Attachment 10b.1 – E001 28VDC Pwr Supply Shelter Power-FMECA.xlsx

XLSX spreadsheet 38 KB Posted

Attached to
DRAFT RFP for Integrated Battle Command System (IBCS) LRIP/FRP
Solicitation number
W31P4Q-20-R-0015
Issued by

About this file

This document contains a preliminary analysis for a 28VDC power supply shelter and a draft request for proposal for the Integrated Battle Command System hardware low rate initial production/full rate production segment.

The preliminary analysis evaluates failure modes for the 28VDC power supply shelter's power supply component, identifying no output, improper output, intermittent operation, improper voltage, and short failures. It determines severity classifications and computes failure probabilities with and without redundancy from emergency offsite capabilities.

The draft RFP seeks hardware production for the Integrated Battle Command System, including maintaining approved software/firmware updates, cybersecurity, authority to operate on existing hardware, and engineering changes. The requirement includes producing hardware end items per technical data packages and the critical item development specification. The solicitation number is W31P4Q-20-R-0015 and the issuing agency is the Department of the Army Materiel Command Contracting Command at Redstone Arsenal. It specifies this is a draft for comment and not a current proposal solicitation.

View the file

Other files

File Type Posted
Attachment 10h - SWFMEA RESULTS.xlsx XLSX spreadsheet
Attachment 10a.9 – R015 PDU Assembly-FMECA.xlsx XLSX spreadsheet
Attachment 10b.9 – E033 R112 Shelter – Server Stack – 03-FMECA.xlsx XLSX spreadsheet
Attachment 22a.1.a - ALH-208670 05 IBCS SHELTER INTERCONNECT.pdf PDF
Attachment 22a - CASS to PDRS.docx DOCX document
Attachment 10c.8 – E053 Shelter Time Server-FMECA.xlsx XLSX spreadsheet
Attachment 10a.1 – R001 HRFU-FMECA.xlsx XLSX spreadsheet
Attachment 22a.1.c - ALH-211130 00 CABLE ASSEMBLY CASS DC POWER.pdf PDF
Attachment 20 - Section M - Evaluation Factors For Award.docx DOCX document
Attachment 10a.15 – R033 Media Converter Module 12-FMECA.xlsx XLSX spreadsheet
Attachment 10c.9 – E059 Shelter Switch – 01-FMECA.xlsx XLSX spreadsheet
Attachment 10a.2 – R002 BPU-FMECAAttachment 10b.2 – E002 Power Inverter Shelter Power-FMECA.xlsx XLSX spreadsheet
Attachment 10g - IBCS - 243-003 HW FMECA Results.pdf PDF
Attachment 22a.3 - S280_SystemPowerAnalysis_Draft_12-5-2017.xlsx XLSX spreadsheet
Attachment 10c.12 – E062 Shelter Router-Red-FMECA.xlsx XLSX spreadsheet
