This solicitation is for the design and construction of a replace boilers project at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The project involves replacing four antiquated water tube boilers and associated piping and support systems with three new energy efficient fire tube boilers. Additional work includes replacing auxiliary systems in Building 39, fuel oil pump sets, condensate piping, deaerator and condensate return tanks, adding a continuous blowdown heat recovery package, and asbestos abatement of replaced piping. The Department of Veterans Affairs, through its Veterans Health Administration Program Contracting Activity Central office, is seeking bids for a firm-fixed-price contract to complete the project according to provided contract drawings and specifications.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVER T-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
ELECTRONIC SAFETY AND SECURITY SYMBOLS
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
M
T
M
T
T
M
M
M
T
T
M
T
M
T
M
T
M
M
T
M
T
M
T
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH CLOSED CIRCUIT TELEVISION
CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, MULTI-SENSOR/PANORAMIC VIEW, ANGLE OF VIEW
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
360°
40°
X
M PTZ
M
T
AP
SECURITY ACCESS, DOOR PROP/EXIT ALARMDA
SECURITY ACCESS, INTERFACE RELAY SWITCH
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR
ARMORED CABLE
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BFF BELOW FINISH FLOOR
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
C CONDUIT
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONT CONTINUE
CONTR CONTRACTOR
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DRSW DOOR SWITCH
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EXIST EXISTING
FLEX FLEXIBLE METALLIC CONDUIT
FT FEET OR FOOT
ELECTRONIC SAFETY AND SECURITY ABBREVIATIONS
GND GROUND
GEN GENERATOR
GTB GROUND TERMINAL BOX
HOA HAND-OFF-AUTOMATIC
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
LF LINEAR FEET (FOOT)
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MT MOUNT
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
N NEUTRAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
REQD REQUIRED
SF SQUARE FOOT (FEET)
SI INTERNATIONAL SYSTEM OF UNITS
SSTV SECURITY SURVEILLANCE TELEVISION
SW SWITCH
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
WP WEATHERPROOF
A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.
B. THE MINIMUM STANDARD FOR ALL WORK SHALL BE THE APPLICABLE CODES REFERENCED ON THE LIFE SAFETY PLANS ON SHEET AE002 INCLUDING THE NATIONAL
ELECTRICAL CODE. WHENEVER THE ENGINEERS DESIGN REQUIRES A HIGHER STANDARD, THE HIGHER STANDARD DESIGN SHOWN SHALL BE FOLLOWED.
C. ALL WORK SHALL BE PERFORMED BY AN ELECTRICIAN LICENSED BY THE STATE OF KANSAS. AT COMPLETION OF THE PROJECT, A CERTIFICATE OF COMPLIANCE
SHALL BE FURNISHED BY THE ELECTRICAL INSPECTION AGENCY HAVING JURISDICTION OVER ELECTRICAL WORK PERFORMED.
D. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, AND TOOLS TO EXECUTE WORK DETAILED BY THE DRAWINGS AND PROJECT SPECIFICATIONS, AND SHALL PROVIDE A COMPLETELY OPERATIONAL VIDEO SURVEILLANCE/ELECTRICAL SYSTEM UPON COMPLETION OF THE PROJECT.
E. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE ELECTRICAL WORK WITH THAT OF OTHER TRADES. THE ELECTRICIAN IS RESPONSIBLE FOR MAKING ALL
ELECTRICAL CONNECTIONS TO THE EQUIPMENT REQUIRING ELECTRICAL POWER, REGARDLESS OF WHO FURNISHED OR INSTALLED IT.
F. THE CONTRACTOR IS RESPONSIBLE FOR DAILY CLEANUP OF ALL WORK AREAS DURING TERM PROJECT; AND FOR RETURNING TO ORIGINAL CONDITION UPON
COMPLETION OF ALL WORK INDICATED.
G. ALL ELECTRICAL WORK SHALL BE WARRANTED FOR ONE YEAR FROM THE DATE OF INSPECTION PUNCHLIST COMPLETION.
H. ALL MATERIALS USED SHALL BE NEW AND UL LISTED WHERE A LISTING EXISTS FOR THE PRODUCT.
I. ALL WIRING SHALL BE COPPER. ALUMINUM WIRING SHALL NOT BE ALLOWED. MINIMUM WIRE SIZE SHALL BE #12 AWG, CONDUCTORS SHALL BE THWN IN SMALLER
SIZES OR MAY BE THW IN LARGER SIZES IF ECONOMICAL, AND SHALL BE RATED 600 VOLTS. RUNS OF 120 VOLTS OVER 50 FEET SHALL UTILIZE #10 AWG TO
PREVENT EXCESSIVE VOLTAGE DROP. CONDUCTORS SHALL BE COLOR CODED AS REQUIRED BY THE NEC.
J. WIRING DEVICES SHALL BE SPEC GRADE, RATED 20 AMPERES. DEVICE PLATES SHALL BE SMOOTH FINISH IVORY NYLON.
K. CONDUIT CONCEALED IN WALLS OR CEILINGS SHALL BE EMT WITH TAMPER PROOF SCREWS, AND EXPOSED CONDUITS SHALL BE EMT WITH TAMPER PROOF SCREWS.
