Attachment 12 - Security - Drawings.pdf

PDF 8 MB Posted

Attached to
36C77622B0029 - Replace Boilers - Leavenworth - Solicitation Federal contract opportunity
Solicitation number
36C77622B0029
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is for the design and construction of a replace boilers project at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The project involves replacing four antiquated water tube boilers and associated piping and support systems with three new energy efficient fire tube boilers. Additional work includes replacing auxiliary systems in Building 39, fuel oil pump sets, condensate piping, deaerator and condensate return tanks, adding a continuous blowdown heat recovery package, and asbestos abatement of replaced piping. The Department of Veterans Affairs, through its Veterans Health Administration Program Contracting Activity Central office, is seeking bids for a firm-fixed-price contract to complete the project according to provided contract drawings and specifications.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77622B0029 - Replace Boilers - Leavenworth - Solicitation, newest first.
File Type Posted
36C77622B0029 0003.pdf PDF
Attachment 26 - RFIs - Technical Questions and Responses - REVISED.pdf PDF
Attachment 21 - Asbestos Report.pdf PDF
Attachment 25 - Site Visit Attendance Sheet.pdf PDF
36C77622B0029 0002.pdf PDF
Attachment 22 - DDC for HVAC.pdf PDF
Attachment 23 - S-532 Drawing Sheet.pdf PDF
Attachment 24 - RFIs - Technical Questions and Responses.pdf PDF
36C77622B0029 0001.pdf PDF
Attachment 03 - Civil - Drawings.pdf PDF
Attachment 04 - Structural - Drawings.pdf PDF
Attachment 05 - Architectural - Drawings.pdf PDF
Attachment 10 - Electrical - Part 1 - Drawings.pdf PDF
36C77622B0029_1.pdf PDF
Attachment 06 - Fire Protection - Drawings.pdf PDF
Attachment 08 - Mechanical - Part 1 - Drawings.pdf PDF
Attachment 09 - Mechanical - Part 2 - Drawings.pdf PDF
Attachment 02 - Hazardous Materials - Drawings.pdf PDF
Attachment 07 - Plumbing - Drawings.pdf PDF
Attachment 13 - Specifications - Volume 1.pdf PDF
Attachment 14 - Specifications - Volume 2.pdf PDF
Attachment 17 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 01 - General Information - Drawings.pdf PDF
Attachment 11 - Electrical - Part 2 - Drawings.pdf PDF
Attachment 15 - Specifications - Volume 3.pdf PDF
Attachment 16 - Boiler Plant - Drawing Sheet - M001.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 19 - Wage Rates - Leavenworth KS 5-21-2022.pdf PDF
Attachment 20 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS

R-EYE RETINA V-VOICE

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL

M-MAG STRIP P-PROXIMITY S-SMART CARD

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CENTRAL PROCESSING UNIT

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE

EXIT DEVICE; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYPE

D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY

FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

R-RECEIVER T-TRANSCEIVER TX-TRANSMITTER

FIELD PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-ALARM C-CARD READER

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

KEYBOARD

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

ELECTRONIC SAFETY AND SECURITY SYMBOLS

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE

X-REQUEST-FOR-EXIT

M

T

M

T

T

M

M

M

T

T

M

T

M

T

M

T

M

M

T

M

T

M

T

RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO D-DIGITAL V-VIDEO

SECURITY ACCESS, ANNUNCIATOR PANEL

SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF UNLESS OTHERWISE NOTED

SECURITY ACCESS, CONTROL UNIT WITH CLOSED CIRCUIT TELEVISION

CAMERA

SECURITY ACCESS, GENERIC "X" INDICATES THE TYPE, PROVIDE SCHEDULE OR LEGEND

SECURITY ACCESS, HORN OR SIREN

SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT

SECURITY ACCESS, PANIC ALARM

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM

SECURITY ACCESS, VOLUMETRIC SENSOR

VIDEO CONTROL KEYBOARD

VIDEO MOTION DETECTOR

SECURITY ACCESS, MULTI-SENSOR/PANORAMIC VIEW, ANGLE OF VIEW

SECURITY ACCESS, SENSOR, BURIED VEHICULAR

SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL

SECURITY ACCESS, TELEPHONE HANDSET

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

360°

40°

X

M PTZ

M

T

AP

SECURITY ACCESS, DOOR PROP/EXIT ALARMDA

SECURITY ACCESS, INTERFACE RELAY SWITCH

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR

ARMORED CABLE

ADA AMERICANS WITH DISABILITIES ACT

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BFF BELOW FINISH FLOOR

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

C CONDUIT

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONT CONTINUE

CONTR CONTRACTOR

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DRSW DOOR SWITCH

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EXIST EXISTING

FLEX FLEXIBLE METALLIC CONDUIT

FT FEET OR FOOT

ELECTRONIC SAFETY AND SECURITY ABBREVIATIONS

GND GROUND

GEN GENERATOR

GTB GROUND TERMINAL BOX

HOA HAND-OFF-AUTOMATIC

HZ HERTZ

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

J-BOX JUNCTION BOX

LF LINEAR FEET (FOOT)

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MT MOUNT

MTD MOUNTED

MTG MOUNTING

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

N NEUTRAL

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

REQD REQUIRED

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SSTV SECURITY SURVEILLANCE TELEVISION

SW SWITCH

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLT

WP WEATHERPROOF

A. REFER TO E-001 FOR ELECTRICAL LEGEND, GENERAL NOTES, AND ABBREVIATIONS.

B. THE MINIMUM STANDARD FOR ALL WORK SHALL BE THE APPLICABLE CODES REFERENCED ON THE LIFE SAFETY PLANS ON SHEET AE002 INCLUDING THE NATIONAL

ELECTRICAL CODE. WHENEVER THE ENGINEERS DESIGN REQUIRES A HIGHER STANDARD, THE HIGHER STANDARD DESIGN SHOWN SHALL BE FOLLOWED.

