This document summarizes an asbestos survey report for Building 39 at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The survey identified asbestos-containing materials in six locations within the building, including brown sink undercoating, white pipe insulation, white tank insulation, and gray insulation. A total of forty-four samples were collected and tested by an independent laboratory, with asbestos detected in samples from the identified areas. The report provides the sample locations, descriptions of materials sampled, and asbestos testing results. It concludes that the VA is responsible for properly managing all asbestos-containing materials and any future renovation or demolition activities that may disturb asbestos will require abatement by licensed contractors according to applicable regulations.
The related federal contract opportunity notice is for replacement of four antiquated water tube boilers and associated piping and support systems with three new energy efficient fire tube boilers at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The project also involves replacement of auxiliary systems in Building 39, fuel oil pump sets, condensate piping, deaerator and condensate return tanks, addition of a continuous blowdown heat recovery package, and asbestos abatement of all replaced piping. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin seeking bids for a firm-fixed-price design-bid-build construction contract to complete the replacement project.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMPREHENSIVE INTERIOR ASBESTOS SURVEY
VA Eastern Kansas Health Care System
Dwight D. Eisenhower VAMC
Building 39
Leavenworth, Kansas 66048
Prepared for:
Department of Veterans Affairs
Network Contracting Office (NCO) 15
3450 S. 4th Street Trafficway
Leavenworth, KS 66048
Prepared by:
ENCON TEAM
Inspection Start Date:
September 02, 2020
AXIOM Service Professionals
P.O. Box 47166
Kansas City, MO 64188
ENCON International, Inc.
7307 Remcon Circle, #103
El Paso, TX 79912
September 18, 2020
Ms. Linda Lawrence, CIH
Industrial Hygienist
Eastern Kansas Healthcare System
2200 SW Gage Blvd.
Topeka, KS 66622 Email: Linda.Lawrence3@va.gov
RE: Submittal of Comprehensive Interior Asbestos Surveys
Contract No. 36C25520P0345, Obligation No. 589C02185
Dwight D. Eisenhower VAMC, Leavenworth, KS - Bldg. #39
Dear Ms. Lawrence, This document summarizes the Asbestos Survey Report for the subject building. The below listed information was utilized to complete the Scope of Work Tasks:
Bldg. No. 39 POC: Linda Lawrence, CIH Phone No: 913-682-2000 ext.52254
Approximate Building Square Footage (SF) Reported by VA: 14,200 SF
ASBESTOS SUMMARY: A total of forty-four (44) bulk samples were effectively collected for lab analysis from this subject building. The attached analytical results indicated that asbestos containing materials were present in the subject building. Contact the Eastern Kansas Healthcare System, Dwight D. Eisenhower
VAMC regarding the latest overall status of any asbestos materials.
SUMMARY TABLE
Were
Found
Were Not
Found
Future Mgt.
Actions
Required?
Asbestos Containing Materials (>1 %) X Yes
Please contact ENCON with any technical questions, or follow-up needs that you may have.
Sincerely, Alex Woelper, P.E.
Sr. Project Manager
CC: Emilio Ballentos (Contract Specialist)
ATTACHMENTS:
Asbestos Survey Report mailto:Linda.Lawrence3@va.gov
COMPREHENSIVE INTERIOR ASBESTOS SURVEY
Dwight D. Eisenhower VAMC ─ Building 39
PURPOSE
ENCON International, Inc., (ENCON) was contracted by the Department of Veterans Affairs
Network Contracting Office (NCO) 15, to perform Comprehensive Interior Asbestos Building
Materials Surveys to identify the presence of any asbestos at a number of buildings at the Topeka and Leavenworth VA Complexes. This project also included the updating of the Asbestos
Management plans for each campus. The following buildings have been included within this contract scope of work for the Dwight D. Eisenhower VAMC: Buildings 28, 30, 31, 33, 36, 37, 39, 40, 41, 54, 55, 66, 71, 73, 77, 81, 89, 90, 91, 94, 95, 97, 110, 112, 113, 117, 122, 123, 140, 143, 149A, 149B, 155, 160, and 161A. The technical objective of this project was to gather information regarding any existing asbestos materials within the assigned buildings, by inspecting and sampling suspect asbestos materials. The overall purpose was to facilitate the VA’s ability to properly operate and maintain its buildings, in compliance with federal regulations, including
VHA Directive 7714 titled, “Asbestos Management Program,” which has been provided at
Attachment 3.
