This document is an attachment to a federal contract opportunity (Attachment 4) for the Mike Monroney Aeronautical Center (MMAC) V-PAR (VTOL Procedures and Analysis Range) Project, specifically a Project Manual Volume 2 for a Type B Design Analysis Contract. The comprehensive document details technical specifications for a construction project, with a detailed table of contents spanning multiple divisions including electrical systems, concrete, metals, telecommunications, and various construction requirements. The manual covers extensive technical specifications for components like conduits, cables, lighting, grounding systems, panelboards, surge protective devices, and telecommunications infrastructure, with specific requirements for materials, installation methods, testing procedures, and quality assurance standards.
The project is a small business set-aside with an estimated price range of $5-10 million, involving construction of a VTOL (Vertical Take-Off and Landing) Procedures and Analysis Range facility at the FAA's Oklahoma City location. The solicitation (6973GH-26-R-00020) indicates proposal questions were due by November 6th, with final proposals due November 17th. The contract will be administered by the Department of Transportation's Federal Aviation Administration Franchise Acquisition Services, with the project focused on creating a specialized facility for analyzing and developing vertical takeoff and landing procedures and technologies.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Mike Monroney Aeronautical Center
Oklahoma City, OK
V-PAR
VTOL - Performance and Analysis Range
100% Type B Design Analysis
Contract No. 6973GH-21-D-00046
Work Order # 23-030509
September 18, 2025 October 15, 2025
100% IFC - Project Manual Volume 2
TABLE OF CONTENTS 00 01 10 - 1
V-PAR, VTOL – PERFORMANCE AND ANALYSIS RANGE BUILDING OK70448-013
SECTION 00 01 10
TABLE OF CONTENTS
SECTIONS PAGES
VOLUME 1
COVER & TABLE OF CONTENTS
00 00 00 - TYPE B PROJECT MANUAL COVER VOLUME 1
00 01 07 - SEALS PAGE
00 01 10 - TABLE OF CONTENTS
DIVISION 00 — PROCUREMENT AND CONTRACTING REQUIREMENTS
00 31 32 - GEOTECHNICAL DATA
00 31 32.1 - FAA Vertiport Facility - ECS Project No. 2033
DIVISION 01 — GENERAL REQUIREMENTS
01 01 00 - SUMMARY OF WORK
01 01 90 - CONTRACT CONSIDERATIONS
01 02 80 - MODIFICATION PROCEDURES
01 03 00 - OPTIONS
01 03 90 - COORDINATION AND MEETINGS
01 30 00 - SUBMITTALS
01 40 00 - QUALITY REQUIREMENTS
01 40 00.01 - STATEMENT OF SPECIAL INSPECTIONS (SSI) -2018
01 43 39 - MOCKUPS
01 50 00 - CONSTRUCTION FACILITIES AND TEMPORARY CONTROLS
01 57 23 - STORMWATER POLLUTION PREVENTION
01 59 00 - FIELD OFFICES AND SHEDS
01 60 00 - MATERIAL AND EQUIPMENT
01 60 10 - SUBSTITUTION REQUEST FORM
01 65 00 - STARTING OF SYSTEMS
01 70 00 - CONTRACT CLOSEOUT
01 73 00 - OPERATION AND MAINTENANCE DATA
01 74 19 - CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL PART 1 - GENERAL
01 77 00 - CLOSEOUT PROCEDURES
DIVISION 03 — CONCRETE
03 10 00 - CONCRETE FORMING AND ACCESSORIES
03 20 00 - CONCRETE REINFORCING
03 30 00 - CAST-IN-PLACE CONCRETE
03 35 11 - CONCRETE FLOOR FINISHES
DIVISION 05 — METALS
05 12 00 - STRUCTURAL STEEL FRAMING
05 21 00 - STEEL JOIST FRAMING
05 31 00 - STEEL DECKING
05 40 00 - COLD-FORMED METAL FRAMING
05 50 00 - METAL FABRICATIONS AND MISCELLANEOUS METAL
DIVISION 06 — WOOD, PLASTICS, AND COMPOSITES
06 10 00 - ROUGH CARPENTRY
06 16 00 - SHEATHING
06 41 00 - ARCHITECTURAL WOOD CASEWORK
06 64 00 - PLASTIC PANELING
TABLE OF CONTENTS 00 01 10 - 2
DIVISION 07 — THERMAL AND MOISTURE PROTECTION
07 21 00 - THERMAL INSULATION
07 21 19 - FOAMED-IN-PLACE INSULATION
07 27 26 - FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13.13 - FORMED METAL WALL PANELS
07 54 23 - THERMOPLASTIC-POLYOLEFIN (TPO) ROOFING
07 62 00 - SHEET METAL FLASHING AND TRIM
07 71 00 - MANUFACTURED ROOF SPECIALTIES
07 92 00 - JOINT SEALANTS
DIVISION 08 — OPENINGS
08 11 13 - HOLLOW METAL DOORS AND FRAMES
08 41 13 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 71 00 - DOOR HARDWARE
08 80 00 - GLAZING
08 91 19 - FIXED LOUVERS
DIVISION 09 — FINISHES
09 22 16 - NON-STRUCTURAL METAL FRAMING
09 29 00 - GYPSUM BOARD
09 30 13 - CERAMIC TILING
09 51 13 - ACOUSTICAL PANEL CEILINGS
09 65 13 - RESILIENT BASE AND ACCESSORIES
09 65 19 - RESILIENT TILE FLOORING
09 91 13 - EXTERIOR PAINTING
09 91 23 - INTERIOR PAINTING
09 96 00 - HIGH-PERFORMANCE COATINGS
DIVISION 10 — SPECIALTIES
10 14 23 - ROOM-IDENTIFICATION PANEL SIGNAGE
