Attachment 15 - 2014 Asbestos Inspection.pdf

PDF 11 MB Posted

Attached to
Sioux Falls Courthouse Window Replacement
Solicitation number
47PJ0025R0028
Issued by

About this file

This file is an asbestos inspection report attachment from 2014 for the Sioux Falls Courthouse Window Replacement project (Solicitation #47PJ0025R0028). The document appears to be a supporting technical document that would provide bidders with information about asbestos conditions in the building related to the window replacement scope. While the specific details of the asbestos inspection report are not provided in the source material, this type of document typically contains sampling locations, test results, and recommendations relevant to construction activities that may disturb asbestos-containing materials.

This document is one of 15 attachments referenced in the main solicitation package issued by GSA Public Buildings Service Region 8 for the window replacement project at the Federal Courthouse located at 400 S. Phillips Ave, Sioux Falls, South Dakota.

View the file

Other files

File Type Posted
The Solicitation- 47PJ0025R0028 AM0004.pdf PDF
SF-30 47PJ0025R0028_AM0004.pdf PDF
SF-30 47PJ0025R0028_AM0002.pdf PDF
RFI Responses Dated 02 14 2025 (AM0002).pdf PDF
47PJ0025R0028 Solicitation (AM0002).pdf PDF
47PJ0025R0028 Solicitation AM0001.pdf PDF
SF-30 47PJ0025R0028_AM0001 2025 01 23.pdf PDF
WD 20250028 01 03 2025.pdf PDF
47PJ0025R0028 CONSTRUCTION SET DRAWINGS SD.pdf PDF
47PJ0025R0028 CONSTRUCTION SET SPECIFICATIONS SD.pdf PDF
47PJ0025R0028 CONSTRUCTION SET SPECIFICATIONS.pdf PDF
Attachment 13 -IRA Project Submittal Form and Data Dictionary.pdf PDF
Attachment 8 - P100 2024 Final.pdf PDF
Attachment 7 - GSA Base Lead Management Requirements.pdf PDF
Attachment 2 - Vendor Manual September 2023.pdf PDF
25R0028 IRA Sustainability Factor Table.xlsx XLSX spreadsheet
Attachment 11 - 23535 Sioux Falls Courthouse IRA Window Replacement Submittal_ Reporting Form.xlsx XLSX spreadsheet
Attachment 10 - Glass - GSA IRA Low Embodied Carbon Requirements.pdf PDF
Attachment 12 - Post Award Allocation Form IRA .xlsx XLSX spreadsheet
Attachment 6 - GSA SD 3rd Party Abatement Clearance Requirements.pdf PDF
Attachment 5 - GSA Rapid City USMS Asbestos Abatement Requirements.pdf PDF
Attachment 4 - GSA Lead Pre-Alteration Assessment SOW.pdf PDF
Offeror Representations and Certifications.pdf PDF
Agreement 47PJ0025R0028.pdf PDF
47PJ0025R0028 Form 1442.pdf PDF
47PJ0025R0028 CONSTRUCTION SET DRAWINGS.pdf PDF
Attachment 14 - Fire Protection MOP and Firewatch Log Example.pdf PDF
Attachment 9 - Supplemental Pricing and Invoicing Instructions IRA.pdf PDF
Attachment 3 - GSA SD Asbestos Pre-alt Inspection SOW.pdf PDF
Attachment 1 - USR_v4 - 3-1-2024 - SF Window Replacement.pdf PDF
SOW - Sioux Falls Courthouse IRA Window Replacement_15 Jan 25.pdf PDF
25R0028 Bid Sheet .xlsx XLSX spreadsheet
Solicitation 47PJ0025R0028.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

March 21, 2014

Asbestos Re-Inspection Report Sioux Falls Federal Building/Courthouse

Sioux Falls, South Dakota GSA Building No. SD0021

Prepared For:

General Services Administration/Public Buildings Services Acquisition Management Group, 8P2PQ

DFC Building 41 – Room 240 Denver, Colorado 80225

Pinyon Project No.:

1/13-346-09.8005.0016

March 21, 2014

Asbestos Re-Inspection Report

Sioux Falls Federal Building/Courthouse

Sioux Falls, South Dakota GSA Building No. SD0021

Prepared For:

General Services Administration/Public Buildings Services Acquisition Management Group, 8P2PQ

DFC Building 41 – Room 240 Denver, Colorado 80225

Pinyon Project No.:

1/13-346-09.8005.0016

Prepared by:

Timothy Grenier

South Dakota Asbestos Building Inspector #6076

Reviewed by:

Peter Becofske

Asbestos Department Manager

GENERAL BUILDING and CONSULTANT INFORMATION

Client General Services Administration/Public Buildings Services

Contact Thomas Record, Regional Industrial Hygienist

Client Telephone # 303.236.2549

Facility Inspected Sioux Falls Federal Building/Courthouse

Facility Address 400 South Phillips Street, Sioux Falls, SD 57104-6851

Date(s) of Re-Inspection January 27-29, 2014

Building Number SD0021

Consulting Firm Name Pinyon Environmental, Inc.

Consulting Firm Address 9100 West Jewell Avenue, Lakewood, CO 80232

Consulting Firm Telephone # 303.980.5200

Laboratory Address EMSL Analytical, Inc., 1010 Yuma Street, Denver, CO 80204

Laboratory Telephone # 303.740.5700

GENERAL BUILDING and CONSULTANT INFORMATION

Sioux Falls Federal Building/Courthouse 400 South Phillips Street Sioux Falls, South Dakota

GSA Building Location Code – SD0021

Date(s) of Construction 1895 with numerous remodels

Square Footage Approximately 78,044 square feet

Construction Stone exterior

Structural Concrete and plaster

Exterior Stone

Interior Concrete, plaster, and drywall

HVAC System Natural gas boiler

Space Utilization Offices and courthouses

Table of Contents

EXECUTIVE SUMMARY

1. Introduction and Scope of Work

2. Inspection Procedures

2.1 Inspection and Sampling

2.2 Laboratory Analysis

2.3 Quality Assurance and Quality Control

3. Survey Findings

3.1 Building Description

3.2 Findings

4. Conclusions and Recommendations

4.1 Conclusions

4.2 Recommendations

5. Removal Cost Estimate

6. Limitations

7. References

Appendices

Appendix A – Figures

Figure A-1 – Suspect ACBM Bulk Sample Locations - Basement Figure A-2 – ACBM Flooring and Miscellaneous Material Locations - Basement Figure A-3 – ACBM Thermal System Insulation Locations - Basement Figure A-4 – Suspect ACBM Bulk Sample Locations – First Floor Figure A-5 – ACBM Flooring and Miscellaneous Material Locations – First Floor Figure A-6 – ACBM Thermal System Insulation Locations – First Floor Figure A-7 – Suspect ACBM Bulk Sample Locations – Second Floor Figure A-8 – ACBM Flooring Material Locations – Second Floor Figure A-9 – ACBM Thermal System Insulation Locations – Second Floor Figure A-10 – Suspect ACBM Bulk Sample Locations – Third Floor Figure A-11 – ACBM Flooring Material Locations – Third Floor Figure A-12 – ACBM Thermal System Insulation Locations – Third Floor Figure A-13 – Suspect ACBM Bulk Sample Locations – Fourth Floor Figure A-14 – ACBM Thermal System Insulation Locations – Fourth Floor