BACKGROUND
The VA has a number of buildings constructed before 1990 when the use of asbestos was prevalent in the construction of buildings. Because these materials still exist in some of these buildings, the
VA is required to identify, assess the condition (stable or deteriorating), determine the nature of building materials (i.e., drywall or floor tile), and the extent of asbestos materials. In accordance with the Clean Air Act (40 CFR 61 Subpart M, Asbestos), any renovation, remodeling or demolition of any structure, (i.e., buildings, facilities, etc.), shall be surveyed for asbestos-containing materials (ACMs) and properly abated prior to any disturbance of the material.
INTRODUCTION
The sixty-one (61) buildings selected for Inspection during this project were contractually provided to ENCON by the VA. The selected buildings were located in two (2) geographic areas:
Topeka Campus (26 buildings) and Leavenworth Campus (35 buildings). Partial records were available for some of these buildings where previous asbestos inspections had been performed.
When available, prior asbestos reports were referenced to enhance the thoroughness of the comprehensive interior asbestos inspections performed for these buildings. The goal of this project was to provide comprehensive interior inspections of the designated facilities, utilizing non-destructive sampling methods. Therefore, on rare occasion some ACMs may be hidden behind walls, under subfloors, or located in other areas that were inaccessible to the inspection personnel, per standard general AHERA sampling protocols. Therefore, there is a very remote chance that limited additional destructive sampling may be required, only if hidden suspect ACMs are found in the future.
REGULATORY STANDARDS
Asbestos in building materials is regulated on the federal level by the Environmental Protection
Agency (EPA), and the Occupational Safety and Health Administration (OSHA). On the state level, Kansas also has regulations pertaining to sampling and abatement of asbestos in buildings.
The inspection was conducted to ensure compliance with National Emission Standards for
Hazardous Air Pollutants (NESHAP) – 40 CFR Part 61, Subpart M, which states that “prior to the commencement of the demolition or renovation, thoroughly inspect the affected facility or part of the facility where the demolition or renovation operation(s) will occur for the presence of asbestos, including Category I and Category II non-friable ACM.” Regulated asbestos containing materials have been designated as RACM. All Asbestos Inspectors were trained under the EPA AHERA
(40 CFR 763) standards. These facilities were sampled under the applicable regulations from the
EPA, 40 CFR 61, and sampling protocols were generally based on EPA AHERA standards, per
EPA 40 CFR 763.86, and in compliance with VHA Directive 7714.
FACILITY DESCRIPTION
Building 39 was constructed in 1886, and was in use at the time of inspection. Its previous use was listed as a “Boiler Plant.” A summary description of this building is presented in Table 1 below.
TABLE 1 – BUILDING DESCRIPTION
Building Items Description
Area of building 14,200 square feet
Date of Construction 1886
Number of floors One (1) floor
Exterior wall materials Brick, rock
Interior walls Plaster, drywall
Interior floors Concrete
Interior floor coverings 12x12 vinyl floor tiles
Ceilings 2x2 lay-in ceiling tiles, 2x4 lay-in ceiling tiles, wood
Notes: None
The main function or purpose, of this facility was identified as follows:
“Boiler Plant.”
HOMOGENEOUS AREAS
Within the facility homogeneous areas were determined. Homogeneous areas are defined as areas of suspect asbestos containing materials including surfacing materials, thermal system insulation
(TSI), or miscellaneous materials that were uniform in color, texture, substrate, and were relatively of the same age. Table 2 below lists the homogeneous areas and the general locations where they were identified.