C. ALL WORK SHALL BE PERFORMED BY AN ELECTRICIAN LICENSED BY THE STATE OF KANSAS. AT COMPLETION OF THE PROJECT, A CERTIFICATE OF COMPLIANCE

SHALL BE FURNISHED BY THE ELECTRICAL INSPECTION AGENCY HAVING JURISDICTION OVER ELECTRICAL WORK PERFORMED.

D. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR, EQUIPMENT, AND TOOLS TO EXECUTE WORK DETAILED BY THE DRAWINGS AND PROJECT SPECIFICATIONS, AND SHALL PROVIDE A COMPLETELY OPERATIONAL VIDEO SURVEILLANCE/ELECTRICAL SYSTEM UPON COMPLETION OF THE PROJECT.

E. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF THE ELECTRICAL WORK WITH THAT OF OTHER TRADES. THE ELECTRICIAN IS RESPONSIBLE FOR MAKING ALL

ELECTRICAL CONNECTIONS TO THE EQUIPMENT REQUIRING ELECTRICAL POWER, REGARDLESS OF WHO FURNISHED OR INSTALLED IT.

F. THE CONTRACTOR IS RESPONSIBLE FOR DAILY CLEANUP OF ALL WORK AREAS DURING TERM PROJECT; AND FOR RETURNING TO ORIGINAL CONDITION UPON

COMPLETION OF ALL WORK INDICATED.

G. ALL ELECTRICAL WORK SHALL BE WARRANTED FOR ONE YEAR FROM THE DATE OF INSPECTION PUNCHLIST COMPLETION.

H. ALL MATERIALS USED SHALL BE NEW AND UL LISTED WHERE A LISTING EXISTS FOR THE PRODUCT.

I. ALL WIRING SHALL BE COPPER. ALUMINUM WIRING SHALL NOT BE ALLOWED. MINIMUM WIRE SIZE SHALL BE #12 AWG, CONDUCTORS SHALL BE THWN IN SMALLER

SIZES OR MAY BE THW IN LARGER SIZES IF ECONOMICAL, AND SHALL BE RATED 600 VOLTS. RUNS OF 120 VOLTS OVER 50 FEET SHALL UTILIZE #10 AWG TO

PREVENT EXCESSIVE VOLTAGE DROP. CONDUCTORS SHALL BE COLOR CODED AS REQUIRED BY THE NEC.

J. WIRING DEVICES SHALL BE SPEC GRADE, RATED 20 AMPERES. DEVICE PLATES SHALL BE SMOOTH FINISH IVORY NYLON.

K. CONDUIT CONCEALED IN WALLS OR CEILINGS SHALL BE EMT WITH TAMPER PROOF SCREWS, AND EXPOSED CONDUITS SHALL BE EMT WITH TAMPER PROOF SCREWS.

ALL CONDUITS SHALL HAVE AN EXTRA CONDUCTOR PULLED FOR GROUNDING. ALL CONDUIT SHALL BE CONCEALED, UNLESS SPECIFICALLY NOTED OTHERWISE. ALL

CONDUIT FITTINGS SHALL BE COMPRESSION TYPE. THE LAST PIECE OF CONDUIT INSTALLED TO EQUIPMENT SHALL BE FLEXIBLE METAL CONDUIT. MINIMUM CONDUIT

SIZE SHALL BE 3/4 INCH. CONDUITS SHALL BE INSTALLED AT RIGHT ANGLES TO CEILINGS, WALLS, AND STRUCTURAL MEMBERS. CONDUIT SHALL BE SUPPORTED BY

PIPE STRAPS, WALL BRACKETS, OR HANGERS. SPACER BACK CLAMPS SHALL BE UTILIZED IN MOIST OR WET AREAS.

L. HUBS SHALL BE USED ON BOXES WHERE CONDUIT ENTERS THE TOP AND IS EXPOSED TO WEATHER. SEALING LOCKNUTS MAY BE USED FOR SIDE ENTRY CONDUITS

IN THIS APPLICATION.

M. CONDUITS SHALL BE SEALED WHERE THEY ENTER THE BUILDING TO PREVENT GROUNDWATER ENTRY.

N. BOXES SHALL BE INSTALLED SUCH THAT THEY ARE SUPPORTED BY THE STRUCTURE. BOXES MAY NOT BE SUPPORTED BY CONDUIT.

O. IN THE ABSENCE OF DETAILS HEREIN ON USE OR INSTALLATION OF A PARTICULAR MATERIAL OR DEVICE, CODES AND MANUFACTURERS RECOMMENDATIONS SHALL BE

USED AS GUIDANCE.

P. IT IS HIGHLY RECOMMENDED THAT THE CONTRACTOR VISIT THE SITE PRIOR TO BIDDING, TO BECOME FAMILIAR WITH EXISTING CONDITIONS TO BE ENCOUNTERED

DURING CONSTRUCTION.

Q. NOT ALL SYMBOLS INDICATED IN THE LEGEND, OR LISTED ABBREVIATIONS, APPEAR ON THE DRAWINGS. COORDINATE WORK ACCORDINGLY. COMPLY WITH

SPECIFICATIONS AND GENERAL NOTES AS APPLICABLE.

R. ALL WORK SHALL COMPLY WITH LATEST EDITION OF NFPA70, NFPA72, NFPA99, NFPA101, NEC & ALL FEDERAL, STATE & LOCAL REGULATIONS.

S. ALL PENETRATIONS THROUGH FLOORS, RATED WALLS AND PARTITIONS SHALL BE SEALED WITH UL APPROVED FIRESTOPPING/SEALANT MATERIAL TO MAINTAIN THE

EXISTING FIRE RATING FOR THE ASSEMBLY.

T. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED WITH ALL FEEDER AND BRANCH CIRCUITS. SIZE IN ACCORDANCE WITH NFPA 70 ARTICLE 250.

