Atch 2 - Annual Hydrant Flow Report_9JUL25 - Dublin - 557-22-700.xlsx
XLSX spreadsheet 104 KB Posted
- Solicitation number
- 36C77625B0013
About this file
This document is an Annual Hydrant Flow Report for the Carl Vinson VA Medical Center in Dublin, GA, dated 7/9/25. The comprehensive inspection report covers 24 fire hydrants across the medical center campus, detailing their physical condition, water pressure, flow rates, and specific location characteristics. The inspection was conducted by Robert Saltz and witnessed by various VA personnel including David Earnest and Michael Walenceus.
Key findings include generally good physical conditions for most hydrants, with two notable exceptions: Hydrant #7 has a broken stem with a free-spinning operating nut, rendering it non-functional, and Hydrant #21 is leaning as if struck by a vehicle. Most hydrants demonstrated consistent initial pressures around 70 PSI, with flow rates between 750-1350 GPM. Two new hydrants were added near Buildings 29 and 89. The report recommends repair of Hydrant #21 to restore its upright position and addresses the non-operational status of Hydrant #7, which could impact emergency water supply capabilities for the medical center.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TR2039: TR2039:
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4121 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 11:10AM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 1 | 2 | 3 | 4 |
| PHYSICAL LOCATION | End of Bldg. 5 | 5A Clinic Amb Ent. | 5A Clinic P/Lot | Beside Bldg 9 |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | |||||||||
| INITIAL | 68 | PSI | 70 | PSI | 70 | PSI | 70 | PSI | |
| RESIDUAL | 55 | PSI | 55 | PSI | 55 | PSI | 45 | PSI | |
| PITOT | 58 | PSI | 55 | PSI | 55 | PSI | 20 | PSI |
| FLOW GPM | 1280 | 1250 | 750 | 750 | |
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | 1 | |
| WATER USED - GALLONS | |||||
| PHYSICAL CONDITION | |||||
| PAINT | GOOD | GOOD | GOOD | GOOD | |
| CHAINS | GOOD | GOOD | GOOD | GOOD | |
| CAPS | GOOD | GOOD | GOOD | GOOD | |
| STEMS | GOOD | GOOD | GOOD | GOOD | |
| PACKING | GOOD | GOOD | GOOD | GOOD | |
| O RING | GOOD | GOOD | GOOD | GOOD | Do not change |
| OPERATING NUT | GOOD | GOOD | GOOD | GOOD | the value in cell D34 |
| VALVE | GOOD | GOOD | GOOD | GOOD | |
| VALVE SEAT | GOOD | GOOD | GOOD | GOOD | |
| CONDITION OF WATER | CLEAR | CLEAR | GOOD | CLEAR | |
| REMARKS: |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 11:20AM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 5 | 6 | 7 | 8 |
| PHYSICAL LOCATION | End of Bldg 13 | Bldg 17/19 P/Lot | Bldg 17/19 P/Lot | Bldg 30 Canine |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | |||||||||
| INITIAL | 70 | PSI | 70 | PSI | 0 | PSI | 72 | PSI | |
| RESIDUAL | 55 | PSI | 55 | PSI | 0 | PSI | 55 | PSI | |
| PITOT | 55 | PSI | 55 | PSI | 0 | PSI | 55 | PSI |
| FLOW GPM | 1250 | 1250 | 0 | 1250 | ||
| TIME FLUSHED, IN MINUTES | 1 | 1 | 0 | 1 | ||
| WATER USED - GALLONS | ||||||
| PHYSICAL CONDITION | ||||||
| PAINT | GOOD | GOOD | GOOD | GOOD | ||
| CHAINS | GOOD | GOOD | GOOD | GOOD | ||
| CAPS | GOOD | GOOD | GOOD | GOOD | ||
| STEMS | GOOD | GOOD | GOOD | GOOD | ||
