This document summarizes an asbestos survey report for Building 39 at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The survey identified asbestos-containing materials in six locations within the building, including brown sink undercoating, white pipe insulation, white tank insulation, and gray insulation. A total of forty-four samples were collected and tested by an independent laboratory, with asbestos detected in samples from the identified areas. The report provides the sample locations, descriptions of materials sampled, and asbestos testing results. It concludes that the VA is responsible for properly managing all asbestos-containing materials and any future renovation or demolition activities that may disturb asbestos will require abatement by licensed contractors according to applicable regulations.

The related federal contract opportunity notice is for replacement of four antiquated water tube boilers and associated piping and support systems with three new energy efficient fire tube boilers at the Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The project also involves replacement of auxiliary systems in Building 39, fuel oil pump sets, condensate piping, deaerator and condensate return tanks, addition of a continuous blowdown heat recovery package, and asbestos abatement of all replaced piping. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center Austin seeking bids for a firm-fixed-price design-bid-build construction contract to complete the replacement project.

View the file

Other files for this federal contract opportunity

Other files attached to 36C77622B0029 - Replace Boilers - Leavenworth - Solicitation, newest first.
File Type Posted
36C77622B0029 0003.pdf PDF
Attachment 26 - RFIs - Technical Questions and Responses - REVISED.pdf PDF
Attachment 25 - Site Visit Attendance Sheet.pdf PDF
36C77622B0029 0002.pdf PDF
Attachment 22 - DDC for HVAC.pdf PDF
Attachment 23 - S-532 Drawing Sheet.pdf PDF
Attachment 24 - RFIs - Technical Questions and Responses.pdf PDF
36C77622B0029 0001.pdf PDF
Attachment 03 - Civil - Drawings.pdf PDF
Attachment 04 - Structural - Drawings.pdf PDF
Attachment 05 - Architectural - Drawings.pdf PDF
Attachment 10 - Electrical - Part 1 - Drawings.pdf PDF
36C77622B0029_1.pdf PDF
Attachment 06 - Fire Protection - Drawings.pdf PDF
Attachment 08 - Mechanical - Part 1 - Drawings.pdf PDF
Attachment 09 - Mechanical - Part 2 - Drawings.pdf PDF
Attachment 12 - Security - Drawings.pdf PDF
Attachment 02 - Hazardous Materials - Drawings.pdf PDF
Attachment 07 - Plumbing - Drawings.pdf PDF
Attachment 13 - Specifications - Volume 1.pdf PDF
Attachment 14 - Specifications - Volume 2.pdf PDF
Attachment 17 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 01 - General Information - Drawings.pdf PDF
Attachment 11 - Electrical - Part 2 - Drawings.pdf PDF
Attachment 15 - Specifications - Volume 3.pdf PDF
Attachment 16 - Boiler Plant - Drawing Sheet - M001.pdf PDF
Attachment 18 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 19 - Wage Rates - Leavenworth KS 5-21-2022.pdf PDF
Attachment 20 - VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMPREHENSIVE INTERIOR ASBESTOS SURVEY

VA Eastern Kansas Health Care System

Dwight D. Eisenhower VAMC

Building 39

Leavenworth, Kansas 66048

Prepared for:

Department of Veterans Affairs

Network Contracting Office (NCO) 15

3450 S. 4th Street Trafficway

Leavenworth, KS 66048

Prepared by:

ENCON TEAM

Inspection Start Date:

September 02, 2020

AXIOM Service Professionals

P.O. Box 47166

Kansas City, MO 64188

ENCON International, Inc.