ALL CONDUITS SHALL HAVE AN EXTRA CONDUCTOR PULLED FOR GROUNDING. ALL CONDUIT SHALL BE CONCEALED, UNLESS SPECIFICALLY NOTED OTHERWISE. ALL
CONDUIT FITTINGS SHALL BE COMPRESSION TYPE. THE LAST PIECE OF CONDUIT INSTALLED TO EQUIPMENT SHALL BE FLEXIBLE METAL CONDUIT. MINIMUM CONDUIT
SIZE SHALL BE 3/4 INCH. CONDUITS SHALL BE INSTALLED AT RIGHT ANGLES TO CEILINGS, WALLS, AND STRUCTURAL MEMBERS. CONDUIT SHALL BE SUPPORTED BY
PIPE STRAPS, WALL BRACKETS, OR HANGERS. SPACER BACK CLAMPS SHALL BE UTILIZED IN MOIST OR WET AREAS.
L. HUBS SHALL BE USED ON BOXES WHERE CONDUIT ENTERS THE TOP AND IS EXPOSED TO WEATHER. SEALING LOCKNUTS MAY BE USED FOR SIDE ENTRY CONDUITS
IN THIS APPLICATION.
M. CONDUITS SHALL BE SEALED WHERE THEY ENTER THE BUILDING TO PREVENT GROUNDWATER ENTRY.
N. BOXES SHALL BE INSTALLED SUCH THAT THEY ARE SUPPORTED BY THE STRUCTURE. BOXES MAY NOT BE SUPPORTED BY CONDUIT.
O. IN THE ABSENCE OF DETAILS HEREIN ON USE OR INSTALLATION OF A PARTICULAR MATERIAL OR DEVICE, CODES AND MANUFACTURERS RECOMMENDATIONS SHALL BE
USED AS GUIDANCE.
P. IT IS HIGHLY RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE PRIOR TO BIDDING, TO BECOME FAMILIAR WITH EXISTING CONDITIONS TO BE ENCOUNTERED
DURING CONSTRUCTION.
Q. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. COORDINATE WORK ACCORDINGLY. COMPLY WITH
SPECIFICATIONS AND GENERAL NOTES AS APPLICABLE.
R. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS.
S. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRESTOPPING/SEALANT MATERIAL TO MAINTAIN THE
EXISTING FIRE RATING FOR THE ASSEMBLY.
T. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED WITH ALL FEEDER AND BRANCH CIRCUITS. SIZE IN ACCORDANCE WITH NFPA 70 ARTICLE 250.
U. COORDINATE INSTALLATION AND FINAL LOCATION OF DATA OUTLETS WITH THE VA.
V. IDENTIFICATION:
RECEPTACLES CONNECTED TO THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE RED WITH A WHITE LABEL CONTAINING THE WORD "EMERGENCY" IN BLACK ON THE TOP
OF THE PLATE AND A WHITE LABEL WITH THE CIRCUIT NUMBER IN BLACK ON THE BOTTOM. "NORMAL" RECEPTACLES SHALL HAVE A WHITE LABEL WITH THE CIRCUIT
NUMBER IN BLACK AT THE BOTTOM OF THE PLATE.
W. PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND TERMINATION POINTS. LABELS SHALL BE SELF ADHESIVE OR
HEAT SHRINK TYPE AND BE PERMANENTLY AFFIXED TO THE WIRE BEING LABELED.
X. NO LIVE WORK WILL BE ALLOWED. EVERY CIRCUIT SHALL BE LOCKED-OUT AND TAGGED-OUT BEFORE COMMENCING WORK.
Y. NO "J" HOOKS. (OR ANY OTHER TYPE OF WIRE "HANGING" SYSTEM IS PERMITTED WITHIN THE SCOPE OF THIS WORK FOR THE ENTIRE LENGTH OF WIRING RUNS
INDICATED.) REFER TO GENERAL NOTE "K".
Z. NEW CONDUIT RUNS SHOWN BY PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL INSTALL NEW CONDUITS IN CONCEALED LOCATIONS UNLESS SPECIFICALLY
NOTED OTHERWISE.
AA. MOST CONDUITS TO BE INSTALLED ABOVE EXISTING SUSPENDED ACOUSTICAL TILE (SAT) CEILINGS IN A MANNER THAT MINIMIZES DAMAGE TO EXISTING SAT CEILINGS.
(REFER TO GENERAL NOTES SHEET E-002.)
AB. TOTAL CONDUIT LENGTHS MAY NOT EXCEED 295'-0" FROM CAMERA LOCATION TO I.T. ROOM CONNECTION POINT.
AC. NEW CONDUITS SHALL BE SECURED TO EXISTING WALL CONSTRUCTION, EXISTING STRUCTURAL SYSTEM OR EXISTING PLASTER FINISHES CONCEALED FROM VIEW (ABOVE
SAT).