Appendix B – Tables

Table B-1 – Summary of Confirmed Asbestos-Containing Materials and Recommended Response Actions

Table B-2 – Summary of Materials Confirmed Not To Contain Asbestos Table B-3 – Bulk Sample Analysis Results and Assumed Materials

Appendix C – Laboratory Analysis Report and Chain of Custody

Appendix D – Photographic Log

Appendix E – Abatement Documents

Table of Contents (continued)

Appendix F – General Inspection Information Asbestos Overview Sample Collection Requirements Material Category List Glossary

Appendix G – Inspector and Laboratory Certifications

Asbestos Re-Inspection Report Page 1 Sioux Falls Federal Building/Courthouse – Sioux Falls, SD March 21, 2014

EXECUTIVE SUMMARY

Pinyon Environmental, Inc. (Pinyon), was retained by General Services Administration (GSA) to perform asbestos re-inspection services of the Sioux Falls Federal Building/Courthouse located at 400 South Phillips Avenue, in Sioux Falls, SD 57104-6848.

The building was constructed in 1895 with numerous remodel dates. The facility inspected is a four-story stone, concrete, and plaster structure. It encompasses a total of 78,044 square feet of building space.

Typical interior finishes observed in the building include 9"x9" or 12"x12" floor tile, vinyl sheet flooring, carpet, terrazzo, stone tile, marble, and bare concrete finished floors. Vinyl tile exists under much of the carpeting. Walls are finished with gypsum wallboard, plaster or wood. Ceilings are finished with gypsum wallboard, plaster, 2'x4' ceiling panels, or 1'x1' glued on ceiling tiles. The exterior of the building is finished in stone. The roof includes both pitched with slate shingles, flat built-up asphalt with gravel ballast or rolled roofing.

The building is heated by two natural gas fired boilers located in the basement. Boiler insulation was not observed. The chiller system is also located in the basement and has been changed out to fiberglass insulation within the chiller room. Fan/mechanical rooms are located on the second, third, and fourth floors. The heating and cooling system pipes are insulated with asbestos- containing material or fiberglass insulation and elbows and joints are insulated with fiberglass and plastic sleeves or non-asbestos-containing mudded material. Domestic lines are insulated with fiberglass straight run insulation and fiberglass with plastic sleeves on the elbows and joints. Black foam insulation was also observed on some pipes. Vent lines are insulated with non-asbestos-containing straight run insulation and associated fittings are insulated with asbestos-containing mudded material. Fire lines located in the basement are insulated with asbestos- containing straight run insulation and mudded fittings. Ducting is either uninsulated or insulated with fiberglass.

During this re-inspection completed on January 27, 28, and 29, 2014, 14 additional suspect asbestos-containing building materials were identified. To protect the structural integrity, five of the suspect materials (CTA01, CTA02, FDM01, CTA03, and CTA04) were assumed to contain asbestos. The remaining nine suspect materials (CT01, DTS01, PC01, PPS01, SUC02, PL01, SUC03, PPS02, and CT02) were analyzed by Polarized Light Microscopy (PLM). Upon PLM analysis sink undercoating (SUC02) was determined to contain asbestos.

Asbestos-containing thermal system insulation in damaged condition was noted in Rooms B3C, B5, and B5A.

Abatement History

Abatement history records were not available for this facility.

Asbestos Findings

Pinyon conducted an asbestos re-inspection of the Sioux Falls Federal Building/Courthouse on January 27, 28, and 29, 2014. Materials assumed to contain asbestos were not sampled to protect structural integrity. The following suspect homogeneous materials were confirmed or assumed to contain asbestos:

Material Description Material Number and Additional Comments

12" x 12" Floor Tile F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

Asbestos Re-Inspection Report Page 2

March 21, 2014

Material Description Material Number and Additional Comments

12" x 12" Floor Tile F2.8 12"x12" Beige w/ peach, brown & white streaks floor tile (ACM) w/mastic (ND)

9" x 9" Floor Tile F3.1 Red with brown and tan streaks floor tile (ACM) with mastic (ND) - Material located beneath non-suspect 12"x12"

9" x 9" Floor Tile F3.2 9"x9" Brown w/red and cream streaks floor tile (ACM) with mastic (ND)

Mastic under Floor Tile/etc. F5.1 Black mastic under various types of flooring

Roofing Materials M1.2 Rolled asphaltic roofing, assumed and not sampled to maintain structural integrity

Roofing Materials M1.3 Asphaltic built-up roofing assumed and not sampled to maintain structural integrity

Gasket Materials T1.1 Heating system flame gaskets, assumed and not sampled to ensure structural integrity

Pipe Joint Insulation T2.5 Fireline mudded fittings

Pipe Joint Insulation T2.7 Vent line mudded fittings

Straight Pipe Insulation T3.5 Fireline hard straight run insulation

Straight Pipe Insulation T3.7 Abandoned heating, hard straight run insulation

Straight Pipe Insulation T3.9 Heating and cooling aircell insulation

HVAC Connector Material T4.1 White vibration joint cloth

Tank Insulation T5.1 Hot water conversion tank insulation

Boiler Breaching/etc. T7.1 Boiler flue insulation

Sink Undercoating SUC02 – black, rough

Ceramic Tile Adhesive CTA01 – under 5”x5” tan tile (Assumed)

Ceramic Tile Adhesive CTA02 – under 6”x12” white tile (Assumed)

Fire Door Material FDM01 – fireproofing within fire door (Assumed)

Ceramic Tile Adhesive CTA03 – under 9”x9” gray tile (Assumed)

Ceramic Tile Adhesive CTA04 – under tan marbled 12”x12” tile (Assumed)

Notes:

“ inches

Asbestos Re-Inspection Report Page 3

March 21, 2014

Recommendations

Based on the results of laboratory analysis of bulk samples and visual and tactile assessment of building materials confirmed to contain asbestos, Pinyon recommends the following specific management actions:

Material Description Material Number and Additional Comments Management

Recommendations

12" x 12" Floor Tile F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) O&M

12" x 12" Floor Tile F2.8 12"x12" Beige w/ peach, brown & white streaks floor tile (ACM) w/mastic (ND) O&M

9" x 9" Floor Tile F3.1 Red with brown and tan streaks floor tile

(ACM) with mastic (ND) - Material located beneath non-suspect 12"x12"

O&M

9" x 9" Floor Tile F3.2 9"x9" Brown w/red and cream streaks floor tile (ACM) with mastic (ND)

O&M

Mastic under Floor Tile/etc.