U. COORDINATE INSTALLATION AND FINAL LOCATION OF DATA OUTLETS WITH THE VA.

V. IDENTIFICATION:

RECEPTACLES CONNECTED TO THE ESSENTIAL ELECTRICAL SYSTEM SHALL BE RED WITH A WHITE LABEL CONTAINING THE WORD "EMERGENCY" IN BLACK ON THE TOP

OF THE PLATE AND A WHITE LABEL WITH THE CIRCUIT NUMBER IN BLACK ON THE BOTTOM. "NORMAL" RECEPTACLES SHALL HAVE A WHITE LABEL WITH THE CIRCUIT

NUMBER IN BLACK AT THE BOTTOM OF THE PLATE.

W. PROVIDE WIRE MARKERS TO IDENTIFY CABLES FOR ALL SYSTEMS AT THE ORIGIN, PULL BOXES, AND TERMINATION POINTS. LABELS SHALL BE SELF ADHESIVE OR

HEAT SHRINK TYPE AND BE PERMANENTLY AFFIXED TO THE WIRE BEING LABELED.

X. NO LIVE WORK WILL BE ALLOWED. EVERY CIRCUIT SHALL BE LOCKED-OUT AND TAGGED-OUT BEFORE COMMENCING WORK.

Y. NO "J" HOOKS. (OR ANY OTHER TYPE OF WIRE "HANGING" SYSTEM IS PERMITTED WITHIN THE SCOPE OF THIS WORK FOR THE ENTIRE LENGTH OF WIRING RUNS

INDICATED.) REFER TO GENERAL NOTE "K".

Z. NEW CONDUIT RUNS SHOWN BY PLANS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL INSTALL NEW CONDUITS IN CONCEALED LOCATIONS UNLESS SPECIFICALLY

NOTED OTHERWISE.

AA. MOST CONDUITS TO BE INSTALLED ABOVE EXISTING SUSPENDED ACOUSTICAL TILE (SAT) CEILINGS IN A MANNER THAT MINIMIZES DAMAGE TO EXISTING SAT CEILINGS.

(REFER TO GENERAL NOTES SHEET E-002.)

AB. TOTAL CONDUIT LENGTHS MAY NOT EXCEED 295'-0" FROM CAMERA LOCATION TO I.T. ROOM CONNECTION POINT.

AC. NEW CONDUITS SHALL BE SECURED TO EXISTING WALL CONSTRUCTION, EXISTING STRUCTURAL SYSTEM OR EXISTING PLASTER FINISHES CONCEALED FROM VIEW (ABOVE

SAT).

AD. CONTRACTOR SHALL TAKE MEASURES NECESSARY TO AVOID CONFLICTS WITH EXISTING MECHANICAL, ELECTRICAL AND PLUMBING (MEP) INFRASTRUCTURE AT NO

ADDITIONAL COST TO VAMC.

AE. VA INFORMATION TECHNOLOGY/SYSTEMS PERSONNEL WILL USE THE CONTRACTOR'S COMPLETED, LABELED AND INDEX LISTED CABLING TO PHYSICALLY MAKE THE FINAL

CONNECTION TO VAMC OWNED SWITCHES INSIDE OF IT ROOMS.

AF. INTRUSION DETECTION SYSTEMS (IDS), DURESS/PANIC SYSTEMS, PHYSICAL ACCESS CONTROL SYSTEMS (PACS), AND SECURITY SURVEILLANCE TELEVISION (SSTV)

DESIGN TO FOLLOW VA PSRDM - CHAPTER 10, VA TDM 2016, AND NEC.

ELECTRONIC SAFETY AND SECURITY GENERAL NOTES:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t

/1

/2

:4

:3

P

M

T-001

SECURITY ELECTRONICS

SYMBOLS AND GENERAL NOTES

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

Revisions: Date:

2022-01-20

0.1 0.2 0.3 0.4 0.5 0.8 1

B

A.7

A.6

A.5

A.4

A

STORAGE

BATHROOM

OFFICE

OFFICE

OFFICE

OFFICE AREA

EXISTING

TUNNEL

TD

B

TD

B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

PLAN

NORTH

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:4

P

M

TD101A

SECURITY ELECTRONICS DEMOLITION

OFFICE AREA LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - OFFICE AREA LOWER FLOOR PLAN

SHEET KEYNOTES:

1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

1 3 4 5 6 7

A.7

A.6

A.5

A.4

A

21 2 3 4 5 6 7

A

B

CONTROL ROOM

EXISTING BOILER

ROOM

EXISTING SHOP

AREA

EXISTING

STORAGE

100A

TD

A

TD

A

TD

C

TD

C

1 1 2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:4

P

M

TD101B

SECURITY ELECTRONICS DEMOLITION

BOILER ROOM WEST LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - BOILER ROOM WEST LOWER FLOOR PLAN

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

SHEET KEYNOTES:

1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.

2 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL PANEL AND ASSOCIATED CONDUIT/CABLING.

7 8 9

A.7

A.6

A.5

A.4

A

97 8

A

B

TD

B

TD

B

EXISTING SHOP

AREA

3SECURITY ROOM

PUMP PIT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:4

P

M

TD101C

SECURITY ELECTRONICS DEMOLTION

BOILER ROOM EAST LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - BOILER ROOM EAST LOWER FLOOR PLAN

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

SHEET KEYNOTES:

1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.

2 EXISTING PHYSICAL ACCESS CONTROL PANEL TO REMAIN. PANEL SERVES THE

ADJACENT SECURITY ELECTRONICS EQUIPMENT RACK.

3 EXISTING SECURITY ELECTRONICS EQUIPMENT RACK TO REMAIN.

A

B

0.1

C

TD

B

TD

B

STORAGE

CONFERENCE

ROOM

CORRIDOR

OFFICE

OFFICE

STORAGE

ELECTRIC SHOP

TOILETS

ELECTRICAL

ROOM

OFFICE

EXISTING

MEZZANINE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:4

P

M

TD102A

SECURITY ELECTRONICS DEMOLITION

OFFICE AREA UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - OFFICE AREA UPPER FLOOR PLAN

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

SHEET KEYNOTES:

1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.

