Attachment 14 Basic Project Design Requirements 23 Oct 20.pdf

PDF 224 KB Posted

Attached to
Maintenance & Repair (M&R) IDIQ, Luke AFB, AZ
Solicitation number
FA488721R0014
Issued by

View the file

Other files

File Type Posted
FA488721R0014 Consolidated RFI Responses.xlsx XLSX spreadsheet
Attachment 8 Luke AFB Disc Submittal Guidelines.pdf PDF
Attachment 9 LUKE Design and Construction Standards.pdf PDF
Attachment 16 NAF Construction Clauses Definitions.pdf PDF
Attachment 2 Wage Determination AZ20210031 Maricopa County 26 Feb 2021.pdf PDF
Attachment 5 Ordering Procedures 26 Feb 2021.pdf PDF
Attachment 17 Joint Venture Teaming Partner Consent Letter 17 Dec 20.pdf PDF
Attachment 1 M and R SOW 5 Mar 2021.pdf PDF
Attachment 12 Luke Specification for Fire Protection and Life Safety 6 Jun 15.pdf PDF
Attachment 3 Wage Determination AZ20210030 Coconio County 26 Feb 2021.pdf PDF
Attachment 11 Fire System Criteria 10 Dec 18.pdf PDF
Attachment 4 PPQ and Cover Letter 17 Dec 2020.pdf PDF
Attachment 6 Luke Master Specifications 9 Sep2020.pdf PDF
Attachment 13 Renovation Project Sustainment and Restoration 23 Oct 20.pdf PDF
Pre- Proposal Conference.pptx PPTX presentation
Attachment 18 Sections L and M Instructions to Offerors and Evaluation Factors 9 Mar 2021.pdf PDF
Solicitation - FA488721R0014.pdf PDF
Attachment 19 Price Evaluation Worksheet 8 Mar 2021.xlsx XLSX spreadsheet
Attachment 10 AETC First 400 Feet Standard Guidance with Luke Supplemental 5 May15 v4.pdf PDF
Attachment 7 AFI 33-118 Electromagnetic Spectrum Management.pdf PDF
Attachment 15 NAF Standard Clauses.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 14 – FA488721R0014 Basic Project Design Requirements

23 October 2020

“Basic Project Design Requirements”

Ron Martin, Asst Fire Chief

Chief, Fire Prevention...x7421

Technical Codes/Reference:

• AFI’s, IBC, IFC, NFPA & UFC Std’s…

• Luke Specification for Fire Protection & Life Safety…

• Luke AFB Master Specification…

Required per code:

• Install Fire Sprinkler System …> 5000sf w/exceptions per AHJ… UFC 3-600-01…

• Replace existing Fire Alarm Control Panel (FACP)… UFC 3-600-01…

• Install Mass Notification System (MNS) per UFC 4-021-01…

• Install Annunciator Panel; required at front entrance... per AHJ...

• Need exterior FA/MNS Speakers @ entrance/exits; allowing hearing within a distance of 16 feet of doorways... UFC 4-021-01

• Install Lexan covers on all manual pull stations for dual action effect to prevent malicious false alarms/provide protection from physical damage... IBC 907.4.2.5…

• S/D needs to be above/within 4' of control panels... (i.e.: FACP, notification appliance circuit power extenders, and supervising station-transmitting equipment...)

• Install fire exit hardware on all exit doors...per AHJ…

• Ensure Smoke/Heat detectors are at least 3' from air source... not just air supply…

• Knox Box required at front/rear entrance... approved by AHJ…FPO has Cert…

• CO detectors are required in area of gas appliance... tied into the FACP & MNS messages...UFC 3-

600-01; 9-19…

• If AED's are installed; they must be connected to the FACP...

• Contact the FPO for list of recorded MNS standardized messages...