TABLE 2 - Homogeneous Areas and Locations Identified
Homogeneous Areas
(Suspect Materials) Location
1 2x2 Lay-In Ceiling Tiles (Fissures / Small Pinholes) Employee Breakroom, Lounge, Office
2 Textured Drywall / Joint Compound (Walls) Employee Breakroom, Lounge, Office
3 Vinyl Cove Base (Grey) / Mastic Employee Breakroom, Lounge, Office
4 12x12 Vinyl Floor Tiles (Almond w/Grey) / Mastic Employee Breakroom, Lounge, Office
5 2x4 Lay-In Ceiling Tiles (Smooth) Locker Room Storage
6 Textured Plaster (Walls) Locker Room & Locker Room Storage
7 Sink Undercoating (Brown) Water Treatment Station
8 Plaster (Walls) Maintenance Supply Storage
9 Pipe Insulation (White) Boiler Room (Boiler Oil Supply System)
10 Pipe Insulation (White) Boiler Room & Auxiliary Generator
Room (Atomizing Steam System)
11 Pipe Insulation (White) Boiler Room & Auxiliary Generator
Room (Main Steam Supply System)
12 Pipe Insulation (White) Boiler Room & Auxiliary Generator
Room (Boiler H20 Supply System)
13 Pipe Insulation (White) Boiler Room (Breeching / Exhaust)
14 Tank Insulation (White) Unexcavated Room at Tanks
SAMPLING METHODOLOGY
The building materials survey tasks were performed in accordance with the EPA NESHAPs and/or
AHERA Regulations. An initial visual inspection of the building was conducted to develop a sampling strategy. This task included determining homogeneous areas / materials, and sample collection locations. Friability was assessed by manually manipulating the suspect asbestos materials utilizing hand pressure to determine if the materials, when dry, could be crumbled, pulverized, or reduced to powder. Fourteen (14) homogeneous areas were established and at least three (3) samples were collected from each area to adequately identify accessible asbestos in the building. Portions of the subject building that had suspect asbestos-containing surfacing, thermal system insulation, or miscellaneous materials were divided into homogeneous areas for sampling.
These samples were each uniquely and individually identified and logged into a chain of custody document and prepared for shipment to a third-party, independent laboratory for analysis. Building materials that were not considered suspect ACM included the following: concrete, metal, glass, and wood. As is commonly practiced, destructive sampling was not authorized or performed to locate hidden or inaccessible materials.
Forty-four (44) suspect ACM samples were collected and submitted for laboratory analysis. Refer to Appendix A for Asbestos sample location drawing(s). Bulk sample analyses were conducted utilizing polarized light microscopy (PLM), as per EPA Test Method 600/R-93/116. This method separates the sample material into various layers based on their morphology, and then identifies the presence of the different asbestos fibers in each of these layers when detected. The laboratory testing was performed by Apex Precision Analytical Services, Inc., located in Friendswood, TX.
Asbestos-Containing Material is defined as a material that contains greater than 1% of any asbestos type including Chrysotile, Amosite, Crocidolite, Tremolite, Anthophyllite, and Actinolite, or combinations of these materials. Asbestos materials are typically determined as recommended in the July 1993 EPA/600/R-93/116 document titled, "Method for the Determination of Asbestos in
Bulk Building Materials." Copies of the asbestos laboratory test results and related laboratory documentation have been provided in Appendix B of this Report.
LABORATORY ANALYSIS
The sample collection and subsequent laboratory analysis indicated that asbestos was identified in the building, as per Table 3 as follows. The NESHAPs definitions were used to define the condition of ACMs, per 40 CFR 61, Subpart M.
The asbestos quantities provided in the prior Table 3 are rough estimates only and must be field verified by any future abatement contractors.
TABLE 3 – Identified Asbestos Containing Materials (> 1%) Condition
Sample No.
Asbestos Containing
Materials
Approx.
Qty.
