Attachment 5 - Drawings 4 of 4 - Dublin GA - EHRM.pdf

PDF 21 MB Posted

Attached to
Z2DZ--EHRM Infrastructure Upgrades Dublin, GA Project 557-22-700 Federal contract opportunity
Solicitation number
36C77625B0013
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document is an architectural and engineering drawing set (Volume 4 of 4) for Electrical and Technology Infrastructure Upgrades at the Carl Vinson VA Medical Center in Dublin, Georgia, with project number 557-22-700. The comprehensive set includes detailed electrical and technology plans for 26 different buildings, covering telecom rooms, technology infrastructure, power systems, and fiber optic backbone routing. Key technical elements include installing new telecommunications rooms with standardized configurations, upgrading electrical panels, implementing new fiber optic cabling infrastructure, installing cable trays, adding power distribution units, and modernizing technology infrastructure across multiple campus buildings.

The drawings specify detailed technical requirements such as installing 18-24" wide cable trays at 9' above finished floor, mounting fire-rated backboards, implementing secondary bonding busbars, installing new patch panels, and providing dedicated power circuits for telecommunications equipment. Each building's telecom room will receive similar standardized upgrades, including new racks, power connections, fire/smoke sleeve assemblies, and infrastructure to support modern technology systems. The project involves extensive work across the VA Medical Center campus, with a focus on upgrading electrical and technology infrastructure to improve communications and technology capabilities.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DZ--EHRM Infrastructure Upgrades Dublin, GA Project 557-22-700, newest first.
File Type Posted
Atch 1 - PreBid RFIs 7.30.2025.xlsx XLSX spreadsheet
36C77625B0013 0004.docx DOCX document
Atch 1 - PreBid RFIs 7.24.2025.xlsx XLSX spreadsheet
36C77625B0013 0003.docx DOCX document
Atch 3 - ICRALevel_Department - Dublin - 557-22-700.pdf PDF
Atch 2 - Annual Hydrant Flow Report_9JUL25 - Dublin - 557-22-700.xlsx XLSX spreadsheet
36C77625B0013 0002.docx DOCX document
Atch 8 - Dublin EHRM_ACM_Matrix - Dublin - 557-22-700.xlsx XLSX spreadsheet
Atch 6 - 013323 Shop Drawings - Dublin - 557-22-700.pdf PDF
Atch 5 - 013216.15 Project Sched_Small - Dublin - 557-22-700.pdf PDF
Atch 4 - Virtual Bid Opening Information - Dublin - 557-22-700.pdf PDF
Atch 9 - 22-192 Existing Cable Counts by TR - Dublin - 557-22-700.xlsx XLSX spreadsheet
Atch 7 - 028333.13 Lead Based Paint - Dublin - 557-22-700.pdf PDF
Atch 1 - PreBid RFIs.xlsx XLSX spreadsheet
36C77625B0013 0001.docx DOCX document
Attachment 1 - Site Visit Sign-in Sheet - Dublin EHRM.pdf PDF
Attachment 2 - Site Visit Agenda - Dublin EHRM.pdf PDF
Attachment 15 - Drwg 82 of 91 REVISED.pdf PDF
Attachment 13 - VAAR LOS Construction.docx DOCX document
Attachment 11 - SOW Atch 4 Specifications.pdf PDF
Attachment 8 - SOW Atch 1 Design Guide Telecom Spaces.pdf PDF
Attachment 3 - Drawings 2 of 4 - Dublin GA - EHRM.pdf PDF
Attachment 10 - SOW Atch 3 Elec Panel Labeling.pdf PDF
Attachment 14 - Division Cost Breakdown.xlsx XLSX spreadsheet
Attachment 9 - SOW Atch 2 EUD Requirements.pdf PDF
Attachment 6 - Site Visit Instructions.docx DOCX document
Attachment 1 - Specifications - Dublin GA - EHRM.pdf PDF
Attachment 12 - Wage Rates - GA20250095 02072025.pdf PDF
Attachment 7 - SOW - Dublin GA - EHRM.pdf PDF
Attachment 4 - Drawings 3 of 4 - Dublin GA - EHRM.pdf PDF
Attachment 2 - Drawings 1 of 4 - Dublin GA - EHRM.pdf PDF
36C77625B0013.docx DOCX document
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7' -0

5'-0"

VAN

ACCESSIBLE

LOADING AREA

SF

SF

EA

SE

MEN

T A

PP

RO

XIM

AT

EL

Y S

HO

WN

' E

XIS

TIN

G W

AT

ER

LI

NE

EA

SE

MEN

T

2.5" PLASTIC WITNESS POST

1/2" REBAR FOUND IN

CONCRETE MONUMENT

CONCRETE NAIL FOUND

Bldg 5 Gen

Bldg 4 Gen

Water Tower Gen

Bldg 8 Gen

Circuit 2 Gen

OBSERVATION MONITORING WELL

UP

UP

DEANE + STROLLO, LLC718 Virginia DriveOrlando, FL. 32803T: (407) 423-5355 F: (407) 422-5994

H

IL

LC

R

ES

T

PK

W

Y.

BE

LL

EV

UE

R D.