AD. CONTRACTOR SHALL TAKE MEASURES NECESSARY TO AVOID CONFLICTS WITH EXISTING MECHANICAL, ELECTRICAL AND PLUMBING (MEP) INFRASTRUCTURE AT NO
ADDITIONAL COST TO VAMC.
AE. VA INFORMATION TECHNOLOGY/SYSTEMS PERSONNEL WILL USE THE CONTRACTOR'S COMPLETED, LABELED AND INDEX LISTED CABLING TO PHYSICALLY MAKE THE FINAL
CONNECTION TO VAMC OWNED SWITCHES INSIDE OF IT ROOMS.
AF. INTRUSION DETECTION SYSTEMS (IDS), DURESS/PANIC SYSTEMS, PHYSICAL ACCESS CONTROL SYSTEMS (PACS), AND SECURITY SURVEILLANCE TELEVISION (SSTV)
DESIGN TO FOLLOW VA PSRDM - CHAPTER 10, VA TDM 2016, AND NEC.
ELECTRONIC SAFETY AND SECURITY GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t
/1
/2
:4
:3
P
M
T-001
SECURITY ELECTRONICS
SYMBOLS AND GENERAL NOTES
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
Revisions: Date:
2022-01-20
0.1 0.2 0.3 0.4 0.5 0.8 1
B
A.7
A.6
A.5
A.4
A
STORAGE
BATHROOM
OFFICE
OFFICE
OFFICE
OFFICE AREA
EXISTING
TUNNEL
TD
B
TD
B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
PLAN
NORTH
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:4
P
M
TD101A
SECURITY ELECTRONICS DEMOLITION
OFFICE AREA LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - OFFICE AREA LOWER FLOOR PLAN
SHEET KEYNOTES:
1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
1 3 4 5 6 7
A.7
A.6
A.5
A.4
A
21 2 3 4 5 6 7
A
B
CONTROL ROOM
EXISTING BOILER
ROOM
EXISTING SHOP
AREA
EXISTING
STORAGE
100A
TD
A
TD
A
TD
C
TD
C
1 1 2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:4
P
M
TD101B
SECURITY ELECTRONICS DEMOLITION
BOILER ROOM WEST LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - BOILER ROOM WEST LOWER FLOOR PLAN
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
SHEET KEYNOTES:
1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.
2 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL PANEL AND ASSOCIATED CONDUIT/CABLING.
7 8 9
A.7
A.6
A.5
A.4
A
97 8
A
B
TD
B
TD
B
EXISTING SHOP
AREA
3SECURITY ROOM
PUMP PIT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:4
P
M
TD101C
SECURITY ELECTRONICS DEMOLTION
BOILER ROOM EAST LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - BOILER ROOM EAST LOWER FLOOR PLAN
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
SHEET KEYNOTES:
1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.
2 EXISTING PHYSICAL ACCESS CONTROL PANEL TO REMAIN. PANEL SERVES THE
ADJACENT SECURITY ELECTRONICS EQUIPMENT RACK.
3 EXISTING SECURITY ELECTRONICS EQUIPMENT RACK TO REMAIN.
A
B
0.1
C
TD
B
TD
B
STORAGE
CONFERENCE
ROOM
CORRIDOR
OFFICE
OFFICE
STORAGE
ELECTRIC SHOP
TOILETS
ELECTRICAL
ROOM
OFFICE
EXISTING
MEZZANINE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:4
P
M
TD102A
SECURITY ELECTRONICS DEMOLITION
OFFICE AREA UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - OFFICE AREA UPPER FLOOR PLAN
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
SHEET KEYNOTES:
1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.
1 3 4 5 6 7
C
B
A.7
A.6
A.5
A.4
A
1 2 3 4 5 6 7
A
B
C
EXISTING
STORAGE
100A
EXISTING
INCINERATOR
TD
A
TD
A
TD
C
TD
C
EXISTING BOILER
ROOM
EXISTING
STACK
EXISTING SHOP
AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:4
P
M
TD102B
SECURITY ELECTRONICS DEMOLITION
BOILER ROOM WEST UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - BOILER ROOM WEST UPPER FLOOR PLAN
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
SHEET KEYNOTES:
1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL
ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.
A.7
A.6
A.5
A.4
A
97 8
A
B
TD
B
TD
B
EXISTING SHOP
AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:5
P
M
TD102C
SECURITY ELECTRONICS DEMOLITION
BOILER ROOM EAST UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS DEMOLITION - BOILER ROOM EAST UPPER FLOOR PLAN
GENERAL NOTES:
1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS
EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE
WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF
ALL RELATED ELECTRICAL EQUIPMENT.
2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED
CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS
TO MAINTAIN THE EXISTING FIRE RATING.
3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND
EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY
ELECTRONICS WORK.
4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF
ANY WORK.
