This document contains a Failure Modes and Effects Criticality Analysis (FMECA) for the blower assembly component of an emergency operations center (EOC) shelter.
The FMECA identifies six potential failure modes for the blower assembly: binding/sticking, inoperative, improper output, will not engage, and no current. It analyzes the effects of each failure mode at the component, equipment, and system level. Though failures could potentially result in hazardous carbon monoxide accumulation, several compensating provisions make this an extremely remote risk, including non-occupancy of the shelter, status indicators, and pre-use testing. The document recommends maintaining a Severity Classification of II. It evaluates potential design modifications to further reduce risk.
The related federal contract opportunity is a draft request for proposal for low-rate initial production and full-rate production of the Integrated Battle Command System hardware. It involves maintaining approved updates and authority to operate on existing hardware, as well as engineering changes, for an Army Materiel Command requirement. Vendors are not to submit proposals in response to the draft RFP.
View the file
Other files for this federal contract opportunity
Show all 50
DRAFT RFP for Integrated Battle Command System (IBCS) LRIP/FRP has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet2
| Row Labels | Sum of Cm | Count of Failure Mode Description |
| Binding/Sticking | 1.08E-04 | 1 |
| Improper Output | 1.08E-04 | 1 |
| Inoperative | 4.31E-04 | 2 |
| No Current | 1.08E-04 | 1 |
| Will Not Engage | 1.08E-04 | 1 |
| Grand Total | 8.61E-04 | 6 |
Prelim Analysis
| PRELIMINARY ANALYSIS: | Major End Item: | Shelter - ECU | |||
| Parent LRU: | E005-Blower Assembly | ||||
| Component: | Blower (Not Critical) | ||||
| Mission Phase-Operational Mode: | All Phases | ||||
| Cr = ∑Cm = | 8.61E-04 | ||||
| Failure Modes | Count of | ||||
| Failure Modes | Severity | ||||
| Classifications | Count of |
Seveverity Classification Failure Modes Sum of Cm Count of Failure Modes
| Inoperative | 2 | 33.33% | Category II | 6 | Inoperative | 4.31E-04 | 2 |
| Binding/Sticking | 1 | 16.67% | Inoperative | 2 | Binding/Sticking | 1.08E-04 | 1 |
| Improper Output | 1 | 16.67% | Binding/Sticking | 1 | Improper Output | 1.08E-04 | 1 |
| No Current | 1 | 16.67% | Improper Output | 1 | No Current | 1.08E-04 | 1 |
| Will Not Engage | 1 | 16.67% | No Current | 1 | Will Not Engage | 1.08E-04 | 1 |
| Grand Total | 6 | Will Not Engage | 1 | Grand Total | 8.61E-04 | 6 | |
| Grand Total | 6 |
Cat I and II
| Major End Item: | Shelter - ECU | ||||||||||||
| Parent LRU: | E005-Blower Assembly | ||||||||||||
| Componet: | Blower (Not Critical) | ||||||||||||
| Mission Phase-Operational Mode: | All Phases | ||||||||||||
| FPMH: | 35.9454 | ||||||||||||
| t: | 72 | ||||||||||||
| Cr = ∑Cm = | 8.61E-04 | ||||||||||||
| Modified Cr = | 1.73E-04 | (Redundancy) | |||||||||||
| Due to the remote chance of hazard levels CO the Severity Classifications will remain at Severity Classification II | |||||||||||||
| Failure Effect at | Failure Detection Method | Compemsating Provisions | |||||||||||
| ID# | Function | Failure Mode Description | Failure Cause | Local Failure Effects | Next Higher Level Failure Effects | Major End Item Failure Effects | Safety Consideration | Safety Impact | Operator Observation | Visual Indicator | C-Bit | ||
| Capabilities | Severity | ||||||||||||
| Classification | Alternate Design | ||||||||||||
| Modifications | Modified Severity | ||||||||||||
| Classification | β | βmod | α | λP | Cm | Mod Cm | |||||||
| 85 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Binding/Sticking | Hardware Failure | Probable loss of vent fan | Probable loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
| 4) TM provides check of Vent Fan before each field installation | Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration | OB-370-50 | N/A | TBD | Category II | EOCs are Redundant | Category III-2R | 0.50 | 0.05 | 0.1667 | 3.59E-05 | 1.08E-04 | 2.16E-05 |
| 86 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Inoperative | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
| 4) TM provides check of Vent Fan before each field installation | Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration | OB-370-50 | N/A | TBD | Category II | EOCs are Redundant | Category III-2R | 0.50 | 0.05 | 0.3333 | 3.59E-05 | 2.15E-04 | 4.31E-05 |
| 87 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Improper Output | Hardware Failure | Probable loss of vent fan | Probable loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
