The file's text, extracted by GovTribe without its formatting.
Rack 1 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Nominal Max Watts | Nominal Max Amps |
| DC POWER | | | | | | | | | | | |
| Voice | CAU-V | CLASSIFIED | D | 20.0 | 20.0 | 0.8 | 20.0 | 1552.0 | 62.1 | 1316.8 | 52.7 |
| Voice | eMCSU (TOCNET) | CLASSIFIED | M*** | 10.9 | 12.0 | 0.8 | 11.8 | | | | |
| Radios | GMR500 | CLASSIFIED | D | 14.0 | 14.0 | 0.8 | 11.2 | | | | |
| Radios | KGV-72 | CLASSIFIED | D | 15.0 | 15.0 | 0.8 | 12.0 | | | | |
| IFCN | KG-250X | CLASSIFIED | D | 19.0 | 19.0 | 0.8 | 15.2 | | | | |
| Timing | Time Server | CLASSIFIED | O | 50.0 | 80.0 | 0.8 | 74.0 | | | | |
| IFCN | IGRM | CLASSIFIED | D | 60.0 | 60.0 | 0.8 | 48.0 | | | | |
| IFCN | BPU | CLASSIFIED | D | 185.0 | 185.0 | 0.8 | 148.0 | | | | |
| IFCN | SCIM | CLASSIFIED | D | 132.0 | 132.0 | 0.8 | 105.6 | | | | |
| Radios | JBCP Processor & Radio | CLASSIFIED | D | 65.0 | 65.0 | 0.8 | 52.0 | | | | |
| Radios | MIDS* LVT-11 Radio (AN/USQ-140(v)2c) | CLASSIFIED | D | 295.0 | 950.0 | 0.8 | 819.0 | | | | |
| NOTE: DC LOADS ARE POWERED BY THE AC SUBSYSYSTEMS IN THIS RACK (POL-PSU) | | | | | | | | | | | |
| AC POWER | | | | | | | | | | | |
| PU, Sec. | CONSOLE KVM | CLASSIFIED | D | 60.0 | 60.0 | 0.8 | 48.0 | 2333.9 | 21.2 | 2015.0 | 18.3 |
| PU, Sec. | KVM SWITCH 01 (Lower) | CLASSIFIED | D | 130.0 | 130.0 | 0.8 | 104.0 | | | | |
| Radios | PIF Cable (MIDS) | CLASSIFIED | D | 18.0 | 18.0 | 0.8 | 14.4 | | | | |
| Lighting | 6x LED Blackout/White Lights | UNCLASS | D | 300.0 | 300.0 | 1.0 | 300.0 | | | | |
| DC PSU | DC PSU load to AC system (@85% eff) | CLASSIFIED | D | 1018.7 | 1825.9 | 1.2 | 1548.6 | | | | |
| *Nominal DC voltage design is 25VDC to comply with MIL-STD-1275D's S-S allowable voltage of 25-30 VDC. |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral |
| ***Nominal Watts (and current) is calculated by Min+DC*(Max-Min) for devices where min/max are not the same |
| CONSTANTS |
| Min Nominal DC Volts: |
| 25 |
| Min Nominal AC Volts: |
| 110 |
Rack 2 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Design Max Watts | Design Max Amps |
| DC POWER | | | | | | | | | | | |
| Radios | RF-300M-V250(1) (2x AN/PRC-117G) | CLASSIFIED | D | 600.0 | 600.0 | 0.5 | 480.0 | 2107.2 | 84.3 | 1685.8 | 67.4 |
| Radios | RF-300M-V250(1) (2x AN/PRC-117G) | CLASSIFIED | D | 600.0 | 600.0 | 0.5 | 480.0 | | | | |
| Radios | TACLINK 3100 | CLASSIFIED | D | 4.0 | 4.0 | 0.8 | 3.2 | | | | |
| Radios | JTT-IBX* p/o AN/URC-145 (V)1 | CLASSIFIED | D | 201.6 | 201.6 | 0.8 | 161.3 | | | | |
| Radios | JTT-EPA* p/o AN/URC-145 (V)1 | CLASSIFIED | D | 504.0 | 504.0 | 0.8 | 403.2 | | | | |
| Radios | JTT-IBX* p/o AN/URC-145 (V)1 | CLASSIFIED | D | 201.6 | 201.6 | 0.8 | 161.3 | | | | |