SHEET KEYNOTES:
8' ROLL-UP DOOR
AIR DUCTING
C O N C R
ETE
SID
EW
ALK
8' ROLL-UP DOOR
' R
O
LL
-U P
D O
O R
∅1 3'-
4"
7'-9"
BUILDING 37
BUILDING 39
ELECTRICAL SHOP
BUILDING 39
BOILER PLANT
BUILDING 39A
STACK
BUILDING 129
BUILDING 28
BUILDING 81
TE
M P O R A R Y
E
LE
C
TR
IC
A L
E Q U
IP
M E N T
(S E E
E
LE
C
TR
IC
A L
D R A W
IN
G S
TE
M P O R A R Y
C O N
TR
O L
R O O M
O
FF
IC
E
TR
A
IL
E R
TEMPORARY 1000 HP STEAM
GENERATION TRAILER NO. 1
TEMPORARY 1000 HP STEAM
GENERATION TRAILER NO. 2
180°
1 2
4 5 6
DIESEL FUEL
TANK
GP1
PEDESTRIAN GATE
24VDC
POWER
SUPPLY
JUNCTION
BOX ON
SECURE SIDE
OF FENCE
MAGNETIC LOCK
BMS W/ DOOR PROP ALARM
REX PUSHBUTTON
CARD READER W/ PIN PAD
24VDC
3-2C/#18 NON-
SHIELDED CABLE,
1-4C/#20 CABLE (1-PR
SHIELDED), 1"C
EXISTING ACCESS
CONTROL PANEL
2 READER
2C/#18 NON-SHIELDED CABLE
2-2C/#18 NON-SHIELDED CABLE
4C/#20 CABLE (1-PR SHIELDED)
SHEET KEYNOTES:
1. CONNECT TO THE 20A/120V CIRCUIT SERVING THE EXISTING PHYSICAL
ACCESS CONTROL PANEL.
120VAC
6C/#18 SHIELDED
PLENUM CABLE, 1"C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
/1
/2
:4
:5
P
M
TY010
SECURITY ELECTRONICS
SITE PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/16" = 1'-0"
SECURITY ELECTRONICS - SITE PLAN
SHEET KEYNOTES:
1 TEMPORARY GATE WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO
POWER SUPPLY AND EXISTING PHYSICAL ACCESS CONTROL PANEL (SHEET TY101C).
REFER TO DETAIL 2 ON SHEET T-502.
2 CARD READER PEDESTAL. REFER TO PEDESTAL DETAILS ON SHEET T-502.
3 REX PUSHBUTTON PEDESTAL. MOUNT SIMILAR TO PEDESTAL DETAILS ON SHEET
T-502.
4 POLE MOUNTED CAMERA WITH SURVEILLANCE CABINET. REFER TO DETAILS ON
SHEET T-503 FOR ADDITIONAL INFORMATION.
5 PROVIDE 4-STRAND 9/125 MICRON SINGLEMODE FIBER OPTIC CABLE, 1"C FROM
SURVEILLANCE CABINET BACK TO SECURITY ELECTRONICS EQUIPMENT RACK (SHEET
TY101A).
6 120V CIRCUIT REQUIRED TO SURVEILLANCE CABINET. REFER TO ELECTRICAL
DRAWINGS FOR CIRCUIT INFORMATION.
GENERAL NOTES:
1 ALL SECURITY ELECTRONICS CABLING SHALL BE INSTALLED IN CONDUIT.
2 WHERE POSSIBLE, UTILIZE THE TEMPORARY PIPE SUPPORTS FROM THE TEMPORARY
BOILER PLANT TRAILERS TO EXISTING BUILDING 39 (REFER TO C102 FOR PIPE
SUPPORT LOCATIONS). OTHERWISE, CONDUIT SHALL BE INSTALLED UNDERGROUND.
3 LOCATE ALL EXISTING UNDERGROUND UTILITIES FOR ALL UNDERGROUND WORK PRIOR
TO EXCAVATION OR TRENCHING. HAND DIG WITHIN 10' OF AN UTILITY CROSSING
WITH NEW WORK.
4 MINIMUM BURY FOR ALL SITE CONDUITS SHALL BE 30", UNLESS OTHEWISE NOTED.
CONTRACTOR IS RESPONSIBLE FOR ALL SITE TRENCHING AND BACKFILL.
5 REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION.
6 REFER TO TEMPORARY PHYSICAL ACCESS CONTROL SYSTEM RISER DIAGRAM, THIS
SHEET.
7 REFER TO SHEETS T-502 PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
8 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM.
9 REFER TO SHEET T-503 FOR CAMERA MOUNTING DETAILS.
10 EQUIPMENT/DEVICES SHOWN ON THIS SHEET SHALL BE COORDINATED WITH GATE
LOCATION AND GENERAL CONTRACTOR PRIOR TO ROUGH-IN.
11 AFTER USE OF THE TEMPORARY CONTROL BUILDING AND BOILERS, CONTRACTOR
SHALL REMOVE ASSOCIATED SECURITY ELECTRONICS DEVICES/EQUIPMENT AND TURN
OVER TO OWNER.