1 3 4 5 6 7

C

B

A.7

A.6

A.5

A.4

A

1 2 3 4 5 6 7

A

B

C

EXISTING

STORAGE

100A

EXISTING

INCINERATOR

TD

A

TD

A

TD

C

TD

C

EXISTING BOILER

ROOM

EXISTING

STACK

EXISTING SHOP

AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:4

P

M

TD102B

SECURITY ELECTRONICS DEMOLITION

BOILER ROOM WEST UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - BOILER ROOM WEST UPPER FLOOR PLAN

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

SHEET KEYNOTES:

1 CONTRACTOR SHALL REMOVE AND PROPERLY DISPOSE OF EXISTING PHYSICAL

ACCESS CONTROL DEVICES AND ASSOCIATED CONDUIT/CABLING.

A.7

A.6

A.5

A.4

A

97 8

A

B

TD

B

TD

B

EXISTING SHOP

AREA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:5

P

M

TD102C

SECURITY ELECTRONICS DEMOLITION

BOILER ROOM EAST UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS DEMOLITION - BOILER ROOM EAST UPPER FLOOR PLAN

GENERAL NOTES:

1 AN EFFORT HAS BEEN MADE TO DOCUMENT MAJOR SECURITY ELECTRONICS

EQUIPMENT/DEVICES FOR REMOVAL; HOWEVER, THE CONTRACTOR SHALL COORDINATE

WITH OTHER TRADES FOR THE COMPLETE DEMOLITION NAD PROPER DISPOSAL OF

ALL RELATED ELECTRICAL EQUIPMENT.

2 WHERE CONDUIT HAS BEEN REMOVED THROUGH EXISTING FIRE RATED

CONSTRUCTION, THE CONTRACTOR SHALL PROPERLY SEAL UNUSED PENTETRATIONS

TO MAINTAIN THE EXISTING FIRE RATING.

3 ALL DEMOLITION WORK SHALL BE COORDINATED WITH ALL OTHER WORK AND

EXISTING CONDITIONS TO ASSURE PROPER REMOVAL OF EXISTING SECURITY

ELECTRONICS WORK.

4 CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE DEMOLITION OF

ANY WORK.

SHEET KEYNOTES:

8' ROLL-UP DOOR

AIR DUCTING

C O N C R

ETE

SID

EW

ALK

8' ROLL-UP DOOR

' R

O

LL

-U P

D O

O R

∅1 3'-

4"

7'-9"

BUILDING 37

BUILDING 39

ELECTRICAL SHOP

BUILDING 39

BOILER PLANT

BUILDING 39A

STACK

BUILDING 129

BUILDING 28

BUILDING 81

TE

M P O R A R Y

E

LE

C

TR

IC

A L

E Q U

IP

M E N T

(S E E

E

LE

C

TR

IC

A L

D R A W

IN

G S

TE

M P O R A R Y

C O N

TR

O L

R O O M

O

FF

IC

E

TR

A

IL

E R

TEMPORARY 1000 HP STEAM

GENERATION TRAILER NO. 1

TEMPORARY 1000 HP STEAM

GENERATION TRAILER NO. 2

180°

1 2

4 5 6

DIESEL FUEL

TANK

GP1

PEDESTRIAN GATE

24VDC

POWER

SUPPLY

JUNCTION

BOX ON

SECURE SIDE

OF FENCE

MAGNETIC LOCK

BMS W/ DOOR PROP ALARM

REX PUSHBUTTON

CARD READER W/ PIN PAD

24VDC

3-2C/#18 NON-

SHIELDED CABLE,

1-4C/#20 CABLE (1-PR

SHIELDED), 1"C

EXISTING ACCESS

CONTROL PANEL

2 READER

2C/#18 NON-SHIELDED CABLE

2-2C/#18 NON-SHIELDED CABLE

4C/#20 CABLE (1-PR SHIELDED)

SHEET KEYNOTES:

1. CONNECT TO THE 20A/120V CIRCUIT SERVING THE EXISTING PHYSICAL

ACCESS CONTROL PANEL.

120VAC

6C/#18 SHIELDED

PLENUM CABLE, 1"C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

/1

/2

:4

:5

P

M

TY010

SECURITY ELECTRONICS

SITE PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/16" = 1'-0"

SECURITY ELECTRONICS - SITE PLAN

SHEET KEYNOTES:

1 TEMPORARY GATE WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO

POWER SUPPLY AND EXISTING PHYSICAL ACCESS CONTROL PANEL (SHEET TY101C).

REFER TO DETAIL 2 ON SHEET T-502.

2 CARD READER PEDESTAL. REFER TO PEDESTAL DETAILS ON SHEET T-502.

3 REX PUSHBUTTON PEDESTAL. MOUNT SIMILAR TO PEDESTAL DETAILS ON SHEET

T-502.

4 POLE MOUNTED CAMERA WITH SURVEILLANCE CABINET. REFER TO DETAILS ON

SHEET T-503 FOR ADDITIONAL INFORMATION.

5 PROVIDE 4-STRAND 9/125 MICRON SINGLEMODE FIBER OPTIC CABLE, 1"C FROM

SURVEILLANCE CABINET BACK TO SECURITY ELECTRONICS EQUIPMENT RACK (SHEET

TY101A).

6 120V CIRCUIT REQUIRED TO SURVEILLANCE CABINET. REFER TO ELECTRICAL

DRAWINGS FOR CIRCUIT INFORMATION.