INDUSTRIAL BLVD.

INDUSTRIAL BLVD.

H

IL

LC

R

ES

T

PK

W

Y.

FAIRVIEW PARK HOSPITAL

FA

IR

VI

EW

P

AR

K

DR

IV

E

Bldg 27 Gen

F

F

F

F

F F

F

F

FF

F

F

SIGN

NE

FF

PL

AC

E

NE

FF

P

LA

CE

BE

LL

EV

UE

AV

EN

UE

AL

EX

AN

DE

R D

RIV

E

JO

HNSO

N ST

REE

T

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

METAL BLDGS.BLDG. 31

BLDG. 46

BLDG. 36

BLDG. 24

BLDG. 43

BLDG. 32

BLDG. 39

GAZEBO

BLDG. 68

BLDG. 67

BLDG. 21

LAKE LEISURE

AC

AC

PARKING

PARKING

BLDG. 34

BLDG. 35

STEPS

RAMP

PATIO

R

AM

P 1:

S

LO

PE

R

AM

P 1:

S

LO

PE

R

AM

P 1:

S

LO

PE

LA

N

D

IN

G

VAN VAN VAN VAN

RAMP

CONCRETE DITCH

CONCRETE

CONCRETE

CONCRETE

SLAB

SLAB

NEW PARKING

CTCT

AC

AC

AC

AC

OBSERVATION MONITORING WELL

BLDG. 17

BLDG.

BLDG. 47

BLDG. 41

BLDG

BLDG. 63

BLDG. 81

BLDG. 82

BLDG. 27

BLDG.

BLDG. 71BLDG. 28

BLDG. 66

CO

OL

IN

G

TO

W

ER

BLDG. 69

BLDG. 30

WATER TANK

BLDG. 5

BLDG. 3 BLDG. 1

BLDG. 9

BLDG. 13

BLDG. 11

BLDG. 2

BLDG. 40

BLDG. 4

BLDG. 6

BLDG. 8

BLDG. 10

BLDG. 12

BLDG. 85

BLDG. 14

BLDG. 86

BLDG. 25

BLDG. 26

BLDG. 29

BLDG. 15

BLDG. 19

GAZEBO

SUBSTATION

BLDG. 44

BLDG. 62

BLDG. 84

BLDG.

Bldg 2 Gen

FUEL

TANK

MRI

BLDG.29

ANNEX

New Water Tower Location

Bldg.10

New Chiller Plant

BLDG. 87

BLACKWOOD DRIVE

EX

IS

TIN

G

JO

HN

SO

N

ST

RE

ET

JOHNSON STREET

ALEXANDER DRIVE

BLACKWOOD DRIVE

TROJAKOWSKI AVENUE

EVANS AVENUE

TROJAKOWSKI AVENUE

EVANS AVENUE

CROWLEY AVENUE

CROWLEY AVENUE

VETERANS PARKWAY US HWY 80

VETERANS PARKWAY US HWY 80 VETERANS PARKWAY US HWY 80

JOHNSON STREET

BLACKWOOD DRIVE

AL

EX

AN

DE

R D

RIV

E

JOHNSON STREET

THOMAS LANE

THOMAS LANE

NORTHWEST DRIVE

JOHNSON STREET

EVANS AVENUE

TROJAKOWSKI AVENUE

NEW JO

HNSON STREET WEST

SHADED BUILDINGS REPRESENT

PROJECT SCOPE

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

PROJECT SITE MAP PROJECT LOCATION MAP

/6

/2

9:

:5

PM

C :\U se rs

\a pu lle n\

D oc um en ts \M

S_

-1

-V A

D ub lin E

H R

M _G

EN

_R

_a pu lle nV D

XT

7.