NOT TO SCALE
PHYSICAL ACCESS CONTROL SYSTEM RISER DIAGRAM - TEMPORARY GATE
M
M
M
0.1 0.2 0.3 0.4 0.5 0.8 1
B
A.7
A.6
A.5
A.4
A
TY
B
HAC
ELECTRICAL
111 SECURITY
CIRCULATION
OFFICE
RESTROOM
STAIR
TOILET
ACCESSIBLE
TOILET
SHOWER
LOCKERS
TY
B
102A
CONTROL ROOM
FF
S
S
S
X
S
X
SS
M
X
F F
SX
F
XS X
FFF
F X
S
X
F
F
F
UTILITY
VESTIBULE
B1121
CONTROLS
DA
DA
DA
DA
C1141
C1041
EXISTING
TUNNEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:5
P
M
TY101A
SECURITY ELECTRONICS
OFFICE AREA LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR ACCESS CONTROL SYSTEM RISER
DIAGRAMS.
2 REFER TO SHEET T-501 FOR ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED ACCESS CONTROL
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - OFFICE AREA LOWER FLOOR PLAN
SHEET KEYNOTES:
1 SECURITY ELECTRONICS EQUIPMENT RACK. REFER TO DETAIL 3 ON SHEET T-602
AND VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM ON SHEET T-605 FOR
ADDITIONAL INFORMATION.
2 EXISTING SECURITY ELECTRONICS EQUIPMENT RACK TO REMAIN.
3 PROVIDE 1"C WITH 12-STRAND MULTIMODE (OM1) OPTICAL FIBER CABLE FROM
FIBER TERMINATION PANEL (EXISTING SECURITY ELECTRONICS EQUIPMENT RACK) TO
FIBER TERMINATION PANEL (NEW SECURITY ELECTRONICS EQUIPMENT RACK).
4 3/4" PLYWOOD TREATED WITH FLAME RETARDANT PAINT - SEE SPECIFICATIONS FOR
FURTHER DETAILS. TYPICAL ON ALL WALLS.
5 TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). REFER TO DETAIL 7, SHEET
E-503 FOR BONDING TO EQUIPMENT WITHIN ROOM.
6 INTRUSION DETECTION SYSTEM CONTROL PANEL. REFER TO SPECIFICATION SECTION
281600.
7 CAT 6A CABLE, 1"C FROM INTRUSION DETECTION CONTROL PANEL TO A DEDICATED
PHYSICAL ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL IN THE
SECURITY ELECTRONICS EQUIPMENT RACK.
8 WALL-MOUNTED EQUIPMENT RACK TO HOUSE INTERCOM SYSTEM HEADEND
EQUIPMENT. REFER TO DETAIL 2, SHEET T-604 FOR ADDITIONAL INFORMATION..
9 CAT 6A UTP, 1"C FROM INTERCOM SYSTEM EQUIPMENT TO DEDICATED PHYSICAL
ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL IN THE SECURITY
ELECTRONICS EQUIPMENT RACK.
10 PHYSICAL ACCESS CONTROL PANEL. REFER TO PACS RISER DIAGRAMS ON SHEET
T-601 THROUGH T-603. REFER TO SPECIFICATION SECTION 281300.
11 DOOR POWER SUPPLIES - QUANTITY AS REQUIRED. REFER TO PACS RISER DIAGRAMS
ON SHEET T-601 THROUGH T-603. REFER TO SPECIFICATION SECTION 281300.
12 SINGLE DOOR WITH ELECTRIC STRIKE. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 1 ON SHEET T-501.
13 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 2 ON SHEET T-501.
14 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.
15 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
16 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"
BELOW CEILING, WHICHEVER IS LOWER.
17 WALL MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AS HIGH AS POSSIBLE,
COORDINATE MOUNTING HEIGHT WITH OTHER TRADES.
18 PROVIDE CONNECTION FROM FIRE ALARM CONTROL MODULE TO PHYSICAL ACCESS
CONTROL SYSTEM. CONTROLLED DOORS SHALL ALLOW FREE EXIST UPON ACTIVATON
OF THE FIRE ALARM SYSTEM AS REQUIRED BY NFPA 72. COORDINATE WITH FIRE
ALARM SYSTEM CONTRACTOR.
19 CEILING MOUNTED CAMERA WITH MOTION DETECTION. REFER TO DETAIL 4, SHEET
T-503.
20 PROVIDE CAT 6A CABLE FROM EACH PHYSICAL ACCESS CONTROL PANEL TO A
DEDICATED PHYSICAL ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL
IN THE SECURITY ELECTRONICS EQUIPMENT RACK.