Attachment 10c.14 – E064 Shelter Router Black – FMECA.xlsx XLSX spreadsheet
Attachment 10d.2 – E144 RWS Bkup Batteries-FMECA.xlsx XLSX spreadsheet
Attachment 10b.2 – E002 Power Inverter Shelter Power-FMECA.xlsx XLSX spreadsheet
Attachment 10e.9 – E147 – Table 3 Assembly-FMECA.xlsx XLSX spreadsheet
Attachment 10c.5 – E050 KG-250X-FMECA.xlsx XLSX spreadsheet
Attachment 10c.16 – E069 Media Converter 03 - FMECA.xlsx XLSX spreadsheet
Attachment 10e.2 – E082 thru E091 Wkstn Laptop-FMECA.xlsx XLSX spreadsheet
Attachment 10d.4 – E151 – Media Converter 04-FMECA.xlsx XLSX spreadsheet
Attachment 10d.7 – E153 RS112 Server -06 Shelter with PT-FMECA.xlsx XLSX spreadsheet
Attachment 13c - IBCS-A301-003 Vol II Instructor Guide.pdf PDF
Attachment 03 - GFP Attachment - LRIP_FRP - 20 April 2020.xlsx XLSX spreadsheet
Attachment 10a.3 – R003 KG-250X-FMECA.xlsx XLSX spreadsheet
Attachment 22a.2 - PDRS Support information for integration task.pptx PPTX presentation
Attachment 19 - Section L - Instructions - Conditions - And Notices To Offerors.docx DOCX document
Attachment 10c.10 – E060 Shelter Switch – 02-FMECA.xlsx XLSX spreadsheet
Attachment 22a.1.e - ALH-215333 00 S-280 CASS INSTALLATION.PDF PDF
Attachment 04b - Draft_Relay Acceptance Test Procedures.docx DOCX document
Attachment 22a.1.f - EOC Shelter views.pptx PPTX presentation
Attachment 10c.6 – E051 IGRM-FMECA.xlsx XLSX spreadsheet
Attachment 10b.7 – E031 R112 Shelter – Server Stack – 01-FEMCA.xlsx XLSX spreadsheet
Attachment 16 - Example Cage Code and Cognizant DCMA DCAA Information.xlsx XLSX spreadsheet
Attachment 13a -A293-004 ETM 60 Percent Draft.pdf PDF
Attachment 04a - Draft_EOC Acceptance Test Procedures.docx DOCX document
Attachment 10d.6 – E153 RS112 Server -05 Shelter with PT-FMECA.xlsx XLSX spreadsheet
Attachment 10d.8 – E153 RS112 Server -07 Shelter with PT-FMECA.xlsx XLSX spreadsheet
Attachment 10e.1 – E067 – EtherNet Switch-FMECA.xlsx XLSX spreadsheet
Attachment 06 - Obsolete Parts List.pdf PDF
Attachment 04c - ECT_Acceptance Test Procedures_FINAL.DOCX DOCX document
Attachment 15a- Example Skill Classification Crosswalk.xlsx XLSX spreadsheet
Attachment 10c.3 – E048 HRFU-FMECA.xlsx XLSX spreadsheet
Attachment 10a.8 – R008 Media Converter Chassis-FMECA.xlsx XLSX spreadsheet
Attachment 10b.6 – E030 KVM Console-FMECA.xlsx XLSX spreadsheet
Attachment 21 - Task Order 0001 Statement of Work.docx DOCX document
Attachment 10a.13 – R031 Black Router--FMECA.xlsx XLSX spreadsheet
Attachment 22a.1.b - ALH-209032 00 CABLE ASSEMBLY CASS ETHERNET.pdf PDF
Show 40 more

