Attachment 11 Fire System Criteria 10 Dec 18.pdf

PDF 231 KB Posted

Attached to
Maintenance & Repair (M&R) IDIQ, Luke AFB, AZ
Solicitation number
FA488721R0014
Issued by

View the file

Other files

File Type Posted
FA488721R0014 Consolidated RFI Responses.xlsx XLSX spreadsheet
Attachment 8 Luke AFB Disc Submittal Guidelines.pdf PDF
Attachment 9 LUKE Design and Construction Standards.pdf PDF
Attachment 16 NAF Construction Clauses Definitions.pdf PDF
Attachment 2 Wage Determination AZ20210031 Maricopa County 26 Feb 2021.pdf PDF
Attachment 5 Ordering Procedures 26 Feb 2021.pdf PDF
Attachment 17 Joint Venture Teaming Partner Consent Letter 17 Dec 20.pdf PDF
Attachment 1 M and R SOW 5 Mar 2021.pdf PDF
Attachment 12 Luke Specification for Fire Protection and Life Safety 6 Jun 15.pdf PDF
Attachment 3 Wage Determination AZ20210030 Coconio County 26 Feb 2021.pdf PDF
Attachment 14 Basic Project Design Requirements 23 Oct 20.pdf PDF
Attachment 4 PPQ and Cover Letter 17 Dec 2020.pdf PDF
Attachment 6 Luke Master Specifications 9 Sep2020.pdf PDF
Attachment 13 Renovation Project Sustainment and Restoration 23 Oct 20.pdf PDF
Pre- Proposal Conference.pptx PPTX presentation
Attachment 18 Sections L and M Instructions to Offerors and Evaluation Factors 9 Mar 2021.pdf PDF
Solicitation - FA488721R0014.pdf PDF
Attachment 19 Price Evaluation Worksheet 8 Mar 2021.xlsx XLSX spreadsheet
Attachment 10 AETC First 400 Feet Standard Guidance with Luke Supplemental 5 May15 v4.pdf PDF
Attachment 7 AFI 33-118 Electromagnetic Spectrum Management.pdf PDF
Attachment 15 NAF Standard Clauses.pdf PDF
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachment 11 – FA488721R0014 Luke Air Force Base

Fire Alarm/Mass Notification System Installation rwm-12/10/2018

Luke Air Force Base Fire Alarm/Mass Notification System Installations

Basic Standard Installation Criteria:

• Standardize Fire Alarms Systems in all base facilities.

• Fire Alarm System/MNS must be compatible with Monaco BTX-21, BTX-M

• Factory train Alarm Maintenance personal on base standard/selected Fire Alarm System.

• Establish bench stock for base standard/selected Fire Alarm System.

• System design must meet AFI’s, ETL’s, UFC 3-600-01, UFC 4-021-01 (Design/O&M for Mass

Notification Systems), NFPA 70/72 and IBC 2009.

• The Fire Alarm Design/MNS is engineered by qualified FPE or NICET level IV personnel.

• Factory trained personnel to perform system installation, testing, training, and maintenance.

• Mass Notification System (MNS) will provide a Common Intelligibility Scale (CIS) for indoor sound at 0.08 CIS minimum value. An intelligibility voice signal being broadcast will be determined at a distance of no more than 33 ft within the same area.

• Fire Alarm initiation will have pull stations (w/ Lexan covers) at all primary exits; monitor all flow switches; smoke/heat detectors (if installed); duct smoke detectors, flame (UVIR) detectors, and monitoring modules. Install smoke detector within 4’ above Fire Alarm Panel.

• Fire Alarm Indication will be by the MNS speaker system (voice) and clear strobes.

• The MNS sound system will override any fire signals and provide indication of ALERT through amber strobes.

• Voice messages can be obtained by the FPO will be per UFC Air Force requirements and have Local Operators Panel(s) with microphone located within a distance determined by the FPO/AHJ, but no further than 200’.

• The MNS sound system w/ BTX-M will have (LVN) Live Voice Notification from Fire Department (ECC) Emergency Communication Center or Base Command Post.

• Monaco Transmitting Zones:

Will include; pull stations, smoke/heat detectors, CO detectors, duct detectors, water flow, tampers switches, AEDs, Emergency infrastructure such as (generators, fuel levels, etc.), flame (UVIR) detectors, remote emergency panic buttons;

• Contact Fire Dept ECC for proper zoning…

• Size of the FACP panel will incorporate the amplifiers and will be mid-size in height, (may require more panels of same height).

• Annunciator panel will be installed in facilities with complex configurations per FPO/AHJ.

• FPO/AHJ will have final acceptance of Fire Alarm System Installation

Ronald W. Martin Chief, Fire Prevention 623/856-7421