7307 Remcon Circle, #103

El Paso, TX 79912

September 18, 2020

Ms. Linda Lawrence, CIH

Industrial Hygienist

Eastern Kansas Healthcare System

2200 SW Gage Blvd.

Topeka, KS 66622 Email: Linda.Lawrence3@va.gov

RE: Submittal of Comprehensive Interior Asbestos Surveys

Contract No. 36C25520P0345, Obligation No. 589C02185

Dwight D. Eisenhower VAMC, Leavenworth, KS - Bldg. #39

Dear Ms. Lawrence, This document summarizes the Asbestos Survey Report for the subject building. The below listed information was utilized to complete the Scope of Work Tasks:

Bldg. No. 39 POC: Linda Lawrence, CIH Phone No: 913-682-2000 ext.52254

Approximate Building Square Footage (SF) Reported by VA: 14,200 SF

ASBESTOS SUMMARY: A total of forty-four (44) bulk samples were effectively collected for lab analysis from this subject building. The attached analytical results indicated that asbestos containing materials were present in the subject building. Contact the Eastern Kansas Healthcare System, Dwight D. Eisenhower

VAMC regarding the latest overall status of any asbestos materials.

SUMMARY TABLE

Were

Found

Were Not

Found

Future Mgt.

Actions

Required?

Asbestos Containing Materials (>1 %) X Yes

Please contact ENCON with any technical questions, or follow-up needs that you may have.

Sincerely, Alex Woelper, P.E.

Sr. Project Manager

CC: Emilio Ballentos (Contract Specialist)

ATTACHMENTS:

Asbestos Survey Report mailto:Linda.Lawrence3@va.gov

COMPREHENSIVE INTERIOR ASBESTOS SURVEY

Dwight D. Eisenhower VAMC ─ Building 39

PURPOSE

ENCON International, Inc., (ENCON) was contracted by the Department of Veterans Affairs

Network Contracting Office (NCO) 15, to perform Comprehensive Interior Asbestos Building

Materials Surveys to identify the presence of any asbestos at a number of buildings at the Topeka and Leavenworth VA Complexes. This project also included the updating of the Asbestos

Management plans for each campus. The following buildings have been included within this contract scope of work for the Dwight D. Eisenhower VAMC: Buildings 28, 30, 31, 33, 36, 37, 39, 40, 41, 54, 55, 66, 71, 73, 77, 81, 89, 90, 91, 94, 95, 97, 110, 112, 113, 117, 122, 123, 140, 143, 149A, 149B, 155, 160, and 161A. The technical objective of this project was to gather information regarding any existing asbestos materials within the assigned buildings, by inspecting and sampling suspect asbestos materials. The overall purpose was to facilitate the VA’s ability to properly operate and maintain its buildings, in compliance with federal regulations, including

VHA Directive 7714 titled, “Asbestos Management Program,” which has been provided at

Attachment 3.

BACKGROUND

The VA has a number of buildings constructed before 1990 when the use of asbestos was prevalent in the construction of buildings. Because these materials still exist in some of these buildings, the

VA is required to identify, assess the condition (stable or deteriorating), determine the nature of building materials (i.e., drywall or floor tile), and the extent of asbestos materials. In accordance with the Clean Air Act (40 CFR 61 Subpart M, Asbestos), any renovation, remodeling or demolition of any structure, (i.e., buildings, facilities, etc.), shall be surveyed for asbestos-containing materials (ACMs) and properly abated prior to any disturbance of the material.

INTRODUCTION

The sixty-one (61) buildings selected for Inspection during this project were contractually provided to ENCON by the VA. The selected buildings were located in two (2) geographic areas:

Topeka Campus (26 buildings) and Leavenworth Campus (35 buildings). Partial records were available for some of these buildings where previous asbestos inspections had been performed.

When available, prior asbestos reports were referenced to enhance the thoroughness of the comprehensive interior asbestos inspections performed for these buildings. The goal of this project was to provide comprehensive interior inspections of the designated facilities, utilizing non-destructive sampling methods. Therefore, on rare occasion some ACMs may be hidden behind walls, under subfloors, or located in other areas that were inaccessible to the inspection personnel, per standard general AHERA sampling protocols. Therefore, there is a very remote chance that limited additional destructive sampling may be required, only if hidden suspect ACMs are found in the future.

