POWER DISTRIBUTION UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYPBD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE
APPROXIMATE ONLY (FIELD VERIFY).
BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED.
THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR
INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR
SHALL CUT OFF CONDUITS AND REMOVE WIRING.
WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE
LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP
OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF
AND CAPPED OR PLUGGED.
THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK.
ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.
ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO
MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.
EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND
NEW AREAS.
ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO
ACCOMPLISH THIS REQUIREMENT.
EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS
REQUIREMENT.
IF POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES SHALL BE INSTALLED IN SEPERATE OR ADJACENT STUD SPACES TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. IF NOT POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES LOCATED IN COMMON STUD SPACES INSTALLED ON OPPOSITE SIDES OF FIRE-RESISTANCE RATED WALLS SHALL BE EQUIPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE
WITH NEC 300.21 AND IBC 714.4.2.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT, SPECIFICATIONS, AND THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
A.
B.
C.
D.
E.
F.
11.
RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER
TRADES.
REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND
NEW CONSTRUCTION.
ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING
TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT
OF FEED WITH AN ENGRAVED BRASS TAG.
REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
2 HOUR FIRE SEPARATION
1 HOUR FIRE SEPARATION
SMOKE RATED
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
8:
:0
AM
C :\U se rs
\c gr iff itt
\D oc um en ts \T
R R oo m
D et ai ls
_R
_c gr iff itt
W H
M
PZ
.rv t
00.ET001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 91PDN
EHRM INFRASTRUCTURE
UPGRADES
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027 NOVEMBER 8, 2024
100% BID DOCUMENTS
557-22-70022-192
KTK
ELECTRICAL SYMBOL LEGEND
LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL GENERAL NOTES
GENERAL ELECTRICAL DEMO NOTES
TEMPORARY FIRESTOPPING
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONSWALL RATING LEGEND
Docusign Envelope ID: 7AE0511C-6224-4AC1-A0CA-266A39A191A9
11/6/2024 11/7/2024
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD)48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
N
S
NURSE CALL PATIENT STATION WITH PILLOW SPEAKER
2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
P NURSE CALL PATIENT BED INTERFACE RECEPTACLE
B NURSE CALL CODE BLUE STATION WITH COVER
E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN
RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)
D NURSE CALL DUTY STATION
M NURSE CALL MASTER STATION/CONSOLE
NURSE CALL DOME LIGHT
(Z - ZONE LIGHT, V - VANDAL RESISTANT)
IC INTERCOM WITH CAMERA
IC INTERCOM MASTER WITH PUSH TO RELEASE DOORM
NURSE CALL WIRELESS ANTENNASNW
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST CHANNEL RACK
OIT EQUIPMENT CABINET
NURSE CALL EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
NCE
MATV
CCTV
BASKET CABLE TARY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
HEADWALL
18"
HEADWALL
/40"
40", 72"
18"
60"
CEILING
CEILING
6' TO TOP
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
HANDWAVE
T
C
NURSE CALL STAFF TERMINAL
NURSE CALL PATIENT STATION WITH CALL CORD.
(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)
60"
HEADWALL
W WIRELESS PENDANT
L
KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"
PATIENT ROAM ALERT ANTENNACEILING
GROUND BUS
CEILING
DOOR
DOOR
48"
ABOVE
DOOR
NURSE CALL DOME LIGHT
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
N M
PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)
88" MOTION DETECTORMD
FLOOR 6", 12" VERTICAL WIRE MANAGEMENT
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
AREA OF REFUGE PANEL6' TO TOP
AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP
AOF
AOFA
IC AREA OF REFUGE INTERCOM48"
AREA OF REFUGE STROBE LIGHTCEILINGSL
DP
DPP
DURESS PANIC ALARM PUSH BUTTON48"
DURESS PANIC ALARM PANEL6' TO TOP
N
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
48"
CEILING
CEILING
TELEMETRY ANTENNA - 2-4 PRCEILING
ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR
CABLE LADDERABOVE
CEILING
CABLES AND CONNECTORS COLOR LEGEND
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
WIRELESS
ACCESS POINT
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
CCTV - IP
BLUE
GREEN
BLACK
IVORY
WHITE
BLUE
GREEN
AQUA
YELLOW
WHITE
BLUE
GREEN
AQUA
YELLOW
WHITE
C
WAP
FO
FO
CCTV
4 PAIR CABLE
4 PAIR CABLE
6/12/24/36
6/12
PACS N/A GRAY N/A PACS MULTI COLOR
CONDUCTORS
4 PAIR CABLE
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FO FIBER OPTIC
FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL
IT INTERCOMMUNICATION ROOM
MATV MASTER ANTENNA TELEVISION
MDA MAIN DISTRIBUTION AREA
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU POWER DISTRIBUTION UNIT
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
rPDU RACK POWER DISTRIBUTION UNIT
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BACKBONE CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
WAO WORK AREA OUTLET
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
TECHNOLOGY GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT
SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL
LISTING REQUIREMENT, SPECIFICATIONS, AND APPLICABLE BUILDING CODES.
PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION
METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607-D - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING
STANDARD.
COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN
ACT".
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY
TESTING AGENCY.
NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE
MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.
ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B.
LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606C OR 606B EDITION AS WELL AS THE STANDARDS
SET FORTH BY THE VA HOSPITAL OIT.
PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569-D.
VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND
EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
UNLESS OTHERWISE INDICATED, MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT. CONTRACTOR TO RE-USE
EXISTING CONDUIT WHERE AVAILABLE.
WALL MOUNTED DEVICES PLACED IN TELECOM ROOM SHALL BE MOUNTED ON FIRE RETARDANT PLYWOOD.
PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS
FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING (BOTH FIBER AND COPPER), JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, BONDING BUS BARS, RACK MOUNTED BONDING BUS, BONDING CABLING, BONDING TO THE GROUNDING SYSTEM, BONDING CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS
DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE J-HOOKS OR FLEXIBLE CONDUITS WHERE CABLE TRAY IS NOT SHOWN, OR IF THE PATH OF THE CABLE TRAY IS OBSTRUCTED. PROVIDE JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, AND COVER PLATES AS NEEDED OR WHERE REQUIRED BY CODE. LABEL AND SUPPORT J-HOOKS, CABLE TRAY, AND
CONDUIT AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
28. PROVIDE 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN EACH NEW TR AND RUN 12 CAT 6A CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.
29. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.
30. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS. CAMERAS SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-
NDAA.
31. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
32. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.
33. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.
34. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD
END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE
REPRESENTATIVE.
35. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.
GENERAL TECHNOLOGY DEMOLITION NOTES
1.
2.
3.
4.
5.
ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).
EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO
THE EXISTING CABLE TRAY.
EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH
THE COR.
EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES.
REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE
UPS AND POWER SOURCE IN TACT.
CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL INFORMATION.
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
8:
:0
AM
C :\U se rs
\c gr iff itt
\D oc um en ts \T
R R oo m
D et ai ls
_R
_c gr iff itt
W H
M
PZ
.rv t
00.ET002
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND, AND
ABBREVIATIONS
2 91PDN
EHRM INFRASTRUCTURE
UPGRADES
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027 NOVEMBER 8, 2024
100% BID DOCUMENTS
557-22-70022-192
KTK
CONDITIONAL NOTE
E
CR
DC ES RX J
M
10 10
PANEL 'A' PANEL 'B'
00.ET5016
A-13,15,17
B-13,15,17
SBB
K
A-2
B-2
A-2
A-2 N
GFIB-2
B-2
A-2
B-2
48"
A
B
C
C
CC
FIRE RATED PATHWAYS
PANEL 'A'1
SBB/PBB
BASKET TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
MOTOR-RATED
SWITCH
16 16
PANEL 'B'PANEL 'A'
BASKET TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
SBB/PBB
DATA PORT
LIGHT SWITCH
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
(M
IN
8'
-0
BASKET TRAY
PANEL 'B'
SBB
NEC REQUIRED WORKING
CLEARANCE, 30" WIDE BY
36" DEEP BY 72" HIGH
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
16 16BASKET TRAY
Engineers Architects
# NEW KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/5
/2
8:
:0
AM
C :\U se rs
\c gr iff itt
\D oc um en ts \T
R R oo m
D et ai ls
_R
_c gr iff itt
W H
M
PZ
.rv t
00.ET501
TYPICAL TELECOM ROOM DETAILS
3 91PDN
EHRM INFRASTRUCTURE
UPGRADES
CARL VINSON VA MEDICAL CENTER
1826 VETERANS BLVD
DUBLIN, GA 31027 NOVEMBER 8, 2024
100% BID DOCUMENTS
557-22-70022-192
KTK
1 ROOMS ARE COOLED WITH DUCTLESS
MINI-SPLITS. DUCTLESS MINI-SPLIT UNITS SHALL
BE POWERED FROM THEIR ASSOCIATED
OUTDOOR CONDENSING UNITS. PROVIDE A
CIRCUIT TO THE CONDENSING UNIT, INCLUDING
RACEWAYS AND CONDUCTORS TO POWER THE
INDOOR UNITS.