10 14 23 -1 - FAA-MMAC DOOR SIGN CRITERIA
10 28 00 - TOILET ACCESSORIES
10 44 13 - FIRE PROTECTION CABINETS
10 44 16 - FIRE EXTINGUISHERS
10 73 16 - WEATHER SHELTER CANOPY
10 73 20 - CANTILEVER CANOPIES
DIVISION 11 — EQUIPMENT
11 30 13 - RESIDENTIAL APPLIANCES
DIVISION 12 — FURNISHINGS
12 24 13 - ROLLER WINDOW SHADES
12 36 61.10 - SOLID SURFACE COUNTERTOPS
DIVISION 22 — PLUMBING
22 05 00 - COMMON WORK RESULTS FOR PLUMBING
22 05 23 - GENERAL-DUTY VALVES FOR PLUMBING PIPING
22 05 29 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
22 05 53 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
22 07 19 - PLUMBING PIPING INSULATION
22 11 16 - DOMESTIC WATER PIPING
22 11 19 - DOMESTIC WATER PIPING SPECIALTIES
22 13 16 - SANITARY WASTE AND VENT PIPING
22 13 19 - SANITARY WASTE PIPING SPECIALTIES
22 13 19.13 - SANITARY DRAINS
22 14 14 - STORM DRAINAGE PIPING
22 14 23 - STORM DRAINAGE PIPING SPECIALTIES
TABLE OF CONTENTS 00 01 10 - 3
22 33 00 - ELECTRIC, DOMESTIC-WATER HEATERS
22 42 00 - COMMERCIAL PLUMBING FIXTURES
DIVISION 23 — HEATING VENTILATING AND AIR CONDITIONING
23 05 00 - COMMON WORK RESULTS FOR HVAC
23 05 48.13 - VIBRATION CONTROLS FOR HVAC
23 05 53 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
23 05 93 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 13 - DUCT INSULATION
23 07 19 - HVAC PIPING INSULATION
23 23 00 - REFRIGERANT PIPING
23 31 13 - METAL DUCTS
23 33 00 - AIR DUCT ACCESSORIES
23 33 46 - FLEXIBLE DUCTS
23 34 00 - HVAC FANS
23 37 13.13 - AIR DIFFUSERS
23 37 13.23 - REGISTERS AND GRILLES
23 81 26 - SPLIT-SYSTEM AIR-CONDITIONERS
23 81 26.01 - MINI-SPLIT AIR-CONDITIONERS
VOLUME 2
DIVISION 26 — ELECTRICAL
26 00 10 - SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
26 05 13 - MEDIUM-VOLTAGE CABLES
26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 29 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
26 05 33.13 - CONDUITS FOR ELECTRICAL SYSTEMS
26 05 33.16 - BOXES AND COVERS FOR ELECTRICAL SYSTEMS
26 05 43 - UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 44 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
26 05 53 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 72 - OVERCURRENT PROTECTIVE DEVICE SHORT-CIRCUIT STUDY PART 1 - GENERAL
26 05 73 - OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL
26 05 74 - OVERCURRENT PROTECTIVE DEVICE ARC-FLASH STUDY PART 1 - GENERAL
26 09 23 - LIGHTING CONTROL DEVICES
26 12 00 - VOLTAGE TRANSFORMERS
26 13 29 - VOLTAGE COMPARTMENTALIZED SWITCHGEAR
26 18 23 - MEDIUM VOLTAGE SURGE ARRESTERS
26 22 13 - LOW-VOLTAGE DISTRIBUTION TRANSFORMERS
26 24 16 - PANELBOARDS
26 27 13 - ELECTRIC METERS
26 27 26 - WIRING DEVICES
26 28 16 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
26 41 13 - LIGHTNING PROTECTION SYSTEMS
26 43 13 - SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
26 50 00 - LIGHTING
DIVISION 27 — COMMUNICATIONS
27 00 00 - GENERAL PROVISION FOR TELECOMMUNICATIONS SPECIFICATIONS
CONSTRUCTION STANDARD
27 00 00.1 - TELECOMMUNICATIONS STANDARDS FOR THE MIKE MONRONEY AERONAUTICAL
CENTER
27 10 00 - STRUCTURED CABLING
TABLE OF CONTENTS 00 01 10 - 4
DIVISION 28 — ELECTRONIC SAFETY AND SECURITY
28 14 00 - ACCESS CONTROL SYSTEM HARDWARE
28 31 10 - FIRE ALARM SYSTEM, ADDRESSABLE, TONE TYPE
DIVISION 31 — EARTHWORK
200 - EARTHWORK (COKC)
300 - SURFACES (COKC)
31 31 16 - TERMITE CONTROL
400 - CONCRETE (COKC)
500 - WATER (COKC)
600 - SANITARY (COKC)
800 - INCIDENTAL CONSTRUCTION (COKC)
900 - MATERIALS (COKC)
C-102 TEMPORARY AIR AND WATER POLLUTION, SOIL EROSION, AND SILTRATION CONTROL
D-701 PIPE FOR STORM DRAINS AND CULVERTS
D-751 MANHOLES, CATCH BASINS, INLETS AND INSPECTION HOLES
L-107 AIRPORT WIND CONES
L-108 UNDERGROUND POWER CABLE FOR AIRPORTS
L-110 AIRPORT UNDERGROUND ELECTRICAL DUCT BANKS AND CONDUITS
L-115 ELECTRICAL JUNCTION STRUCTURES
L-125 INSTALLATION OF AIRPORT LIGHTING SYSTEMS
P-152 EXCAVATION, SUBGRADE, AND EMBANKMENT
P-156 CEMENT TREATED SUBGRADE
P-209 CRUSHED AGGREGATE BASE COURSE
P-501 CEMENT CONCRETE PAVEMENT
P-605 JOINT SEALANTS FOR PAVEMENTS
P-610 CONCRETE FOR MISCELLANEOUS STRUCTURES
P-620 RUNWAY AND TAXIWAY MARKING
T-904 SODDING
T-905 TOPSOIL
DIVISION 33 — UTILITIES
33 71 19 - ELECTRICAL UNDERGROUND DUCTS, DUCTBANKS, AND MANHOLES
SUPPLEMENTAL REQUIREMENTS FOR
ELECTRICAL
26 00 10 - 1
SECTION 26 00 10 - SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Requirements generally applicable to all electrical Work on the Project, including but not limited to Work specified in Divisions 26,.