REGULATORY STANDARDS

Asbestos in building materials is regulated on the federal level by the Environmental Protection

Agency (EPA), and the Occupational Safety and Health Administration (OSHA). On the state level, Kansas also has regulations pertaining to sampling and abatement of asbestos in buildings.

The inspection was conducted to ensure compliance with National Emission Standards for

Hazardous Air Pollutants (NESHAP) – 40 CFR Part 61, Subpart M, which states that “prior to the commencement of the demolition or renovation, thoroughly inspect the affected facility or part of the facility where the demolition or renovation operation(s) will occur for the presence of asbestos, including Category I and Category II non-friable ACM.” Regulated asbestos containing materials have been designated as RACM. All Asbestos Inspectors were trained under the EPA AHERA

(40 CFR 763) standards. These facilities were sampled under the applicable regulations from the

EPA, 40 CFR 61, and sampling protocols were generally based on EPA AHERA standards, per

EPA 40 CFR 763.86, and in compliance with VHA Directive 7714.

FACILITY DESCRIPTION

Building 39 was constructed in 1886, and was in use at the time of inspection. Its previous use was listed as a “Boiler Plant.” A summary description of this building is presented in Table 1 below.

TABLE 1 – BUILDING DESCRIPTION

Building Items Description

Area of building 14,200 square feet

Date of Construction 1886

Number of floors One (1) floor

Exterior wall materials Brick, rock

Interior walls Plaster, drywall

Interior floors Concrete

Interior floor coverings 12x12 vinyl floor tiles

Ceilings 2x2 lay-in ceiling tiles, 2x4 lay-in ceiling tiles, wood

Notes: None

The main function or purpose, of this facility was identified as follows:

“Boiler Plant.”

HOMOGENEOUS AREAS

Within the facility homogeneous areas were determined. Homogeneous areas are defined as areas of suspect asbestos containing materials including surfacing materials, thermal system insulation

(TSI), or miscellaneous materials that were uniform in color, texture, substrate, and were relatively of the same age. Table 2 below lists the homogeneous areas and the general locations where they were identified.

TABLE 2 - Homogeneous Areas and Locations Identified

Homogeneous Areas

(Suspect Materials) Location

1 2x2 Lay-In Ceiling Tiles (Fissures / Small Pinholes) Employee Breakroom, Lounge, Office

2 Textured Drywall / Joint Compound (Walls) Employee Breakroom, Lounge, Office

3 Vinyl Cove Base (Grey) / Mastic Employee Breakroom, Lounge, Office

4 12x12 Vinyl Floor Tiles (Almond w/Grey) / Mastic Employee Breakroom, Lounge, Office

5 2x4 Lay-In Ceiling Tiles (Smooth) Locker Room Storage

6 Textured Plaster (Walls) Locker Room & Locker Room Storage

7 Sink Undercoating (Brown) Water Treatment Station

8 Plaster (Walls) Maintenance Supply Storage

9 Pipe Insulation (White) Boiler Room (Boiler Oil Supply System)

10 Pipe Insulation (White) Boiler Room & Auxiliary Generator

Room (Atomizing Steam System)

11 Pipe Insulation (White) Boiler Room & Auxiliary Generator

Room (Main Steam Supply System)

12 Pipe Insulation (White) Boiler Room & Auxiliary Generator

Room (Boiler H20 Supply System)

13 Pipe Insulation (White) Boiler Room (Breeching / Exhaust)

14 Tank Insulation (White) Unexcavated Room at Tanks

SAMPLING METHODOLOGY

The building materials survey tasks were performed in accordance with the EPA NESHAPs and/or

AHERA Regulations. An initial visual inspection of the building was conducted to develop a sampling strategy. This task included determining homogeneous areas / materials, and sample collection locations. Friability was assessed by manually manipulating the suspect asbestos materials utilizing hand pressure to determine if the materials, when dry, could be crumbled, pulverized, or reduced to powder. Fourteen (14) homogeneous areas were established and at least three (3) samples were collected from each area to adequately identify accessible asbestos in the building. Portions of the subject building that had suspect asbestos-containing surfacing, thermal system insulation, or miscellaneous materials were divided into homogeneous areas for sampling.