| NOTE: DC LOADS ARE POWERED BY THE AC SUBSYSYSTEMS IN THIS RACK (POL-PSU) | | | | | | | | | | | |
| AC POWER | | | | | | | | | | | |
| MDP | NET GUARDIAN 16A | CLASSIFIED | D | 20.0 | 20.0 | 0.8 | 16.0 | 2503.8 | 22.8 | 2003.0 | 18.2 |
| DC PSU | DC PSU load to AC system (@85% eff) | CLASSIFIED | D | 2483.8 | 2483.8 | N/A | 1987.0 | | | | |
| *Nominal DC voltage design is 25VDC to comply with MIL-STD-1275D's S-S allowable voltage of 25-30 VDC. |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral |
| <--This type of highlighting denotes components that need further investigation as datasheet values appear excessive |
| CONSTANTS | |
| Min Nominal DC Volts: | |
| 25 | |
| Min Nominal AC Volts: | |
| 110 | |
Rack 3 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Design Max Watts | Design Max Amps |
| DC POWER | | | | | | | | | | | |
| Radios | EPLRS (AN/VSQ-2(v)2) with URO | CLASSIFIED | M | 17.4 | 17.4 | 0.8 | 13.9 | 75.0 | 3.0 | 60.0 | 2.4 |
| Radios | CASS | CLASSIFIED | D | 75.0 | 75.0 | 0.8 | 60.0 | | | | |
| NOTE: DC LOADS ARE POWERED BY THE AC SUBSYSYSTEMS IN THIS RACK (POL-PSU) | | | | | | | | | | | |
| AC POWER | | | | | | | | | | | |
| Operator | USB Jackbox - Operator 1 | CLASSIFIED | D | 18.0 | 18.0 | 0.8 | 14.4 | 1914.2 | 17.4 | 1658.2 | 15.1 |
| Operator | USB Jackbox - Operator 2 | CLASSIFIED | D | 18.0 | 18.0 | 0.8 | 14.4 | | | | |
| Operator | TL-354 Display - Operator 1 | CLASSIFIED | D | 90.0 | 90.0 | 0.8 | 72.0 | | | | |
| Operator | TL-354 Display - Operator 2 | CLASSIFIED | D | 90.0 | 90.0 | 0.8 | 72.0 | | | | |
| Operator | Printer | CLASSIFIED | D | 50.0 | 50.0 | 0.8 | 40.0 | | | | |
| Radios | ADSI 3U | CLASSIFIED | O*** | 156.0 | 300.0 | 0.8 | 271.2 | | | | |
| Operator | Getac X500 - NW MGT | CUI | D*** | 48.0 | 65.0 | 0.8 | 61.6 | | | | |
| LAN | Media Converter Chassis | CUI | D | 20.0 | 20.0 | 0.8 | 16.0 | | | | |
| LAN, Sec. | Cisco 4321 ISO Router | CUI | D | 125.0 | 125.0 | 0.8 | 100.0 | | | | |
| LAN, Sec. | Cisco 4351 Router with Switch Module | CUI | D | 430.0 | 430.0 | 0.8 | 430.0 | | | | |
| LAN, Sec. | Cisco Firewall | CUI | M/D | 120.0 | 120.0 | 0.8 | 96.0 | | | | |
| LAN | Alarm Amplifier | CUI | O | 500.0 | 500.0 | 0.8 | 400.0 | | | | |
| DC PSU | DC PSU load to AC system (@85% eff) | CLASSIFIED | D | 88.2 | 88.2 | N/A | 70.6 | | | | |
| *Nominal DC voltage design is 25VDC to comply with MIL-STD-1275D's S-S allowable voltage of 25-30 VDC. | | | | | | | | | | | |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral | | | | | | | | | | | |
| ***Nominal Watts (and current) is calculated by Min+DC*(Max-Min) for devices where min/max are not the same | | | | | | | | | | | |
| | <--This type of highlighting denotes components that need further investigation as datasheet values appear excessive | | | | | | | | | | |