B. Related Requirements:
1. Section 01 81 16 "Facility Environmental Requirements" specifies basis-of-design environmental conditions and performance criteria that are applicable to product selection and installation of the Work on the Project.
1.2 REFERENCES
A. Abbreviations and Acronyms for Electrical Terms and Units of Measure:
1. A: Ampere, unit of electrical current.
2. AC or ac: Alternating current.
3. AIC: Ampere interrupting capacity.
4. AL, Al, or ALUM: Aluminum.
5. ASD: Adjustable-speed drive.
6. AWG: American wire gauge; see ASTM B258.
7. BIL: Basic impulse insulation level.
8. BIM: Building information modeling.
9. BMS: Building management system.
10. CAD: Computer-aided design or drafting.
11. CB: Circuit breaker.
12. cd: Candela, the SI fundamental unit of luminous intensity.
13. CO/ALR: Copper-aluminum, revised.
14. CU or Cu: Copper.
15. CU-AL or AL-CU: Copper-aluminum.
16. DC or dc: Direct current.
17. DDC: Direct digital control (HVAC).
18. EGC: Equipment grounding conductor.
19. EMP: Electrical maintenance program (operation and maintenance); electromagnetic pulse (transient analysis).
20. EPS: Emergency power supply.
21. EPSS: Emergency power supply system.
22. ESS: Energy storage system.
23. EV: Electric vehicle.
24. EVPE: Electric vehicle power export equipment.
25. EVSE: Electric vehicle supply equipment.
26. FACU: Fire-alarm control unit.
27. fc: Footcandle, an internationally recognized unit of illuminance equal to one lumen per square foot or 10.76 lx. The simplified conversion 1 fc = 10 lx in the Specifications is common practice and considered adequate precision for building construction activities.
When there are conflicts, lux is the primary unit; footcandle is specified for convenience.
28. FLC: Full-load current.
29. ft: Foot.
26 00 10 - 2
30. ft-cd: Foot-candle, the antiquated U.S. standard unit of illuminance, equal to one international candle measured at a distance of one foot, that was superseded in 1948 by the unit "footcandle" when the SI unit candela (cd) replaced the international candle; see "fc."
31. FTP: File transfer protocol.
32. GEC: Grounding electrode conductor.
33. GFCI: Ground-fault circuit interrupter.
34. GND: Ground.
35. HACR: Heating, air conditioning, and refrigeration.
36. HDPE: High-density polyethylene.
37. HP or hp: Horsepower.
38. HVAC: Heating, ventilating, and air conditioning.
39. Hz: Hertz.
40. inch: Inch. To avoid confusion, the abbreviation "in." is not used.
41. I/O: Input/output.
42. IP: Ingress protection rating (enclosures); Internet protocol (communications).
43. IT&R: Inspecting, testing, and repair.
44. ITE: Information technology equipment.
45. kAIC: Kiloampere interrupting capacity.
46. kcmil or MCM: One thousand circular mils.
47. kV: Kilovolt.
48. kVA: Kilovolt-ampere.
49. kvar: Kilovolt-ampere reactive.
50. kW: Kilowatt.
51. kWh: Kilowatt-hour.
52. lb: Pound (weight).
53. lbf: Pound (force).
54. LED: Light-emitting diode.
55. Li-ion: Lithium-ion.
56. lm: Lumen, the SI-derived unit of luminous flux.
57. LRC: Locked-rotor current.
58. LV: Low voltage.
59. lx: Lux, the SI-derived unit of illuminance equal to one lumen per square meter.
60. m: Meter.
61. MLO: Main lugs only.
62. MOV: Metal-oxide varistor.
63. MV: Medium voltage.
64. MVA: Megavolt-ampere.
65. mW: Milliwatt.
66. MW: Megawatt.
67. MWh: Megawatt-hour.
68. N.C.: Normally closed.
69. Ni-Cd: Nickel-cadmium.
70. Ni-MH: Nickel-metal hydride.
71. N.O.: Normally open.
72. NPT: National (American) standard pipe taper.
73. OCPD: Overcurrent protective device.
74. PC: Personal computer.
75. PCS: Power conversion system.
76. PCU: Power-conditioning unit.
77. PF or pf: Power factor.
78. PHEV: Plug-in hybrid electric vehicle.
79. PoE: Power over Ethernet.
80. PVC: Polyvinyl chloride.
81. RFI: (electrical) Radio-frequency interference; (contract) Request for interpretation.
26 00 10 - 3
82. RMS or rms: Root-mean-square.
83. RPM or rpm: Revolutions per minute.
84. SCADA: Supervisory control and data acquisition.
85. SCCR: Short-circuit current rating.
86. SCR: Silicon-controlled rectifier.
87. SPD: Surge protective device.
88. sq.: Square.