Location
F ri ab il it y
C at eg o ry
D am ag e
19-21 Sink Undercoating (Brown) ~4 SF Water Treatment Station NF I G
25-27 Pipe Insulation (White) ~90 LF Boiler Room (Boiler Oil Supply System) F - G
32-33 Pipe Insulation (White)
~350 LF
Boiler Room & Auxiliary Generator
Room (Main Steam Supply System) F - D
34, 36 Pipe Insulation (White)
~717 LF
Boiler Room & Auxiliary Generator
Room (Boiler H20 Supply System) F - G
38 Pipe Insulation (White) ~2,800 SF Boiler Room (Breeching / Exhaust) F - G
43-44 Tank Insulation (White) ~180 SF Unexcavated Room at Tanks F - G
*Friability: (F) – Friable; (NF) – Non-Friable
**Category: (I) – Category I; (II) – Category II
***Damage Condition: (G) – Good; (D) – Damaged; (SD) – Significantly Damaged
QUALIFICATIONS
This Comprehensive Interior Asbestos Survey was performed by ENCON Team Sr. Field
Inspectors Kody Tramm, and Glenn Robinson on September 02, 2020, and was conducted in accordance with the EPA National Emission Standards for Hazardous Air Pollutants (NESHAP):
40 CFR Part 61, Subpart M. Sampling protocols were performed in general accordance with
AHERA. The Inspectors had received training under the AHERA required Asbestos Inspector
Course and had received annual refresher training within the past year.
LIMITATIONS
The overall purpose of this Comprehensive Interior Asbestos Survey was to identify if ACM was present, within the qualifications and limitations summarized below. Reliance on this report is specifically limited to gathering initial information regarding the presence of asbestos in building materials. Any time that ACMs may be identified during the performance of an asbestos survey, the owner of the building is responsible to the occupants and to the public to manage these materials properly, per Local, State and Federal regulations. Prior to the abatement or removal of any ACMs, an asbestos project design should be properly created, by a qualified asbestos consulting firm, 1) to ensure that materials will be properly managed, and 2) to prepare a more accurate estimate of materials to be abated. This Survey Report was specifically prepared for the
Department of Veterans Affairs Network Contracting Office (NCO) 15, and the extent of liability incurred by the ENCON Team, is limited to the amount of the report fee paid by its Client. The
VA agrees that the ENCON Team cannot be held responsible for any liability based on reliance of this report by any third party for any business reasons.
CONCLUSIONS
1. The survey for the subject building was successfully completed, as required, per State and
Federal environmental standards. Refer to Table 1 for building details.
2. Suspect ACMs were potentially identified in fourteen (14) homogeneous areas at the subject building. Refer to Table 2 for a listing of homogeneous areas.
3. A total of forty-four (44) suspect ACM samples were collected from the building interior, and were properly analyzed by an independent, qualified third-party laboratory. Refer to
Appendix A for details regarding all sample locations.
4. A review of the laboratory test results indicated that ACMs were identified at the subject building. Refer to Table 3 for a confirmation listing of any identified ACMs.
5. Some ACMs were confirmed in six (6) homogeneous areas at the subject building. Refer to Appendix A and Appendix B for details regarding sample locations and descriptions.
6. The VA is responsible for properly managing all materials at the subject building.
7. Prior to any future renovation or demolition activities, asbestos related abatement activities will need to be performed by properly licensed personnel. Any ACMs should not be disturbed by unlicensed and / or untrained personnel.
8. Proper 10-day advance NESHAP notification should be made to the appropriate authorities prior to disturbance of any ACMs. Such disturbance includes abatement activities, building renovations, routine operation & maintenance activities, or any planned demolition in facilities or public buildings.
9. If disturbance of ACMs is anticipated, then these materials should be properly removed in advance of disturbance by licensed and trained personnel, as required by State and Federal regulations.
10. Abatement activities should be performed by a licensed Asbestos Abatement Contractor, with project management and air monitoring support by an experienced, certified Asbestos
Consulting Firm.
Future Contingent Requirements: The following additional requirements would need to be followed, only if additional hidden ACMs are identified through future destructive sampling activities.
1. In the unlikely event that additional “hidden suspect ACMs” are encountered during any future renovation or demolition activities, further limited sampling and lab analysis would be required. VA asbestos and / or safety personnel should be notified immediately for public safety and environmental compliance actions to properly manage any confirmed additional ACMs.
2. If disturbance of any newly identified ACMs is required in the future, then these materials should also be properly removed in advance of disturbance by licensed and trained personnel, as required by State and Federal regulations.