These samples were each uniquely and individually identified and logged into a chain of custody document and prepared for shipment to a third-party, independent laboratory for analysis. Building materials that were not considered suspect ACM included the following: concrete, metal, glass, and wood. As is commonly practiced, destructive sampling was not authorized or performed to locate hidden or inaccessible materials.

Forty-four (44) suspect ACM samples were collected and submitted for laboratory analysis. Refer to Appendix A for Asbestos sample location drawing(s). Bulk sample analyses were conducted utilizing polarized light microscopy (PLM), as per EPA Test Method 600/R-93/116. This method separates the sample material into various layers based on their morphology, and then identifies the presence of the different asbestos fibers in each of these layers when detected. The laboratory testing was performed by Apex Precision Analytical Services, Inc., located in Friendswood, TX.

Asbestos-Containing Material is defined as a material that contains greater than 1% of any asbestos type including Chrysotile, Amosite, Crocidolite, Tremolite, Anthophyllite, and Actinolite, or combinations of these materials. Asbestos materials are typically determined as recommended in the July 1993 EPA/600/R-93/116 document titled, "Method for the Determination of Asbestos in

Bulk Building Materials." Copies of the asbestos laboratory test results and related laboratory documentation have been provided in Appendix B of this Report.

LABORATORY ANALYSIS

The sample collection and subsequent laboratory analysis indicated that asbestos was identified in the building, as per Table 3 as follows. The NESHAPs definitions were used to define the condition of ACMs, per 40 CFR 61, Subpart M.

The asbestos quantities provided in the prior Table 3 are rough estimates only and must be field verified by any future abatement contractors.

TABLE 3 – Identified Asbestos Containing Materials (> 1%) Condition

Sample No.

Asbestos Containing

Materials

Approx.

Qty.

Location

F ri ab il it y

C at eg o ry

D am ag e

19-21 Sink Undercoating (Brown) ~4 SF Water Treatment Station NF I G

25-27 Pipe Insulation (White) ~90 LF Boiler Room (Boiler Oil Supply System) F - G

32-33 Pipe Insulation (White)

~350 LF

Boiler Room & Auxiliary Generator

Room (Main Steam Supply System) F - D

34, 36 Pipe Insulation (White)

~717 LF

Boiler Room & Auxiliary Generator

Room (Boiler H20 Supply System) F - G

38 Pipe Insulation (White) ~2,800 SF Boiler Room (Breeching / Exhaust) F - G

43-44 Tank Insulation (White) ~180 SF Unexcavated Room at Tanks F - G

*Friability: (F) – Friable; (NF) – Non-Friable

**Category: (I) – Category I; (II) – Category II

***Damage Condition: (G) – Good; (D) – Damaged; (SD) – Significantly Damaged

QUALIFICATIONS

This Comprehensive Interior Asbestos Survey was performed by ENCON Team Sr. Field

Inspectors Kody Tramm, and Glenn Robinson on September 02, 2020, and was conducted in accordance with the EPA National Emission Standards for Hazardous Air Pollutants (NESHAP):

40 CFR Part 61, Subpart M. Sampling protocols were performed in general accordance with

AHERA. The Inspectors had received training under the AHERA required Asbestos Inspector

Course and had received annual refresher training within the past year.

LIMITATIONS

The overall purpose of this Comprehensive Interior Asbestos Survey was to identify if ACM was present, within the qualifications and limitations summarized below. Reliance on this report is specifically limited to gathering initial information regarding the presence of asbestos in building materials. Any time that ACMs may be identified during the performance of an asbestos survey, the owner of the building is responsible to the occupants and to the public to manage these materials properly, per Local, State and Federal regulations. Prior to the abatement or removal of any ACMs, an asbestos project design should be properly created, by a qualified asbestos consulting firm, 1) to ensure that materials will be properly managed, and 2) to prepare a more accurate estimate of materials to be abated. This Survey Report was specifically prepared for the

Department of Veterans Affairs Network Contracting Office (NCO) 15, and the extent of liability incurred by the ENCON Team, is limited to the amount of the report fee paid by its Client. The

VA agrees that the ENCON Team cannot be held responsible for any liability based on reliance of this report by any third party for any business reasons.