89. SWD: Switching duty.
90. TEFC: Totally enclosed fan-cooled.
91. TVSS: Transient voltage surge suppressor.
92. UL: (standards) UL Standards & Engagement Inc.; (product categories) UL, LLC.
93. UL CCN: UL Category Control Number.
94. UPS: Uninterruptible power supply.
95. UV: Ultraviolet.
96. V: Volt, unit of electromotive force.
97. V(ac): Volt, alternating current.
98. V(dc): Volt, direct current.
99. VA: Volt-ampere, unit of complex electrical power.
100. VAR: Volt-ampere reactive, unit of reactive electrical power.
101. VFC: Variable-frequency controller.
102. VOM: Volt-ohm-multimeter.
103. VoIP: Voice over Internet Protocol.
104. VPN: Virtual private network.
105. VRLA: Valve regulated lead acid; also called "sealed lead acid (SLA)" or "valve regulated sealed lead acid."
106. W: Watt, unit of real electrical power.
107. WAN: Wide area network.
108. Wh: Watt-hour, unit of electrical energy usage.
109. WR: Weather resistant.
B. Abbreviations and Acronyms for Electrical Raceway Types:
1. EMT: Electrical metallic tubing.
2. EMT-S: Steel electrical metallic tubing.
3. EPEC: Electrical HDPE underground conduit (thin wall).
4. EPEC-A: Type A electrical HDPE underground conduit.
5. EPEC-B: Type B electrical HDPE underground conduit.
6. ERMC: Electrical rigid metal conduit.
7. ERMC-S: Steel electrical rigid metal conduit.
8. ERMC-S-G: Galvanized-steel electrical rigid metal conduit.
9. ERMC-S-PVC: PVC-coated-steel electrical rigid metal conduit.
10. FMC: Flexible metal conduit.
11. FMC-S: Steel flexible metal conduit.
12. FMT: Steel flexible metallic tubing.
13. HDPE: HDPE underground conduit (thick wall).
14. HDPE-40: Schedule 40 HDPE underground conduit.
15. IMC: Steel electrical intermediate metal conduit.
16. LFMC: Liquidtight flexible metal conduit.
17. LFMC-S: Steel liquidtight flexible metal conduit.
18. PVC: Rigid PVC conduit.
19. PVC-40: Schedule 40 rigid PVC conduit.
20. PVC-A: Type A rigid PVC concrete-encased conduit.
21. PVC-EB: Type EB rigid PVC concrete-encased underground conduit.
22. RGS: See ERMC-S-G.
23. RMC: See ERMC.
26 00 10 - 4
C. Abbreviations and Acronyms for Electrical Single-Conductor and Multiple-Conductor Cable Types:
1. MC: Metal-clad cable.
2. MV: Medium-voltage cable.
3. RHW: Thermoset rubber, moisture-resistant cable.
4. SE: Service-entrance cable.
5. SER: Service-entrance cable, round.
6. SEU: Service-entrance cable, flat.
7. TBS: Thermoplastic cable with outer braid.
8. TC: Tray cable.
9. TC-ER: Tray cable, exposed run.
10. THW: Thermoplastic, heat- and moisture-resistant cable.
11. THHN: Thermoplastic, heat-resistant cable with nylon jacket outer sheath.
12. THHW: Thermoplastic, heat- and moisture-resistant cable.
13. THWN: Thermoplastic, moisture- and heat-resistant cable with nylon jacket outer sheath.
14. TW: Thermoplastic, moisture-resistant cable.
15. UF: Underground feeder and branch-circuit cable.
16. USE: Underground service-entrance cable.
17. XHH: Cross-linked polyethylene, heat-resistant cable.
18. XHHW: Cross-linked polyethylene, heat- and moisture-resistant cable.
D. Abbreviations and Acronyms for Electrical Flexible Cord Types:
1. SEO: 600 V extra-hard-usage, hard-service cord with thermoplastic elastomer insulation and oil-resistant thermoplastic elastomer outer covering for damp locations.
2. SEOW: 600 V extra-hard-usage, hard-service cord with thermoplastic elastomer insulation and oil-resistant thermoplastic elastomer outer covering for damp or wet locations.
3. SEOO: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoplastic elastomer insulation and oil-resistant thermoplastic elastomer outer covering for damp locations.
4. SEOOW: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoplastic elastomer insulation and oil-resistant thermoplastic elastomer outer covering for damp or wet locations.
5. SO: 600 V extra-hard-usage, hard-service cord with thermoset insulation and oil-resistant thermoset outer covering for damp locations.
6. SOW: 600 V extra-hard-usage, hard-service cord with thermoset insulation and oil-resistant thermoset outer covering for damp or wet locations.
7. SOO: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoset insulation and oil-resistant thermoset outer covering for damp locations.
8. SOOW: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoset insulation and oil-resistant thermoset outer covering for damp or wet locations.
9. STO: 600 V extra-hard-usage, hard-service cord with thermoplastic insulation and oil-resistant thermoplastic outer covering for damp locations.
10. STOW: 600 V extra-hard-usage, hard-service cord with thermoplastic insulation and oil-resistant thermoplastic outer covering for damp or wet locations.
11. STOO: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoplastic insulation and oil-resistant thermoplastic outer covering for damp locations.
12. STOOW: 600 V extra-hard-usage, hard-service cord with oil-resistant thermoplastic insulation and oil-resistant thermoplastic outer covering for damp or wet locations.
E. Definitions:
1. Basic Impulse Insulation Level (BIL): Reference insulation level expressed in impulse crest voltage with a standard wave not longer than 1.5 times 50 microseconds and 1.5 times 40 microseconds.
26 00 10 - 5
2. Cable: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "cable" is (1) a conductor with insulation, or a stranded conductor with or without insulation (single-conductor cable); or (2) a combination of conductors insulated from one another (multiple-conductor cable).
3. Communications Jack: A fixed connecting device designed for insertion of a communications cable plug.
4. Communications Outlet: One or more communications jacks, or cables and plugs, mounted in a box or ring, with a suitable protective cover.
5. Conductor: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "conductor" is (1) a wire or combination of wires not insulated from one another, suitable for carrying an electric current; (2) (National Electrical Safety Code) a material, usually in the form of wire, cable, or bar, suitable for carrying an electric current; or (3) (general) a substance or body that allows a current of electricity to pass continuously along it.