3. Any future abatement activities of previously hidden ACMs would also need to be performed by a licensed Asbestos Abatement Contractor, with project management and air monitoring support by an experienced, certified Asbestos Consulting Firm.
ATTACHMENTS
Refer to a copy of personnel certifications and VA document VHA Directive 7714 titled, “Asbestos Management Program," at Attachment 2 and Attachment 3, respectively. Additionally, a copy of the facilities’ Asbestos Management Plan has been provided at Attachment 4. Contact the personnel listed below with any clarifications that may be needed.
Inspected by:
Kody Tramm
Lead Asbestos Inspector AXIOM Service Professionals
Reviewed by:
Rosie Jimenez
Project Coordinator
Approved by:
Alex Woelper, P.E.
Sr. Project Manager
APPENDICES:
A. Asbestos Sample Location Drawing(s)
B. Laboratory Documentation
APPENDIX A
Asbestos Sample Location Drawing(s)
Draw by:
JA
7307 Remcon Cir, Ste 103
El Paso, Texas, 79912 915.833.3740
Sheet
ENV-1
ENCON
INTERNATIONAL, INC
NOT TO SCALE
Positive Asbestos Sample Locations
Asbestos Sample Location Drawing - Floor Plan ( Approx. 4,375 SF )
## Asbestos Sample Locations
Project:
# 113-20
EASTERN KANSAS VA
Asbestos Survey
Location:
Building # 39
Total Bldg. Area = 14,200 SF
Leavenworth, KS Date: 09-18-2020
Built (1886)
AW
Break Rm.
Lounge
13 - 15
16 - 18
19 - 21
25 - 27
Draw by:
JA
7307 Remcon Cir, Ste 103
El Paso, Texas, 79912 915.833.3740
Sheet
ENV-1
ENCON
INTERNATIONAL, INC
NOT TO SCALE
Project:
# 113-20
EASTERN KANSAS VA
Asbestos Survey
Location:
Building # 39
Total Bldg. Area = 14,200 SF
Leavenworth, KS Date: 09-18-2020
Built (1886)
AW
Pipe Insulation
Asbestos Homogeneous Areas - Floor Plan ( Approx. 4,375 SF )
Asbestos Homogeneous Areas
Tank Insulation
Sink Undercoating ( Brown )
APPENDIX B
Laboratory Documentation
ASBESTOS BULK ANALYSIS REPORT
September 15, 2020
ENCON International
5020-4224
Date:
Report:
113-20 / VA Kansas – Leavenworth, Building #39
This document shall be considered a duly signed original report of the results obtained from the analysis(es) performed. All analyses are done within government guidelines and regulations.
Gary R. Simmons Laboratory Manager
Lab Comments on Project: N/A
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-01
5020-4224-02
5020-4224-03
5020-4224-04A
5020-4224-04B 95%
5020-4224-04C
5020-4224-04D 10%
5020-4224-05A
5020-4224-05B 95%
5020-4224-05C
Bldg. 39 – 1 White,Grey / 2x2 Ceiling Tile / Fibrous /
Homogeneous None Detected
Cellulose Fibrous Glass
45% 5%
Binder
Bldg. 39 – 2 White,Grey / 2x2 Ceiling Tile / Fibrous /
Homogeneous None Detected
Cellulose Fibrous Glass
45% 5%
Binder
Bldg. 39 – 3 White,Grey / 2x2 Ceiling Tile / Fibrous /
Homogeneous None Detected
Cellulose Fibrous Glass
45% 5%
Binder
Bldg. 39 – 4 White / Texture / NonFibrous /
Homogeneous None Detected None Detected Binder
Off White / Joint Tape / Fibrous / Homogeneous
None Detected Cellulose Binder
White / Joint Compound / NonFibrous / Homogeneous
None Detected None Detected Binder
Brown,White / Drywall / Fibrous / Homogeneous
None Detected Cellulose Binder
Bldg. 39 – 5 White / Texture / NonFibrous /
Homogeneous None Detected None Detected Binder
Off White / Joint Tape / Fibrous / Homogeneous