CONCLUSIONS

1. The survey for the subject building was successfully completed, as required, per State and

Federal environmental standards. Refer to Table 1 for building details.

2. Suspect ACMs were potentially identified in fourteen (14) homogeneous areas at the subject building. Refer to Table 2 for a listing of homogeneous areas.

3. A total of forty-four (44) suspect ACM samples were collected from the building interior, and were properly analyzed by an independent, qualified third-party laboratory. Refer to

Appendix A for details regarding all sample locations.

4. A review of the laboratory test results indicated that ACMs were identified at the subject building. Refer to Table 3 for a confirmation listing of any identified ACMs.

5. Some ACMs were confirmed in six (6) homogeneous areas at the subject building. Refer to Appendix A and Appendix B for details regarding sample locations and descriptions.

6. The VA is responsible for properly managing all materials at the subject building.

7. Prior to any future renovation or demolition activities, asbestos related abatement activities will need to be performed by properly licensed personnel. Any ACMs should not be disturbed by unlicensed and / or untrained personnel.

8. Proper 10-day advance NESHAP notification should be made to the appropriate authorities prior to disturbance of any ACMs. Such disturbance includes abatement activities, building renovations, routine operation & maintenance activities, or any planned demolition in facilities or public buildings.

9. If disturbance of ACMs is anticipated, then these materials should be properly removed in advance of disturbance by licensed and trained personnel, as required by State and Federal regulations.

10. Abatement activities should be performed by a licensed Asbestos Abatement Contractor, with project management and air monitoring support by an experienced, certified Asbestos

Consulting Firm.

Future Contingent Requirements: The following additional requirements would need to be followed, only if additional hidden ACMs are identified through future destructive sampling activities.

1. In the unlikely event that additional “hidden suspect ACMs” are encountered during any future renovation or demolition activities, further limited sampling and lab analysis would be required. VA asbestos and / or safety personnel should be notified immediately for public safety and environmental compliance actions to properly manage any confirmed additional ACMs.

2. If disturbance of any newly identified ACMs is required in the future, then these materials should also be properly removed in advance of disturbance by licensed and trained personnel, as required by State and Federal regulations.

3. Any future abatement activities of previously hidden ACMs would also need to be performed by a licensed Asbestos Abatement Contractor, with project management and air monitoring support by an experienced, certified Asbestos Consulting Firm.

ATTACHMENTS

Refer to a copy of personnel certifications and VA document VHA Directive 7714 titled, “Asbestos Management Program," at Attachment 2 and Attachment 3, respectively. Additionally, a copy of the facilities’ Asbestos Management Plan has been provided at Attachment 4. Contact the personnel listed below with any clarifications that may be needed.

Inspected by:

Kody Tramm

Lead Asbestos Inspector AXIOM Service Professionals

Reviewed by:

Rosie Jimenez

Project Coordinator

Approved by:

Alex Woelper, P.E.

Sr. Project Manager

APPENDICES:

A. Asbestos Sample Location Drawing(s)

B. Laboratory Documentation

APPENDIX A

Asbestos Sample Location Drawing(s)

Draw by:

JA

7307 Remcon Cir, Ste 103

El Paso, Texas, 79912 915.833.3740

Sheet

ENV-1

ENCON

INTERNATIONAL, INC

NOT TO SCALE

Positive Asbestos Sample Locations

Asbestos Sample Location Drawing - Floor Plan ( Approx. 4,375 SF )

## Asbestos Sample Locations

Project:

# 113-20

EASTERN KANSAS VA

Asbestos Survey

Location:

Building # 39

Total Bldg. Area = 14,200 SF

Leavenworth, KS Date: 09-18-2020

Built (1886)

AW

Break Rm.