GENERAL NOTES:

1 ALL SECURITY ELECTRONICS CABLING SHALL BE INSTALLED IN CONDUIT.

2 WHERE POSSIBLE, UTILIZE THE TEMPORARY PIPE SUPPORTS FROM THE TEMPORARY

BOILER PLANT TRAILERS TO EXISTING BUILDING 39 (REFER TO C102 FOR PIPE

SUPPORT LOCATIONS). OTHERWISE, CONDUIT SHALL BE INSTALLED UNDERGROUND.

3 LOCATE ALL EXISTING UNDERGROUND UTILITIES FOR ALL UNDERGROUND WORK PRIOR

TO EXCAVATION OR TRENCHING. HAND DIG WITHIN 10' OF AN UTILITY CROSSING

WITH NEW WORK.

4 MINIMUM BURY FOR ALL SITE CONDUITS SHALL BE 30", UNLESS OTHEWISE NOTED.

CONTRACTOR IS RESPONSIBLE FOR ALL SITE TRENCHING AND BACKFILL.

5 REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION.

6 REFER TO TEMPORARY PHYSICAL ACCESS CONTROL SYSTEM RISER DIAGRAM, THIS

SHEET.

7 REFER TO SHEETS T-502 PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

8 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM.

9 REFER TO SHEET T-503 FOR CAMERA MOUNTING DETAILS.

10 EQUIPMENT/DEVICES SHOWN ON THIS SHEET SHALL BE COORDINATED WITH GATE

LOCATION AND GENERAL CONTRACTOR PRIOR TO ROUGH-IN.

11 AFTER USE OF THE TEMPORARY CONTROL BUILDING AND BOILERS, CONTRACTOR

SHALL REMOVE ASSOCIATED SECURITY ELECTRONICS DEVICES/EQUIPMENT AND TURN

OVER TO OWNER.

NOT TO SCALE

PHYSICAL ACCESS CONTROL SYSTEM RISER DIAGRAM - TEMPORARY GATE

M

M

M

0.1 0.2 0.3 0.4 0.5 0.8 1

B

A.7

A.6

A.5

A.4

A

TY

B

HAC

ELECTRICAL

111 SECURITY

CIRCULATION

OFFICE

RESTROOM

STAIR

TOILET

ACCESSIBLE

TOILET

SHOWER

LOCKERS

TY

B

102A

CONTROL ROOM

FF

S

S

S

X

S

X

SS

M

X

F F

SX

F

XS X

FFF

F X

S

X

F

F

F

UTILITY

VESTIBULE

B1121

CONTROLS

DA

DA

DA

DA

C1141

C1041

EXISTING

TUNNEL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:5

P

M

TY101A

SECURITY ELECTRONICS

OFFICE AREA LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR ACCESS CONTROL SYSTEM RISER

DIAGRAMS.

2 REFER TO SHEET T-501 FOR ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED ACCESS CONTROL

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - OFFICE AREA LOWER FLOOR PLAN

SHEET KEYNOTES:

1 SECURITY ELECTRONICS EQUIPMENT RACK. REFER TO DETAIL 3 ON SHEET T-602

AND VIDEO SURVEILLANCE SYSTEM RISER DIAGRAM ON SHEET T-605 FOR

ADDITIONAL INFORMATION.

2 EXISTING SECURITY ELECTRONICS EQUIPMENT RACK TO REMAIN.

3 PROVIDE 1"C WITH 12-STRAND MULTIMODE (OM1) OPTICAL FIBER CABLE FROM

FIBER TERMINATION PANEL (EXISTING SECURITY ELECTRONICS EQUIPMENT RACK) TO

FIBER TERMINATION PANEL (NEW SECURITY ELECTRONICS EQUIPMENT RACK).

4 3/4" PLYWOOD TREATED WITH FLAME RETARDANT PAINT - SEE SPECIFICATIONS FOR

FURTHER DETAILS. TYPICAL ON ALL WALLS.

5 TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). REFER TO DETAIL 7, SHEET

E-503 FOR BONDING TO EQUIPMENT WITHIN ROOM.

6 INTRUSION DETECTION SYSTEM CONTROL PANEL. REFER TO SPECIFICATION SECTION

281600.

7 CAT 6A CABLE, 1"C FROM INTRUSION DETECTION CONTROL PANEL TO A DEDICATED

PHYSICAL ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL IN THE

SECURITY ELECTRONICS EQUIPMENT RACK.

8 WALL-MOUNTED EQUIPMENT RACK TO HOUSE INTERCOM SYSTEM HEADEND

EQUIPMENT. REFER TO DETAIL 2, SHEET T-604 FOR ADDITIONAL INFORMATION..

9 CAT 6A UTP, 1"C FROM INTERCOM SYSTEM EQUIPMENT TO DEDICATED PHYSICAL

ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL IN THE SECURITY

ELECTRONICS EQUIPMENT RACK.

10 PHYSICAL ACCESS CONTROL PANEL. REFER TO PACS RISER DIAGRAMS ON SHEET

T-601 THROUGH T-603. REFER TO SPECIFICATION SECTION 281300.

11 DOOR POWER SUPPLIES - QUANTITY AS REQUIRED. REFER TO PACS RISER DIAGRAMS

ON SHEET T-601 THROUGH T-603. REFER TO SPECIFICATION SECTION 281300.

12 SINGLE DOOR WITH ELECTRIC STRIKE. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 1 ON SHEET T-501.

13 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 2 ON SHEET T-501.

14 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.

15 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.

16 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"

BELOW CEILING, WHICHEVER IS LOWER.

17 WALL MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AS HIGH AS POSSIBLE,

COORDINATE MOUNTING HEIGHT WITH OTHER TRADES.

18 PROVIDE CONNECTION FROM FIRE ALARM CONTROL MODULE TO PHYSICAL ACCESS

CONTROL SYSTEM. CONTROLLED DOORS SHALL ALLOW FREE EXIST UPON ACTIVATON

OF THE FIRE ALARM SYSTEM AS REQUIRED BY NFPA 72. COORDINATE WITH FIRE

ALARM SYSTEM CONTRACTOR.