F5.1 Black mastic under various types of flooring O&M

Roofing Materials M1.2 Rolled asphaltic roofing, assumed and not sampled to maintain structural integrity O&M

Roofing Materials M1.3 Asphaltic built-up roofing assumed and not sampled to maintain structural integrity O&M

Gasket Materials T1.1 Heating system flame gaskets, assumed and not sampled to insure structural integrity

O&M

Pipe Joint Insulation T2.5 Fire line mudded fittings

Remove from Corridor B3C (in front of Room

B8 door) O&M for rest of material

Pipe Joint Insulation T2.7 Vent line mudded fittings O&M

Straight Pipe Insulation T3.5 Fire line hard straight run insulation O&M

Straight Pipe Insulation T3.7 Abandoned heating, hard straight run insulation O&M

Straight Pipe Insulation T3.9 Heating and cooling aircell insulation O&M

HVAC Connector Material T4.1 White vibration joint cloth O&M

Tank Insulation T5.1 Hot water conversion tank insulation O&M

Boiler Breaching/etc. T7.1 Boiler flue insulation O&M

Sink Undercoating SUC02 – black, rough O&M

Ceramic Tile Adhesive CTA01 – under 5”x5” tan tile O&M

Ceramic Tile Adhesive CTA02 – under 6”x12” white tile O&M

Fire Door Material FDM01 – fireproofing within fire door O&M

Ceramic Tile Adhesive CTA03 – under 9”x9” gray tile O&M

Asbestos Re-Inspection Report Page 4

March 21, 2014

Material Description Material Number and Additional Comments Management

Recommendations

Ceramic Tile Adhesive CTA04 – under tan marbled 12”x12” tile O&M

Notes:

O&M Operations and Maintenance

Asbestos Re-Inspection Report Page 5

March 21, 2014

1. Introduction and Scope of Work

Pinyon Environmental was retained by General Services Administration to perform a re-inspection asbestos survey of the Sioux Falls Federal Building/Courthouse located at 400 South Phillips Avenue in Sioux Falls, South Dakota. The purpose of this survey was to identify friable and non-friable suspect asbestos-containing building materials (ACBM).

The scope of this inspection included the following activities:

Surveying, identifying, and sampling suspect friable and non-friable ACBM.

Preparing this comprehensive report documenting the sampling procedures and results of the ACBM survey.

To accomplish this survey, all accessible areas of the building were identified by name and assigned room numbers. A summary of identified functional spaces is presented in Table 3-1.

Within each space, suspect building materials were identified. P i n y o n uses a standardized numbering format to identify suspect building materials, and to identify bulk samples.

The report contains six sections. The six sections are: introduction and scope of work; inspection procedures; survey findings; conclusions and recommendations; removal cost estimate; and limitations sections. The report also contains seven appendices. Appendix A contains figures, Appendix B contains tables, Appendix C contains the laboratory analysis report and chain of custodies, Appendix D contains a Photographic Log, Appendix E contains abatement documents (if there are any), Appendix F contains general inspection informations, and Appendix G contains inspector and laboratory certification.

Asbestos Re-Inspection Report Page 6

March 21, 2014

2. Inspection Procedures

The asbestos survey was performed using the applicable portions of the currently recognized standard protocol developed for schools under AHERA, as promulgated in Title 40, Code of Federal Regulations (40 CFR), Part 763 and as amended in the Federal Register (EPA, 2011). Since the primary concern for this investigation was to identify potential asbestos hazards in the entire building, Pinyon or its representatives visually inspected existing conditions within the entire facility. An overview of asbestos and current regulations and a glossary of common terms is presented in Appendix F.

2.1 Inspection and Sampling

The inspection was conducted by our State certified and AHERA accredited asbestos inspector, and consisted of a detailed visual survey of surfacing materials, thermal system insulation, and miscellaneous materials throughout the building. Suspect ACBM was then grouped into homogeneous materials and sampling plans developed. Components of the inspection included:

Identification of homogeneous suspect materials on a room by room basis (Appendices A and B).

An assessment of known or assumed ACBM, generally classifying the materials using categories defined in the AHERA and National Emission Standards of Hazardous Air Pollutants (NESHAP), for asbestos. A description of NESHAP categories is presented in the Section 3 Room-By-Room Table Key.

Homogeneous suspect ACBM’s were, for the purpose of this study, placed into the following four materials type categories: Thermal System Insulation (TSI), surfacing materials, miscellaneous materials, and floor covering. AHERA sampling protocol specifies sampling procedures for each material type (Appendix F).

Sample locations for this survey were chosen in a non-random fashion, with emphasis placed on obtaining samples of each type of accessible, suspect material and minimizing damage to the material being sampled (Appendix A Figures A-1, A-4, A-7, A-10, and A-13). Samples were collected by carefully removing small portions of the suspect material in a non-abrasive manner. If possible, samples from existing damaged areas or loose pieces of material were collected. Samples were obtained by using techniques such as wet slicing, wet boring or similar methods designed to limit contamination of the area during sampling. The sampled area was sealed using patching compounds, duct tape, or spray encapsulates as appropriate to the material being sampled.

Immediately after collection, samples were placed in pre-labeled ‘zip-lock’ bags. The bags with samples were then placed in a large re-sealable plastic bag for transportation to the laboratory.

Photographs of each suspect ACBM were taken during the inspection (Appendix D).

2.2 Laboratory Analysis

Bulk samples obtained during the inspection were assigned bulk sample numbers and entered on sample summary/chain-of-custody forms. The analysis was performed in accordance with EPA Interim Method 600/M4-82-020, which employs polarized light microscopy (PLM) with dispersion staining for identification of mineral forms of asbestos. The quantification of asbestos in the sample is intended to be an estimate only and the limit of detection for this method is approximately 1% by volume.