| CONSTANTS | | | | | | | | | | | |
| Min Nominal DC Volts: | | | | | | | | | | | |
| 25 | | | | | | | | | | | |
| Min Nominal AC Volts: | | | | | | | | | | | |
| 110 | | | | | | | | | | | |
Rack 4 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Design Max Watts | Design Max Amps |
| AC POWER | | | | | | | | | | | |
| LAN, Pri. | Cisco Switch 02 | CLASSIFIED | D | 281.0 | 281.0 | 0.8 | 224.8 | 4563.0 | 41.5 | 4006.8 | 36.4 |
| LAN, Pri. | Cisco Switch 01 | CLASSIFIED | D | 281.0 | 281.0 | 0.8 | 224.8 | | | | |
| LAN, Pri. | Cisco Firewall | CLASSIFIED | M | 120.0 | 120.0 | 0.8 | 96.0 | | | | |
| LAN, Pri. | Cisco 4321 ISO Router | CLASSIFIED | D | 125.0 | 125.0 | 0.8 | 100.0 | | | | |
| LAN, Pri. | Cisco 4351 Router with Switch Module | CLASSIFIED | M | 430.0 | 430.0 | 0.8 | 344.0 | | | | |
| LAN | Media Converter Chassis 02 | CLASSIFIED | D | 64.0 | 70.0 | 0.8 | 56.0 | | | | |
| LAN | Cross Domain Solution | CLASSIFIED | O-MFG-EMAIL | 28.0 | 28.0 | 0.8 | 22.4 | | | | |
| Operator | RS-11x Workstation 02 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 459.0 | 0.8 | 406.8 | | | | |
| Operator | RS-11x Workstation 01 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 459.0 | 0.8 | 406.8 | | | | |
| PU, Sec. | RS-112 BS Server 02 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PU, Sec. | RS-112 BS Server 01 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PU, Sec. | RS-112 VM Server 02 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PU, Sec. | RS-112 VM Server 01 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PFPU | RS-112 Stand-in Server 03 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PFPU | RS-112 Stand-in Server 02 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| PFPU | RS-112 Stand-in Server 01 | CLASSIFIED | O-MFG-EMAIL*** | 198.0 | 330.0 | 0.8 | 303.6 | | | | |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral |
| ***Nominal Watts is Min/STBY+DC*(max-min) for devices where min/max are not the same |
| CONSTANTS | Notes: |
| Min Nominal DC Volts: | SM server rack similar to this one pulls 1KVA at idle (~100w/server) |
| 25 | Server Power estimate data from Crystal: |
-CMS-00500 is 330W peak and 198W nominal -CMS-00310/245 (old variants) use 314 peak and 188 nominal -workstations are 459 based on engineering analysis (have not benchmarked actual hardware yet)
| Min Nominal AC Volts: |
| 110 |
System Loads
| AC Watts | | |
| Non-Racked Loads: | | <--these input to rest of the sheets |
| Lighting* | 300 | These don't auto-update |
| GPFU | 510 | |
| ECS | 10800 | |
| Mast Motor | 600 | |
| Total Watts | 12,210.00 | |
| Amps/leg on 208V side for large-non-racked loads | 21.36 | |