rv t

GE-001

COVER

1 1DSC

EHRM INFRASTRUCTURE

UPGRADES

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027 NOVEMBER 8, 2024

100% BID DOCUMENTS

557-22-70022-192

VARIOUS

EHRM INFRASTRUCTURE UPGRADES

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027

VA PROJECT #: 557-22-700

KTK

NORTH

NORTH

DRAWING LIST - VOLUME 4 OF 4

SHEET NUMBER SHEET NAME DWG OF DWG

GENERAL

GE-001 COVER 1 1

ELECTRICAL

00.ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 91

00.ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 91

00.ET501 TYPICAL TELECOM ROOM DETAILS 3 91

00.ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 91

00.ET503 ELECTRICAL AND TECHNOLOGY DETAILS 5 91

00.ET504 TECHNOLOGY DETAILS 6 91

00.ET505 CHANNEL RACK POWER AND TE DETAILS 7 91

00.ET506 TR RACK DETAILS 8 91

00.ET507 SITE TECHNOLOGY DETAILS 9 91

00.TS101 SITE FIBER BACKBONE ROUTING PLAN 10 91

00.TS102 SITE FIBER BACKBONE ROUTING DIAGRAM 11 91

00.T-601 TECHNOLOGY RISERS 12 91

01.ET411 BUILDING 1, LEVEL A, TELECOM ROOM 101-1 PLANS 13 91

01.ET421 BUILDING 1, LEVEL B, TELECOM ROOM 207-1 PLANS 14 91

01.ET601 BUILDING 1, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 15 91

02.ET401 BUILDING 2, LEVEL C, TELECOM ROOM BM123B-2 PLANS 16 91

02.ET411 BUILDING 2, LEVEL A, TELECOM ROOM 104-2 PLANS 17 91

02.ET421 BUILDING 2, LEVEL B, TELECOM ROOM 209A-2 PLANS 18 91

02.ET601 BUILDING 2, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 19 91

03.ET401 BUILDING 3, LEVEL C, TELECOM ROOM BM101A-3 PLANS 20 91

03.ET412 BUILDING 3, LEVEL A, CONFERENCE ROOM 112A-3 PLANS 21 91

03.ET421 BUILDING 3, LEVEL B, TELECOM ROOM 219-3 PLANS 22 91

03.ET601 BUILDING 3, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 23 91

04.ET401 BUILDING 4, LEVEL C, TELECOM ROOM BM105-4 PLANS 24 91

04.ET411 BUILDING 4, LEVEL A, TELECOM ROOM 118-4 PLANS 25 91

04.ET421 BUILDING 4, LEVEL B, TELECOM ROOM 202-4 PLANS 26 91

04.ET601 BUILDING 4, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 27 91

05.ET411 BUILDING 5, LEVEL A, TELECOM ROOM C137-5 PLANS 28 91

05.ET601 BUILDING 5, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 29 91

06.ET411 BUILDING 6, LEVEL A, TELECOM ROOM 103-6 PLANS 30 91

06.ET421 BUILDING 6, LEVEL B, TELECOM ROOM 226-6 PLANS 31 91

06.ET601 BUILDING 6, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 32 91

08.ET411 BUILDING 8, LEVEL A, TELECOM ROOM 172C-8 PLANS 33 91

08.ET421 BUILDING 8, LEVEL B, TELECOM ROOM 213-8 PLANS 34 91

08.ET601 BUILDING 8, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 35 91

09.ET421 BUILDING 9, LEVEL B, TELECOM 210A-9 PLANS 36 91

09.ET601 BUILDING 9, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 37 91

10.ET401 BUILDING 10, LEVEL C, TELECOM ROOM BM107A-10 PLANS 38 91

10.ET411 BUILDING 10, LEVEL A, TELECOM ROOM 130-10 PLANS 39 91

10.ET421 BUILDING 10, LEVEL B, TELECOM ROOM 205-10 PLANS 40 91

10.ET601 BUILDING 10, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 41 91

11.ET401 BUILDING 11, LEVEL C, TELECOM ROOM BM101A-11 PLANS 42 91

11.ET411 BUILDING 11, LEVEL A, TELECOM ROOM 125-11 PLANS 43 91

11.ET421 BUILDING 11, LEVEL B, TELECOM ROOM 235-11 PLANS 44 91

11.ET601 BUILDING 11, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 45 91

12.ET401 BUILDING 12, LEVEL C, TELECOM ROOM BM103A-12 PLANS 46 91

12.ET411 BUILDING 12, LEVEL A, TELECOM ROOM 117A-12 PLANS 47 91

12.ET421 BUILDING 12, LEVEL B, TELECOM ROOM 232A-12 PLANS 48 91

12.ET601 BUILDING 12, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 49 91

13.ET411 BUILDING 13, LEVEL A, TELECOM ROOM 104-13 PLANS 50 91

13.ET421 BUILDING 13, LEVEL B, TELECOM ROOM 224-13 PLANS 51 91

13.ET601 BUILDING 13, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 52 91

14.ET401 BUILDING 14, LEVEL C, TELECOM ROOM BM104A-14 PLANS 53 91

14.ET411 BUILDING 14, LEVEL A, TELECOM ROOM 101A-14 PLANS 54 91

14.ET421 BUILDING 14, LEVEL B, TELECOM ROOM 232-14 PLANS 55 91

14.ET601 BUILDING 14, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 56 91

15.ET411 BUILDING 15, LEVEL A, TELECOM ROOM 107-15 PLANS 57 91

15.ET421 BUILDING 15, LEVEL B, TELECOM ROOM 230-15 PLANS 58 91

15.ET601 BUILDING 15, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 59 91

16.ET401 BUILDING 16, LEVEL C, TELECOM ROOM B11A-16 PLANS 60 91

16.ET421 BUILDING 16, LEVEL B, TELECOM ROOM 216-16 PLANS 61 91

16.ET601 BUILDING 16, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 62 91

17.ET411 BUILDING 17, LEVEL A, TELECOM ROOM 111-17 PLANS 63 91

17.ET421 BUILDING 17, LEVEL B, TELECOM ROOM 205-17 PLANS 64 91

17.ET601 BUILDING 17, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 65 91

19.ET411 BUILDING 19, LEVEL A, TELECOM ROOM 117-19 PLANS 66 91

19.ET421 BUILDING 19, LEVEL B, TELECOM ROOM 216A-19 PLANS 67 91

19.ET601 BUILDING 19, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 68 91

25.ET411 BUILDING 25, LEVEL A, TELECOM ROOM 101A-25 PLANS 69 91

25.ET601 BUILDING 25, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 70 91

26.ET401 BUILDING 26, LEVEL C, TELECOM ENCLOSURE BM108B-26 PLANS 71 91

26.ET411 BUILDING 26, LEVEL A, TELECOM ROOM 106-26 PLANS 72 91

26.ET601 BUILDING 26, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 73 91

27.ET411 BUILDING 27, LEVEL A, TELECOM ROOM 107-27 PLANS 74 91

27.ET601 BUILDING 27, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 75 91

28.ET411 BUILDING 28, LEVEL A, TELECOM ROOM 108-28 PLANS 76 91