| 4) TM provides check of Vent Fan before each field installation | Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration | OB-370-50 | N/A | TBD | Category II | EOCs are Redundant | Category III-2R | 0.50 | 0.05 | 0.1667 | 3.59E-05 | 1.08E-04 | 2.16E-05 |
| 88 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Inoperative | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
| 4) TM provides check of Vent Fan before each field installation | Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration | OB-370-50 | N/A | TBD | Category II | EOCs are Redundant | Category III-2R | 0.50 | 0.05 | 0.3333 | 3.59E-05 | 2.15E-04 | 4.31E-05 |
| 89 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Will Not Engage | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
| 4) TM provides check of Vent Fan before each field installation | Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration | OB-370-50 | N/A | TBD | Category II | EOCs are Redundant | Category III-2R | 0.50 | 0.05 | 0.1667 | 3.59E-05 | 1.08E-04 | 2.16E-05 |
| 90 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | No Current | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 N/A TBD Category II EOCs are Redundant Category III-2R 0.50 0.05 0.1667 3.59E-05 1.08E-04 2.16E-05
E005 Data
| Major End Item: | Shelter - ECU | ||||||||||||
| Parent LRU: | E005-Blower Assembly | ||||||||||||
| Componet: | Blower (Not Critical) | ||||||||||||
| Mission Phase-Operational Mode: | All Phases | ||||||||||||
| FPMH: | 35.9454 | ||||||||||||
| t: | 72 | ||||||||||||
| Cr = ∑Cm = | 1.72E-03 | ||||||||||||
| Modified Cr = | 1.73E-04 | (Redundancy) | |||||||||||
| Due to the remote chance of hazard levels CO the Severity Classifications will remain at Severity Classification II | |||||||||||||
| Failure Effect at | Failure Detection Methd | Compemsating Provisions | |||||||||||
| ID# | Function | Failure Mode Description | Failure Cause | Local Failure Effects | Next Higher Level Failure Effects | Major End Item Failure Effects | Safety Consideration | Safety Impact | Operator Observation | Visual Indicator | C-Bit | ||
| Capabilities | Severity | ||||||||||||
| Classification | Alternate Design | ||||||||||||
| Modifications | Modified Severity | ||||||||||||
| Classification | β | βmod | α | λP | Cm | Mod Cm | |||||||
| 85 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Binding/Sticking | Hardware Failure | Probable loss of vent fan | Probable loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and
| Light Indication | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.1667 | 3.59E-05 | 2.15E-04 | 2.16E-05 |
| 86 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Inoperative | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and
| Light Indication | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3333 | 3.59E-05 | 4.31E-04 | 4.31E-05 |
| 87 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Improper Output | Hardware Failure | Probable loss of vent fan | Probable loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and
| Light Indication | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.1667 | 3.59E-05 | 2.15E-04 | 2.16E-05 |
| 88 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Inoperative | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and
| Light Indication | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.3333 | 3.59E-05 | 4.31E-04 | 4.31E-05 |
| 89 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | Will Not Engage | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and
| Light Indication | N/A | TBD | Category I | EOCs are Redundant | Category III-1R | 1.00 | 0.05 | 0.1667 | 3.59E-05 | 2.15E-04 | 2.16E-05 |
| 90 | The vent fan draws outside filtered air into the shelter through the blower door at a rate of 60 Cubic Feet Per Minute (CFM). Note that the shelter is not typically occupied. | No Current | Hardware Failure | Loss of vent fan | Loss of shelter fresh air supply | Possible personnel illness/death due to high CO concentration (note that EOC Shelter is typically not occupied) | Extremely Remote. |
1) Shelter is not typically occupied,
2) LED light on PDP provides indication of Vent Fan Operation,
3) CO Monitor provides annunciation of high CO levels,
4) TM provides check of Vent Fan before each field installation Ventilation Hardware Malfunction: Possible Hazardous Carbon Monoxide Concentration OB-370-50 and Light Indication N/A TBD Category I EOCs are Redundant Category III-1R 1.00 0.05 0.1667 3.59E-05 2.15E-04 2.16E-05