| *Lighting is .5A per light @ 120V |
| *Lighting is powered from SP or Rack1 via Automatic Transfer Switch |
Shelter Total
| EQUIPMENT | AC Loading (amps are 'per phase' on the 208 side and UPS eff effect incorporated where applicable) | | | | | | | |
| Max Watts | MaxAmps(A) | MaxAmps(B) | MaxAmps(C) | Nominal Watts | NominalAmps(A) | NominalAmps(B) | NominalAmps(C) |
| Rack 1 | 2,745.8 | 4.8 | 4.8 | 4.8 | 1,549.2 | 2.7 | 2.7 | 2.7 |
| Rack 2 | 2,945.6 | 5.2 | 5.2 | 5.2 | 2,356.5 | 4.1 | 4.1 | 4.1 |
| Rack 3 | 2,252.0 | 3.9 | 3.9 | 3.9 | 1,950.8 | 3.4 | 3.4 | 3.4 |
| Rack 4 | 5,368.2 | 9.4 | 9.4 | 9.4 | 4,713.9 | 8.2 | 8.2 | 8.2 |
| Mast Motor | 600.0 | 1.0 | 1.0 | 1.0 | 600.0 | 1.0 | 1.0 | 1.0 |
| GCU | 510.0 | 0.9 | 0.9 | 0.9 | 510.0 | 0.9 | 0.9 | 0.9 |
| ECU | 10,800.0 | 18.9 | 18.9 | 18.9 | 10,800.0 | 18.9 | 18.9 | 18.9 |
| EST TOTALS (pf@1) | | | | | | | | |
| Racks: | 13,311.7 | 24.3 | 24.3 | 24.3 | 10,570.4 | 18.5 | 18.5 | 18.5 |
| Shelter | 11,910.0 | 20.8 | 20.8 | 20.8 | 11,910.0 | 20.8 | 20.8 | 20.8 |
| ALL: | 25,221.7 | 44.1 | 44.1 | 44.1 | 22,480.4 | 39.3 | 39.3 | 39.3 |
| <-- BIG CHANGE: We can use the 60A shore power cable and still have over 30% margin. --> | | | | | | | | |
| UPS efficiency is assumed to be: | | | 85% | (Does not include current to charge batteries) | | | | |
| The mast motor and ECU compressor/fan are probably 0.8pf or worse, depending on speed/load, but are assumed to be 1 for estimations as they are small compared to heating elemnts and electronic loads | | | | | | | | |
| Old Calculations that are hard to understand, but should still auto-update with new data: | | | | | | | |
| Rack | Load Total DC | | | Load Total AC | Total AC Amps | Total AC Watts | Network Power Analysis |
| | Design Max Watts | DC Supply | | | | | |
| Watts | Design Max Amps | AC/DC Supply | | | | | | |
| Amps | Design Max Watts | Design Max Amps | | Total AC | | | | |
| Watts | Total DC | | | | | | | |
| Watts | Rack Total | | | | | | | |
Watts
| 1 | 1316.82 | 1549.20 | 52.67 | 14.08 | 2014.98 | 18.32 | 32.40 | 3564.17 | 2014.98 | 1316.82 | 3331.79 |
| 2 | 1685.76 | 1983.25 | 67.43 | 18.03 | 2003.01 | 18.21 | 36.24 | 3986.26 | 2003.01 | 1685.76 | 3688.77 |
| 3 | 60.00 | 70.59 | 2.40 | 0.64 | 1658.19 | 2.40 | 3.04 | 334.59 | 1658.19 | 60.00 | 1718.19 |
| 4 | 0.00 | 0.00 | 0.00 | 0.00 | 4006.80 | 36.43 | 36.43 | 4006.80 | 4006.80 | 0.00 | 4006.80 |
| Total | 3062.58 | 3603.03 | 122.50 | 32.75 | 9682.98 | 75.35 | Rack Total | 11891.82 | Rack Total | | 12745.55 |
| | | | | | | W/S Wattage | 346.00 | | | 346.00 |
| | | | | | | Shelter Lighting | 360.00 | | | 360.00 |
| | | | | | | Shelter Total | 12597.82 | | | 13451.55 |
| CONSTANTS | | | | | | | Shelter Total Amps | 114.53 | | | 122.29 |