28.ET601 BUILDING 28, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 77 91

29.ET411 BUILDING 29, LEVEL A, TELECOM ENCLOSURE 113A-29 PLANS 78 91

29.ET601 BUILDING 29, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 79 91

30.ET411 BUILDING 30, LEVEL A, TELECOM ENCLOSURE 104-30 PLANS 80 91

30.ET601 BUILDING 30, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 81 91

40.ET412 BUILDING 40, LEVEL A, COMPUTER ROOM 106 TECHNOLOGY PLANS 82 91

85.ET411 BUILDING 85, LEVEL A, TELECOM ROOM 121-85 PLANS 83 91

85.ET601 BUILDING 85, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 84 91

86.ET411 BUILDING 86, LEVEL A, TELECOM ROOM 106-86 PLANS 85 91

86.ET601 BUILDING 86, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 86 91

87.ET411 BUILDING 87, LEVEL A, TELECOM ROOM 120-87 PLANS 87 91

87.ET412 BUILDING 87, LEVEL A, TELECOM ROOM 169-87 PLANS 88 91

87.ET601 BUILDING 87, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 89 91

89.ET411 BUILDING 89, LEVEL A, TELECOM ROOM 1215-89 PLANS 90 91

89.ET601 BUILDING 89, SINGLE LINE, BONDING, AND FIBER RISER DIAGRAMS 91 91

VOLUME 4 OF 4

Docusign Envelope ID: B71C0D48-D83D-418C-8E57-61AA26C33206

11/8/202411/8/2024

S SS

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA

TYPE

EQUIPMENT CONNECTIONAS

NOTED

E

AS

SPECIFIED

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

120V SIMPLEX RECEPTACLE18"

2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED7'-0"

CENTER

4' LINEAR - WALL MOUNTED7'-0"

CENTER

WALL SCONCE6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

UPS UNINTERUPTABLE POWER

SUPPLY

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PDU POWER DISTRIBUTION UNIT

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYPBD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HARD WIRED

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.

CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE

APPROXIMATE ONLY (FIELD VERIFY).

BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED.

THE CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.

EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR

INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.

OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR

SHALL CUT OFF CONDUITS AND REMOVE WIRING.

WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE

LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.

WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP

OR PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF

AND CAPPED OR PLUGGED.

THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK.

ALL RESTORATION WORK SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.

ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO

MEET THE REQUIREMENTS AND INTENT OF THE PROJECT.

EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND

NEW AREAS.

ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.

CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO

ACCOMPLISH THIS REQUIREMENT.

EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS

REQUIREMENT.

IF POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES SHALL BE INSTALLED IN SEPERATE OR ADJACENT STUD SPACES TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. IF NOT POSSIBLE, ALL NEWLY INSTALLED ELECTRICAL BOXES LOCATED IN COMMON STUD SPACES INSTALLED ON OPPOSITE SIDES OF FIRE-RESISTANCE RATED WALLS SHALL BE EQUIPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE

WITH NEC 300.21 AND IBC 714.4.2.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT, SPECIFICATIONS, AND THE APPLICABLE BUILDING CODES.

VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

A.

B.

C.

D.

E.

F.

11.

RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE

REMOVED FROM THE PREMISES.

ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER

TRADES.

REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES

CONTINUATION THROUGH THE AREA.

ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.

ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND

NEW CONSTRUCTION.

ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING

TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.

REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.

MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR

SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT

OF FEED WITH AN ENGRAVED BRASS TAG.

REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.

EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

2 HOUR FIRE SEPARATION

1 HOUR FIRE SEPARATION

SMOKE RATED

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/5

/2

8:

:0

AM

C :\U se rs

\c gr iff itt

\D oc um en ts \T

R R oo m

D et ai ls

_R

_c gr iff itt

W H

M

PZ

.rv t

00.ET001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 91PDN

EHRM INFRASTRUCTURE

UPGRADES

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027 NOVEMBER 8, 2024

100% BID DOCUMENTS

557-22-70022-192

KTK

ELECTRICAL SYMBOL LEGEND

LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES GENERAL ELECTRICAL REMODELING NOTES

ELECTRICAL GENERAL NOTES

GENERAL ELECTRICAL DEMO NOTES

TEMPORARY FIRESTOPPING

METHOD OF SHORT CIRCUIT CURRENT CALCULATIONSWALL RATING LEGEND

Docusign Envelope ID: 7AE0511C-6224-4AC1-A0CA-266A39A191A9

11/6/2024 11/7/2024

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

TELCO OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD)48"CR

ES

DC

RX

48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)