Asbestos Re-Inspection Report Page 7

March 21, 2014

2.3 Quality Assurance and Quality Control

Quality Assurance and Quality Control (QA/QC) measures adopted by Pinyon involved field and office components. Key parameters are summarized below:

Field QA/QC

Review inspection forms for completeness

Check homogeneous materials listing for sufficient number of collected samples

Verify locations of major mechanical components

Office QA/QC

Review lab results for completeness

Ensure appropriate cross-referencing of results, forms for given ACBM

Ensure drawings are updated as necessary following field QC

Verify approximate quantities of ACBM based on drawing review

Review recorded field comments for meaning, incorporate as necessary into report

Asbestos Re-Inspection Report Page 8

March 21, 2014

3. Survey Findings

3.1 Building Description

Pinyon Environmental, Inc. (Pinyon), was retained by General Services Administration (GSA) to perform asbestos re-inspection services of the Sioux Falls Federal Building/Courthouse located at 400 South Phillips Avenue, in Sioux Falls, SD 57104-6848.

The building was constructed in 1895 with numerous remodel dates. The facility inspected is a four-story stone, concrete, and plaster structure. It encompasses a total of 78,044 square feet of building space.

Typical interior finishes observed in the building include 9"x9" or 12"x12" floor tile, vinyl sheet flooring, carpet, terrazzo, stone tile, marble, and bare concrete finished floors. Vinyl tile exists under much of the carpeting. Walls are finished with gypsum wallboard, plaster or wood. Ceilings are finished with gypsum wallboard, plaster, 2'x4' ceiling panels, or 1'x1' glued on ceiling tiles. The exterior of the building is finished in stone. The roof includes both pitched with slate shingles, flat built-up asphalt with gravel ballast or rolled roofing.

The building is heated by two natural gas fired boilers located in the basement. Boiler insulation was not observed. The chiller system is also located in the basement and has been changed out to fiberglass insulation within the chiller room. Fan/mechanical rooms are located on the second, third, and fourth floors. The heating and cooling system pipes are insulated with asbestos- containing material or fiberglass insulation and elbows and joints are insulated with fiberglass and plastic sleeves or non-asbestos-containing mudded material. Domestic lines are insulated with fiberglass straight run insulation and fiberglass with plastic sleeves on the elbows and joints. Black foam insulation was also observed on some pipes. Vent lines are insulated with non-asbestos-containing straight run insulation and associated fittings are insulated with asbestos-containing mudded material. Firelines located in the basement are insulated with asbestos- containing straight run insulation and mudded fittings. Ducting is either uninsulated or insulated with fiberglass.

During this re-inspection completed on January 27, 28, and 29, 2014, 14 additional suspect asbestos-containing building materials were identified. To protect the structural integrity, five of the suspect materials (CTA01, CTA02, FDM01, CTA03, and CTA04) were assumed to contain asbestos. The remaining nine suspect materials (CT01, DTS01, PC01, PPS01, SUC02, PL01, SUC03, PPS02, and CT02) were analyzed by Polarized Light Microscopy (PLM). Upon PLM analysis sink undercoating (SUC02) was determined to contain asbestos.

3.2 Findings

Pinyon conducted an asbestos re-inspection of the Sioux Falls Federal Building/Courthouse on January 27, 28, and 29, 2014. Materials assumed to contain asbestos were not sampled to protect structural integrity. The following suspect homogeneous materials were confirmed (Appendix C) or assumed to contain asbestos:

Material Description Material Number and Additional Comments

12" x 12" Floor Tile F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

12" x 12" Floor Tile F2.8 12"x12" Beige w/ peach, brown & white streaks floor tile

(ACM) w/mastic (ND)

9" x 9" Floor Tile F3.1 Red with brown and tan streaks floor tile (ACM) with mastic

(ND) - Material located beneath non-suspect 12"x12"

Asbestos Re-Inspection Report Page 9

March 21, 2014

Material Description Material Number and Additional Comments

9" x 9" Floor Tile F3.2 9"x9" Brown w/red and cream streaks floor tile (ACM) with mastic (ND) Mastic under Floor Tile/etc. F5.1 Black mastic under various types of flooring

Roofing Materials M1.2 Rolled asphaltic roofing, assumed and not sampled to maintain structural integrity

Roofing Materials M1.3 Asphaltic built-up roofing assumed and not sampled to maintain structural integrity

Gasket Materials T1.1 Heating system flame gaskets, assumed and not sampled to insure structural integrity Pipe Joint Insulation T2.5 Fire line mudded fittings Pipe Joint Insulation T2.7 Vent line mudded fittings

Straight Pipe Insulation T3.5 Fire line hard straight run insulation Straight Pipe Insulation T3.7 Abandoned heating, hard straight run insulation Straight Pipe Insulation T3.9 Heating and cooling aircell insulation

HVAC Connector Material T4.1 White vibration joint cloth Tank Insulation T5.1 Hot water conversion tank insulation

Boiler Breaching/etc. T7.1 Boiler flue insulation Sink Undercoating SUC02 – black, rough

Ceramic Tile Adhesive CTA01 – under 5”x5” tan tile (Assumed) Ceramic Tile Adhesive CTA02 – under 6”x12” white tile (Assumed)

Fire Door Material FDM01 – fireproofing within fire door (Assumed) Ceramic Tile Adhesive CTA03 – under 9”x9” gray tile (Assumed) Ceramic Tile Adhesive CTA04 – under tan marbled 12”x12” tile (Assumed)

Asbestos Re-Inspection Report Page 10

March 21, 2014

TABLE 3-1: Functional Space Summary Floor Room Functional Space Comments

1 101

ENTRANCES AND

EXIT AREAS Exterior Landing

1 101A ENTRANCES AND

EXIT AREAS Vestibule

1 102 OFFICES Office 1 103 LOBBIES Lobby 1 103A HALLWAYS Corridor 1 103B HALLWAYS Corridor 1 104 LOBBIES Reception 1 104A WORK-ROOM Copy and Stacks 1 104B OFFICES Office 1 105 OFFICES Office 1 106 OFFICES Office 1 106A COMPUTER ROOM Computer Room 1 107 STORAGE Storage 1 107A STORAGE Storage 1 108 STORAGE 12"x12" Floor Tile 1 111 OFFICES GSA Office 1 111A STORAGE Storage 1 113 JANITOR CLOSET Janitor Closet