| Min Nominal DC Volts: | | | | | | | Per Phase | 38.18 | | | 40.76 |
| 25 | | | | | | | | | | | |
| Min Nominal AC Volts: | | | | | | | | | | | |
| 110 | | | | | | | | | | | |
| Min S-S AC L-L Volts | | | | | | | | | | | |
| 190.5 | | | | | | | | | | | |
System Total
| Total AC Watts |
| Shelter | 12597.82 |
| GPFU | 510.00 |
| ECS | 10800.00 |
| Mast Motor | 600.00 |
| System Total Watts | 24507.82 |
| System Total Amps | 85.03 |
2ePFPUrack4 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Design Max Watts | Design Max Amps |
| AC POWER | | | | | | | | | | | |
| LAN, Pri. | Cisco Switch 02 | CLASSIFIED | O | 133.60 | 133.60 | 0.80 | 106.88 | 4800.20 | 43.64 | 4694.56 | 42.68 |
| LAN, Pri. | Cisco Switch 01 | CLASSIFIED | O | 133.60 | 133.60 | 0.80 | 106.88 | | | | |
| LAN, Pri. | Cisco Firewall | CLASSIFIED | M | 120.00 | 120.00 | 0.80 | 96.00 | | | | |
| LAN, Pri. | Cisco 2901 ISO Router | CLASSIFIED | D*** | 40.00 | 50.00 | 0.80 | 48.00 | | | | |
| LAN, Pri. | Cisco 2951 Router with Switch Module | CLASSIFIED | M | 100.00 | 100.00 | 0.80 | 80.00 | | | | |
| LAN | Media Converter Chassis 02 | CLASSIFIED | D*** | 64.00 | 70.00 | 0.80 | 68.80 | | | | |
| LAN | Cross Domain Solution | CLASSIFIED | D | 25.00 | 25.00 | 0.80 | 20.00 | | | | |
| Operator | RS-114 Workstation 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 459.00 | 1.00 | 459.00 | | | | |
| Operator | RS-114 Workstation 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 459.00 | 1.00 | 459.00 | | | | |
| PU, Sec. | RS-112 BS Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 BS Server 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 VM Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 VM Server 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 03 | CLASSIFIED | D | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 01 | CLASSIFIED | D | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | ePFPU#1 | CLASSIFIED | O-MFG-EMAIL | 500.00 | 800.00 | 1.00 | 800.00 | | | | |
| PU, Sec. | ePFPU#2 | CLASSIFIED | O-MFG-EMAIL | 500.00 | 800.00 | 1.00 | 800.00 | | | | |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral |
| ***Nominal Watts is Min/STBY+DC*(max-min) for devices where min/max are not the same |
| CONSTANTS | Notes: |
| Min Nominal DC Volts: | SM server rack similar to this one pulls 1KVA at idle (~100w/server) |
| 25 | Server Power estimate data from Crystal: |
-CMS-00500 is 330W peak and 198W nominal -CMS-00310/245 (old variants) use 314 peak and 188 nominal
| Min Nominal AC Volts: | | | | | |
| 110 | | | | | |
| Old rack without ePFPU was | 4563.00 | watts | 41.48 | amps |
| upper is | 237.2 | watts | 2.16 | amps |
3ePFPUrack4 Equipment Power Data Type M = Measured, D = Datasheet