WIRELESS ACCESS POINT - N-4 PR UTP

WALL PHONEW

N

S

NURSE CALL PATIENT STATION WITH PILLOW SPEAKER

2 ADDITIONAL PUSHBUTTONS, 1/4 RECEPTACLE AND COVER

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

P NURSE CALL PATIENT BED INTERFACE RECEPTACLE

B NURSE CALL CODE BLUE STATION WITH COVER

E NURSE CALL EMERGENCY STATION WITH PULL CORD AND AUDIO +40" AFF IN

RESTROOM, +72" AFF IN SHOWER (V - VANDAL RESISTANT, PB - PUSH BUTTON)

D NURSE CALL DUTY STATION

M NURSE CALL MASTER STATION/CONSOLE

NURSE CALL DOME LIGHT

(Z - ZONE LIGHT, V - VANDAL RESISTANT)

IC INTERCOM WITH CAMERA

IC INTERCOM MASTER WITH PUSH TO RELEASE DOORM

NURSE CALL WIRELESS ANTENNASNW

N

TV OUTLET WALL MOUNTED

48"

54"

DESK

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST CHANNEL RACK

OIT EQUIPMENT CABINET

NURSE CALL EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

NCE

MATV

CCTV

BASKET CABLE TARY

N

N

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

HEADWALL

18"

HEADWALL

/40"

40", 72"

18"

60"

CEILING

CEILING

6' TO TOP

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

HANDWAVE

T

C

NURSE CALL STAFF TERMINAL

NURSE CALL PATIENT STATION WITH CALL CORD.

(1 - SINGLE, 2 - DUAL, V - VANDAL RESISTANT)

60"

HEADWALL

W WIRELESS PENDANT

L

KP PATIENT ROAM ALERT ACCESS CONTROL KEYPAD48"

PATIENT ROAM ALERT ANTENNACEILING

GROUND BUS

CEILING

DOOR

DOOR

48"

ABOVE

DOOR

NURSE CALL DOME LIGHT

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

N M

PATIENT STATION (PB - PUSH BUTTON, M - MICROPHONE, K -KEYED)

88" MOTION DETECTORMD

FLOOR 6", 12" VERTICAL WIRE MANAGEMENT

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

AREA OF REFUGE PANEL6' TO TOP

AREA OF REFUGE ANNUNCIATION PANEL6' TO TOP

AOF

AOFA

IC AREA OF REFUGE INTERCOM48"

AREA OF REFUGE STROBE LIGHTCEILINGSL

DP

DPP

DURESS PANIC ALARM PUSH BUTTON48"

DURESS PANIC ALARM PANEL6' TO TOP

N

SECURE WIRELESS ACCESS POINT - N-4 PR UTP

N

CEILING

S

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

CEILING

48"