1 114

ENTRANCES AND

EXIT AREAS Vestibule

1 114A

ENTRANCES AND

EXIT AREAS Exterior Landing

1 115 MULTI-PURPOSE

ROOM

Break Room

1 117 MULTI-PURPOSE

ROOM

Court Room

1 117A MEETING ROOMS Conference Room 1 117C CONFERENCE ROOM Conference Room 1 119 OFFICES Receptionist Office 1 119B MEETING ROOMS Conference Room 1 119C OFFICES Office 1 119D OFFICES Office 1 119E OFFICES Judge's Chambers 1 119F RESTROOM Restroom 1 120 RESTROOM Men's Restroom 1 122 RESTROOM Restroom Entrance 1 122A RESTROOM Women's Restroom

1 124

ENTRANCES AND

EXIT AREAS Grand Jury Entrance

1 124A

MULTI-PURPOSE

ROOM Grand Jury

1 124B RESTROOM Women's Restroom 1 124C RESTROOM Men's Restroom 1 125 OFFICES Office 1 125A LOBBIES Reception Room

Asbestos Re-Inspection Report Page 11

March 21, 2014

Floor Room Functional Space Comments 1 125B MEETING ROOMS Conference Room 1 127 HALLWAYS Corridor 1 127A COMPUTER ROOM Computer Room 1 127B STORAGE Files 1 127C OFFICES Office 1 127D OFFICES Office 1 127F RESTROOM Restroom 1 128 OFFICES Receptionist Office 1 128A STORAGE Files 1 128B RESTROOM Restroom 1 128C STORAGE Storage 1 129B OFFICES Office 1 129C OFFICES Office 1 129D MEETING ROOMS Conference Room 2 201 HALLWAYS Corridor 2 201A HALLWAYS Corridor 2 202 OFFICES Office 2 202A JANITOR CLOSET Closet 2 202B RESTROOM Restroom 2 203 OFFICES Office

2 204 MULTI-PURPOSE

ROOM

Jury Room

2 204A STORAGE Storage 2 205A STORAGE Storage 2 205B STORAGE Storage

2 206 MULTI-PURPOSE

ROOM

Court Room

2 206B STORAGE Storage 2 206D RESTROOM Women's Restroom 2 206E RESTROOM Men's Restroom 2 207 RESTROOM Men's Restroom 2 208 OFFICES Office 2 208A CLOSET Closet 2 208B RESTROOM Restroom 2 212 OFFICES Office 2 212A STORAGE Storage 2 212B OFFICES Office 2 212C OFFICES Office 2 214 OFFICES Office 2 215 MECHANICAL ROOM Mechanical Room 2 216 LOBBIES Lobby 2 216A OFFICES Office 2 216B JANITOR CLOSET Closet 2 216C OFFICES Office 2 216D COMPUTER ROOM Computer Room 2 216E STORAGE Storage 2 216F VAULTS Vault 2 217 RESTROOM Women's Restroom

Asbestos Re-Inspection Report Page 12

March 21, 2014

Floor Room Functional Space Comments

2 217A

ELEVATOR

ROOM/HOISTWAYS Elevator Control

2 218 N/A Holding Cells 2 218A N/A Cell 2 219 MECHANICAL ROOM Mechanical Room 2 220 N/A Court Room 2 221 MECHANICAL ROOM Mechanical Room 2 221A STORAGE Storage 2 221B RESTROOM Restroom 2 221C HALLWAYS Corridor 2 221D MEETING ROOMS Conference Room 2 222 OFFICES Office 2 222A JANITOR CLOSET Closet 2 222B OFFICES Office 2 222D STORAGE Storage 2 223 N/A Witness Room 2 225 MECHANICAL ROOM Mechanical Room 2 231 LIBRARY/CORRIDOR Library 2 231A N/A Witness Room 2 231B HALLWAYS Corridor 2 231D OFFICES Office 2 231E OFFICES Office 2 231F OFFICES Office 2 231G OFFICES Office 2 231H VAULTS Vault 2 231I STORAGE Storage 2 231J STORAGE Storage 2 231K STORAGE Storage 2 232 HALLWAYS Corridor

2 232A MULTI-PURPOSE

ROOM

Library

2 232B

MULTI-PURPOSE

ROOM Break Room

2 232C VAULTS Vault 2 233 STORAGE Storage 3 301 HALLWAYS Corridor 3 302 STAIRWELLS Corridor/Stairs 3 303 OFFICES Office 3 303A JANITOR CLOSET Closet 3 303B STORAGE Storage 3 303C RESTROOM Restroom 3 303D MEETING ROOMS Conference Room 3 303E OFFICES Office 3 304 OFFICES Office 3 304A OFFICES Office 3 305 OFFICES Office 3 306 RESTROOM Men's Restroom

Asbestos Re-Inspection Report Page 13

March 21, 2014

Floor Room Functional Space Comments

3 307 RESTROOM

Women's Restroom

Lounge Entrance 3 307A RESTROOM Women's Restroom 3 308 MECHANICAL ROOM Mechanical Room 3 309A STORAGE Storage 3 309B OFFICES Office 3 309C OFFICES Office 3 309D OFFICES Office

3 310

MULTI-PURPOSE

ROOM Library

3 311 HALLWAYS Corridor 3 311A JANITOR CLOSET Closet 3 311B RESTROOM Restroom 3 311C OFFICES Office 3 311D STORAGE Storage 3 311E OFFICES Judge's Chambers 3 311F HALLWAYS Corridor 3 311G RESTROOM Restroom

3 311H MULTI-PURPOSE

ROOM

Library

3 311I KITCHEN Kitchen Area 3 315 OFFICES Office 3 315A JANITOR CLOSET Closet 3 315B WORK-ROOM Copy Room 3 315C STAIRWELLS Corridor 3 315D STORAGE Storage 4 401 RECEPTION Receptionist Office 4 401A OFFICES Office 4 401B OFFICES Office 4 401C OFFICES Office 4 402 STAIRWELLS Stairs 4 403 ATTICS Attic/Storage 4 404 ATTICS Attic/Storage 4 405 STAIRWELLS Corridor 4 406 ATTICS Attic/Storage 4 407 ATTICS Attic/Storage 4 408 ATTICS Attic/Storage 4 409 ATTICS Attic/Storage 4 410 ATTICS Attic/Storage 4 411 PENTHOUSE Penthouse

4 412

ELEVATOR

ROOM/HOISTWAYS Penthouse Elevator

5 501 EXTERIOR Exterior 6 601 ROOFS Second Floor Roof - Flat

6 602 ROOFS

Second Floor Roof -

Pitched 6 603 ROOFS Third Floor Roof - Flat

Asbestos Re-Inspection Report Page 14

March 21, 2014

Floor Room Functional Space Comments

6 604 ROOFS

Fourth Floor Roof -

Pitched B B1 STORAGE Storage B B10 MECHANICAL ROOM Mechanical Room B B11 N/A Chiller Room

B B11A

TELEPHONE/ELEC.