19 CEILING MOUNTED CAMERA WITH MOTION DETECTION. REFER TO DETAIL 4, SHEET

T-503.

20 PROVIDE CAT 6A CABLE FROM EACH PHYSICAL ACCESS CONTROL PANEL TO A

DEDICATED PHYSICAL ACCESS CONTROL/INTRUSION DETECTION SYSTEM PATCH PANEL

IN THE SECURITY ELECTRONICS EQUIPMENT RACK.

360°

90°

360°

360°

1 3 4 5 6 7

B

A.7

A.6

A.5

A.4

A

21 2 3 4 5 6 7

A

B

TY

A

100c 100b100d

100D

100a

EXISTING

STORAGE

100A

101B

TY

C

TY

C

3 3 3

F

X S X

F F F

F

X M X

F F F F

M M

S S S F F F F FF

M M M M M M S

F

4 4 4

5S

F

C1011 A1002 A1003

CONTROL ROOM

BOILER ROOM

DA

DA DA DA DA

12 12

DA

E1001

D1002

D1003

A1001

17 17

TY

A

D1001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:5

P

M

TY101B

SECURITY ELECTRONICS

BOILER ROOM WEST LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - BOILER ROOM WEST LOWER FLOOR PLAN

SHEET KEYNOTES:

1 SINGLE DOOR WITH ELECTRIC STRIKE. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 1 ON SHEET T-501.

2 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 2 ON SHEET T-501.

3 OVERHEAD DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 5 ON SHEET T-501.

4 OVERHEAD DOOR CONTROLLER. COORDINATE LOCATION WITH OVERHEAD DOOR

INSTALLER.

5 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.

6 IP VIDEO MASTER STATION - DESK MOUNTED.

7 REMOTE VASS/SSTV WORKSTATION.

8 43" LED VIDEO SURVEILLANCE MONITOR. COORDINATE LOCATION AND MOUNTING

HEIGHT WITH OWNER.

9 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"

BELOW CEILING, WHICHEVER IS LOWER.

10 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.

11 CEILING MOUNTED CAMERA. REFER TO DETAIL 4, SHEET T-503.

12 BOILER CONTROL PANEL.

13 PROVIDE CONNETION (BOILER FAULT COMMON ALARM) FROM BOILER MASTER

CONTROL PANEL TO INTRUSION DETECTION CONTROL PANEL.

14 WALL MOUNTED CAMERA 180-DEGREE PANORAMIC CAMERA (REFER TO DETAIL 3,

SHEET T-503). MOUNT AT 10'-0" AFF, HOWEVER, FIELD COORDINATE EXACT

MOUNTING FOR OPTIMAL COVERAGE. .

15 WALL MOUNTED CAMERA (REFER TO DETAIL 3, SHEET T-503). MOUNT AT

12'-0"AFF AND PROVIDE COVERAGE OF BOILER PANEL.

16 WALL MOUNTED CAMERA (REFER TO DETAIL 3, SHEET T-503). MOUNT AT

10'-0"AFF AND PROVIDE COVERAGE OF BOILER PANEL.

17 PENDANT MOUNTED 360-DEGREE FISHEYE PANORAMIC CAMERA (REFER TO DETAIL 5,

SHEET T-503). MOUNT AT 12'-0" AFF; HOWEVER, FIELD COORDINATE EXACT

MOUNTING FOR OPTIMAL COVERAGE.

18 SURFACE MOUNTED 360-DEG PANORAMIC CAMERA. MOUNT TO BOTTOM OF

CATWALK. PROVIDE COVERAGE OF NORTHWEST AREA OF BOILER PLANT AND

EXISTING STEAM TUNNEL.

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM

RISER DIAGRAMS.

2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION

DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN

SECURITY 112 (SHEET TY101A).

360°

B

A.7

A.6

A.5

A.4

A

97 8

A

B

TY

B

TY

B

BOILER PLANT

PUMP PIT

SECURITY ROOM

DA

S

S

X S

M

SX

S

100C

F1001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BOILER

RM EAST

BOILER

RM WEST

STORAGE

OFFICE AREA

/1

/2

:4

:5

P

M

TY101C

SECURITY ELECTRONICS

BOILER ROOM EAST LOWER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - BOILER ROOM EAST LOWER FLOOR PLAN

SHEET KEYNOTES:

1 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"

BELOW CEILING, WHICHEVER IS LOWER.

2 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.

3 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 2 ON SHEET T-501.

4 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.

5 PENDANT MOUNTED 360-DEGREE PANORAMIC CAMERA (REFER TO DETAIL 5, SHEET

T-503). MOUNT AT 14'-6" AFF; HOWEVER, FIELD COORDINATE EXACT MOUNTING

FOR OPTIMAL COVERAGE.

6 UTILIZE THE EXISTING PHYSICAL ACCESS CONTROL PANEL TO PROVIDE CONTROL OF

THE TEMPORARY GATE (SHEET TY010). PROGRAM THE EXISTING CONTROL PANEL AS

REQUIRED TO INCORPORATE THE ADDED INPUT/OUTPUTS. REFER TO PHYSICAL

ACCESS CONTROL SYSTEM RISER DIAGRAM - TEMPORARY GATE (SHEET TY010).

7 POWER SUPPLY FOR MAGNETIC LOCK FOR TEMPORARY GATE (TY010). CONNECT TO

THE 20A/120V CIRCUIT SERVING THE EXISTING PHYSICAL ACCESS CONTROL PANEL.

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM

RISER DIAGRAMS.

2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION

DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN

SECURITY 112 (SHEET TY101A).

REF.