360°
90°
360°
360°
1 3 4 5 6 7
B
A.7
A.6
A.5
A.4
A
21 2 3 4 5 6 7
A
B
TY
A
100c 100b100d
100D
100a
EXISTING
STORAGE
100A
101B
TY
C
TY
C
3 3 3
F
X S X
F F F
F
X M X
F F F F
M M
S S S F F F F FF
M M M M M M S
F
4 4 4
5S
F
C1011 A1002 A1003
CONTROL ROOM
BOILER ROOM
DA
DA DA DA DA
12 12
DA
E1001
D1002
D1003
A1001
17 17
TY
A
D1001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:5
P
M
TY101B
SECURITY ELECTRONICS
BOILER ROOM WEST LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - BOILER ROOM WEST LOWER FLOOR PLAN
SHEET KEYNOTES:
1 SINGLE DOOR WITH ELECTRIC STRIKE. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 1 ON SHEET T-501.
2 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 2 ON SHEET T-501.
3 OVERHEAD DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 5 ON SHEET T-501.
4 OVERHEAD DOOR CONTROLLER. COORDINATE LOCATION WITH OVERHEAD DOOR
INSTALLER.
5 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
6 IP VIDEO MASTER STATION - DESK MOUNTED.
7 REMOTE VASS/SSTV WORKSTATION.
8 43" LED VIDEO SURVEILLANCE MONITOR. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH OWNER.
9 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"
BELOW CEILING, WHICHEVER IS LOWER.
10 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.
11 CEILING MOUNTED CAMERA. REFER TO DETAIL 4, SHEET T-503.
12 BOILER CONTROL PANEL.
13 PROVIDE CONNETION (BOILER FAULT COMMON ALARM) FROM BOILER MASTER
CONTROL PANEL TO INTRUSION DETECTION CONTROL PANEL.
14 WALL MOUNTED CAMERA 180-DEGREE PANORAMIC CAMERA (REFER TO DETAIL 3,
SHEET T-503). MOUNT AT 10'-0" AFF, HOWEVER, FIELD COORDINATE EXACT
MOUNTING FOR OPTIMAL COVERAGE. .
15 WALL MOUNTED CAMERA (REFER TO DETAIL 3, SHEET T-503). MOUNT AT
12'-0"AFF AND PROVIDE COVERAGE OF BOILER PANEL.
16 WALL MOUNTED CAMERA (REFER TO DETAIL 3, SHEET T-503). MOUNT AT
10'-0"AFF AND PROVIDE COVERAGE OF BOILER PANEL.
17 PENDANT MOUNTED 360-DEGREE FISHEYE PANORAMIC CAMERA (REFER TO DETAIL 5,
SHEET T-503). MOUNT AT 12'-0" AFF; HOWEVER, FIELD COORDINATE EXACT
MOUNTING FOR OPTIMAL COVERAGE.
18 SURFACE MOUNTED 360-DEG PANORAMIC CAMERA. MOUNT TO BOTTOM OF
CATWALK. PROVIDE COVERAGE OF NORTHWEST AREA OF BOILER PLANT AND
EXISTING STEAM TUNNEL.
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM
RISER DIAGRAMS.
2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION
DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN
SECURITY 112 (SHEET TY101A).
360°
B
A.7
A.6
A.5
A.4
A
97 8
A
B
TY
B
TY
B
BOILER PLANT
PUMP PIT
SECURITY ROOM
DA
S
S
X S
M
SX
S
100C
F1001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BOILER
RM EAST
BOILER
RM WEST
STORAGE
OFFICE AREA
/1
/2
:4
:5
P
M
TY101C
SECURITY ELECTRONICS
BOILER ROOM EAST LOWER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - BOILER ROOM EAST LOWER FLOOR PLAN
SHEET KEYNOTES:
1 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"
BELOW CEILING, WHICHEVER IS LOWER.
2 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
3 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 2 ON SHEET T-501.
4 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.
5 PENDANT MOUNTED 360-DEGREE PANORAMIC CAMERA (REFER TO DETAIL 5, SHEET
T-503). MOUNT AT 14'-6" AFF; HOWEVER, FIELD COORDINATE EXACT MOUNTING
FOR OPTIMAL COVERAGE.
6 UTILIZE THE EXISTING PHYSICAL ACCESS CONTROL PANEL TO PROVIDE CONTROL OF
THE TEMPORARY GATE (SHEET TY010). PROGRAM THE EXISTING CONTROL PANEL AS
REQUIRED TO INCORPORATE THE ADDED INPUT/OUTPUTS. REFER TO PHYSICAL
ACCESS CONTROL SYSTEM RISER DIAGRAM - TEMPORARY GATE (SHEET TY010).
7 POWER SUPPLY FOR MAGNETIC LOCK FOR TEMPORARY GATE (TY010). CONNECT TO
THE 20A/120V CIRCUIT SERVING THE EXISTING PHYSICAL ACCESS CONTROL PANEL.
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM
RISER DIAGRAMS.
2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION
DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN
SECURITY 112 (SHEET TY101A).
REF.