Lounge

13 - 15

16 - 18

19 - 21

25 - 27

Draw by:

JA

7307 Remcon Cir, Ste 103

El Paso, Texas, 79912 915.833.3740

Sheet

ENV-1

ENCON

INTERNATIONAL, INC

NOT TO SCALE

Project:

# 113-20

EASTERN KANSAS VA

Asbestos Survey

Location:

Building # 39

Total Bldg. Area = 14,200 SF

Leavenworth, KS Date: 09-18-2020

Built (1886)

AW

Pipe Insulation

Asbestos Homogeneous Areas - Floor Plan ( Approx. 4,375 SF )

Asbestos Homogeneous Areas

Tank Insulation

Sink Undercoating ( Brown )

APPENDIX B

Laboratory Documentation

ASBESTOS BULK ANALYSIS REPORT

September 15, 2020

ENCON International

5020-4224

Date:

Report:

113-20 / VA Kansas – Leavenworth, Building #39

This document shall be considered a duly signed original report of the results obtained from the analysis(es) performed. All analyses are done within government guidelines and regulations.

Gary R. Simmons Laboratory Manager

Lab Comments on Project: N/A

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-01

5020-4224-02

5020-4224-03

5020-4224-04A

5020-4224-04B 95%

5020-4224-04C

5020-4224-04D 10%

5020-4224-05A

5020-4224-05B 95%

5020-4224-05C

Bldg. 39 – 1 White,Grey / 2x2 Ceiling Tile / Fibrous /

Homogeneous None Detected

Cellulose Fibrous Glass

45% 5%

Binder

Bldg. 39 – 2 White,Grey / 2x2 Ceiling Tile / Fibrous /

Homogeneous None Detected

Cellulose Fibrous Glass

45% 5%

Binder

Bldg. 39 – 3 White,Grey / 2x2 Ceiling Tile / Fibrous /

Homogeneous None Detected

Cellulose Fibrous Glass

45% 5%

Binder

Bldg. 39 – 4 White / Texture / NonFibrous /

Homogeneous None Detected None Detected Binder

Off White / Joint Tape / Fibrous / Homogeneous

None Detected Cellulose Binder

White / Joint Compound / NonFibrous / Homogeneous

None Detected None Detected Binder

Brown,White / Drywall / Fibrous / Homogeneous

None Detected Cellulose Binder

Bldg. 39 – 5 White / Texture / NonFibrous /

Homogeneous None Detected None Detected Binder

Off White / Joint Tape / Fibrous / Homogeneous

None Detected Cellulose Binder

White / Joint Compound / NonFibrous / Homogeneous

None Detected None Detected Binder

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-05D 10%

5020-4224-06A

5020-4224-06B 10%

5020-4224-07A

5020-4224-07B

5020-4224-08A

5020-4224-08B

5020-4224-09A

5020-4224-09B

5020-4224-10A

Bldg. 39 – 5 Brown,White / Drywall / Fibrous /

Homogeneous None Detected Cellulose Binder

Bldg. 39 – 6 White / Compound / NonFibrous /

Homogeneous None Detected None Detected Binder

Brown,White / Drywall / Fibrous / Homogeneous

None Detected Cellulose Binder

Bldg. 39 – 7 Grey / Cove Base / NonFibrous /

Homogeneous None Detected None Detected Binder

Yellow / Mastic / NonFibrous / Homogeneous

None Detected None Detected Binder

Bldg. 39 – 8 Grey / Cove Base / NonFibrous /

Homogeneous None Detected None Detected Binder

Yellow / Mastic / NonFibrous / Homogeneous

None Detected None Detected Binder

Bldg. 39 – 9 Grey / Cove Base / NonFibrous /

Homogeneous None Detected None Detected Binder