CEILING

CEILING

TELEMETRY ANTENNA - 2-4 PRCEILING

ROBOT PHARMACY ANTENNA - 1-4 PRCEILINGR

CABLE LADDERABOVE

CEILING

CABLES AND CONNECTORS COLOR LEGEND

DESCRIPTION

ITEM JACK CABLE PATCH CABLES I.D. NOTES

DATA/COMPUTER

WIRELESS

ACCESS POINT

FIBER - MULTI-MODE

FIBER - SINGLE-MODE

CCTV - IP

BLUE

GREEN

BLACK

IVORY

WHITE

BLUE

GREEN

AQUA

YELLOW

WHITE

BLUE

GREEN

AQUA

YELLOW

WHITE

C

WAP

FO

FO

CCTV

4 PAIR CABLE

4 PAIR CABLE

6/12/24/36

6/12

PACS N/A GRAY N/A PACS MULTI COLOR

CONDUCTORS

4 PAIR CABLE

ADO AUTOMATIC DOOR OPERATOR

AFF ABOVE FINISH FLOOR

BOD BASIS OF DESIGN

CCTV CLOSED CIRCUIT TELEVISION

COAX COAXIAL CABLE

COMM COMMUNICATION

COR CONTRACTING OFFICER REPRESENTATIVE

DC DOOR CONTACT SWITCH

DN DOWN

DO DOOR OPERATOR

DVC DIGITAL VOICE COMMAND

DVR DIGITAL VIDEO RECORDER

E EXISTING DEVICES

EEB EMERGENCY EXIT BUTTON

EL ELECTRICAL STRIKE

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FO FIBER OPTIC

FAGAP FIRE ALARM GRAPHIC ANNUNCIATOR PANEL

IT INTERCOMMUNICATION ROOM

MATV MASTER ANTENNA TELEVISION

MDA MAIN DISTRIBUTION AREA

MM MULTI MODE FIBER

NAC NETWORK APPLIANCE CIRCUIT PANEL

N NEW DEVICES

NCA NETWORK CONTROL ANNUNCIATOR

NS NO SCALE

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

TECHNOLOGY ABBREVIATIONS LIST

OC ON CENTER

OIT OFFICE OF INFORMATION TECHNOLOGY

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM

PB PUSH BUTTON

PBB PRIMARY BONDING BUSBAR

PDU POWER DISTRIBUTION UNIT

POE POWER OVER ETHERNET

PR PAIR

RBB RACK BONDING BUSBAR

rPDU RACK POWER DISTRIBUTION UNIT

RX REQUEST TO EXIT

SBB SECONDARY BONDING BUSBAR

SEP SERVICE ENTRANCE PROTECTION

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE FIBER

TBB TELECOM BACKBONE CONDUCTOR

TEL TELEPHONE

TGB TELECOM GROUND BUS BAR

TM TELEMONITORING

TMGB TELECOM MAIN GROUND BUS BAR

TP TWISTED PAIR

TR TELECOM ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

WM WIRE MANAGEMENT

WAP WIRELESS ACCESS POINT

WAO WORK AREA OUTLET

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

TECHNOLOGY GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA

STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT

SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL

LISTING REQUIREMENT, SPECIFICATIONS, AND APPLICABLE BUILDING CODES.

PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION

METHOD MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607-D - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

COMPLY WITH THE LATEST ANSI/TIA/EIA 568B - COMMERCIAL BUILDING TELECOMMUNICATIONS WIRING

STANDARD.

COMPLY WITH THE LATEST ANSI/TIA/EIA 569B - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.

COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN

ACT".

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY

TESTING AGENCY.

NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE

MORE STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.

ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B.

LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606C OR 606B EDITION AS WELL AS THE STANDARDS

SET FORTH BY THE VA HOSPITAL OIT.

PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY PER TIA/EIA 569-D.

VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND

EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.

ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

UNLESS OTHERWISE INDICATED, MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT. CONTRACTOR TO RE-USE

EXISTING CONDUIT WHERE AVAILABLE.

WALL MOUNTED DEVICES PLACED IN TELECOM ROOM SHALL BE MOUNTED ON FIRE RETARDANT PLYWOOD.

PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS

FOR A COMPLETE SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.

26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING (BOTH FIBER AND COPPER), JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, BONDING BUS BARS, RACK MOUNTED BONDING BUS, BONDING CABLING, BONDING TO THE GROUNDING SYSTEM, BONDING CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS

DESCRIBED IN THE SPECIFICATIONS.

27. PROVIDE J-HOOKS OR FLEXIBLE CONDUITS WHERE CABLE TRAY IS NOT SHOWN, OR IF THE PATH OF THE CABLE TRAY IS OBSTRUCTED. PROVIDE JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, AND COVER PLATES AS NEEDED OR WHERE REQUIRED BY CODE. LABEL AND SUPPORT J-HOOKS, CABLE TRAY, AND

CONDUIT AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

28. PROVIDE 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN EACH NEW TR AND RUN 12 CAT 6A CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.

29. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.

30. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS. CAMERAS SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-

NDAA.

31. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

32. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.

33. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.

34. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD

END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE

REPRESENTATIVE.

35. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.

GENERAL TECHNOLOGY DEMOLITION NOTES

1.

2.

3.

4.

5.

ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).

EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO

THE EXISTING CABLE TRAY.

EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH

THE COR.

EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES.

REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE

UPS AND POWER SOURCE IN TACT.

CONTRACTOR TO REFER TO TELECOMM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL INFORMATION.

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/5

/2

8:

:0

AM

C :\U se rs

\c gr iff itt

\D oc um en ts \T

R R oo m

D et ai ls

_R

_c gr iff itt

W H

M

PZ

.rv t

00.ET002

TECHNOLOGY GENERAL NOTES,

SYMBOL LEGEND, AND

ABBREVIATIONS

2 91PDN

EHRM INFRASTRUCTURE

UPGRADES

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027 NOVEMBER 8, 2024

100% BID DOCUMENTS

557-22-70022-192

KTK

CONDITIONAL NOTE

E

CR

DC ES RX J

M

10 10

PANEL 'A' PANEL 'B'

00.ET5016

A-13,15,17

B-13,15,17

SBB

K

A-2

B-2

A-2

A-2 N

GFIB-2

B-2

A-2

B-2

48"

A

B

C

C

CC

FIRE RATED PATHWAYS

PANEL 'A'1

SBB/PBB

BASKET TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

MOTOR-RATED

SWITCH

16 16

PANEL 'B'PANEL 'A'

BASKET TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

SBB/PBB

DATA PORT

LIGHT SWITCH

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

(M

IN

8'

-0

BASKET TRAY

PANEL 'B'

SBB

NEC REQUIRED WORKING

CLEARANCE, 30" WIDE BY

36" DEEP BY 72" HIGH

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

16 16BASKET TRAY

Engineers Architects

# NEW KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/5

/2

8:

:0

AM

C :\U se rs

\c gr iff itt

\D oc um en ts \T

R R oo m

D et ai ls

_R

_c gr iff itt

W H

M

PZ

.rv t

00.ET501

TYPICAL TELECOM ROOM DETAILS

3 91PDN

EHRM INFRASTRUCTURE

UPGRADES

CARL VINSON VA MEDICAL CENTER

1826 VETERANS BLVD

DUBLIN, GA 31027 NOVEMBER 8, 2024

100% BID DOCUMENTS

557-22-70022-192

KTK

1 ROOMS ARE COOLED WITH DUCTLESS

MINI-SPLITS. DUCTLESS MINI-SPLIT UNITS SHALL

BE POWERED FROM THEIR ASSOCIATED

OUTDOOR CONDENSING UNITS. PROVIDE A

CIRCUIT TO THE CONDENSING UNIT, INCLUDING

RACEWAYS AND CONDUCTORS TO POWER THE

INDOOR UNITS.