| O = Other | Min (RX/idle) Watts | Max (TX) Watts | Duty Cycle | Nominal Watts | MAX Load Total | | Nominal Load Total | | | | | |
| Subsystem | Description | Network Class | | | | | | Max Watts (120V Side) | Max Amps (120V side) | Design Max Watts | Design Max Amps |
| AC POWER | | | | | | | | | | | |
| LAN, Pri. | Cisco Switch 02 | CLASSIFIED | O | 133.60 | 133.60 | 0.80 | 106.88 | 5170.20 | 47.00 | 5063.76 | 46.03 |
| LAN, Pri. | Cisco Switch 01 | CLASSIFIED | O | 133.60 | 133.60 | 0.80 | 106.88 | | | | |
| LAN, Pri. | Cisco Firewall | CLASSIFIED | M | 120.00 | 120.00 | 0.80 | 96.00 | | | | |
| LAN, Pri. | Cisco 2901 ISO Router | CLASSIFIED | D | 40.00 | 50.00 | 0.80 | 40.00 | | | | |
| LAN, Pri. | Cisco 2951 Router with Switch Module | CLASSIFIED | M | 100.00 | 100.00 | 0.80 | 80.00 | | | | |
| LAN | Media Converter Chassis 02 | CLASSIFIED | D | 64.00 | 70.00 | 0.80 | 56.00 | | | | |
| LAN | Cross Domain Solution | CLASSIFIED | D | 25.00 | 25.00 | 0.80 | 20.00 | | | | |
| Operator | RS-112 Workstation 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 459.00 | 1.00 | 459.00 | | | | |
| Operator | RS-112 Workstation 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 459.00 | 1.00 | 459.00 | | | | |
| PU, Sec. | RS-112 BS Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 BS Server 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 VM Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PU, Sec. | RS-112 VM Server 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 03 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 02 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | RS-112 Stand-in Server 01 | CLASSIFIED | O-MFG-EMAIL | 198.00 | 330.00 | 1.00 | 330.00 | | | | |
| PFPU | ePFPU#1 | CLASSIFIED | O-MFG-EMAIL | 500.00 | 800.00 | 1.00 | 800.00 | | | | |
| PFPU | ePFPU#2 | CLASSIFIED | O-MFG-EMAIL | 500.00 | 800.00 | 1.00 | 800.00 | | | | |
| PFPU | ePFPU#3 | CLASSIFIED | O-MFG-EMAIL | 500.00 | 800.00 | 1.00 | 800.00 | | | | |
| **Nominal AC voltage design is 110V from MIL-STD-1332B class 2C S-S voltage of 110V-120V phase-neutral | | | | | | | |
| Notes: | | | | | | MAX LOAD |
| SM server rack similar to this one pulls 1KVA at idle (~100w/server) | | | | | UPS#1 | |
| Server Power estimate data from Crystal: | | | | | UPS#2 | |
| -CMS-00500 is 330W peak and 198W nominal | | | | | UPS#3 | |
| -CMS-00310/245 (old variants) use 314 peak and 188 nominal | | | | | | |
| Old rack without ePFPU was | 4563.00 | watts | 41.48 | amps | | |
| upper is | 607.2 | watts | 5.52 | amps | | |
RefWireAmpacity Wire Size (AWG) '975 Derated Current (Amperes) NEC Ampacity Based on Circular Mils @ 20C (100% pure copper) Watts per 10 feet at XX amps (RMS for AC) This is PER CONDUCTOR/RUN