Yellow / Mastic / NonFibrous / Homogeneous

None Detected None Detected Binder

Bldg. 39 – 10 Off White,Grey / 12x12 Floor Tile /

NonFibrous / Homogeneous

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-10B

5020-4224-11A

5020-4224-11B

5020-4224-12A

5020-4224-12B

5020-4224-13

5020-4224-14

5020-4224-15

5020-4224-16

5020-4224-17

Bldg. 39 – 10 Yellow / Mastic / NonFibrous /

Homogeneous None Detected None Detected Binder

Bldg. 39 – 11 Off White,Grey / 12x12 Floor Tile /

NonFibrous / Homogeneous None Detected None Detected Binder

Yellow / Mastic / NonFibrous / Homogeneous

None Detected None Detected Binder

Bldg. 39 – 12 Off White,Grey / 12x12 Floor Tile /

NonFibrous / Homogeneous None Detected None Detected Binder

Yellow / Mastic / NonFibrous / Homogeneous

None Detected None Detected Binder

Bldg. 39 – 13 White,Grey / Drywall Ceiling Tile /

Fibrous / Homogeneous None Detected

Cellulose Fibrous Glass

10% 2%

Binder

Bldg. 39 – 14 White,Grey / Drywall Ceiling Tile /

Fibrous / Homogeneous None Detected

Cellulose Fibrous Glass

10% 2%

Binder

Bldg. 39 – 15 White,Grey / Drywall Ceiling Tile /

Fibrous / Homogeneous None Detected

Cellulose Fibrous Glass

10% 2%

Binder

Bldg. 39 – 16 Grey / Plaster / NonFibrous /

Homogeneous None Detected None Detected Binder

Bldg. 39 – 17 Grey / Plaster / NonFibrous /

Homogeneous

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-18

5020-4224-19 3%

5020-4224-20 3%

5020-4224-21 3%

5020-4224-22

5020-4224-23

5020-4224-24

5020-4224-25

5020-4224-26

5020-4224-27

Bldg. 39 – 18 Grey / Plaster / NonFibrous /

Homogeneous None Detected None Detected Binder

Bldg. 39 – 19 Brown / Sink Coating / Fibrous /

Homogeneous Chrysotile None Detected Binder

Bldg. 39 – 20 Brown / Sink Coating / Fibrous /

Homogeneous Chrysotile None Detected Binder

Bldg. 39 – 21 Brown / Sink Coating / Fibrous /

Homogeneous Chrysotile None Detected Binder

Bldg. 39 – 22 Grey,Brown,Off White / Plaster /

NonFibrous / Homogeneous None Detected None Detected Binder

Bldg. 39 – 23 Grey,Brown,Off White / Plaster /

NonFibrous / Homogeneous None Detected None Detected Binder

Bldg. 39 – 24 Grey,Brown,Off White / Plaster /

NonFibrous / Homogeneous None Detected None Detected Binder

Bldg. 39 – 25 Off White / Insulation / Fibrous /

Homogeneous Chrysotile Amosite

20% 5%

None Detected Binder

Bldg. 39 – 26 Off White / Insulation / Fibrous /

Homogeneous Chrysotile Amosite

20% 5%

None Detected Binder

Bldg. 39 – 27 Red,Off White / Insulation / Fibrous /

Homogeneous Chrysotile Amosite

20% 5%

None Detected Binder

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-28 5%

5020-4224-29 70%

5020-4224-30 5%

5020-4224-31 3%

5020-4224-32 70%

5020-4224-33A 25%

5020-4224-33B 70%

5020-4224-34

5020-4224-35 5%

5020-4224-36

Bldg. 39 – 28 White / Insulation / Fibrous /

Homogeneous None Detected Synthetic Binder

Bldg. 39 – 29 Grey / Insulation / Fibrous / Homogeneous None Detected Fibrous Glass Binder