2 TELECOMMUNICATIONS CHANNEL RACK,23.75

INCHES WIDE, 30 INCHES DEEP, 84 INCHES HIGH,

45RU, WHITE. PROVIDE ORTRONICS (LEGRAND)

MM2073038-W, OR APPROVED EQUIVALENT.

CONTRACTOR SHALL COORDINATE ADDITIONAL

DETAILS INCLUDING BUT NOT LIMITED TO

GROUNDING AND BONDING DETAILS, DATA

ELEVATIONS AND POWER ELEVATIONS IN THE

DRAWINGS.

3 VERTICAL CABLE MANAGEMENT CAGE WITH

DOOR, 6 INCHES WIDE, 84 INCHES HIGH, 45RU,

WHITE. PROVIDE ORTRONICS (LEGRAND)

MM20VMD706-W, OR APPROVED EQUIVALENT.

4 RACK POWER CONNECTION MOUNTED TO THE

CHANNEL STEEL ABOVE THE RACKS MINIMUM 12"

AWAY FROM CABLE TRAY. FOR EACH RACK,

PROVIDE L21-20R RECEPTACLE. PROVIDE (3) 12

AWG AND (1) 10 AWG NEUTRAL (1) 12 AWG GND IN

3/4" CONDUIT. REFER TO RACK POWER

ELEVATION AND SCHEMATIC DIAGRAMS ON

SHEET 00.ET505.

5 SECONDARY BONDING BUSBAR TO BE LOCATED

BEHIND OR TO THE SIDE OF THE RACKS.

TELECOMMUNICATIONS EQUIPMENT SHALL BE

BONDED ACCORDING TO THE GROUNDING AND

BONDING DETAILS. REFER TO DETAILS 3 AND 4

ON SHEET 00.ET503 FOR MORE INFORMATION.

6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE UL

LISTED ASSEMBLIES, STI EZ-PATH, SERIES 44+

FOR 4” FIRE-RATED PATHWAY, OR APPROVED

EQUIVALENT. INSTALL SLEEVES ABOVE DOOR

HEADER AT AN ELEVATION COORDINATED TO BE

ABOVE THE EXISTING CEILING HEIGHT IN THE

ADJACENT CORRIDOR. REFER TO 400 SERIES ET

SHEETS FOR QUANTITIES.

7 PROVIDE NEW BASKET CABLE TRAY

THROUGHOUT ROOM AND ABOVE THE CHANNEL

RACKS. PROVIDE WITH WATERFALL DROPOUTS

INTO EACH RACK, 90 DEGREE CORNERS AND ALL

RELATED FITTINGS. SEE DETAIL 10 ON 00.ET504

FOR MORE INFO. B.O.D.: CABLOFIL CF105/600 AND

CF150/600 SERIES OR EQUIVALENT.

8 PROVIDE TWO RECEPTACLES ON EACH WALL, AS

SHOWN WITH ONE BEING FED FROM PANEL 'A'

THE OTHER FROM PANEL 'B'.

9 FIRE RETARDANT PLYWOOD BACKBOARD,

PAINTED ON ALL 6 SIDES. SEE ARCHITECTURAL

DRAWINGS FOR MORE DETAILS.

10 LIGHTING AND APPLIANCE PANELBOARDS.

PROVIDE PANELS MOUNTED ON CHANNEL STEEL

SUPPORTS. UNLESS NOTED OTHERWISE ON THE

400 SERIES ET SHEETS, PANEL 'A' SHALL BE FED

FROM A SOURCE WITH GENERATOR BACKUP, AND

PANEL 'B' SHALL BE FED FROM A NORMAL UTILITY

SOURCE.

12 PROVIDE 120V POWER FOR 8"X8"X4" HINGED

CONTROLLER BOX MOUNTED ABOVE DOOR.

REFERENCE DETAIL ON SHEET 5/00.E-503.

13 PROVIDE CABLING FOR VA FURNISHED WIRELESS

ACCESS POINT.

14 PROVIDE RECEPTACLE NEAR DOOR, WITH POWER

EXTENDED FROM AN EXISTING CONVENIENCE

OUTLET CIRCUIT ORIGINATING FROM A PANEL

NOT IN THE ROOM.

15 PROVIDE WALL PHONE OUTLET IN EVERY

TELECOM ROOM.

16 BASKET CABLE TRAY IS SHOWN OFFSET FROM

WALL FOR GRAPHICAL PURPOSES ONLY. INSTALL

CABLE TRAY FLUSH WITH WALL EXCEPT ABOVE

POWER PANELS AND MECHANICAL EQUIPMENT

WHERE SPACE IS NEEDED FOR PIPES AND

CONDUIT.

17 PROVIDE MULTI SENSOR CAMERA AND CONNECT

TO EXISTING CAMERA SYSTEM.