M
0.1 0.2 0.3 0.4 0.5 0.8 1
C
B
A.7
A.6
A.5
A.4
A
A
B
0.1
C
STAIR
BREAK ROOM
TRAINING ROOM
CONFERENCE
ROOM
CORRIDOR
OFFICE
OFFICE
STORAGE
STORAGE
ELECTRIC SHOP
TOILETS
ELECTRICAL
ROOM
OFFICE
TY
B
208F
XMX
FFF
S X
X
M
S
S
S
S
X M X
S SS
TY
B
S
S
S S
DA
DA
DA
DA
X
S
S
S
M X
S
C2041
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:0
P
M
TY102A
SECURITY ELECTRONICS
OFFICE AREA UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - OFFICE AREA UPPER FLOOR PLAN
SHEET KEYNOTES:
1 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 2 ON SHEET T-501.
2 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
3 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"
BELOW CEILING, WHICHEVER IS LOWER.
4 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.
5 CEILING MOUNTED CAMERA. REFER TO DETAIL 4, SHEET T-503.
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM
RISER DIAGRAMS.
2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION
DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN
SECURITY 112 (SHEET TY101A).
M
MM
M
1 3 4 5 6 7
C
B
A.7
A.6
A.5
A.4
A
1 2 3 4 5 6 7
A
B
C
TY
A
TY
A
BOILER ROOM
EXISTING
STORAGE
100A
TRANSFORMER
ROOM
GENERATOR
ROOM
TY
C
TY
C
201A
203A
202B
202A
SX
M
X
S
S
S
S
X M X
S S S
S
M
X
M
XS
S
S
S
S
S
S
B2031
LINK
6 6
EXISTING
STACK
203B
DA
DA
DA
DA
DA
X F
M F
FX
S
B2011
DA
7 S
X S
M S
SM
X S
S
S
DAD
B2021
B100A1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:0
P
M
TY102B
SECURITY ELECTRONICS
BOILER ROOM WEST UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - BOILER ROOM WEST UPPER FLOOR PLAN
SHEET KEYNOTES:
1 DOUBLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION PANELS.
REFER TO DETAIL 3 ON SHEET T-501.
2 DOUBLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 4 ON SHEET T-501.
3 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER
SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION
PANELS. REFER TO DETAIL 2 ON SHEET T-501.
4 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.
5 WALL MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AS HIGH AS POSSIBLE,
COORDINATE MOUNTING HEIGHT WITH OTHER TRADES.
6 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"
BELOW CEILING, WHICHEVER IS LOWER.
7 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.
8 PROVIDE CONNECTION (GENERATOR FAULT COMMON ALARM) FROM GENERATOR
CONTROLLER TO INTRUSION DETECTION CONTROL PANEL.
9 OVERHEAD DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO
ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION PANELS.
REFER TO DETAIL 1 ON SHEET T-502.
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM
RISER DIAGRAMS.
2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION
DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN
SECURITY 112 (SHEET TY101A).
A.7
A.6
A.5
A.4
A
97 8
A
B
BOILER ROOM
TY
B
TY
B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR
ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND
SIGNATURE OF THE PROFESSIONAL ENGINEEER
MR PROJECT NO:
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t
ACTUAL
NORTH
KEYPLAN
BLDG
39A
BOILER
RM EAST
BOILER
RM WEST
STORAGEELECTRICAL
SHOP
OFFICE AREA
LINK
STACK
/1
/2
:4
:0
P
M
TY102C
SECURITY ELECTRONICS
BOILER ROOM EAST UPPER FLOOR PLAN
REPLACE BOILERS
IN BUILDING 39
DWIGHT D. EISENHOWER VA MEDICAL
CENTER - LEAVENWORTH, KS
589A6-19-204
2022-01-20 PJB PJB0509-006
BID DOCUMENTS
SCALE: 1/4" = 1'-0"
SECURITY ELECTRONICS - BOILER ROOM EAST UPPER FLOOR PLAN
SHEET KEYNOTES:
GENERAL NOTES:
1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM
RISER DIAGRAMS.
2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.
3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS
CONNECTIONS AND ROUGH-IN REQUIREMENTS.
4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.
5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.
6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.
7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.
8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION
DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN
SECURITY 112 (SHEET TY101A).
SUSPENDED CEILING
ELECTRIC
STRIKE
46"
DOORS: 101B, 102A, 111, 112
2C/#18 NON-SHIELDED, 3/4"C
BALANCED MAGNETIC SWITCH
(WITH 10-SECOND ANTI-PROP ALARM)
JUNCTION
BOX
SECURE
CONTACTLESS SMARTCARD
READER WITH KEYPAD
(UNSECURE SIDE OF DOOR)
2-2C/#18 NON-SHIELDED, 3/4"C
POWER
SUPPLY
120VAC
24VDC
CLASS II STEPDOWN
TRANSFORMER
6C/#18 SHIELDED
PLENUM CABLE, 3/4"C
POWER
SUPPLY
120VAC
12VDC
CLASS II STEPDOWN
TRANSFORMER
REQUEST TO EXIT (REX)
MOTION DETECTOR
4C/#20 CABLE
(1-PR SHIELDED), 3/4"C
ACCESS
CONTROL
PANEL
CAT 6A UTP, 1"C TO ETHERNET SWITCH AT
SECURITY ELECTRONICS EQUIPMENT RACK
3-2C/#18 NON-
SHIELDED CABLE
2-4C/#20 CABLE
(1-PR SHIELDED),
1-1/4"C
(WHERE PRESENT)
4C/#20 CABLE
(1-PR SHIELDED), 3/4"C
EMERGENCY REX
PUSHBUTTON
GENERAL NOTE:
1. NOTE SHOWN - PROVIDE ADDITIONAL
CONDUIT/WIRING TO INTRUSION DETECTION
PANEL FROM BALANCED MAGNETIC
SWITCH (DPDT).