6. Conduit: A structure containing one or more duct raceways.
7. Direct Buried: Installed underground without encasement in concrete or other protective material.
8. Duct Bank: An arrangement of conduit providing one or more continuous duct raceways between two points.
9. Duct Raceway: A single enclosed raceway for conductors or cable.
10. Electrical Service: The conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served.
11. Enclosure: The case or housing of an apparatus, or the fence or wall(s) surrounding an installation, to prevent personnel from accidentally contacting energized parts or to protect the equipment from physical damage. Types of enclosures and enclosure covers include the following:
a. Cabinet: An enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung.
b. Concrete Box: A box intended for use in poured concrete.
c. Conduit Body: A means for providing access to the interior of a conduit or tubing system through one or more removable covers at a junction or terminal point. In the United States, conduit bodies are listed in accordance with outlet box requirements.
d. Conduit Box: A box having threaded openings or knockouts for conduit, EMT, or fittings.
e. Cover Plate: A cover designed for protecting wiring devices installed in flush-mounted device boxes while permitting their safe operation; also called a faceplate or wallplate.
f. Cutout Box: An enclosure designed for surface mounting that has swinging doors or covers secured directly to and telescoping with the walls of the enclosure.
g. Device Box: A box with provisions for mounting a wiring device directly to the box.
h. Floor Box: A box mounted in the floor intended for use with a floor box cover and other components to complete the floor box enclosure.
i. Floor-Mounted Enclosure: A floor box and floor box cover assembly with means to mount in the floor that is sealed against the entrance of scrub water at the floor level.
j. Junction Box: A box with a blank cover that joins different runs of raceway or cable and provides space for connection and branching of the enclosed conductors.
k. Outlet Box: A box that provides access to a wiring system having pryout openings, knockouts, threaded entries, or hubs in either the sides or the back, or both, for the entrance of conduit, conduit or cable fittings, or cables, with provisions for mounting an outlet box cover, but without provisions for mounting a wiring device directly to the box.
26 00 10 - 6
l. Pull Box: A box with a blank cover that joins different runs of raceway and provides access for pulling or replacing the enclosed cables or conductors.
m. Ring: A sleeve, which is not necessarily round, used for positioning a recessed wiring device flush with the plaster, concrete, drywall, or other wall surface.
n. Ring Cover: A box cover, with raised center portion to accommodate a specific wall or ceiling thickness, for mounting wiring devices or luminaires flush with the surface.
o. Termination Box: An enclosure designed for installation of termination base assemblies consisting of bus bars, terminal strips, or terminal blocks with provision for wire connectors to accommodate incoming or outgoing conductors, or both.
12. Emergency Systems: Those systems legally required and classed as emergency by municipal, state, federal, or other codes, or by any governmental agency having jurisdiction that are designed to ensure continuity of lighting, electrical power, or both, to designated areas and equipment in the event of failure of the normal supply for safety to human life.
13. Fault Limited: Providing or being served by a source of electrical power that is limited to not more than 100 W when tested in accordance with UL 62368-1.
a. The term "fault limited" is intended to encompass most Class 1, 2, and 3 power-limited sources complying with Article 725 of NFPA 70; Class ES1 and ES2 electrical energy sources that are Class PS1 electrical power sources (e.g., USB);
and Class ES3 electrical energy sources that are Class PS1 and PS2 electrical power sources (e.g., PoE). See UL 62368-1 for discussion of classes of electrical energy sources and classes of electrical power sources.
14. High-Performance Building: A building that integrates and optimizes on a life-cycle basis all major high-performance attributes, including energy conservation, environment, safety, security, durability, accessibility, cost-benefit, productivity, sustainability, functionality, and operational considerations.
15. Jacket: A continuous nonmetallic outer covering for conductors or cables.
16. Luminaire: A complete lighting unit consisting of a light source such as a lamp, together with the parts designed to position the light source and connect it to the power supply. It may also include parts to protect the light source or the ballast or to distribute the light.
17. Mode: The terms "Active Mode," "Off Mode," and "Standby Mode" are used as defined in the Energy Independence and Security Act (EISA) of 2007.
18. Multi-Outlet Assembly: A type of surface, flush, or freestanding raceway designed to hold conductors, receptacles, and switches, assembled in the field or at the factory.
19. One-Line Diagram: A diagram that shows, by means of single lines and graphic symbols, the course of an electric circuit or system of circuits and the component devices or parts used therein. Also called "single-line diagram."
20. Plenum: A compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.
21. Protective Device: A device that senses when an abnormal current flow, abnormal voltage potential, or other abnormal electrical waveform exists and then disconnects the affected portion of the circuit from the system. Common protective devices include fuses, circuit breakers, relays, ground-fault circuit interrupters, and arc-fault circuit interrupters.
22. Receptacle: A fixed connecting device arranged for insertion of a power cord plug. Also called a power jack.
23. Receptacle Outlet: One or more receptacles mounted in a box with a suitable protective cover.
24. Sheath: A continuous metallic covering for conductors or cables.
25. UL Category Control Number (CCN): An alphabetic or alphanumeric code used to identify product categories covered by UL's Listing, Classification, and Recognition Services.
26. Voltage Class: For specified circuits and equipment, voltage classes are defined as follows:
26 00 10 - 7
a. Control Voltage: Having electromotive force between any two conductors, or between a single conductor and ground, that is supplied from a battery or other Class 2 or Class 3 power-limited source.
b. Line Voltage: (1) (controls) Designed to operate using the supplied low-voltage power without transformation. (2) (transmission lines, transformers, SPDs) The line-to-line voltage of the supplying power system.
c. Extra-Low Voltage (ELV): Not having electromotive force between any two conductors, or between a single conductor and ground, exceeding 30 V(ac rms), 42 V(ac peak), or 60 V(dc).
d. Low Voltage (LV): Having electromotive force between any two conductors, or between a single conductor and ground, that is rated above 30 V but not exceeding 1000 V.
e. Medium Voltage (MV): Having electromotive force between any two conductors, or between a single conductor and ground, that is rated about 1 kV but not exceeding 69 kV.
27. Wire: In accordance with NIST NBS Circular 37 and IEEE standards, in the United States for the purpose of interstate commerce, the definition of "wire" is a slender rod or filament of drawn metal. A group of small wires used as a single wire is properly called a "stranded wire." A wire or stranded wire covered with insulation is properly called an "insulated wire" or a "single-conductor cable." Nevertheless, when the context indicates that the wire is insulated, the term "wire" will be understood to include the insulation.
