About this file
Written by GovTribe AI
· Jul 18, 2025
This document is an Annual Hydrant Flow Report for the Carl Vinson VA Medical Center in Dublin, GA, dated 7/9/25. The comprehensive inspection report covers 24 fire hydrants across the medical center campus, detailing their physical condition, water pressure, flow rates, and specific location characteristics. The inspection was conducted by Robert Saltz and witnessed by various VA personnel including David Earnest and Michael Walenceus.
Key findings include generally good physical conditions for most hydrants, with two notable exceptions: Hydrant #7 has a broken stem with a free-spinning operating nut, rendering it non-functional, and Hydrant #21 is leaning as if struck by a vehicle. Most hydrants demonstrated consistent initial pressures around 70 PSI, with flow rates between 750-1350 GPM. Two new hydrants were added near Buildings 29 and 89. The report recommends repair of Hydrant #21 to restore its upright position and addresses the non-operational status of Hydrant #7, which could impact emergency water supply capabilities for the medical center.
Other files for this federal contract opportunity
Other files attached to Z2DZ--EHRM Infrastructure Upgrades Dublin, GA Project 557-22-700, newest first.
File
Type
Posted
Atch 1 - PreBid RFIs 7.30.2025.xlsx
XLSX spreadsheet
Aug 1, 2025
36C77625B0013 0004.docx
DOCX document
Aug 1, 2025
Atch 1 - PreBid RFIs 7.24.2025.xlsx
XLSX spreadsheet
Jul 25, 2025
36C77625B0013 0003.docx
DOCX document
Jul 25, 2025
Atch 3 - ICRALevel_Department - Dublin - 557-22-700.pdf
PDF
Jul 18, 2025
36C77625B0013 0002.docx
DOCX document
Jul 18, 2025
Atch 9 - 22-192 Existing Cable Counts by TR - Dublin - 557-22-700.xlsx
XLSX spreadsheet
Jul 18, 2025
Atch 7 - 028333.13 Lead Based Paint - Dublin - 557-22-700.pdf
PDF
Jul 18, 2025
Atch 8 - Dublin EHRM_ACM_Matrix - Dublin - 557-22-700.xlsx
XLSX spreadsheet
Jul 18, 2025
Atch 6 - 013323 Shop Drawings - Dublin - 557-22-700.pdf
PDF
Jul 18, 2025
Atch 5 - 013216.15 Project Sched_Small - Dublin - 557-22-700.pdf
PDF
Jul 18, 2025
Atch 4 - Virtual Bid Opening Information - Dublin - 557-22-700.pdf
PDF
Jul 18, 2025
Atch 1 - PreBid RFIs.xlsx
XLSX spreadsheet
Jul 18, 2025
36C77625B0013 0001.docx
DOCX document
Jul 2, 2025
Attachment 1 - Site Visit Sign-in Sheet - Dublin EHRM.pdf
PDF
Jul 2, 2025
Attachment 2 - Site Visit Agenda - Dublin EHRM.pdf
PDF
Jul 2, 2025
Attachment 15 - Drwg 82 of 91 REVISED.pdf
PDF
Jun 12, 2025
Attachment 13 - VAAR LOS Construction.docx
DOCX document
Jun 12, 2025
Attachment 11 - SOW Atch 4 Specifications.pdf
PDF
Jun 12, 2025
Attachment 8 - SOW Atch 1 Design Guide Telecom Spaces.pdf
PDF
Jun 12, 2025
Attachment 5 - Drawings 4 of 4 - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
Attachment 3 - Drawings 2 of 4 - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
Attachment 14 - Division Cost Breakdown.xlsx
XLSX spreadsheet
Jun 12, 2025
Attachment 9 - SOW Atch 2 EUD Requirements.pdf
PDF
Jun 12, 2025
Attachment 6 - Site Visit Instructions.docx
DOCX document
Jun 12, 2025
Attachment 1 - Specifications - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
Attachment 10 - SOW Atch 3 Elec Panel Labeling.pdf
PDF
Jun 12, 2025
Attachment 12 - Wage Rates - GA20250095 02072025.pdf
PDF
Jun 12, 2025
Attachment 7 - SOW - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
Attachment 4 - Drawings 3 of 4 - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
Attachment 2 - Drawings 1 of 4 - Dublin GA - EHRM.pdf
PDF
Jun 12, 2025
36C77625B0013.docx
DOCX document
Jun 12, 2025
Show all 32
On GovTribe
Work with this file on GovTribe
Download the original file
Contacts named in this file
Similar government files
Ask GovTribe AI about this file
Text version
The file's text, extracted by GovTribe without its formatting.