2 TELECOMMUNICATIONS CHANNEL RACK,23.75
INCHES WIDE, 30 INCHES DEEP, 84 INCHES HIGH,
45RU, WHITE. PROVIDE ORTRONICS (LEGRAND)
MM2073038-W, OR APPROVED EQUIVALENT.
CONTRACTOR SHALL COORDINATE ADDITIONAL
DETAILS INCLUDING BUT NOT LIMITED TO
GROUNDING AND BONDING DETAILS, DATA
ELEVATIONS AND POWER ELEVATIONS IN THE
DRAWINGS.
3 VERTICAL CABLE MANAGEMENT CAGE WITH
DOOR, 6 INCHES WIDE, 84 INCHES HIGH, 45RU,
WHITE. PROVIDE ORTRONICS (LEGRAND)
MM20VMD706-W, OR APPROVED EQUIVALENT.
4 RACK POWER CONNECTION MOUNTED TO THE
CHANNEL STEEL ABOVE THE RACKS MINIMUM 12"
AWAY FROM CABLE TRAY. FOR EACH RACK,
PROVIDE L21-20R RECEPTACLE. PROVIDE (3) 12
AWG AND (1) 10 AWG NEUTRAL (1) 12 AWG GND IN
3/4" CONDUIT. REFER TO RACK POWER
ELEVATION AND SCHEMATIC DIAGRAMS ON
SHEET 00.ET505.
5 SECONDARY BONDING BUSBAR TO BE LOCATED
BEHIND OR TO THE SIDE OF THE RACKS.
TELECOMMUNICATIONS EQUIPMENT SHALL BE
BONDED ACCORDING TO THE GROUNDING AND
BONDING DETAILS. REFER TO DETAILS 3 AND 4
ON SHEET 00.ET503 FOR MORE INFORMATION.
6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE UL
LISTED ASSEMBLIES, STI EZ-PATH, SERIES 44+
FOR 4” FIRE-RATED PATHWAY, OR APPROVED
EQUIVALENT. INSTALL SLEEVES ABOVE DOOR
HEADER AT AN ELEVATION COORDINATED TO BE
ABOVE THE EXISTING CEILING HEIGHT IN THE
ADJACENT CORRIDOR. REFER TO 400 SERIES ET
SHEETS FOR QUANTITIES.
7 PROVIDE NEW BASKET CABLE TRAY
THROUGHOUT ROOM AND ABOVE THE CHANNEL
RACKS. PROVIDE WITH WATERFALL DROPOUTS
INTO EACH RACK, 90 DEGREE CORNERS AND ALL
RELATED FITTINGS. SEE DETAIL 10 ON 00.ET504
FOR MORE INFO. B.O.D.: CABLOFIL CF105/600 AND
CF150/600 SERIES OR EQUIVALENT.
8 PROVIDE TWO RECEPTACLES ON EACH WALL, AS
SHOWN WITH ONE BEING FED FROM PANEL 'A'
THE OTHER FROM PANEL 'B'.
9 FIRE RETARDANT PLYWOOD BACKBOARD,
PAINTED ON ALL 6 SIDES. SEE ARCHITECTURAL
DRAWINGS FOR MORE DETAILS.
10 LIGHTING AND APPLIANCE PANELBOARDS.
PROVIDE PANELS MOUNTED ON CHANNEL STEEL
SUPPORTS. UNLESS NOTED OTHERWISE ON THE
400 SERIES ET SHEETS, PANEL 'A' SHALL BE FED
FROM A SOURCE WITH GENERATOR BACKUP, AND
PANEL 'B' SHALL BE FED FROM A NORMAL UTILITY
SOURCE.
12 PROVIDE 120V POWER FOR 8"X8"X4" HINGED
CONTROLLER BOX MOUNTED ABOVE DOOR.
REFERENCE DETAIL ON SHEET 5/00.E-503.
13 PROVIDE CABLING FOR VA FURNISHED WIRELESS
ACCESS POINT.
14 PROVIDE RECEPTACLE NEAR DOOR, WITH POWER
EXTENDED FROM AN EXISTING CONVENIENCE
OUTLET CIRCUIT ORIGINATING FROM A PANEL
NOT IN THE ROOM.
15 PROVIDE WALL PHONE OUTLET IN EVERY
TELECOM ROOM.
16 BASKET CABLE TRAY IS SHOWN OFFSET FROM
WALL FOR GRAPHICAL PURPOSES ONLY. INSTALL
CABLE TRAY FLUSH WITH WALL EXCEPT ABOVE
POWER PANELS AND MECHANICAL EQUIPMENT
WHERE SPACE IS NEEDED FOR PIPES AND
CONDUIT.