None Detected Cellulose Binder
White / Joint Compound / NonFibrous / Homogeneous
None Detected None Detected Binder
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-05D 10%
5020-4224-06A
5020-4224-06B 10%
5020-4224-07A
5020-4224-07B
5020-4224-08A
5020-4224-08B
5020-4224-09A
5020-4224-09B
5020-4224-10A
Bldg. 39 – 5 Brown,White / Drywall / Fibrous /
Homogeneous None Detected Cellulose Binder
Bldg. 39 – 6 White / Compound / NonFibrous /
Homogeneous None Detected None Detected Binder
Brown,White / Drywall / Fibrous / Homogeneous
None Detected Cellulose Binder
Bldg. 39 – 7 Grey / Cove Base / NonFibrous /
Homogeneous None Detected None Detected Binder
Yellow / Mastic / NonFibrous / Homogeneous
None Detected None Detected Binder
Bldg. 39 – 8 Grey / Cove Base / NonFibrous /
Homogeneous None Detected None Detected Binder
Yellow / Mastic / NonFibrous / Homogeneous
None Detected None Detected Binder
Bldg. 39 – 9 Grey / Cove Base / NonFibrous /
Homogeneous None Detected None Detected Binder
Yellow / Mastic / NonFibrous / Homogeneous
None Detected None Detected Binder
Bldg. 39 – 10 Off White,Grey / 12x12 Floor Tile /
NonFibrous / Homogeneous
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-10B
5020-4224-11A
5020-4224-11B
5020-4224-12A
5020-4224-12B
5020-4224-13
5020-4224-14
5020-4224-15
5020-4224-16
5020-4224-17
Bldg. 39 – 10 Yellow / Mastic / NonFibrous /
Homogeneous None Detected None Detected Binder
Bldg. 39 – 11 Off White,Grey / 12x12 Floor Tile /
NonFibrous / Homogeneous None Detected None Detected Binder
Yellow / Mastic / NonFibrous / Homogeneous
None Detected None Detected Binder
Bldg. 39 – 12 Off White,Grey / 12x12 Floor Tile /
NonFibrous / Homogeneous None Detected None Detected Binder
Yellow / Mastic / NonFibrous / Homogeneous
None Detected None Detected Binder
Bldg. 39 – 13 White,Grey / Drywall Ceiling Tile /
Fibrous / Homogeneous None Detected
Cellulose Fibrous Glass
10% 2%
Binder
Bldg. 39 – 14 White,Grey / Drywall Ceiling Tile /
Fibrous / Homogeneous None Detected
Cellulose Fibrous Glass
10% 2%
Binder
Bldg. 39 – 15 White,Grey / Drywall Ceiling Tile /
Fibrous / Homogeneous None Detected
Cellulose Fibrous Glass
10% 2%
Binder
Bldg. 39 – 16 Grey / Plaster / NonFibrous /
Homogeneous None Detected None Detected Binder
Bldg. 39 – 17 Grey / Plaster / NonFibrous /
Homogeneous
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-18
5020-4224-19 3%
5020-4224-20 3%
5020-4224-21 3%
5020-4224-22
5020-4224-23
5020-4224-24
5020-4224-25
5020-4224-26
5020-4224-27
Bldg. 39 – 18 Grey / Plaster / NonFibrous /
Homogeneous None Detected None Detected Binder
Bldg. 39 – 19 Brown / Sink Coating / Fibrous /
Homogeneous Chrysotile None Detected Binder
Bldg. 39 – 20 Brown / Sink Coating / Fibrous /
Homogeneous Chrysotile None Detected Binder
Bldg. 39 – 21 Brown / Sink Coating / Fibrous /
Homogeneous Chrysotile None Detected Binder
Bldg. 39 – 22 Grey,Brown,Off White / Plaster /
NonFibrous / Homogeneous None Detected None Detected Binder
Bldg. 39 – 23 Grey,Brown,Off White / Plaster /
NonFibrous / Homogeneous None Detected None Detected Binder
Bldg. 39 – 24 Grey,Brown,Off White / Plaster /
NonFibrous / Homogeneous None Detected None Detected Binder
Bldg. 39 – 25 Off White / Insulation / Fibrous /