ROOMS Electric Room

B B12 STORAGE Storage B B13 RESTROOM Men's Restroom B B14 N/A Vacant B B15B JANITOR CLOSET Closet B B17C CELL Cell B B17D CORRIDOR Corridor B B18 OFFICES Office B B18A STORAGE Storage B B19 FITNESS CENTER Aerobics Room B B19A STORAGE Storage

B B19B

MULTI-PURPOSE

ROOM Refreshment Room

B B2 STORAGE Storage B B20 STAIRWELLS Corridor B B20A RESTROOM Restroom B B20B STORAGE Storage B B20C STAIRWELLS Stairs B B21 N/A Vacant B B22 GYMNASIUM Gymnasium/Storage B B23 OFFICES Office B B24 GYMNASIUM Gymnasium B B26 N/A Pipe Access B B28 STAIRWELLS Corridor B B28A VAULTS Vault B B28B RESTROOM Washroom

B B28C

MULTI-PURPOSE

ROOM Break Room

B B29

TELEPHONE/ELEC.

ROOMS Phone Room

B B3 STAIRWELLS Corridor B B30 STORAGE Storage B B36 STORAGE Storage B B37 STORAGE Hazmat Storage B B38 STORAGE Storage B B39 STORAGE Storage B B3A STAIRWELLS Corridor B B3B MECHANICAL ROOM Boiler Room B B3C STAIRWELLS Corridor B B4 STORAGE Storage B B4A STORAGE Storage B B5 STAIRWELLS Corridor

Asbestos Re-Inspection Report Page 15

March 21, 2014

Floor Room Functional Space Comments B B5A OFFICES Office B B6 STORAGE Storage B B7 STORAGE Storage B B7A STORAGE Storage B B8 N/A GSA Shop B B8A STORAGE Shop Storage

B B8B MECHANICAL ROOM Emergency Generator Room

B E-1

ELEVATOR

ROOM/HOISTWAYS Public Elevator

B E-2

ELEVATOR

ROOM/HOISTWAYS Utility Elevator

B E-3 ELEVATOR

ROOM/HOISTWAYS

Public Elevator

B S1A STAIRWELLS West Stairwell 1 S1B STAIRWELLS Stairs 2 S1C STAIRWELLS Stairs 3 S1D STAIRWELLS Stairs 4 S1E STAIRWELLS Stairs B S2A STAIRWELLS South Stairwell B S3A STAIRWELLS Northeast Stairwell 1 S3B STAIRWELLS Stairs 2 S3C STAIRWELLS Stairs 3 S3D STAIRWELLS Stairs B SB1 N/A Landing

B SB2 ENTRANCES AND

EXIT AREAS

Vestibule

N/A Not Applicable

Asbestos Re-Inspection Report Page 16

March 21, 2014

Table B Key

The following is an explanation of each column listed in Table B:

Floor No.

The floor level of the building.

Room No.

A list of all spaces in numeric order. Due to the need for each inspected space to have a unique identifying number, the room numbers in this column may differ from the actual room numbers used in the building.

The drawings in Appendix A are annotated with the assigned numbers from the inspection and can be used to resolve any questions.

Room Description

A general description for the use of the room at the time of the inspection.

Homogeneous Material Number and Description

This column provides a number and description of all suspect ACBM in each functional space/room. A summary of homogeneous ACBM types can be found in Appendix B, Table 1. A list of non-asbestos containing homogeneous materials can be found in Appendix B, Table 2.

Bulk Sample No.

Bulk samples collected during this current inspection are listed in this column. Sample location within the room and sample analysis can be found in Appendix B, Table 3.

ACBM

This column either lists “Yes” for suspect materials determined to be an ACBM or “No” if analysis of the suspect material comes back negative for the presence of asbestos.

Friable

If a suspect material can be reduced to powder with hand pressure, “Yes” will be typed into this column.

Otherwise, “No” will be typed into the column.

ACBM Quantity

The quantity of a specific ACBM located within a room will be listed in this column.

Units

This column lists how the ACBM was measured (SF = square feet; EA = each; LF = linear feet).

Asbestos Re-Inspection Report Page 17

March 21, 2014

Table B Key (continued)

Hazard Rank and Removal Priority

Per AHERA regulations, each known and/or assumed friable asbestos-containing material is assessed for condition and is assigned a Hazard Rank number and Removal Priority number which is listed in these two columns. The Hazard Rank and Removal Priority for Friable ACBM table is located on the following page as a supplement to Table B and details the procedure for assigning AHERA Hazard Ranking and Removal Priorities for materials based on the degree of damage observed.

Asbestos Re-Inspection Report Page 18

March 21, 2014

Supplement to Table B: Room by Room Summary of Suspect and Confirmed ACBMs

Response Actions Based on Hazard Ranking

Hazard Rank Removal Priority

AHERA

Categories Response Actions Required by AHERA

7 1 Significantly Damaged

Evacuate or restrict the area if needed. Remove the ACBM (or enclose or encapsulate it if sufficient to contain fibers).

Repair of TSI allowed if feasible and safe. O&M required for all

ACBM.

6 2

Damaged with Potential for Significant Damage

Evacuate or restrict the area if needed. Remove, enclose, encapsulate, or repair to correct damage. Take steps to reduce potential for disturbance. O&M required for all ACBM.

5 3 Damaged with Potential for

Damage

Remove, enclose, encapsulate, or repair to correct damage.

O&M required for all ACBM.

4 4 Damaged with

Low Potential for Damage

Same as Hazard Rank 5

3 5

Good with Potential for Significant Damage

Evacuate or restrict the area if needed. Take steps to reduce potential for disturbance. O&M required for all ACBM.

2 6 Good with

Potential for Damage

O&M required for all ACBM.

Take steps to reduce potential for damage.