| Single Wire | Bundled Wire or Cable | Up to 3 Wire-Bundle | Ohms/1k-Ft@25C | OHMS/1k-FT@50C | 0.25 | 0.5 | 1 | 1.5 | 2 | 2.5 | 3 | 4 | 5 | 6 | 7 | 9 | 30 | 45 |
| 30 | 1.3 | 0.7 | --- | 105.2 | 115.4 | 0.072 | 0.289 | 1.154 | 2.597 | 4.616 | 7.213 | 10.386 | 18.464 | 28.850 | 41.544 | 56.546 | 93.474 | 1038.600 | 2336.850 |
| 28 | 1.8 | 1 | --- | 66.17 | 72.55 | 0.045 | 0.181 | 0.726 | 1.632 | 2.902 | 4.534 | 6.530 | 11.608 | 18.138 | 26.118 | 35.550 | 58.766 | 652.950 | 1469.138 |
| 26 | 2.5 | 1.4 | --- | 41.62 | 45.63 | 0.029 | 0.114 | 0.456 | 1.027 | 1.825 | 2.852 | 4.107 | 7.301 | 11.408 | 16.427 | 22.359 | 36.960 | 410.670 | 924.008 |
| 24 | 3.3 | 2 | --- | 26.17 | 28.7 | 0.018 | 0.072 | 0.287 | 0.646 | 1.148 | 1.794 | 2.583 | 4.592 | 7.175 | 10.332 | 14.063 | 23.247 | 258.300 | 581.175 |
| 22 | 4.5 | 2.5 | --- | 16.46 | 18.05 | 0.011 | 0.045 | 0.181 | 0.406 | 0.722 | 1.128 | 1.625 | 2.888 | 4.513 | 6.498 | 8.845 | 14.621 | 162.450 | 365.513 |
| 20 | 6.5 | 3.7 | --- | 10.35 | 11.35 | 0.007 | 0.028 | 0.114 | 0.255 | 0.454 | 0.709 | 1.022 | 1.816 | 2.838 | 4.086 | 5.562 | 9.194 | 102.150 | 229.838 |
| 18 | 9.2 | 5 | --- | 6.51 | 7.14 | 0.004 | 0.018 | 0.071 | 0.161 | 0.286 | 0.446 | 0.643 | 1.142 | 1.785 | 2.570 | 3.499 | 5.783 | 64.260 | 144.585 |
| 16 | 13 | 6.5 | --- | 4.094 | 4.489 | 0.003 | 0.011 | 0.045 | 0.101 | 0.180 | 0.281 | 0.404 | 0.718 | 1.122 | 1.616 | 2.200 | 3.636 | 40.401 | 90.902 |
| 14 | 19 | 8.5 | 20 | 2.575 | 2.823 | 0.002 | 0.007 | 0.028 | 0.064 | 0.113 | 0.176 | 0.254 | 0.452 | 0.706 | 1.016 | 1.383 | 2.287 | 25.407 | 57.166 |
| 12 | 25 | 11.5 | 25 | 1.619 | 1.773 | 0.001 | 0.004 | 0.018 | 0.040 | 0.071 | 0.111 | 0.160 | 0.284 | 0.443 | 0.638 | 0.869 | 1.436 | 15.957 | 35.903 |
| 10 | 33 | 16.5 | 30 | 1.018 | 1.117 | 0.001 | 0.003 | 0.011 | 0.025 | 0.045 | 0.070 | 0.101 | 0.179 | 0.279 | 0.402 | 0.547 | 0.905 | 10.053 | 22.619 |
| 8 | 44 | 23 | 40 | 0.6405 | 0.7023 | 0.000 | 0.002 | 0.007 | 0.016 | 0.028 | 0.044 | 0.063 | 0.112 | 0.176 | 0.253 | 0.344 | 0.569 | 6.321 | 14.222 |
| 6 | 60 | 30 | 55 | 0.4028 | 0.4416 | 0.000 | 0.001 | 0.004 | 0.010 | 0.018 | 0.028 | 0.040 | 0.071 | 0.110 | 0.159 | 0.216 | 0.358 | 3.974 | 8.942 |
| 4 | 81 | 40 | 70 | 0.2533 | 0.2778 | 0.000 | 0.001 | 0.003 | 0.006 | 0.011 | 0.017 | 0.025 | 0.044 | 0.069 | 0.100 | 0.136 | 0.225 | 2.500 | 5.625 |
| 2 | 108 | 50 | 95 | 0.1593 | 0.1747 | 0.000 | 0.000 | 0.002 | 0.004 | 0.007 | 0.011 | 0.016 | 0.028 | 0.044 | 0.063 | 0.086 | 0.142 | 1.572 | 3.538 |
| 0 | 147 | 75 | 125 | 0.1002 | 0.1099 | 0.000 | 0.000 | 0.001 | 0.002 | 0.004 | 0.007 | 0.010 | 0.018 | 0.027 | 0.040 | 0.054 | 0.089 | 0.989 | 2.225 |
| 00 | 169 | 87.5 | 145 | 0.079 | 0.08712 | 0.000 | 0.000 | 0.001 | 0.002 | 0.003 | 0.005 | 0.008 | 0.014 | 0.022 | 0.031 | 0.043 | 0.071 | 0.784 | 1.764 |