18 LIGHTING TO BE FED FROM CLOSEST EXISTING

CRITICAL LIGHTING CIRCUIT IN HALLWAY.

Scale: 3/8" = 1'-0"1 ELECTRICAL FLOOR PLAN - TYPICAL 3-RACK TR Scale: 3/8" = 1'-0"2 ELECTRICAL CEILING PLAN - TYPICAL 3-RACK TR

Scale: 3/8" = 1'-0"6 PLAN WEST ELEVATION Scale: 3/8" = 1'-0"5 PLAN NORTH ELEVATION

Scale: 3/8" = 1'-0"3 PLAN SOUTH ELEVATION Scale: 3/8" = 1'-0"4 PLAN EAST ELEVATION

PER PHASE CONNECTED LOAD: 3.85 kVA 3.33 kVA 3.16 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

29 0 -- 30 1 -- SPACE

27 0 -- 28 1 -- SPACESPARE

(SEE PANEL NOTE 1 BELOW) 20 A 3

25 0 -- 26 1 -- SPACE

23 0 -- 24 1 -- SPACE

21 0 -- 22 1 -- SPACERACK RECEPTACLE 20 A 3

19 0 0 20 17 1.66 0 18

2 30 A SPARE

15 1.66 0 16RACK RECEPTACLE 20 A 3

13 1.66 0 14

2 30 A SPARE

11 1.66 0 12 1 20 A PACS J-BOX

9 1.66 0 10 1 20 A CONDENSATE PUMPRACK RECEPTACLE 20 A 3

7 1.66 0 8 1 20 A SPARE

5 0 0 6 1 20 A SPARE

3 0 0.18 4 1 20 A CONVENIENCE RCPTSURGE PROTECTIVE DEVICE

(SEE PANEL NOTE 4 BELOW) 30 A 3

1 0 0.72 2 1 20 A TELECOM ROOM RCPT

LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction

MOUNTING: SURFACE FED FROM: LOCATION:PANEL: A

VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC: 10,000 AMPS

SYMMETRICAL

PER PHASE CONNECTED LOAD: 5.47 kVA 4.76 kVA 4.76 kVA

SPACE -- 1 41 -- -- 42 1 -- SPACE

SPACE -- 1 39 -- -- 40 1 -- SPACE

SPACE -- 1 37 -- -- 38 1 -- SPACE

SPACE -- 1 35 -- -- 36 1 -- SPACE

SPACE -- 1 33 -- -- 34 1 -- SPACE

SPACE -- 1 31 -- -- 32 1 -- SPACE

29 0 -- 30 1 -- SPACE

27 0 -- 28 1 -- SPACESPARE

(SEE PANEL NOTE 1 BELOW) 20 A 3

25 0 -- 26 1 -- SPACE

23 1.66 -- 24 1 -- SPACE

21 1.66 -- 22 1 -- SPACERACK RECEPTACLE 30 A 3

19 1.66 0 20 1 20 A SPARE

17 1.66 0 18 1 20 A SPARE

15 1.66 0 16 1 20 A SPARERACK RECEPTACLE 20 A 3

13 1.66 0 14 1 20 A SPARE

11 1.66 0 12 1 20 A SPARE

9 1.66 0 10 1 20 A SPARERACK RECEPTACLE 20 A 3

7 1.66 0 8 1 20 A SPARE

5 0 0 6 1 20 A SPARE

3 0 0 4 1 20 A SPARESURGE PROTECTIVE DEVICE

(SEE PANEL NOTE 3 BELOW) 30 A 3

1 0 0.72 2 1 20 A TELECOM ROOM RCPT

LOAD NAME BKR P CKT A (kVA) B (kVA) C (kVA) CKT P BKR LOAD NAME ENCLOSURE: NEMA 1 BRANCH: SEE ONE-LINE EXISTING/NEW: New Construction

MOUNTING: SURFACE FED FROM: LOCATION:PANEL: B

VOLTAGE: 120/208V, 3PH, 4W MAINS: 100 A MLO AIC: 10,000 AMPS

SYMMETRICAL

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

C 4' LINEAR LED STRIPLIGHT WITH FROSTED

LENS

CHAIN

SUSPEND

LED; 4,585

LUMENS; 80 CRI;

3500K

ELECTRONIC

LED DRIVER

MVOLT 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 35K 80CRI BAA

D 4' LINEAR LED WALL BRACKET WITH FROSTED

LENS MOUNTED AT 8' 6"

WALL

MOUNTED

LED; 4,585

LUMENS; 80 CRI;

3500K

ELECTRONIC

LED DRIVER

MVOLT 40 W LITHONIA WL4 40L MVOLT LP835 BAA

F 2' X 4' ARCHITECTURAL TROFFER; WITH

CURVED, SMOOTH CENTER DIFFUSER; TO

MATCH EXISTING

RECESSED

GRID

LED; 4800

LUMENS; 80 CRI;

3500K

0-10V

DIMMABLE TO

5% DRIVER

MVOLT 38 W LITHONIA 2BLT4 48L ADSM EZ1 LP835 BAA

P1 4" X 10'-0" DIRECT LINEAR…

This is the start of the file's text. The full file is on GovTribe.