DOOR PROP ALARM (SET @ 10 SEC)
DOORS: 100C, 100D, 104
31, 33, 34, 201A, 203A, 203B, 208
BALANCED MAGNETIC SWITCH
(WITH 10-SECOND ANTI-PROP ALARM)
JUNCTION
BOX
SECURE
2C/#18 NON-SHIELDED, 3/4"C
POWER
SUPPLY
120VAC
24VDC
CLASS II STEPDOWN
TRANSFORMER
POWER
SUPPLY
120VAC
12VDC
ACCESS
CONTROL
PANEL
CAT 6A UTP, 1"C TO ETHERNET SWITCH AT
SECURITY ELECTRONICS EQUIPMENT RACK
CLASS II STEPDOWN
TRANSFORMER
2-2C/#18 NON-SHIELDED,
3/4"C
MAGNETIC LOCK
SUSPENDED CEILING
(WHERE PRESENT)
46"
CONTACTLESS SMARTCARD
READER WITH KEYPAD
(UNSECURE SIDE OF DOOR)
EMERGENCY REX
PUSHBUTTON
6C/#18 SHIELDED
PLENUM CABLE, 3/4"C
4C/#20 CABLE
(1-PR SHIELDED), 3/4"C
3-2C/#18 NON-
SHIELDED CABLE
2-4C/#20 CABLE
(1-PR SHIELDED),
1-1/4"C
REQUEST TO EXIT (REX)
MOTION DETECTOR
4C/#20 CABLE
(1-PR SHIELDED), 3/4"C
GENERAL NOTE:
1. NOTE SHOWN - PROVIDE ADDITIONAL
CONDUIT/WIRING TO INTRUSION DETECTION
PANEL FROM BALANCED MAGNETIC
SWITCH (DPDT).
DOOR PROP ALARM (SET @ 10 SEC)
DOORS: 19, 202A
MAGNETIC LOCK
46"
CONTACTLESS SMARTCARD
READER WITH KEYPAD
(UNSECURE SIDE OF DOOR)
EMERGENCY REX
PUSHBUTTON
BALANCED MAGNETIC SWITCH
(WITH 10-SECOND ANTI-PROP ALARM)
JUNCTION
BOX
REQUEST TO EXIT (REX)
MOTION DETECTOR
POWER
SUPPLY
12VDC
ACCESS
CONTROL
PANEL
CAT 6A UTP, 1"C TO ETHERNET SWITCH AT
SECURITY ELECTRONICS EQUIPMENT RACK
CLASS II STEPDOWN
TRANSFORMER
120VAC
POWER
SUPPLY
120VAC
24VDC
CLASS II STEPDOWN
TRANSFORMER
SUSPENDED CEILING
(WHERE PRESENT)
4-2C/#18 NON-
SHIELDED CABLE
2-4C/#20 CABLE
(1-PR SHIELDED), 1-1/2"C
6C/#18 SHIELDED
PLENUM CABLE, 3/4"C
4C/#20 CABLE
(1-PR SHIELDED), 3/4"C
2C/#18 NON-SHIELDED CABLE, 3/4"C
2-2C/#18 NON-SHIELDED CABLE, 3/4"C
4C/#20 CABLE (1-PR SHIELDED), 3/4"C
SECURE
GENERAL NOTE:
1. NOTE SHOWN - PROVIDE ADDITIONAL
CONDUIT/WIRING TO INTRUSION DETECTION
PANEL FROM BALANCED MAGNETIC
SWITCH (DPDT).
DOOR PROP ALARM
(SET @ 10 SEC)
SUSPENDED CEILING
DOORS: 100a, 100b, 100c, 100d
SECURE
POWER
SUPPLY
120VAC
12VDC
CLASS II STEPDOWN
TRANSFORMER
ACCESS
CONTROL
PANEL
CAT 6A UTP, 1"C TO ETHERNET SWITCH AT
SECURITY ELECTRONICS EQUIPMENT RACK
(WHERE PRESENT)
FLOOR MOUNTED
MAGNETIC SWITCH
RECESSED
JUNCTION BOX
46"
CONTACTLESS SMARTCARD
READER WITH KEYPAD
(SECURE SIDE OF DOOR)
UP/DOWN/STOP
PUSHBUTTON
4#14, 1#14 GND, 3/4"C
2-2C/#18 NON-SHIELDED
CABLE, 3/4"C
COILING DOOR OPERATOR WITH
120-SECOND…