M

0.1 0.2 0.3 0.4 0.5 0.8 1

C

B

A.7

A.6

A.5

A.4

A

A

B

0.1

C

STAIR

BREAK ROOM

TRAINING ROOM

CONFERENCE

ROOM

CORRIDOR

OFFICE

OFFICE

STORAGE

STORAGE

ELECTRIC SHOP

TOILETS

ELECTRICAL

ROOM

OFFICE

TY

B

208F

XMX

FFF

S X

X

M

S

S

S

S

X M X

S SS

TY

B

S

S

S S

DA

DA

DA

DA

X

S

S

S

M X

S

C2041

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:0

P

M

TY102A

SECURITY ELECTRONICS

OFFICE AREA UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - OFFICE AREA UPPER FLOOR PLAN

SHEET KEYNOTES:

1 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 2 ON SHEET T-501.

2 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.

3 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"

BELOW CEILING, WHICHEVER IS LOWER.

4 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.

5 CEILING MOUNTED CAMERA. REFER TO DETAIL 4, SHEET T-503.

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM

RISER DIAGRAMS.

2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION

DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN

SECURITY 112 (SHEET TY101A).

M

MM

M

1 3 4 5 6 7

C

B

A.7

A.6

A.5

A.4

A

1 2 3 4 5 6 7

A

B

C

TY

A

TY

A

BOILER ROOM

EXISTING

STORAGE

100A

TRANSFORMER

ROOM

GENERATOR

ROOM

TY

C

TY

C

201A

203A

202B

202A

SX

M

X

S

S

S

S

X M X

S S S

S

M

X

M

XS

S

S

S

S

S

S

B2031

LINK

6 6

EXISTING

STACK

203B

DA

DA

DA

DA

DA

X F

M F

FX

S

B2011

DA

7 S

X S

M S

SM

X S

S

S

DAD

B2021

B100A1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:0

P

M

TY102B

SECURITY ELECTRONICS

BOILER ROOM WEST UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - BOILER ROOM WEST UPPER FLOOR PLAN

SHEET KEYNOTES:

1 DOUBLE DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO

ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION PANELS.

REFER TO DETAIL 3 ON SHEET T-501.

2 DOUBLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 4 ON SHEET T-501.

3 SINGLE DOOR WITH MAGNETIC LOCK. PROVIDE CONDUIT/WIRING BACK TO POWER

SUPPLIES AND ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION

PANELS. REFER TO DETAIL 2 ON SHEET T-501.

4 INTERCOM/VIDEO STATION. MOUNT AT 46" AFF TO CENTERLINE.

5 WALL MOUNTED CAMERA WITH MOTION DETECTION. MOUNT AS HIGH AS POSSIBLE,

COORDINATE MOUNTING HEIGHT WITH OTHER TRADES.

6 INTRUSION DETECTION SYSTEM - SPEAKER/SIREN. MOUNT AT 80" AFF OR 6"

BELOW CEILING, WHICHEVER IS LOWER.

7 INTRUSION DETECTION SYSTEM - KEY PAD. MOUNT AT 46" AFF TO CENTERLINE.

8 PROVIDE CONNECTION (GENERATOR FAULT COMMON ALARM) FROM GENERATOR

CONTROLLER TO INTRUSION DETECTION CONTROL PANEL.

9 OVERHEAD DOOR WITH MONITORING ONLY. PROVIDE CONDUIT/WIRING BACK TO

ASSOCIATED PHYSICAL ACCESS CONTROL AND INTRUSION DETECTION PANELS.

REFER TO DETAIL 1 ON SHEET T-502.

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM

RISER DIAGRAMS.

2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION

DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN

SECURITY 112 (SHEET TY101A).

A.7

A.6

A.5

A.4

A

97 8

A

B

BOILER ROOM

TY

B

TY

B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR

ANY PURPOSE WHATSOEVER WITHOUT THE SEAL AND

SIGNATURE OF THE PROFESSIONAL ENGINEEER

MR PROJECT NO:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e in c h o n e fo o t

ACTUAL

NORTH

KEYPLAN

BLDG

39A

BOILER

RM EAST

BOILER

RM WEST

STORAGEELECTRICAL

SHOP

OFFICE AREA

LINK

STACK

/1

/2

:4

:0

P

M

TY102C

SECURITY ELECTRONICS

BOILER ROOM EAST UPPER FLOOR PLAN

REPLACE BOILERS

IN BUILDING 39

DWIGHT D. EISENHOWER VA MEDICAL

CENTER - LEAVENWORTH, KS

589A6-19-204

2022-01-20 PJB PJB0509-006

BID DOCUMENTS

SCALE: 1/4" = 1'-0"

SECURITY ELECTRONICS - BOILER ROOM EAST UPPER FLOOR PLAN

SHEET KEYNOTES:

GENERAL NOTES:

1 REFER TO SHEETS T-601 THRU T-603 FOR PHYSICAL ACCESS CONTROL SYSTEM

RISER DIAGRAMS.

2 REFER TO SHEET T-501 FOR PHYSICAL ACCESS CONTROL SYSTEM DETAILS.

3 COORDINATE WITH DOOR HARDWARE INSTALLER FOR ALL REQUIRED PACS

CONNECTIONS AND ROUGH-IN REQUIREMENTS.

4 REFER TO SHEET T-604 FOR INTRUSION DETECTION SYSTEM RISER DIAGRAM.

5 REFER TO SHEET T-604 FOR INTERCOM SYSTEM RISER DIAGRAM.

6 REFER TO SHEET T-605 FOR VIDEO SURVEILLANCE SYSTEM DIAGRAM.

7 REFER TO SHEET T-502 FOR CAMERA MOUNT DETAILS.

8 HEADEND EQUIPMENT ASSOCIATED WITH PHYSICAL ACCESS CONTROL, INTRUSION

DETECTION, VIDEO SURVEILLANCE, AND INTERCOM SYSTEMS ARE LOCATED IN

SECURITY 112 (SHEET TY101A).