| PACKING | GOOD | GOOD | GOOD | GOOD | ||
| O RING | GOOD | GOOD | GOOD | GOOD | Do not change | |
| OPERATING NUT | GOOD | GOOD | GOOD | GOOD | the value in cell D34 | |
| VALVE | GOOD | GOOD | GOOD | GOOD | ||
| VALVE SEAT | GOOD | GOOD | GOOD | GOOD | ||
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | CLEAR | ||
| REMARKS: | Hydrant Number 7 Has A Broke Stem And Operating Nut Is Free Spinning. Could Not Flow |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 11:45AM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | Michael Walenceus |
| HYDRANT # | 9 | 10 | 11 | 12 |
| PHYSICAL LOCATION | Behind Bldg 29 | End of Bldg 15 | Bldg 28 | End of Bldg 11 |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | ||||||||
| INITIAL | 72 | PSI | 70 | PSI | PSI | 70 | PSI | |
| RESIDUAL | 55 | PSI | 55 | PSI | PSI | 55 | PSI | |
| PITOT | 55 | PSI | 55 | PSI | PSI | 55 | PSI |
| FLOW GPM | 1250 | 1250 | 1250 | |
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | |
| WATER USED - GALLONS | ||||
| PHYSICAL CONDITION | ||||
| PAINT | GOOD | GOOD | GOOD | |
| CHAINS | GOOD | GOOD | GOOD | |
| CAPS | GOOD | GOOD | GOOD | |
| STEMS | GOOD | GOOD | GOOD | |
| PACKING | GOOD | GOOD | GOOD | |
| O RING | GOOD | GOOD | GOOD | Do not change |
| OPERATING NUT | GOOD | GOOD | GOOD | the value in cell D34 |
| VALVE | GOOD | GOOD | GOOD | |
| VALVE SEAT | GOOD | GOOD | GOOD | |
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | |
| REMARKS: |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 12:00PM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 13 | 14 | 15 | 16 |
| PHYSICAL LOCATION | Chiller Plant | Bldg 4 Ramp | Bldg. 26 By Boiler | Bldg 12 |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | |||||||||
| INITIAL | 70 | PSI | 70 | PSI | 70 | PSI | 70 | PSI | |
| RESIDUAL | 50 | PSI | 50 | PSI | 55 | PSI | 55 | PSI | |
| PITOT | 50 | PSI | 50 | PSI | 55 | PSI | 55 | PSI |
| FLOW GPM | 1190 | 1250 | 1250 | ||
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | ||
| WATER USED - GALLONS | |||||
| PHYSICAL CONDITION | |||||
| PAINT | GOOD | GOOD | GOOD | GOOD | |
| CHAINS | GOOD | GOOD | GOOD | GOOD | |
| CAPS | GOOD | GOOD | GOOD | GOOD | |
| STEMS | GOOD | GOOD | GOOD | GOOD | |
| PACKING | GOOD | GOOD | GOOD | GOOD | |
| O RING | GOOD | GOOD | GOOD | GOOD | Do not change |
| OPERATING NUT | GOOD | GOOD | GOOD | GOOD | the value in cell D34 |
| VALVE | GOOD | GOOD | GOOD | GOOD | |
| VALVE SEAT | GOOD | GOOD | GOOD | GOOD | |
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | CLEAR | |
| REMARKS: |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 12:15PM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 17 | 18 | 19 | 20 |
| PHYSICAL LOCATION | Bldg 16 | Behind Bldg. 86 | Parking By 86 | End of Bldg 8 |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | |||||||||
| INITIAL | 70 | PSI | 70 | PSI | 70 | PSI | 70 | PSI | |
| RESIDUAL | 60 | PSI | 60 | PSI | 60 | PSI | 60 | PSI | |
| PITOT | 60 | PSI | 60 | PSI | 60 | PSI | 65 | PSI |
| FLOW GPM | 1300 | 1300 | 1300 | 1350 | |
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | 1 | |
| WATER USED - GALLONS | |||||
| PHYSICAL CONDITION | |||||
| PAINT | GOOD | GOOD | GOOD | GOOD | |