Latest 50 of 98 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet2

Row LabelsSum of CmCount of Failure Mode Description
Improper Output1.03E-052
Improper Voltage1.03E-052
Intermittent Operation2.31E-053
No Output1.04E-035
Short1.08E-042
Grand Total1.19E-0314

Prelim Analysis

PRELIMINARY ANALYSIS:Major End Item:Shelter -Power
Parent LRU:E001 - 28 VDC Power Supply # 1
Component:28 VDC Power Supply
Mission Phase-Operational Mode:All Phases
Cr = ∑Cm =1.19E-03
Failure ModesCount of
Failure ModesSeverity
ClassificationsCount of

Seveverity Classification Failure Modes Sum of Cm Count of Failure Modes

No Output535.71%Category I5Improper Output1.03E-052
Intermittent Operation321.43%No Output4Improper Voltage1.03E-052
Improper Output214.29%Short1Intermittent Operation2.31E-053
Improper Voltage214.29%Category III9No Output1.04E-035
Short214.29%Improper Output2Short1.08E-042
Grand Total14Improper Voltage2Grand Total1.19E-0314
Intermittent Operation3
No Output1
Short1
Grand Total14

Cat I and II

Major End Item:Shelter -Power
Parent LRU:E001 - 28 VDC Power Supply # 1
Component:28 VDC Power Supply
Mission Phase-Operational Mode:All Phases
FPMH:1.916
t:72
Cr = ∑Cm =2.29E-04
Modified Cr =2.27E-05(Redundancy)
Due to the EOC Redundancy the Severity Classifications can be reduced Severity Classification III-1R
Failure Effect atFailure Detection MethodCompemsating Provisions
ID#FunctionFailure Mode DescriptionFailure CauseLocal Failure EffectsNext Higher Level Failure EffectsMajor End Item Failure EffectsSafety
ConsiderationSafety
ImpactOperator ObservationVisual IndicatorC-Bit
CapabilitiesSeverity
ClassificationAlternate Design
ModificationsModified Severity
ClassificationββmodαλPCmMod Cm
1AC Input for AC/DC Power supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.92E-064.93E-052.46E-06
2Provides 28VDC RTN for the AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power Supply ReturnLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.92E-064.93E-052.46E-06
3DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.92E-064.93E-052.46E-06
7DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterShortHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.14291.92E-061.97E-059.85E-07
8DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AOB-001-01N/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.92E-064.93E-052.46E-06

E001 Data

Major End Item:Shelter -Power
Parent LRU:E001 - 28 VDC Power Supply # 1
Component:28 VDC Power Supply
Mission Phase-Operational Mode:All Phases
FPMH:10.000
t:72
Cr = ∑Cm =1.19E-03
Modified Cr =1.18E-04(Redundancy)
Due to the EOC Redundancy the Severity Classifications can be reduced Severity Classification III-1R
Failure Effect atFailure Detection MethodCompemsating Provisions
ID#FunctionFailure Mode DescriptionFailure CauseLocal Failure EffectsNext Higher Level Failure EffectsMajor End Item Failure EffectsSafety
ConsiderationSafety
ImpactOperator ObservationVisual IndicatorC-Bit
CapabilitiesSeverity
ClassificationAlternate Design
ModificationsModified Severity
ClassificationββmodαλPCmMod Cm
1AC Input for AC/DC Power supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.00E-052.57E-041.29E-05
2Provides 28VDC RTN for the AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power Supply ReturnLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.00E-052.57E-041.29E-05
3DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.00E-052.57E-041.29E-05
4DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterImproper OutputHardware FailurePossible loss of Shelter DC Power SupplyPossible loss of DC Input Power to ShelterPossible loss of ShelterN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.14291.00E-055.14E-065.14E-06
5DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterImproper VoltageHardware FailurePossible loss of Shelter DC Power SupplyPossible loss of Shelter DC Power SupplyPossible loss of Shelter DC Power SupplyN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.14291.00E-055.14E-065.14E-06
6DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterIntermittent OperationHardware FailurePossible loss of Shelter DC Power SupplyPossible loss of Shelter DC Power SupplyPossible loss of Shelter DC Power SupplyN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.21431.00E-057.71E-067.71E-06
7DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterShortHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AN/AN/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.14291.00E-051.03E-045.14E-06
8DC output of AC/DC Power Supply which supplies 28VDC/200A service to the ShelterNo OutputHardware FailureLoss of Shelter DC Power SupplyLoss of DC Input Power to ShelterLoss of ShelterN/AN/AOB-001-01N/ATBDCategory IEOCs are RedundantCategory III-1R1.000.050.35711.00E-052.57E-041.29E-05
9DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.No OutputHardware FailureLoss of AC/DC StatusLoss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.35711.00E-051.29E-051.29E-05
10DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.Improper OutputHardware FailurePossible Loss of AC/DC StatusPossible Loss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.14291.00E-055.14E-065.14E-06
11DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.Improper VoltageHardware FailureProbable Loss of AC/DC StatusProbable Loss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.14291.00E-055.14E-065.14E-06
12DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.Intermittent OperationHardware FailureProbable Loss of AC/DC StatusProbable Loss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.21431.00E-057.71E-067.71E-06
13DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.ShortHardware FailureLoss of AC/DC StatusLoss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.14291.00E-055.14E-065.14E-06
14DC output of AC/DC Power Supply which supplies 28VDC for Status Lines.Intermittent OperationHardware FailureLoss of AC/DC StatusLoss of AC/DC StatusPossible delay in starting a missionN/AN/AN/AN/ATBDCategory IIIEOCs are RedundantCategory III0.050.050.21431.00E-057.71E-067.71E-06

File details come from the government source that posted it. Updated .