TR2039: TR2039:
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4121
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 11:10AM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 1 2 3 4
PHYSICAL LOCATION End of Bldg. 5 5A Clinic Amb Ent. 5A Clinic P/Lot Beside Bldg 9
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 68 PSI 70 PSI 70 PSI 70 PSI
RESIDUAL 55 PSI 55 PSI 55 PSI 45 PSI
PITOT 58 PSI 55 PSI 55 PSI 20 PSI
FLOW GPM 1280 1250 750 750
TIME FLUSHED, IN MINUTES 1 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD GOOD
CAPS GOOD GOOD GOOD GOOD
STEMS GOOD GOOD GOOD GOOD
PACKING GOOD GOOD GOOD GOOD
O RING GOOD GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR GOOD CLEAR
REMARKS:
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 11:20AM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 5 6 7 8
PHYSICAL LOCATION End of Bldg 13 Bldg 17/19 P/Lot Bldg 17/19 P/Lot Bldg 30 Canine
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 70 PSI 70 PSI 0 PSI 72 PSI
RESIDUAL 55 PSI 55 PSI 0 PSI 55 PSI
PITOT 55 PSI 55 PSI 0 PSI 55 PSI
FLOW GPM 1250 1250 0 1250
TIME FLUSHED, IN MINUTES 1 1 0 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD GOOD
CAPS GOOD GOOD GOOD GOOD
STEMS GOOD GOOD GOOD GOOD
PACKING GOOD GOOD GOOD GOOD
O RING GOOD GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR CLEAR
REMARKS: Hydrant Number 7 Has A Broke Stem And Operating Nut Is Free Spinning. Could Not Flow
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 11:45AM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: Michael Walenceus
HYDRANT # 9 10 11 12
PHYSICAL LOCATION Behind Bldg 29 End of Bldg 15 Bldg 28 End of Bldg 11
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 72 PSI 70 PSI PSI 70 PSI
RESIDUAL 55 PSI 55 PSI PSI 55 PSI
PITOT 55 PSI 55 PSI PSI 55 PSI
FLOW GPM 1250 1250 1250
TIME FLUSHED, IN MINUTES 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD
CAPS GOOD GOOD GOOD
STEMS GOOD GOOD GOOD
PACKING GOOD GOOD GOOD
O RING GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR
REMARKS:
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 12:00PM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 13 14 15 16
PHYSICAL LOCATION Chiller Plant Bldg 4 Ramp Bldg. 26 By Boiler Bldg 12
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 70 PSI 70 PSI 70 PSI 70 PSI
RESIDUAL 50 PSI 50 PSI 55 PSI 55 PSI
PITOT 50 PSI 50 PSI 55 PSI 55 PSI
FLOW GPM 1190 1250 1250
TIME FLUSHED, IN MINUTES 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD GOOD
CAPS GOOD GOOD GOOD GOOD
STEMS GOOD GOOD GOOD GOOD
PACKING GOOD GOOD GOOD GOOD
O RING GOOD GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR CLEAR
REMARKS:
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 12:15PM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 17 18 19 20
PHYSICAL LOCATION Bldg 16 Behind Bldg. 86 Parking By 86 End of Bldg 8
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 70 PSI 70 PSI 70 PSI 70 PSI
RESIDUAL 60 PSI 60 PSI 60 PSI 60 PSI
PITOT 60 PSI 60 PSI 60 PSI 65 PSI
FLOW GPM 1300 1300 1300 1350
TIME FLUSHED, IN MINUTES 1 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD GOOD
CAPS GOOD GOOD GOOD GOOD
STEMS GOOD GOOD GOOD GOOD
PACKING GOOD GOOD GOOD GOOD
O RING GOOD GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD BROKEN the value in cell D34
VALVE GOOD GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR CLEAR
REMARKS:
Hydrant #20 -- operating nut cap has broken off top of hydrant. Hydrant can still be flowed.
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 12:30PM
Dublin, GA 31021
Attn: Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 21 22 23 24
PHYSICAL LOCATION End of Bldg 6 Front Gate Front of Bldg 1 Front of Bldg 1
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 70 PSI 66 PSI 66 PSI 66 PSI
RESIDUAL 55 PSI 50 PSI 50 PSI 50 PSI
PITOT 55 PSI 50 PSI 50 PSI 50 PSI
FLOW GPM 1250 1190 1190 1190
TIME FLUSHED, IN MINUTES 1 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD GOOD
CAPS GOOD GOOD GOOD GOOD
STEMS GOOD GOOD GOOD GOOD
PACKING GOOD GOOD GOOD GOOD
O RING GOOD GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR CLEAR
REMARKS:
Hydrant #21 is leaning, as if struck by a vehicle. Recommend it be repaired to upright position.
ERROR:#VALUE!
ERROR:#VALUE!
1350 Northmeadow Pkwy. Suite 100
Roswell, GA 30076
678-896-4090
FIRE HYDRANT INSPECTION & FLOW TEST REPORT
LOCATION: Carl Vinson VA Medical Center DATE: 7/9/25
1826 Veterans Blvd. TIME: 12:45PM
Dublin, GA 31021
Attn:Jason Scott
TEST MADE BY: Robert Saltz
WITNESSED BY: David Earnest
HYDRANT # 25 29 29
PHYSICAL LOCATION Front of Bldg 86 Back Of Bldg 29 Front Of Bldg 29
NOZZLE SIZE 2.5 INCH 2.5 INCH 2.5 INCH 2.5 INCH
PRESSURES
INITIAL 70 PSI 66 PSI 66 PSI PSI
RESIDUAL 60 PSI 60 PSI 60 PSI PSI
PITOT 60 PSI 60 PSI 60 PSI PSI
FLOW GPM 1300 1190 1190
TIME FLUSHED, IN MINUTES 1 1 1
WATER USED - GALLONS
PHYSICAL CONDITION
PAINT GOOD GOOD GOOD
CHAINS GOOD GOOD GOOD
CAPS GOOD GOOD GOOD
STEMS GOOD GOOD GOOD
PACKING GOOD GOOD GOOD
O RING GOOD GOOD GOOD Do not change
OPERATING NUT GOOD GOOD GOOD the value in cell D34
VALVE GOOD GOOD GOOD
VALVE SEAT GOOD GOOD GOOD
CONDITION OF WATER CLEAR CLEAR CLEAR
REMARKS: 2 New Hydrants Were Added For Bldg. 29 And 1 At Building 89.