1 7 Good with Low

Potential for Disturbance

O&M required for all ACBM

Notes:

O&M Operations and Maintenance ACBM Asbestos Containing Building Materials TSI Thermal System Insulation

TABLE B: Room-by-Room Summary of Suspect and Confirmed ACBM’s

Facility Name: Sioux Falls Federal Building/Courthouse Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021 Date of Inspection: January 27, 28, and 29, 2014 Site Inspected By: Tim Grenier

Asbestos Re-Inspection Report Page 11

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 101 Exterior Landing Walls - Stone None No NA NA NA NA NA

1 101 Exterior Landing Floor, ceiling - Concrete None No NA NA NA NA NA

1 101A Vestibule M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 101A Vestibule Walls, ceiling - Glass None No NA NA NA NA NA 1 101A Vestibule Floor, cove base - Stone None No NA NA NA NA NA

1 102 Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 246 SF 1 7

1 102 Office M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 102 Office M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 102 Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 102 Office Floor - Carpet None No NA NA NA NA NA

1 102B Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 192 SF 1 7

1 102B Office M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 102B Office M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 102B Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 102B Office Floor - Carpet None No NA NA NA NA NA 1 103 Lobby M5.5 2'x2' Decorative None No NA NA NA NA NA

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 12

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 103 Lobby M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 103 Lobby Floor, cove base - Stone tile None No NA NA NA NA NA

1 103A Corridor M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 103A Corridor M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 103A Corridor F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 1386 SF 1 7

1 103A Corridor F2.2 12"x12" Cream with beige and white flecks floor tile with mastic

F2.2 A,B,C No NA NA NA NA NA

1 103A Corridor F2.3 12"x12" Dark beige with brown flecks floor tile with mastic

F2.3 A,B,C No NA NA NA NA NA

1 103A Corridor M3.1 Walls - First floor wallboard/taping/compound

None No NA NA NA NA NA

1 103A Corridor PL01 - Plaster - white plaster blocks

PL01-

001, 002,003, 004, 005, 006, 007

No NA NA NA NA NA

1 103B Corridor M5.2 2'x4' Divided 92'x2') small cavity and pinhole

None No NA NA NA NA NA

1 103B Corridor M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 103B Corridor Walls, cove base - Marble None No NA NA NA NA NA 1 103B Corridor Floor - Tile, marble None No NA NA NA NA NA

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 13

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 103B Corridor M12.2 4" Vinyl cove base with brown adhesive None No NA NA NA NA NA

1 104 Reception M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 104 Reception Floor - Carpet None No NA NA NA NA NA

1 104 Reception M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 104 Reception F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 120 SF 1 7

1 104 Reception M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 104A Copy and Stacks

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None Yes No 590 SF 1 7

1 104A Copy and Stacks

M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 104A Copy and Stacks

M5.1 2'x4' Small fissure and pinhole

M5.1 C No NA NA NA NA NA

1 104A Copy and Stacks

M3.1 Walls - First floor wallboard/taping/compound

None No NA NA NA NA NA

1 104A Copy and Stacks Floor - Carpet None No NA NA NA NA NA

1 104B Office Floor - Carpet None No NA NA NA NA NA

1 104B Office M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 14

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 104B Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 762 SF 1 7

1 104B Office M7.1 Plaster (1895) None No NA NA NA NA NA

1 104B Office M5.1 2'x4' Small fissure and pinhole None No NA NA NA NA NA

1 105 Office Floor - Carpet None No NA NA NA NA NA

1 105 Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 195 SF 1 7

1 105 Office M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 105 Office M5.1 2'x4' Small fissure and pinhole None No NA NA NA NA NA

1 105 Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 105 Office M3.1 Walls - First floor wallboard/taping/compound

None No NA NA NA NA NA

1 106 Office Floor - Carpet None No NA NA NA NA NA

1 106 Office M3.1 Walls - First floor wallboard/taping/compound None No NA NA NA NA NA

1 106 Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 106 Office M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 106 Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 194 SF 1 7

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 15

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 106 Office M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 106 Office T2.2 Heating and cooling mudded fittings None No NA NA NA NA NA

1 106 Office T3.1 Fiberglass straight run insulation, domestic None No NA NA NA NA NA

1 106 Office PL01 - Plaster - white plaster blocks

PL01-

001, 002,003, 004, 005, 006, 007

No NA NA NA NA NA

1 106A Computer Room

M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 106A Computer Room Floor - Carpet None No NA NA NA NA NA

1 106A Computer Room M7.1 - Plaster (1895) None No NA NA NA NA NA

1 106A Computer Room

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None Yes No 40 SF 1 7

1 106A Computer Room

M12.1 4' & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 106A Computer Room

M3.1 Walls - First floor wallboard/taping/compound

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 16

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 107 Storage F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 224 SF 1 7

1 107 Storage M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 107 Storage M5.6 2'x4' Deep worm and pinhole

M5.6 A,B,C No NA NA NA NA NA

1 107 Storage M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 107 Storage Floor - Carpet None No NA NA NA NA NA

1 107 Storage PL01 - Plaster - white plaster blocks

PL01-

001, 002,003, 004, 005, 006, 007

No NA NA NA NA NA

1 107A Storage F2.4 12'x12' Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None No NA NA NA NA NA

1 107A Storage M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 107A Storage M12.1 4" &6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 107A Storage M5.3 2'x4' Dense medium fissure and pinhole

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 17

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 107A Storage PL01 - Plaster - white plaster blocks

PL01-

001, 002,003, 004, 005, 006, 007

No NA NA NA NA NA

1 108 Conference Room

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None Yes No 578 SF 1 7

1 108 Conference Room

M5.3 2'x4' Dense medium fissure and pinhole None No NA NA NA NA NA

1 108 Conference Room M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 108 Conference Room Floor - Carpet None No NA NA NA NA NA

1 108 Conference Room

PL01 - Plaster - white plaster blocks

PL01-

001, 002,003, 004, 005, 006, 007

No NA NA NA NA NA

1 111 GSA Office M5.2 2'x4' Divided (2'x2') small cavity and pinhole

M5.2 C No NA NA NA NA NA

1 111 GSA Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 111 GSA Office M12.2 4" Vinyl cove base with brown adhesive M12.2 C No NA NA NA NA NA

1 111 GSA Office F2.4 12"x12" Beige w/dark beige & white floor tile

F2.4 C Yes No 180 SF 1 7

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 18

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 111 GSA Office Floor - Carpet None No NA NA NA NA NA 1 111A Storage Floor - Carpet None No NA NA NA NA NA

1 111A Storage F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 127 SF 1 7

1 111A Storage M12.2 4" Vinyl cove base with brown adhesive

None No NA NA NA NA NA

1 111A Storage M5.2 2'x4' Divided (2'x2') small cavity and pinhole

None No NA NA NA NA NA

1 111A Storage M7.1 Walls - Plaster M7.1 G No NA NA NA NA NA

1 113 Janitor Closet T3.2 Heating and cooling fiberglass straight run insulation

None No NA NA NA NA NA

1 113 Janitor Closet T2.2 Heating and cooling mudded fittings

None No NA NA NA NA NA

1 113 Janitor Closet Floor - Terrazzo None No NA NA NA NA NA 1 113 Janitor Closet M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 113 Janitor Closet Walls - Marble None No NA NA NA NA NA