1.3 INFORMATIONAL SUBMITTALS
A. Electrical Installation Schedule: At preconstruction meeting, and periodically thereafter as dates change, provide schedule for electrical installation Work to Owner and Architect including, but not limited to, milestone dates for the following activities:
1. Submission of power system studies.
2. Submission of specified coordination drawings.
3. Submission of action submittals specified in Division 26.
4. Utility service outages.
5. Utility service inspection and activation.
6. Closing of walls and ceilings containing electrical Work.
7. System startup, testing, and commissioning activities for major electrical equipment.
8. System startup, testing, and commissioning activities for emergency lighting.
9. System startup, testing, and commissioning activities for automation systems (SCADA, BMS, lighting, HVAC, fire alarm, fire pump, etc.).
10. Pouring of concrete housekeeping pads for electrical equipment and testing of concrete samples.
11. Requests for special inspections.
12. Requests for inspections by authorities having jurisdiction.
B. Qualification Statements:
1. For qualified regional manufacturer.
2. For structural professional engineer.
3. For electrical professional engineer.
4. For ERMC-S-PVC raceway Installer.
5. For medium-voltage cable Installer.
6. For medium-voltage duct Installer.
7. For medium-voltage equipment Installer.
8. For EVSE Installer.
9. For lightning protection system Installer.
10. For power quality specialist.
26 00 10 - 8
11. For medium-voltage andlow-voltage electrical testing agency and on-site electrical testing supervisor.
12. For luminaire photometric testing laboratory.
13. For lighting testing and inspecting agency.
1.4 CLOSEOUT SUBMITTALS
A. Facility EMP Binders:
1. Complete Set: On USB media that is clearly and permanently labeled with attached placard on lanyard to prevent misplacement.
B. Operation and Maintenance Data:
1. Include the following information:
a. Manufacturer's operating specifications.
b. User's guides for software and hardware.
c. Schedule of maintenance material items recommended to be stored at the Project site.
d. Detailed instructions covering operation under both normal and abnormal conditions.
e. Time-current curves for overcurrent protective devices and manufacturer's written instructions for testing and adjusting their settings.
f. List of load-current and overload-relay heaters with related motor nameplate data.
g. List of lamp types and photoelectric relays used on the Project, with ANSI and manufacturers' codes.
h. Manufacturer's instructions for setting field-adjustable components.
i. Manufacturer's instructions for testing, adjusting, and reprogramming microprocessor controls.
j. .
C. Software and Firmware Operational Documentation: Provide software and firmware operational documentation in Facility EPM Binders, including the following:
1. Software operating and upgrade manuals.
2. Names, versions, and website addresses for locations of installed software.
3. Device address list.
4. Printout of software application and graphic screens.
5. Testing and adjusting of panic and emergency power features.
D. Software:
1. Program Software Backup: Provide USB media that is clearly and permanently labeled with attached placard on lanyard to prevent misplacement.
2. Provide to Owner upgrades and unrestricted licenses for Government use for installed and backup software, including operating systems and programming tools required for operation and maintenance.
PART 2 - PRODUCTS
2.1 SUBSTITUTION LIMITATIONS FOR ELECTRICAL EQUIPMENT
A. Substitution requests for electrical equipment will be entertained under the following conditions:
1. Substitution requests may be submitted for consideration prior to the Electrical
Preconstruction Conference if accompanied by value analysis data indicating that
26 00 10 - 9 substitution will comply with the Project performance requirements while significantly increasing value for Owner throughout life of facility.
2. Substitution requests may be submitted for consideration concurrently with submission of power system study reports when those reports indicate that substitution is necessary for safety of maintenance personnel and facility occupants.
3. Contractor is responsible for sequencing and scheduling power system studies and electrical equipment procurement. After the Electrical Preconstruction Conference, insufficient lead time for electrical equipment delivery will not be considered a valid reason for substitution.
2.2 FACILITY ELECTRICAL MAINTENANCE PROGRAM (EMP) BINDERS
A. Description: Set of binders containing operation and maintenance data for facility's electrical equipment that was compiled during analysis of installed electrical Work for Facility EMP development.
B. Applicable Standards:
1. Regulatory Requirements: Comply with requirements in NFPA 70B.
2. General Characteristics:
a. Volume 1 - Introduction:
1) Summarize how Facility EMP analysis was performed, how data were collected, and how volumes are organized.
2) Describe Facility EMP and provide recommended policies and procedures for implementing the program and keeping it current.
3) Provide place for Owner to identify contact information for employees responsible for implementing and maintaining Facility EMP.
PART 3 - EXECUTION
3.1 DEVELOPMENT OF FACILITY ELECTRICAL MAINTENANCE PROGRAM (EMP)
A. Conduct Facility EMP analysis in accordance with NFPA 70B requirements.
B. Compile operation and maintenance data from Facility EMP analysis and submit Facility EMP Binders.
3.2 INSTALLATION OF ELECTRICAL WORK
A. Unless more stringent requirements are specified in the Contract Documents or manufacturers' written instructions, comply with NFPA 70 and NECA NEIS 1 for installation of electrical Work on the Project. Consult Architect for resolution of conflicting requirements.
END OF SECTION 26 00 10
This page intentionally left blank
MEDIUM-VOLTAGE CABLES 26 05 13 - 1
SECTION 26 05 13 - MEDIUM-VOLTAGE CABLES
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Medium voltage cable.
B. Cable accessories.
1.2 REFERENCE STANDARDS
A. IEEE C2 - National Electrical Safety Code(R) (NESC(R)); 2023.
B. IEEE 48 - IEEE Standard for Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5 kV through 500 kV; 2020.
C. NEMA WC 74 - 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy; 2022.
D. NETA ATS - Standard for Acceptance Testing Specifications for Electrical Power Equipment And Systems; 2025.
E. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
1.3 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide for cable, terminations, and accessories.
C. Test Reports: Indicate results of cable test in tabular form and in plots of current versus voltage for incremental voltage steps, and current versus time at 30 second intervals at maximum voltage.
D. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency specified under Regulatory Requirements. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
1.4 QUALITY ASSURANCE
A. Comply with NFPA 70.
B. Products: Listed, classified, and labeled as suitable for the purpose intended.
MEDIUM-VOLTAGE CABLES 26 05 13 - 2
C. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
PART 2 - PRODUCTS
2.1 MEDIUM-VOLTAGE CABLE
A. Provide cables with lead content less than 300 parts per million.
B. Medium Voltage Cable: NEMA WC 74 ethylene propylene insulated cable.
1. Voltage: 15 kV, grounded.
2. Conductor: Copper, concentric, compressed, or compact, stranded, with foil conductor shield.
3. Construction: Single conductor with metal 1/3 concentric neutral insulation shielding.
4. Insulation Jacket: PVC, 80 mils minimum thickness.
2.2 CABLE ACCESSORIES
A. Separable Insulated Connectors
1. Dead-Break Cable Terminators: Elbow-type unit with 600A continuous-current rating;
designed for de-energized disconnecting and connecting; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.
2. Load-break Cable Terminators: Elbow-type unit with 200A load make/break and continuous-current rating; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capactiance coupled.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify that conduit, duct, trench, or manholes are ready to receive cable.
B. Verify that field measurements are as indicated.
C. Verify routing and termination locations of cable bank prior to rough-in.
D. Cable routing is shown in approximate locations unless dimensioned. Route as required to complete wiring system.
3.2 PREPARATION
A. Use swab to clean conduits before pulling cables.
MEDIUM-VOLTAGE CABLES 26 05 13 - 3
3.3 INSTALLATION
A. Avoid abrasion and other damage to cables during installation.
B. Use suitable lubricants and pulling equipment.
C. Sustain cable pulling tensions and bending radii below recommended limits.
D. Ground cable shield at each termination and splice.
E. Install cables in manholes along wall providing longest route.
F. Arrange cable in manholes to avoid interference with duct entrances.
3.4 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Inspect exposed cable sections for physical damage.
C. Inspect cable for proper connections as indicated.
D. Inspect shield grounding, cable supports, and terminations for proper installation.
E. Perform tests and inspections in accordance with NETA ATS utilizing Very Low Frequency (VLF) testing.
3.5 PROTECTION
A. Protect installed cables from entrance of moisture.
END OF SECTION 26 05 13
LOW-VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES
26 05 19 - 1
SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Copper building wire.
2. Metal-clad cable, Type MC.
3. Connectors and splices.
B. Related Requirements:
1. Section 01 81 16 "Facility Environmental Requirements" specifies basis-of-design environmental conditions and performance criteria that are applicable to product selection and installation of the Work on the Project.
2. Section 01 81 23 "Facility Seismic and Wind Criteria" specifies basis-of-design seismic and wind criteria for nonstructural components on the Project.
3. Section 26 00 10 "Supplemental Requirements for Electrical" specifies additional requirements applicable to coordinating, scheduling, and sequencing of the Work specified in this Section.
4. Section 26 05 13 "Medium-Voltage Cables" for single-conductor and multiconductor cables, cable splices, and terminations for electrical distribution systems with 601 to 35 000 V.
5. Section 26 05 23 "Control-Voltage Electrical Power Cables" for control systems communications cables and Classes 1, 2, and 3 control cables.
6. Section 27 13 13 "Communications Copper Backbone Cabling" for twisted pair cabling used for data circuits.
7. Section 27 15 13 "Communications Copper Horizontal Cabling" for twisted pair cabling used for data circuits.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1.3 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
PART 2 - PRODUCTS
2.1 COPPER BUILDING WIRE
A. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.
B. Standards:
26 05 19 - 2
1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
2. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide."
C. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors.
D. Conductor Insulation:
1. Type USE-2 and Type SE. Comply with UL 854.
2. Type THHNand Type THWN-2. Comply with UL 83.
3. Type THWandType THW-2. Comply with NEMA WC-70/ICEA S-95-658 and UL 83.
4. Type UF. Comply with UL 83 and UL 493.
5. Type XHHW-2. Comply with UL 44.
2.2 METAL-CLAD CABLE, TYPE MC
A. Description: A factory assembly of one or more current-carrying insulated conductors in an overall metallic sheath.
B. Standards:
1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
2. Comply with UL 1569.
3. Conductor and Cable Marking: Comply with wire and cable marking according to UL's
"Wire and Cable Marking and Application Guide."
C. Circuits:
1. Single circuit.
2. Power-Limited Fire-Alarm Circuits: Comply with UL 1424.
D. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B8 for stranded conductors.
E. Ground Conductor: Insulated.
F. Conductor Insulation:
1. Type TFN/THHN/THWN-2. Comply with UL 83.
2. Type XHHW-2. Comply with UL 44.
G. Armor: Steel, interlocked.
2.3 CONNECTORS AND SPLICES
A. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
B. Lugs: One piece, seamless, designed to terminate conductors specified in this Section.
1. Material: Copper.
2. Type: Two hole with standard barrels.
3. Termination: Compression.
26 05 19 - 3
PART 3 - EXECUTION
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Feeders:
1. Copper; solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B. Branch Circuits:
1. Copper:
a. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING
METHODS
A. Service Entrance: Type THHN/THWN-2, single conductors in raceway.
B. Exposed Feeders: Type THHN/THWN-2, single conductors in raceway.
C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN/THWN-2, single conductors in raceway.
D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN/THWN- 2, single conductors in raceway.
E. Exposed Branch Circuits, Including in Crawlspaces: Type THHN/THWN-2, single conductors in raceway.
F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN/THWN-2, single conductors in raceway.
G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type THHN/THWN-2, single conductors in raceway.
H. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainless steel, wire-mesh, strain relief device at terminations to suit application.
3.3 INSTALLATION, GENERAL
A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated.
B. Complete raceway installation between conductor and cable termination points in accordance with Section 26 05 33.13 "Conduits for Electrical Systems" prior to pulling conductors and cables.
C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
26 05 19 - 4
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.
F. Support cables according to Section 26 05 29 "Hangers and Supports for Electrical Systems."
3.4 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.
B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inch of slack.
3.5 IDENTIFICATION
A. Identify and color-code conductors and cables according to Section 26 05 53 "Identification for Electrical Systems."
B. Identify each spare conductor at each end with identity number and location of other end of conductor, and identify as spare conductor.