| CHAINS | GOOD | GOOD | GOOD | GOOD | |
| CAPS | GOOD | GOOD | GOOD | GOOD | |
| STEMS | GOOD | GOOD | GOOD | GOOD | |
| PACKING | GOOD | GOOD | GOOD | GOOD | |
| O RING | GOOD | GOOD | GOOD | GOOD | Do not change |
| OPERATING NUT | GOOD | GOOD | GOOD | BROKEN | the value in cell D34 |
| VALVE | GOOD | GOOD | GOOD | GOOD | |
| VALVE SEAT | GOOD | GOOD | GOOD | GOOD | |
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | CLEAR | |
| REMARKS: | |||||
| Hydrant #20 -- operating nut cap has broken off top of hydrant. Hydrant can still be flowed. |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 12:30PM | |
| Dublin, GA 31021 | |||
| Attn: Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 21 | 22 | 23 | 24 |
| PHYSICAL LOCATION | End of Bldg 6 | Front Gate | Front of Bldg 1 | Front of Bldg 1 |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | |||||||||
| INITIAL | 70 | PSI | 66 | PSI | 66 | PSI | 66 | PSI | |
| RESIDUAL | 55 | PSI | 50 | PSI | 50 | PSI | 50 | PSI | |
| PITOT | 55 | PSI | 50 | PSI | 50 | PSI | 50 | PSI |
| FLOW GPM | 1250 | 1190 | 1190 | 1190 | |
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | 1 | |
| WATER USED - GALLONS | |||||
| PHYSICAL CONDITION | |||||
| PAINT | GOOD | GOOD | GOOD | GOOD | |
| CHAINS | GOOD | GOOD | GOOD | GOOD | |
| CAPS | GOOD | GOOD | GOOD | GOOD | |
| STEMS | GOOD | GOOD | GOOD | GOOD | |
| PACKING | GOOD | GOOD | GOOD | GOOD | |
| O RING | GOOD | GOOD | GOOD | GOOD | Do not change |
| OPERATING NUT | GOOD | GOOD | GOOD | GOOD | the value in cell D34 |
| VALVE | GOOD | GOOD | GOOD | GOOD | |
| VALVE SEAT | GOOD | GOOD | GOOD | GOOD | |
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | CLEAR | |
| REMARKS: | |||||
| Hydrant #21 is leaning, as if struck by a vehicle. Recommend it be repaired to upright position. |
| do not change | |
| Power | 0.54 |
ERROR:#VALUE!
ERROR:#VALUE!
| 1350 Northmeadow Pkwy. Suite 100 |
| Roswell, GA 30076 |
| 678-896-4090 |
| FIRE HYDRANT INSPECTION & FLOW TEST REPORT |
| LOCATION: | Carl Vinson VA Medical Center | DATE: | 7/9/25 |
| 1826 Veterans Blvd. | TIME: | 12:45PM | |
| Dublin, GA 31021 | |||
| Attn:Jason Scott |
| TEST MADE BY: | Robert Saltz |
| WITNESSED BY: | David Earnest |
| HYDRANT # | 25 | 29 | 29 | |
| PHYSICAL LOCATION | Front of Bldg 86 | Back Of Bldg 29 | Front Of Bldg 29 | |
| NOZZLE SIZE | 2.5 INCH | 2.5 INCH | 2.5 INCH | 2.5 INCH |
| PRESSURES | ||||||||
| INITIAL | 70 | PSI | 66 | PSI | 66 | PSI | PSI | |
| RESIDUAL | 60 | PSI | 60 | PSI | 60 | PSI | PSI | |
| PITOT | 60 | PSI | 60 | PSI | 60 | PSI | PSI |
| FLOW GPM | 1300 | 1190 | 1190 | ||
| TIME FLUSHED, IN MINUTES | 1 | 1 | 1 | ||
| WATER USED - GALLONS | |||||
| PHYSICAL CONDITION | |||||
| PAINT | GOOD | GOOD | GOOD | ||
| CHAINS | GOOD | GOOD | GOOD | ||
| CAPS | GOOD | GOOD | GOOD | ||
| STEMS | GOOD | GOOD | GOOD | ||
| PACKING | GOOD | GOOD | GOOD | ||
| O RING | GOOD | GOOD | GOOD | Do not change | |
| OPERATING NUT | GOOD | GOOD | GOOD | the value in cell D34 | |
| VALVE | GOOD | GOOD | GOOD | ||
| VALVE SEAT | GOOD | GOOD | GOOD | ||
| CONDITION OF WATER | CLEAR | CLEAR | CLEAR | ||
| REMARKS: | 2 New Hydrants Were Added For Bldg. 29 And 1 At Building 89. |