SUSPENDED CEILING

ELECTRIC

STRIKE

46"

DOORS: 101B, 102A, 111, 112

2C/#18 NON-SHIELDED, 3/4"C

BALANCED MAGNETIC SWITCH

(WITH 10-SECOND ANTI-PROP ALARM)

JUNCTION

BOX

SECURE

CONTACTLESS SMARTCARD

READER WITH KEYPAD

(UNSECURE SIDE OF DOOR)

2-2C/#18 NON-SHIELDED, 3/4"C

POWER

SUPPLY

120VAC

24VDC

CLASS II STEPDOWN

TRANSFORMER

6C/#18 SHIELDED

PLENUM CABLE, 3/4"C

POWER

SUPPLY

120VAC

12VDC

CLASS II STEPDOWN

TRANSFORMER

REQUEST TO EXIT (REX)

MOTION DETECTOR

4C/#20 CABLE

(1-PR SHIELDED), 3/4"C

ACCESS

CONTROL

PANEL

CAT 6A UTP, 1"C TO ETHERNET SWITCH AT

SECURITY ELECTRONICS EQUIPMENT RACK

3-2C/#18 NON-

SHIELDED CABLE

2-4C/#20 CABLE

(1-PR SHIELDED),

1-1/4"C

(WHERE PRESENT)

4C/#20 CABLE

(1-PR SHIELDED), 3/4"C

EMERGENCY REX

PUSHBUTTON

GENERAL NOTE:

1. NOTE SHOWN - PROVIDE ADDITIONAL

CONDUIT/WIRING TO INTRUSION DETECTION

PANEL FROM BALANCED MAGNETIC

SWITCH (DPDT).

DOOR PROP ALARM (SET @ 10 SEC)

DOORS: 100C, 100D, 104

31, 33, 34, 201A, 203A, 203B, 208

BALANCED MAGNETIC SWITCH

(WITH 10-SECOND ANTI-PROP ALARM)

JUNCTION

BOX

SECURE

2C/#18 NON-SHIELDED, 3/4"C

POWER

SUPPLY

120VAC

24VDC

CLASS II STEPDOWN

TRANSFORMER

POWER

SUPPLY

120VAC

12VDC

ACCESS

CONTROL

PANEL

CAT 6A UTP, 1"C TO ETHERNET SWITCH AT

SECURITY ELECTRONICS EQUIPMENT RACK

CLASS II STEPDOWN

TRANSFORMER

2-2C/#18 NON-SHIELDED,

3/4"C

MAGNETIC LOCK

SUSPENDED CEILING

(WHERE PRESENT)

46"

CONTACTLESS SMARTCARD

READER WITH KEYPAD

(UNSECURE SIDE OF DOOR)

EMERGENCY REX

PUSHBUTTON

6C/#18 SHIELDED

PLENUM CABLE, 3/4"C

4C/#20 CABLE

(1-PR SHIELDED), 3/4"C

3-2C/#18 NON-

SHIELDED CABLE

2-4C/#20 CABLE

(1-PR SHIELDED),

1-1/4"C

REQUEST TO EXIT (REX)

MOTION DETECTOR

4C/#20 CABLE

(1-PR SHIELDED), 3/4"C

GENERAL NOTE:

1. NOTE SHOWN - PROVIDE ADDITIONAL

CONDUIT/WIRING TO INTRUSION DETECTION

PANEL FROM BALANCED MAGNETIC

SWITCH (DPDT).

DOOR PROP ALARM (SET @ 10 SEC)

DOORS: 19, 202A

MAGNETIC LOCK

46"

CONTACTLESS SMARTCARD

READER WITH KEYPAD

(UNSECURE SIDE OF DOOR)

EMERGENCY REX

PUSHBUTTON

BALANCED MAGNETIC SWITCH

(WITH 10-SECOND ANTI-PROP ALARM)

JUNCTION

BOX

REQUEST TO EXIT (REX)

MOTION DETECTOR

POWER

SUPPLY

12VDC

ACCESS

CONTROL

PANEL

CAT 6A UTP, 1"C TO ETHERNET SWITCH AT

SECURITY ELECTRONICS EQUIPMENT RACK

CLASS II STEPDOWN

TRANSFORMER

120VAC

POWER

SUPPLY

120VAC

24VDC

CLASS II STEPDOWN

TRANSFORMER

SUSPENDED CEILING

(WHERE PRESENT)

4-2C/#18 NON-

SHIELDED CABLE

2-4C/#20 CABLE

(1-PR SHIELDED), 1-1/2"C

6C/#18 SHIELDED

PLENUM CABLE, 3/4"C

4C/#20 CABLE

(1-PR SHIELDED), 3/4"C

2C/#18 NON-SHIELDED CABLE, 3/4"C

2-2C/#18 NON-SHIELDED CABLE, 3/4"C

4C/#20 CABLE (1-PR SHIELDED), 3/4"C

SECURE

GENERAL NOTE:

1. NOTE SHOWN - PROVIDE ADDITIONAL

CONDUIT/WIRING TO INTRUSION DETECTION

PANEL FROM BALANCED MAGNETIC

SWITCH (DPDT).

DOOR PROP ALARM

(SET @ 10 SEC)

SUSPENDED CEILING

DOORS: 100a, 100b, 100c, 100d

SECURE

POWER

SUPPLY

120VAC

12VDC

CLASS II STEPDOWN

TRANSFORMER

ACCESS

CONTROL

PANEL

CAT 6A UTP, 1"C TO ETHERNET SWITCH AT

SECURITY ELECTRONICS EQUIPMENT RACK

(WHERE PRESENT)

FLOOR MOUNTED

MAGNETIC SWITCH

RECESSED

JUNCTION BOX

46"

CONTACTLESS SMARTCARD

READER WITH KEYPAD

(SECURE SIDE OF DOOR)

UP/DOWN/STOP

PUSHBUTTON

4#14, 1#14 GND, 3/4"C

2-2C/#18 NON-SHIELDED

CABLE, 3/4"C

COILING DOOR OPERATOR WITH

120-SECOND…

This is the start of the file's text. The full file is on GovTribe.