Bldg. 39 – 30 White / Insulation / Fibrous /

Homogeneous None Detected Synthetic Binder

Bldg. 39 – 31 White / Insulation / Fibrous /

Homogeneous None Detected Synthetic Binder

Bldg. 39 – 32 Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder

Bldg. 39 – 33 Yellow,Brown / Wrap / Fibrous /

Homogeneous None Detected Cellulose Binder

Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder

Bldg. 39 – 34 Light Grey,White / Insulation / Fibrous /

Homogeneous Amosite

Crocidolite 60% 5%

None Detected Binder

Bldg. 39 – 35 White / Insulation / Fibrous /

Homogeneous None Detected Synthetic Binder

Bldg. 39 – 36 Off White / Insulation / Fibrous /

Homogeneous Chrysotile Amosite

20%

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-37

5020-4224-38 70%

5020-4224-39

5020-4224-40A 10%

5020-4224-40B 5%

5020-4224-41 5%

5020-4224-42A 10%

5020-4224-42B 5%

5020-4224-43A 30%

5020-4224-43B 60%

Bldg. 39 – 37 White,Off White / Insulation / Fibrous /

Homogeneous None Detected

Cellulose Synthetic

10% 5%

Binder

Bldg. 39 – 38 Grey / Insulation / Fibrous / Homogeneous Chrysotile None Detected Binder

Bldg. 39 – 39 White,Grey / Insulation / Fibrous /

Homogeneous None Detected

Synthetic Fibrous Glass

5% 10%

Binder

Bldg. 39 – 40 Off White / Mastic Wrap / Fibrous /

Homogeneous None Detected Fibrous Glass Binder

White,Grey / Insulation / Fibrous / Homogeneous

None Detected Synthetic Binder

Bldg. 39 – 41 White / Insulation / Fibrous /

Homogeneous None Detected Synthetic Binder

Bldg. 39 – 42 Orange / Mastic Wrap / Fibrous /

Homogeneous None Detected Fibrous Glass Binder

White / Insulation / Fibrous / Homogeneous

None Detected Synthetic Binder

Bldg. 39 – 43 Orange / Wrap / Fibrous / Homogeneous None Detected Cellulose Binder

Grey / Insulation / Fibrous / Homogeneous Amosite None Detected Binder

Analytical results and reports are generated by Apex Precision Analytical Services at the request of and for the exclusive use of the person or entity (client) named on such report. Result, reports or copies of same will not be released by Apex Precision Analytical Services to any third party without the written request from client. These results only repesent the materials submitted. Supporting laboratory documentation is available upon request. This report cannot be used to represent conditions at any other location, date or time and does not imply that this space is free from these or any other contaminants. No responsibility or liability is assumed for the manner in which these results are used or interpreted. This must not be used to claim product endorsement by NVLAP or any government agency of the United States. Apex Precision Analytical Services reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.

NVLAP Lab Code: 200633-0 PLM TDSHS Asbestos License#: 30-0312 PLM/PCM

ENCON International 5020-4224

7307 Remcon Circle, Suite 100 September 15, 2020

El Paso, TX 79912 September 2, 2020

915-833-3740 September 10, 2020

Contact: Tim Jones 72 Hour

113-20 / VA Kansas – Leavenworth, Building #39

PLM (Bulk) - Asbestos Analysis Report - Visual ID (EPA Method 600/R-93-116 Visual Area Estimation)

Report Number:

Report Date:

Samples Collected:

Date Received:

Turn-around time:

Job ID / Site:

Client Sample

Number

Lab Sample

Number

(by layer)

Color / Description / Fibrous /

NonFibrous / Homogeneity

Asbestos Content

Type & %

Non-Asbestos Fibrous

Type & % Matrix

5020-4224-44A

5020-4224-44B

Bldg. 39 – 44 Yellow / Wrap / Fibrous / Homogeneous None Detected None Detected Binder

White,Grey / Insulation / Fibrous / Homogeneous

Amosite Crocidolite

40%

Bldg. No.39.pdf
Sheets and Views
Bldg. No.39-Model
Bldg. No.39 Hom.pdf
Sheets and Views
Bldg. No.39-Model

File details come from the government source that posted it. Updated .