17 PROVIDE MULTI SENSOR CAMERA AND CONNECT
TO EXISTING CAMERA SYSTEM.
18 LIGHTING TO BE FED FROM CLOSEST EXISTING
CRITICAL LIGHTING CIRCUIT IN HALLWAY.
Scale: 3/8" = 1'-0"1 ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR Scale: 3/8" = 1'-0"2 ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR
Scale: 3/8" = 1'-0"6 PLAN WEST ELEVATION Scale: 3/8" = 1'-0"5 PLAN NORTH ELEVATION
Scale: 3/8" = 1'-0"3 PLAN SOUTH ELEVATION Scale: 3/8" = 1'-0"4 PLAN EAST ELEVATION
PER PHASE CONNECTED LOAD: 3.85 kVA 3.33 kVA 3.16 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
29 0 -- 30 1 -- SPACE
27 0 -- 28 1 -- SPACESPARE
(SEE PANEL NOTE 1 BELOW) 20 A 3
25 0 -- 26 1 -- SPACE
23 0 -- 24 1 -- SPACE
21 0 -- 22 1 -- SPACERACK RECEPTACLE 20 A 3
19 0 0 20 17 1.66 0 18
2 30 A SPARE
15 1.66 0 16RACK RECEPTACLE 20 A 3
13 1.66 0 14
2 30 A SPARE
11 1.66 0 12 1 20 A PACS J-BOX
9 1.66 0 10 1 20 A CONDENSATE PUMPRACK RECEPTACLE 20 A 3
7 1.66 0 8 1 20 A SPARE
5 0 0 6 1 20 A SPARE
3 0 0.18 4 1 20 A CONVENIENCE RCPTSURGE PROTECTIVE DEVICE
(SEE PANEL NOTE 4 BELOW) 30 A 3
1 0 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:PANEL: A
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC: 10,000 AMPS
SYMMETRICAL
PER PHASE CONNECTED LOAD: 5.47 kVA 4.76 kVA 4.76 kVA
SPACE -- 1 41 -- -- 42 1 -- SPACE
SPACE -- 1 39 -- -- 40 1 -- SPACE
SPACE -- 1 37 -- -- 38 1 -- SPACE
SPACE -- 1 35 -- -- 36 1 -- SPACE
SPACE -- 1 33 -- -- 34 1 -- SPACE
SPACE -- 1 31 -- -- 32 1 -- SPACE
29 0 -- 30 1 -- SPACE
27 0 -- 28 1 -- SPACESPARE
(SEE PANEL NOTE 1 BELOW) 20 A 3
25 0 -- 26 1 -- SPACE
23 1.66 -- 24 1 -- SPACE
21 1.66 -- 22 1 -- SPACERACK RECEPTACLE 30 A 3
19 1.66 0 20 1 20 A SPARE
17 1.66 0 18 1 20 A SPARE
15 1.66 0 16 1 20 A SPARERACK RECEPTACLE 20 A 3
13 1.66 0 14 1 20 A SPARE
11 1.66 0 12 1 20 A SPARE
9 1.66 0 10 1 20 A SPARERACK RECEPTACLE 20 A 3
7 1.66 0 8 1 20 A SPARE
5 0 0 6 1 20 A SPARE
3 0 0 4 1 20 A SPARESURGE PROTECTIVE DEVICE
(SEE PANEL NOTE 3 BELOW) 30 A 3
1 0 0.72 2 1 20 A TELECOM ROOM RCPT
LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction
MOUNTING: SURFACE FED FROM: LOCATION:PANEL: B
VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC: 10,000 AMPS
SYMMETRICAL
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
C 4' LINEAR LED STRIPLIGHT WITH FROSTED
LENS
CHAIN
SUSPEND
LED; 4,585
LUMENS; 80 CRI;
3500K
ELECTRONIC
LED DRIVER
MVOLT 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 35K 80CRI BAA
D 4' LINEAR LED WALL BRACKET WITH FROSTED
LENS MOUNTED AT 8' 6"
WALL
MOUNTED
LED; 4,585
LUMENS; 80 CRI;
3500K
ELECTRONIC
LED DRIVER
MVOLT 40 W LITHONIA WL4 40L MVOLT LP835 BAA
F 2' X 4' ARCHITECTURAL TROFFER; WITH
CURVED, SMOOTH CENTER DIFFUSER; TO
MATCH EXISTING
RECESSED
GRID
LED; 4800
LUMENS; 80 CRI;
3500K
0-10V
DIMMABLE TO
5% DRIVER
MVOLT 38 W LITHONIA 2BLT4 48L ADSM EZ1 LP835 BAA
P1 4" X 10'-0" DIRECT LINEAR…