3.6 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 26 05 44 "Sleeves and Sleeve Seals for Electrical Raceways and Cabling."
3.7 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Section 07 84 13 "Penetration Firestopping."
3.8 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors for compliance with requirements.
2. Perform each of the following visual and electrical tests:
a. Inspect exposed sections of conductor and cable for physical damage and correct connection according to the single-line diagram.
26 05 19 - 5
b. Test bolted connections for high resistance using one of the following:
1) A low-resistance ohmmeter.
2) Calibrated torque wrench.
c. Inspect compression-applied connectors for correct cable match and indentation.
d. Inspect for correct identification.
e. Inspect cable jacket and condition.
f. Insulation-resistance test on each conductor for ground and adjacent conductors.
Apply a potential of 500 V(dc) for 300 V rated cable and 1000 V(dc) for 600 V rated cable for a one-minute duration.
g. Continuity test on each conductor and cable.
h. Uniform resistance of parallel conductors.
B. Cables will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports to record the following:
1. Procedures used.
2. Results that comply with requirements.
3. Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.
END OF SECTION 26 05 19
GROUNDING AND BONDING FOR
ELECTRICAL SYSTEMS
26 05 26 - 1
SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Grounding and bonding conductors.
2. Grounding and bonding clamps.
3. Grounding and bonding bushings.
4. Grounding and bonding hubs.
5. Grounding and bonding connectors.
6. Intersystem bonding bridge grounding connectors.
7. Grounding and bonding busbars.
8. Grounding (earthing) electrodes.
B. Related Requirements:
1. Section 01 81 16 "Facility Environmental Requirements" specifies basis-of-design environmental conditions and performance criteria that are applicable to product selection and installation of the Work on the Project.
2. Section 26 00 10 "Supplemental Requirements for Electrical" specifies additional requirements applicable to coordinating, scheduling, and sequencing of the Work specified in this Section.
3. Section 26 41 13 "Lightning Protection for Structures" specifies bonding of lightning protection grounding electrodes to facility grounding electrodes.
4. Section 26 05 53 "Identification for Electrical Systems" specifies electrical equipment labels and warning signs installed by this Section.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Product Listing: Include copy of unexpired approval letter, on letterhead of qualified electrical testing agency, certifying product's compliance with specified listing criteria.
a. If listed manufacturer differs from selling manufacturer, indicate relationship between entities on submittal. Clearly indicate which entity warrants product performance and fitness for purpose.
b. Listing criteria identified in approval letter must match specified listing criteria. UL label indicating approval of equipment's enclosure is not considered approval of equipment for intended application.
c. Product identification in approval letter must match product branding and model numbers in submittal. Approval letters for discontinued or superseded products are unacceptable for submitted product.
B. Shop Drawings: Prepare and submit the following:
1. Plans showing dimensioned locations of grounding features described in "Field Quality
Control for Grounding and Bonding" Article, including the following:
a. Grounding electrodes.
C. Field quality-control reports.
26 05 26 - 2
1.3 INFORMATIONAL SUBMITTALS
A. Manufacturer's published instructions.
1.4 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data:
1. In addition to items specified in Section 26 00 10 "Supplemental Requirements for
Electrical," include the following:
a. Plans showing locations of grounding features described in "Field Quality Control for Grounding and Bonding" Article, including the following:
1) Grounding electrodes.
b. Instructions for periodic testing and inspection of grounding features at test wells based on NETA MTS.
1) Tests must determine if ground-resistance or impedance values remain within specified maximums, and instructions must recommend corrective action if values do not.
2) Include recommended testing intervals.
1.5 QUALIFICATIONS
A. Electrical Power Testing (EPT) Technician III: Possessing active NICET EPT Level III certification. Able to manage switching procedures, conduct tests of complex equipment, analyze test and equipment data, plan a job, and lead a team. Has experience performing NFPA 70B, IEEE, and NETA electrical tests.
B. Electrical Power Testing and Inspecting Agency: Entities possessing active credentials from a qualified electrical testing laboratory recognized by authorities having jurisdiction.
1. On-site electrical testing supervisors must possess active NICET EPT Technician III certification.
1.6 SERVICE CONDITIONS FOR ELECTRICAL EQUIPMENT
A. Soil Resistivity: Grounding (earthing) Work on the Project must account for soil resistivity conditions specified in Section 01 81 16 "Facility Environmental Requirements."
B. Electrical and ICT Equipment Grounding (Earthing): Do not exceed 25 Ω resistance to ground (earth).
1. Contact Architect for resolution if 25 Ω specified resistance to ground (earth) is not attained after complying with prescriptive requirements in Article 250 of NFPA 70.
26 05 26 - 3
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Regulatory Requirements: Products or components listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2.2 GROUNDING AND BONDING CONDUCTORS
A. Equipment Grounding Conductor:
1. Standard Features: 600 V, THHN/THWN-2, copper or tinned-copper wire or cable, green color, in accordance with Section 26 05 19 "Low-Voltage Electrical Power Conductors and Cables."
B. ASTM - Bare Copper Grounding and Bonding Conductor:
1. Standard Features: Complying with one or more of the following:
a. Soft or Annealed Copper Wire: ASTM B3.
b. Concentric-Lay Stranded Copper Conductor: ASTM B8.
c. Tin-Coated Soft or Annealed Copper Wire: ASTM B33.
d. 19-Wire Combination Unilay-Stranded Copper Conductor: ASTM B787/B787M.
2.3 GROUNDING AND BONDING CLAMPS
A. Description: Clamps suitable for attachment of grounding and bonding conductors to grounding electrodes, pipes, tubing, and rebar. Grounding and bonding clamps specified in this article are also suitable for use with communications applications.
B. UL KDER and KDSH - Hex-Fitting-Type Pipe and Rod Grounding and Bonding Clamp:
1. Source Limitations: Obtain products from single manufacturer.
2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following UL product categories:
a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.
3. Standard Features:
a. Two pieces with stainless steel bolts.
b. Clamp Material: Silicon bronze.
c. Listed for outdoor…