Homogeneous Chrysotile Amosite
20% 5%
None Detected Binder
Bldg. 39 – 26 Off White / Insulation / Fibrous /
Homogeneous Chrysotile Amosite
20% 5%
None Detected Binder
Bldg. 39 – 27 Red,Off White / Insulation / Fibrous /
Homogeneous Chrysotile Amosite
20% 5%
None Detected Binder
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-28 5%
5020-4224-29 70%
5020-4224-30 5%
5020-4224-31 3%
5020-4224-32 70%
5020-4224-33A 25%
5020-4224-33B 70%
5020-4224-34
5020-4224-35 5%
5020-4224-36
Bldg. 39 – 28 White / Insulation / Fibrous /
Homogeneous None Detected Synthetic Binder
Bldg. 39 – 29 Grey / Insulation / Fibrous / Homogeneous None Detected Fibrous Glass Binder
Bldg. 39 – 30 White / Insulation / Fibrous /
Homogeneous None Detected Synthetic Binder
Bldg. 39 – 31 White / Insulation / Fibrous /
Homogeneous None Detected Synthetic Binder
Bldg. 39 – 32 Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder
Bldg. 39 – 33 Yellow,Brown / Wrap / Fibrous /
Homogeneous None Detected Cellulose Binder
Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder
Bldg. 39 – 34 Light Grey,White / Insulation / Fibrous /
Homogeneous Amosite
Crocidolite 60% 5%
None Detected Binder
Bldg. 39 – 35 White / Insulation / Fibrous /
Homogeneous None Detected Synthetic Binder
Bldg. 39 – 36 Off White / Insulation / Fibrous /
Homogeneous Chrysotile Amosite
20%
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-37
5020-4224-38 70%
5020-4224-39
5020-4224-40A 10%
5020-4224-40B 5%
5020-4224-41 5%
5020-4224-42A 10%
5020-4224-42B 5%
5020-4224-43A 30%
5020-4224-43B 60%
Bldg. 39 – 37 White,Off White / Insulation / Fibrous /
Homogeneous None Detected
Cellulose Synthetic
10% 5%
Binder
Bldg. 39 – 38 Grey / Insulation / Fibrous / Homogeneous Chrysotile None Detected Binder
Bldg. 39 – 39 White,Grey / Insulation / Fibrous /
Homogeneous None Detected
Synthetic Fibrous Glass
5% 10%
Binder
Bldg. 39 – 40 Off White / Mastic Wrap / Fibrous /
Homogeneous None Detected Fibrous Glass Binder
White,Grey / Insulation / Fibrous / Homogeneous
None Detected Synthetic Binder
Bldg. 39 – 41 White / Insulation / Fibrous /
Homogeneous None Detected Synthetic Binder
Bldg. 39 – 42 Orange / Mastic Wrap / Fibrous /
Homogeneous None Detected Fibrous Glass Binder
White / Insulation / Fibrous / Homogeneous
None Detected Synthetic Binder
Bldg. 39 – 43 Orange / Wrap / Fibrous / Homogeneous None Detected Cellulose Binder
Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder
Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM
ENCON International 5020-4224
7307 Remcon Circle, Suite 100 September 15, 2020
El Paso, TX 79912 September 2, 2020
915-833-3740 September 10, 2020
Contact: Tim Jones 72 Hour
113-20 / VA Kansas – Leavenworth, Building #39
PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)
Report Number:
Report Date:
Samples Collected:
Date Received:
Turn-around time:
Job ID / Site:
Client Sample
Number
Lab Sample
Number
(by layer)
Color / Description / Fibrous /
NonFibrous / Homogeneity
Asbestos Content
Type & %
Non-Asbestos Fibrous
Type & % Matrix
5020-4224-44A
5020-4224-44B
Bldg. 39 – 44 Yellow / Wrap / Fibrous / Homogeneous None Detected None Detected Binder
White,Grey / Insulation / Fibrous / Homogeneous
Amosite Crocidolite
40%