1 114 Vestibule T3.2 Heating and cooling fiberglass straight run insulation

None No NA NA NA NA NA

1 114 Vestibule T2.8 Heating and cooling mudded fitting - Assumed

None Yes Yes 1 EA 2 6

1 114 Vestibule T2.2 Heating and cooling mudded fittings None No NA NA NA NA NA

1 114 Vestibule T3.7 Abandoned heating, hard straight run insulation

T3.7 A,B,C Yes Yes 8 LF 2 6

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 19

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 114 Vestibule M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

1 114 Vestibule M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 114 Vestibule F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 118 SF 1 7

1 114 Vestibule Walls - brick None No NA NA NA NA NA

1 114A Exterior Landing Floor, ceiling - Concrete None No NA NA NA NA NA

1 114A Exterior Landing Walls - CMU None No NA NA NA NA NA

1 115 Break Room M5.1 2'x4' Small fissure and pinhole None No NA NA NA NA NA

1 115 Break Room M7.1 Walls - Plaster None No NA NA NA NA NA

1 115 Break Room M12.1 4"x6" Vinyl cove base with white or cream adhesive

None No NA NA NA NA NA

1 115 Break Room F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 217 SF 1 7

1 115 Break Room Floor - Carpet None No NA NA NA NA NA 1 117 Court Room M7.1 Walls - Plaster None No NA NA NA NA NA 1 117 Court Room Floor - Carpet, concrete None No NA NA NA NA NA 1 117 Court Room Cove base - Wood None No NA NA NA NA NA 1 117 Court Room Floor - Carpet, concrete None No NA NA NA NA NA

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 20

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 117 Court Room M12.2 4" Vinyl cove base with brown adhesive M12.2 A No NA NA NA NA NA

1 117 Court Room M5.1.1 2'x4' Small fissure and pinhole M5.1 A No NA NA NA NA NA

1 117 Court Room M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 117 Court Room M3.1 Walls - First floor wallboard/taping/compound

M3.1 A No NA NA NA NA NA

1 117A Conference Room

M5.1 2'x4' Small fissure and pinhole

M5.1 B No NA NA NA NA NA

1 117A Conference Room Floor - Carpet, concrete None No NA NA NA NA NA

1 117A Conference Room

M3.1 Walls - First floor wallboard/taping/compound M3.1 B No NA NA NA NA NA

1 117A Conference Room M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 117C Conference Room

M5.7 2'x4' Dense small fissure and pinhole

M5.7 B,C

No NA NA NA NA NA

1 117C Conference Room Floor - Carpet None No NA NA NA NA NA

1 117C Conference Room M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 117C Conference Room

M12.2 4" Vinyl cove base with brown adhesive None No NA NA NA NA NA

1 117C Conference Room

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) F2.4 B Yes No 233 SF 1 7

1 117C Conference Room

M5.1 2'x4' Small fissure and pinhole

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 21

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 117C Conference Room

F1.3 Gray vinyl sheet flooring

F1.3 A,B,C No NA NA NA NA NA

1 117C Conference Room

M12.1 4' & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 117C Conference Room

M3.1 Walls - First floor wallboard/taping/compound None No NA NA NA NA NA

1 117C Conference Room

M5.1 2'x4' Small fissure and pinhole

None No NA NA NA NA NA

1 119 Receptionist Office Floor - Carpet None No NA NA NA NA NA

1 119 Receptionist Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 119 Receptionist Office

M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

1 119 Receptionist Office

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) F2.4 A Yes No 461 SF 1 7

1 119 Receptionist Office

M3.1 Walls - First floor wallboard/taping/compound

None No NA NA NA NA NA

1 119 Receptionist Office

M5.7 2"x4" Dense small fissure and pinhole

M5.7 A No NA NA NA NA NA

1 119 Receptionist Office

M12.1 4" & 6" Vinyl cove base with white or cream adhesive None No NA NA NA NA NA

1 119B Conference Room

M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 22

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 119B Conference Room M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 119B Conference Room Floor - Carpet None No NA NA NA NA NA

1 119B Conference Room Cove base - Wood None No NA NA NA NA NA

1 119B Conference Room

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None Yes No 438 SF 1 7

1 119C Office Floor - Carpet None No NA NA NA NA NA

1 119C Office M3.1 Walls - First floor wallboard/taping/compound None No NA NA NA NA NA

1 119C Office M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

1 119C Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 193 SF 1 7

1 119C Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 119D Office F2.4 12"x12" Beige w/dark beige & white floor tile (ACM) with mastic (ACM)

None Yes No 185 SF 1 7

1 119D Office M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

1 119D Office M7.1 Walls - Plaster (1895) None No NA NA NA NA NA 1 119D Office Floor - Carpet None No NA NA NA NA NA

1 119E Judge's Chambers

M5.2 2'x4' Divided (2'x2') small cavity and pinhole

Address: 400 South Phillips Avenue City, State, ZIP Code: Sioux Falls, South Dakota 57104-6848 Building Number: SD0021

Asbestos Re-Inspection Report Page 23

March 21, 2014

Floor No.

Room No.

Room Description

Homogeneous Material Number and Description

Bulk Sample

No.

ACBM Friable ACBM

Quantity Units Hazard

Rank1 Removal Priority2

1 119E Judge's Chambers Floor - Carpet None No NA NA NA NA NA

1 119E Judge's Chambers

F2.4 12"x12" Beige w/dark beige & white floor tile

(ACM) with mastic (ACM) None Yes No 339 SF 1 7

1 119E Judge's Chambers M7.1 Walls - Plaster None No NA NA NA NA NA

1 119F Restroom M5.2 2'x4' Divided (2'x2') small cavity and pinhole

None No NA NA NA NA NA

1 119F Restroom Floors, walls - Ceramic tile None No NA NA NA NA NA

1 120 Men's Restroom

M5.2 2'x4' Divided (2'x2') small cavity and pinhole None No NA NA NA NA NA

1 120 Men's Restroom Floor, walls - Ceramic tile None No NA NA NA NA NA

1 122 Restroom Entrance

M5.2 2'x4' Divided (2'x2') small cavity and pinhole

None No NA NA NA NA NA

1 122 Restroom Entrance M7.1 Walls - Plaster (1895) None No NA NA NA NA NA

1 122 Restroom Entrance Floor - Tile, marble None No NA NA NA NA NA

1 122 Restroom Entrance Walls - Marble None No NA NA NA NA NA

1 122A…